47
 Smart Water for Smart Cities Arc Flash Mitigation Enhancing Personnel Safety Terry L. Schiazza Low Voltage Offer Marketing Seneca (SC) Plant Sponsored by the Water Wastewater Competency Center  Atlanta, GA May 2014

WWCC Arc Flash Mitigation Atlanta

Embed Size (px)

DESCRIPTION

Arc Flash Mitigation

Citation preview

  • Smart Water for

    Smart Cities

    Arc Flash Mitigation

    Enhancing Personnel Safety

    Terry L. Schiazza

    Low Voltage Offer Marketing

    Seneca (SC) Plant

    Sponsored by the Water Wastewater Competency Center

    Atlanta, GA May 2014

  • 2

    Graduated (1980) Georgia Institute of Technology Bachelor of Mechanical Engineering

    Graduated (1991) Clemson University

    Master of Human Resource Development

    Began career at Square D in 1980 and serve as Business Development Manager for Partner Business Unit

    Member of IEEE/IAS and AIST - IEEE/PCIC Chemical Subcommittee

    - AIST Energy Applications Technology Committee

    Standards Working Group member of - IEEE 1683

    - IEEE C37.20.7

    Terry L. Schiazza

    Co-authored published IEEE paper (Paper No. PCIC-2008-31) presented at the 2008

    Petroleum and Chemical Industry Committee

    (PCIC) conference in Cincinnati.

    ELECTRONIC MOTOR CIRCUIT PROTECTORS

    A fresh perspective on sizing circuit protection for

    branch motor circuits in a low voltage motor

    control center

    Co-authored published AISTech 2012 Proceedings (Paper 25222113) presented at the 2012 Association

    for Iron & Steel Technology Conference in Atlanta.

    New Approach for Intelligent Motor Control Centers

    *Recipient of the 2013 AIST Farrington Award received

    at the Pittsburgh Technology Conference

  • Arc Flash Principles and Theory

  • Arc Flash Characteristics Arc Blast & Arc Flash occur

    together. The term Arc Flash

    often refers to both

    phenomena. From here on,

    the term Arc Flash will be

    used for both terms.

    Thermal

    Effects

    Pressure

    Effects

  • Why is Arc-Flash Analysis Important?

    Need to provide optimal safety for electrical workers

    Increasing awareness of arc-flash hazards

    Calculation of Arc-Flash Incident Energy (AFIE) allows selection of adequate Personal Protective Equipment (PPE) if equipment must be worked while energized

    Working on or near exposed live parts: NFPA 70E requires an arc-flash hazard analysis if equipment >50V is not placed in an electrically safe working condition

    OSHA is enforcing NFPA 70E!

    NEC 2014 Impact Changes (Section 240.87)

  • NFPA 70E PPE Table Table 130.7(C)(11) Protective Clothing Characteristics

    Typical Protective Clothing Systems

    Hazard/Risk

    Category

    Clothing Description

    (Typical number of clothing layers is given in parentheses)

    Required Minimum

    Arc Rating of PPE

    [J/cm2(cal/cm2)]

    0 Non-melting, flammable materials (i.e., untreated cotton, wool, rayon, or silk, or

    blends of these materials) with a fabric weight at least 4.5 oz/yd2 (1)

    N/A

    1 FR shirt and FR pants or FR coverall (1) 16.74 (4)

    2 Cotton underwear conventional short sleeve and brief/shorts, plus FR shirt and

    FR pants (1 or 2)

    33.47 (8)

    3 Cotton underwear plus FR shirt and FR pants plus FR coverall, or cotton underwear

    plus two FR coveralls (2 or 3)

    104.6 (25)

    4 Cotton underwear plus FR shirt and FR pants plus multilayer flash suit (3 or more) 167.36 (40)

    Note: Arc rating is defined in Article 100 and can be either ATPV or EBT. ATPV is defined in ASTM F 1959-99

    as the incident energy on a fabric or material that results in sufficient heat transfer through the fabric or

    material to cause the onset of a second-degree burn based on the Stoll curve. EBT is defined in ASTM F

    1959-99 as the average of the five highest incident energy exposure values below the Stoll curve where the

    specimens do not exhibit breakopen. EBT is reported when ATPV cannot be measured due to FR fabric

    breakopen. (APTV = Arc Thermal Protective Value)

  • AF Testing & Models

    To date, there are no practical theoretical models that match tested arc flash results

    Instead, state-of-the-art techniques use empirical models based upon test results

    IEEE 1584-2002 gives an empirical model that, if properly applied, gives 95% confidence that calculated PPE will be adequate or more-than-adequate for hazards associated with heat energy from an arc

    Other effects, such as pressure-wave effects and the effects of the expulsion of molten metal, are not taken into account in the IEEE-1584 model.

  • IEEE 1584 Model

    Ia is the arcing current (kA), defined by IEEE-1584 as:

    K = -0.153 for open configurations, = -0.097 for box configurations Ibf: Bolted fault current for three-phase faults (symm. RMS) (kA) V: System voltage (kV) G: gap between conductors, (mm) Represents current that would flow through the arc during

    an arcing fault typically 50% - 60% of bolted fault current for 480V system

    bfIlogG00304.0bfIlogV5588.0G000526.0V0966.0bfIlog662.0K10aI

  • En is the normalized incident energy

    K1 = -0.792 for open configurations, = -0.555 for box configurations K2 = 0 for ungrounded or HRG systems, = -0.113 for grounded systems Ia is the arcing current (kA) (Calculated) G is gap between conductors, (mm) (Measured) Represents arc-flash incident energy normalized to a

    working distance of 610mm and 0.2s arcing time

    G0011.0Ilog081.1KKn

    a2110E

    IEEE 1584 Model

  • E is the calculated incident energy

    Cf = 1.5 for voltages 1kV, = 1.0 for voltages > 1kV t: Arcing time in seconds D: Working distance (mm) x: Distance exponent (tabulated in IEEE 1584) Note that once E is calculated, the process should be repeated but for Ia =

    85% of the calculated value. The larger of the two values for E is the calculated arc-flash incident energy.

    (cal/cm2)

    x

    x

    nfD

    tECE

    610

    2.0

    IEEE 1584 Model

  • What System Parameters Can be

    Changed to Reduce AFIE? From IEEE 1584 model:

    System Voltage Bolted fault current Gap between conductors Arcing time

    System voltage: Generally not practical to change

    Gap between conductors: Would require different equipment construction, not practical to change

    That leaves bolted fault current and arcing time.

  • Effect of Changing Bolted Fault Current

    on AFIE Lower bolted fault current leads to

    lower arcing current

    Arcing current determines arcing time!

    Overcurrent protective devices, which define the arcing time, may take longer to trip with lower arcing current due to inverse time-current characteristics

    Higher arcing current: 0.06s arcing time

    Lower arcing current: 1s arcing time

  • Arc Flash Mitigation Methods

  • Enhancing Personnel Safety

    Number of arc flash explosions that occur in

    electrical equipment every day in the United States - According to statistics compiled by Cap-Schell, Inc.,

    a Chicago-based research and consulting firm that

    specializes in preventing workplace injuries and deaths

    5-10

    Each year the number of patients that are

    emitted to burn centers due to arc flash events - Report by research on IEEE Website

    2000

  • Electrical Safety

    Electrical Safety Then and Now http://esfi.org/index.cfm/page/Electrical-Safety-Then-and-Now/cdid/12394/pid/10272

    Workplace Electrical Injury and Fatality Statistics http://esfi.org/index.cfm/page/Workplace-Electrical-Injury-and-Fatality-Statistics,-2003-

    2010/cdid/12396/pid/3003

    http://esfi.org/index.cfm/pid/11506

  • Arc Flash Mitigation Solutions

    Prevention / Avoidance

    Passive Containment

    Energy Redirection

    Installation Considerations

    Plenums (ductwork)

    Size of Equipment

    Equipment location

    Passive Protection

    Virtual Mains

    Zone Selective Interlocking

    Bus Differential Relays

    Low Arc Flash CB

    High Resistance Grounding

    Arc Flash Sensing Relay-

    VAMPTM technology

    Active Protection

    LV Arc Flash Sensing Relay

    with Arc Quenching technology

    MV Arc TerminatorTM

    Interactive Protection

    Energy-Reducing

    Maintenance Switches

    System Design

    De-energize Equipment

    Site Safety Procedures

    Intelligent MCCs

    AF Mitigating Features (Equipment Design)

    Electric Operated CBs

    AF

  • 19

    Zone Selective Interlocking

    Bolted Fault Current 62kA Arc Fault Current 29kA Incident Energy 24 3.33 cal/cm2

    PPE Category 1

    Bolted Fault Current 62kA Arc Fault Current 29kA Incident Energy 24 3.33 cal/cm2

    PPE Category 1

    .1sec

    10kA 100kA

    1sec

    10sec

    100sec

    1kA

    M1 3000A

    tSD .3 Sec

    F1 800A

    F2 800A

    F3 800A

    F4 800A

    No restraint signal

    Short time delay will be

    ignored

    Incident Energy 24 20 cal/cm2

    PPE Category 3

    Bolted Fault Current 62kA Arc Fault Current 29kA

    Coordinated System

  • Arc flash detection relay (1-2 msec) (light sensors/current-optional) Tripping of upstream breaker Fault location identification Multiple zones protection (optional)

    MAIN CB

    CB F1 CB F2 CB F3

    Transformer

    Primary fuse

    LV Switchgear

    x Fault

    AF

    Relay

    Zone 1

    Z2 Z3 Z4 Optional

    Arc Flash Relay Systems

  • Typical System Design

  • Virtual Main

  • Arc Terminator System Operation Sense a Fault Current + Detect an Arc = Close Shorting Switch

  • MasterClad Arc Resistant Ratings

    Nominal Voltage 4.16 kV 7.2 kV 13.8 kV

    Maximum Voltage 4.76 kV 8.25 kV 15.0 kV

    BIL (kV) 60 95 95

    Continuous

    Current (A)

    1200, 2000,

    3000(*)

    1200, 2000,

    3000(*)

    1200, 2000,

    3000(*)

    Interrupting

    Current (kA)

    40, 50 40 25, 40, 50

    Internal Arc

    Current (kA)

    Up to 63, 0.5 sec Up to 63, 0.5 sec Up to 63, 0.5 sec

    Enclosure Types Nema 1 Nema 1 Nema 1

    (*) Only for 1 High

  • Pressure Relief Flaps

    Arc Plenum - Optional

    Medium Voltage MCC

    Compartmentalized

    Construction

    Bolted Rear Panels

    Top View

    Rear View

    Interlocked rear panel to Frame Construction

    Top and Bottom Access Panels

    Easy Removal

    Enclosure AR Type 2

  • ANSI C37.20.1 Power-Zone 4 Drawout Switchgear ANSI C37.20.7, Annex D Arc Resistant (ANSI C37.20.1 Power-Zone 4 Drawout Switchgear)

    North America

    Low Voltage Arc Resistant Offer

  • Schneider Electric SpecTech 2012, November Update 28

    IIEEE C37.20.7-2007

    IEEE guide for testing metal-enclosed switchgear rated up

    to 38 kV for internal arcing

    faults

    A procedure for testing and evaluating the performance of

    metal-enclosed switchgear for

    internal arcing faults is

    covered. A method of

    identifying the capabilities of

    this equipment is given.

    Service conditions,

    installation, and application of

    equipment are also discussed.

  • Without ArcBlokTM

    (1 shot) at 65 kAIR @ 480 Vac

    AR LV Equipment- Design Values

  • With ArcBlokTM

    (1 shot) at 65 kAIR @ 480 Vac

    AR LV Equipment- Design Values

  • Schneider Electric SpecTech 2012, November Update 31

    Testing Standard

    Reinforced, Compartmentalized Enclosure

    Ratings Bus and Breaker kAIR Accessibility Type (2A/2B)

    Optional Features Insulated Bus Plenums Zone Selection Interlocking High Resistant Grounding Energy Reduction

    Maintenance Switch

    Breaker Remote Racking

    Arc Resistant Considerations

  • Air Intake Design

    Optimized Air Flow

    Dynamic Spring Loaded Pressure Flap

  • Plenums

  • Plenums for PZ-4

  • What is the Standard for Low Voltage

    Motor Control Centers?

  • Low Voltage Motor Control Center A Standard Dilemma.Resolved

    IEEE PC37.20.7, Draft 6 May 2014, Annex H

    Purpose of the Annex is to provide specific information

    for test sample configuration,

    testing methods, test assessment,

    and additional ratings that are

    specific to LV MCCs (UL845)

    There currently is no standard or guide for testing Low Voltage Motor Control Centers for

    internal arcing faults however based on

    recent decisions within IEEE, AR MCCs will

    now be covered in Annex H of the IEEE

    C37.20.7 standard.

    The most important test parameters for determining equipment capability

    is establishing -

    The preferred rated arcing duration test (H.3)

    The means of establish an arc to produce enough ionized gas quickly

    enough to prevent premature

    extinction at lower voltages (H.4)

    Current discussions within the working group indicate that the minimum arcing duration test

    will be no less than 100 ms

  • Pull Box

    Plenum

    Exhaust Options

    Baffle

    Plenum UL Witnessed

    Plenum Design

    Top Entry thru Pull Box

    Single Plenum

    Pull Box

    28.5 in

    10 ft.

    Minimum height from bottom of

    section to obstruction above MCC

    14.24 in.

    Rear Front

    Ceiling or obstruction above MCC

  • Thank You

  • Appendix

  • MasterClad Arc Resistant 2-High

    Circuit breaker

    compartment

    Relay & instrument door

    Cable

    compartment

    Main Bus

    compartment

  • MasterClad Arc Resistant with Plenum

    Plenum Required if: Ceiling* less than

    192 Power Zone Center

    Application Exhaust needed from

    equipment room 50kA or 63kA rating

    (optional use-arc shield)

    *As measured from the floor

  • MasterClad Arc Resistant

    Arc Shield

    Arc Shield Required if: 50kA or 63kA

    rating (optional use-plenum)

    Increase likelihood of protection for front, rear, & sides of equipment

  • ArcBlok Patented Technology Internal Arc Gas Management System

    Prevents and

    Controls Arcing Cluster Shields

    Cradle Barriers

    Arc Ventilation

  • Exhaust Methods - Baffles

    Roof Baffles

    14 Guage Steel

    Exhaust Flap

    Louvered

    10 ft. Clearence

    Ceiling

    Base of

    Equipment

  • Internal Arc Gas Management

    Shroud Power

    Stabs Vertical Bus

    Isolation

    Ventilated

    Mid-Shelf

  • Model 6 Arc Resistant Highlights

    Testing Standard C37.20.7, Annex H

    UL Witnessed

    Reinforced Enclosure 12 gauge steel Additional hardware Metal Control Station Plate Filter box (VFD) Baffle compartment assembly

    Ratings 65 kAIR @ 600 Vac Type 2A 100 ms (Stage 1) 500 ms (Stage 2) 2000A Bus (Stage 1) 2500A Bus (Stage 2)

    Additional top

    mid bracket

    Reinforced door

    with hinges

    Additional bottom

    mid bracket

    Clip on Fast

    Lead Screws

    Metal Control

    Station Plate

    Filter Box for

    Thermal Ventilation

  • 47

    References

    Arc Flash Mitigation

    AT327/July 2013

    SE Engineering Services

    1910BR1205

    Arc Flash Description of Services

    SAFARC01R02/12

    Industry-Leading Expertise We currently have more than 130 power

    system engineers. SE Engineering

    Services has completed over 10,000

    power system assessments, studies,

    and designs including IBM.

  • Arc Flash Analysis

    An arc flash analysis is performed to estimate incident energy levels, to identify

    appropriate levels of Personal Protective Equipment (PPE) and to determine flash

    protection boundaries at specific points in an electrical distribution system.

    The Occupational Safety and Health Administration requires employers to protect

    facility workers and contractors from the hazards associated with electrical shock,

    arc, and blast. The National Fire Protection Agency, producers of the National

    Electrical Code, developed a set of guidelines to assist employers in complying with

    OSHA laws in the NFPA 70E, Standard for Electrical Safety in the Workplace.

    We offer arc flash analyses based on the results from the Short-circuit and

    Overcurrent Device Coordination studies, and are calculated using the

    equations provided in IEEE Std. 1584-2002.

  • Arc Flash Mitigation

    Enhancing Personnel Safety

    April 23, 2014

    Terry L. Schiazza

    Business Development Mgr.

    Seneca, SC Manufacturing Facility