Features Flush panel extra rigid construction. Low noise levels. Eleven speed transformer. Full acoustic and thermal insulation. Various filter options. All types of controls available, fitted and wired. Outputs available up to 6.4 kW cooling and 6.9 kW heating. Hydropac Designed and Built in Britain Patent Nos. Pending June 2003 Horizontal Hydropac PHW173 Illustrated Hydropac Waterside Control Fan Coil Units For Horizontal and Vertical Applications

Waterside Control Fan Coil Units For Horizontal and Vertical

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Waterside Control Fan Coil Units For Horizontal and Vertical

Features

Flush panel extra rigidconstruction.

Low noise levels.

Eleven speed transformer.

Full acoustic and thermalinsulation.

Various filter options.

All types of controlsavailable, fitted and wired.

Outputs available up to 6.4kW cooling and 6.9kWheating.

Hydropac

Designed and Built in Britain

Patent Nos. Pending

June 2003

Horizontal Hydropac PHW173 Illustrated

HydropacWaterside Control Fan Coil Units

For Horizontal and Vertical Applications

Page 2: Waterside Control Fan Coil Units For Horizontal and Vertical

Hydropac

2

Hydropac (Series PHW)

Actionair Hydropac horizontalceiling void mounted type fancoils are waterside control,suitable for operation againstmoderate duct resistances,using chilled water coolingmedium and low pressure hotwater heating medium.Temperature control is bymeans of modulating 4-portdiverting valves on heatingand cooling, operated bystand alone or BMScontroller with room or returnair temperature sensor.

Designated ‘PHW’, the seriesconsists of standard 230mm(PHW230) deep and slimline170mm (PHW170) deepversions.

PHW230 and PHW170 SeriesRobust construction 1.6mmtop panel and fan deck, all otherpanels 1.2mm galvanisedsteel.

Interchangeable spun steelspigots and insulatedblanking plates.

Quick installation with recessedreinforced slotted mountingpoints.

High quality EBM Ziehlexternal rotor motor fans.

Fully insulated withClass ‘O’ open cellthermal and acousticfoam.

Page 3: Waterside Control Fan Coil Units For Horizontal and Vertical

Hydropac

3

Detail ConstructionEasy filter removal with threefilter options:

EU3 Filter Media.

EU2 Metal Mesh.

Commissioning filter (EU2Metal Mesh + Media Filter.)

High performance coils withvents and drains. Circuited toprovide full contra flow.

Pipe support plate.

Insulated removable powdercoated drain tray, withconnection options.

Illuminated on/off switch with 3 speed fan and fine adjustmentswitches. Giving 9 speeds onexterior of units.

Enclosure incorporating 11speed transformer with 24 voltoutput for FCU controller.

Page 4: Waterside Control Fan Coil Units For Horizontal and Vertical

11 °C min air off 14 °C min air off

ChW 6°C flow,11°C return ChW 10°C flow,14°C return

Model Speed Airflow Sensible Total Sensible/Total Cooling Heating Fan Input N.R.Setting (I/s) Cooling Cooling (Watts) (Watts) (Watts) Guide*

(Watts) (Watts)

2 75 905 1040 730 1050 33 30

3 85 990 1125 790 1130 47 32

PHW231 4 100 1120 1255 880 1240 57 35

5 115 1240 1385 980 1345 66 38

6 125 1325 1475 1050 1415 78 40

2 110 1530 1890 1180 2150 50 30

3 125 1710 2080 1300 2290 70 32

PHW232 4 150 2020 2430 1520 2500 90 35

5 175 2320 2800 1730 2700 110 38

6 185 2400 2890 1780 2800 144 40

2 90 1310 1640 1010 1960 60 30

3 120 1620 2000 1240 2220 75 32

PHW232X 4 160 2110 2540 1570 2500 114 35

5 200 2690 3240 1990 2900 125 38

6 230 3050 3720 2260 3200 160 40

2 175 2450 3020 1830 3200 110 30

3 200 2800 3460 2070 3400 140 32

PHW233 4 240 3360 4150 2460 3800 180 35

5 280 3920 4850 2870 4100 220 38

6 305 4270 5270 3110 4400 270 40

2 170 2660 3460 1970 3810 110 30

3 210 3200 4160 2360 4200 140 32

PHW234 4 255 3650 4950 2820 4610 220 35

5 300 4000 5740 3280 5010 275 38

6 330 4200 6050 3530 5300 370 40

2 195 2800 3400 2150 4110 165 30

3 235 3350 4050 2610 4410 200 32

PHW234X 4 290 4000 4770 3180 4910 240 35

5 340 4300 4960 3680 5410 300 38

6 375 4500 5100 4010 5700 356 40

2 185 2650 3210 2000 4510 165 30

3 225 3100 3710 2400 4910 200 32

PHW235 4 280 4000 4830 3010 5410 290 35

5 340 4800 5800 3640 5910 365 38

6 375 5300 6400 3920 6310 495 40

2 230 3300 4010 2550 4910 227 30

3 275 3900 4720 2990 5410 288 32

PHW235X 4 340 4800 5800 3640 5910 364 35

5 405 5400 6370 4290 6510 440 38

6 445 5600 6450 4670 6910 556 40

Hydropac PHW 230 Series

4

PHW 230 Series Thermal Performance Data

Cooling:Summer On-coil air 23 °C Dry Bulb, 16 °C Wet Bulb. Max Coil Pd = 20kPa

Heating:Winter On-coil air temperature 20 °C Dry Bulb. Max Coil Pd = 10kPa

The Fan Coil selections are based on thefollowing entering air conditions:

General: External Resistance 30Pa. Electrical Supply 230 Volts/ 1 phase /50 Hz.Please refer to our Fan Coil Technical Department for alternative conditions.

* see page 7 for NR Predictor.

Waterside control 230mm deep ceiling void mounted chassis unit

LPHW 82°C flow 72°C return

Page 5: Waterside Control Fan Coil Units For Horizontal and Vertical

5

Hydropac PHW 230 Series

Model Dim A Dim B Weights SpigotsPHW 231 380 350 25kg 1-4-7PHW 232/2X 730 700 35kg 1-2-6-7PHW 233 1080 1050 50kg 1-2-4-6-7PHW 234/4X 1430 1400 70kg 1-2-3-5-6-7PHW 235/5X 1780 1750 90kg 1-2-3-4-5-6-7

PHW 230 Series Dimensions

Page 6: Waterside Control Fan Coil Units For Horizontal and Vertical

Hydropac PHW 170 Series

6

Cooling:Summer On-coil air 23 °C Dry Bulb, 16 °C Wet Bulb.Max Coil Pd = 20kPa

Heating:Winter On-coil air temperature 20 °C Dry Bulb.Max Coil Pd = 10kPa

The Fan Coil selections are based on thefollowing entering air conditions:

General: External Resistance 30Pa. Electrical Supply 230 Volts/ 1 phase /50 Hz.Please refer to our Fan Coil Technical Department for alternative conditions.* see page 7 for NR Predictor.

11 °C min air off 14 °C min air offChW 6°C flow,11°C return ChW 10°C flow,14°C return

Model Speed Airflow Sensible Total Sensible/Total Cooling Heating Fan Input N.R.Setting (I/s) Cooling Cooling (Watts) (Watts) (Watts) Guide*

(Watts) (Watts)

2 90 1192 1407 978 1982 40 30

3 105 1385 1602 1120 2187 50 32

PHW172 4 120 1532 1786 1255 2357 62 35

5 135 1701 1673 1394 2525 74 38

6 155 1928 2225 1579 2742 89 40

2 145 1893 2225 1550 3081 80 30

3 170 2187 2257 1790 3390 101 32

PHW173 4 185 2380 2751 1932 3355 133 35

5 205 2592 3011 2123 3772 160 38

6 235 2941 3403 2410 4092 189 40

2 155 2237 2738 1675 3655 80 30

3 180 2573 3136 1916 4026 101 32

PHW174 4 195 2774 3374 2067 4246 133 35

5 215 3035 3680 2268 4519 160 38

6 245 3399 4092 2557 4861 189 40

2 200 2825 3427 2127 4740 113 30

3 230 3228 3905 2423 5191 143 32

PHW175 4 245 3429 4145 2577 5415 187 35

5 265 3696 4481 2786 5706 224 38

6 290 4002 4808 3031 5997 267 40

Unit Dim A Dim B Dim C Weight SPIGOT OPTIONSPHW 172 730 700 225 32kg 1-2-4-7-8PHW 173 1080 1050 267 45kg 1-2-3-6-7-8PHW 174 1430 1400 287 65kg 1-2-3-4-6-7-8PHW 175 1780 1750 300 85kg 1-2-3-4-5-6-7-8

PHW 170 Series Thermal Performance Data

Dimensions

Waterside control 170mm deep ceiling void mounted chassis unit

LPHW 82°C flow 72°C return

Page 7: Waterside Control Fan Coil Units For Horizontal and Vertical

Hydropac PHW 230 / 170 Series

7

Acoustic Performance Data

Fresh air supply duct.

Return air grille/diffuser(not positioned directlybelow unit intakes).

T Bar grid false ceiling witheither 10mm thick fibre boardtiles or insulated metal pantiles.

Buildingstructure.

Internalroom.

Wall/glazing.

Fan coil unit.

Diffuserplenum.

Minimum 1 metre lengthSonodec 25 acoustic flex.

‘NR’ predictions quoted are basedupon extensive acousticindependent tests to the abovearrangement and are intended as aguide to levels which can beexpected.

The following qualifications must apply:-

Units must be mounted correctly, usingrubber washers, onto a solid structure.

The units should be mounted into a falseceiling of not less than 300mm deep,constructed of a standard ‘T’ bar gridwith 10mm thick fibre board tiles orinsulated metal pan tiles.

Rooms of open plan or partitioned designshould be furnished, carpeted and haveno more than 20% glass area with nohighly reflective surfaces such as ceramictiles etc.

Where a single unit is serving a room thedimensions should be based upon acooling load of 120w/sq.m e.g a unitgiving 1.2kW total cooling output shouldbe serving a room with a floor area of notless than 10sq.m. In an open plan areaunits should be mounted at a minimumof 4.5m centres and no closer than 1.5mfrom a corner.

Return air grilles should not be positioneddirectly below unit intakes.

At least 1m of acoustic flexible ducting(Sonodec 25 or similar) is used on eachspigot outlet. A maximum air velocity of3.0m/s per outlet spigot to achieve NR35.

The above should give the predicted Lpat 1.5m from the nearest diffuser.

For detailed acoustic data ofInlet/Casing Radiated andDischarge Sound Power Levels,please refer to Actionair SalesOffice.

*Notes on ‘NR’ predictions

Typical Horizontal Fan Coil Unit Arrangement

Page 8: Waterside Control Fan Coil Units For Horizontal and Vertical

8

Discharge spigotcan be vertical orhorizontal.

EBM Ziehl externalrotor motor fans.

Protected controlenclosure.

Hydropac (Series PVW)

Actionair vertical chassisand cased wall mountedfan coils are waterside control,suitable for free-blow,applications or vertical ductedarrangements operating up to60 Pa external resistance,using chilled water coolingmedium and low pressure hotwater medium.Temperature control is bymeans of modulating 4-portdiverting valves on heatingand cooling.Designated PVW the seriesconsists of five models 230mmdeep, with six non-cased/casedvariations.

PVW230 Series Detail Constru

Condensate removalpump when used.

Removable frontaccess.

Slide out filters.

Hydropac

Page 9: Waterside Control Fan Coil Units For Horizontal and Vertical

9

ctionPVW 230 Cases Options andMounting Arrangements

Option 1. Low levelmounting with front angledgrille outlet.

Option 2. Low levelmounting with front angledgrille outlet and front facegrille inlet.

Option 3. High levelmounting as per option 2but with protection panelon underside .

Option 4. High levelmounting with front grilleoutlet and undersidegrille inlet.

Hydropac

Page 10: Waterside Control Fan Coil Units For Horizontal and Vertical

11 °C min air off 14 °C min air off

ChW 6°C flow, 11°C return ChW 10°C flow, 14°C return

Model Speed Airflow Sensible Total Sensible/Total Cooling Heating Fan Input N.R.Setting (I/s) Cooling Cooling (Watts) (Watts) (Watts) Guide*

(Watts) (Watts)2 40 419 463 350 704 17 30

3 50 489 534 380 829 20 32

. PVW231 4 60 557 570 400 883 22 35

5 60 557 605 410 934 25 38

6 70 617 668 430 1017 28 40

2 90 888 971 778 1737 32 30

3 100 957 1041 840 1851 36 32

PVW232 4 110 1025 1113 903 1964 40 35

5 120 1093 1185 968 2077 45 38

6 130 1162 1259 1034 2188 49 40

2 115 1292 1446 1017 2458 50 30

3 140 1525 1695 1170 2757 60 32

PVW233 4 160 1715 1898 1296 2992 65 35

5 180 1905 2105 1428 3224 75 38

6 215 2229 2455 1666 3604 90 40

2 140 1530 1701 1246 3066 58 30

3 160 1702 1881 1363 3303 63 32

PVW234 4 200 2057 2263 1608 3767 80 35

5 220 2241 2463 1738 3995 90 38

6 240 2428 2866 1873 4220 100 40

2 185 1925 2122 1578 4018 85 30

3 225 2213 2428 1784 4436 120 32

PVW235 4 250 2472 2706 1970 4788 150 35

5 275 2697 2949 2133 5078 165 38

6 320 3117 3404 2449 5594 185 40

10

Hydropac Series PVW 230

Cooling:Summer On-coil air 23 °C Dry Bulb, 16 °C Wet Bulb.Max Coil Pd = 20kPa

Heating:Winter On-coil air temperature 20 °C Dry Bulb.Max Coil Pd = 10kPa

The Fan Coil selections are based on thefollowing entering air conditions:

General: External Resistance 10Pa. Electrical Supply 230 Volts/ 1 phase /50 Hz.* see page 11 for NR Predictor.

Unit Dim A Dim B WeightPVW 231 785 310 30kgPVW 232 1035 660 43kgPVW 233 1385 1010 62kgPVW 234 1735 1360 86kgPVW 235 2085 1710 110kg

Chassis Dimensions

PVW 230 Series Thermal Performance Data230mm deep vertical wall mounted chassis / cased units

LPHW 82°C flow72°C return

Page 11: Waterside Control Fan Coil Units For Horizontal and Vertical

Hydropac Series PVW 230

11

‘NR’ predictions are based uponextensive acoustic independenttests and are intended as a guideto levels which can be expected,when measured at 2.0m.

The following qualifications apply:-

Units must be mounted correctly, usingfixing points provided onto a flat, solidsurface, such as concrete or brick wall insuch a way that they are not subjected toundue stress and are checked foraccuracy of horizontal levelling.

Rooms of open plan or partitioned designshould be furnished, carpeted and haveno more than 20% glass area with nohighly reflective surfaces such as ceramictiles etc.

Where a single unit is serving a room thedimensions should be based upon acooling load of 120w/sq.m e.g a unitgiving 1.2kW total cooling output shouldbe serving a room with a floor area of notless than 10sq.m. In an open plan areaunits should be mounted at a minimum of3m centres and no closer than 1.5m froma corner.

Units installed in accordance with theabove should give the predicted N.R. levelwhen measured at a distance of 2.0mfrom any surrounding flat surface.

For detailed acoustic data ofRadiated Sound Power Levels,please refer to Technical SalesOffice.

PVW 230 Series

*Notes on ‘NR’ predictions Case Dimensional Data

Unit Dim A Dim B WeightPVW 231 815 310 35kgPVW 232 1065 660 50kgPVW 233 1415 1010 70kgPVW 234 1785 1360 95kgPVW 235 2115 1710 120kg

Option 1 Case

Option 2 and 3 Case

Option 4 Case

Page 12: Waterside Control Fan Coil Units For Horizontal and Vertical

PR

OD

UC

ED

BY

GR

AP

HIC

PA

RT

NE

RS

HIP

012

27 2

8087

7

Actionair

Technical Support

Actionair provide quality productsbacked by a dedicated teamcommitted to providing the verybest in customer service.

Specialist response from theActionair Sales Team, administrativeresponse from the ComputerisedSales Office and productmaintenance from the Team ofExperienced Service Engineers, whounderstand fully the needs of theindustry.

Actionair Products

For information on ourcomprehensive range of Fire,Smoke and Air Control Dampers, aswell as Application, Technical andPricing Advice, please refer to theActionair Sales Office.

The information contained herein issubject to change without notice due tocontinuing research and development.

Quality System Certificate No 017

Assessed to ISO 9001 : 2000

Actionair, South Street, Whitstable, Kent CT5 3DU EnglandTel: (01227) 276100 Fax: (01227) 264262 International Code: +441227

Email: [email protected] Website: www.actionair.co.uk

N O C O M P R O M I S E

ww

w.a

cti

on

air

.co