Programmable Controller

PLC Board

Controlador Programable

Tarjeta PLCControlador Programvel

Carto PLC

Users guide Guia del usuario Manual do usurio

MANUAL PLC1.01 BOARDPROGRAMMABLE IN LADDER LANGUAGE BY WLP SOFTWARE

04/2004

PLC1 Software: V1.4X WLP Software: V3.4X 0899.4794 E/2

Summary of Revisions

The table below describes all revisions made to this manual.Revision 1 Description First Edition Section -

Summary1 2 Quick Parameter Reference ......................................................... 07 Fault Messages ........................................................................... 26

CHAPTER 1

IntroductionCHAPTER 2

Safety NoticesCHAPTER 3

General InformationCHAPTER

4 5 6

General Characteristics of the PLC1CHAPTER

Connector DescriptionCHAPTER

Configuration of the CFW-09 Converter with PLC BoardCHAPTER

7 8 9

Board Installation into the ConverterCHAPTER

Detailed Parameter DescriptionCHAPTER

WLPCHAPTER

10 11

WLP BlocksCHAPTER

RTU - Modbus Protocol in the PLC1

PLC - QUCIK PARAMETER REFERENCE

QUICK PARAMETER REFERENCE, FAULT MESSAGES Software: V1.4X Application: Model: Serial Number: Responsible: Date: /

/

.

The parameter range starts from 750 up to 899, totalizing 150 parameters. The first 50 parameters are predefined by the system or are reserved parameters. The 100 remaining parameters are for general use and may be set by the user. Please find below a description of the parameters defined by the system.

1. PARAMETERSParameter P750 P751 P752 (*) P753 (*) P754 P755 Function PLC1 firmware version Scan cycle in 100s units Resets the retentive markers Loads factory settings , if =1234 Position reference (rotations) Position reference (fraction of rotation) Position signal 0 = negative 1 = positive Real position (rotations) Real position (fraction of rot.) Kp: proportional position gain Ki: Integral position gain Max. lag error Disables user program if =1 PLC address at netwrok Adjustable Range Read Read 0...1 0..65535 Read Read 0 0 rot degrees / 10 x100s Factory Setting Unit Page

P756 P757 P758 P760 P761 P762 P763 P764 (*)

Read Read Read 0...200 0...200 0...65535 0...1 1...247 1 = 1200bps 2 = 2400bps 3 = 4800bps 4 = 9600bps 5 = 19200bps Read 0...10000 0...65535 0...3599 50 0 0 0 1 rot degrees / 10

degrees / 10

P765 (*)

Baud rate of RS232

4 bits/second

P766 P767 (*) P768 (*) P769 (*)

Status of the Digital Inputs Synchronou speed of the motor in RPM Encoder pulse number Encoder zero pulse position

1800 1024 0

RPM ppr degrees / 10

(*) IMPORTANT: to enable the system to operate according the parameter seeting, the system must be reset after one or more parameters have been changed.

4

PLC - QUCIK PARAMETER REFERENCE

Parameter

Function

Adjustable Range 0=1Mbit/s 1=Reserved 2=500 Kbit/s

Factory Setting

Unit

Page

P772

CAN Baudrate

3=250 Kbit/s 4=125 Kbit/s 5=100 Kbit/s 6=50 Kbit/s 7=20 Kbit/s 8=10 Kbit/s

0

bits/second

P773 P775 P776 P777 P778

Bus off recovery CAN Status Counter of received telegrams Counter of trasmitted telegrams Counter of detected erros

0=Manual 1=Automatic Read Read Read

Read

5

PLC - QUCIK PARAMETER REFERENCE

2. Error Messages

Display

Description

Note

E50 E51

Lag error Error during program saving Two or more movements enabled simultaneously Movement data are not valid

Fatal Error, it disables the converter. Refer to Parameter P762. Reset the systems and try again. Check the user program logic

E52

E53 E54

E55

E56 E57

E58

E61

Perhaps some speed, acceleration value, etc. was reset to zero. Attempt to execute some movement Inverter disabled with disabled inverter Incompatible program Check program and install it again. or out of memory This error also occurs when there is limits no program installed in the PLC (PLC powered-up first time). Wrong CRC Transmit it again. Shaft has not been Before an absolut movement , referenced to absolute you must set the machine movement movement to zero position. Fatal Error: after enabled initial Master Reference communication, between master and Fault slave, by any cause has been disabled. Bus off has been detected on the CAN bus due to a high number of transfer Bus off erros. These erros may be caused due to bus problems or due to improper installation.

Note: In fatal erros, E50 and E58, the inverter is disabled and need restart.

6

CHAPTER

1

INTRODUCTIONThe PLC1 board adds important PLC (Programmable Logical Controller) functions to the CFW-09, enabling the execution of complex linkage program by using the digital board inputs and outputs as well as the digital and analog inputs and outputs of the own inverter which can be accessed by the users program. Among the several available functions we can mention simple contacts and coils up to functions that uses floating point, such as sum, subtraction, multiplication, division, trigonometry, square root functions, etc. Other important functions are the PID blocks, high-pass and low-pass filters, saturation, comparison. All these functions operate with floating point. Besides the functions mentioned above, the PLC1 provides blocks for motor speed and motor position control, that is a trapezoidal-profile positioning and a S-profile positioning, speed reference generation with trapezoidal acceleration ramp, etc. (Note: when positioning functions used, the coupling of an encoder on motor shaft is required). All functions can interact with the user through the 100 programmable parameters that can be acessed directly through the inverter HMI. The texts and user units of the programmable parameters can be customized by the WLP.

ATTENTION!The CFW-09 inverter software version should be the version V2.40 or later.

7

CHAPTER

2

SAFETY NOTICESThis Manual contains all necessary information for the correct installation and operation of the PLC1 with the CFW-09 Variable Frequency Drive. The PLC1 Manual has been written for qualified personnel with suitable training of technical qualifications to operate this type of equipment Only qualified personnel should plan or implement the installation, startup, operation and maintenance of the CFW-09 and associated equipment. The personnel must follow all safety instructions included in this Manual and/or defined by the local regulations. Failure to comply with these instructions may result in personnel injury and/or equipmrnt damage.

NOTE!In this Manual, qualified personnel are defined as people that are trained to: 1. Install, ground, power up and operate the CFW-09, as well as the PLC1 board, according to this Manual and the local safety procedures; 2. Use the safety equipment according to the local regulations; 3. Give first aid.

DANGER!Always disconnect the supply voltage before touching any electrical component inside the inverter. Many components are charged with high voltages, even after the incoming AC power supply has been disconnected or switched OFF. Wait at least 10 minutes for the total discharge of the power capacitors. Always connect the frame of the equipment to the ground (PE) at the suitable connection point.

ATTENTION!All electronic boards have components that are sensitive to electrostatic discharges. Never touch any of the electrical components or connectors without following proper grounding procedures. If necessary to do so, touch the properly grounded metallic frame or use a suitable ground strap.

NOTE!Read this entire Manual carefully and completely before installing or operating PLC1 board with the CFW-09.

8

CHAPTER

3

GENERAL INFORMATIONThis chapter defines the contents and purpose of this manual

3.1

ABOUT THIS MANUAL

This manual describes the basic procedures required for the WLP installation, the creation of projects and provides a general view on the block existing in the PLC1. Chapter 1- Introduction Chapter 2 - Safety Notices; Chapter 3 -General Information; Chapter 4 - General characteristics of the PLC1; Chapter 5 -Description of the Connectors; Chapter 6 - Configuration of the CFW-09 converter with PLC board; Chapter 7 - Installation of the board into the converter; Chapter 8 - Detailed Parameter description; Chapter 9 - WLP blocks; Chapter 10 - WLP; Chapter 11 - RTU - Modbus Protocol in the PLC1. This Manual provides information required for the correct use of the PLC1. As the PLC1 is very flexible, it allows many different operation modes as described in this Manual. As the PLC1 can be applied in several ways, it is impossible to describe here all application possibilities of this board. WEG does not assume any responsibility when the PLC1 is not used according to this manual. No part of this Manual may be reproduced in any form, without written consent of WEG.

9

CHAPTERGENERAL CHARACTERISTICS OF THE PLC14.1 Hardware

4

9 isolated digital inputs, bi-directional, 24VDC 3 digital relay output 250V x 3A 3 digital optocoupled outputs, bi-directional, 48VDC x 500mA 1 isolated encoder input, with external supply between 18 and 30VDC Encoder supply - 15VDC x 300mA 1 serial communication interface RS-232C (standard Protocol: MODBUS-RTU) All sizes compatible with CFW-09 User programming in Ladder language, with specific blocks for positioning and PLC functions It permits the use of digital and analog inputs/ouputs of the CFW-09, comprising 15 digital inputs, 9 digital ou