80
HIGH FLEXIBILITY WITH CAPACITY ADJUSTMENTAvailable in three basic sizes which can be optimally adjusted. Cooling: 9 – 56kW & Heating 10 – 63kW. Multiple interfaces can be installed together for up to 90kW Cooling and 90kW Heating.
LED MOUNTED DISPLAYBuilt in display for easy trouble-shooting
VRF DX INTERFACE
MODEL DX COIL CA-PACITY (KW)
SETTING CA-PACITY (HP)
CAPACITY SETTING CODE
(ENC1)ENC1 SETTING NO. OF IDU AD-
DRESSES OCCUPIED
AHUKZ-01B
9~11.2 3.2 7
111.2~14 4 8
14~18 5 9
18~20 6 A
AHUKZ-02B
20~25 8
B 225~30 10
30~36 12
AHUKZ-03B
36~40 14C 3
40~45 16
45~50 18D 4
50~56 20
FLEXIBLE CONTROLSCan be controlled via standard Midea controller or 3rd Party controller via 0-10VDC.
WIDE APPLICATION RANGEUp to 45kW available from a single sideflowoutdoor unit.
MANUAL OPERATION TIMER DEF./FAN ALARM
Timer indicator
Operation lamp
Manual button
Alarm indicator
Infrared signal receiver
LED display
Defrost indicator (cooling and heating type)or fan only indicator (cooling only type)
81
VRF DX INTERFACE
Up to 45kW from a single Sideflow UnitUp to 90kW from single outdoor unit Wide capacity range with up to 56kW from a single Unit
MODEL AHUKZ-01B AHUKZ-02B AHUKZ-03B
Power supply Phase/V/Hz 1-phase,220-240V,50Hz
Recommended Fuse Size A 5 5 5
Interconnecting Wiring mm 3 Core Screened 0.75mm²
CapacityCooling kW 9-20 20-33 28.1-56
Heating kW 10-22.4 22.4-35 31.5-63
Net dimension (WxHxD) mm 375x350x150 375x350x150 375x350x150
Packing dimension (WxHxD) mm 490x420x240 490x420x240 490x420x240
Net/gross weight kg 8.7/10 8.7/10 8.7/10
Piping connectionsInlet pipe mm(inch) Φ9.53 (3/8) Φ12.7 (1/2) Φ15.9 (5/8)
Outlet pipe mm(inch) Φ9.53 (3/8) Φ12.7 (1/2) Φ15.9 (5/8)
Nominal Conditions: Cooling: indoor 27°C DB, 19°C WB; outdoor 35°C DB, 24°C WB. Nominal Conditions: Heating: indoor 20°C DB, outdoor 7°C DB, 6°C WB.
Option 1: Midea controllerOption 2: 3rd party DDC controller
Midea AHU KitAHU or Indoor Unit
Outdoor Unit