Tata Power 2

Embed Size (px)

Citation preview

  • 8/10/2019 Tata Power 2

    1/39

  • 8/10/2019 Tata Power 2

    2/39

    ACKNOWLEDGEMENT:

    Our report will remain incomplete if we do not mention the efforts of

    those people who helped us in completing this project.Firstly we want to thank Mr. Binay Khalkho Manager-H.R. and

    Deepu Minz H.R. Dept TATA POWER Jamshedpur and the electrical

    department for letting us use the department data and carry out the

    necessary field work.

    We would like to express our gratitude to Mr.G.P.Shastry,

    Department Head, EMD, for his support, encouragement and all the

    technical help without which the completion of this project would

    have been impossible.

    We are also deeply indebted to Mr. Soumendra Mandal, EMD Project

    coordinator, whose technical input, stimulating suggestions and

    encouragement helped us in completion of report and provided us

    with practical on field knowledge of the subject.

    We also want to thank my co-trainees from various colleges who

    supported us in work. Their presence made our stay at TATA

    POWER a pleasant and learning experience in all aspects of life.

  • 8/10/2019 Tata Power 2

    3/39

  • 8/10/2019 Tata Power 2

    4/39

    CONTENTS

    Tata power

    Jojobera Thermal Power Plant

    Areas of operation

    Coal Handling Plant

    Boiler & Turbine Area

    Transformer Yard

    Electrical Switchyard

    Electrostatic Precipitator

    Transformers

    Conclusion

    Bibliography

  • 8/10/2019 Tata Power 2

    5/39

    Jojobera Thermal Power plant

    The Jojobera Thermal Power Plant, in Jamshedpur has an installed capacity of

    547.5MW. It has a 5 generating units comprising of a single 67.5MW unit and

    four units of 120MW each.

    Units:

    Unit#1: 67.5MW (commissioned in 1996)

    Unit#2: 120MW (commissioned in 2000)

    Unit#3: 120MW (commissioned in 2001)

    Unit#4: 120MW (commissioned in 2005)

    Unit#5: 120MW (commissioned in 2011)

    In total there are total 9 number of transmission lines going to various

    substations in the city.

    Transmission Lines (each 132kv):

    Line1: Golmuri

    Line2: Golmuri

    Line3: Golmuri

    Line4: Main Ring Substation (MRSS4)

    Line5: Blower House (TATA STEEL)

    Line6: Bara, Sonari

    Line7: Main Ring Substation (MRSS2)

    Line8: Main Ring Substation (MRSS2)

    Line9: Tata Growth Shop

  • 8/10/2019 Tata Power 2

    6/39

    Total number of bus couplers and bus sectionalizers used for transmission are:

    Bus sectionalizers: 4

    Bus couplers: 3

    Total bus sections: 6

    The transmission line diagram of the plant is as follows:

    RAW MATERIAL

    (COAL)CHP

    BOILER AND

    TURBINE

    TRANSFORMER

    YARDSWITCHYARD

    ELECTROSTATIC

    PRECIPITATOR

    FLY ASH

    AS SIDE

    PRODUCT

    TO DIFFERENT

    PLACES BY

    TRANSMISSION

    LINES

  • 8/10/2019 Tata Power 2

    7/39

    Areas of operationThe main area of operation or the division of the thermal power

    plant is into the following areas:

    Coal Handling Plant

    Boiler & Turbine Areas

    Transformer Yard

    Electrostatic Precipitator

    Switchyard

    COAL HANDLING PLANT

    Coal Handling Plant is the most essential part of any thermal plant. CHP is

    responsible for the procurement and the supply of the coal to the coal millbunkers so that the required supply of pulverized coal is obtained for the

    generation of power. CHP in thermal power plant comprises the process from

    the unloading till filling bunkers of respective coal mills in different units.

    Function and Capacity

    Procurement of coal

    Unloading , sizing and storing of coal

    Feeding of coal

    The design capacity of CHP is 1176TPH and rated capacity is 100TPH

    Middling coal from TISCO West Bokaro Collieries

    IB Valley coal from Mahanandi Coalfields Ltd.

    Coals are crushed by primary crusher and secondary crusher.

  • 8/10/2019 Tata Power 2

    8/39

    PROCESS FLOW CHART OF CHP

    Step 1 Railway Rakers

    Step 2 Wagon Tipplers

    Step 3 Hopper

    Step 4 Apron Feeder

    Step 5 Primary Feeder

    Step 6 Eccentric Disk Screen

    Step 7 Secondary Crusher

    Step 8 Conveyer

    Step 9 Bunker

    Specifications of Jojobera CHP plant:

    Capacity of CHP 1176 ton/hr

    Capacity of Wagon Tippler 105 ton

    Coal carrying capacity of one wagon 58-60 ton(approx.)

    Coal carrying capacity of one rake 3500 ton(approx.)Charging rate of side arm charger 20 wagon/hr

    Capacity of primary crusher 1176 ton/hr

    Capacity of secondary crusher 1176 ton/hr

    Total length of conveyer 3km(approx.)

    Input/ Output coal size primary crusher 600mm/150mm

    Input/ Output coal size secondary crusher 300mm/25mm

    Average coal consumption per day 30004000 ton

    Coal storage capacity of stockyard 1000 tons

    Major auxiliaries of CHP are:

    1. Wagon Tipplers:

    The wagon tippler is driven by 110KV motor and the top lamping device is

    actuated by hydraulic cylinders. Cylinders are operated by a hydraulic power

    pack which gives necessary fluid flow and pressure by means of 30KV

  • 8/10/2019 Tata Power 2

    9/39

    hydraulic motor to operate the hydraulic cylinder. All these motors are PLC

    controlled.

    Wagons arriving at CHP are placed by hydraulic operated side arm charger

    on wagon tippler which is driven by 415V ac, 125KV induction motor.TATA Honeywell PLC performs the entire of wagon tippling.

    Individual coal loaded wagons are placed on wagon tippler cradle. Wagon

    tippler raise command is given by operator and sequence of tippling

    operation starts in auto mode controlled by PLC.

    During tippling operation the along with loaded wagons rotates for 135

    140 degrees and dumps the coal into the hooper.

    2. Side Arm Chargers

    It is hydraulic equipment provided at wagon tippler to place coal wagons as

    per requirement avoiding the engagement of the locomotive during

    unloading operation. A batch of 2022 coal loaded wagon can be handled

    at a time. A 450KW motor in side arm chargers is connected with the SAC

    hydraulic power pack which delivers necessary torque to the SAC. SAC in

    each operation gets connected to the rack of the loaded wagon by swing arm

    and brings the individual wagon to cradle for tripling.

    3. Conveyer Belts:

    A conveyer belt (or belt conveyer) consists of two or more pulleys, with a

    continuous loop of materialthe conveyer beltthat rotates about them.

    One or both of the pulleys are powered, moving the belt and the material on

    the belt forward. The powered pulley is called the drive pulley while the

    unpowered pulley is called the idler.

    4. Primary Crusher:

    It is also known as rotator breaker. It is a horizontal drum having perforated

    screen plates inside the drum and is supporting rollers along with two guide

    rollers. Lifting shelves are fitted inside the drum which lifts up coal fed at

    one end during its rotation the coal is reduced in size and passes through the

    perforated screened plates having 150mm diameter holes. The uncrushed

  • 8/10/2019 Tata Power 2

    10/39

  • 8/10/2019 Tata Power 2

    11/39

    Practical arrangement in a simple steam power plant working on Rankine cycle

    is shown ahead.

    Thus in Rankine cycle, isothermal heat addition and heat rejection processes

    have been replaced by isobaric processes. Realization of isobaric heat additionand heat rejection in boiler and condenser respectively is in conformity

    with nature of operation of these devices. Isobaric heat addition can be had in

    boiler from sub cooled liquid to superheated steam without any limitations.

    Boiler mountings:

    Water level indicator

    Safety valve

    High steam and low pressure safety valves

    Fusible plugs

    Pressure gauge

    Stop valve

    Feed check valve

    Blowof cock

    Manhole and Mudbox

    Boiler accessories:

  • 8/10/2019 Tata Power 2

    12/39

    Super heater

    Economizer

    Air preheater

    Feed pump

    N.B :- Boiler mountings and accessories may vary for different types of boilers.

    Some of the boiler accessories and mountings are described below.

    Super Heater: Its purpose is to super heat steam and is a type of heat

    exchanger in which steam flows inside tubes and hot gases surround it.

    Economizer: It is also a heat recovery device in which feed water is

    heated from heat available with exhaust gases. Thus hot feed water

    available from economizer lowers the fuel requirement in combustion

    economizer also helps in removal of dissolved gases by preheating of

    water and thus minimizes tendency of corrosion and pitting.

    Feed pump: Feed pump is used for sending water into boiler at the

    pressure at which steam generation takes place. It is generally of three

    types i.e. centrifugal pump, reciprocating pump and injectors.

    Safety valve: Its function is to prevent the steam pressure from

    exceeding a limiting maximum pressure value. Safety valve should

    operate automatically by releasing excess steam and bring pressure

    down within safe limits.

    Pressure gauge: It is used for pressure measurement. Pressure is

    continuously monitored so as to avoid occurrence of over shooting of

    boiler pressure, although safety devices to protect boiler against pressure

    rising beyond a limit is provided but pressure gauges are also used for

    monitoring pressure.

    Stop valve: It regulates the flow of steam from the boiler. The is

    generally mounted on highest part of boiler shell and performs function

    of regulating the flow of steam from boiler. Stop valve generally has

    main body of cast steel; valve, valve seat and nut etc. are of brass.

    Manhole and Mudbox: Manhole provides opening for cleaning,

    inspection and maintenance purpose. Mudbox is a collection chamber

    for collecting the mud.

  • 8/10/2019 Tata Power 2

    13/39

    TURBINE AUXILLARIES:

    A steam turbine is a prime mover in which rotary motion is obtained by thegradual change of momentum of the steam. In a steam turbine following are the

    main parts:

    The nozzle in which energy of high pressure is converted in to kinetic

    energy, so that steam issues from nozzle at high velocity.

    The blade which change the direction of motion of steam issuing from

    the nozzle that force acts on the blade to change momentum and propel

    them.

    The auxiliaries are:

    Condensate extraction pump

    Hot well make up pump

    Grand stream condenser

    Surface condenser

    Extraction steam system

    LP Heater: A heater located between the condensate pump and either the

    boiler feed pump.

    HP Heater: A heater located downstream of the boiler feed pump.

    Deaerator: It is a device that is widely used for the removal of oxygen

    and other dissolved gases from the feed water to steam- generating

    boilers

    Operation:

    The steam cycle is working on a heat regeneration cycle. Feed water is supplied

    to the drum through the economizer outer limbs. Water in the boiler tubes

    absorbs heat from the furnaces. The mixtures of the water and steam is

  • 8/10/2019 Tata Power 2

    14/39

    discharged into the boiler drums. The separated saturated steam is led to super

    heater where it is heated to about 810K.

    Superheated steam from the boiler is fed to the turbine via the turbine top valve,

    emergency stop and governing valve. Steam first enters the HP turbine, getsexpanded here and then it is directed to the inlet of the LP turbine for further

    expansion. In the process the turbine starts rotating which in turn rotates the

    prime mover of the generator, thus producing electricity.

    Steam undergoing expansion in the allowed to flow through the condenser

    where the steam is condensed by cooling water supplied by C.W pumps. The

    condensate collected in the hot wells and pumped by vertical condensate

    extraction pumps to the de aerator through air ejector, gland steam condenser,

    drain cooler and LP heater. From the de aerator feed water storage tank, feed

    water is pumped to the economizer inlet header through two HP heater. During

    this process, the condensate steam is collected in different system. Heat is

    recovered at various points and is fed to the main feed water system.

    The ratings of UNIT #2 turbo generator of TATA Power Jojobera Power Plantis given below:

    1. K.W : 120000

    2. P.F : 0.8

    3. KVA : 150000

  • 8/10/2019 Tata Power 2

    15/39

    TURBO GENERATOR

    A turbo generator is a combination of a turbine directly connected to an electric

    generator for the generation of electric power. Large steam powered turbo

    generators provide the majority of the worlds electricity and are also used by

    steam powered turbo electric ships.

    Smaller turbogenerators with gas turbine is often used as auxiliary power

    units. For base loads diesel generators are usually preferred, since they offer

    better fuel efficiency, but on the other hand diesel generator have a lower power

    density and hence require more space.

    The efficiency of larger gas turbine plants can be enhanced by using a combined

    cycle, where the hot exhaust gases are used to generate steam which drives

    another turbo generator.

    Generator produces alternating current:

    The generator is connected to the turbine drive shaft. It has a moving partthe

    rotor and a fixed part the stator. The rotors outersurface is covered with

    electromagnets. The stators inner surface, or cylinder wall, is made up ofcopper windings. When the rotor turns inside the stator, the electrons in the

    copper windings vibrate. Their movement generates an electric currents,

    similar to the one created by Michael Faraday in his 1831 experiment on

    electromagnetic induction, but on a much larger scale.

    Turbine have a constant rotation speed:

    All the generators units in a power system must be synchronised. In other words

    its essential that they maintain an exact rotation speed. To ensure adequate

    power quality. Equipment that runs on electricity is designed to use alternating

    current of specific frequencies. This frequency depends on the generating units

    rotation speed i.e. the no of times per second that rotor magnet travel past the

    stator winding. This frequency is expressed in cycles per second, or hertz(Hz),

    named after the German physicist Heinrich Hertz, to prove the existence of

    radio waves.

  • 8/10/2019 Tata Power 2

    16/39

    Stator :-

    The stator consists of two party viz. The outer casing and inner framesupporting the core the winding outer casing is of welded construction welded

    tubes and ducts provide flow path for cooling. Inner stator consists of stator and

    core windings. Stator core stacked with insulated electrical sheet steel

    lamination clamping fingers ensures a uniform pressure and intensive cooling of

    stator core ends. Stator winding fractional pitched, two layers consisting of

    individual bars. To minimize the losses, the bars are separately brazed together

    and insulated from each other

  • 8/10/2019 Tata Power 2

    17/39

    TRANSFORMER YARD

    The transformer yard of Jojobera thermal plant comprises of following

    transformers:

    TYPE OF TRANSFORMER QUANTITY

    1. Generating transformer (GT) 5

    2. Unit Auxiliary transformer (UAT) 5

    3. Station transformer (ST) 3

    4. Sub station transformer (SST) 8

    Generating Transformer (GT)- 11KV/132KV

    The generating transformer is used as a step up transformer which produces

    11KV and steps up this voltage to 132KV for transmission. Electricity produced

    at 11KV cannot be transmitted owing to large losses due to heavy current at the

    voltage level. A generating transformer is used to increase the voltage level to

    132KV to meet the transmission requirements GTs are step up transformers

    with deltaconnected LV windings are connected to the transmission lines.

    Specifications:

    GT#1

    Make BHEL

  • 8/10/2019 Tata Power 2

    18/39

    Rating 90MVA

    Voltage 11/132KV

    CoolingHV

    LV

    ONAF ONAN30MVA 55MVA

    90MVA 55MVANo Load Voltage

    HV

    LV

    ONAF ONAN

    133V 139V

    10.5V 10.5V

    Line Current

    HVLV

    ONAF ONAN

    373.8A 228.4A4943.7A 3024.5A

    Phase 3

    Connection Y

    Frequency 50HzInsulation level

    HV

    LV

    ONAF ONAN

    660KV 275KV

    75KV 25KV

    Weight (of oil)

    (total)

    30500Kg

    116000Kg

    GT#2, GT#3, and GT#4

    Make BHEL

    Rating 90/120/150 MVA

    Voltage 11/132KV

    Cooling

    HV

    LV

    ONAF ONAN

    30MVA 55MVA

    90MVA 55MVA

    No Load Voltage

    HV

    LV

    ONAF ONAN

    133V 139V

    10.5V 10.5V

    Line Current

    HV

    LV

    ONAF ONAN

    373.8A 228.4A

    4943.7A 3024.5A

    Phase 3

    Connection Y

    Frequency 50Hz

    Insulation level

    HV

    LV

    ONAF ONAN

    275KV 650KV

    28KV 75KV

    Weight (of oil) 30500Kg

  • 8/10/2019 Tata Power 2

    19/39

    (total) 116000Kg

    Unit Auxiliary Transformer (UAT) 11KV/6.6KV

    UAT is a power transformer that supplies power to the auxiliary equipment of

    the power generating station during its normal operation. This transformer is

    connected directly to the generator output by a tapoff of the isolated phase

    bus duct and thus becomes the cheapest source of power to the generating

    station.

    It is generally a threewinding transformer where the primary winding is equal

    to the main generator voltage rating. The UATs are connected to the generators

    as step down transformers. Rated KVA of UAT is approximately 15% of thegenerator rating.

    Specifications:

    UAT#1

    Make BHEL

    Rating 11/6.6KV

    No Load VoltageHV

    LV

    11000V

    6600V

    Line Current

    HV

    LV

    656.1/787.3A

    1045.9/1255.1A

    Phase 3

    Vector group DdO

    Cooling ONAF/ONAN

    Impedance at normal temperature 8.76%Impedance at extreme temperature 8.05%

    Weight (of oil )

    (total)

    6265Kg

    16500Kg

    Station Transformer (ST)132KV/33KV/6.6KV

    A critical function of any electricity generation and distribution system is

    stepping up or down of voltage at various points in the delivery network. Thevoltage is stepped up or down at substations using station transformers. The se

  • 8/10/2019 Tata Power 2

    20/39

    may come in various sizes, depending upon the site transformers, but are

    normally connected to the network through overhead connections which results

    in exposed HV or LV bushings that necessitate a fence or other protective

    enclosure for personnel safety and security.

    At Tata Power Jojobera plant, there are three numbers of 3 winding

    132/22/6.6KV station transformers (ST#1, ST#2, ST#3) to cater to station loads

    such as CHP,DM water plant, AIC plant, ESP unit etc. These also supply power

    to the customers as Tata Motors, Tata Cummins, and Lafarge Cement at 33KV.

    There are two numbers of feeders for each recipient, normally which are kept

    ON from the Jojobera plant end.

    Specifications:

    ST#1, ST#2, ST#3

    Make BHEL

    Rating 75MVA

    Voltage 132/33/6.6KV

    Oil quantity 32250 Lts

    Cooling ONAF/ONAN

    Connection HVStar, MVStar, LVDelta

    Vector group HVMV: YNynoHVLV: YNd1

    Insulation level

    1.) Impulse withstand voltage2.) 1 min. Power frequency

    withstand voltage

    HV MV LV

    550 75 60230 28 20

    No load losses at rated voltage andfrequency

    42 KW

    Load losses at principal tap and rated

    output

    268 KW

    Auxiliary losses 5.2KW (Max.)

    Weight (of oil )

    (total)

    30500Kg

    116000Kg

    TRANSFORMERS AT JOJOBERA PLANT AND THEIR USES:

  • 8/10/2019 Tata Power 2

    21/39

    USTs are located in power plant to step down the voltage level from

    6.6KV to 415V. The rating for this transformer corresponds to the rating

    of the auxiliary load to be borne. Generally, these are stationed indoor

    and are dry type transformers.

    Power at Jojobera plant of Tata Power is evacuated at 132KV

    33KV system supplies power to Lafarge cement plant, Tata Cummins and

    TELCO. For each of the aforesaid units, there are two feeders of 33KV

    each. To facilitate this is a 33 kV bus with two incomers and one bus

    couplers. Each incomer is capable of bearing the full load.

    There are six 6.6 kV buses. All the HT motors, 6.6kV/440V transformers

    are connected to the 6.6kV buses employ SF6 breakers. If the unit trips

    then all the load gets transferred to the station transformer automatically.

    There are 14 415 V buses, all the 415V motors like ACW pumps, CCW

    pumps, valves, blowers, ACs are connected to the 415V bus system.

    SWITCHYARD

    Switchyard is protected area where all the switchgears and its equipment are

    installed power transmission. Switchgear is used for switching, controlling and

    protecting device. Switchgear equipment is essentially concerned with

    switching and interrupting currents either under normal or abnormal operatingconditions. Switchyard is hub for electrical power sources, transformers,

    remotely controlled arc snuffing breakers, metering devices etc.

    Switchyard forms the integral part of any power plant. These power plants have

    their main plant equipment integral controls as well as Plant Distributive

    Control System (DCS). While the entire plant is integrated at the DCS level,

    true unification is achieved by incorporating/integrating switchyard controls.

    Features:

    1.) Monitoring of status of switchyard equipment like isolators, circuit

    breakers etc.

    2.) Issue of close/open commands to isolators, breakers, etc.

    3.) Monitoring of system parameters like voltage, current, frequency, MW,

    MVAR, energy.

    4.) Controlling operations of protective relays.

    5.)Presentation of information useful to operator in different forms.

    6.) Generation of reports.

  • 8/10/2019 Tata Power 2

    22/39

    7.) Storage and revival of reports.

    8.) Remote control and monitoring of different kinds of frequencies

    through fibre optics/PLCC communication like wave traps.

    Switchyard Equipments

    CURRENT TRANSFORMER (CT)

    Current transformer is used to measure current at reduced current as well as for

    the protection of the system. It is mainly a step down current to known ratio.

    The primary of this transformer consists of one or more turns of thick wire

    connected in series with the line. The secondary consists of large number ofturns of fine wire which provides measuring instrument and relay a current

    which is a constant fraction of current in the line. It reduces heavy current

    flowing in the element of a power system to low values that are suitable for

    relay operation. Nickel iron is used for the construction of CT because it gives a

    good accuracy up to 5 times the rated current.

    Types of CT:

    a) Live Tank Current Transformer: In the live tank design, active part (i.e.core with secondary and primary duly insulated) is in the top tank. Top

    tank is live and secondary is insulated and taken to the bottom tank.

    b) Dead Tank Current Transformer: in dead tank design, active part is in

    bottom tank is in ground potential (i.e. dead) and the primary is insulated

    and taken to the top tank for primary termination.

    POTENTIAL TRANSFER (PT)

    Potential transformer is mainly a step down transformer which steps down thevoltage to known ratio. It is used for protection as well as measurement of

    voltage in the system. The primary of this transformer consists of a large

    number of turns which provides measuring instruments and relays, a voltage

    which is known fraction of line voltage.

    Types of PT:

    a) Capacitive Voltage Transformer (CVT): CVT is used to measure high ac

    voltage. It consists of capacitive potential divider and step down

  • 8/10/2019 Tata Power 2

    23/39

    transformer. Primary side of transformer is connected to the high voltage

    side together with capacitive and secondary side of transformer is having

    measuring instrument.

    Advantages of CVT are:

    Low impedance measuring device is used in CVT

    Cost of device reduced

    Loss is less

    b) Inductive Voltage Transformer (IVT): IVT are used for voltage metering

    and protection in high voltage network systems. They transform the high

    voltage into low voltage adequate to be processed in measuring and

    protection instruments secondary equipment, such as relays & recorders.

    ISOLATORS

    It is a disconnection switch which operates at no load condition both manually

    as well as remote. During faulty conditions circuit breaker operates first and

    then isolator is opened. After getting recovered from the fault, the isolator is

    closed first then the circuit breaker in order to avoid flashover.

    Isolators have provisions for a padlock so that inadvertent operation is not

    possible. In high-voltage or complex systems, these padlocks may be part of

    a trapped key-interlock system to ensure proper sequence of operation. In some

    designs, the isolator switch has the additional ability to earth the isolated circuit

    thereby providing additional safety. Such an arrangement would apply to

    circuits which inter-connect power distribution systems where both ends of the

    circuit need to be isolated.

    So definition of isolator can be rewritten as Isolator is a manually operated

    mechanical switch which separates a part of the electrical power system

    The main difference in isolator and a circuit breaker is that an isolator is an off

    load device intended to be opened only after a current has been interrupted by

    some other control device. Safety regulations of the utility must prevent any

    attempt to open the disconnector while it supplies current.

    Classification of isolators

  • 8/10/2019 Tata Power 2

    24/39

    Isolators are classified into three categories based on its breaking method.

    Horizontal break: In these isolators the operating arm moves in a

    horizontal plane. It can be further classified into:-

    1. Centre break2. Double break

    Vertical break

    Pantograph

  • 8/10/2019 Tata Power 2

    25/39

    CIRCUIT BREAKER

    The circuit breakers are the device, which is capable of making and breaking of

    an electrical circuit under normal and abnormal conditions. During normal

    operating condition the Circuit Breaker(CB) can be opened or closed by astation operator for the purpose of switching and maintenance. During the

    abnormal or faulty conditions the relays senses the fault and closes the trip

    circuit breaker. Thereafter the circuit breaker opens. The circuit breaker has two

    working positions, open & closed. These correspond to open circuit breaker

    contact and closed circuit breaker contact respectively. The operation of

    automatic opening and closing the contact is achieved by means of operating of

    the circuit breaker. As the relay contact closes the trip circuit is closed and the

    operating mechanism. In Tata Power, the 132kV breakers for GT#1,2,3 all ABBand arc SF6 circuit breaker in which closing and tripping charged spring.

    Classification of Circuit Breaker

    a) Oil Circuit Breaker: It employs the basic technique of oil for arc

    extinction. Upon interruption of the electric circuit, an electric arc forms

    between the contacts of the circuit breaker. Because of the high

    temperature of the arc the oil is evaporated and oil vapours are partially

    decomposed liberating ethylene, methane and other gases. A gas bubble

    is formed in the arcing zone; the pressure in the bubble may be as high as

    several dozen mega N/m2. The arc is then extinguished, both because of

    its elongation upon parting of contacts and because of intensive cooling

    by the gases and oil vapour.

    b) Vacuum Circuit Breaker: Vacuum circuit breakers are circuit breakers

    which are used to protect medium and high voltage circuits from

    dangerous electrical situations. A vacuum circuit breaker is such kind ofcircuit-breaker where the arc-quenching takes place in vacuum. The

    technology is suitable for mainly medium voltage application. For higher

    voltage vacuum technology has been developed but not commercially

    viable. The operation of opening and closing of current carrying contacts

    and associated arc interruption take place in a vacuum chamber in the

    breaker which is called vacuum interrupter. The vacuum interrupter

    consists of a steel arc chamber in the centre symmetrically arranged

    ceramic insulators. The vacuum pressure inside a vacuum interrupter is

    normally maintained at 10- 6

    bar.

  • 8/10/2019 Tata Power 2

    26/39

    c) Air Blast Circuit Breaker: It uses compressed air or gas as the interrupting

    or the breaking medium. Gases such as hydrogen, carbon-dioxide,

    nitrogen and Freon can be used as arc interrupting medium, but

    compressed air is the most suitable arc interrupting medium. The reason

    is nitrogen has the similar circuit breaking properties as that of

    compressed air medium. Carbon-dioxide has a drawback that is difficult

    to control owing to the freezing at valves and other restricted passages.

    Hydrogen has increased breaking capacity bit it is costlier. The air blast

    circuit breaker requires an auxiliary compressed air system which

    supplies air to the breaker air receiver.

    d) SF6 Circuit Breaker: A circuit breaker in which the current carrying

    contacts operate in sulphur hexafluoride or SF6 gas is known as an

    SF6 circuit breaker. SF6 has excellent insulating property. SF6has high

    electro-negativity. That means it has high affinity of absorbing free

    electron. Hence, for heavier and less mobile charged particles in SF6 gas,

    it acquires very high dielectric strength. Not only the gas has a good

    dielectric strength but also it has the unique property of fast

    recombination after the source energizing the spark is removed. The gas

    has also very good heat transfer property. Due to its low gaseous

    viscosity (because of less molecular mobility) SF6gas can efficiently

    transfer heat by convection. So due to its high dielectric strength and high

    cooling effect SF6 gas is approximately 100 times more effective arc

    quenching media than air. Due to these unique properties of this

    gas SF6 circuit breaker is used in complete range of medium voltage and

    high voltage electrical power system. These circuit breakers are available

    for the voltage ranges from 33KV to 800KV and even more.

  • 8/10/2019 Tata Power 2

    27/39

    LIGHTNING ARRESTER

    A lightning arrester is a device used electrical power systems and

    telecommunications systems to protect the insulation conductors of the system

    from the damaging effects of lightning. The typical lightning arrester has a highvoltage terminal and a ground terminal. When a lightning surge (or switching

    surge, which is very similar) travels along the power line to the arrester, the

    current from the surge is diverted through the arrester to earth.

    If protection fails or is absent, lightning that strikes the electrical system

    introduces thousands of kilovolts that may damage the transmission lines, and

    can also cause severe damage to transformers and other electrical or electronic

    devices. Lightning produced extreme voltage spikes in incoming power lines

    can damage electrical home appliances.

    Here zinc oxide arresters are used. Zinc oxide arresters have energy absorption

    level.

    Types:

    1. Rod gap arrester

    2. Horn gap arrester

    3. Multi gap arrester4. Expulsion type lightning arrester

    5. Valve type lightning arrester

  • 8/10/2019 Tata Power 2

    28/39

    RELAYS

    A relay is an electrically operated switch. Many relays use an electromagnet to

    mechanically operate a switch, but other operating principles are also used, such

    as solid-state relays. Relays are used where it is necessary to control a circuit bya low-power signal (with complete electrical isolation between control and

    controlled circuits), or where several circuits must be controlled by one signal.

    The first relays were used in long distance telegraph circuits as amplifiers: they

    repeated the signal coming in from one circuit and re-transmitted it on another

    circuit. Relays were used extensively in telephone exchanges and early

    computers to perform logical operations.

    A type of relay that can handle the high power required to directly control an

    electric motor or other loads is called a contactor. Solid-state relays control

    power circuits with no moving parts, instead using a semiconductor device to

    perform switching. Relays with calibrated operating characteristics and

    sometimes multiple operating coils are used to protect electrical circuits from

    overload or faults; in modern electric power systems these functions are

    performed by digital instruments still called "protective relays".

    BUS COUPLER

    The main function of bus coupler is to couple the busses. For each and every

    instrument a cable comes at the input terminal of bus coupler. Output terminal

    of this coupler goes to the control room. Thus each equipment can be controlled

    either manually or by control room. It comes into action if any fault occurs in

    the bus.

    Bus coupler configurations are available as non-terminated or internally

    terminated. If two or more non-terminated couplers are used on a bus, then the

    couplers at each end of the bus must be terminated externally with 78ohm terminators on the unused bus connections of the end couplers. Alternately,

    internally single terminated couplers (with or without the non-functional bus

    connectors) can be supplied.

    BUS SECTIONALIZERS

    The sectionalizer is a self-contained, circuit-opening device used in conjunctionwith source-side protective devices, such as reclosers or circuit breakers, to

    automatically isolate faulted sections of electrical distribution systems. Power tooperate the control circuitry and the mechanism is obtained from the line

  • 8/10/2019 Tata Power 2

    29/39

    ELECTROSTATIC PRECIPITATOR

    (E.S.P)

    An electrostatic precipitator (ESP) is a highly efficient filtration device that

    removes fine particles, like dust and smoke, from a flowing gas using the force

    of an induced electrostatic charge minimally impeding the flow of gases

    through the unit.

    In contrast to wet scrubbers which apply energy directly to the flowing fluid

    medium, an ESP applies energy only to the particulate matter being collected

    and therefore is very efficient in its consumption of energy (in the form of

    electricity

    Exhaust gases contain large quantity dust particles which are emitted into the

    atmosphere. This poses threat to mankind as devastating health hazard.

    The dust issuing from exhaust of the plant can most effectively be prevented

    from entering into atmosphere by employing ESP.

    Here de dusting of exhaust gases from boiler is done.

    Exhaust gases contain large quantity dust particles which are emitted into the

    atmosphere. This poses threat to mankind as devastating health hazard.

  • 8/10/2019 Tata Power 2

    30/39

    E.S.P advantages:

    Ability to treat volume of gases at high temperature.

    Ability to cope up with corrosive atmosphere.

    Offers low resistance path to gas flow. E.S.P uses intense electric forces to separate suspended particles from the

    flue gases.

    Processes involved:

    Electric charging of suspended particles.

    Collection of charged particles on collecting diodes.

    Removal of particles from collecting diodes.

    Five fields to keep emission within limits.

    Electromagnetic control system is used.

  • 8/10/2019 Tata Power 2

    31/39

    TRANSFORMERS

    A transformer is an electrical device that can change electrical energy of a

    given voltage into electrical energy at a different voltage level. It consists of twocoils arranged in such a way that the magnetic field surrounding of one coil cuts

    through the other coil. When an alternating voltage is applied to (across) one

    coil induces an alternating voltage in the other coil. Transformers will not work

    with direct current, since no changing magnetic field is produced, and therefore

    no current can be induced. The factor which determines whether a transformer

    is a step up or step down type is the turns ratio. The turns ratio in the primary

    winding to the number of turns in the secondary winding.

    The TATA power Jojobera division has got the following types of transformers:

    Generating Transformer (GT)5

    Station Transformer (ST)3

    Substation Transformer (SST)8

    Unit Auxiliary Transformer (UAT)5

    Essential parts of a Transformer:

    LV Winding:

    The LV Winding or Low Voltage winding is that winding of a

    transformer which has less number of turns compared to the high

    voltage winding. As a result, the voltage generated in this winding i.e.

    LV winding, also the LV winding is generally Delta connected.

    HV Winding:The HV winding or High Voltage winding has more number of turns

    as compared to the LV winding so voltage regulation is better. So the

    voltage required in this type of winding is more than the LV side. The

    HV winding is generally Star connected.

    Transformer Core:

    The core makes up the bulk of the transformer and so selection of proper

    material plays an important role in the transformers overall function,working and efficiency. A range of different cores exist viz... steel

  • 8/10/2019 Tata Power 2

    32/39

  • 8/10/2019 Tata Power 2

    33/39

    Transformer tank:

    Most power transformers are filled with transformer oil, a high dielectric

    fluid that both cools and insulates the windings. Transformer oil is ahighly refined mineral oil that cools the windings and insulation bu

    circulating within the transformer tank.

    Radiator:

    Radiators are used to circulate the oil in a transformer by natural

    convection.

    Conservator:

    A conservator as the name suggests is a reservoir used in conserving or

    storing oil. If the transformer tank oil reduces due to a kind of overload

    or any other ambient conditions, the conservator will feed the oil into the

    main tank and if expansion occurs in the transformer oil, that oil will go

    to the conservator.

    Buchholz relay:

    In the field of electric power distribution and transmission, a buchholz

    relay is a safety device mounted on some oil filled transformers

    equipped with an external overhead oil reservoir/conservator. It is used

    as a protective device sensitive to the effects of dielectric failure inside

    the equipment.

    On a slow accumulation of gas, due to slight overload or any ambient

    condition, gas produced by decomposition of insulating oil accumulates

    in the top of the relay and forces the oil level downward.

  • 8/10/2019 Tata Power 2

    34/39

    On load Tap Changer (OLTC):

    The OLTC is located in HV winding of a transformer. The tapping is

    taken from HV winding because..

    In HV winding, no. of turns is more, so voltage regulation is good.

    The LV winding is nearer to the core, so that less insulation can be

    provided between core and winding.

    In HV winding, current carrying capacity is less than LV winding.

    The function of OLTC is to give constant voltage to the secondary

    winding, rather maintain/regulate the output voltage of a transformer.

    Breather:

    When load on transformer increases or when the transformer is under fullload, the insulating oil in the transformer gets heated up, expands and

    gets expelled out into the conservator, thus subsequently pushing the dry

    air out of the conservator tank through the silica gel breather.

    When the oil cools down, air from the atmosphere is drawn into the

    transformer. This is called Breathing in of the transformer.

    During the breathing process, the incoming air may contain moisture and

    dirt which should be removed in order to prevent any physical damage.

    Hence the air is made to pass through Silica gel breather, which willabsorb the moisture in the air and ensure that only dry air enters into the

    transformer.

    Silica gel in the breather is blue when installed and they turn to pink

    colour after absorbing moisture, thus indicating replacement of the

    crystals. Thus silica gel breathers provide an economic and efficient

    means of controlling the level of moisture entering into the conservator

    tank during the breathing process.

    Neutral Grounding Resistor:

    The purpose of a Neutral Grounding Resistor (NGR) is to limit the

    ground fault current to a safe level so that all the electrical equipment in

    the power system is protected. The resistor should be the only current

    path between the neutral of the power transformers and ground.

    Cooling Fans:

    Oil Natural Air Forced (ONAF):

  • 8/10/2019 Tata Power 2

    35/39

    For oil filled transformers, the cooling ducts in the coils must be in

    sufficient number and size to allow dielectric fluid to flow through

    the coils to remove heat. This oil can move by simple convection

    (Oil Natural Air Natural) or it can be forced cooled by pumping

    fluid. Additionally, the tank surface must be large enough to

    transfer heat away from the fluid by the combined actions of

    conduction, convection or radiation. To maximise the cooling

    effect, cooling fans are added to expedite the heat removal through

    radiators.

    Thus ONAF uses natural circulation of the oil with the help of fans

    to increase the air flow and thus increase the rating of the

    transformer.

    Oil Natural Air Natural (ONAN):

    This is the simplest transformer cooling system. The full form of

    ONAN is "Oil Natural Air Natural". Here natural convectional

    flow of hot oil is utilized for cooling. In convectional circulation

    of oil, the hot oil flows to the upper portion of the transformer tank

    and the vacant place is occupied by cold oil. This hot oil which

    comes to upper side, will dissipate heat in the atmosphere by

    natural conduction, convection & radiation in air and will become

    cold. In this way the oil in the transformer tank continually

    circulate when the transformer put into load. As the rate of

    dissipation of heat in air depends upon dissipating surface of the

    oil tank, it is essential to increase the effective surface area of the

    tank. So additional dissipating surface in the form of tubes or

    radiators connected to the transformer tank.

    Oil Forced Air Forced (OFAF):

    OFAF means "Oil Forced Air Forced" cooling methods of

    transformer. In oil forced air natural cooling system of

    transformer, the heat dissipation is accelerated by using forced air

    on the dissipating surface but circulation of the hot oil in

    transformer tank is natural convectional flow.

    The heat dissipation rate can be still increased further if this oil

    circulation is accelerated by applying some force. In OFAF

    cooling system the oil is forced to circulate within the closed loop

    of transformer tank by means of oil pumps.

  • 8/10/2019 Tata Power 2

    36/39

    Minimum Oil Gauge (MOG):

    MOG in transformer is used to show analogic indication of oil level

    inside the conservator tank and upon requirement; it also gives alarm

    signals when the oil level reduces below minimum/maximum level.

    Oil Temperature Indicator (OTI) & Winding Temperature

    Indicator (WTI):

    Oil Temperature Indicator (OTI): The OTI measures the Top Oil

    Temperature. It is used for control and protection for all

    transformers. This device measures top oil temperature with the

    help of sensing bulb immersed in the pocket by using liquid

    expansion in the bulb through a capillary line to operatingmechanism. A link and lever mechanism amplifies this movement

    to the disc carrying pointer and mercury switches. When volume

    of the liquid in operating mechanism changes, the bellow attached

    to end of capillary tube expands and contracts. This movement of

    bellow is transmitted to the pointer in temperature indicator of

    transformer through a lever linkage mechanism.

    Winding Temperature Indicator (WTI):

    This device measures the LV and HV winding temperature. A

    winding temperature indicator or WTI is also used as protection of

    transformer. The basic operating principle of WTI is same as OTI.

    But only difference is that the sensing bulb pocket on transformer

    top cover is heated by a heater coil surrounded it. This heater coilis fed by secondary of current transformers associated with

    transformer winding. Hence the current through the heater coil is

    directly proportional to the electric current flowing through

    transformer winding.

  • 8/10/2019 Tata Power 2

    37/39

  • 8/10/2019 Tata Power 2

    38/39

  • 8/10/2019 Tata Power 2

    39/39