-- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT
BOX.CEILING MOUNTED LIGHTING FIXTURE AND OUTLET
--
LIGHTINGDESCRIPTIONSYMBOL
-- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT
WALL MOUNTED LIGHTING FIXTURE AND OUTLET
--
BOX.
CEILING/WALL EXIT LIGHT AND OUTLET BOX,LED TYPE, SELF CONTAINED, WITH BATTERY PACK:- SHADED AREA INDICATES ILLUMINATED FACE(S)- ARROW INDICATES DIRECTION
EMERGENCY UNIT EQUIPMENT, 90 MINUTEBATTERY PACK, CHARGER AND TEST SWITCH.
NOTE: SEE LIGHT FIXTURE SCHEDULE AND SPECIFICATIONSFOR COMPLETE FIXTURE DESCRIPTION.
DESCRIPTIONSYMBOL
WIRING DEVICES
LINE VOLTAGE SWITCH- LOWER CASE LETTER DENOTES SWITCHING ZONES- 'T' DENOTES SWITCH TYPE:MC - MOMENTARY CONTACTD - DIMMERWP - WEATHER PROOF
LOW VOLTAGE SWITCH
OCCUPANCY SENSOR, CEILING MOUNTED
ABBREVIATIONSDESCRIPTIONSYMBOL
L
LTG
C
A, AMP AMPERE
AMPS INTERRUPTING CAPACITYAIC
AC ALTERNATING CURRENT
ABOVE FINISHED FLOORAFF
ATC AUTOMATIC TEMPERATURE CONTROL
AUTOMATIC TRANSFER SWITCHATS
BAS BUILDING AUTOMATION SYSTEM
BUILDING MANAGEMENT SYSTEMBMS
BFG BELOW FINISHED GRADEC, CDT CONDUIT
CIRCUIT BREAKERCB
CABINET HEIGHTCH
CKT CIRCUIT
CONDUIT ONLYC.O., CO
CONFIG. CONFIGURATION
CENTERLINE
CONVENIENCECONV
CM CONSTRUCTION MANAGER
DIGITAL DATA CONTROLDDC
DWG DRAWING
ELECTRICAL CONTRACTORE.C.
ELEC ELECTRICAL
EMERGENCYEM
EMT ELECTRICAL METALLIC TUBING
ELECTRICALLY OPERATED 'ON-OFF'E.O.
EQUALEQ
EWC ELECTRIC WATER COOLER
FIRE ALARMFAFAI FURNISH AND INSTALL
FS FIRE SHUTTER/DOOR
FULL LOAD AMPSFLA
FSD FIRE SMOKE DAMPER
GROUNDG, GND
GEN GENERATOR
GROUND FAULT CIRCUIT INTERRUPTERGFCI
HC HUNG CEILING
HIGH INTENSITY DISCHARGEHID
HAND-OFF-AUTOMATICHOA
HORSE POWERHP
INSTALLED BY ELECTRICAL CONTRACTORIBEC
FURNISHED BY OTHERSFBO
ISOLATED GROUNDIGJB,J JUNCTION BOX
KILO VOLT- AMPEREKVA
KW KILO WATT
KILO WATT HOURKWH
LC
LCP
LOCK & COVER
LIGHTING CONTROL PANEL
LIGHTING
LOW VOLTAGELV
LVR LOW VOLTAGE RELAY
MOTOR CONTROL CENTERMCC
MOTOR CONTROL PANELMCP
MER MECHANICAL EQUIPMENT ROOM
MANUFACTURERMFRR
MIN MINIMUM
MAIN LUGS ONLYMLO
MSB MAIN SWITCHBOARD
MOUNTEDMTD
N NEUTRAL
NOT APPLICABLENA, N/A
NEMA NATIONAL ELECTRICAL MANUFACTURERSASSOCIATION
N.C. NORMALLY CLOSED
NOT IN CONTRACTNIC
# NUMBER
NORMALLY OPENN.O.
NTS NOT TO SCALE
ON CENTEROC
POLESP
PB PULL BOX
POWER FACTOR CORRECTIONPFC
PH, ø PHASE
PANELPNL
PVC POLYVINYL CHLORIDE
POWERPWR
RC REHEAT COIL
RECEPTACLERECPT, REC
RM ROOM
SIGNAGESG
SHT SHEET
SPECIFICATIONSSPEC
SPDT SINGLE POLE DOUBLE THROW
SINGLE POLE SINGLE THROW
SWITCH
SPST
SW
SWBD
SWGR
SWITCHBOARD
SWITCHGEAR
TIME CLOCKTC
TYP TYPICAL
UNDERGROUNDUG
UON, U.O.N. UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLYUPS
UNF UNFUSED
VOLTV
VA VOLT-AMPERES
VACUUM PRESSURE IMPREGNATIONVPI
VAPOR TIGHTVT
W WATT
WEATHER PROOFWP
XFMR TRANSFORMER
POWERDESCRIPTIONSYMBOL
SAFETY DISCONNECT SWITCH, 3 POLE UONA: 30A UNFUSED AF: 30A FUSEDB: 60A UNFUSED BF: 60A FUSEDC: 100A UNFUSED CF: 100A FUSEDD: 200A UNFUSED DF: 200A FUSEDE: 400A UNFUSED EF: 400A FUSED- '4x' DENOTES NEMA ENCLOSURE IF INDICATED
TRANSFORMER, SEE SCHEDULE FOR RATING
RELAY - NUMERAL DENOTES NUMBER OF POLES
SURFACE MOUNTED PANELBOARD
FLOOR MOUNTED DISTRIBUTION/SWITCHBOARD
CONDUIT AND WIRE HOMERUN. CONTINUOUS RUN TOMCC, PANELBOARD, SWITCHBOARD OR EQUIPMENTCABINET.
CONDUIT AND WIRE RUN IN WALL OR CEILING SPACE,OR RUN EXPOSED IN UNFINISHED SPACE.
FUSED DISCONNECT SWITCH- NUMERICAL DENOTES TRIP SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED
AUTOMATIC TRANSFER SWITCH, SEE RISERDIAGRAM FOR RATING
FLUSH MOUNTED PANELBOARD
PULLBOX
R
HOSPITALDESCRIPTIONSYMBOL
NURSE CALL SYSTEM PATIENT STATION WALLMOUNTED OR ON PATIENT HEADWALL UNIT
NURSE CALL SYSTEM EMERGENCY STATION, WALLMOUNTED AT +48" UON.
NURSE CALL SYSTEM TOILET STATION, WALLMOUNTED AT +30" UON. WITH PULL CORD
NURSE CALL SYSTEM SHOWER STATION, WALLMOUNTED AT +60" UON. WITH PULL CORD
NURSE CALL SYSTEM DUTY STATION, WALLMOUNTED AT +48" UON.
NURSE CALL SYSTEM STAFF STATION, WALLMOUNTED AT +48" UON.
NURSE CALL CODE BLUSE STATION, WALL MOUNTAT +48" OR MOUNT ON PATIENT HEADWALL UON.
NURSE CALL SYSTEM DOME LIGHT, WALL MOUNTED(SEE ARCH. ELEVATORS FOR EXACT LOCATION)
NURSE CALL SYSTEM DOME LIGHT, CEILING MOUNT
NURSE CALL SYSTEM CONTROL PANEL
R 6
ATS
4x AF
J
J
J
T4
a,b
Ta,b
XP - EXPLOSION PROOF
O
OCCUPANCY SENSOR, WALL MOUNTEDO
PHOTOCELL CONTROLLER, CEILING MOUNTED
PHOTOCELL CONTROLLER, WALL MOUNTED
LIGHTING CONTACTOR
TIME CLOCK
PUSH BUTTON
REMOTE CONTROL SWITCHRC
TC
LC
SURGE SUPPRESSIONSS
XP EXPLOSION PROOF
SIMPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON
QUAD RECEPTACLE WALL MOUNTED, +18" AFF, UON
SPECIAL RECEPTACLE WALL MOUNTED, +18" AFF, UON
SIMPLEX RECEPTACLE CEILING MOUNTED
DUPLEX RECEPTACLE CEILING MOUNTED
QUAD RECEPTACLE CEILING MOUNTED
SPECIAL RECEPTACLE CEILING MOUNTED
SIMPLEX RECEPTACLE FLUSH FLOOR MOUNTED
DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED
QUAD RECEPTACLE FLUSH FLOOR MOUNTED
SPECIAL RECEPTACLE FLUSH FLOOR MOUNTED
JUNCTION BOX RECESSED WALL MOUNTED
JUNCTION BOX RECESSED CEILING MOUNTED
JUNCTION BOX RECESSED FLUSH FLOOR MOUNTED
LIGHTNING PROTECTION& GROUNDING
DESCRIPTIONSYMBOL- 'L' DENOTES LIGHTNING PROTECTION MAINCONDUCTOR
LIGHTING PROTECTION AIR TERMINAL
GROUND ELECTRODE CONNECTION TO EQUIPMENT
THRU ROOF PENETRATION CABLE IN CONDUIT
TRIANGULAR GROUND GRID - THREE 3/4" x10'-0" RODS SPACED 30'-0" MINIMUM APARTINTERCONNECTED WITH 4/0 COPPER CONDUCTOR.
THRU ROOF PENETRATION TO STEEL
FULL DOWNLEAD TO GROUND
STEEL COLUMN BOND TO GROUND
EXPOSED DOWNLEAD TO GROUND
2"x1/4" COPPER GROUND BUS BAR, LENGTH ASINDICATED ON PLANS.
- 'G' DENOTES COUNTERPOISE/GROUND CABLE
GROUND PLATE CONNECTION SOLID COPPER,24"x24"x20 GA.
GROUND ELECTRODE 3/4" COPPER ROD, 10'-0"DEEP - "TW" INDICATES TEST WELL
G
TW
L
PS
ES
TS
SH
DS
SS
NURSE CALL SYSTEM MASTER ANNUCIATOR STAT
CB
NCCP
MA
MISCELLANEOUSDESCRIPTIONSYMBOL
FEEDER SIZE, SEE FEEDER SCHEDULE
REFERENCE NOTE
DETAIL REFERENCE:- DETAIL DESIGNATION- SHEET NUMBER REFERENCE
EQUIPMENT REFERENCE. COORDINATE EQUIPMENTWITH MECHANICAL/PLUMBING TRADES. SEEMECHANICAL/PLUMBING DRAWINGS FOR LOCATIONS.
EF1
#
P380D
SINGLE LINE DIAGRAMDESCRIPTIONSYMBOL
PANELBOARD, SEE PANEL SCHEDULE FOR RATING.
MOLDED CASE CIRCUIT BREAKER:- 'TEXT' DENOTES CB ACCESSORIES
LOW VOLTAGE DRAW OUT CIRCUIT BREAKER:
MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER
AUTOMATIC TRANSFER SWITCH
GENERATOR
UTILITY METER
DIGITAL MULTIFUNCTION METER WITHCURRENT/POTENTIAL TRANSFORMER AS REQUIRED
ST, ET. GFP, EO, LSI TRIP FUNCTIONS- NUMERICAL DENOTES TRIP SIZE
- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE
WITH INTEGRAL TRIP UNIT
LOW VOLTAGE FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES
ST, GFR, EO, LO, LOCK OUT PROVISIONS- NUMERICAL DENOTES FUSE SIZE
MEDIUM VOLTAGE DRAWOUT FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES FUSE SIZE
ENCLOSED CIRCUIT BREAKER- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE
ENCLOSED SAFETY DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE
ENCLOSED FUSED DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE
INTERMEDIATE CLASS MOV SURGE ARRESTER- NUMERICAL DENOTES ARRESTER RATING
MOTOR
AUTOMATIC TRANSFER SWITCHW/BYPASS ISOLATION
KEY INTERLOCK
RELAY NUMERICAL INDICATES TYPE
CURRENT TRANSFORMER:- '200/5' DENOTES CT RATIO IF INDICATED
POTENTIAL TRANSFORMER:- NUMERICAL DENOTES QUANTITY OF FUSES
INVERTER
RECTIFIER
BATTERY
TRANSFORMER WITH PRIMARY ANDSECONDARY CONNECTIONSAS INDICATED ON RISER DIAGRAM.
M
A
FEEDER
BUSWAY
PANEL
1
51
BW
200/5
KI
GFPTRIP
N E
L
LSITRIP
STTRIP
STTRIP
GFP
FUSE
M VA
52
GFP
FUSE
G
M
SA
12KV
ATS-#CONNAMPS
ATS-#CONNAMPS
DIGITAL ENERGY METERM
DUPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON
X
LETTER DESIGNATION ON RECEPTACLES:A = ARC FAULT CIRCUIT INTERRUPTERG = GROUND FAULT CIRCUIT INTERRUPTERIG = ISOLATED GROUNDWP = WEATHER PROOF WITH 'GFCI'S = SAFETYCT = ABOVE COUNTERCR = CRITICALEQ = EQUIPMENTLS = LIFE SAFETY+X" = INDICATES MOUNTING HEIGHTSHADING = INDICATES RECEPTACLE ON EMERGENCY
CONDUIT AND WIRE RUN EXPOSED ON WALL ORCEILING IN FINISHED SPACE.
CONDUIT AND WIRE RUN CONCEALED IN SLAB, UNDERSLAB OR UNDERGROUND
GROUND CONNECTION
MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS MOUNTEDAGAINST AN ADJACENT WALL OR OTHERWISEREMOTE FROM THE MOTOR. SEE MOTOR EQUIPMENTSCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROLEQUIPMENT, QUANTITY OF MOTORS CONNECTED TOCONTROLLER, AND OTHER DETAILS. CONDUCTOR SIZEBETWEEN CONTROLLER AND MOTOR SHALL MATCHTHE UPSTREAM OF THE CONTROLLER UNLESS NOTEDOTHERWISE ON THE SCHEDULE.MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS EITHERINTEGRAL TO THE EQUIPMENT OR MOUNTEDDIRECTLY ONTO THE EQUIPMENT. SEE MOTOREQUIPMENT SCHEDULE(S) FOR CIRCUITING, TYPE OFCONTROL EQUIPMENT, QUANTITY OF MOTORSCONNECTED TO CONTROLLER, AND OTHER DETAILS.CONDUCTOR SIZE BETWEEN CONTROLLER ANDMOTOR SHALL MATCH THE UPSTREAM OF THECONTROLLER UNLESS NOTED OTHERWISE ON THESCHEDULE.
CB4x 225
+X"
ACCESS FLOOR BOX WITH OUTLETS AS SPECIFIED
POKE THROUGH FLOOR BOX WITH OUTLETS ASSPECIFIED
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT CAPPED
ARC FAULT CIRCUIT INTERRUPTERAFCI
RACEWAYS
FLEXIBLE CONNECTION
CONDUIT AND WIRE, HASH MARKS INDICATE NUMBEROF WIRES. # HASH MARKS INDICATES 3#12+1#10N+1#12G IN 3/4" CONDUIT UON.
P
P
E-3A
DESCRIPTION
FIRE ALARM SYMBOLSSYMBOL
FIRE SERVICE OR EMERGENCY TELEPHONEJ - JACKFTS - FIRE FIGHTER’s TELEPHONE SYSTEM
MANUAL PULL STATION
MANUAL STATIONHL - HALON
CO2 - CARBON DIOXIDE
FO - FOAMWM - WATER MISTDL - DELUGE SPRINKLERPRE - PREACTION SYSTEM
ABORT SWITCHHL - HALON
CO2 - CARBON DIOXIDECA - CLEAN AGENT
DL - DELUGE SPRINKLERPRE - PREACTION SYSTEMEPO - EMERGENCY POWER OFF
HEAT DETECTORR/F - RATE OF RISE AND FIXED TEMPERATURER/C - RATE COMPENSATIONF - FIXED TEMPERATURER - RATE OF RISE ONLY
SMOKE DETECTORP - PHOTOELECTRICBR - BEAM RECEIVERBT - BEAM TRANSMITTER
SMOKE DETECTOR FOR DUCT
SMOKE/HEAT DETECTOR
HEAT LINE-TYPE DETECTOR(HEAT SENSITIVE CABLE)
GAS DETECTOR
FLAME DETECTORF - FLAMEUV - ULTRAVIOLETUV/IR - COMBINATION ULTRAVIOLET/INFRAREDVR - VISIBLE RADIATION
ADDRESSABLE MODULEAIM - INPUTAOM - OUTPUT
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCHW - WATERLA - LOW AIRHA - HIGH AIR
LEVEL DETECTOR/SWITCH
TAMPER DETECTOR/SWITCH
VALVE TAMPER DETECTOR/SWITCH
OUTPUT RELAY
TEMPERATURE SWITCHHT - HIGH TEMPERATURELT - LOW TEMPERATURE
AUDIO DEVICE (WALL MOUNTED)H - HORNS - SPEAKER
C - CHIMEM - MINI
AUDIO DEVICE (CEILING MOUNTED)H - HORNS - SPEAKER
C - CHIME
STROBE (WALL MOUNTED)
STROBE (CEILING MOUNTED)
AUDIO/VISUAL COMBINATION (WALL MOUNTED)H - HORNS - SPEAKER
C - CHIME
AUDIO/VISUAL COMBINATION (CEILING MOUNTED)H - HORNS - SPEAKER
C - CHIME
ROTATED BEACON
BELL (WALL MOUNTED)V - VIBRATING
VS - VIBRATING/STROBEGS - GONG/STROBE
DOOR HOLDER FLOOR/DOOR
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
AIR SAMPLING CONTROL DETECTOR PANEL
ELEVATOR STATUS/RECALL
FIRE ALARM COMMUNICATOR
HVAC CONTROL PANEL
VOICE EVACUATION PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER
DATA GATHERING PANEL
FIRE COMMAND SYSTEM
SPRINKLER ALARM PANEL
RELAY ALARM PANEL
PURGE PANEL
FIRE ALARM CONTROL UNIT
BATTERY PACK AND CHARGER
AMPLIFIER RACK
FIRE SYSTEM CONTROL PANELHL - HALON
CO2 - CARBON DIOXIDE
DC - DRY CHEMICALWC - WET CHEMICALDL - DELUGE SPRINKLER
REMOTE TEST SWITCH
DC - DRY CHEMICALWC - WET CHEMICALCA - CLEAN AGENT
DC - DRY CHEMICALFO - FOAM WC - WET CHEMICAL
WM - WATER MIST
P - PHONE
I - IONIZATIONASD - AIR SAMPLING
IR - INFRARED
G - GONG
FO - FOAMWM - WATER MIST
T - TROUBLE
CA - CLEAN AGENT
HL
AIM
AMP
ASFP
H
H
H
H
BATT
GS
DGP
J
ESR
EVAC
FAC
FACP
FACU
FATC
FCS
F
FSA
FSCPHL
FTR
HVA
P
HL
R
PP
LA
RTS
RP
SAP
FIRE SYSTEM ANNUNCIATOR PANELFSAP
P
R
HT
F
A - ACCESSIBLE
PB
PLAN NORTH
Project Team
WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002
Scale:
© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.
3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692
ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Date:Project Name: HFR 12/27/2017
Issue for Bid
701 Avenida de las AmericasHouston, TX 77010
CIVIL ENGINEERMartinez MooreContact: TBDt: TBD
MEP ENGINEERArupContact: Tom Smitht: 713.343.1472
PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD
ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD
Key Plan
Revisions
01-12-2018
12" = 1'-0"
ELECTRICAL -SYMBOLS,ABBREVIATIONS, ANDDRAWING LIST
WT-1-E.0.01
PACKAGE 1
ELECTRICAL DRAWING LISTDRG NO. DRAWING TITLE SCALE
WT-1-E.0.01 ELECTRICAL - SYMBOLS, ABBREVIATIONS, AND DRAWING LIST NTSWT-1-E.2.30 ELECTRICAL - SEGMENT THREE - BASEMENT - POWER PLAN 1/8" = 1'-0"WT-1-E.4.00.1 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 1 NTSWT-1-E.4.00.2 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 2 NTSWT-1-E.7.00.1 ELECTRICAL - BASEMENT - PARTIAL PLANS 1/4" = 1'-0"
No. Date Description
BB AA ABCEFJLNOPQRS.TU.VXYZ DGHKMW
28
27
26
24
22
21
20
19
18
17
16
15
14
13
12
11
10
8
7
6
5
4
3
2
1
9
23
25
USS-BA
USS-BB
BLB
BLL
BEHC
BETC
BELC
BLC
BHC
BDPC
BLK
BLH
BLG
BLA
BHA
BLJ
PC-3
PC-2
PC-1
BEHABETA
BELA
BDPA
PLAN NORTH
Project Team
WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002
Scale:
© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.
3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692
ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Date:Project Name: HFR 12/27/2017
Issue for Bid
701 Avenida de las AmericasHouston, TX 77010
CIVIL ENGINEERMartinez MooreContact: TBDt: TBD
MEP ENGINEERArupContact: Tom Smitht: 713.343.1472
PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD
ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD
Key Plan
Revisions
01-12-2018
1/8" = 1'-0"
ELECTRICAL -SEGMENT THREE -BASEMENT - POWERPLAN
WT-1-E.2.30
PACKAGE 1
No. Date Description
1/8" = 1'-0"1 BASEMENT - SEGMENT THREE
1500KVA4160/208V
USS-BA-TX
BASEMENT
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
LEVEL 6
LEVEL 7
ROOF
200A
APS2100A MLO208/120VWPA - CULLEN
225A MLO208/120V
PC460kVA
APL2225A MLO208/120V
PC560kVA
UP2A100A MLO208/120V
4#600MCMIN 3 1/2"
BULLSWITCH
BROWN #1208V
UPS2100A
208/120V
UPS1200A
208/120V
UPL1225A
208/120V
4#600MCMIN 3 1/2"
BULLSWITCH
CULLEN #1208V
BULLSWITCH
CULLEN #2208V
UPL2A-LT225A MLO208/120V
UPL2A-RT225A MLO208/120V
WPB - CULLEN225A MLO208/120V
WPA - BROWN225A MLO208/120V
WPB - BROWN225A MLO208/120V
UPL1A225A
208/120V
RENTALSOUNDSWITCH
208V
RENTALSOUNDSWITCH
208V
UPL2225A
208/120V
CULLEN STAGE BROWN STAGE
BULLSWITCH
BROWN #2208V
BULLSWITCH
BROWN #3208V
BULLSWITCH
BROWN #4208V
RENTALSOUNDSWITCH
208V
USS-BA4000A MCB, 208/120V 3PH., 4W, 100KAIC
200A 200A 200A 200A 150A 100A150A 400A200A 100A 200A 400A 400A 200A400A 400A 200A 200A 200A 200A 60A 200A100A 2 X 400APROVISION
4 X 100APROVISION
LSIG4000A
M VA
2 X 225APROVISION
NOT IN THE SCOPE OF THIS BID
SPD 250kA
MSB, 4160V
P380
D
P380
D
P200
D
P200
D
P150
DP1
50D
P150
DP1
50DP2
00D
P70D
P110
D
P200
D
P200
D
P200
D
P200
D
P200
D
P200
D
P110
D
P380
D
P380
D
P380
D
P380
D
P200
D
P70D
P200
D
PLAN NORTH
Project Team
WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002
Scale:
© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.
3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692
ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Date:Project Name: HFR 12/27/2017
Issue for Bid
701 Avenida de las AmericasHouston, TX 77010
CIVIL ENGINEERMartinez MooreContact: TBDt: TBD
MEP ENGINEERArupContact: Tom Smitht: 713.343.1472
PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD
ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD
Key Plan
Revisions
01-12-2018
12" = 1'-0"
ELECTRICAL - SINGLELINE DIAGRAM -SHEET 1
WT-1-E.4.00.1
PACKAGE 1
No. Date Description
MSB, 4160V
BASEMENT
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
LEVEL 5
LEVEL 6
LEVEL 7
ROOF
USS-BB4000A MCB, 208/120V 3PH., 4W, 100KAIC
1500KVA4160/208V
USS-BB-TX400A
ASS1
2LA100 MLO208/120V
1LA100 MLO208/120V
PC760kVA
D6
EMERGENCYCIRCUITS
FROM 3ELA
3LA100 MLO208/120V
APS1 APL1
PC140kVA
PC240kVA
ASL1
PC340kVA
UPL3 UPS3
P85D
P200
D
P150
D
P55D
P110
D
P110
D
P110
D
P110
D
P110
D
P150
D
P110
D
P200
D
D5
EMERGENCYCIRCUITS FEDFROM BELBREHERSAL
STORAGE NEARTO ELEC (2.B.39)E2.20
P110
D
P70D
P110
D
WAGONLIFT208V
M VA
100A 150A 150A100A 60A 50A 200A 200A 100A 200A 100A
FUTURE400A MLO208/120V
P380
D
400A
FUTURE400A MLO208/120V
P380
D
400A
FUTURE225A MLO208/120V
P230
D
225A
FUTURE225A MLO208/120V
P230
D
225A
FUTURE225A MLO208/120V
P230
D
225A
FUTURE225A MLO208/120V
P230
D
225A
FUTURE225A MLO208/120V
P230
D
225A 2 X 400APROVISION
4 X 100APROVISION
2 X 225APROVISION
P200
D
200A
P200
D
200A
LOADINGDOCK
(KLIEGL)208V
LOADINGDOCK
(KLIEGL)208V
NOT IN THE SCOPE OF THIS BID
SPD
LSIG4000A
250kA
PLAN NORTH
Project Team
WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002
Scale:
© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.
3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692
ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Date:Project Name: HFR 12/27/2017
Issue for Bid
701 Avenida de las AmericasHouston, TX 77010
CIVIL ENGINEERMartinez MooreContact: TBDt: TBD
MEP ENGINEERArupContact: Tom Smitht: 713.343.1472
PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD
ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD
Key Plan
Revisions
01-12-2018
12" = 1'-0"
ELECTRICAL - SINGLELINE DIAGRAM -SHEET 2
WT-1-E.4.00.2
PACKAGE 1
No. Date Description
V
X
Y
Z
W
24 22 21 20 19 18 172325
USS-BA
USS-BB
BELA
BEHA
PC-1 PC-2 PC-3
BLJ
BHA
BLA
BLG
(SUSPENDED)
2' - 0"
2' - 0
"
2' - 0
"
2' - 0"
REMOVABLE FLOOR SECTION.
22' - 11"
5' - 6
"9'
- 0"
2' - 0
"
TOP VIEW
FRONT VIEW
SECONDARYDISTRIBUTION SECTION120/208V 3PH., 4W.
TRANSFORMER SECTION4160V 3PH., 3W - 120/208V4PH., 4W
INCOMING SECTION4160V 3PH. 3W
TOP HAT SECTION
*NOTE: DIMENSIONS ARE PROVIDED AS MAXIMUMS FOR A FRONT ACCESS ONLY UNIT SUBSTATION.REFER TO SINGLE LINE DIAGAMS FOR ADDITIONAL INFORMATION.
Project Team
WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002
Scale:
© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.
3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692
ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Date:Project Name: HFR 12/27/2017
Issue for Bid
701 Avenida de las AmericasHouston, TX 77010
CIVIL ENGINEERMartinez MooreContact: TBDt: TBD
MEP ENGINEERArupContact: Tom Smitht: 713.343.1472
PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD
ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD
Key Plan
Revisions
01-12-2018
As indicated
ELECTRICAL -BASEMENT - PARTIALPLANS
WT-1-E.7.00.1
PACKAGE 1
1/4" = 1'-0"1 Enlarged Electrical Room B80
2 Electrical Room B80 Isometric
1/8" = 1'-0"3TYPICAL UNIT SUBSTATION ELEVATIONDETAIL
No. Date Description