Contents Description Page Type FG 15–225A Three-Pole 2 Type JG 175–250A Three-Pole 4 Type KG 300–400A Three-Pole 6 Type LG 450–600A Three-Pole 8 Type MG 700–800A Three-Pole 10 Type NG 900–1200A Three-Pole 12 Effective April 2011 Supersedes October 1997 Technical Data TD01214004E Molded-case circuit breakers engine generator

Td 01214004 e

Embed Size (px)

DESCRIPTION

ok

Citation preview

  • ContentsDescription Page

    Type FG 15225A Three-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Type JG 175250A Three-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Type KG 300400A Three-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Type LG 450600A Three-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Type MG 700800A Three-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Type NG 9001200A Three-Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Effective April 2011Supersedes October 1997 Technical Data TD01214004E

    Molded-case circuit breakers engine generator

  • 2Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 1. Type FG 15225A Three-PoleDimensions in Inches (mm)

    0.62(15.7)

    2x 1.03 (26.2)

    2.35 (59.7) R

    1.56(39.6)

    0.38(9.7)

    0.75(19.0)

    1.41(35.8)

    4.50(114.3)

    0.75(19.0)

    2.72(69.1)

    0.17 (4.3)

    0.34(8.6)

    0.02(0.5)

    0.69(17.5)

    1.38(35.1)

    0.02 (0.5)

    4x 0.09(2.3)R

    4.00(101.6)

    1.72(43.7)

    0.82(20.8)

    1.03 (26.2)

    0.74(18.8)

    1.38(35.1)

    1.38(35.1)

    4.13 (104.9) +0.00 0.02

    0.74(18.8)

    2.06(52.3)

    1.00(25.4)

    0.50(12.7)

    1.56(39.6)

    0.08(2.0)

    0.75(19.0)

    2.38(60.5)

    0.50(12.7)

    3.38(85.9)

    2.99(75.9)

    AB

    DE

    0.19 (4.8) R

    0.19 (4.8) R

    0.38(9.7)

    1.33(33.8) 1.33

    (33.8)

    0.16(4.1) R

    0.47(11.9)

    0.27(6.9)

    0.63(16.0)

    1.13(28.7)

    53

    +0.03 (0.8)0.02 (0.5)

    6.00(152.4)

    0.18(4.6)

    0.31 (7.9)

    0.27(6.9)

    0.47(11.9)

    0.47(11.9)

    0.19 (4.8)

    R 0.09(2.3)

    1.22(31.0)

    0.22 (5.6)

    2.38

    0.30 (7.6) Wide Conductor with 0.22 (5.6) Hole

    0.50 (12.7) Wide Conductor with 0.22 (5.6) Diameter Hole

    To Top of Clip

    Adjusting Knob forAdjustable Styles Only

    Load End

    Line End

    Handle: 0.34 (8.6) Wide x 0.38 (9.7) Thick0 Taper, Load End 7 Taper, Line End

    Note:This Drawing Shall Not be Used for Circuit Breaker Tolerances Except Where Specically Identied.

    0.38(9.7)

    0.20 (5.1) Diameter Hole 4x 0.33 (8.4) x 1.94 (49.3) from Top 0.34 (8.6) x 0.66 (16.8) from BottomFor 0.164-32 (#8) x 1.50 (38.1) Mounting Screw

    0.45 (11.4) Diameter Hole 6x

    0.11 (2.8) x 0.31 (7.9) 3x To accept #6 Thread Cutting Screws

    0.13 (3.3) x 0.48 (12.2) 6xTo accept #8 Thread Cutting Screws

    Though for Attachment Leads

    0.13 (3.3) x 0.75 (19.0) Slots for Attachment Leads

    0.08(2.0) 0.75

    (19.0)

    0.25 (6.4)

    0.06 (1.5)

    C

    3.50 (88.9) +0.03 (0.8) 0.02 (0.5)

    3.39 (86.1) +0.03 (0.8) 0.02 (0.5)

    3.19 (81.0) +0.03 (0.8) 0.02 (0.5)

    2.94 (74.7)

    2.22 (56.4)1.77 (45.0)

    Breaker Status

    Dimensions

    a B C D e

    On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6)Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7)Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.6) 2.42 (61.5) 2.56 (65.0)Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.2)

  • 3Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 2. Type FG 15225A Three-Pole Cutout and Drilling PlanDimensions in Inches (mm)

    1.38(35.1)

    0.69(17.5)Line

    End

    0.1632 Tap6x

    0.75(19.1)

    2.88(73.2)

    4.50(114.3)Breaker

    Handle

    Load End

    Front Connected Drilling Plan

    R 0.25(6.4)

    2.31(58.7)

    1.91(48.5)

    BreakerHandle

    2.91(73.9)

    0.58(14.7)

    0.50(12.7)

    Location of Terminal Access Holes if Required

    Front Cover Cutout

    Load End

    1.38(35.1)

    1.38(35.1)

    0.59(15.0)

    1.19(30.5)

    Line End

    +0.036.000.02

    BreakerHandle

    Load End

    Rear Connected Stud to Terminal

    1.38(35.1) 2.75

    (69.9)

    0.44 (11.2) for 15 to 100A0.56 (14.2) for 125 to 150A

    5.06(128.5)

    3.16(80.3)

    0.47(11.9)

    0.19(4.8)

  • 4Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 3. Type JG 175250A Three-PoleDimensions in Inches (mm)

    0.03 (0.8)4.13 (104.9)

    2.75 (69.9)1.38

    (35.1)0.69(17.5)

    0.69(17.5)0.19 (4.8) R

    0.69 (17.5) Diameter 6 Holes

    0.28 (7.1) Diameter4 Mounting Holes0.50 (12.7) Diameter C'bores

    0.50 (12.7)0.78 (19.8)

    1.72(43.7)

    2.59(65.8)

    10.00(254.0)

    8.34(211.8)

    7.25(184.1)

    0.25 (6.4) R

    0.50 (12.7)

    0.19(4.8)

    1.38(35.1) 0.88

    (22.4)

    2.84(72.1)

    7.53(191.3)

    3.75(95.3)

    4.00(101.6)

    0.25(6.4)

    0.03 (0.8)

    0.88 (22.4)

    0.11 (2.8) Diameter6 Holes

    2.13(54.1)

    0.94(23.9)

    1.00(25.4)

    0.13(3.3)

    3.81 (96.8)

    4.06 (103.1)

    0.81 (20.6)0.63 (16.0)

    0.16 (4.1)

    0.50 (12.7)

    1.06(26.9)

    0.06 (1.5)0.63 (16.0)

    5.80(147.3)

    15

    5.50

    5

    RESET

    3

    OFF

    0.04

    1.49(37.8)

    1.03(26.2)

    0.47 (11.9)

    0.75 (19.0)

    Outside0.90 (22.9)

    Center1.51

    (38.4)

    For GeneratorBreakers Only

    ONTRIP

    Breaker Handle

    Typical Three-Pole Thermal-MagneticTrip Unit

    8.09(205.5)

    4.89(124.2)

    1.38(35.1)

    4.89(124.2)

    0.81(20.6)

    0.81(20.6)

    2.75(69.9)

    2.75(69.9)

    1.38 (35.1)

    0.25(6.4)

    8.09(205.5)

    0.50(12.7)

    0.38(9.7)

    0.75(19.0)

    0.63 (16.0)Diameter6 Holes

    0.69 (17.5)

    0.56(14.2) R

    0.44 (11.2)Diameter4 Holes

    0.56 (14.2) R

    0.69 (17.5)1.38

    (35.1)

    7.25(184.1)

    4.08(103.6)

    0.2520 Tap4 Holes

    0.78 (19.8)

    1.56(39.6)

    3.94(100.1)

    2.92(74.2)

    0.72 (18.3)

    1.75(44.4)

    3.33(84.6)0.88 (22.4)

    1.38 (35.1)

    0.34 (8.6) R

    0.19 (4.8) R

    3.50 (88.9)

    2.75 (69.9)

    0.50 (12.7) Diameter3 Megger HolesIf Required

    2.55(64.8)

    0.63 (16.0) Diameter(For GeneratorBreakers Only)

    Front Cover Cutout Breaker Mounting Drawout Support Blocks Rear Connection Studs

    Handle

    Breaker

    Omit 2 Center Holes For Two-pole Breakers

    Breaker

    3.83 (97.3)

    4.06 (103.1)

    4.31 (109.5)

    4.94 (125.5) Max.

    CL

    CL

    Line End

    Load End

    CL

    CL

    HandleCL

    HandleCL

    1.38 (35.1)

    HandleCL

    Terminal ArrangementsStyle number

    Catalog number

    Cable type

    ampere rating

    Wire Size

    torque(Lb-in)

    Cu single 70250 #4350 kcmil 180 1254C14G02 T250KBCu-Al single 70250 #4350 kcmil 275 176C446G01 TA250KB

  • 5Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 4. Type JG 175250A Three-PoleDimensions in Inches (mm)

    LineLine EndBreaker Mounting HolesUse M6 x 1 x 73.025 Pan Head Screw with SemsTightening Torque 7.34 NmLoad End M6 x 3.50 (88.9) Pan Head

    0.28(7.1)Dia

    0.50(12.7)Dia

    2.37(60.3)

    0.50(12.7)

    0.31(7.9)Dia

    DC

    BA

    Load

    EF

    0.03(0.8)

    0.69(17.5) 4.34

    (110.2)

    2.09(53.1)

    7.47(189.7)

    0.81(20.7)

    1.00(25.4)

    0.50(12.7)

    1.00(25.4)

    0.50(12.7)

    0.27(6.8)Dia

    2.13(54.1)

    9.72(246.9)

    4.89(124.3)

    5.64(143.3)

    1.00(25.4)

    0.50(12.7)

    3.63(92.1)

    1.81(46.0)

    2.25(57.2)1.13

    (28.6)

    3.09(78.6)

    4.81(122.3)

    8 x 0.15 (3.8) Dia

    0.50 (12.7)Deep

    0.37(9.5)

    0.37(9.5)0.75

    (19.1)Off

    On

    Bkr Contact Position IndicatorsREDOn/IGREENOff/OWHITETrip

    2.75(69.8)

    1.37(34.9)

    Breaker Shown in OFF Position

    Magnetic Multiples of In

    Thermal

    Magnetic

    Trip Unit

    Push to Trip

    75

    10 5

    75

    10 5

    75

    10 5Amps (In) C Cat. No.

    of Breaker HandleCL

    CL

    Breaker Status

    Dimensions

    a B C D e F

    Handle operating Force (n)

    Reset 3.91 (99.3)

    3.96 (100.6)

    4.21 (106.9)

    4.36 (110.7)

    4.90 (124.5)

    4.95 (125.7)

    169.0

    Off 4.02 (102.1)

    4.06 (103.1)

    4.32 (109.8)

    4.45 (113.0)

    4.91 (124.7)

    4.95 (125.7)

    97.9

    Trip 4.79 (121.7)

    4.71 (119.6)

    5.10 (129.5)

    5.10 (129.5)

    4.87 (123.7)

    4.85 (123.2)

    On 5.20 (132.1)

    5.12 (130.1)

    5.54 (140.7)

    5.49 (139.5)

    4.79 (121.6)

    4.72 (119.9)

    142.3

  • 6Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 5. Type KG 300400A Three-PoleDimensions in Inches (mm)

    5.49 (139.4)Line End

    Line End

    Line End

    Line EndLoad End

    Load End

    3.43 (87.3)

    1.71 (43.6)

    0.50 (12.7)

    0.11 (2.8) Dia. x 0.29 Deep, 4 Holes, Accept #6 Thread Cutting Screws

    n 0.62 (15.9)

    4.43 (112.7)

    7.40 (188.1)

    1.25 (31.7)

    1.16 (29.5)

    Dimensions for Extended

    Terminals and Barrier

    Style Numbers 4212B60G02, 4212B61G02,

    and 1492D24H01

    3.81 (96.8)

    0.19 (4.8)

    0.77 (19.5)

    0.06 (1.6)

    0.19 (4.8) R

    0.50 (12.7)

    0.94 (23.8)

    0.75 (19.0)

    0.37 (9.5)

    Contact Position Indicators Red/I-On

    Green/O-OffWhite-Trip

    0.37 (9.5)

    0.09 R 0.18 R (4.7)

    2.43 (61.9)

    4.12 (104.8)2.06 (52.4)

    0.86 (21.8)

    0.84 (21.4)

    2.81 (71.4)

    0.12 (3.2)

    3.56 (90.5)

    4.00 (101.6)

    0.25 (6.3)

    0.25 (6.3) RLoad End

    0.06 (1.6)

    4.31 (109.5)

    0.44 (11.1)

    0.87 (22.2)

    2.37 (60.3)

    DC

    BA

    EF

    1.06 (27.0)

    0.75 Wide Conductor with 0.39 Dia. Hole Line and Load End

    0.28 Dia. Mounting Holes4 Holes for 0.25-20 x 1.50

    Mounting Screws0.50 Dia. CBore from Top

    2.87 Deep Load End2.62 Deep Line End

    0.44 Dia. CBore0.75 Deep from Bottom

    8.44 (214.3)

    0.34 (8.7) R

    3.75 (95.2)

    0.18 (4.7) R

    1.31 (33.3)2.62 (66.7) 2.39

    (60.7)4.78 (121.5)

    1.72 (43.7)0.86 (21.8)

    0.84 (21.4)

    q Breaker Handle

    Drill Plan for Mounting Bolts Front Connected Terminals

    0.87 (22.2) Dia. (6-PLS) (Omit 2 Center Holes

    for Two-Pole)

    q Breaker Handle

    1.72 (43.7)

    0.62 (15.9) Dia. 3 Places

    (For Generator Breakers Only)

    8.43 (214.3)

    4.92 (125.0)

    3.51 (89.3)

    0.25-20 (M6) Tap 4 Holes

    0.83 (21.0)1.64 (41.7)

    1.25 (31.7)

    8.87 (225.4)

    10.12 (257.2)

    0.62 (15.9)

    0.18 (4.8) Dia. CBore 0.03 DP0.15 Dia. Hole 0.50 DP to Accept #8 Thread Cutting

    Screws (8-Places)

    1.72 (43.6)

    0.25 (6.3) R 1.62 (41.3)

    1.22 (30.9)

    4.78 (121.4)

    2.39 (60.7)

    1.62 (41.2)

    On / I

    Off / O

    2.56 (65.1)

    1.72 (43.7)

    8.87 (225.4)

    5.14 (130.6)

    3.73 (94.8)

    1.87 (47.6)

    Drill Plan for Rear Connected Studs

    4.06 (103.2)0.06 (1.6)

    0.50 (12.7)

    0.55 (13.9) 0.70 (17.7)

    For Generator Breakers Only

    39 ~

    q Handle

    0.12 (3.2) Wide x 0.75 (19.0) Slots for Attachment Leads

    1.73 (44.0)

    0.19 (4.8) 1.05 (26.6) 0.21

    (5.3)

    0.50 (12.7)

    3.87 R 0.50 (12.7)

    1.06 (27.1)

    0.06 (1.6)

    3.81 (96.8)

    Trough for Attachment Leads

    0.50 (12.7)

    0.69 (17.6)

    1.00 (25.4)

    5.00 (127.0)

    5.77 (146.4)

    5.97 (151.5)

    43 ~

    q Breaker Handle

    q Breaker Handle

    Terminal Arrangements Cable type

    Wire Size (kcmil)

    number of Cables

    torque(Lb-in)

    Style number

    Catalog number

    Cu #3350 Single 275 5112A68G02 T300KCu 250500 Single 375 5112A69G02 T350KCu 3/0250 Double 275 4212B60G02 T400KCu/Al #3350 Single 275 5112A70G02 TA300KCu/Al 250500 Single 375 5112A71G02 TA350KCu/Al 3/0250 Double 275 4212B61G02 TA400K

    Breaker Status

    Dimensions

    a B C D e F

    On 5.39 5.20 5.69 5.61 4.72 4.77Off 4.16 4.21 4.46 4.64 4.95 4.91Tripped 4.77 4.69 5.08 5.11 4.89 4.89Reset 4.07 4.14 4.57 4.56 4.95 4.90

  • 7Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 6. Type KG 300400A Three PoleDimensions in Inches (mm)

    4.47 (113.5)

    8.87 (225.4)

    5.14 (130.6)

    3.52 (89.3)

    4.92 (125.0)

    0.84 (21.4)

    Front Cover Cutout4.78 (121.5)

    2.39 (60.7)

    1.25 (31.7)

    1.64 (41.7)0.83 (21.0)

    3.75 (95.2)

    2.62 (66.7)1.31 (33.3)

    0.18 R (4.8)

    0.34 R (8.7)

    1.72 (43.7)0.86 (21.8)

    8.44 (214.3)

    0.87 (22.2) Dia. (6-PLS) (Omit 2 Center Holes for Two-Pole)

    0.25-20 (M6) Tap 4 Holes

    3.73 (94.8)

    0.72 (43.7)

    0.72 (43.7)

    Drill Plan for Rear Connected Studs

    q Breaker Handle

    q Breaker Handle

    Drill Plan for Mounting Bolts Front Connected

    Terminals

    Load EndOPTIM Circuit Breakers OnlyOtherwise Same As Sheet 1

    Load EndLine End

    Load End

    Line End

    Line End

    q Breaker Handle

    q Breaker Handle

    1.37 (34.9)

    5.14 (130.6)

    10.50 (266.7)

    5.95 (151.2)

    8.87 (225.4)

    3.73 (94.8)

    1.37 (34.9)

    0.56 (14.3)

    3.44 (87.3)

    1.72 (43.7)

    3.37 (85.7)

    9.69 (246.1)

    3.37 (85.7)5.25 (133.3)

    0.69 (17.5)

    1.75 (44.4)

    1.75 (44.4)

    0.56 (14.3)

    0.62 (15.9)0.62 (15.9) 0.31 (7.9)

    1.71 (43.7)0.86 (21.8)

    3.73 (94.8)

    8.87 (225.4)

    5.14 (130.6)3.44 (87.3)

    1.72 (43.7)

    1.37 (34.9)

    0.87 (22.2) R Line End

    1.37 (34.9)

    0.44 (11.1) Dia.

    4 Holes for 0.31 (7.9) Mtg Bolts

    0.62 (15.9) Load End

    Drilling Plan for Mounting Panel Drawout Studs

    Terminal Arrangements Cable type

    Wire Size (kcmil)

    number of Cables

    torque(Lb-in)

    Style number

    Catalog number

    Cu #3350 Single 275 5112A68G02 T300KCu 250500 Single 375 5112A69G02 T350KCu 3/0250 Double 275 4212B60G02 T400KCu/Al #3350 Single 275 5112A70G02 TA300KCu/Al 250500 Single 375 5112A71G02 TA350KCu/Al 3/0250 Double 275 4212B61G02 TA400K

    Breaker Status

    Dimensions

    a B C D e F

    On 5.39 5.20 5.69 5.61 4.72 4.77Off 4.16 4.21 4.46 4.64 4.95 4.91Tripped 4.77 4.69 5.08 5.11 4.89 4.89Reset 4.07 4.14 4.57 4.56 4.95 4.90

  • 8Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 7. Type LG 450600A Three-PoleDimensions in Inches (mm)

    4x 0.31 (7.9) Mounting HolesFor 0.2520 x 1.50 (38.1)Mounting Screws 0.53 (13.5) From Top2x 2.63 (66.8) Line End2x 2.88 (73.2) Load End 0.53 (13.5) x 0.88 (22.4) From Bottom

    0.80 (20.3)

    1.50(38.1)

    0.31(7.9) R

    0.02(0.5)

    2.29(58.2)

    1.23 (31.2)

    0.75(19.1)

    0.38(9.7)

    0.30 (7.6)

    1.15 (29.2)

    1.13 (28.7)

    5.09(129.3)

    1.13 (28.7)

    4.00(101.6)

    5.62(142.7)

    10.75(273.1)

    2.28(58.0)

    1.59(40.6)

    3.02(76.7)

    5.05(128.3)

    5.96(151.4)

    11.34(288.0)

    9.53(242.1)

    4.87(123.7)

    4.26(108.2)

    0.42 (10.7)

    0.88 (22.4)

    0.44(11.2)

    12x 0.2520 Tap

    3.64(92.5)

    7.28(184.9)

    0.25 (6.4) R0.16 (4.1) R

    0.25 (6.4) R

    4.13(104.9)

    2.06(52.3)

    2.75(69.9)

    1.38(35.1)

    9.59(243.6)

    0.25(6.4)

    0.19 (4.8)

    8.25(209.6)

    4.13(104.9)

    2.75(69.9)

    5.50(139.7)

    12.50(317.5)

    6.49(164.8)

    Ove

    rall

    Ext

    end

    ed L

    eng

    th

    Load End

    Trip Unit May Be Either Thermal/Magnetic

    Or Electronic

    HandleMo

    un

    tin

    g H

    ole

    s

    Ext

    end

    ed Te

    rmin

    als

    Terminal BarrierUsed With ExtendedTerminals Only (TA603LD)

    0.52 (13.2) Hex 0.25 (6.4) x 0.33 (8.4) Hole

    Removable Terminal Cover Must Be in Place While in Service

    8x 0.15 (3.8) Hole 0.50 (12.7) x to Accept #8 Thread Cutting Screws

    Sta

    nd

    ard

    Term

    inal

    s

    Contact Position IndicatorsRed/IOnGreen/0OffWhiteTrip

    Line End

    3.50 (88.9) R

    1.27(32.3)

    0.06(1.5)

    0.53(13.5)

    3.81(96.8)

    4.06(103.1)

    4.38(111.3)

    1.00 (25.4) x 1.91 (48.5) R Wide

    1.00 (25.4) x 1.91 (48.5) R Wide

    450.22(5.6) 0.38

    (9.7)

    5.14(130.6)

    2.05(52.1)

    0.25(6.4) 0.53

    (13.5)

    0.06 (1.5) R

    45

    1.15(29.2)

    0.47(11.9)

    3.62(91.9)

    4.33(110.0)

    8.21(208.5)

    0.44(11.2)

    0.50(12.7)

    14.7

    ON

    19.2OFF

    24.2RESET

    0.2 TRIP

    6.69(170.0)

    0.50(12.7)

    0.47(11.9)

    0.61(15.5)

    A

    B

    0.38(9.7)

    Handle

    Handle

    6x 0.11 (2.8) x 0.31 (7.9) to Accept #6 Thread Cutting Screws

    0.13 (3.3) Wide x 0.75 (19.1) Slots for Attachment Leads

    Trough For Attach-mentLeads

    CL

    CL

    CL

    1.63(41.4)

    3.25(82.6)

    1.63(41.4)

    3.22(81.8)

    0.81(20.6)

    1.91(48.5)

    1.91(48.5)

    2.75(69.9)

    1.88 (47.8) Wide Conductorwith 0.41 (10.4) HoleLine and Load Ends(Current Carrying Parts Omitted in Center Pole for Two-Pole Breaker)

    Terminal Arrangements Cable type

    Wire Size (kcmil)

    number of Cables

    torque(Lb-in)

    Style number

    Catalog number

    Cu 250350 Double 275 4223B88G11 T602LDCu/Al 350350 Double 275 4223B88G02 TA602LDCu/Al 400500 Double 275 4223B89G02 TA603LD

    Breaker Status

    Dimensions

    a B

    On 6.18 (157.0) 6.61 (167.9)Off 4.16 (105.7) 4.58 (116.3)Tripped 5.30 (134.6) 5.74 (145.8)Reset 3.88 (98.6) 4.29 (109.0)

  • 9Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 8. Type LG 450600A Three-Pole Cutout and Drilling PlanDimensions in Inches (mm)

    4x 0.2520 Tap

    Line End

    Handle

    Breaker

    Load End

    Front Connected Drilling Plan

    5.05(128.3)

    9.53(242.1)

    1.38(35.1) 2.75

    (69.9)

    3.44(87.4)

    1.72(43.7)

    Handle

    Breaker

    R 0.25 (6.4)

    1.33(33.8) 2.29

    (58.2)

    3.28(83.3)

    1.50(38.1)

    R 0.19(4.8)3.64

    (92.5)7.28

    (184.9)

    Front Cover Cutout

    1.06 (26.9)6x for Three-Pole Breaker4x for Two-Pole BreakerOmit Center PoleTwo-Pole Breaker

    Line End

    Handle

    Breaker

    Load End

    5.08(129.0)

    9.60(243.8)

    2.75(69.9)

    5.50(139.7)

    Rear Connected StudsDrilling Plan

    CL

    CL

    CL

    CL

    CL

    CL

    Terminal Arrangements Cable type

    Wire Size (kcmil)

    number of Cables

    torque(Lb-in)

    Style number

    Catalog number

    Cu 250350 Double 275 4223B88G11 T602LDCu/Al 350350 Double 275 4223B88G02 TA602LDCu/Al 400500 Double 275 4223B89G02 TA603LD

  • 10

    Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 9. Type MG 700800A Three-PoleDimensions in Inches (mm)

    1.38(35.1)

    2.75(69.9)

    7.68(195.1)

    14.75(374.7)

    1.33(33.8)

    3.28(83.3)

    0.97(24.6)

    1.50(38.1)

    3.61(91.7)

    7.28(184.9)

    0.25(6.35)

    0.19(4.83)

    1.72(43.7)

    3.44(87.4)0.3116 Tap

    4 Holes

    Front Connected Drilling Plan

    Load End

    Line End

    Handle

    Breaker

    Front Cover Cutout

    0.53(13.5) 0.50

    (12.7)

    4.06(103.1)

    4.38(111.3)

    0.55(14.0)

    0.50(12.7)

    14.7

    19.224.2

    2.53(64.3)

    BA

    1.41(35.8)Max.

    2.02(51.3)

    0.42(10.7)

    On

    ResetOff

    HandlePivot

    0.20(5.1) Tripped

    7.68(195.1)

    14.75(374.7)

    1.38(35.1)

    2.75(69.9)

    2.75(69.9)

    5.50(139.7)

    8.30(210.8)

    16.00(406.4)

    4.13(104.9)

    8.25(209.5)

    6.05(153.7)

    11.50(292.1)

    Handle Pivot

    Load End

    Line End

    0.5013 Tap Thru

    0.81(20.6)

    1.63(41.4)

    3.25(82.6)

    1.87(47.5)

    0.38 (9.7) Diameter 4 Holes for 0.3116 x 1.75 (44.4) Lg Mounting Screws

    CL

    CL

    BreakerCL

    HandleCL

    CL

    1.63(41.4)

    Breaker Status

    Dimensions

    a B

    On 8.72 (221.5) 9.17 (232.9)Off 6.72 (170.7) 7.14 (181.4)Tripped 7.86 (199.6) 8.30 (210.8)Reset 6.44 (163.6) 6.84 (173.7)

    Terminal Arrangements Cable type

    Wire Size (kcmil)

    torque(Lb-in)

    Style number

    Catalog number

    Cu/Al (2) #1500 kcmil 375 672B657G01 TA700MA1Cu/Al (3) 3/0400 kcmil 375 672B655G01 TA800MA2Cu/Al (2) 500750 kcmil 500 1254C01G02 TA801MACu (2) 2/0500 kcmil 300 672B653G01 T600MA1Cu (3) 3/0300 kcmil 275 672B651G01 T800MA1

  • 11

    Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator

    eaton Corporation www.eaton.com

    Figure 10. Type NG 9001200A Three-PoleDimensions in Inches (mm)

    2.98(75.7)

    3.85 (97.8) R

    18.2

    RESET

    14.2OFF

    19.2

    On

    4.13(104.9)

    11.50(292.1)

    of

    Term

    inal

    s

    0.53(13.5)

    9.25(235.0)

    16.00(406.4)

    Ove

    rall

    Len

    gth

    8.25(209.6)

    14.75(374.7)

    of

    Mo

    un

    tin

    g H

    ole

    s

    0.06(1.5)

    1.10(27.9)

    0.38(9.7)

    0.35(8.9)

    0.06(1.5)

    1.03(26.2)

    8.62(218.9)

    0.53(13.5)

    1.16(29.5)

    AB

    1.06(26.9)

    0.53(13.5)

    7.00(177.8)

    0.30(7.6)

    0.95(24.1)

    0.13(3.3) R

    2.80(71.1)

    0.31(7.9) R

    3.81(96.8)

    2.51(63.8)

    1.38(35.1)

    2.75(69.9)

    2.98(75.7)

    2.35(59.7)

    6.01(152.7)

    0.75(19.1)

    0.38(9.7)

    3.24(82.3)

    0.06 (1.5) R

    0.25 (6.4) R

    0.09(2.3) R

    1.67(42.4)

    13.20(335.3)

    11.58(294.1)

    1.20(30.5)

    Tripped

    Line End

    Load End

    Handle

    0.13 (3.3) x 0.75 (19.1) Slots For Attachment Leads

    HandlePivot

    0.06(1.5) R

    0.06(1.5)

    4.09(103.9)

    5.06(128.5)

    2.00(50.8)

    0.09(2.3) R

    2.00(50.8)

    1.00(25.4)

    2.75(69.9)

    1.56(39.6)

    8.25(209.6)

    3.38(85.9)

    1.69(42.9)

    0.78(19.8)

    For Two-Pole Breaker Omit Current Carrying Parts From Center Pole

    Removable TerminalCover Must Be inPlace While in Service

    0.34 (8.6) Diameter Mounting Holes 0.70 (17.8) Diameter C'bore 4.45 Deep From Top 0.59 (15.0) Diameter C'bore 0.36 (9.1) Deep From Bottom

    0.5013 Tap12 Holes

    Removable TerminalCover Must Be inPlace While in Service

    Contact Position IndicatorRedOn/IGreenOff/OWhiteTripped

    0.2

    0.15 Diameter Hole0.52 Deep to Accept a #8 Thread Cutting Screw6 Places

    Trough for AttachmentLead

    3.34(84.8)

    5.19(131.8)

    5.25(133.4)

    5.50(139.7)

    6.00(152.4)

    7.19(182.6)

    View In Direction of Arrow "X"

    C L

    C L

    CL

  • Eaton CorporationElectrical Sector1111 Superior Ave .Cleveland, OH 44114United States877-ETN-CARE (877-386-2273)Eaton .com

    2011 Eaton CorporationAll Rights ReservedPrinted in USAPublication No . TD01214004E / Z11056April 2011

    Eaton is a registered trademark of Eaton Corporation .

    All other trademarks are property of their respective owners .

    Technical Data TD01214004EEffective April 2011

    Molded-case circuit breakers engine generator