Upload
akppk1384
View
9
Download
0
Embed Size (px)
DESCRIPTION
Arc Flash Mitigation
Citation preview
Smart Water for
Smart Cities
Arc Flash Mitigation
Enhancing Personnel Safety
Terry L. Schiazza
Low Voltage Offer Marketing
Seneca (SC) Plant
Sponsored by the Water Wastewater Competency Center
Atlanta, GA May 2014
2
Graduated (1980) Georgia Institute of Technology Bachelor of Mechanical Engineering
Graduated (1991) Clemson University
Master of Human Resource Development
Began career at Square D in 1980 and serve as Business Development Manager for Partner Business Unit
Member of IEEE/IAS and AIST - IEEE/PCIC Chemical Subcommittee
- AIST Energy Applications Technology Committee
Standards Working Group member of - IEEE 1683
- IEEE C37.20.7
Terry L. Schiazza
Co-authored published IEEE paper (Paper No. PCIC-2008-31) presented at the 2008
Petroleum and Chemical Industry Committee
(PCIC) conference in Cincinnati.
ELECTRONIC MOTOR CIRCUIT PROTECTORS
A fresh perspective on sizing circuit protection for
branch motor circuits in a low voltage motor
control center
Co-authored published AISTech 2012 Proceedings (Paper 25222113) presented at the 2012 Association
for Iron & Steel Technology Conference in Atlanta.
New Approach for Intelligent Motor Control Centers
*Recipient of the 2013 AIST Farrington Award received
at the Pittsburgh Technology Conference
Arc Flash Principles and Theory
Arc Flash Characteristics Arc Blast & Arc Flash occur
together. The term Arc Flash
often refers to both
phenomena. From here on,
the term Arc Flash will be
used for both terms.
Thermal
Effects
Pressure
Effects
Why is Arc-Flash Analysis Important?
Need to provide optimal safety for electrical workers
Increasing awareness of arc-flash hazards
Calculation of Arc-Flash Incident Energy (AFIE) allows selection of adequate Personal Protective Equipment (PPE) if equipment must be worked while energized
Working on or near exposed live parts: NFPA 70E requires an arc-flash hazard analysis if equipment >50V is not placed in an electrically safe working condition
OSHA is enforcing NFPA 70E!
NEC 2014 Impact Changes (Section 240.87)
NFPA 70E PPE Table Table 130.7(C)(11) Protective Clothing Characteristics
Typical Protective Clothing Systems
Hazard/Risk
Category
Clothing Description
(Typical number of clothing layers is given in parentheses)
Required Minimum
Arc Rating of PPE
[J/cm2(cal/cm2)]
0 Non-melting, flammable materials (i.e., untreated cotton, wool, rayon, or silk, or
blends of these materials) with a fabric weight at least 4.5 oz/yd2 (1)
N/A
1 FR shirt and FR pants or FR coverall (1) 16.74 (4)
2 Cotton underwear conventional short sleeve and brief/shorts, plus FR shirt and
FR pants (1 or 2)
33.47 (8)
3 Cotton underwear plus FR shirt and FR pants plus FR coverall, or cotton underwear
plus two FR coveralls (2 or 3)
104.6 (25)
4 Cotton underwear plus FR shirt and FR pants plus multilayer flash suit (3 or more) 167.36 (40)
Note: Arc rating is defined in Article 100 and can be either ATPV or EBT. ATPV is defined in ASTM F 1959-99
as the incident energy on a fabric or material that results in sufficient heat transfer through the fabric or
material to cause the onset of a second-degree burn based on the Stoll curve. EBT is defined in ASTM F
1959-99 as the average of the five highest incident energy exposure values below the Stoll curve where the
specimens do not exhibit breakopen. EBT is reported when ATPV cannot be measured due to FR fabric
breakopen. (APTV = Arc Thermal Protective Value)
AF Testing & Models
To date, there are no practical theoretical models that match tested arc flash results
Instead, state-of-the-art techniques use empirical models based upon test results
IEEE 1584-2002 gives an empirical model that, if properly applied, gives 95% confidence that calculated PPE will be adequate or more-than-adequate for hazards associated with heat energy from an arc
Other effects, such as pressure-wave effects and the effects of the expulsion of molten metal, are not taken into account in the IEEE-1584 model.
IEEE 1584 Model
Ia is the arcing current (kA), defined by IEEE-1584 as:
K = -0.153 for open configurations, = -0.097 for box configurations Ibf: Bolted fault current for three-phase faults (symm. RMS) (kA) V: System voltage (kV) G: gap between conductors, (mm) Represents current that would flow through the arc during
an arcing fault typically 50% - 60% of bolted fault current for 480V system
bfIlogG00304.0bfIlogV5588.0G000526.0V0966.0bfIlog662.0K10aI
En is the normalized incident energy
K1 = -0.792 for open configurations, = -0.555 for box configurations K2 = 0 for ungrounded or HRG systems, = -0.113 for grounded systems Ia is the arcing current (kA) (Calculated) G is gap between conductors, (mm) (Measured) Represents arc-flash incident energy normalized to a
working distance of 610mm and 0.2s arcing time
G0011.0Ilog081.1KKn
a2110E
IEEE 1584 Model
E is the calculated incident energy
Cf = 1.5 for voltages 1kV, = 1.0 for voltages > 1kV t: Arcing time in seconds D: Working distance (mm) x: Distance exponent (tabulated in IEEE 1584) Note that once E is calculated, the process should be repeated but for Ia =
85% of the calculated value. The larger of the two values for E is the calculated arc-flash incident energy.
(cal/cm2)
x
x
nfD
tECE
610
2.0
IEEE 1584 Model
What System Parameters Can be
Changed to Reduce AFIE? From IEEE 1584 model:
System Voltage Bolted fault current Gap between conductors Arcing time
System voltage: Generally not practical to change
Gap between conductors: Would require different equipment construction, not practical to change
That leaves bolted fault current and arcing time.
Effect of Changing Bolted Fault Current
on AFIE Lower bolted fault current leads to
lower arcing current
Arcing current determines arcing time!
Overcurrent protective devices, which define the arcing time, may take longer to trip with lower arcing current due to inverse time-current characteristics
Higher arcing current: 0.06s arcing time
Lower arcing current: 1s arcing time
Arc Flash Mitigation Methods
Enhancing Personnel Safety
Number of arc flash explosions that occur in
electrical equipment every day in the United States - According to statistics compiled by Cap-Schell, Inc.,
a Chicago-based research and consulting firm that
specializes in preventing workplace injuries and deaths
5-10
Each year the number of patients that are
emitted to burn centers due to arc flash events - Report by research on IEEE Website
2000
Electrical Safety
Electrical Safety Then and Now http://esfi.org/index.cfm/page/Electrical-Safety-Then-and-Now/cdid/12394/pid/10272
Workplace Electrical Injury and Fatality Statistics http://esfi.org/index.cfm/page/Workplace-Electrical-Injury-and-Fatality-Statistics,-2003-
2010/cdid/12396/pid/3003
http://esfi.org/index.cfm/pid/11506
Arc Flash Mitigation Solutions
Prevention / Avoidance
Passive Containment
Energy Redirection
Installation Considerations
Plenums (ductwork)
Size of Equipment
Equipment location
Passive Protection
Virtual Mains
Zone Selective Interlocking
Bus Differential Relays
Low Arc Flash CB
High Resistance Grounding
Arc Flash Sensing Relay-
VAMPTM technology
Active Protection
LV Arc Flash Sensing Relay
with Arc Quenching technology
MV Arc TerminatorTM
Interactive Protection
Energy-Reducing
Maintenance Switches
System Design
De-energize Equipment
Site Safety Procedures
Intelligent MCCs
AF Mitigating Features (Equipment Design)
Electric Operated CBs
AF
19
Zone Selective Interlocking
Bolted Fault Current 62kA Arc Fault Current 29kA Incident Energy 24 3.33 cal/cm2
PPE Category 1
Bolted Fault Current 62kA Arc Fault Current 29kA Incident Energy 24 3.33 cal/cm2
PPE Category 1
.1sec
10kA 100kA
1sec
10sec
100sec
1kA
M1 3000A
tSD .3 Sec
F1 800A
F2 800A
F3 800A
F4 800A
No restraint signal
Short time delay will be
ignored
Incident Energy 24 20 cal/cm2
PPE Category 3
Bolted Fault Current 62kA Arc Fault Current 29kA
Coordinated System
Arc flash detection relay (1-2 msec) (light sensors/current-optional) Tripping of upstream breaker Fault location identification Multiple zones protection (optional)
MAIN CB
CB F1 CB F2 CB F3
Transformer
Primary fuse
LV Switchgear
x Fault
AF
Relay
Zone 1
Z2 Z3 Z4 Optional
Arc Flash Relay Systems
Typical System Design
Virtual Main
Arc Terminator System Operation Sense a Fault Current + Detect an Arc = Close Shorting Switch
MasterClad Arc Resistant Ratings
Nominal Voltage 4.16 kV 7.2 kV 13.8 kV
Maximum Voltage 4.76 kV 8.25 kV 15.0 kV
BIL (kV) 60 95 95
Continuous
Current (A)
1200, 2000,
3000(*)
1200, 2000,
3000(*)
1200, 2000,
3000(*)
Interrupting
Current (kA)
40, 50 40 25, 40, 50
Internal Arc
Current (kA)
Up to 63, 0.5 sec Up to 63, 0.5 sec Up to 63, 0.5 sec
Enclosure Types Nema 1 Nema 1 Nema 1
(*) Only for 1 High
Pressure Relief Flaps
Arc Plenum - Optional
Medium Voltage MCC
Compartmentalized
Construction
Bolted Rear Panels
Top View
Rear View
Interlocked rear panel to Frame Construction
Top and Bottom Access Panels
Easy Removal
Enclosure AR Type 2
ANSI C37.20.1 Power-Zone 4 Drawout Switchgear ANSI C37.20.7, Annex D Arc Resistant (ANSI C37.20.1 Power-Zone 4 Drawout Switchgear)
North America
Low Voltage Arc Resistant Offer
Schneider Electric SpecTech 2012, November Update 28
IIEEE C37.20.7-2007
IEEE guide for testing metal-enclosed switchgear rated up
to 38 kV for internal arcing
faults
A procedure for testing and evaluating the performance of
metal-enclosed switchgear for
internal arcing faults is
covered. A method of
identifying the capabilities of
this equipment is given.
Service conditions,
installation, and application of
equipment are also discussed.
Without ArcBlokTM
(1 shot) at 65 kAIR @ 480 Vac
AR LV Equipment- Design Values
With ArcBlokTM
(1 shot) at 65 kAIR @ 480 Vac
AR LV Equipment- Design Values
Schneider Electric SpecTech 2012, November Update 31
Testing Standard
Reinforced, Compartmentalized Enclosure
Ratings Bus and Breaker kAIR Accessibility Type (2A/2B)
Optional Features Insulated Bus Plenums Zone Selection Interlocking High Resistant Grounding Energy Reduction
Maintenance Switch
Breaker Remote Racking
Arc Resistant Considerations
Air Intake Design
Optimized Air Flow
Dynamic Spring Loaded Pressure Flap
Plenums
Plenums for PZ-4
What is the Standard for Low Voltage
Motor Control Centers?
Low Voltage Motor Control Center A Standard Dilemma.Resolved
IEEE PC37.20.7, Draft 6 May 2014, Annex H
Purpose of the Annex is to provide specific information
for test sample configuration,
testing methods, test assessment,
and additional ratings that are
specific to LV MCCs (UL845)
There currently is no standard or guide for testing Low Voltage Motor Control Centers for
internal arcing faults however based on
recent decisions within IEEE, AR MCCs will
now be covered in Annex H of the IEEE
C37.20.7 standard.
The most important test parameters for determining equipment capability
is establishing -
The preferred rated arcing duration test (H.3)
The means of establish an arc to produce enough ionized gas quickly
enough to prevent premature
extinction at lower voltages (H.4)
Current discussions within the working group indicate that the minimum arcing duration test
will be no less than 100 ms
Pull Box
Plenum
Exhaust Options
Baffle
Plenum UL Witnessed
Plenum Design
Top Entry thru Pull Box
Single Plenum
Pull Box
28.5 in
10 ft.
Minimum height from bottom of
section to obstruction above MCC
14.24 in.
Rear Front
Ceiling or obstruction above MCC
Thank You
Appendix
MasterClad Arc Resistant 2-High
Circuit breaker
compartment
Relay & instrument door
Cable
compartment
Main Bus
compartment
MasterClad Arc Resistant with Plenum
Plenum Required if: Ceiling* less than
192 Power Zone Center
Application Exhaust needed from
equipment room 50kA or 63kA rating
(optional use-arc shield)
*As measured from the floor
MasterClad Arc Resistant
Arc Shield
Arc Shield Required if: 50kA or 63kA
rating (optional use-plenum)
Increase likelihood of protection for front, rear, & sides of equipment
ArcBlok Patented Technology Internal Arc Gas Management System
Prevents and
Controls Arcing Cluster Shields
Cradle Barriers
Arc Ventilation
Exhaust Methods - Baffles
Roof Baffles
14 Guage Steel
Exhaust Flap
Louvered
10 ft. Clearence
Ceiling
Base of
Equipment
Internal Arc Gas Management
Shroud Power
Stabs Vertical Bus
Isolation
Ventilated
Mid-Shelf
Model 6 Arc Resistant Highlights
Testing Standard C37.20.7, Annex H
UL Witnessed
Reinforced Enclosure 12 gauge steel Additional hardware Metal Control Station Plate Filter box (VFD) Baffle compartment assembly
Ratings 65 kAIR @ 600 Vac Type 2A 100 ms (Stage 1) 500 ms (Stage 2) 2000A Bus (Stage 1) 2500A Bus (Stage 2)
Additional top
mid bracket
Reinforced door
with hinges
Additional bottom
mid bracket
Clip on Fast
Lead Screws
Metal Control
Station Plate
Filter Box for
Thermal Ventilation
47
References
Arc Flash Mitigation
AT327/July 2013
SE Engineering Services
1910BR1205
Arc Flash Description of Services
SAFARC01R02/12
Industry-Leading Expertise We currently have more than 130 power
system engineers. SE Engineering
Services has completed over 10,000
power system assessments, studies,
and designs including IBM.
Arc Flash Analysis
An arc flash analysis is performed to estimate incident energy levels, to identify
appropriate levels of Personal Protective Equipment (PPE) and to determine flash
protection boundaries at specific points in an electrical distribution system.
The Occupational Safety and Health Administration requires employers to protect
facility workers and contractors from the hazards associated with electrical shock,
arc, and blast. The National Fire Protection Agency, producers of the National
Electrical Code, developed a set of guidelines to assist employers in complying with
OSHA laws in the NFPA 70E, Standard for Electrical Safety in the Workplace.
We offer arc flash analyses based on the results from the Short-circuit and
Overcurrent Device Coordination studies, and are calculated using the
equations provided in IEEE Std. 1584-2002.
Arc Flash Mitigation
Enhancing Personnel Safety
April 23, 2014
Terry L. Schiazza
Business Development Mgr.
Seneca, SC Manufacturing Facility