98
036-31114-001-E-0411

Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

036-31114-001-E-0411

Page 2: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

036-31114-001-E-0411

Page 3: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

036-31114-001-E-0411

Indoor Unit Outdoor Unit Special Application Note

PSC Air Handler Single Stage Air Conditioner

V/S Air Handler Single Stage Air Conditioner

PSC Air Handler Single Stage Air Conditioner

V/S Air Handler Single Stage Air Conditioner

Modulating Furnace Single Stage Air Conditioner

Two Stage PSC Furnace Single Stage Air Conditioner

Two Stage V/S Furnace Single Stage Air Conditioner

Single Stage Furnace (X-13) Single Stage Air Conditioner

Modulating Furnace Two Stage Air Conditioner

Two Stage V/S Furnace Two Stage Air Conditioner

Two Stage PSC Furnace Two Stage Air Conditioner

Single Stage Furnace (X-13) Two Stage Air Conditioner

V/S Air Handler Two Stage Air Conditioner

PSC Air Handler Two Stage Air Conditioner

V/S Air Handler Two Stage Air Conditioner

Two Stage V/S Furnace Two Stage Air Conditioner

Modulating Furnace Two Stage Air Conditioner

Two Stage PSC Furnace Two Stage Air Conditioner

Single Stage Furnace (X-13) Two Stage Air Conditioner

V/S Air Handler Two Stage Air Conditioner

PSC Air Handler Two Stage Air Conditioner

V/S Air Handler Two Stage Air Conditioner

Two Stage V/S Furnace Two Stage Air Conditioner

Modulating Furnace Two Stage Air Conditioner

Two Stage PSC Furnace Two Stage Air Conditioner

Single Stage Furnace (X-13) Two Stage Air Conditioner

V/S Air Handler Two Stage Air Conditioner

PSC Air Handler Two Stage Air Conditioner

V/S Air Handler Two Stage Air Conditioner

Single Stage PSC Furnace Single Stage Air Conditioner

Modulating Furnace Single Stage Air Conditioner

Two Stage PSC Furnace Single Stage Air Conditioner

Single Stage Furnace (X-13) Single Stage Air Conditioner

PSC Air Handler Single Stage Air Conditioner

V/S Air Handler Single Stage Air Conditioner

PSC Air Handler Single Stage Air Conditioner

V/S Air Handler Single Stage Air Conditioner

1033

1034

1035

1036

1027

1028

1029

1030

1031

1032

1021

1022

1023

1024

1025

1026

1015

1016

1017

1018

1019

1020

1037

use specific UPG thermostats as shown, and may not include all thermostats soldwith or for UPG residential products. Due to continuous product improvements, allspecifications are subject to change without notice. For distribution use only - not to be

1012

1013

1014

1008

Low Voltage System Wiring Diagrams

This document provides specific details for making low voltage wiring connections of UPG Residential products. This includes diagrams for many specific air conditioning or heat pump outdoor applications with air handlers or gas furnaces. These diagrams

Number

1001

used at point of retail sale. All rights reserved. For the most up-to-date technical

Table of Contents - Low Voltage System Wiring Diagrams

information, please visit our website at www.york.com.

1009

1010

1011

1002

1003

1004

1005

1006

1007

Page 4: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

036-31114-001-E-0411Indoor Unit Outdoor Unit Special Application Note

Two Stage V/S Furnace Single Stage Heat Pump (YGVI control)Modulating Furnace Single Stage Heat Pump (YGVI control)Two Stage PSC Furnace Single Stage Heat Pump (YGVI control)Single Stage Furnace (X-13) Single Stage Heat Pump (YGVI control)PSC Air Handler Single Stage Heat Pump (YGVI control)V/S Air Handler Single Stage Heat Pump (YGVI control)PSC Air Handler Single Stage Heat Pump (YGVI control)V/S Air Handler Single Stage Heat Pump (YGVI control)PSC Air Handler Single Stage Heat Pump (YGVI control)V/S Air Handler Single Stage Heat Pump (YGVI control)PSC Air Handler Single Stage Heat Pump (YGVI control)V/S Air Handler Single Stage Heat Pump (YGVI control)Two Stage V/S Furnace Two Stage Heat Pump (YGVI control)Modulating Furnace Two Stage Heat Pump (YGVI control)Two Stage PSC Furnace Two Stage Heat Pump (YGVI control)Two Stage V/S Furnace Two Stage Heat Pump (YGVI control)V/S Air Handler Two Stage Heat Pump (YGVI control)PSC Air Handler Two Stage Heat Pump (YGVI control)V/S Air Handler Two Stage Heat Pump (YGVI control)Two Stage V/S Furnace Two Stage Heat Pump (YGVI control)Modulating Furnace Two Stage Heat Pump (YGVI control)Two Stage PSC Furnace Two Stage Heat Pump (YGVI control)Two Stage V/S Furnace Two Stage Heat Pump (YGVI control)V/S Air Handler Two Stage Heat Pump (YGVI control)PSC Air Handler Two Stage Heat Pump (YGVI control)V/S Air Handler Two Stage Heat Pump (YGVI control)Two Stage V/S Furnace Two Stage Heat Pump (YGVI control)Modulating Furnace Two Stage Heat Pump (YGVI control)Two Stage PSC Furnace Two Stage Heat Pump (YGVI control)Two Stage V/S Furnace Two Stage Heat Pump (YGVI control)V/S Air Handler Two Stage Heat Pump (YGVI control)PSC Air Handler Two Stage Heat Pump (YGVI control)V/S Air Handler Two Stage Heat Pump (YGVI control)Single Stage PSC Furnace Single Stage Heat Pump (Demand Defrost) Modulating Furnace Single Stage Heat Pump (Demand Defrost) Single Stage Furnace (X-13) Single Stage Heat Pump (Demand Defrost) PSC Air Handler Single Stage Heat Pump (Demand Defrost) V/S Air Handler Single Stage Heat Pump (Demand Defrost) PSC Air Handler Single Stage Heat Pump (Demand Defrost) V/S Air Handler Single Stage Heat Pump (Demand Defrost) PSC Air Handler Single Stage Heat Pump (Demand Defrost) V/S Air Handler Single Stage Heat Pump (Demand Defrost) PSC Air Handler Single Stage Heat Pump (Demand Defrost) V/S Air Handler Single Stage Heat Pump (Demand Defrost) Single Stage PSC Furnace Single Stage Heat Pump (Timed Temp)Modulating Furnace Single Stage Heat Pump (Timed Temp)Single Stage Furnace (X-13) Single Stage Heat Pump (Timed Temp)PSC Air Handler Single Stage Heat Pump (Timed Temp)V/S Air Handler Single Stage Heat Pump (Timed Temp)PSC Air Handler Single Stage Heat Pump (Timed Temp)V/S Air Handler Single Stage Heat Pump (Timed Temp)PSC Air Handler Single Stage Heat Pump (Timed Temp)V/S Air Handler Single Stage Heat Pump (Timed Temp)PSC Air Handler Single Stage Heat Pump (Timed Temp)V/S Air Handler Single Stage Heat Pump (Timed Temp)

Notes:a. Some diagram numbers may not be used (e.g. for obsolete controls or reserved for future use).b. Some thermostats may require special connections (refer to thermostat instructions if necessary).

2052205320542055

204620472048204920502051

204020412042204320442045

203420352036203720382039

20322033

20272028202920302031

202120222023202420252026

201520162017201820192020

200920102011201220132014

200320042005200620072008

2001

Number

2002

Page 5: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1001 PSC Air Handler – Single Stage Air Conditioner (with AC control)

F*FP

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

W1First Stage Heat

W2Second Stage Heat

( ) Convenience Terminal

No function in thisapplication

1

1

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

036-31114-001-E-0411

Page 6: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1002 V/S Air Handler – Single Stage Air Conditioner (with AC control)

F*FV

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

3

3

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

External Humidistat(Optional)

Open on Humidity Rise

4

Part Number:S1-2HU16700124

4

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 7: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1003 PSC Air Handler – Single Stage Air Conditioner (with AC control)

MX

MA

AHX

AHP

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional) The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 8: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1004 V/S Air Handler – Single Stage Air Conditioner (with AC control)

MV

AV

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 9: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1005 Modulating Furnace – Single Stage Air Conditioner (with AC control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “GAS”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “NO” The AC control listed

may or may not be present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 10: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1006 Two Stage PSC Furnace – Single Stage Air Conditioner (with AC control)

TM(8,L)T

TM9T

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “GAS”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 11: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1007 Two Stage V/S Furnace – Single Stage Air Conditioner (with AC control)

TM(8,L)V

TM9V

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “GAS”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “NO”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

The AC control listed may or may not be

present depending on the model selected. If the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 12: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1008 Single Stage Furnace (X-13) – Single Stage Air Conditioner (with AC control)

T*(8,L)X

TM9X

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “GAS”

SINGLE STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

SINGLE STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 13: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1009 Modulating Furnace – Two Stage Air Conditioner (with AC control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

HEATPUMP jumper must be set to “NO”

036-31114-001-E-0411

Page 14: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1010 Two Stage V/S Furnace – Two Stage Air Conditioner (with AC control)

TM(8,L)V

TM9V

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “NO”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

036-31114-001-E-0411

Page 15: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1011 Two Stage PSC Furnace – Two Stage Air Conditioner (with AC control)

TM(8,L)T

TM9T

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

036-31114-001-E-0411

Page 16: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1012 Single Stage Furnace (X-13) – Two Stage Air Conditioner (with AC control)

T*(8,L)X

TM9X

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

036-31114-001-E-0411

Page 17: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1013 V/S Air Handler – Two Stage Air Conditioner (with AC control)

F*FV

ID MODELS

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

External Humidistat(Optional)

Open on Humidity Rise

4

Part Number:S1-2HU16700124

4

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

3

3

Jumper 1 must be set to “ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

036-31114-001-E-0411

Page 18: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1014 PSC Air Handler – Two Stage Air Conditioner (with AC control)

MX

MA

AHX

AHP

ID MODELS

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

036-31114-001-E-0411

Page 19: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1015 V/S Air Handler – Two Stage Air Conditioner (with AC control)

MV

AV

ID MODELS

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 2 must be set to “GAS”

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

036-31114-001-E-0411

Page 20: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1016 Two Stage V/S Furnace – Two Stage Air Conditioner (with AC control)

TM(8,L)V

TM9V

ID MODELS

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “GAS”

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “NO”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

036-31114-001-E-0411

Page 21: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1017 Modulating Furnace – Two Stage Air Conditioner (with AC control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “GAS”

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “NO”

036-31114-001-E-0411

Page 22: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1018 Two Stage PSC Furnace – Two Stage Air Conditioner (with AC control)

TM(8,L)T

TM9T

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “GAS”

036-31114-001-E-0411

Page 23: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1019 Single Stage Furnace (X-13) – Two Stage Air Conditioner (with AC control)

T*(8,L)X

TM9X

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “GAS”

036-31114-001-E-0411

Page 24: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1020 V/S Air Handler – Two Stage Air Conditioner (with AC control)

F*FV

ID MODELS

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

3

3

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “ELEC”

036-31114-001-E-0411

Page 25: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1021 PSC Air Handler – Two Stage Air Conditioner (with AC control)

MX

MA

AHX

AHP

ID MODELS

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “ELEC”

036-31114-001-E-0411

Page 26: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1022 V/S Air Handler – Two Stage Air Conditioner (with AC control)

MV

AV

ID MODELS

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

Jumper 1 must be set to “GAS/ELEC”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

C24 – Volt Common

Jumper 3 must be set to “ELEC”

036-31114-001-E-0411

Page 27: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1023 Two Stage V/S Furnace – Two Stage Air Conditioner (with AC control)

TM(8,L)V

TM9V

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “NO”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-mustbe set to 8-2 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 28: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1024 Modulating Furnace – Two Stage Air Conditioner (with AC control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 10-1 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “NO”

036-31114-001-E-0411

Page 29: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1025 Two Stage PSC Furnace – Two Stage Air Conditioner (with AC control)

TM(8,L)T

TM9T

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-mustbe set to 8-2 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

036-31114-001-E-0411

Page 30: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1026 Single Stage Furnace (X-13) – Two Stage Air Conditioner (with AC control)

T*(8,L)X

TM9X

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 10-1 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

036-31114-001-E-0411

Page 31: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1027 V/S Air Handler – Two Stage Air Conditioner (with AC control)

F*FV

ID MODELS

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

3

3

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-mustbe set to 8-2 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

External Humidistat(Optional)

Open on Humidity Rise

4

Part Number:S1-2HU16700124

4

036-31114-001-E-0411

Page 32: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1028 PSC Air Handler – Two Stage Air Conditioner (with AC control)

MX

MA

AHX

AHP

ID MODELS

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-mustbe set to 8-2 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 33: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1029 V/S Air Handler – Two Stage Air Conditioner (with AC control)

MV

AV

ID MODELS

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

TWO STAGEAIR

CONDITIONER

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

Y2Second StageCompressor

TWO STAGEAIR CONDITIONER

Part Number:SAP

501264

2

2

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

C24 – Volt Common

YFirst Stage Compressor

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

W2Second Stage Heat

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-mustbe set to 8-2 Heat/2 CoolMultistage Conventional

WFirst Stage Heat

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 34: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1030 Single Stage PSC Furnace – Single Stage Air Conditioner

GY8S

TG(8,L)S

TG9S

ID MODELS

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “GAS”

Jumper 2 must be moved to “ELEC/GAS”

C24 – Volt Common

R24 – Volt Hot

WFull Stage Heat

Y / Y2First

Stage Compressor

SINGLE STAGE PSCFURNACE

GFan

SINGLE STAGEPSC

FURNACE

Part Number:SAP

539617

1

1

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 35: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1031 Modulating Furnace – Single Stage Air Conditioner

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

External Humidistat(Optional)

Open on Humidity Rise

2

Part Number:S1-2HU16700124

2

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “GAS”

Jumper 2 must be moved to “ELEC/GAS”

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “NO”

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 36: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1032 Two Stage PSC Furnace – Single Stage Air Conditioner

TM(8,L)T

TM9T

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “GAS”

Jumper 2 must be moved to “ELEC/GAS”

The STAGING jumper must be set to desired

position other than “OFF”

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 37: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1033 Single Stage Furnace (X-13) – Single Stage Air Conditioner

T*(8,L)X

TM9X

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “GAS”

Jumper 2 must be moved to “ELEC/GAS”

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 38: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1034 PSC Air Handler – Single Stage Air Conditioner

F*FP

ID MODELS

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “ELEC/HP”

Jumper 2 must be moved to “ELEC/GAS”

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 39: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1035 V/S Air Handler – Single Stage Air Conditioner

F*FV

ID MODELS

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “ELEC/HP”

Jumper 2 must be moved to “ELEC/GAS”

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 40: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1036 PSC Air Handler – Single Stage Air Conditioner

MX

MA

AHX

AHP

ID MODELS

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “ELEC/HP”

Jumper 2 must be moved to “ELEC/GAS”

External Humidistat(Optional)

Open on Humidity Rise

2

Part Number:S1-2HU16700124

2

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 41: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

1037 V/S Air Handler – Single Stage Air Conditioner

MV

AV

ID MODELS

C24 – Volt Common

YCompressor Contactor

SINGLE STAGEAIR CONDITIONER

SINGLE STAGEAIR

CONDITIONER

YFull Stage Compressor

O / BReversing Valve

GFan

S1-THEC11P5bS1-THEC11Nb

THERMOSTAT

RH24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

WFull Stage Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

Jumper 1 must be moved to “ELEC/HP”

Jumper 2 must be moved to “ELEC/GAS”

External Humidistat(Optional)

Open on Humidity Rise

2

Part Number:S1-2HU16700124

2

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

The AC control listed may or may not be

present depending on the model selected. If

the wire is not present, then the R wire is not

needed.

036-31114-001-E-0411

Page 42: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2001 Two Stage V/S Furnace – Single Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Setup Step 50 “Dual Fuel” must be set

“External”

036-31114-001-E-0411

Page 43: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2002 Modulating Furnace – Single Stage Heat Pump (with YGVI control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Setup Step 50 “Dual Fuel” must be set

“External”

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “YES”

036-31114-001-E-0411

Page 44: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2003 Two Stage PSC Furnace – Single Stage Heat Pump (with YGVI control)

TM(8,L)T

TM9T

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Setup Step 50 “Dual Fuel” must be set

“External”

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

036-31114-001-E-0411

Page 45: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2004 Single Stage Furnace (X-13) – Single Stage Heat Pump (with YGVI control)

T*(8,L)X

TM9X

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Setup Step 50 “Dual Fuel” must be set

“External”

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

036-31114-001-E-0411

Page 46: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2005 PSC Air Handler – Single Stage Heat Pump (with YGVI control)

F*FP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

036-31114-001-E-0411

Page 47: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2006 V/S Air Handler – Single Stage Heat Pump (with YGVI control)

F*FV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

3

Part Numbers:SAP

524851500644

3

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

036-31114-001-E-0411

Page 48: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2007 PSC Air Handler – Single Stage Heat Pump (with YGVI control)

MX

MA

AHX

AHP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

036-31114-001-E-0411

Page 49: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2008 V/S Air Handler – Single Stage Heat Pump (with YGVI control)

MV

AV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

036-31114-001-E-0411

Page 50: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2009 PSC Air Handler – Single Stage Heat Pump (with YGVI control)

F*FP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

036-31114-001-E-0411

Page 51: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2010 V/S Air Handler – Single Stage Heat Pump (with YGVI control)

F*FV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

3

Part Numbers:SAP

524851500644

3

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

External Humidistat(Optional)

Open on Humidity Rise

4

Part Number:S1-2HU16700124

4

036-31114-001-E-0411

Page 52: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2011 PSC Air Handler – Single Stage Heat Pump (with YGVI control)

MX

MA

AHX

AHP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 53: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2012 V/S Air Handler – Single Stage Heat Pump (with YGVI control)

MV

AV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

SINGLE STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

GFan

S1-THSU21P1b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 54: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2013 Two Stage V/S Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set

“External”

036-31114-001-E-0411

Page 55: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2014 Modulating Furnace – Two Stage Heat Pump (with YGVI control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set

“External”

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “YES”

036-31114-001-E-0411

Page 56: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2015 Two Stage PSC Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)T

TM9T

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set

“External”

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

036-31114-001-E-0411

Page 57: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2016 Two Stage V/S Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set

“External”

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

036-31114-001-E-0411

Page 58: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2017 V/S Air Handler – Two Stage Heat Pump (with YGVI control)

F*FV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

3

Part Numbers:SAP

524851500644

3

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “2”

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

036-31114-001-E-0411

Page 59: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2018 PSC Air Handler – Two Stage Heat Pump (with YGVI control)

MX

MA

AHX

AHP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “2”

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

036-31114-001-E-0411

Page 60: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2019 V/S Air Handler – Two Stage Heat Pump (with YGVI control)

MV

AV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “2”

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

036-31114-001-E-0411

Page 61: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2020 Two Stage V/S Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 1Heat Pump Backup Heat

Source is Fossil Fuel

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

Thermostat Installer Setup0210-External Fossil Fuel

Kit- must be set to 1Heat Pump Control

is Controlling Heat PumpBackup Heat

036-31114-001-E-0411

Page 62: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2021 Modulating Furnace – Two Stage Heat Pump (with YGVI control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “YES”

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 1Heat Pump Backup Heat

Source is Fossil Fuel

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

Thermostat Installer Setup0210-External Fossil Fuel

Kit- must be set to 1Heat Pump Control

is Controlling Heat PumpBackup Heat

036-31114-001-E-0411

Page 63: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2022 Two Stage PSC Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)T

TM9T

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 1Heat Pump Backup Heat

Source is Fossil Fuel

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

Thermostat Installer Setup0210-External Fossil Fuel

Kit- must be set to 1Heat Pump Control

is Controlling Heat PumpBackup Heat

036-31114-001-E-0411

Page 64: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2023 Two Stage V/S Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 1Heat Pump Backup Heat

Source is Fossil Fuel

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

Thermostat Installer Setup0210-External Fossil Fuel

Kit- must be set to 1Heat Pump Control

is Controlling Heat PumpBackup Heat

036-31114-001-E-0411

Page 65: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2024 V/S Air Handler – Two Stage Heat Pump (with YGVI control)

F*FV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

3

Part Numbers:SAP

524851500644

3

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 0Heat Pump Backup Heat

Source is Electric

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

036-31114-001-E-0411

Page 66: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2025 PSC Air Handler – Two Stage Heat Pump (with YGVI control)

MX

MA

AHX

AHP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 0Heat Pump Backup Heat

Source is Electric

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

036-31114-001-E-0411

Page 67: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2026 V/S Air Handler – Two Stage Heat Pump (with YGVI control)

MV

AV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

Thermostat Installer Setup0200-Backup Heat Source-

must be set to 0Heat Pump Backup Heat

Source is Electric

C24 – Volt Common

YFirst Stage Compressor

O/BReversing Valve

Y2Second StageCompressor

GFan

*PP32U70124

THERMOSTAT

R24 – Volt Hot(Heat XFMR)

RC24 – Volt Hot(Cool XFMR)

Connection of the “C”terminal, 24-Volt commonis optional when used with

batteries

Thermostat Installer Setup0170-System Type-must

be set to 12-3 Heat/2Heat Pump

LMalfunction Light

EEmergency Heat

AUXAuxiliary Heat

Thermostat Installer Setup0190-Changeover Valve-

must be set to 0O/B terminal

Energized in Cooling

036-31114-001-E-0411

Page 68: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2027 Two Stage V/S Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

Jumper 1 must be set to “GAS”

036-31114-001-E-0411

Page 69: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2028 Modulating Furnace – Two Stage Heat Pump (with YGVI control)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “YES”

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

Jumper 1 must be set to “GAS”

036-31114-001-E-0411

Page 70: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2029 Two Stage PSC Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)T

TM9T

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGE PSCFURNACE

GFan

TWO STAGE PSC FURNACE

1

Part Number:SAP

542767

1

The STAGING jumper must be set to “OFF”

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

Jumper 1 must be set to “GAS”

036-31114-001-E-0411

Page 71: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2030 Two Stage V/S Furnace – Two Stage Heat Pump (with YGVI control)

TM(8,L)V

TM9V

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “ON”

Bonnet Sensor Kit(Optional)

S1-37309243000

2

Part Numbers:SAP

524851500644

2

C24 – Volt Common

R24 – Volt Hot

Y/Y2Second or Full

Stage Compressor

W / W1First Stage Heat

W2Second Stage Heat

Y1First

Stage Compressor

TWO STAGEVARIABLE SPEED

FURNACE CONTROL

GFan

TWO STAGE VARIABLE

SPEED FURNACE

1

Part Number:SAP

542766

1

The STAGING jumper must be set to “OFF”

OReversing Valve

X/LMalfunction Light

DHUMDehumidification

The HEAT PUMP jumper must be set to “YES”

Move the DHUM jumper to “YES” if a humidistat is to

be used.

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

Jumper 1 must be set to “GAS”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 72: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2031 V/S Air Handler – Two Stage Heat Pump (with YGVI control)

F*FV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

3

Part Numbers:SAP

524851500644

3

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

Jumper 1 must be set to “ELEC”

External Humidistat(Optional)

Open on Humidity Rise

4

Part Number:S1-2HU16700124

4

036-31114-001-E-0411

Page 73: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2032 PSC Air Handler – Two Stage Heat Pump (with YGVI control)

MX

MA

AHX

AHP

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

Jumper 1 must be set to “ELEC”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 74: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2033 V/S Air Handler – Two Stage Heat Pump (with YGVI control)

MV

AV

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1 OUTFirst Stage Heat

W2 OUTSecond Stage Heat

Y2 OUTSecond StageCompressor

Y1Single StageCompressor

X/LMalfunction Light

Y2Second StageCompressor

WAuxiliary Heat

BSBonnet Sensor

BSGBonnet Sensor

YORKGUARD VICONTROL

TWO STAGEHEAT PUMP

Change FFuel jumperon the heat pump control

to “OFF”

2

Part Numbers:SAP

524851500644

2

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

Jumper 2 must be set to “HP”

Y1First Stage

Compressor

W2Second Stage Heat

Y2Second StageCompressor

GFan

S1-THEU22P7b

THERMOSTAT

R24 – Volt Hot

W1/O/BFirst Stage Heat

C24 – Volt Common

Jumper 3 must be set to “O”

Jumper 1 must be set to “ELEC”

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 75: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2034 Single Stage PSC Furnace – Single Stage Heat Pump (Demand Defrost)

GY8S

TG(8,L)S

TG9S

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

C24 – Volt Common

R24 – Volt Hot

WFull Stage Heat

Y / Y2First

Stage Compressor

SINGLE STAGE PSCFURNACE

GFan

SINGLE STAGEPSC

FURNACE

Part Number:SAP

539617

1

1

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Jumper 2 must be set to “O”

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set “ON”

Suggestion: For optimal operation add an OD temp sensor.

036-31114-001-E-0411

Page 76: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2035 Modulating Furnace – Single Stage Heat Pump (Demand Defrost)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “YES”

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Jumper 2 must be set to “O”

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set “ON”

Suggestion: For optimal operation add an OD temp sensor.

036-31114-001-E-0411

Page 77: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2036 Single Stage Furnace (X-13) – Single Stage Heat Pump (Demand Defrost)

T*(8,L)X

TM9X

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Jumper 2 must be set to “O”

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set “ON”

Suggestion: For optimal operation add an OD temp sensor.

036-31114-001-E-0411

Page 78: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2037 PSC Air Handler – Single Stage Heat Pump (Demand Defrost)

F*FP

ID MODELS

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

036-31114-001-E-0411

Page 79: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2038 V/S Air Handler – Single Stage Heat Pump (Demand Defrost)

F*FV

ID MODELS

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

3

3

036-31114-001-E-0411

Page 80: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2039 PSC Air Handler – Single Stage Heat Pump (Demand Defrost)

MX

MA

AHX

AHP

ID MODELS

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

036-31114-001-E-0411

Page 81: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2040 V/S Air Handler – Single Stage Heat Pump (Demand Defrost)

MV

AV

ID MODELS

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

036-31114-001-E-0411

Page 82: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2041 PSC Air Handler – Single Stage Heat Pump (Demand Defrost)

F*FP

ID MODELS

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

036-31114-001-E-0411

Page 83: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2042 V/S Air Handler – Single Stage Heat Pump (Demand Defrost)

F*FV

ID MODELS

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

3

3

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

036-31114-001-E-0411

Page 84: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2043 PSC Air Handler – Single Stage Heat Pump (Demand Defrost)

MX

MA

AHX

AHP

ID MODELS

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 85: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2044 V/S Air Handler – Single Stage Heat Pump (Demand Defrost)

MV

AV

ID MODELS

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

DEMAND DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP = Legacy

67297 = 031-01975

2

2

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 86: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2045 Single Stage PSC Furnace – Single Stage Heat Pump (Timed Temp)

GY8S

TG(8,L)S

TG9S

ID MODELS

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

C24 – Volt Common

R24 – Volt Hot

WFull Stage Heat

Y / Y2First

Stage Compressor

SINGLE STAGE PSCFURNACE

GFan

SINGLE STAGEPSC

FURNACE

Part Number:SAP

539617

1

1

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Jumper 2 must be set to “O”

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set “ON”

Suggestion: For optimal operation add an OD temp sensor.

036-31114-001-E-0411

Page 87: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2047 Modulating Furnace – Single Stage Heat Pump (Timed Temp)

(Y,L,C)*(8,L)C

T*(8,L)C

T*9C

(Y,L,C)*9C

ID MODELS

TM9M

YM9M

YM(8,L)M

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

MODULATINGFURNACE CONTROL

GFan

MODULATINGFURNACE

Y/Y2Second or Full

Stage Compressor

DHUMDehumidification-

Open on Humidity Rise

WModulating Heat

Move HUMIDISTATjumper to “YES”

if humidistat is to be used.

LO COMPSingle Stage

Compressor (OUT)

OReversing Valve

Energized in Cool

HI COMPSecond Stage

Compressor (OUT)

1

Part Number’s:SAP

364809364810

1

HEATPUMP jumper must be set to “YES”

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Jumper 2 must be set to “O”

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set “ON”

Suggestion: For optimal operation add an OD temp sensor.

036-31114-001-E-0411

Page 88: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2047 Single Stage Furnace (X-13) – Single Stage Heat Pump (Timed Temp)

T*(8,L)X

TM9X

ID MODELS

C24 – Volt Common

R24 – Volt Hot

Y1First Stage Compressor

SINGLE STAGE FURNACE (X-13)

GFan

SINGLE STAGE FURNACE (X-13)

Y/Y2Second or Full

Stage Compressor

WFirst Stage Heat

1

Part Number:SAP

542760

1

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM

GFan

S1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM

Fault

C24 – Volt Common

Suggestion: Set setup step 26 “2nd Stage

Deadband” and step 29 “Minutes Between 1st

and 2nd” to 0.

Jumper 2 must be set to “O”

Jumper 3 must be set to “GAS”

Jumper 1 must be set to “HEATPUMP”

Setup Step 50 “Dual Fuel” must be set “ON”

Suggestion: For optimal operation add an OD temp sensor.

036-31114-001-E-0411

Page 89: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2048 PSC Air Handler – Single Stage Heat Pump (Timed Temp)

F*FP

ID MODELS

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

036-31114-001-E-0411

Page 90: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2049 V/S Air Handler – Single Stage Heat Pump (Timed Temp)

F*FV

ID MODELS

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIME TEMPDEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

3

3

036-31114-001-E-0411

Page 91: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2050 PSC Air Handler – Single Stage Heat Pump (Timed Temp)

MX

MA

AHX

AHP

ID MODELS

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

036-31114-001-E-0411

Page 92: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2051 V/S Air Handler – Single Stage Heat Pump (Timed Temp)

MV

AV

ID MODELS

Jumper 2 must be set to “O”

Jumper 3 must be set to “ELEC”

Jumper 1 must be set to “HEATPUMP”

Y1First Stage

Compressor

W2Second Stage Heat

W1/O/BFirst Stage Heat

HUM(only on S1-

THSU32HP7b)

GFan

S1-THSU32P7bS1-THSU32HP7b

THERMOSTAT

W3Third Stage Heat

R24 – Volt Hot

Y2Second StageCompressor

DHUM(only on S1-

THSU32HP7b)

Fault

C24 – Volt Common

Setup Step 24 “Number Of Compressor Stages”

must be set “1”

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

036-31114-001-E-0411

Page 93: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2052 PSC Air Handler – Single Stage Heat Pump (Timed Temp)

F*FP

ID MODELS

PSCAIR HANDLER

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

(O)Reversing Valve

Energized in Cool

PSCAIR HANDLER

CONTROL

GFan

( ) Convenience Terminal

No function in thisapplication

Refer to AH documentation

for W1 and W2 electricheat staging options.

Part Numbers:SAP = Legacy

10160 = 031-01264

1

1

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

036-31114-001-E-0411

Page 94: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2053 V/S Air Handler – Single Stage Heat Pump (Timed Temp)

F*FV

ID MODELS

C24 – Volt Common

R24 – Volt Hot

W1First Stage Heat

W2Second Stage Heat

YSecond or Full

Stage Compressor

10160 Air Handler Control

GFan

VARIABLE SPEED

AIR HANDLER

(X/L)Malfunction Light

HUMDehumidification

(Y2)Second StageCompressor

Y1First Stage

Compressor

13690 CFM Control

Must remove “Humidistat”

jumper on CFM controlif a humidistat is to be

used

Refer to AH documentation

for W1 and W2 electricheat staging options.

( ) Convenience Terminal

No function in thisapplication

Part Numbers:SAP = Legacy

10160 = 031-01264Part Numbers:

SAP = Legacy13690 = 031-01958

1

(O)Reversing Valve

Energized in Cool

2

1

2

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

3

3

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

036-31114-001-E-0411

Page 95: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2054 PSC Air Handler – Single Stage Heat Pump (Timed Temp)

MX

MA

AHX

AHP

ID MODELS

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

PSCAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

PSCAIR HANDLER

Part Numbers:SAP = Legacy

159480 = 031-09156

1

Move HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 96: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

2055 V/S Air Handler – Single Stage Heat Pump (Timed Temp)

MV

AV

ID MODELS

24VAC Humidifier(Optional)

24VACElectronic Air Cleaner

(Optional)

Y1First

Stage Compressor

COM24 – Volt Common

R24 – Volt Hot

GFan

W2Second Stage Heat

OReversing Valve

Energized in Cool

X/LMalfunction Light

HUMHumidity Switch

Open on Humidity Rise

VARIABLE SPEEDAIR HANDLER

CONTROL

Y/Y2Second or Full

Stage Compressor

W1First Stage Heat

EAC(24 VAC out)

Electronic Air Cleaner

HUM OUT(24 VAC out)

Humidifier

1

VARIABLE SPEED

AIR HANDLER

Part Number:SAP

536805

1

Move the HUM STATjumper to “YES”

if humidistat is to be used.

Refer to AH documentation

for W1 and W2 electricheat staging options.

OReversing Valve

Energized in Cool

C24 – Volt Common

R24 – Volt Hot

W1/66(out)Heat

YCompressor

TIMED TEMP DEFROSTCONTROL

X/LMalfunction Light

WAuxiliary Heat

SINGLE STAGEHEAT PUMP

Part Numbers:SAP

18390

2

2

YFirst Stage

Compressor

OReversing Valve

Energized in Cool

GFan

S1-THEH21P5bS1-THEH21Nb

THERMOSTAT

R24 – Volt Hot

W Auxiliary Heat

C24 – Volt Common

Common Wire is optional when batteries

are used.

External Humidistat(Optional)

Open on Humidity Rise

3

Part Number:S1-2HU16700124

3

036-31114-001-E-0411

Page 97: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

036-31114-001-E-0411

Page 98: Visio-036-31114-001-E-0411 - UPGNET · 036-31114-001-E-0411 Indoor Unit Outdoor Unit Special Application Note Two Stage V/S Furnace Single Stage Heat Pump (YGVI control) Modulating

Johnson Controls Unitary Products5005 York Drive

Norman, OK 73069

Subject to change without notice. Published in U.S.A. 036-31114-001-E-0411Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 036-31114-001-D-0610