10th September 2012, version 1.1
Xiria EIEC Medium Voltage Switchgear up to 24 kV
Extendable, metal-enclosed Single Busbar Solid- & Air-insulated
2 2
MV Switchgear Technology is in our DNA
Leader in design, manufacture and sales of MV equipment in accordance with IEC standards
5 5
Basic Design
1. Low voltage compartment
2. Protection relay
3. Control panel
4. Mimic diagram
5. Voltage detection system
6. Inspection window
7. Mechanism
8. Cable cones
9. Cable clamps
10. Earth bar
11. Busbar
12. Change-over switch
13. Vacuum interrupter
14. Current transformers
15. Voltage transformers
16. Coil and resistor
6 6
Main Components (1)Vacuum circuit-breaker
Features
• Environmental friendly vacuum interrupters
• Simple spring charging mechanism
• No use of lubricants
• Housed in a sealed for live enclosure
• Position indication by means of inspection windows and mechanical indicators
• Auxiliary contacts for Open/Close position
2-position change-over switch
Features
• Manual-operated switch with 2 positions (service / earthed)
• Maintenance free
• Housed in a sealed for live enclosure
• Auxiliary contacts for Service / Earthed position
• Mechanically Interlocked with the circuit-breaker
7 7
Main Components (2)
Busbars
Features
• Single phase insulated
• Air insulated
• Housed in a sealed for life enclosure
• Simple and robust construction
• Easy to couple
8 8
Eaton Core Technologies (1)
Solid insulation
Features
• Environmental friendly isolation
• Robust construction
• Cooling purpose
Electrical field control
Features
• Reliable construction
• Air insulated compartment
• Compact panels
9 9
Eaton Core Technologies (2)
Vacuum technology
Features
• Safe, compact & reliable construction
• None affected contacts
• Environmental friendly switching medium
• 30.000 operations
10 10
Reliable and Safe in Operation (1)
Preventing an Internal Arc• Use of electrical field control
• Protected voltage transformers
• Single pole insulated parts
• Sealed for life fully enclosed housing
Sealed for life fully enclosed housing• protects primary parts against environmental
influences
• Provides a maintenance free mechanism
• Internal arc proof
11 11
Reliable and Safe in Operation (2)
Controlling an Internal Arc• No phase-to-phase short circuit minimizes pressure
• Integrated compartments reduce pressure
• Integrated arc absorber reduces output impact
Arc absorber• Ceramic block
• Breaks and filters the fire and gasses significantly
• 9 m2 absorbing surface
12 12
• Compartments protected against penetration by objects
• Capacitive voltage detection system for verification of safe isolation form supply
• Operation only possible with closed compartment
• Logical mechanical and electrical interlocks prevent incorrect operation
• Smooth contemporary design
• Visible isolation by means of inspection windows in the front
Safe in Use (1)
13 13
Safe in Use (2)
What you see is what you get!• Visible isolation by means of inspection windows in the front
14 14
Low Total Cost of Ownership
Low initial cost• Panels width only 500 mm
• Cable connection form from the front
• Integrated arc channel with absorber
• 12 and 24 kV panels in the same housing
Low service cost during operation• Robust “lean” design with minimum number of parts
• Product quality guaranteed by routine testing in the factory
• Primary parts and mechanism installed in a fully sealed for life enclosed housing
• Maintenance free vacuum circuit-breaker
• No SF6 pressure checks
Low end of life disposal cost• Fully recycling or re-use of materials
15 15
User friendly
Easy and ergonomic connection of cables• Primary cable 700 mm from front level
• Secondary cables entering from the top
• All cables to be connected from the front
Clear and simple control panels• Control panels with uniform intuitive mimic diagram
• Positioned on good height
• Set-up based on customer request
16 16
Environmental friendly
Environmental friendly design• Use of minimized number of components
• Materials with no/less impact on the environment
• No use of SF6 gas for insulation or switching
Efficient use of material• Low production waste material
• Use of modern machines
No service checks on site• Maintenance free switchgear
• Environmental friendly insulation and switching medium
Re-use or recycle of materials• Use of environmental friendly materials
• Cooperation with specialized partners
17 17
Exactly how you want it (1)
Simple configuration, coupling and extension• Different panel types in any sequence
• Quick and easy coupling at site possible
• Possibility to extend in the future
18 18
Exactly how you want it (2)
Flexible application of secondary apparatus, protection relays and substation automation• Voltage transformers
• Current transformers
• Protection relays
• Ready for Smart Grids application(remote communication / automated systems)
19 19
Xiria integrated metering solutions
Control- and tariff metering in medium voltage distribution• Application of your current- and voltage transformers• Easy disassembly and assembly for local calibration• Sealed secondary connections possible• Safe arc-resistant enclosure• Easy connection with insulated busbars• Easy to install (compact) and extend• According to the DIN 42600 standards.
20 20
Technical data - metering solutions• Degree of protection primary part IP31D• Degree of protection secondary part IP3XD
Standards• System IEC 62271-200• Current transformers IEC 60044-1• Voltage transformers IEC 60044-2• Dimensions current- and voltage transformers DIN 42600 T.8/T.9 - Small
Dimensions 12 & 24 kV IEC• Panel width 850 mm• Panel height 1325 mm• Panel depth 755 mm
26 26
Technical dataRated voltagePower frequency withstand voltageImpulse withstand voltageRated current busbars Short-time current * optional 3 s
Rated normal current (max.) circuit-breaker paneltransformer panelload-break switch panelbusbar sectionaliser paneldirect busbar panelmetering panel
Degree of protectionClassification according to IEC 62271-200:Loss of service continuityPartition classInternal arc
12 kV28 kV75 / 95 kV630 A20 kA-1s*
630 A200 A630 A630 A630 A630 AIP 31D
LSC 2BPMIAC AFL
24 kV50 kV125 kV630 A20 kA-1s*
630 A200 A630 A630 A630 A630 AIP 31D
LSC 2BPMIAC AFL
27 27
Standards
Xiria E complies with the following international standards:
IEC 62271-1 Common specificationsIEC 62271-100 Circuit-breakers (E2, M2, C2)IEC 62271-102 Disconnectors and earthing switches (E2, M0)IEC 62271-103 High-voltage switchesIEC 62271-200 Metal enclosed switchgear and controlgearIEC 62271-304 Severe climatic conditionsIEC 60044-1 Current transformersIEC 60044-2 Voltage transformersIEC 60529 Degrees of protection (IP Code)IEC 61850 Communication networks and systems in substationsIEC 61243-5 Live working - Voltage detectors –
Part 5: Voltage detecting systems
28 28
Applications
• Utilities (subdistribution stations)• Commercial and governmental buildings• Infrastructure projects• Industry
29 29
Applications
• Utilities (main- and subdistribution stations)• Commercial and governmental buildings• Infrastructure projects• Industry
30 30
Applications
• Utilities (main- and subdistribution stations)• Commercial and governmental buildings• Infrastructure projects• Industry
31 31
Applications
• Utilities (main- and subdistribution stations)• Commercial and governmental buildings• Infrastructure projects• Industry
32 32
Reference list Xiria family
The Netherlands Gemaal Gorzeman Hellevoetsluis ● Philips Roozendaal ● Essent ● Tetra Pak Moerdijk ● Solvay Olst ●Stork Heijmans ● Quercus Zoetermeer ● UMC Utrecht ● Imtech ● NRE Eindhoven ● Van Alfen Almere ● Prominent ●Airport Schiphol ● Frico Cheese Bedum ● AMC Health Care ● SuikerUnie ● Deltion College Zwolle ● BAM Techniek ●Tuinderij vd Berg ● Vandenberg Roses ● Stolze/Arthura ● Marjoland ● Westland ● Coca Cola Dongen ● Eneco ●Westmere ● Kester Invest ● NUON Amsterdam RAI ● Van Gelder Airbase Leeuwarden ● Rendo Denmark Kommunekemi Fyn Industri ● BOE Jutland ● Nyborg ● GEAS A/S Grindsted ● Energy Fyn Odense ● Saeby Kommunale Elforsyning Germany Eimers GmbH ● Streif Baulogistik ● Emscher Lippe Energie ● Vattenfall HEW United KingdomNCE Radcliffe Hospital ● Rolls Royce Derby ● Royal Hospital London Ireland E&I Engineering Prisons ● TEC Dublin ●Belfast City Hospital Sweden Fortum Service ● Tranäs Energi ● Graniger Kalmar Energi ● Nätstations Alliansen ● Midroc Elektro ● Eldistributions-service i Väst ● Vattenvall Service ● Nacka energi ● Holtab AB ● Bjäre Kraft AB ● Skaraborgs Elektriska ● Karlstadt Elnät AB ● Skövde Elnat ● Elektroproduktion AB IKEA ● Linjemontage Grästorp ● Elajo Reftele Rullpack ● Selga AB Norrahammar ● Höganäs Energi AB ● Ratel Entrepenad AB ● Stockholms Läns Elektriska ●Hideskins Energi Australia City Power Melbourne ● Snowy Hydro ● ETSA Adelaide ● Capral Aluminium Japan NKE Wind Power South Korea Samki Kenya Burhani Norway Troms Kraft Tromse ● Repvag Kraftlag Havoysund ● More Trafo AS Sykkylven Finland Vällnönkatu ● Je-Urakointi OY Switserland Huser & Peyer AG Austria Stadtwerke Schwaz ● Salzburg AG ● EVN AG ● OMV Estonia Tehenergo Tallin Poland Zdzislaw Stachowiak Ostrow Czech Republic SG Brno ●Spectrum Vyskov Ikea Brno ● Zapustkova kovarna China Power Supply Board Shanghai ● Power Supply ShenyangColombia Disico Iceand Karahnjuka Tunnel Belgium STIB Brussel Metro India C&S Reliance Mumbai Hungary ELMU ●Uvill Kft ● MaxCity, Budaörs Italy WE Walter srl
34 34
SummarySafe in Use• Inspection windows
• Protected compartments
• Logical interlocks
• Operation outside HV compartments
Reliable and Safe in Operation• IEC certified
• Quality assurance DIN EN9001
• Routine tested
• Single pole insulation
• Ferro resonance protected VT’s
• Integrated arc absorbers
Environmental Friendly• Minimized number of components
• Environmental friendly materials used
• No use of SF6 -gas
• Energy efficient production
• Minimal number of transition points
• Re-use or recyclable materials
User Friendly• Cable connection 700 mm height
• Easy secondary cable connection
• Clear and simple operation panels
Low Total Cost of Ownership• Low initial cost
• Low cost during service
• Low end of life disposal cost
36 36
Eaton IEC MV Systems
A complete range of compact SF6 free solutions
SVS Power Xpert®UX
MMSMagnefix Xiria
Safe – Reliable – Sustainable
Power Xpert®FMX
Xiria E