BROAD Central Air Conditioning TerminalsDesign & Model selection Manual
■ Product category
● Fan coils cooling capacity: 1.8-25kW area coverage: 10-300m2
● Air handlers cooling capacity: 25-250kW area coverage: 200-4,000m2
fresh air flow: 3,250-32,500m3/h for fresh air demand of 160-1,600 people ● Fresh air units fresh air flow : 50-40,000m3/h for fresh air demand of 2-2,000 people ● Hot water tanks capacity: 100-200 liters
■ Applications
● Fan coils for all kinds of rooms● Air handlers for big rooms as well as a whole building● Fresh air units supply fresh air for a single room or a
whole building● Hot water tanks couple with BROAD villa air
conditioning or other hot water supply equipment (primary heating
water heats up city water in the tank)
CONTENTS
Fan coils
GeneralP&I diagramSpecificationsPerformance curves Model selectionAccessories and supply scopeDimensionsInstallation tips
Air handlers
GeneralSpecificationsPerformance curves Accessories and supply scopeDimensionsInstallation tips
Fresh air units
GeneralSpecificationsPerformance curves Accessories and supply scopeDimensionsInstallation tips
Tips for fresh air design
Hot water tanks
SpecificationsModelsAccessories and supply scopeDimensionsInstallation tips
13489111231
333536363739
404243434445
46
5050505152
Compared with motorcar, aircraft and other industrial technologies, BROAD fan coils had nothing to be proud of. However, once you know from the following "comparativism" how much BROAD has contributed to innovations of human air conditioning technologies in the past 100 years, you will have to term it a miracle.
1
Cooling capacity:1.8~25kW Area coverage: 10~300 m2
Suitable for all kinds of rooms
Health ScienceElectrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open design, all by a slight touchAcoustics• The inverter fan is equipped with stepless frequency control. • The ultra-thin aluminum fan blade operates without noise. • If the fan is operating at low speed, you can not hear any noise
but your own breathing in serene nights. Aesthetics• Not gaudy, no show-off, not even one redundancy. Only beauty. • Metal shell and coated with top quality car paint. It will still
appear new after several decades. • 139 varieties available in any color, match well with any interior
design style. Thermodynamics • As the density of cold air is greater than that of hot air, low
position installation of fan coils saves energy dramatically, namely 30-60% in cooling and 10-40% in heating operation.
• Customers can choose from a selection of over 100 varieties for low position installation.Economics• Use a heat meter to measure air conditioning consumption, implement energy saving management, and actualize cost evaluation.• The market price of a heat meter alone is more expensive than a conventional air-con, yet its energy-saving potentials are huge.• The heat meter uses an ultrasonic flow meter to measure the flow rate accurately and constantly. It cooperates with two thermometers at Class 0.01°C to measure cold/heat energy accurately. • Record energy consumption and expenses of the moment, today, this month, this year and last year.Engineering• All pipe fittings that were previously site mounted are now installed in the factory. • Factory fabrication eliminates quality risks and avoids redoing. • Achieving central air conditioning industrialization. Lazybones' Philosophy• Intelligent switch enables year-round operator-free . • Auto on/off per ambient temperature saves both labor and energy.
Fan coils
Note: Features, functions and accessories of all 139 fan coil models conform to this illustration. This product is compatible to any air conditioning system and applicable to both new and replacement projects.
Comparativism• The conventional central air conditioning indoor units (fan coils)
are nothing but a combination of “fan + coil + water pan + shell + filter”. The mesh of their filters is only a little bit smaller than a matchstick. Helplessly dirty inside, they have become seedbeds for pathogens, as their interiors are completely enclosed and never cleanable.
• The conventional split units are similar to “fan coils” with only an additional temperature control. Some products have introduced so called “hi-techs” such as photocatalyst, silver ion…which are usually a hoax.
General
Conventional fan coils
Conventional split units
2
P&I diagram
3
L1 L2 L3 L4
BBA RFM
YK XK
T2 T1 C H
dirty air inlet
SNKZDW
SS
power supply
CCQYA ZMK
HXT CDY
T4F1
F3
T3
CFK
GLQUSSP
EM A/C water supply
RSMJK
DRVFJ
condensate outlet
F2
XFN
PG
clean air outletcoarse filter
electrostatic cleaner
active carbon
A/C water return
Controlled objectsF1: CCQ:
FJ:XFN: L1:L2:L3:L4:
SensorsT1:T2:T3:T4:USH:C:
Control devicesSS:SNK:DRV:CDY:
EM:XK:YK:ZMK:CFK:RSM:
JK:RFM:
BBA:
OthersPG:YA:HXT:ZDW:SP:F2:
F3:GLQ:
A/C water motor valve electrostatic cleaner (positive tungsten filament + negative aluminum plate)fanfresh air valve*1 st loop lighting control*2nd loop lighting control*3rd loop lighting control*4th loop lighting control*
indoor temp. sensoroutdoor temp. sensor*A/C water inlet temp. sensorA/C water outlet temp. sensor ultrasonic flow meter*hygrometer*CO2 sensor*
safety switchfan coil control boardmotor driveelectrostatic cleaner power supplyintegraphcontrollerremote control*lighting control board*fresh air valve control board*wired communication module*central controller*wireless communication module*Building manager and gateway*
coilauto air vent active carboncoarse filterwater collection panmanual valve (shut off and regulating)manual valve (shut off)filter
Notes:1. * indicates options2. Signal output from actuator Signal input from sensor Communication3. Either optional wired or wireless
communication.
No. NameCode
Cooling
capacity
kW
Air
Āow
m3/h
Water
Āow
kg/h
Water
resist-
ance
kPa
Min.
noise
level
dB(A)
Max.
noise
level
dB(A)
Power
demand
W
Weight
kg
Dimensions
(L×W×H)
mm
A/C
W.
pipe
mm
Conden-
sate
pipe
mm
Air
distance
Energy
saving
rating
Installa-
tion
height
mm
Applica-
tions
1 Thin 1.8 360 221 30 23 37 45 18 1140x180x307 DN15 Φ16
m
200
2 2.7 540 331 30 25 39 50 23 1500x180x307 DN15 Φ16
a
above
3 AA 3.6 720 442 30 27 41 78 28 1800x180x307 DN15 Φ16 floor
4 Curve 1.8 360 221 30 23 37 45 16 1140x180x330 DN15 Φ16 8
5 2.7 540 331 30 25 39 50 20 1500x180x330 DN15 Φ16
a
6 AD 3.6 720 442 30 27 41 78 26 1800x180x330 DN15 Φ16
7 Bend 1.8 360 221 30 23 37 45 17 1140x195x328 DN15 Φ16 8
8 2.7 540 331 30 25 39 50 24 1500x195x328 DN15 Φ16
b
1800
9 AG 3.6 720 442 30 27 41 78 28 1800x195x328 DN15 Φ16 ~2000
10 Semi- 1.8 360 221 30 23 37 45 18 1140x195x355 DN15 Φ16 8 above
11 circle 2.7 540 331 30 25 39 50 25 1500x195x355 DN15 Φ16
b
floor
12 *AJ 3.6 720 442 30 27 41 78 29 1800x195x355 DN15 Φ16
13 Triangle 1.8 360 221 30 23 37 45 19 1140x270x375 DN15 Φ16 8
14 2.7 540 331 30 25 39 50 26 1500x270x375 DN15 Φ16
b
15 *AM 3.6 720 442 30 27 41 78 30 1800x270x375 DN15 Φ16
16 L.Thin 1.8 360 221 30 23 37 45 18 307x180x1140 DN15 Φ16 10 600
17 2.7 540 331 30 25 39 50 23 307x180x1500 DN15 Φ16
b
above
18 AB 3.6 720 442 30 27 41 78 28 307x180x1800 DN15 Φ16 floor
19 R.Thin 1.8 360 221 30 23 37 45 18 307x180x1140 DN15 Φ16 10 for
20 2.7 540 331 30 25 39 50 23 307x180x1500 DN15 Φ16
b
1.8kW
21 AC 3.6 720 442 30 27 41 78 28 307x180x1800 DN15 Φ16
22 L.Curve 1.8 360 221 30 23 37 45 16 330x180x1140 DN15 Φ16 10 350
23 2.7 540 331 30 25 39 50 20 330x180x1500 DN15 Φ16
b
above
24 AE 3.6 720 442 30 27 41 78 26 330x180x1800 DN15 Φ16 floor
25 R.Curve 1.8 360 221 30 23 37 45 16 330x180x1140 DN15 Φ16 10 for
26 2.7 540 331 30 25 39 50 20 330x180x1500 DN15 Φ16
b
2.7kW
27 AF 3.6 720 442 30 27 41 78 26 330x180x1800 DN15 Φ16
28 L.Bend 1.8 360 221 30 23 37 45 17 328x195x1140 DN15 Φ16 10 200
29 2.7 540 331 30 25 39 50 24 328x195x1500 DN15 Φ16
b
above
30 AH 3.6 720 442 30 27 41 78 28 328x195x1800 DN15 Φ16 floor
31 R.Bend 1.8 360 221 30 23 37 45 17 328x195x1140 DN15 Φ16 10 for
32 2.7 540 331 30 25 39 50 24 328x195x1500 DN15 Φ16
b
3.6kW
33 AI 3.6 720 442 30 27 41 78 28 328x195x1800 DN15 Φ16
34 L.Semi- 1.8 360 221 30 23 37 45 18 355x195x1140 DN15 Φ16 10
35 circle 2.7 540 331 30 25 39 50 25 355x195x1500 DN15 Φ16
b
36 *AK 3.6 720 442 30 27 41 78 29 355x195x1800 DN15 Φ16
37 R.Semi- 1.8 360 221 30 23 37 45 18 355x195x1140 DN15 Φ16 10
38 circle 2.7 540 331 30 25 39 50 25 355x195x1500 DN15 Φ16
b
39 *AL 3.6 720 442 30 27 41 78 29 355x195x1800 DN15 Φ16
40 L.Triangle 1.8 360 221 30 23 37 45 19 375x270x1140 DN15 Φ16 10
41 2.7 540 331 30 25 39 50 26 375x270x1500 DN15 Φ16
b
42 *AN 3.6 720 442 30 27 41 78 30 375x270x1800 DN15 Φ16
43 R.Triangle 1.8 360 221 30 23ß 37 45 19 375x270x1140 DN15 Φ16 10
44 2.7 540 331 30 25 39 50 26 375x270x1500 DN15 Φ16
b
45 *AO 3.6 720 442 30 27 41 78 30 375x270x1800 DN15 Φ16
Fan coils - specifications
室内机
4
Serie
s T
hin
Se
ries 8
5
Fan coils - specifications
Serie
s T
hic
k Se
ries
No. NameCode
Cooling
cap
kW
Air
Āow
m3/h
Water
Āow
kg/h
Water
resist-
ance
kPa
Min.
noise
level
dB(A)
Max.
noise
level
dB(A)
Power
demand
W
Weight
kg
Dimensions
(L×W×H)
mm
A/C
W.
pipe
mm
Conden-
sate
pipe
mm
Air
distance
Energysaving
rating
Installa-
tion
height
mm
Applica-
tions
52 Thick
DB
3.6 648 442 30 27 41 130 32 890x264x465 DN15 Φ16 12 a 250above
floor53 4.5 810 552 30 30 43 130 35 1060x264x465 DN20 Φ16
54 5.4 972 663 40 32 43 140 44 1260x264x465 DN20 Φ16
55 7.2 1296 884 40 34 45 140 50 1450x264x465 DN20 Φ16
56 9 1620 1105 40 36 48 245 61 1760x264x465 DN25 Φ16
57 12 2160 1473 50 40 50 260 70 2200x264x465 DN25 Φ16
52 L.Thick 3.6 648 442 30 27 41 130 32 465x264x890 DN15 Φ16 12 100
53 4.5 810 552 30 30 43 130 35 465x264x1060 DN20 Φ16
b
~500
54 DC 5.4 972 663 40 32 45 140 44 465x264x1260 DN20 Φ16 above
55 7.2 1296 884 40 34 46 140 50 465x264x1450 DN20 Φ16 floor
56 9 1620 1105 40 36 48 245 61 465x264x1760 DN25 Φ16
57 12 2160 1473 50 40 50 260 70 465x264x2200 DN25 Φ16
58 R.Thick 3.6 648 442 30 27 41 130 32 465x264x890 DN15 Φ16 12
59 4.5 810 552 30 30 43 130 35 465x264x1060 DN20 Φ16
b
60 DD 5.4 972 663 40 32 45 140 44 465x264x1260 DN20 Φ16
61 7.2 1296 884 40 34 46 140 50 465x264x1450 DN20 Φ16
62 9 1620 1105 40 36 48 245 61 465x264x1760 DN25 Φ16
63 12 2160 1473 50 40 50 260 70 465x264x2200 DN25 Φ16
64 Oval 3.6 648 442 30 27 41 130 36 1080x264x600 DN15 Φ16 12 1500
65 5.4 972 663 40 32 45 140 44 1480x264x660 DN20 Φ16
b
above
66 DQ 9 1620 1105 40 36 48 245 63 2000x264x680 DN25 Φ16 floor
67 12 2160 1473 50 40 50 260 78 2460x264x760 DN25 Φ16
68 L.Oval 3.6 648 442 30 27 41 130 36 600x264x1080 DN15 Φ16 15 Central
69 5.4 972 663 40 32 45 140 44 660x264x1480 DN20 Φ16
b
line
70 DR 9 1620 1105 40 36 48 245 63 680x264x2000 DN25 Φ16 1,200
71 12 2160 1473 50 40 50 260 78 760x264x2460 DN25 Φ16 ~1,600
72 R.Oval 3.6 648 442 30 27 41 130 36 600x264x1080 DN15 Φ16 15 above
73 5.4 972 663 40 32 45 140 44 660x264x1480 DN20 Φ16
b
floor
74 DS 9 1620 1105 40 36 48 245 63 680x264x2000 DN25 Φ16
75 12 2160 1473 50 40 50 260 78 760x264x2460 DN25 Φ16
76 Long- 7.2 1296 884 40 34 46 300 53 1450x304x465 DN20 Φ16 20 1800
77 rangeDE
12 2160 1473 50 40 50 450 79 2200x304x465 DN25 Φ16
c
abovefloor
78 Vertical 7.2 1296 884 40 34 46 300 53 465x304x1450 DN20 Φ16 20 100
79 Long- 12 2160 1473 50 40 50 450 79 465x304x2200 DN25 Φ16
b
~1,000
range above
DF floor
6
Serie
s W
all
Built
-in S
erie
s A
van
t-g
ard
e S
erie
s
No. NameCode
Cool-
ing
capa-
city
kW
Air
Āow
m3/h
Water
Āow
kg/h
Water
resist-
ance
kPa
Min.
noise
level
dB(A)
Max.
noise
level
dB(A)
Power
demand
W
Weight
kg
Dimensions
(L×W×H)
mm
A/C
W.
pipe
mm
Conden-
sate
pipe
mm
Air
distance
Energy
saving rating
Installa-
tion
height
mm
Applica-
tions
80 Piano 9 1350 1105 40 36 46 300 71 1080x430x900 DN25 Φ16 15 Floor
CC
a
standing
81 Cube 4.5 675 552 40 30 41 110 32 500x500x550 DN20 Φ16 10 Rear
82 CD 9 1350 1105 40 36 48 220 64 1000x500x550 DN25 Φ16
a
200
83 vase- 3.6 540 442 30 27 39 78 27 406x310x993 DN15 Φ16 10 against
stand*CE
a
wall
84 Diamond 3.6 720 442 30 27 41 90 36 820x180x1140 DN15 Φ16 8x2 700
85 *DP 5.4 1080 663 40 32 45 100 58 820x180x1500 DN15 Φ16
b
Above floor
86 Column 1.8 360 221 30 23 37 45 19 1020xΦ260 DN15 Φ16 8 1800
87 AP 2.7 540 331 30 25 39 50 23 1420xΦ260 DN15 Φ16
c
Above
88 3.6 720 442 30 27 41 78 30 1720xΦ260 DN15 Φ16 floor
89 Polygon 1.8 360 221 30 23 37 45 19 1020x225x290 DN15 Φ16 8
90 AR 2.7 540 331 30 25 39 50 23 1420x225x290 DN15 Φ16
c
91 3.6 720 442 30 27 41 78 30 1720x225x290 DN15 Φ16
92 Vertical 1.8 360 221 30 23 37 45 19 Φ260x1020 DN15 Φ16 10 100
93 Column 2.7 540 331 30 25 39 50 23 Φ260x1420 DN15 Φ16
b
Above
94 *AQ 3.6 720 442 30 27 41 78 30 Φ260x1720 DN15 Φ16 floor
95 Vertical 1.8 360 221 30 23 37 45 19 290x225x1020 DN15 Φ16 10 or floor
96 Polygon 2.7 540 331 30 25 39 50 23 290x225x1420 DN15 Φ16
b
standing
97 *AS 3.6 720 442 30 27 41 78 30 290x225x1720 DN15 Φ16 with a retainer
98 Jet 5.4 810 663 40 32 41 130 42 Φ600x750 DN15 Φ16 15 2000
CA
c
Above
floor
99 Wall 2.7 540 331 30 25 39 50 23 1500x210x315 DN15 Φ16 10 100
100 Built-in 3.6 720 442 30 27 41 78 31 1800x210x315 DN15 Φ16
a
Above
101 DG 4.5 810 552 30 30 43 130 36 1180x314x465 DN20 Φ16 floor
102 5.4 972 663 40 32 45 140 41 1380x314x465 DN20 Φ16
103 7.2 1296 884 40 34 46 140 50 1570x314x465 DN20 Φ16
104 9 1620 1105 40 36 48 245 55 1920x314x465 DN25 Φ16
105 12 2160 1473 50 40 50 260 74 2363x314x465 DN25 Φ16
106 L.Wall 2.7 540 331 30 25 39 50 23 315x210x1500 DN15 Φ16 10
107 Built-in 3.6 720 442 30 27 41 78 31 315x210x1800 DN15 Φ16
b
108 DH 4.5 810 552 30 30 43 130 36 465x314x1180 DN20 Φ16
109 5.4 972 663 40 32 45 140 41 465x314x1380 DN20 Φ16
110 7.2 1296 884 40 34 46 140 50 465x314x1570 DN20 Φ16
111 9 1620 1105 40 36 48 245 55 465x314x1920 DN25 Φ16
112 12 2160 1473 50 40 50 260 74 465x314x2363 DN25 Φ16
113 R.Wall 2.7 540 331 30 25 39 50 23 315x210x1500 DN15 Φ16 10
114 Built-in 3.6 720 442 30 27 41 78 31 315x210x1800 DN15
b
115 DI 4.5 810 552 30 30 43 130 36 465x314x1180 DN20 Φ16
116 5.4 972 663 40 32 45 140 41 465x314x1380 DN20 Φ16
117 7.2 1296 884 40 34 46 140 50 465x314x1570 DN20 Φ16
118 9 1620 1105 40 36 48 245 55 465x314x1920 DN25 Φ16
119 12 2160 1473 50 40 50 260 74 465x314x2363 DN25 Φ16
120 Wall Built 5.4 972 663 40 32 45 168 40 465x314x1380 DN20 Φ16 15
121 in Duct 9 1620 1105 40 36 48 310 66 465x314x1920 DN25 Φ16
b
122 DJ 12 2160 1473 50 40 50 450 71 465x314x2363 DN25 Φ16
123 Floor 3.6 720 442 30 27 39 78 35 1800x331x269 DN15 Φ16 6 Floor
124 DM 12 2160 1473 50 40 50 260 74 2363x511x377 DN25 Φ16
b
level
m
No. NameCode
Cool-
ing
capa-
city
kW
Air
Āow
m3/h
Water
Āow
kg/h
Water
resist-
ance
kPa
Min.
noise
level
dB(A)
Max.
noise
level
dB(A)
Power
demand
W
Weight
kg
Dimensions
(L×W×H)
mm
A/C
W.
pipe
mm
Conden-
sate
pipe
mm
Air
distance
Energy
saving rating
Installa-
tion
height
mm
Applica-
tions
125 Ceiling 4.5 810 552 30 30 41 140 50 1020x1020x190 DN15 Φ16 10 Ceiling
126 Square 7.2 1296 884 40 34 45 140 70 1020x1020x270 DN20 Φ16
d
mounted
*DN
127 Wing 4.5 810 552 30 30 41 168 37 1200x880x315 DN20 Φ16 15
128 *DO 7.2 1296 884 40 34 45 300 56 1600x880x315 DN20 Φ16
d
129 Ceiling Built- 4.5 810 552 30 30 43 168 35 1180x465x314 DN20 Φ16 15 Ceiling
130 in Duct 5.4 972 663 40 32 45 178 40 1380x465x314 DN20 Φ16
d
mounted and
131 DK 12 2160 1473 50 33 50 460 74 2363x465x314 DN25 Φ16 connected to air ducts
132 Ceiling 2.7 540 331 30 25 39 60 29 1500x315x210 DN15 Φ16 6 Ceiling
133 Built-in 4.5 810 552 30 30 43 140 34 1180x465x314 DN20 Φ16
d
mounted
134 DL 5.4 972 663 40 32 45 150 40 1380x465x314 DN20 Φ16
135 12 2160 1473 50 33 48 270 74 2363x465x314 DN25 Φ16
136 High 18 2700 2210 55 32 50 450 238 840x380x2590 DN25 Φ20 25 Inside
137 Board 25 3750 3100 60 34 53 620 298 840x380x3200 DN32 Φ20
b
the hall,
EH at wall
138 High 18 2700 2210 55 32 50 450 226 530x530x2590 DN25 Φ20 corner or
139 Stripe 25 3750 3100 60 34 53 620 282 530x530x3200 DN32 Φ20 against
*EK the wall
7
residences hotelrooms
officebuildings theatres hospitals
shops,restaurants,public places
publicpassages
airports,exhibition halls,supermarkets,lobbies
Notes:1. Rated conditions for cooling: inlet air dry bulb temperature: 27 oC, wet bulb temperature: 19.5 oC, chilled water outlet/inlet temperature: 14/7 oC rated conditions for heating: inlet air dry bulb temperature: 21 oC, heating water outlet/inlet temperature: 55/65 oC2. Heating capacity is 1.5 times of cooling capacity3. Noise level is measured 1m distance from the unit4. “Left” or “right” refers to air blow direction. Arrow indicates the angle between blow direction and installation plane. 45° downwards 0° downwards 45° leftwards 45° rightwards 0° leftwards 0° rightwards5. Energy saving rating a: 30~60%, b: 20~40%, c: 10~30%, d: 0% (comparison with conventional ceiling mounted fan coils. Higher the room, more energy saving)6. * means standard lights, and ※ means optional lights.
7. Nomenclature: code letter + cooling capacity(kW), e.g. 2.7kW thin model is named as AA2.78. Back pressure for wall built-in duct and ceiling built-in models: 4.5 kW:50Pa, 5.4 kW:55Pa, 12 kW:65Pa9.
Symbols for recommended applications:
Fan coils - specifications
Serie
s C
eili
ng
bu
ilt-in
Se
ries
Larg
e S
erie
s
m
0 20 40 60 80 100 120
Air flow %
140
100
50
DJ/DK12
DJ/DK5.4
DJ/DK4.5
Accessories(optional)
Common Colors (light paint)
8
Performance curves
Chilled water temperature vs.Cooling capacity
Chilled water flowrate vs. Cooling capacity
Air flow vs. static pressure (for wall built-in duct and ceiling built-in duct models)
140
120
100
80
60
40
23 24 25 26 27 28
Return air temp. ℃
5℃
6℃
7℃
8℃
9℃
10℃
100
95
90
85
80
75
7050 60 70 80 90 100
Flowrate %
Co
olin
g c
ap
ac
ity %
Co
olin
g c
ap
ac
ity %
Exte
rna
l sta
tic p
ress
ure
Pa
Wine red
Lilac
Ferrari yellow
Light brownish
Black
Skin
Ocean blue
Silver grey
Antique brass
Medium grey
Orange
Forest green
No. Name Applicable to Function
1 Retainer Vertical Column,
Vertical Polygon
for floorstandingfan coils
2 cone-tube supporter
Vertical Column,
Vertical Polygon
for floorstandingfan coils
3 Remote control
1 for each room or 1 for every
3 fan coils is recommended
control thefan coil and
lighting
4 Remote control socket
Remote control hold remote control
5 4-loop lighting control
Fan coils lighting remote control
6 Outdoor thermometer
Fan coils, air handlers
on/off per ambient
temperature
7 CO2 sensor price reduction if not selected
oxygen deficiency
alarm
8 Ultrasonicflowmeter
price reduction if not selected
energy metering
9 Wired communication module
Fan coils, air handlers
central control
10 Fresh air valve control Fan coils Control freshair valve
11 Bracket Thin,Curve, Thick models
For occasions where wall mounting is not possible
12 Bracket All vertically installed models
(i.e. left / right models)
13 Diagonal/ flat grille cover all models for concealed installation
(cellular coveris the standard)
interior decoration
14 Common colors all models matching the interior design
15 Optional colors and shell material
all models matching the interior design
LoadBROAD standard: 40-70W/m2 for apartments or hotels; 50-80W/m2 for offices; 60-90W/m2 for villas; 80-130W/m2 for shops ,restaurants or lobbies; 130-210W/m2 for theatres, exhibition halls or airports. High load is to be designed for places of high population density, high storey and high ratio of wall to floor area, and places of temporary use (quicker air conditioning effect can be achieved). The total cooling load of fan coils(including fresh air load) could be 15%-30% higher than that of the chiller. Fan coil selection is upon actual demand and doesn’t allow any redundancy. In case it’s insufficient, a fan coil of exposed installation can be easily replaced with a larger model.
QuantityUsually one for each room. 2 units can be considered for room over 100m2. More units make higher investment.
Style Usually a suitable fan coil is readily available to match the interior design once the interior design style is confirmed. The standard color is recommended. If customers want to change it even during the installation, it can be easily replaced with a cover of required color.
Energy savingLow position installation at wall corner can save 30%-60% energy compared with ceiling-mounted installation. Do not select ceiling suspended or ceiling built-in models except for the replacement of old system. Vertical models can be considered for rooms with limited space. Furthermore, heat meters may help facilitate behavioral energy saving greatly.
CostLow position installation of fan coils not only saves operating cost, but also reduces huge investment 1. reduce fan coil load 2. reduce chiller load3. save pipeline and installation cost 4. save building height.
ComfortSome people are even sensitive to very slight noise. If the inverter-controlled motor is adopted, no noise can be heard at low speed. Actually 90% of time air conditioning systems are operating under partial load. The units cannot blow straightly to places where people usually stay.
Features BROAD fan coils consist of 6 series & 139 varieties. A careful study of their features should be made before selection.Product photos and typical applications are available in our catalog.
• Thin series The delicate styled thin series fan coils have a great varieties and present vivid individualities. They can cover an area from 10-200m2. The prices are relatively higher. Curve and Thin Models are recommended for energy saving.Cooling capacity: 1.8kW, 2.7kW, 3.6kWHeating capacity: 2.7kW, 4kW, 5.4kWArea coverage: 10-50m2
• Thick seriesThick series with magnificent styles can serve an area of 20-1500m2. Their prices (per kW or RT cooling capacity) are relatively low. They are not only suitable for low-end places but also medium and up-market locations, especially the Oval Model with specially ordered cover ( such as mirror stainless steel cover, brushed stainless steel cover, or even the luxurious titanium cover). Thick Model is recommended as the priority, which is the most energy saving.Cooling capacity: 3.6kW,4.5kW,5.4kW,7.2kW, 9kW,12kWHeating capacity: 5.4kW,6.9kW,8.1kW,10.8kW, 13.5kW,18kWArea coverage: 20-160m2
• Avant-garde seriesVarious varieties with unique characteristics are completely different from conventional fan coils. They are suitable for places from 10-500m2, and with higher prices. Vertical Column Model and Polygon Model can be wall-mounted or at wall corner, or floor-standing with a retainer (1.8kW model even can be equipped with a cone-tube supporter). In this series Piano Model is recommended as the first choice, as it is suitable for most places with easy installation, small space occupancy (based upon cooling capacity) and energy saving. It can be multi-functional: a food table, a TV set stand, a podium, a reception desk or even a bar counter.Cooling capacity: 1.8kW,2.7kW,3.6kW,4.5kW, 5.4kW,9kWHeating capacity: 2.7kW,4kW,5.4kW,6.8kW, 8.1kW,13.5kWArea coverage: 10-120m2
99
Fan coils - model selection
• Wall built-in seriesSimplicity is the style, and it can serve an area of 15-500m2. Either wall built-in, floor built-in, or cabinet built-in, especially suitable for complicated public areas. Cellular cover is standard for Wall Built-in Model, but grille cover or diagonal grille cover is optional. Wall Built-in Model is recommended as the first choice for its energy saving. In addition, Wall Built-in Duct Model can connect multiple air ducts up to 2~6 rooms. In this case the initial cost and installation cost are reduced dramatically, which even can be affordable for low-cost houses (ducts are not long, not much dust inside, furthermore, the electrostatic cleaner can kill more than 90% bacteria inside).Cooling capacity: 2.7kW, 3.6kW, 4.5kW, 5.4kW, 7.2kW, 9kW, 12kWHeating capacity: 4kW, 5.4kW, 6.8kW, 8.1kW, 10.8kW, 13.5kW, 18kWArea coverage: 15~160m2
• Ceiling built-in seriesBROAD does not recommend this series due to its non energy saving (fan coils are highly ceiling built-in and whole room space consumes energy). It can be adopted to replacement for old buildings where all the fan coils are ceiling built-in. A special note: this series is not suitable for rooms of 3m+ high because of too much energy waste as well as initial cost waste( the model size of chiller and fan coils has to be increased).In addition, cellular cover is standard for Ceiling Built-in Model and CeilingBuilt-in Duct Model, but flat grille cover or diagonal grille cover is optional.Cooling capacity: 2.7kW, 4.5kW,5.4kW, 7.2kW, 12kWHeating capacity: 4kW, 6.8kW, 8.1kW, 10.8kW,18kWArea coverage: 15-100m2
• Large seriesThe style is designed to impress and inspire. It can serve any spacious area larger than 100m2 with 25m far-reaching air blow. It can be installed at the center or against wall. High Stripe Model even can be at the corner. Both sides of High Board Model have covers accessible to maintenance. It can be used as a billboard. The only inconvenience is that a ladder is needed for maintenance.Cooling capacity: 18kW, 25kWHeating capacity: 27kW, 37.5kWArea coverage: 100~300m2
Options
• CO2 sensorCustomers can select one piece only if several fan coils are installed in the room.
• Ultrasonic flow meterIt can be skipped if the customer doesn’t want to have air conditioning billing and energy saving management.
• Outdoor temp. sensorCustomer can select 1 piece if several fan coils are installed in the room. It is not necessary for a building of closed type which can not be cooled down by opening windows or fresh air.
• Lighting remote controlEach fan coil can control 4 lighting loops. It is not necessary if the customer doesn’t want to control lighting by fan coil remote control or implement illumination management for energy saving through BMS.
• Fresh air valve controlEach fan coil has optional 3-position control interface for fresh air valve upon CO2 concentration.
• Color"Standard" colors of each type are indicated on the first page of each series in the catalog of ‘REDEFINE LIFE’. 7% additional price to be charged for “basic” colors. “optional” colors can be offered on case base, but the additional cost may be very high. Colors can be mixed according to customer’s color palette. Special materials are also available for special orders, such as gold-plating in right figure (it is very expensive with long lead time)
• Remote controlIt controls not only temperature and air speed, but also the room lighting. We recommend one for each room. If several fan coils are installed in a room, one for every three fan coils is recommended. It may not be necessary for public places like hotel rooms.
1010
ModelName
Cooling Capacity
kW
Expansion bolt Controller
(pc)
Controller holder
(pc)
Active carbon
(pc)
Bellow with sealing gasket
Braze welded ends
Pre-installed valve
Specsmm
Qnty(pc)
Specsmm
Lengthmm
Qnty(pc)
Specsmm
Qnty(pc)
Specsmm
Qnty(pc)
Thin Series 1.8/2.7/3.6 M6×80 4 1 1 4 DN15 200 2 15 2 DN15 1
Thick
3.6 M8×80 4 1 1 4 DN15 200 2 15 2 DN15 1
4.5/5.4/7.2 M8×80 4 1 1 4 DN20 200,150 1 each 22 2 DN20 1
9/12 M8×80 4 1 1 4/6 DN25 200,150 1 each 28 2 DN25 1
L.Thick 3.6 M8×80 4 1 1 4 DN15 150,300 1 each 15 2 DN15 1
4.5/5.4/7.2 M8×80 4 1 1 4 DN20 150,300 1 each 22 2 DN20 1
9/12 M8×80 4 1 1 4/6 DN25 150,300 1 each 28 2 DN25 1
R.Thick 3.6 M8×80 4 1 1 4 DN15 200 2 15 2 DN15 1
4.5/5.4/7.2 M8×80 4 1 1 4 DN20 200 2 22 2 DN20 1
9/12 M8×80 4 1 1 4/6 DN25 200 2 28 2 DN25 1
Oval R.Oval
3.6 M8×80 4 1 1 4 DN15 200 2 15 2 DN15 1
5.4 M8×80 4 1 / 4 DN20 200 2 22 2 DN20 1
9/12 M8×80 4 1 / 4/6 DN25 200 2 28 2 DN25 1
L.Oval 3.6 M8×80 4 1 1 4 DN15 200,300 1 each 15 2 DN15 1
5.4 M8×80 4 1 / 4 DN20 200,300 1 each 22 2 DN20 1
9/12 M8×80 4 1 / 4/6 DN25 200,300 1 each 28 2 DN25 1
Long-range 7.2 M8×80 4 1 1 4 DN20 200 2 22 2 DN20 1
12 M8×80 4 1 / 6 DN25 200 2 28 2 DN25 1
Vertical long-range
7.2 M8×80 4 1 1 4 DN20 200,250 1 each 22 2 DN20 1
12 M8×80 4 1 / 6 DN25 200,250 1 each 28 2 DN25 1
Piano 9 M8×80 4 1 1 4 DN25 300.500 1 each 28 2 DN25 1
Cube 4.5 M6×80 4 1 1 4 DN20 200,300 1 each 22 2 DN20 1
9 M6×80 4 1 1 4 DN25 200,300 1 each 28 2 DN25 1
Vase-stand 3.6 M6×80 4 1 1 4 DN15 200 2 15 2 DN15 1
Diamond 3.6 M6×80 8 2 2 4 DN15 200 4 15 4 DN15 2
5.4 M6×80 8 2 2 4 DN15 200 4 15 4 DN15 2
Column Polygon
1.8/2.7/3.6 M6×80 4 1 1 4 DN15 150 2 15 2 DN15 1
Jet 5.4 M10×80 4 1 / 4 DN15 200 2 15 2 DN15 1
Wall Built-in 2.7/3.6 M6×80 4 1 / 4 DN15 200 2 15 2 DN15 1
4.5/5.4/7.2 M8×80 4 1 / 4 DN20 250 2 22 2 DN20 1
9/12 M8×80 4 1 / 4/6 DN25 250 2 28 2 DN25 1
L.Wall Built-inR.Wall Built-in
2.7/3.6 M6×80 4 1 / 4 DN15 200 2 15 2 DN15 1
4.5/5.4/7.2 M8×80 4 1 / 4 DN20 250,300 1 each 22 2 DN20 1
9/12 M8×80 4 1 / 4/6 DN25 250,300 1 each 28 2 DN25 1
Wall Built-in Duct
5.4 M8×80 4 1 / 4 DN15 250,300 1 each 22 2 DN15 1
9/12 M8×80 4 1 / 4/6 DN25 250,300 1 each 28 2 DN25 1
Floor 3.6 M6×80 4 1 / 4 DN15 150,200 1 each 15 2 DN15 1
12 M8×80 4 1 / 6 DN25 350,200 1 each 28 2 DN25 1
CeilingSquare
4.5 M8×80 8 1 / 4 DN15 200 2 15 2 DN15 1
7.2 M8×80 8 1 / 4 DN20 200 2 22 2 DN20 1
Wing 4.5/7.2 M8×80 4 1 / 4 DN20 150,250 1 each 22 2 DN20 1
Ceiling Built-in Duct
4.5/5.4 M8×80 4 1 / 4 DN20 200 2 22 2 DN20 1
12 M8×80 4 1 / 6 DN25 200 2 28 2 DN25 1
CeilingBuilt-in
2.7 M6×80 4 1 / 4 DN15 200 2 15 2 DN15 1
4.5/5.4 M8×80 4 1 / 4 DN20 200 2 22 2 DN20 1
12 M8×80 4 1 / 6 DN25 200 2 28 2 DN25 1
Large Series 18 M12×100 4 1 1 12 DN25 200 2 28 2 DN25 1
25 M12×100 4 1 1 16 DN32 200 2 35 2 DN32 2
Note:1. Two pieces of 300mm bellow will be supplied for Thick models if installed with bracket.2. Two pieces of 400mm bellow will be supplied for Vertical Column models if installed with cone-tube supporter .3. Pre-installed valve and braze welded ends will be delivered before the system installation.
11
Fan coils - accessories and supply scope
Ce
ilin
g b
uilt
-in S
erie
s W
all
Built
-in S
erie
s A
van
t-g
ard
e S
erie
s T
hic
k Se
ries
Thin Series
Curve Model AD
Thin models enlarged scheme of pipe connection
Thin AA Triangle AM Semicircle AJ Bend AG
Thin Series
12
Note:dimension units are in mm, and it is the same on the following pages.
Fan coils - dimensions
Vertical Thin Series
Vertical Thin enlarged scheme of pipe connection
Left Curve Model AE
Left Bend Model AH
Left Semicicle Model AK
Left Thin Model AB
13
Left Triangle Model AN
Thin Series
L.Thick Model, R.Thick Model DC, DD
Thick Model DB
14
Thick Series
Oval Model DQ
L.Oval Model, R.Oval Model DR, DS
15
Thick Series
Long-range Model DE
Vertical Long-range Model DF
16
Piano Model CC
17
Avant-garde Series
Vase-stand Model CE
Cube Model CD
18
Diamond Model DP
Jet Model CA
19
Avant-garde Series
Column Model AP
Vertical Column Model AQ(wall-mounted and wall corner installation)
20
Polygon Model AR
Vertical Polygon Model AS(wall-mounted and wall corner installation)
21
Avant-garde Series
Floor standing vert ical column & polygon1.8kW instal lat ion with cone tube supporter
2.7kW, 3.6kW Vertical Column Model (installation with tray supporter)
22
Wall Built-in Model DG
2.7kW, 3.6kW
4.5kW~12kW
23
Wall Built-in Series
Left Wall Built-in Model, Right Wall Built-in Model DH, DJ
4.5~12kW2.7, 3.6kW
24
Wall Built-in Duct Model DJ
25
Wall Built-in Series
Floor Model DM3.6kW
12kW
26
Ceiling Square Model DN
Wing Model DO
27
Ceiling Built-in Series
Ceiling Built-in Model DL 2.7kW
4.5kW, 5.4kW, 12kW
28
Ceiling Built-in Duct Model DK
High Board Model EH
29
Large Series
High Stripe Model EK
30
A. Tips for installation location①Placed high in offices stuffed with desks.②Placed low in high-storey rooms. ③Do not select ceiling built-in models for those
places with rigid cleaning requirements such as hospitals, micro-electronics workshops, bedrooms, etc.
④The place should be good for air circulation of the whole room, and the air outlet cannot face people or bed straightly.
⑤Match the decoration and do not affect the room aesthetics.
⑥Convenient for pipe connection and condensate drain.
⑦Easy for maintenance. B. Tips for piping and wiring pre-installation① Pipes must be laid during construction period.② Copper tubes must be adopted in supply/ return
water pipes. Low temperature braze welding is recommended in connecting the pipes. The A/ C W. pipes should be covered with rubber plastic cold insulation material and non-metal tubes can be used for condensate pipe.
③BROAD pre-installed valve should be installed at the end of pipeline. Water supply valve is also a flow regulating valve which can balance the flowrate of each fan coil. It also has a shutoff function which facilitates filter washing. Filter must be re-fixed after washing.
Note: Please follow the marks to install and make sure not to mix up the supply & return W. pipes, otherwise the coils will be blocked!
④ After completion of whole building installation, keep the chilled water pump running
continuously for min. 5 days to accumulate impurities at each filter. Wash the filters before the Fan Coils are installed.
Installation items
BROAD Fan Coil Installation Tips
Installation proceduresA LocatingThe designer selects fan coils and decides their installation locations according to room function and decoration style to facilitate the pre-installation work like piping and wiring.
B Pre-installed piping and wiringDuring the construction, A/C water supply & return pipe (with pre-installed valve), condensate pipe, power supply cable, lighting output and outdoor thermometer cable shall be implemented to the installation place of fan coils.
C Shell installationFan coil is to be installed after the room decoration. Handle it with care to avoid any damage. Locate and drill holes on the wall against the screw holes on the shell back first, then insert expansion bolts and mount the unit.
D Pipe connectionConnect the pre-installed water supply pipe, water return pipe and condensate pipe to the fan coils. Flexible stainless steel bellow pipe can be used for water return & supply pipe.
F Lighting cable connectionLeading 9×0.75 mm2 lighting cables from fan coil wiring terminal to 4-loop lighting control can actualize coupled twin connection and control (30W for each loop). Energy efficient lamps are recommended. If the lamp power is more than 30W, an amplifier can be introduced.
H Outdoor thermometer installationLead a 2×0.3mm2 cable from fan coil wiring terminal. Install the sensor outside the window and avoid direct sunshine.
I Controller installationThe controller can be installed on a supporter supplied with the unit, or lead 3×0.15mm2 control cable from the wiring terminal and install the controller onto the wall nearby. The location should be convenient to operate and looks harmonious.
E Power connectionLead 3×1.0mm2 power cable from the wiring terminal to indoor power supply (1.5mm2 power cable to be used for ≥9kW models).
G Indoor thermometer installationLead a 2×0.3 mm2 cable from fan coil wiring terminal and install it onto the wall 2m away from the unit (~1.3m above floor). If the thermometer is too close from the indoor unit, it may indicate air blowing temperature instead of the average room temperature.
31
W. returnvalve
Bellow for temporary circulation
Condensatepipe
W. supply valve
Water filter
Pre-installed valve (BROAD supply)
e
power
Condensate a.fan coilb.controller (installed on the unit or on the wall)c.outdoor thermometer (installed out of window)d.indoor thermometere.lighting control (4 loops)
a
bd
c
e
e
e
e
Note: BROAD Fan Coils are totally different from the conventional fan coils both technology-wise and function-wise. The following instructions must be strictly followed in installation. BROAD Fan Coils are multi-functional products. Besides adjusting the indoor temperature and purifying the air, it also can actualize automatic on/ off according to ambient temperature, and lighting control through the remote control.All basic functions introduced here (not including optional items) must be installed (as the right diagram).
A/C w. returnA/C w. supply
N
K1 K2 K3 K4
L L41L32L31L22L21L12L11 L42light control box
Item Installa-tion
position
Material Applicable to
Material source
Scope
Power supply for
fan coils
Wiring terminal
3×1.0mm2 plastic
coated wire3×1.5mm2
plastic coated wire
1.8~7.2kW
9~25kW
user installer
Controller Wiring terminal
3×0.15mm2 communica-
tion cable (max. 10m)
wall built-in series,
ceiling built-in series
(special order
for other models)
BROAD installer
Outdoor temp. sensor
Wiring terminal
2×0.3mm2 communica-
tion cable (max. 5m)
fan coils(optional)
BROAD installer
Light control
Light control
box
9×0.75mm2
plastic coated wire
fan coils (optional)
user installer
Fresh air valve
control
Fresh air control
box
2×0.75mm2
plasticcoated wire
fan coils (optional)
user installer
Electric wiringList of site work
Note:①All electric materials and methods for installation
must comply with the local codes and standards.②Adopt the embedded PVC conduit inside wall for
indoor wiring layout.③The total cross sectional area of all wires should be
less than 40% of that of wiring conduits.④Power cable can be branched through junction
box, but communication cable can't be branched or intermediately connected.
⑤Eliminate the burr of PVC conduit ends or use jacket to protect wire insulation.Pull the wires evenly in order not to break it.
⑥A proper length should be reserved on wire outlets of junction box, which facilitates wire connection and repair.
32
Stainless steel bellow (BROAD supply)
Exterior wiring diagram
N
LNPE
GNDS5VT2T2L
T2 XK
AC 220-240V50/60Hzpower supply
outdoor thermometer
controller
control box
C. Tips for shell installation①Keep the shell horizontal with no more than 2 mm
gradient.②The expansion bolts should be strong enough to
support at least 3 times the weight of the shell (as there might be impact when the cover is being opened).
D. Tips for piping connection①Shut off the pre-installed valves (water return/
supply valves), take out and wash water filter, then fix them back.
②Take out the bellow for temporary circulation and send it back to BROAD.
③Connect the pre-installed valves with the fan coil by 2 stainless steel bellows of proper length.
④The condensate pipe must be with a certain gradient. No gradient is needed for A/C water pipes since auto air vent is available in the unit.
Wiring diagram of light control(only connect to L12/L22/L32/L42 when separate control is needed )
Power on inspection①After the installation is completed, check
the settings in fan coil controller item by item according to “Parameter Setting” chapter of the User's Manual.
②Pay special attention to the fan motor noise, outdoor/ indoor temperature and CO2 concentration.
③Check fan coil and lighting on/off through remote control.
A/C hydraulic balance commissioningStart up all the fan coils in the whole building for cooling or heating operation, use an infrared thermometer to test whether the air outlet temperature from each fan coil is the same. Turn up its flow regulating valve or turn down valves of nearby fan coils if the air temperature from a fan coil cannot reach the target. Repeat the adjustment till a hydraulic balance is reached.Generally the valve openness of those fan coils which are closer to the chiller should be smaller.
Air purification commissioningTake out the electrostatic cleaner after operating for a day and check dust collection. If not, there might be some faults. Please notify BROAD or BROAD authorized service provider.
Meeting a fresh air demand of 160~1600 peopleFresh air flowrate: 3250, 6500, 13000, 16900, 32500m3/hCooling capacity: 25kW, 50kW, 100kW, 130kW, 250kWArea coverage: 200~4000m2/unit
Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designComplete functions: air conditioning, fresh air, humidification and Electrostatic cleaner auto cleaningQuiet operation: inverter Fan, noiseless at low speedWidely applied: suitable for big rooms and a whole building
General
Air handlers
33
Air handlers
Centrifugal fan
Inverter
Control box
Detergentreservior
Coil(the only shared part with conventional products)
Spraying nozzles for auto cleaning
Water make-up motor valve
Air outlet(flange to be supplied if connected to air ducts)
Electrostatic cleaner
Air inlet (flange to be supplied if connected to air ducts)
A/C Water motor valve
Heat meter
FilterWater collection pan
34
Heat recovery air handlers
Meeting a fresh air demand of 120~1200 peopleFresh air capacity: 2500, 5000, 10000, 13000, 25000m3/hCooling capacity: 25kW, 50kW, 100kW, 130kW, 250kWArea coverage: 200~4000m2/unitSuitable for icy and torrid areas to fully exert its energy saving function
Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designComplete functions: air conditioning, fresh air, exhaust air, heat exchange between fresh air and exhaust air, humidification and electrostatic cleaner auto cleaningSuper energy saving: Equipped with air heat exchanger to enable heat exchange between fresh and exhaust air, heat recovery efficiency 60~90%Contamination free: aluminum alloy heat exchanger eliminates cross contamination the conventional paper heat exchangers might have(complete heat exchanger)Quiet operation: inverter fan, noiseless at low speedWidely applied: suitable for big rooms and a whole building
Fresh air fan
Inverter
Detergent reservoir
A/C Coils (the only shared part with conventional products)
Spraying nozzles for auto cleaning
Water collection pan
Water make-up motor valve
Fresh air inlet (flange to be supplied if connected to air ducts)
Control box
Electrostatic cleaner
Exhaust air inlet (flange to be supplied if connected to air ducts)
A/C Water motor valve
Heat meter
Filter
Exhaust air fan
Cleaning pump
Air heat exchanger (aluminum)
Exhaust air outlet(flange to be supplied if connected to air ducts)
Fresh air outlet (flange to be supplied if connected to air ducts)
No. Name& Code
Cooling capacity
kW
Air Flow
m3/h
Residualpressure
Pa
Water flow
m3/h
Waterresis-
tance
kPa
Min.noise level
dB(A)
Max.noise level
dB(A)
Power demand
kW
Weight
kg
DimensionsL×W×H
mm
A/C water
pipe
mm
Cond-ensate
pipe
mm
Installation
1 Air 25 3250 200 3.1 60 34 48 1.3 272 850x850x1850 DN32 Φ22 Against wall,
2 handler 50 6500 200 6.2 70 34 52 2.5 460 1640x850x1850 DN32 Φ22 inside the
3 EC 100 13000 200 12.4 75 34 58 5.0 840 3220x850x1850 DN50 Φ28 hall, inside
4 130 16900 300 16.1 80 36 60 9.5 900 2080x1000x2700 DN50 Φ28 machine room
5 250 32500 300 18.6 95 36 65 17.8 1814 4100x1000x2700 DN70 Φ35 or outdoors
6 Heat 25 2500 150 3.1 60 34 48 2.5 520 850x1800x2100 DN32 Φ22 inside the hall,
7 recovery 50 5000 150 6.2 70 34 52 5.0 1040 1640x1800x2100 DN32 Φ22 inside machine
8 air handler 100 10000 150 12.4 75 34 58 9.5 2000 3220x1800x2100 DN50 Φ28 room or
9 ED 130 13000 250 16.1 80 36 60 17.8 2520 2080x2000x2700 DN50 Φ28 outdoors
10 250 25000 250 18.6 95 36 65 35.0 4500 4100x2000x2700 DN70 Φ35
Air handlers - specifications
Note: 1. The above rated condition is tested under return air operation: inlet air dry bulb temperature: 27℃, wet bulb temperature: 19.5℃, chilled water outlet/inlet temperature: 14/7℃ rated conditions for heating: inlet air dry bulb temperature: 21℃, heating water outlet/inlet temperature: 55/65℃2. Heating capacity is 1.5 times of the cooling capacity.3. Cooling capacity under fresh air operation is 1.4 times of that under return air condition. rated conditions for cooling: inlet air dry bulb temperature: 34℃, wet bulb temperature: 28℃, chilled water outlet/inlet temperature: 14/7℃ rated conditions for heating: inlet air dry bulb temperature: -4℃, heating water outlet/inlet temperature: 55/65℃4. Noise level is measured 1m distance from the unit. 5. Nomenclature: code letter + cooling capacity(kW) e.g. 25kW air handler is named as EC25.
35
Air handlers - performance curves
36
Series Model
kW
Expansion bolt Bellow Adapter Sealing gasket Braze welding ends
Pre-installed valve
Model
mm
Qnty
pc
Model
mm
Length
mm
Qnty
pc
Model Qnty
pc
Model
mm
Qnty
pc
Model
mm
Qnty
pc
Model
mm
Qnty
pcAir
handlers25 M12×100 4 DN32 300 2 1" -11/2" 4 Φ43×Φ36.6×1.9
Φ49×Φ41×464
35 2 DN32 2
50 M12×100 4 DN32 300 2 11/4" -11/2"
4 Φ43×Φ36.6×1.9Φ49×Φ41×4
64
35 2 DN32 2
100 M12×100 4 DN50 400 2 2"-21/2" 4 Φ68×Φ58.6×3.1 10 54 2 DN50 2
130 M12×100 4 DN50 400 2 2"-21/2" 4 Φ68×Φ58.6×3.1 10 54 2 DN50 2
250 M12×100 4 DN70 500 2 21/2" -3" 4 Φ82×Φ74×4 10 76 2 DN70 2
Note: Pre-installed manual valve will be delivered with braze welding ends before the system installation.
Accessory supply list
Chilled W. temperature vs cooling capacity
140
120
100
80
60
40
23 24 25 26 27 28
5℃
6℃
7℃
8℃
9℃
10℃
Chilled W. flowrate vs cooling capacity
Air flow vs static pressure
500
400
300
200
100
0 20 40 60 80 100 120 140 160
EC130、250
EC25~100
ED25~100
ED130、250
100
95
90
85
80
75
7050 60 70 80 90 100
Air flow %
Air return temp. ℃ Flowrate %
Co
olin
g c
ap
ac
ity %
Co
olin
g c
ap
ac
ity %
Exte
rna
l sta
tic p
ress
ure
Pa
Air handlers - dimension
37
Air handler EC
Note:dimension units are in mm, and it is the same on the following pages.
38
Heat recovery air handler ED
A. LocatingThe designer selects air handler(or heat recovery air handler)and decides their installation locations according to the function and decoration style of the room to facilitate piping and wiring pre-installation.
B. Piping and wiring pre-installationDuring the construction, A/C water supply & return pipe (with pre-installed valve), water make-up pipe, drain pipe, power supply cable, lighting output cable shall be implemented to the installation place of air handler unit.
C. Hole opening on the wallFor new buildings, fresh air hole openings should be reserved according to designs. For existing buildings, the position and dimension of fresh air hole openings should be marked firstly in accordance with specified air handler models then make the hole openings based on designs.
E. Shell installationLocate (heat recovery) air handler against the prepared holes, then fix it with expansion bolts.
I. Outdoor thermometer installationLead a 2×0.3mm2 cable from air handler unit wiring terminal. Install the sensor outside the window avoiding direct sunshine.
G. Power connectionLead three-phase power cable from the wiring terminal to indoor power supply.
D. Air duct installationAir ducts should be pre-installed according to fresh air demands and the installation place of air handler unit, and the duct dimension as well as installation methods should meet requirements.
F. Pipe connectionConnect the pre-installed water supply pipe, water return pipe, water make-up pipe, drain pipe and air duct to the unit. Flexible stainless steel bellow pipe can be used as water return & supply pipe.
J. Controller installationUsually the controller is installed on the supporter attached with the unit. Another way is to lead a 3×0.15mm2 cable from the wiring terminal and install it on the wall nearby with convenience for control and without undermining the indoor decoration design.
H. Indoor thermometer installationLead a 2×0.3 mm2 cable from air handler unit wiring terminal and install it onto the wall 5m away from the unit (1.3m above floor). If the thermometer is too close to the indoor unit, it will indicate the air blowing temperature from the unit instead of the average temperature of the room.
Air handler Installation TipsElectric wiring
Item Installation position
Material applicable to
Material source
Scope
Power supply
Inside control
cabinet
3x2.5+1x1.5mm2
cable
3x4.0+1x2.5mm2
cable3x6.0+1x4.0mm2
cable3x16+1x10mm2
cable3x25+1x16mm2
cable
EC/ED25
EC/ED50
EC100
EC130
ED100
EC250
ED130
ED250
users installer
Controller Wiring terminal
3x0.15mm2
communication cable
(max. 10m)
All models
BROAD installer
Outdoor thermometer
Wiring terminal
2x0.3mm2
communication cable
(max. 5m)
All models
(optional)
BROAD installer
Exterior wiring diagram
Scope of site work
Power on inspection,A/C hydraulic balance commissioning and air purification commissioning
The same as BROAD Fan Coil Installation Tips(Please refer to P32. )
Installation procedures
N
NPE
GNDS5VT2
T2
L1
XK
3N 380-410V 50/60Hz
Power supplyOutdoor thermometer
Controller
L3L2 T2
L1 L3L2
~
39
exhaust air inlet
air heat exchanger (aluminum)
electrostatic cleaner
active carbon
fresh air fan
fresh air outlet
inverter motor
exhaust air outlet
exhaust air fan
fresh air inlet
General
Meeting a fresh air demand of 5~20 peopleFresh air capacity: 100, 240, 400m3/hArea coverage: 200~4000m2/unitInstallation: wall mounted (two oval openings to be made on the wall)Suitable for icy and torrid areas to fully exert its energy saving function
Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designSuper energy-saving: Equipped with air heat exchanger to enable heat exchange between fresh and exhaust air, heat recovery efficiency 50~80%Contamination free: Aluminum alloy heat exchanger eliminates cross contamination the conventional paper heat exchangers might have(total heat exchanger)Easy installation: plug and play, instantly eliminates urban pollutionQuiet operation: inverter Fan, noiseless at low speed
Fresh air units
40
Heat recovery fresh air units
co2 sensor
Fresh air units Large fresh air units
Meeting a fresh air demand of 2~2000 peopleApplicable for air purifying indoor and outdoorLarge fresh air unit with electrostatic cleaner auto cleaning function
41
Large fresh air unit
Fresh air capacity: 4000, 8000, 16000, 20000, 40000 m3/hArea coverage: 1000~10000m2
the same structure as air handler, only without A/C coil.
CO2 sensor
Air intake pipe(Inserted into wall)
Inverter fan
Electrostatic cleaner
Active carbon
Controller
Super purification: Electrostatic cleaning, active carbon detoxification, oxygen deficiency protection, interior open designEasy installation: plug and play, instantly eliminates urban pollutionQuiet operation: inverter Fan, noiseless at low speedWidely applied: suitable for big rooms and a whole building
Fresh air unit
Fresh air capacity: 50, 100, 240, 400, 1000 ,2000m3/hArea coverage: 10~500m2
No. Name Code
Air flow
m3/h
Residual pressure
Pa
Min.noise level
dB(A)
Max.noise level
dB(A)
Power demand
W
Weight
kg
SizeL×W×H
mm
Installation
1 Heat recovery 100 / 28 37 35 12 330x150x570 Wall mounted
2 fresh air 240 / 28 37 150 34 520x255x8503 unit 400 / 30 39 200 45 580x320x960
SA4 Fresh air 100 / 22 32 20 4.5 340x150x240 Wall mounted5 unit 240 / 22 35 35 6.5 340x150x500
6 TAWF 400 / 24 35 40 9 340x150x745
7 1000 / 26 40 90 27 480x230x848 Floor standing8 2000 / 28 42 150 45 480x230x15639 Big fresh 4000 150 34 48 1300 165 850x850x1850 Floor standing10 air unit 8000 150 34 52 2500 330 1640x850x1850 Holes to be11 THWH 16000 150 34 54 5000 670 3220x850x1850 opened on the 12 20000 250 36 54 9500 850 2080x1000x2700 wall for these 413 40000 250 36 56 17800 1600 4100x1000x2700 models
14
Window fresh air
unitTDWD
50 / 27 42 5 1.5 200x143x225 Against the window (holes to be opened
on the window)
Fresh air units - specifications
Fresh air units
Fresh air accessories
No. Name Code
Air flow
m3/h
Residual pressure
Pa
Min.noise level
dB(A)
Max.noise level
dB(A)
Power demand
W
Weight
kg
SizeL×W×H
mm
Installation
1 Ventilator 100 / 28 43 58 3 170x72x170 near a fan coil2 VA 240 / 33 48 81 5 190x98x1903 400 / 38 54 126 8 220x99x2204 800 / 42 56 213 14 310x108x3105 Big ventilator 2000 500 45 63 300 28 505x239x528 near an air handler 6 VC 4000 540 48 64 750 55 580x290x5837 Fresh air box 600 / / / / 6 890x264x140 Air inlet of the8 WB 800 / / / / 7 1060x264x140 “Thick” units9 1000 / / / / 8 1260x264x14010 1300 / / / / 9 1450x264x14011 1600 / / / / 10.5 1760x264x14012 2100 / / / / 12.2 2200x264x14013 Big fresh 4000 20 38 614x6841170 Air inlet of the14 air valve
WF
10000 20 57 1114x929x1795 air handler andheat recovery air
handler
42
Note: 1. Fresh air units do not have air conditioning function.2. Noise level is measured 1m distance from the unit. 3. Nomenclature: code letter + air flow e.g. 100m3/h fresh air unit is named as TAWF100.
Note: 1. Fresh air accessories are coupled with fan coils and air handlers.2. Noise level is measured 1m distance from the unit. 3. Nomenclature: code letter + air flow e.g. 100m3/h fresh air ventilator is named as VA100.
Fresh air units - performance curves
43
Accessory supply list
Name Model
m3/h
Expansion bolts Active carbon
pcsModel
mmQnty
pcs
Heat recovery fresh air unit
100 M6×80 4 4
240~400 M6×80 6 4
Fresh air unit 100~2000 / / 4
Big fresh air unit 4000~40000 M12×100 4 /
Window fresh air unit
50 / / 4
Big fresh air unit air flow vs static pressure
0 20 40 60 80 100 120
500
400
300
200
100
Air flow %
THWH20000、40000
THWH4000~16000
Exte
rna
l sta
tic p
ress
ure
Pa
Fresh air units - dimensions
Heat recovery fresh air unit SA
Fresh air unit TAWF
Big fresh air unit THWH The dimension for big fresh air units is the same as air handlers; please refer to P37.
44
TAWF100 TAWF240~2000
Big fresh air unit exterior wiring diagram
GND
XK
N
NPE
S5VL1
3N 380-410V 50/60Hz
Power supplyController
L3L2
L1 L3L2
~
Control box
NPE L
N L
Control box
AC 220-240V 50/60Hz
Power supply
Fresh air unit/ heat recovery fresh air unit exterior wiring diagram
Item Installation position
Material Applicableto
Material source
Installation
Power supply
Inside the control
cabinet
3x1.0mm2plastic coated wire
3x2.5+1x1.5mm2
cable
3x4.0+1x2.5mm2
cable3x16+1x10mm2
cable
SA100~400
TAWF100
~2000
TAWH4000
~16000
TAWH20000
TAWH40000
users installer
Controller Wiring terminal
3x0.15mm2
communication cable (max. 10m)
All models BROAD installer
List of site Installation
F. Power on inspectionAfter the proper installation is confirmed, turn on the unit, adjust the fan frequency, test the sound of fan, and check the CO2 concentration displayed on the controller.
A. LocatingThe designer selects the model of fresh air unit according to fresh air solution, and locates the installation position for opening.
B. Making holes in the wallFor new buildings, openings should be reserved according to the design. For existing buildings, mark the position and dimension of openings according to different models, then open fresh air holes, and polish them with cement. After the structure construction, indoor walls and floor flatting get finished, recheck the position and dimension of installation, and immediate modifications are needed if it can not meet the requirements (in order to prevent rainfall from flowing indoor, through-wall hole should be higher on the indoor side and lower on the outer side. They also should look neat and nice).
C. Open-box inspectionCheck the product number, product name and model: inspect the shell and accessories to see if they are complete and in good condition. If there is any damage, please notify the supplier.
D. Shell installationFor fresh air unit: inset the fresh air inlet/ outlet pipe into cement holes, After the cement is hardened and the pipes are fixed, steadily install the fresh air unit.For heat recovery fresh air unit and large fresh air unit: locating the unit to the fresh air inlet/outlet hole,and fix it with expanded bolt.
E. Power connectionLead power cable from the wiring terminal to indoor power supply.
45
Fresh air units - Installation Tips
Installation procedures Electric wiring
Item Focuses or Disputes BROAD Solutions
Fresh air amount
What’s the suitable rate?
20m3/h per capita. For low occupancy density rooms such as villas, 2m3/h per square meter.
Air outlet
How to use fresh air effectively?
Locate the fresh air outlet and exhaust air outlet as far as possible so that fresh air can be fully used.
Air duct How to avoid air duct pollution?
Air ducts are seedbeds for pathogens. The solution is not to use air ducts
Cost How to minimize the cost?
Install fresh air boxes on fan coils to draw fresh air from outside
Energy-saving
Is it worth increasing investment to save energy?
1. In icy areas (temp <-10°C in winter), the payback can be within 1-3 years if fresh air heat recovery system is introduced.
2. In areas with mild climate (16-26°C), by selecting larger fresh air units and using fresh air for cooling in transitional season, the payback can be within 2-6 years.
46
Fresh air unit model selection tips
Tips for fresh air system selection
How much fresh air are we breathing?Staying in a room lacking of fresh air is like living on the sea without freshwater. You can breathe (drink seawater), but will be suffocated to death (thirst). According to authoritative investigations, everybody in the world has more or less suffered from fresh air deficiency (oxygen deficiency), e.g.:• In cold seasons people always close doors and
windows to keep warm and save energy. Their faces turn red, not because of the warmth but of oxygen deficiency.
• In hot seasons people always close doors and windows to keep cool and save energy. People are lethargic, not because of fatigue but of oxygen deficiency.
• The ultimate tightness of doors and windows due to quality advancement in recent years makes oxygen deficiency problem more serious.
• Some modern buildings that appear to be full of hi-techs are still using the conventional “low-tech” design and management of ventilation system, which leads to :• Oxygen deficiency• Toxic gases from refurbishing & building materials,
furniture, carpets can not be emitted in time.• Hundreds of people are breathing the same
mouthful of air that is cross contaminated.• A great number of pathogens are bred inside air ducts.
What kind of houses can breathe?Each BROAD fan coil is equipped with an expensive optical instrument – CO2 sensor to monitor oxygen deficiency any minute. People inhale O2 and exhale CO2, by measuring the CO2 level oxygen deficiency is to be indicated.To “know” is very important, but to “do” is even more. To meet different building constructions, functions, purchasing power and climates, BROAD has developed dozens of fresh air products that are totally different from conventional products but cheaper and more energy efficient. They can solve all fresh air problems comprehensively and let each building/room breathe freely.
What‘s the harm of oxygen deficiency?Deficiency of fresh air inside a room will lead to oxygen (O2) deficiency and carbonic acid (CO2) concentration increase in our blood, causing insufficient O2 supply to the brain, headache, chest pain, cold limb and sleepiness, etc. Extended stay in an oxygen-deficient environment will result in skin-coarsening, premature senility, hypomnesia, slow of response, or most seriously heart diseases, brain damnification and stroke. People in serious oxygen deficiency may even lose their lives unconsciously.
What are the features of conventional “low-tech” modes?
• Just “go with your heart”– do not take even fundamental technical measures (such as CO2 sensor) to verify the design, guide the commissioning and check the operation.
• “30/70 ratio” fresh air –in the whole ventilation system, 70% air circulation is from indoor exhaust air and 30% from outdoor fresh air, resulting in cross contamination. All people in the building are breathing the same air. If someone gets sick, it may pass on to everyone.
• Short circuit between fresh and exhaust air system – the fresh air inlet and outlet are too close. Part of fresh air is expelled before people can breathe it.
• Pathogens are easily bred inside fresh air ducts.• As no technical instrument is introduced, it turns out
not enough fresh air in some places and excessive fresh air in other places (which is energy wasting). It also wastes a lot of energy without using heat recovery devices.
BROAD Fresh Air System Conventional Fresh Air System
Eliminates pollution from outdoors
Outdoor fresh air is purified by electrostatic cleaner and active carbon before entering the room.
Outdoor air incompletely filtered Filters are widely used, which cannot filter micro particles.
Eradicates pollution inside air ducts • Small buildings – the fresh air units can draw outdoor air into each room directly. • Large buildings – fresh air can be supplied to the passages by large-sized air ducts, then pumped into individual room by suction ducts from the interior windows. • In order to match perfectly different construction styles, BROAD provides dozens of products and optional accessories.
Serious pollution inside air ducts • Fresh Air ducts are extended to each room. Air ducts in a mansion may outstretch several or scores of kilometers. The air ducts are mixed and anfractuous, becoming the pollution sources. • The air ducts are not cleaned in years or even the whole lifespan. Pathogens are bred rapidly inside, making the air ducts even dirtier than inside drains.
Well-proportioned fresh air Fan coils and fresh air units in each room are equipped with CO2 sensor, which is monitoring fresh air deficiency and excess 24/ 7.
Unbalanced fresh air CO2 sensors are not used, only a few to be installed in 5-star hotels. It may result in excessive fresh air in some rooms and not enough fresh air in other rooms.
Many alternatives • 5 modes, 30+ products and dozens of accessories available. • Custom design can be made according to building structures, functions, energy saving objectives,budgets, etc. • Suitable for fresh air system modifications of old buildings.
Few choices Only two modes all over the world.
Space saving • “Direct fresh air system” takes almost no space. • “Exhaust air duct system” is 50% space saving. • The space saving cost is possibly higher than the investment on equipment.
Large space taking Air ducts outstretch horizontally and vertically into a building and occupy very large space.
47
BROAD Fresh Air System vs. Conventional Fresh Air System
BROAD fresh air system solutionFor conventional central air conditioning system, fresh air duct system is very complicated. It looks like blood vessels stretching every corner of buildings. In a large building, there are several dozen kilometers of fresh air ducts. In the past few people noticed what was inside fresh air ducts. In recent years “sick building syndrome” (SBS) broke out worldwide, more and more people learned about it. Before Beijing Olympic Games, the investigation into indoor air quality of more than 10,000 large-scale buildings revealed that less than 1% of fresh air ducts in these buildings were cleaned. Similar situation exists worldwide. Furthermore in those cleaned buildings only less than 40% fresh air ducts can be cleaned even with cleaning robots.
Now, the question we are facing is to develop smaller and more practical robots to clean fresh air ducts, or not to use fresh air ducts completely.
If the first choice is taken, besides technical difficulties, how to afford the costly cleaning fee (approximate USD14/m2, which is nearly the same as an initial cost) and how to stand the polluted air during hundred days between two cleaning intervals, so the only solution to prevent pollution is not to use fresh air ducts.
Category Solutions Selected products Advantages Disadvantages ApplicationDirect fresh air system
Solution 1 Fresh air unit to get outdoor fresh air directly
Easy and simple installation
High costOnly suitable for rooms with outer wall
Any buildings including buildings without BROAD fan coils and renovated old buildings
Solution 2 Heat recovery fresh air unit to get outdoor fresh air and vent indoor air
Easy and simple installationEnergy-saving
Very high costOnly suitable for rooms with outer wall
Solution 3 Fresh air box to get outdoor fresh air directly by fan
Easy and simple installationFresh air box is cheap
Only suitable for rooms with outerwall (an opening on the wall)
Only for buildings equipped with BROAD fan coils
Solution 4 Ventilator to get outdoor fresh air to rooms
Easy and simple installationVentilator is cheap
Only suitable for rooms with outerwall or close to outer wall
Exhaust ventilation system
Solution 5 Exhaust duct purified fresh air will be pumped into rooms from passages
For big areasNo opening on the outer wallnot affecting building profile
High engineering cost Much space-taking
Buildings inconvenient for making an opening on the outer wall
Item 1 Air handler exhaust ventilator: Air handler will supply fresh air to passages; Fresh air will be pumped into individual rooms with exhaust ventilator and exhaust duct
Very high cost
Item 2 Heat recovery air handler will supply fresh air to passages; Fresh air will be pumped into individual rooms with exhaust duct
Energy-saving High cost Buildings inconvenient for making an opening on the outer wall, and in icy or torrid areas
48
BROAD fresh air system solution
Ventilator
Solution 3
Solution 5
Solution 4
Solution 5
Solution 5
Solution 5
Exhaust duct
Solution 1
Solution 2
Fresh air unit
Fresh air boxHeat recovery fresh air unit
Fresh air
exhaust air
air condi-tioning
Solution 5(Item 2) Solution 5(Item 1)
Heat recovery air handlerAir handler
Exhaust ventilator
air conditioning
Applications:Matching with BROAD villa air conditioning or other chillers to provide hot water (external primary heating water heats city water in the tank).
Working principle:The cycling of primary heating water in coils heats the city water in the tank, making the temperature of city water inside reach the setting temperature.The heat exchange coil connects to the primary heating water (60~120℃) from outside devices. When hot water temperature is at the setting temperature, the motor valve will shut off the primary heating water. When the temperature is lower than the setting, the motor valve will reopen and thus heat the hot water. The heating and temperature control are actualized in this way.
Features:• All-copper interior and coil are bacteria-killing.• Hand access hole design, easy to open for cleaning.• It adopts separate hot water tank system to
materialize 30% energy saving than centralized systems. The reason is that the valve will be closed automatically once the hot water is heated to the setting temperature. Thus, heat loss and electricity consumption can be minimized.
• Tanks are installed near the place where water is used so hot water comes out as soon as the valve is opened. It is unnecessary to keep circulation pump running 24 hours a day to maintain hot water temperature.
• Separate tank system maintains stable hot water temperature.
Hand hole cover is easily removable
Hot water tanks
100% pure copper interior
Pure copper heat exchange coil
Heat insulation
Controller(link with BMS)
Steel shell &car paint
Automatic valve and water inlet/outlet pipe system
Removable lower cover ( facilitate installation and interior cleaning )
49
Hot water tanks - specifications Accessory supply list
Models
Item Specifications
Hot water temperature
20~85℃
Primary heating water temperature
60~120℃
Pressure ≤0.8MPa
Power demand
10W
Power supply 220~240V, 50/ 60Hz (special orders for other power supplies)
Material Shell (steel sheets), interior(copper)
Sealing parts Fluorine rubber
Protection level
IP44
Installation Vertical up (wall-mounted or bracket-mounted)
Model Volume
L
SizeL×W×H
mm
Operation weight
kg
Pipe connection diameter
mm
RL100 100 430x345x1790 145 DN15Copper tube is recommendedRL200 200 530x430x2150 270
No. Name Quantity Specifi-cation
Application Remark
1 Expansion bolt
2 sets M10 Fixing the tank on the wall or bracket
/
2 Controller 1 piece / Controlling hot water temperature in the tank
/
3 Plastic flexible conduit
1 piece φ10 Connecting to the cone-shaped drain outlet
/
4 Bracket 1 set / Floor standing installation of hot water tank
Optional
5 Bolt 4 sets M16 Fixing the tank on the bracket
6 Bellow 4 piece DN15x300
Pipe Connection
/
Note:1. Nomenclature: Code + capacity e.g. 100L Hot water tank to be named as RL1002. For floor-standing installation with a bracket,the price will
be 10% higher.
50
51
Note:dimension units in mm.
Hot water tank - dimensions
Tips for piping and wiring pre-installation• Pipes must be laid during construction phase.• All pipes except city water pipe must be copper tubes with rubber plastic insulation.• Only BROAD valve set could be installed. Note: Please check the marks to avoid any
mistakes in matching pipes.• After completion of whole building installation,
keep the hot water pump running continuously for min. 1 day to collect all impurities of primary heating water to filters.Then clean all the filters.
Tips for tank installation• Tanks must be installed vertically, wall mounted or floor standing with brackets.• The installation strength of expansion bolts must be at least 3 times more than the operating weight.
Hot water tank - installation tips
Exterior wiring diagram
Electric wiring
PE
N
LN
GNDS5VL
XK
AC 220-240V50/60HzPower supply
Controller
B A G
485 communication
Control box
Item Install-ation
position
Material Appli-cable
to
Material source
Installation
Power supply
Wiring terminal
3x1.0mm2
plastic coated
wire
All users installer
485 communi-
cation
Wiring terminal
2x0.3mm2
double stranded
wire
All users installer
List of Installation
Installation procedure
52
D. Pipe connectionConnect the pre-installed primary heating water outlet & inlet pipe, city water make-up pipe and hot water outlet pipe to the hot water tank through bendable stainless steel bellows.
E. Electrical wiringLead power cable from the wiring terminal to indoor power supply. Lead 485 communication cables in if there is a central controller.
C. Tank installationRL100 and RL200 are usually wall amounted, or floor standing installation with a bracket, while RL300 and RL500 can only use brackets. After the building decoration, screw hole lofting of wall fixture or brackets, drilling, expansion bolts installation, fixing wall fixture or brackets, and tank installation shall be conducted step by step.
J. Power on inspectionAfter the proper installation is comfirmed, turn on the unit to check whether the controller and temperature control are OK.
A. LocatingThe designer selects hot water tanks according to requivement for hot water,and decides the installation location to facilitate the pre-installation work.
B. Piping and wiring pre-installationA/C primary heating water outlet & inlet pipe, city water make-up pipe, hot water outlet pipe, drain pipe, power supply cable and 485 communication cables should be pre-installed during construction.
F. Controller installationUsually the controller is installed on the supporter attached with the unit. Another way is to lead a 3×0.15mm2 cable from the wiring terminal and install it onto the wall nearby with convenience for control and without undermining the indoor decoration design.