System Configuration Data Sheet February 2015 00806-0100-5100, Rev AA Rosemount Tank Gauging System www.rosemount-tg.com System Information In order to be able to correctly configure and assemble the parts of the system, the System Configuration Data Sheet must be filled in. It is also necessary to provide drawings of the tank farm layout with proposed location of Level Gauges, Field Displays, Tank Hubs, System Hubs, Field Bus Modems, TankMaster etc. Note The information on this form is used for tagging signs, temperature sensor specification and wireless network information only. No setting of device data base is done based on information on this data sheet. Please state all distances in metric units. System Overview Customer Information Rosemount Tank Gauging system number:_______________________ Installation site: ____________________________________________ Total number of tanks: _______________________________________ Year and Month: ____________________________________________ End Customer:_____________________________________________ Contact Name: _____________________________________________ Telephone: ________________________________________________ P.O. Reference No:___________________________________________ Customer Signoff: ______________________________________________________________________________________________________ Email address: _________________________________________________________________________________________________________ www ESD TankMaster PC in Network TankMaster.net for Web Access Alternative Connection to DCS/PLC/SCADA/Host 1420 Smart Wireless Gateway 2460 System Hub Alternative Connection to DCS/PLC/SCADA/Host Alternative Connection to DCS/PLC/SCADA/Host 5900C 775 3051S 5300 2160 3308 2410 644 2230 5900S 2240S 5400 3051S 644 5900S 2-in-1 2410 2410 5400 Alarm 644 Temperature Transmitter with Single Point Temperature Sensor Smart Wireless THUM Adapter 2230 Graphical Field Display 2410 Tank Hub Field Communicator 5300 Guided Wave Radar Transmitter 765 Multiple Spot Temperature and Water Level Sensor 2240S Multi-input TemperatureTransmitter 565/566 Multiple Spot Temperature Sensor 2120/2130/2160 Liquid Level Switch 3051S Pressure Transmitter 5900S Radar Level Gauge (2-in-1 optional) Still-pipe Array Horn LPG/LNG Still-pipe Array Cone LPG/LNG Parabolic 5900C Radar Level Gauge 3308 Wireless Guided Wave Radar Transmitter 5400 Radar Level Transmitter 5900S 2240S 2410 bolic 2180 Field Bus Modem

System Information Rosemount Tank … · System Information ... 5400 3051S 644 5900S 2-in ... For complete help on preplanning of a Tank Gauging Wireless network see Reference Manual

Embed Size (px)

Citation preview

System Configuration Data SheetFebruary 201500806-0100-5100, Rev AA

Rosemount Tank Gauging System

System InformationIn order to be able to correctly configure and assemble the parts of the system, the System Configuration Data Sheet must be filled in. It is also necessary to provide drawings of the tank farm layout with proposed location of Level Gauges, Field Displays, Tank Hubs, System Hubs, Field Bus Modems, TankMaster etc.

NoteThe information on this form is used for tagging signs, temperature sensor specification and wireless network information only. No setting of device data base is done based on information on this data sheet.

Please state all distances in metric units.

System Overview

Customer Information

Rosemount Tank Gauging system number:_______________________ Installation site: ____________________________________________

Total number of tanks: _______________________________________ Year and Month: ____________________________________________

End Customer:_____________________________________________ Contact Name: _____________________________________________

Telephone: ________________________________________________ P.O. Reference No:___________________________________________

Customer Signoff: ______________________________________________________________________________________________________

Email address: _________________________________________________________________________________________________________

www

ESD

TankMasterPC in Network

TankMaster.net for Web Access

Alternative Connectionto DCS/PLC/SCADA/Host

1420 Smart WirelessGateway

2460System Hub

Alternative Connectionto DCS/PLC/SCADA/Host

Alternative Connectionto DCS/PLC/SCADA/Host

5900C 775

3051S

5300

2160

3308

2410

644

22305900S2240S5400

3051S644

5900S 2-in-1

2410 2410

5400

Alarm

644 Temperature Transmitter with Single PointTemperature Sensor

Smart Wireless THUM Adapter

2230 GraphicalField Display

2410 Tank Hub

FieldCommunicator

5300 GuidedWave Radar Transmitter

765 Multiple Spot Temperature and Water Level Sensor

2240S Multi-input TemperatureTransmitter

565/566 Multiple Spot Temperature Sensor

2120/2130/2160Liquid Level Switch

3051S Pressure Transmitter

5900S Radar Level Gauge(2-in-1 optional)

Still-pipe Array Horn LPG/LNG Still-pipe Array Cone LPG/LNG

Parabolic

5900C Radar Level Gauge

3308 WirelessGuided Wave RadarTransmitter

5400 RadarLevelTransmitter

5900S 2240S2410

bolic

2180 FieldBus Modem

Fn1 2 34 5 67 8 9. 0 -

www.rosemount-tg.com

February 2015Rosemount Tank Gauging System

Tank Name Antenna Type Tank ProductTank Height

(mm)5900 Radar Tag Name

2410 Hub Tag Name

2240 Temp Tx Tag Name

2230 Display Tag Name

Note

2

February 2015 Rosemount Tank Gauging System

Tag/Tank name

L0 Temp sensor length include WLS (mm)

Position of temperature spot elements from sensor bottom end (mm)

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

T1 T2 T3 T4 T5 T6 T7 T8

T9 T10 T11 T12 T13 T14 T15 T16

3

February 2015Rosemount Tank Gauging System

Multiple Spot Temperature Sensor Multiple Spot Temperature Sensor with WLS

L= Distance from nozzle top to tank bottom

LW = Height of weight

LT = Total length of temp sensor and WLS

L0 = LT + 350 (mm)

Where:350 = Distance from top of sensor to lower thread (exact position of flange can be adjusted up or down about 100 mm at installation using the nuts and the 256 mm thread length)

Lowest temp. spot (T1) 0,5 - 1,0 m above tank bottom, min 300 mm from eye bolt in level sensor

Highest temp. spot 0,5 - 1,0 m below max level, min 1000 mm from top of sensor

L= Distance from nozzle top to tank bottom

LW = Height of weight

LT = Total length of temp sensor and WLS

L0 = LT + 350 (mm)

Where:350 = Distance from top of sensor to lower thread (exact position of flange can be adjusted up or down about 100 mm at installation using the nuts and the 256 mm thread length)

Lowest temp. spot (T1) 0,5 - 1,0 m above tank bottom, min 300 mm from eye bolt in level sensor

Highest temp. spot 0,5 - 1,0 m below max level, min 1000 mm from top of sensor

T1

LWLTLL0

T2T3

Min. 500 mm

Min. 1000 mm350

mm

Hig

hest

tem

pera

ture

ele

men

t <T1

6

Max Filling Level

T1

LWLTLL0

T2T3

Min

. 150

mm

Min. 500 mm

Min. 1000 mm350

mm

Hig

hest

tem

pera

ture

ele

men

t <T1

6

Max Filling Level

4

February 2015 Rosemount Tank Gauging System

Wireless Network Design (if included)

For complete help on preplanning of a Tank Gauging Wireless network see Reference Manual 300570EN. Tools to be used are a scaled sketch of the

installation site and AMS Wireless SNAP-ON Software.

Rule of 5 Found to be OK: Comments: _____________________________________________________________________________________

_____________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________

Rule of 3 Found to be OK: Comments:____________________________________________________________________________________

_____________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________

Rule of 25% Found to be OK: Comments:____________________________________________________________________________________

_____________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________

Make a small sketch of the planned Wireless Network or send a copy of the SNAP-ON design picture

5

Rosemount Tank Gauging World Headquarters

System Configuration Data SheetFebruary 2015

Rosemount Tank Gauging System00806-0100-5100, Rev AA

Emerson Process Management Box 130 45SE-402 51 GothenburgSWEDEN

+46 31 337 00 00+46 31 25 30 22 [email protected]

Rosemount Tank Gauging North America Inc.Emerson Process Management 6005 Rogerdale RoadMail Stop NC 13677072 Texas, Houston, USA

+1 281 988 4000+1 800 722 2865 [email protected]

Latin America Regional OfficeEmerson Process Management 1300 Concord Terrace, Suite 400Sunrise, Florida, 33323, USA

+1 954 846 5030+1 954 846 [email protected]

Asia Pacific Regional OfficeEmerson Process Management Asia Pacific Pte Ltd1 Pandan CrescentSingapore 128461

+65 6777 8211+65 6777 0947 [email protected]

Rosemount Tank Gauging Middle East & Africa.Emerson Process Management P. O Box 20048Manama, Bahrain

+973 1722 6610+973 1722 7771 [email protected]

The Emerson logo is a trademark and service mark of Emerson Electric Co.Rosemount and Rosemount logotype are registered trademarks of Rosemount Inc.All other marks are the property of their respective owners.

© 2015 Rosemount Tank Radar AB all rights reserved.