- - SHADED AREA FIXTURE ON EMERGENCY CIRCUIT BOX. CEILING MOUNTED LIGHTING FIXTURE AND OUTLET - - LIGHTING DESCRIPTION SYMBOL - - SHADED AREA FIXTURE ON EMERGENCY CIRCUIT WALL MOUNTED LIGHTING FIXTURE AND OUTLET - - BOX. CEILING/WALL EXIT LIGHT AND OUTLET BOX, LED TYPE, SELF CONTAINED, WITH BATTERY PACK: - SHADED AREA INDICATES ILLUMINATED FACE(S) - ARROW INDICATES DIRECTION EMERGENCY UNIT EQUIPMENT, 90 MINUTE BATTERY PACK, CHARGER AND TEST SWITCH. NOTE: SEE LIGHT FIXTURE SCHEDULE AND SPECIFICATIONS FOR COMPLETE FIXTURE DESCRIPTION. DESCRIPTION SYMBOL WIRING DEVICES LINE VOLTAGE SWITCH - LOWER CASE LETTER DENOTES SWITCHING ZONES - 'T' DENOTES SWITCH TYPE: MC - MOMENTARY CONTACT D - DIMMER WP - WEATHER PROOF LOW VOLTAGE SWITCH OCCUPANCY SENSOR, CEILING MOUNTED ABBREVIATIONS DESCRIPTION SYMBOL L LTG C A, AMP AMPERE AMPS INTERRUPTING CAPACITY AIC AC ALTERNATING CURRENT ABOVE FINISHED FLOOR AFF ATC AUTOMATIC TEMPERATURE CONTROL AUTOMATIC TRANSFER SWITCH ATS BAS BUILDING AUTOMATION SYSTEM BUILDING MANAGEMENT SYSTEM BMS BFG BELOW FINISHED GRADE C, CDT CONDUIT CIRCUIT BREAKER CB CABINET HEIGHT CH CKT CIRCUIT CONDUIT ONLY C.O., CO CONFIG. CONFIGURATION CENTERLINE CONVENIENCE CONV CM CONSTRUCTION MANAGER DIGITAL DATA CONTROL DDC DWG DRAWING ELECTRICAL CONTRACTOR E.C. ELEC ELECTRICAL EMERGENCY EM EMT ELECTRICAL METALLIC TUBING ELECTRICALLY OPERATED 'ON-OFF' E.O. EQUAL EQ EWC ELECTRIC WATER COOLER FIRE ALARM FA FAI FURNISH AND INSTALL FS FIRE SHUTTER/DOOR FULL LOAD AMPS FLA FSD FIRE SMOKE DAMPER GROUND G, GND GEN GENERATOR GROUND FAULT CIRCUIT INTERRUPTER GFCI HC HUNG CEILING HIGH INTENSITY DISCHARGE HID HAND-OFF-AUTOMATIC HOA HORSE POWER HP INSTALLED BY ELECTRICAL CONTRACTOR IBEC FURNISHED BY OTHERS FBO ISOLATED GROUND IG JB,J JUNCTION BOX KILO VOLT- AMPERE KVA KW KILO WATT KILO WATT HOUR KWH LC LCP LOCK & COVER LIGHTING CONTROL PANEL LIGHTING LOW VOLTAGE LV LVR LOW VOLTAGE RELAY MOTOR CONTROL CENTER MCC MOTOR CONTROL PANEL MCP MER MECHANICAL EQUIPMENT ROOM MANUFACTURER MFRR MIN MINIMUM MAIN LUGS ONLY MLO MSB MAIN SWITCHBOARD MOUNTED MTD N NEUTRAL NOT APPLICABLE NA, N/A NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION N.C. NORMALLY CLOSED NOT IN CONTRACT NIC # NUMBER NORMALLY OPEN N.O. NTS NOT TO SCALE ON CENTER OC POLES P PB PULL BOX POWER FACTOR CORRECTION PFC PH, ø PHASE PANEL PNL PVC POLYVINYL CHLORIDE POWER PWR RC REHEAT COIL RECEPTACLE RECPT, REC RM ROOM SIGNAGE SG SHT SHEET SPECIFICATIONS SPEC SPDT SINGLE POLE DOUBLE THROW SINGLE POLE SINGLE THROW SWITCH SPST SW SWBD SWGR SWITCHBOARD SWITCHGEAR TIME CLOCK TC TYP TYPICAL UNDERGROUND UG UON, U.O.N. UNLESS OTHERWISE NOTED UNINTERRUPTIBLE POWER SUPPLY UPS UNF UNFUSED VOLT V VA VOLT-AMPERES VACUUM PRESSURE IMPREGNATION VPI VAPOR TIGHT VT W WATT WEATHER PROOF WP XFMR TRANSFORMER POWER DESCRIPTION SYMBOL SAFETY DISCONNECT SWITCH, 3 POLE UON A: 30A UNFUSED AF: 30A FUSED B: 60A UNFUSED BF: 60A FUSED C: 100A UNFUSED CF: 100A FUSED D: 200A UNFUSED DF: 200A FUSED E: 400A UNFUSED EF: 400A FUSED - '4x' DENOTES NEMA ENCLOSURE IF INDICATED TRANSFORMER, SEE SCHEDULE FOR RATING RELAY - NUMERAL DENOTES NUMBER OF POLES SURFACE MOUNTED PANELBOARD FLOOR MOUNTED DISTRIBUTION/SWITCHBOARD CONDUIT AND WIRE HOMERUN. CONTINUOUS RUN TO MCC, PANELBOARD, SWITCHBOARD OR EQUIPMENT CABINET. CONDUIT AND WIRE RUN IN WALL OR CEILING SPACE, OR RUN EXPOSED IN UNFINISHED SPACE. FUSED DISCONNECT SWITCH - NUMERICAL DENOTES TRIP SIZE - '4x' DENOTES NEMA ENCLOSURE IF INDICATED AUTOMATIC TRANSFER SWITCH, SEE RISER DIAGRAM FOR RATING FLUSH MOUNTED PANELBOARD PULLBOX R HOSPITAL DESCRIPTION SYMBOL NURSE CALL SYSTEM PATIENT STATION WALL MOUNTED OR ON PATIENT HEADWALL UNIT NURSE CALL SYSTEM EMERGENCY STATION, WALL MOUNTED AT +48" UON. NURSE CALL SYSTEM TOILET STATION, WALL MOUNTED AT +30" UON. WITH PULL CORD NURSE CALL SYSTEM SHOWER STATION, WALL MOUNTED AT +60" UON. WITH PULL CORD NURSE CALL SYSTEM DUTY STATION, WALL MOUNTED AT +48" UON. NURSE CALL SYSTEM STAFF STATION, WALL MOUNTED AT +48" UON. NURSE CALL CODE BLUSE STATION, WALL MOUNT AT +48" OR MOUNT ON PATIENT HEADWALL UON. NURSE CALL SYSTEM DOME LIGHT, WALL MOUNTED (SEE ARCH. ELEVATORS FOR EXACT LOCATION) NURSE CALL SYSTEM DOME LIGHT, CEILING MOUNT NURSE CALL SYSTEM CONTROL PANEL R 6 ATS 4x AF J J J T4 a,b T a,b XP - EXPLOSION PROOF O OCCUPANCY SENSOR, WALL MOUNTED O PHOTOCELL CONTROLLER, CEILING MOUNTED PHOTOCELL CONTROLLER, WALL MOUNTED LIGHTING CONTACTOR TIME CLOCK PUSH BUTTON REMOTE CONTROL SWITCH RC TC LC SURGE SUPPRESSION SS XP EXPLOSION PROOF SIMPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON QUAD RECEPTACLE WALL MOUNTED, +18" AFF, UON SPECIAL RECEPTACLE WALL MOUNTED, +18" AFF, UON SIMPLEX RECEPTACLE CEILING MOUNTED DUPLEX RECEPTACLE CEILING MOUNTED QUAD RECEPTACLE CEILING MOUNTED SPECIAL RECEPTACLE CEILING MOUNTED SIMPLEX RECEPTACLE FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED QUAD RECEPTACLE FLUSH FLOOR MOUNTED SPECIAL RECEPTACLE FLUSH FLOOR MOUNTED JUNCTION BOX RECESSED WALL MOUNTED JUNCTION BOX RECESSED CEILING MOUNTED JUNCTION BOX RECESSED FLUSH FLOOR MOUNTED LIGHTNING PROTECTION & GROUNDING DESCRIPTION SYMBOL - 'L' DENOTES LIGHTNING PROTECTION MAIN CONDUCTOR LIGHTING PROTECTION AIR TERMINAL GROUND ELECTRODE CONNECTION TO EQUIPMENT THRU ROOF PENETRATION CABLE IN CONDUIT TRIANGULAR GROUND GRID - THREE 3/4" x 10'-0" RODS SPACED 30'-0" MINIMUM APART INTERCONNECTED WITH 4/0 COPPER CONDUCTOR. THRU ROOF PENETRATION TO STEEL FULL DOWNLEAD TO GROUND STEEL COLUMN BOND TO GROUND EXPOSED DOWNLEAD TO GROUND 2"x1/4" COPPER GROUND BUS BAR, LENGTH AS INDICATED ON PLANS. - 'G' DENOTES COUNTERPOISE/GROUND CABLE GROUND PLATE CONNECTION SOLID COPPER, 24"x24"x20 GA. GROUND ELECTRODE 3/4" COPPER ROD, 10'-0" DEEP - "TW" INDICATES TEST WELL G TW L PS ES TS SH DS SS NURSE CALL SYSTEM MASTER ANNUCIATOR STAT CB NCCP MA MISCELLANEOUS DESCRIPTION SYMBOL FEEDER SIZE, SEE FEEDER SCHEDULE REFERENCE NOTE DETAIL REFERENCE: - DETAIL DESIGNATION - SHEET NUMBER REFERENCE EQUIPMENT REFERENCE. COORDINATE EQUIPMENT WITH MECHANICAL/PLUMBING TRADES. SEE MECHANICAL/PLUMBING DRAWINGS FOR LOCATIONS. EF 1 # P380D SINGLE LINE DIAGRAM DESCRIPTION SYMBOL PANELBOARD, SEE PANEL SCHEDULE FOR RATING. MOLDED CASE CIRCUIT BREAKER: - 'TEXT' DENOTES CB ACCESSORIES LOW VOLTAGE DRAW OUT CIRCUIT BREAKER: MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER AUTOMATIC TRANSFER SWITCH GENERATOR UTILITY METER DIGITAL MULTIFUNCTION METER WITH CURRENT/POTENTIAL TRANSFORMER AS REQUIRED ST, ET. GFP, EO, LSI TRIP FUNCTIONS - NUMERICAL DENOTES TRIP SIZE - 'TEXT' DENOTES CB ACCESSORIES - NUMERICAL DENOTES TRIP SIZE WITH INTEGRAL TRIP UNIT LOW VOLTAGE FUSE/SWITCH UNIT - 'TEXT' DENOTES FUSE ACCESSORIES ST, GFR, EO, LO, LOCK OUT PROVISIONS - NUMERICAL DENOTES FUSE SIZE MEDIUM VOLTAGE DRAWOUT FUSE/SWITCH UNIT - 'TEXT' DENOTES FUSE ACCESSORIES - NUMERICAL DENOTES FUSE SIZE ENCLOSED CIRCUIT BREAKER - 'TEXT' DENOTES CB ACCESSORIES - NUMERICAL DENOTES TRIP SIZE ENCLOSED SAFETY DISCONNECT SWITCH - 'TEXT' DENOTES FUSE ACCESSORIES - NUMERICAL DENOTES SWITCH SIZE ENCLOSED FUSED DISCONNECT SWITCH - 'TEXT' DENOTES FUSE ACCESSORIES - NUMERICAL DENOTES SWITCH SIZE INTERMEDIATE CLASS MOV SURGE ARRESTER - NUMERICAL DENOTES ARRESTER RATING MOTOR AUTOMATIC TRANSFER SWITCH W/BYPASS ISOLATION KEY INTERLOCK RELAY NUMERICAL INDICATES TYPE CURRENT TRANSFORMER: - '200/5' DENOTES CT RATIO IF INDICATED POTENTIAL TRANSFORMER: - NUMERICAL DENOTES QUANTITY OF FUSES INVERTER RECTIFIER BATTERY TRANSFORMER WITH PRIMARY AND SECONDARY CONNECTIONS AS INDICATED ON RISER DIAGRAM. M A FEEDER BUSWAY PANEL 1 51 BW 200/5 KI GFP TRIP N E L LSI TRIP ST TRIP ST TRIP GFP FUSE M V A 52 GFP FUSE G M SA 12KV ATS-# CONN AMPS ATS-# CONN AMPS DIGITAL ENERGY METER M DUPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON X LETTER DESIGNATION ON RECEPTACLES: A = ARC FAULT CIRCUIT INTERRUPTER G = GROUND FAULT CIRCUIT INTERRUPTER IG = ISOLATED GROUND WP = WEATHER PROOF WITH 'GFCI' S = SAFETY CT = ABOVE COUNTER CR = CRITICAL EQ = EQUIPMENT LS = LIFE SAFETY +X" = INDICATES MOUNTING HEIGHT SHADING = INDICATES RECEPTACLE ON EMERGENCY CONDUIT AND WIRE RUN EXPOSED ON WALL OR CEILING IN FINISHED SPACE. CONDUIT AND WIRE RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND GROUND CONNECTION MOTOR CONTROL EQUIPMENT AND CONNECTION TO CONTROLLED MOTOR(S). CONTROLLER IS MOUNTED AGAINST AN ADJACENT WALL OR OTHERWISE REMOTE FROM THE MOTOR. SEE MOTOR EQUIPMENT SCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROL EQUIPMENT, QUANTITY OF MOTORS CONNECTED TO CONTROLLER, AND OTHER DETAILS. CONDUCTOR SIZE BETWEEN CONTROLLER AND MOTOR SHALL MATCH THE UPSTREAM OF THE CONTROLLER UNLESS NOTED OTHERWISE ON THE SCHEDULE. MOTOR CONTROL EQUIPMENT AND CONNECTION TO CONTROLLED MOTOR(S). CONTROLLER IS EITHER INTEGRAL TO THE EQUIPMENT OR MOUNTED DIRECTLY ONTO THE EQUIPMENT. SEE MOTOR EQUIPMENT SCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROL EQUIPMENT, QUANTITY OF MOTORS CONNECTED TO CONTROLLER, AND OTHER DETAILS. CONDUCTOR SIZE BETWEEN CONTROLLER AND MOTOR SHALL MATCH THE UPSTREAM OF THE CONTROLLER UNLESS NOTED OTHERWISE ON THE SCHEDULE. CB 4x 225 +X" ACCESS FLOOR BOX WITH OUTLETS AS SPECIFIED POKE THROUGH FLOOR BOX WITH OUTLETS AS SPECIFIED CONDUIT TURNING UP CONDUIT TURNING DOWN CONDUIT CAPPED ARC FAULT CIRCUIT INTERRUPTER AFCI RACEWAYS FLEXIBLE CONNECTION CONDUIT AND WIRE, HASH MARKS INDICATE NUMBER OF WIRES. # HASH MARKS INDICATES 3#12+1#10N+ 1#12G IN 3/4" CONDUIT UON. P P E - 3 A DESCRIPTION FIRE ALARM SYMBOLS SYMBOL FIRE SERVICE OR EMERGENCY TELEPHONE J - JACK FTS - FIRE FIGHTER’s TELEPHONE SYSTEM MANUAL PULL STATION MANUAL STATION HL - HALON CO2 - CARBON DIOXIDE FO - FOAM WM - WATER MIST DL - DELUGE SPRINKLER PRE - PREACTION SYSTEM ABORT SWITCH HL - HALON CO2 - CARBON DIOXIDE CA - CLEAN AGENT DL - DELUGE SPRINKLER PRE - PREACTION SYSTEM EPO - EMERGENCY POWER OFF HEAT DETECTOR R/F - RATE OF RISE AND FIXED TEMPERATURE R/C - RATE COMPENSATION F - FIXED TEMPERATURE R - RATE OF RISE ONLY SMOKE DETECTOR P - PHOTOELECTRIC BR - BEAM RECEIVER BT - BEAM TRANSMITTER SMOKE DETECTOR FOR DUCT SMOKE/HEAT DETECTOR HEAT LINE-TYPE DETECTOR (HEAT SENSITIVE CABLE) GAS DETECTOR FLAME DETECTOR F - FLAME UV - ULTRAVIOLET UV/IR - COMBINATION ULTRAVIOLET/INFRARED VR - VISIBLE RADIATION ADDRESSABLE MODULE AIM - INPUT AOM - OUTPUT FLOW DETECTOR/SWITCH PRESSURE DETECTOR/SWITCH W - WATER LA - LOW AIR HA - HIGH AIR LEVEL DETECTOR/SWITCH TAMPER DETECTOR/SWITCH VALVE TAMPER DETECTOR/SWITCH OUTPUT RELAY TEMPERATURE SWITCH HT - HIGH TEMPERATURE LT - LOW TEMPERATURE AUDIO DEVICE (WALL MOUNTED) H - HORN S - SPEAKER C - CHIME M - MINI AUDIO DEVICE (CEILING MOUNTED) H - HORN S - SPEAKER C - CHIME STROBE (WALL MOUNTED) STROBE (CEILING MOUNTED) AUDIO/VISUAL COMBINATION (WALL MOUNTED) H - HORN S - SPEAKER C - CHIME AUDIO/VISUAL COMBINATION (CEILING MOUNTED) H - HORN S - SPEAKER C - CHIME ROTATED BEACON BELL (WALL MOUNTED) V - VIBRATING VS - VIBRATING/STROBE GS - GONG/STROBE DOOR HOLDER FLOOR/DOOR FIRE ALARM CONTROL PANEL FIRE SYSTEM ANNUNCIATOR ALARM AIR SAMPLING CONTROL DETECTOR PANEL ELEVATOR STATUS/RECALL FIRE ALARM COMMUNICATOR HVAC CONTROL PANEL VOICE EVACUATION PANEL FIRE ALARM TERMINAL CABINET FIRE ALARM TRANSPONDER DATA GATHERING PANEL FIRE COMMAND SYSTEM SPRINKLER ALARM PANEL RELAY ALARM PANEL PURGE PANEL FIRE ALARM CONTROL UNIT BATTERY PACK AND CHARGER AMPLIFIER RACK FIRE SYSTEM CONTROL PANEL HL - HALON CO2 - CARBON DIOXIDE DC - DRY CHEMICAL WC - WET CHEMICAL DL - DELUGE SPRINKLER REMOTE TEST SWITCH DC - DRY CHEMICAL WC - WET CHEMICAL CA - CLEAN AGENT DC - DRY CHEMICAL FO - FOAM WC - WET CHEMICAL WM - WATER MIST P - PHONE I - IONIZATION ASD - AIR SAMPLING IR - INFRARED G - GONG FO - FOAM WM - WATER MIST T - TROUBLE CA - CLEAN AGENT HL AIM AMP ASFP H H H H BATT GS DGP J ESR EVAC FAC FACP FACU FATC FCS F FSA FSCP HL FTR HVA P HL R PP LA RTS RP SAP FIRE SYSTEM ANNUNCIATOR PANEL FSAP P R HT F A - ACCESSIBLE PB PLAN NORTH Project Team WORTHAM THEATER REHABILITATION 501 Texas Ave Houston, TX 77002 Scale: © Copyright 2018 All information, drawn, written, or implied, appearing in this document constitutes the original and unpublished work of HarrisonKornberg Architects, LLC. and may not be duplicated, distributed, or disclosed by any means without the prior written consent of HarrisonKornberg Architects, LLC. This is an instrument of services and sole property of the author. The use of this document shall be revoked if any of the design intent or the construction methods shown herein are not adhered to, or the terms of the contractual agreement for its use is violated. Written dimensions on these drawings shall have precedence over scale dimensions. Contractors shall be responsible for all dimensions and conditions on the job. HarrisonKornberg Architects, LLC must be notified of any variation from the dimension and conditions shown by these drawings. 3800 Buffalo Speedway, Suite 550 Houston, Texas 77098 tel (713) 229-0688 fax (713) 229-0692 ARCHITECT HarrisonKornberg Contact: David Kaczynski t: 713.229.0688 A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 Date: Project Name: HFR 12/27/2017 Issue for Bid 701 Avenida de las Americas Houston, TX 77010 CIVIL ENGINEER Martinez Moore Contact: TBD t: TBD MEP ENGINEER Arup Contact: Tom Smith t: 713.343.1472 PARKING CONSULTANT Walker Parking Contact: Jeremy Rocha t: TBD ACOUSTICS / AV / IT Jaffe Holden Contact: Garth Hemphill t: TBD Key Plan Revisions 01-12-2018 12" = 1' - 0" ELECTRICAL - SYMBOLS, ABBREVIATIONS, AND DRAWING LIST WT - 1 - E.0.01 PACKAGE 1 ELECTRICAL DRAWING LIST DRG NO. DRAWING TITLE SCALE WT-1-E.0.01 ELECTRICAL - SYMBOLS, ABBREVIATIONS, AND DRAWING LIST NTS WT-1-E.2.30 ELECTRICAL - SEGMENT THREE - BASEMENT - POWER PLAN 1/8" = 1'-0" WT-1-E.4.00.1 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 1 NTS WT-1-E.4.00.2 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 2 NTS WT-1-E.7.00.1 ELECTRICAL - BASEMENT - PARTIAL PLANS 1/4" = 1'-0" No. Date Description

WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

Embed Size (px)

Citation preview

Page 1: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

-- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT

BOX.CEILING MOUNTED LIGHTING FIXTURE AND OUTLET

--

LIGHTINGDESCRIPTIONSYMBOL

-- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT

WALL MOUNTED LIGHTING FIXTURE AND OUTLET

--

BOX.

CEILING/WALL EXIT LIGHT AND OUTLET BOX,LED TYPE, SELF CONTAINED, WITH BATTERY PACK:- SHADED AREA INDICATES ILLUMINATED FACE(S)- ARROW INDICATES DIRECTION

EMERGENCY UNIT EQUIPMENT, 90 MINUTEBATTERY PACK, CHARGER AND TEST SWITCH.

NOTE: SEE LIGHT FIXTURE SCHEDULE AND SPECIFICATIONSFOR COMPLETE FIXTURE DESCRIPTION.

DESCRIPTIONSYMBOL

WIRING DEVICES

LINE VOLTAGE SWITCH- LOWER CASE LETTER DENOTES SWITCHING ZONES- 'T' DENOTES SWITCH TYPE:MC - MOMENTARY CONTACTD - DIMMERWP - WEATHER PROOF

LOW VOLTAGE SWITCH

OCCUPANCY SENSOR, CEILING MOUNTED

ABBREVIATIONSDESCRIPTIONSYMBOL

L

LTG

C

A, AMP AMPERE

AMPS INTERRUPTING CAPACITYAIC

AC ALTERNATING CURRENT

ABOVE FINISHED FLOORAFF

ATC AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC TRANSFER SWITCHATS

BAS BUILDING AUTOMATION SYSTEM

BUILDING MANAGEMENT SYSTEMBMS

BFG BELOW FINISHED GRADEC, CDT CONDUIT

CIRCUIT BREAKERCB

CABINET HEIGHTCH

CKT CIRCUIT

CONDUIT ONLYC.O., CO

CONFIG. CONFIGURATION

CENTERLINE

CONVENIENCECONV

CM CONSTRUCTION MANAGER

DIGITAL DATA CONTROLDDC

DWG DRAWING

ELECTRICAL CONTRACTORE.C.

ELEC ELECTRICAL

EMERGENCYEM

EMT ELECTRICAL METALLIC TUBING

ELECTRICALLY OPERATED 'ON-OFF'E.O.

EQUALEQ

EWC ELECTRIC WATER COOLER

FIRE ALARMFAFAI FURNISH AND INSTALL

FS FIRE SHUTTER/DOOR

FULL LOAD AMPSFLA

FSD FIRE SMOKE DAMPER

GROUNDG, GND

GEN GENERATOR

GROUND FAULT CIRCUIT INTERRUPTERGFCI

HC HUNG CEILING

HIGH INTENSITY DISCHARGEHID

HAND-OFF-AUTOMATICHOA

HORSE POWERHP

INSTALLED BY ELECTRICAL CONTRACTORIBEC

FURNISHED BY OTHERSFBO

ISOLATED GROUNDIGJB,J JUNCTION BOX

KILO VOLT- AMPEREKVA

KW KILO WATT

KILO WATT HOURKWH

LC

LCP

LOCK & COVER

LIGHTING CONTROL PANEL

LIGHTING

LOW VOLTAGELV

LVR LOW VOLTAGE RELAY

MOTOR CONTROL CENTERMCC

MOTOR CONTROL PANELMCP

MER MECHANICAL EQUIPMENT ROOM

MANUFACTURERMFRR

MIN MINIMUM

MAIN LUGS ONLYMLO

MSB MAIN SWITCHBOARD

MOUNTEDMTD

N NEUTRAL

NOT APPLICABLENA, N/A

NEMA NATIONAL ELECTRICAL MANUFACTURERSASSOCIATION

N.C. NORMALLY CLOSED

NOT IN CONTRACTNIC

# NUMBER

NORMALLY OPENN.O.

NTS NOT TO SCALE

ON CENTEROC

POLESP

PB PULL BOX

POWER FACTOR CORRECTIONPFC

PH, ø PHASE

PANELPNL

PVC POLYVINYL CHLORIDE

POWERPWR

RC REHEAT COIL

RECEPTACLERECPT, REC

RM ROOM

SIGNAGESG

SHT SHEET

SPECIFICATIONSSPEC

SPDT SINGLE POLE DOUBLE THROW

SINGLE POLE SINGLE THROW

SWITCH

SPST

SW

SWBD

SWGR

SWITCHBOARD

SWITCHGEAR

TIME CLOCKTC

TYP TYPICAL

UNDERGROUNDUG

UON, U.O.N. UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLYUPS

UNF UNFUSED

VOLTV

VA VOLT-AMPERES

VACUUM PRESSURE IMPREGNATIONVPI

VAPOR TIGHTVT

W WATT

WEATHER PROOFWP

XFMR TRANSFORMER

POWERDESCRIPTIONSYMBOL

SAFETY DISCONNECT SWITCH, 3 POLE UONA: 30A UNFUSED AF: 30A FUSEDB: 60A UNFUSED BF: 60A FUSEDC: 100A UNFUSED CF: 100A FUSEDD: 200A UNFUSED DF: 200A FUSEDE: 400A UNFUSED EF: 400A FUSED- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

TRANSFORMER, SEE SCHEDULE FOR RATING

RELAY - NUMERAL DENOTES NUMBER OF POLES

SURFACE MOUNTED PANELBOARD

FLOOR MOUNTED DISTRIBUTION/SWITCHBOARD

CONDUIT AND WIRE HOMERUN. CONTINUOUS RUN TOMCC, PANELBOARD, SWITCHBOARD OR EQUIPMENTCABINET.

CONDUIT AND WIRE RUN IN WALL OR CEILING SPACE,OR RUN EXPOSED IN UNFINISHED SPACE.

FUSED DISCONNECT SWITCH- NUMERICAL DENOTES TRIP SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

AUTOMATIC TRANSFER SWITCH, SEE RISERDIAGRAM FOR RATING

FLUSH MOUNTED PANELBOARD

PULLBOX

R

HOSPITALDESCRIPTIONSYMBOL

NURSE CALL SYSTEM PATIENT STATION WALLMOUNTED OR ON PATIENT HEADWALL UNIT

NURSE CALL SYSTEM EMERGENCY STATION, WALLMOUNTED AT +48" UON.

NURSE CALL SYSTEM TOILET STATION, WALLMOUNTED AT +30" UON. WITH PULL CORD

NURSE CALL SYSTEM SHOWER STATION, WALLMOUNTED AT +60" UON. WITH PULL CORD

NURSE CALL SYSTEM DUTY STATION, WALLMOUNTED AT +48" UON.

NURSE CALL SYSTEM STAFF STATION, WALLMOUNTED AT +48" UON.

NURSE CALL CODE BLUSE STATION, WALL MOUNTAT +48" OR MOUNT ON PATIENT HEADWALL UON.

NURSE CALL SYSTEM DOME LIGHT, WALL MOUNTED(SEE ARCH. ELEVATORS FOR EXACT LOCATION)

NURSE CALL SYSTEM DOME LIGHT, CEILING MOUNT

NURSE CALL SYSTEM CONTROL PANEL

R 6

ATS

4x AF

J

J

J

T4

a,b

Ta,b

XP - EXPLOSION PROOF

O

OCCUPANCY SENSOR, WALL MOUNTEDO

PHOTOCELL CONTROLLER, CEILING MOUNTED

PHOTOCELL CONTROLLER, WALL MOUNTED

LIGHTING CONTACTOR

TIME CLOCK

PUSH BUTTON

REMOTE CONTROL SWITCHRC

TC

LC

SURGE SUPPRESSIONSS

XP EXPLOSION PROOF

SIMPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON

QUAD RECEPTACLE WALL MOUNTED, +18" AFF, UON

SPECIAL RECEPTACLE WALL MOUNTED, +18" AFF, UON

SIMPLEX RECEPTACLE CEILING MOUNTED

DUPLEX RECEPTACLE CEILING MOUNTED

QUAD RECEPTACLE CEILING MOUNTED

SPECIAL RECEPTACLE CEILING MOUNTED

SIMPLEX RECEPTACLE FLUSH FLOOR MOUNTED

DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

QUAD RECEPTACLE FLUSH FLOOR MOUNTED

SPECIAL RECEPTACLE FLUSH FLOOR MOUNTED

JUNCTION BOX RECESSED WALL MOUNTED

JUNCTION BOX RECESSED CEILING MOUNTED

JUNCTION BOX RECESSED FLUSH FLOOR MOUNTED

LIGHTNING PROTECTION& GROUNDING

DESCRIPTIONSYMBOL- 'L' DENOTES LIGHTNING PROTECTION MAINCONDUCTOR

LIGHTING PROTECTION AIR TERMINAL

GROUND ELECTRODE CONNECTION TO EQUIPMENT

THRU ROOF PENETRATION CABLE IN CONDUIT

TRIANGULAR GROUND GRID - THREE 3/4" x10'-0" RODS SPACED 30'-0" MINIMUM APARTINTERCONNECTED WITH 4/0 COPPER CONDUCTOR.

THRU ROOF PENETRATION TO STEEL

FULL DOWNLEAD TO GROUND

STEEL COLUMN BOND TO GROUND

EXPOSED DOWNLEAD TO GROUND

2"x1/4" COPPER GROUND BUS BAR, LENGTH ASINDICATED ON PLANS.

- 'G' DENOTES COUNTERPOISE/GROUND CABLE

GROUND PLATE CONNECTION SOLID COPPER,24"x24"x20 GA.

GROUND ELECTRODE 3/4" COPPER ROD, 10'-0"DEEP - "TW" INDICATES TEST WELL

G

TW

L

PS

ES

TS

SH

DS

SS

NURSE CALL SYSTEM MASTER ANNUCIATOR STAT

CB

NCCP

MA

MISCELLANEOUSDESCRIPTIONSYMBOL

FEEDER SIZE, SEE FEEDER SCHEDULE

REFERENCE NOTE

DETAIL REFERENCE:- DETAIL DESIGNATION- SHEET NUMBER REFERENCE

EQUIPMENT REFERENCE. COORDINATE EQUIPMENTWITH MECHANICAL/PLUMBING TRADES. SEEMECHANICAL/PLUMBING DRAWINGS FOR LOCATIONS.

EF1

#

P380D

SINGLE LINE DIAGRAMDESCRIPTIONSYMBOL

PANELBOARD, SEE PANEL SCHEDULE FOR RATING.

MOLDED CASE CIRCUIT BREAKER:- 'TEXT' DENOTES CB ACCESSORIES

LOW VOLTAGE DRAW OUT CIRCUIT BREAKER:

MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER

AUTOMATIC TRANSFER SWITCH

GENERATOR

UTILITY METER

DIGITAL MULTIFUNCTION METER WITHCURRENT/POTENTIAL TRANSFORMER AS REQUIRED

ST, ET. GFP, EO, LSI TRIP FUNCTIONS- NUMERICAL DENOTES TRIP SIZE

- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

WITH INTEGRAL TRIP UNIT

LOW VOLTAGE FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES

ST, GFR, EO, LO, LOCK OUT PROVISIONS- NUMERICAL DENOTES FUSE SIZE

MEDIUM VOLTAGE DRAWOUT FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES FUSE SIZE

ENCLOSED CIRCUIT BREAKER- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

ENCLOSED SAFETY DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

ENCLOSED FUSED DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

INTERMEDIATE CLASS MOV SURGE ARRESTER- NUMERICAL DENOTES ARRESTER RATING

MOTOR

AUTOMATIC TRANSFER SWITCHW/BYPASS ISOLATION

KEY INTERLOCK

RELAY NUMERICAL INDICATES TYPE

CURRENT TRANSFORMER:- '200/5' DENOTES CT RATIO IF INDICATED

POTENTIAL TRANSFORMER:- NUMERICAL DENOTES QUANTITY OF FUSES

INVERTER

RECTIFIER

BATTERY

TRANSFORMER WITH PRIMARY ANDSECONDARY CONNECTIONSAS INDICATED ON RISER DIAGRAM.

M

A

FEEDER

BUSWAY

PANEL

1

51

BW

200/5

KI

GFPTRIP

N E

L

LSITRIP

STTRIP

STTRIP

GFP

FUSE

M VA

52

GFP

FUSE

G

M

SA

12KV

ATS-#CONNAMPS

ATS-#CONNAMPS

DIGITAL ENERGY METERM

DUPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON

X

LETTER DESIGNATION ON RECEPTACLES:A = ARC FAULT CIRCUIT INTERRUPTERG = GROUND FAULT CIRCUIT INTERRUPTERIG = ISOLATED GROUNDWP = WEATHER PROOF WITH 'GFCI'S = SAFETYCT = ABOVE COUNTERCR = CRITICALEQ = EQUIPMENTLS = LIFE SAFETY+X" = INDICATES MOUNTING HEIGHTSHADING = INDICATES RECEPTACLE ON EMERGENCY

CONDUIT AND WIRE RUN EXPOSED ON WALL ORCEILING IN FINISHED SPACE.

CONDUIT AND WIRE RUN CONCEALED IN SLAB, UNDERSLAB OR UNDERGROUND

GROUND CONNECTION

MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS MOUNTEDAGAINST AN ADJACENT WALL OR OTHERWISEREMOTE FROM THE MOTOR. SEE MOTOR EQUIPMENTSCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROLEQUIPMENT, QUANTITY OF MOTORS CONNECTED TOCONTROLLER, AND OTHER DETAILS. CONDUCTOR SIZEBETWEEN CONTROLLER AND MOTOR SHALL MATCHTHE UPSTREAM OF THE CONTROLLER UNLESS NOTEDOTHERWISE ON THE SCHEDULE.MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS EITHERINTEGRAL TO THE EQUIPMENT OR MOUNTEDDIRECTLY ONTO THE EQUIPMENT. SEE MOTOREQUIPMENT SCHEDULE(S) FOR CIRCUITING, TYPE OFCONTROL EQUIPMENT, QUANTITY OF MOTORSCONNECTED TO CONTROLLER, AND OTHER DETAILS.CONDUCTOR SIZE BETWEEN CONTROLLER ANDMOTOR SHALL MATCH THE UPSTREAM OF THECONTROLLER UNLESS NOTED OTHERWISE ON THESCHEDULE.

CB4x 225

+X"

ACCESS FLOOR BOX WITH OUTLETS AS SPECIFIED

POKE THROUGH FLOOR BOX WITH OUTLETS ASSPECIFIED

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT CAPPED

ARC FAULT CIRCUIT INTERRUPTERAFCI

RACEWAYS

FLEXIBLE CONNECTION

CONDUIT AND WIRE, HASH MARKS INDICATE NUMBEROF WIRES. # HASH MARKS INDICATES 3#12+1#10N+1#12G IN 3/4" CONDUIT UON.

P

P

E-3A

DESCRIPTION

FIRE ALARM SYMBOLSSYMBOL

FIRE SERVICE OR EMERGENCY TELEPHONEJ - JACKFTS - FIRE FIGHTER’s TELEPHONE SYSTEM

MANUAL PULL STATION

MANUAL STATIONHL - HALON

CO2 - CARBON DIOXIDE

FO - FOAMWM - WATER MISTDL - DELUGE SPRINKLERPRE - PREACTION SYSTEM

ABORT SWITCHHL - HALON

CO2 - CARBON DIOXIDECA - CLEAN AGENT

DL - DELUGE SPRINKLERPRE - PREACTION SYSTEMEPO - EMERGENCY POWER OFF

HEAT DETECTORR/F - RATE OF RISE AND FIXED TEMPERATURER/C - RATE COMPENSATIONF - FIXED TEMPERATURER - RATE OF RISE ONLY

SMOKE DETECTORP - PHOTOELECTRICBR - BEAM RECEIVERBT - BEAM TRANSMITTER

SMOKE DETECTOR FOR DUCT

SMOKE/HEAT DETECTOR

HEAT LINE-TYPE DETECTOR(HEAT SENSITIVE CABLE)

GAS DETECTOR

FLAME DETECTORF - FLAMEUV - ULTRAVIOLETUV/IR - COMBINATION ULTRAVIOLET/INFRAREDVR - VISIBLE RADIATION

ADDRESSABLE MODULEAIM - INPUTAOM - OUTPUT

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCHW - WATERLA - LOW AIRHA - HIGH AIR

LEVEL DETECTOR/SWITCH

TAMPER DETECTOR/SWITCH

VALVE TAMPER DETECTOR/SWITCH

OUTPUT RELAY

TEMPERATURE SWITCHHT - HIGH TEMPERATURELT - LOW TEMPERATURE

AUDIO DEVICE (WALL MOUNTED)H - HORNS - SPEAKER

C - CHIMEM - MINI

AUDIO DEVICE (CEILING MOUNTED)H - HORNS - SPEAKER

C - CHIME

STROBE (WALL MOUNTED)

STROBE (CEILING MOUNTED)

AUDIO/VISUAL COMBINATION (WALL MOUNTED)H - HORNS - SPEAKER

C - CHIME

AUDIO/VISUAL COMBINATION (CEILING MOUNTED)H - HORNS - SPEAKER

C - CHIME

ROTATED BEACON

BELL (WALL MOUNTED)V - VIBRATING

VS - VIBRATING/STROBEGS - GONG/STROBE

DOOR HOLDER FLOOR/DOOR

FIRE ALARM CONTROL PANEL

FIRE SYSTEM ANNUNCIATOR ALARM

AIR SAMPLING CONTROL DETECTOR PANEL

ELEVATOR STATUS/RECALL

FIRE ALARM COMMUNICATOR

HVAC CONTROL PANEL

VOICE EVACUATION PANEL

FIRE ALARM TERMINAL CABINET

FIRE ALARM TRANSPONDER

DATA GATHERING PANEL

FIRE COMMAND SYSTEM

SPRINKLER ALARM PANEL

RELAY ALARM PANEL

PURGE PANEL

FIRE ALARM CONTROL UNIT

BATTERY PACK AND CHARGER

AMPLIFIER RACK

FIRE SYSTEM CONTROL PANELHL - HALON

CO2 - CARBON DIOXIDE

DC - DRY CHEMICALWC - WET CHEMICALDL - DELUGE SPRINKLER

REMOTE TEST SWITCH

DC - DRY CHEMICALWC - WET CHEMICALCA - CLEAN AGENT

DC - DRY CHEMICALFO - FOAM WC - WET CHEMICAL

WM - WATER MIST

P - PHONE

I - IONIZATIONASD - AIR SAMPLING

IR - INFRARED

G - GONG

FO - FOAMWM - WATER MIST

T - TROUBLE

CA - CLEAN AGENT

HL

AIM

AMP

ASFP

H

H

H

H

BATT

GS

DGP

J

ESR

EVAC

FAC

FACP

FACU

FATC

FCS

F

FSA

FSCPHL

FTR

HVA

P

HL

R

PP

LA

RTS

RP

SAP

FIRE SYSTEM ANNUNCIATOR PANELFSAP

P

R

HT

F

A - ACCESSIBLE

PB

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

12" = 1'-0"

ELECTRICAL -SYMBOLS,ABBREVIATIONS, ANDDRAWING LIST

WT-1-E.0.01

PACKAGE 1

ELECTRICAL DRAWING LISTDRG NO. DRAWING TITLE SCALE

WT-1-E.0.01 ELECTRICAL - SYMBOLS, ABBREVIATIONS, AND DRAWING LIST NTSWT-1-E.2.30 ELECTRICAL - SEGMENT THREE - BASEMENT - POWER PLAN 1/8" = 1'-0"WT-1-E.4.00.1 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 1 NTSWT-1-E.4.00.2 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 2 NTSWT-1-E.7.00.1 ELECTRICAL - BASEMENT - PARTIAL PLANS 1/4" = 1'-0"

No. Date Description

Page 2: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

BB AA ABCEFJLNOPQRS.TU.VXYZ DGHKMW

28

27

26

24

22

21

20

19

18

17

16

15

14

13

12

11

10

8

7

6

5

4

3

2

1

9

23

25

USS-BA

USS-BB

BLB

BLL

BEHC

BETC

BELC

BLC

BHC

BDPC

BLK

BLH

BLG

BLA

BHA

BLJ

PC-3

PC-2

PC-1

BEHABETA

BELA

BDPA

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

1/8" = 1'-0"

ELECTRICAL -SEGMENT THREE -BASEMENT - POWERPLAN

WT-1-E.2.30

PACKAGE 1

No. Date Description

1/8" = 1'-0"1 BASEMENT - SEGMENT THREE

Page 3: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

1500KVA4160/208V

USS-BA-TX

BASEMENT

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

LEVEL 5

LEVEL 6

LEVEL 7

ROOF

200A

APS2100A MLO208/120VWPA - CULLEN

225A MLO208/120V

PC460kVA

APL2225A MLO208/120V

PC560kVA

UP2A100A MLO208/120V

4#600MCMIN 3 1/2"

BULLSWITCH

BROWN #1208V

UPS2100A

208/120V

UPS1200A

208/120V

UPL1225A

208/120V

4#600MCMIN 3 1/2"

BULLSWITCH

CULLEN #1208V

BULLSWITCH

CULLEN #2208V

UPL2A-LT225A MLO208/120V

UPL2A-RT225A MLO208/120V

WPB - CULLEN225A MLO208/120V

WPA - BROWN225A MLO208/120V

WPB - BROWN225A MLO208/120V

UPL1A225A

208/120V

RENTALSOUNDSWITCH

208V

RENTALSOUNDSWITCH

208V

UPL2225A

208/120V

CULLEN STAGE BROWN STAGE

BULLSWITCH

BROWN #2208V

BULLSWITCH

BROWN #3208V

BULLSWITCH

BROWN #4208V

RENTALSOUNDSWITCH

208V

USS-BA4000A MCB, 208/120V 3PH., 4W, 100KAIC

200A 200A 200A 200A 150A 100A150A 400A200A 100A 200A 400A 400A 200A400A 400A 200A 200A 200A 200A 60A 200A100A 2 X 400APROVISION

4 X 100APROVISION

LSIG4000A

M VA

2 X 225APROVISION

NOT IN THE SCOPE OF THIS BID

SPD 250kA

MSB, 4160V

P380

D

P380

D

P200

D

P200

D

P150

DP1

50D

P150

DP1

50DP2

00D

P70D

P110

D

P200

D

P200

D

P200

D

P200

D

P200

D

P200

D

P110

D

P380

D

P380

D

P380

D

P380

D

P200

D

P70D

P200

D

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

12" = 1'-0"

ELECTRICAL - SINGLELINE DIAGRAM -SHEET 1

WT-1-E.4.00.1

PACKAGE 1

No. Date Description

Page 4: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

MSB, 4160V

BASEMENT

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

LEVEL 5

LEVEL 6

LEVEL 7

ROOF

USS-BB4000A MCB, 208/120V 3PH., 4W, 100KAIC

1500KVA4160/208V

USS-BB-TX400A

ASS1

2LA100 MLO208/120V

1LA100 MLO208/120V

PC760kVA

D6

EMERGENCYCIRCUITS

FROM 3ELA

3LA100 MLO208/120V

APS1 APL1

PC140kVA

PC240kVA

ASL1

PC340kVA

UPL3 UPS3

P85D

P200

D

P150

D

P55D

P110

D

P110

D

P110

D

P110

D

P110

D

P150

D

P110

D

P200

D

D5

EMERGENCYCIRCUITS FEDFROM BELBREHERSAL

STORAGE NEARTO ELEC (2.B.39)E2.20

P110

D

P70D

P110

D

WAGONLIFT208V

M VA

100A 150A 150A100A 60A 50A 200A 200A 100A 200A 100A

FUTURE400A MLO208/120V

P380

D

400A

FUTURE400A MLO208/120V

P380

D

400A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A 2 X 400APROVISION

4 X 100APROVISION

2 X 225APROVISION

P200

D

200A

P200

D

200A

LOADINGDOCK

(KLIEGL)208V

LOADINGDOCK

(KLIEGL)208V

NOT IN THE SCOPE OF THIS BID

SPD

LSIG4000A

250kA

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

12" = 1'-0"

ELECTRICAL - SINGLELINE DIAGRAM -SHEET 2

WT-1-E.4.00.2

PACKAGE 1

No. Date Description

Page 5: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

V

X

Y

Z

W

24 22 21 20 19 18 172325

USS-BA

USS-BB

BELA

BEHA

PC-1 PC-2 PC-3

BLJ

BHA

BLA

BLG

(SUSPENDED)

2' - 0"

2' - 0

"

2' - 0

"

2' - 0"

REMOVABLE FLOOR SECTION.

22' - 11"

5' - 6

"9'

- 0"

2' - 0

"

TOP VIEW

FRONT VIEW

SECONDARYDISTRIBUTION SECTION120/208V 3PH., 4W.

TRANSFORMER SECTION4160V 3PH., 3W - 120/208V4PH., 4W

INCOMING SECTION4160V 3PH. 3W

TOP HAT SECTION

*NOTE: DIMENSIONS ARE PROVIDED AS MAXIMUMS FOR A FRONT ACCESS ONLY UNIT SUBSTATION.REFER TO SINGLE LINE DIAGAMS FOR ADDITIONAL INFORMATION.

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

As indicated

ELECTRICAL -BASEMENT - PARTIALPLANS

WT-1-E.7.00.1

PACKAGE 1

1/4" = 1'-0"1 Enlarged Electrical Room B80

2 Electrical Room B80 Isometric

1/8" = 1'-0"3TYPICAL UNIT SUBSTATION ELEVATIONDETAIL

No. Date Description