38CKC018–06050 Hertz
Wiring Diagrams
Fig. 1—38CKC018, 024, 036230v, 1 Phase, 50 Hertz
A96164
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT CONTACTOR
CAP CAPACITOR (DUAL RUN)
*CH CRANKCASE HEATER
COMP COMPRESSOR 320668-101 REV. C
*CH
RED or BLK
CONTBLK
YELYEL
COMP
BLK
BLU CAP
YEL
BLUBLU
YEL*ST
BRN
*SR
*SCOFM
BRN
BRNBLK
BLK
230 1ØPOWERSUPPLY
GNDEQUIP
+t
A1
A2 11 21
13 23
H
C
F
YEL
VIOBLU
(NOTE #14)
(NOTE #9)
(NOTE #8)
YEL
*LPS
YEL
*CTD
*DTS*HPS
INDOOR BLOWER MOTOR
EXTERNALPOWERSUPPLY
24 V
(NOTE #3)
INDOOR THERMOSTAT(NOTE #5)
RGY
BRN
BLKBLU BLKBLU
*LLS
BLUBLU
BLKBLK
LOGICT1 T3
T2
1 2
5
CONT
A1
11 21
*CH
EQUIPGND
*SR
*SC
H
COMP
*ST
C
F
CAP
OFM
CONT
23 13
A2
5 2
1
S
CR
*LPS
*CTD
*DTS*HPS
*LLS
IFR
THERMOSTATINDOOR
Y
G
RCR
EXTERNAL POWER SUPPLY 24 V
CR
(NOTE #14)
+t
LOGICT1 T3
T2
CONT
IFR
1. Symbols are electrical representation only.2. Compressor and fan motor furnished with inherent thermal protection.3. To be wired in accordance with National Electric N.E.C. and local codes.4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.5. Use copper conductors only. Use conductors suitable for at least 75°C (167°F).6. Connection for typical cooling only thermostat. For other arrangements, see installation instructions.7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN lead.8. When start relay and start capacitor are installed, start thermistor is not used.9. CH not used on all units.10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire.11. Check all electrical connections inside control box for tightness.12. Do not attempt to operate unit until service valves have been opened.13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between
high and low side before starting.14. Wire not present if HPS, LPS, DTS or CTD are used.
-LEGEND- -NOTES-
1. Compressor damage may occur if system is overcharged.2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The
charge is adequate for most systems using matched coils and tubing not over 15 feet long. The bestperformance will be achieved when the unit operates with a suction gas superheat at the compressorinlet of 5 °F at normal rating conditions of the air conditioning and refrigeration institute (ARI). Thischart may be used to approximate the charge if ARI rating conditions cannot be obtained. ARI ratingconditions are equivalent to DOE test "A" conditions. See product data literature for required indoor airflow rates and for use of line lengths over 15 Ft.
3. Carefully relieve refrigerant pressure within this unit before final disposal.
CAUTION
CONNECTION DIAGRAM SCHEMATIC DIAGRAM (LADDER FORM)
SCR
RED or BLK
*CTD COMPRESSOR TIME DELAY
*DTS DISCHARGE TEMP. SWITCH
*HPS HIGH PRESSURE SWITCH
IFR INDOOR FAN RELAY
*LLS LIQ. LINE SOLENOID VALVE
*LPS LOW PRESSURE SWITCH
OFM OUTDOOR FAN MOTOR
*SC START CAPACITOR
*SR START RELAY
*ST START THERMISTOR
* MAY BE FACTORY OR FIELD INSTALLED.
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Book 1 4Tab 3a 2a
PC 101 Catalog No. 003-844 Printed in U.S.A. Form 38CKC-C3W Pg 1 5-99 Replaces: 38CKC-C2W
Fig. 2—38CKC036, 048, 060400v, 3 Phase, 50 Hertz
A99095
NOTES:
-LEGEND-
1. SYMBOLS ARE ELECTRICAL REPRESENTATIONONLY.
2. COMPRESSOR AND FAN MOTOR FURNISHED WITHINHERENT THERMAL PROTECTION.
3. TO BE WIRED IN ACCORDANCE WITH NATIONALELECTRIC N.E.C. AND LOCAL CODES.
4. N.E.C. CLASS 2, 24 V CIRCUIT, MIN. 40 VA REQUIRED,60 VA ON UNITS INSTALLED WITH LLS.
5. USE COPPER CONDUCTORS ONLY. USECONDUCTORS SUITABLE FOR AT LEAST 75°C (167°F).
6. TYPICAL COOLING ONLY THERMOSTAT, FOR OTHERARRANGEMENTS SEE INSTALLATION INSTRUCTIONS.
7. IF INDOOR SECTION HAS A TRANSFORMER WITH AGROUNDED SECONDARY, CONNECT THEGROUNDED SIDE TO THE BRN LEAD.
8. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED MUSTBE REPLACED, USE THE SAME OR EQUIVALENTWIRE.
9. CHECK ALL ELECTRICAL CONNECTIONS INSIDECONTROL BOX FOR TIGHTNESS.
10. DO NOT ATTEMPT TO OPERATE UNIT UNTIL SERVICEVALVES HAVE BEEN OPENED.
11. DO NOT RAPID CYCLE COMPRESSOR. COMPRESSORMUST BE OFF 3 MINUTES TO ALLOW PRESSURES TOEQUALIZE BETWEEN HIGH AND LOW SIDE BEFORESTARTING.
12. IT IS IMPERATIVE TO CONNECT 3Ø FIELD POWER TOUNIT WITH CORRECT PHASING. WRONG PHASINGWILL CAUSE REVERSE ROTATION OF SCROLLCOMPRESSOR WHICH WILL RESULT IN REDUCEDCURRENT DRAW, ELEVATED NOISE LEVEL ANDIMPROPER OPERATION. IF ROTATION IS REVERSED,SIMPLY INTERCHANGE ANY TWO OF THE THREEPOWER CONNECTIONS ON FIELD SIDE.
1. Compressor damage may occur if system is over charged.2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The charge is adequate for
most systems using matched coils and tubing not over 15 feet long. The best performance will be achieved when the unitoperates with a suction gas superheat at the compressor inlet of 5°F. at normal rating conditions of the Air Conditioning andRefrigeration Institute (ARI). This chart may be to approximate the charge if ARI rating conditions cannot be obtained. ARIrating conditions are equivalent to DOE test "A" conditions. See product data literature for required indoor air flowrates and for use of line lengths over 15 ft.
3. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open alflow-control devices, including solenoid valves.
CAUTION
325512-101 REV. A
SCHEMATIC DIAGRAM (LADDER FORM)
CONNECTIONDIAGRAM
CONT
OFMBRN
BLK
400 3ØPOWERSUPPLY
GNDEQUIP
A1
A2
12 22
13 23
VIO
*LPS
YEL
CTD
*HPS
INDOOR BLOWER MOTOR
EXTERNALPOWERSUPPLY
24 V
(NOTES #3 & #6)
INDOOR THERMOSTAT(NOTE #5)
RGY
BRN
BLU YELBLU
*LLS
BLKBLK
LOGICT1 T3
T2
CONT
A1
11 21
*CH
EQUIPGND
OFM CONT
23 13
A2
*LPS
CTD
*HPS
*LLS
IFR
THERMOSTATINDOOR
Y
G
RCR
EXTERNAL POWER SUPPLY 24 V
CR
LOGICT1 T3
T2
ALERT !SEE NOTE #12
11 21A3
T2T1
T3
BLK
YELYEL
BLU
BLK
YEL
CAP
COMP
RED or BLK
RED or BLK*CH
BLU
IFR
COMP
CAP
22 12A3
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONT CONTACTOR
CAP CAPACITOR (DUAL RUN)
*CH CRANKCASE HEATER
COMP COMPRESSOR
*CTD COMPRESSOR TIME DELAY
IDF INDOOR FAN
*HPS HIGH PRESSURE SWITCH
IFR INDOOR FAN RELAY
*LLS LIQ. LINE SOLENOID VALVE
*LPS LOW PRESSURE SWITCH
OFM OUTDOOR FAN MOTOR
* MAY BE FACTORY OR FIELD INSTALLED.
CONT
CONT
BRN
T2T1
T3
!
Copyright 1999 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 38ckcc3w
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Book 1 4Tab 3a 2a
PC 101 Catalog No. 003-844 Printed in U.S.A. Form 38CKC-C3W Pg 2 5-99 Replaces: 38CKC-C2W