260
1 Simulation of Solar Powered Absorption Cooling System for Buildings in Pakistan A thesis submitted to The University of Manchester for the Degree of Doctor of Philosophy in the Faculty of Engineering and Physical Sciences 2016 Muhammad Asim School of Mechanical, Aerospace and Civil Engineering University of Manchester

Simulation of Solar Powered Absorption Cooling System for

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

1

Simulation of Solar Powered Absorption Cooling

System for Buildings in Pakistan

A thesis submitted to The University of Manchester for the Degree of

Doctor of Philosophy

in the Faculty of Engineering and Physical Sciences

2016

Muhammad Asim

School of Mechanical, Aerospace and Civil Engineering

University of Manchester

2

Table of Contents

Abstract ............................................................................................................................. 7

Declaration ........................................................................................................................ 8

Copyright Statement .......................................................................................................... 9

Acknowledgement........................................................................................................... 10

List of Publications ......................................................................................................... 11

List of Tables .................................................................................................................. 12

List of Figures ................................................................................................................. 13

Abbreviations and Symbols ............................................................................................. 17

Chapter 1: Introduction ................................................................................................... 22

1.1 Background ........................................................................................................... 22

1.2 Energy .................................................................................................................. 22

1.3 World Energy ....................................................................................................... 23

1.4 Pakistan and Energy .............................................................................................. 25

1.4.1 Electricity Generation History ....................................................................... 27

1.4.2 Current Status and Future Plans .................................................................... 28

1.5 Impact of the Energy Crisis ................................................................................... 30

1.6 Conclusion ............................................................................................................ 32

1.7 Aims and Objective ............................................................................................... 33

1.8 Structure of the Thesis .......................................................................................... 34

Chapter 2: Renewable Energy Resources in Pakistan ...................................................... 36

2.1 Introduction .......................................................................................................... 36

2.2 Renewable Energy Potential .................................................................................. 36

2.2.1 Wind Energy .................................................................................................. 36

2.2.2 Hydroelectric Energy ..................................................................................... 38

2.2.3 Solar Energy .................................................................................................. 39

2.3 Solar Energy Systems and Pakistan ....................................................................... 42

2.4 Current Status of Solar Energy Application ........................................................... 45

2.4.1 Photovoltaics ................................................................................................. 45

2.4.2 Solar Thermal ................................................................................................ 46

2.5 Institutional Infrastructure ..................................................................................... 47

2.5.1 Pakistan Council for Renewable Energy Technologies ................................... 48

2.5.2 Alternative Energy Development Board (AEDB) ............................................ 48

2.5.3 Educational Institutes .................................................................................... 48

2.5.4 Pakistan Engineering Council (PEC) ............................................................. 49

3

2.6 Doctoral Research on Solar Energy Potential in Pakistan ...................................... 49

2.7 Conclusion ............................................................................................................ 50

Chapter 3: Pakistan’s Climate and Buildings’ Energy ...................................................... 52

3.1 Introduction .......................................................................................................... 52

3.2 Geography of Pakistan .......................................................................................... 52

3.2.1 Population ..................................................................................................... 55

3.3 Climate of Pakistan ............................................................................................... 55

3.3.1 Temperature and Humidity ............................................................................ 56

3.4 Heat Index and Pakistan ........................................................................................ 57

3.5 Thermal Extremes in Pakistan ............................................................................... 59

3.6 Comfort Temperature ............................................................................................ 60

3.6.1 Standard Comfort Temperature ...................................................................... 60

3.6.2 Adaptive Thermal Comfort ............................................................................. 62

3.7 Building Energy in Pakistan .................................................................................. 65

3.7.1 Energy Efficient Buildings: ............................................................................ 66

3.7.2 Building Energy Code of Pakistan.................................................................. 67

3.7.3 Benefits of Introducing Building Energy Code in Pakistan ............................. 68

3.8 Case Study of Energy Efficiency Improvement in Existing Houses in Pakistan ..... 69

3.8.1 Results of the Case Study ............................................................................... 70

3.8.2 Findings on the Basis of Energy Efficient Housing Reports ............................ 74

3.9 Conclusion ............................................................................................................ 74

Chapter 4: Solar Cooling Systems ................................................................................... 76

4.1 Introduction .......................................................................................................... 76

4.2 Solar Electric Cooling ........................................................................................... 77

4.3 Solar Thermal Cooling .......................................................................................... 80

4.3.1 History of Solar Thermal Cooling Systems Development ................................ 81

4.3.2 World Solar Thermal Cooling Status 2014 and IEA Road Map 2050 .............. 82

4.3.3 Solar Thermal Cooling Systems ..................................................................... 82

4.4 Solar Thermal Collectors....................................................................................... 83

4.4.1 Stationary Collectors: .................................................................................... 84

4.4.2 Concentrating Solar Power (CSP) ................................................................. 88

4.4.3 Comparison of Thermal Collectors ................................................................ 93

4.5 Thermal Cooling Systems ..................................................................................... 94

4.5.1 Absorption System.......................................................................................... 95

4.5.2 Adsorption System.......................................................................................... 97

4

4.5.3 Solid and Liquid Desiccant Cooling System ................................................... 98

4.5.4 Ejector System ............................................................................................. 103

4.6 Solar Cooling for Hot Climates ........................................................................... 104

4.6.1 Solar Cooling System Research for Pakistan and India ................................ 108

4.7 Conclusion .......................................................................................................... 110

Chapter 5: Methodology ................................................................................................ 112

5.1 Introduction ........................................................................................................ 112

5.2 Experimental Study ............................................................................................. 113

5.2.1 Limitations of Experimental Study ................................................................ 115

5.3 Simulation Study................................................................................................. 116

5.3.1 Limitations of Simulation Study .................................................................... 117

5.4 Solar Energy System Simulation Programs ......................................................... 118

5.4.1 WATSUN ..................................................................................................... 118

5.4.2 Polysun ........................................................................................................ 119

5.4.3 f-Chart Method and Program ...................................................................... 119

5.5 Building Energy Simulation Programs ................................................................ 120

5.5.1 Energy Plus ................................................................................................. 120

5.5.2 Integrated Environment Solutions (IES) Virtual Environment (VE) .............. 121

5.5.3 TRNSYS ....................................................................................................... 122

5.5.4 TRNSYS Validity .......................................................................................... 127

5.6 Meteorological Data for Simulation Program ..................................................... 129

5.6.1 Weather Data Types ..................................................................................... 129

5.6.2 Pakistan Weather Data ................................................................................ 131

5.7 Conclusion .......................................................................................................... 136

5.7.1 Methodology ..................................................................................................... 136

5.7.2 Weather Data ............................................................................................... 137

Chapter 6: Building Model and Simulation ................................................................... 139

6.1 Introduction ........................................................................................................ 139

6.2 Building Model ................................................................................................... 140

6.3 TRNSYS Simulation Studio ................................................................................ 143

6.3.1 The Building’s Initial Parameters ................................................................ 144

6.3.2 Zones’ Thermal and Material Properties...................................................... 147

6.4 Building Model Initial Simulation Results .......................................................... 152

6.4.1 Internal Gains and Infiltration Addition ....................................................... 154

6.5 Building Model Modification ............................................................................. 156

5

6.5.2 Modified Building Model Results ................................................................. 158

6.5.3 Building Envelope Conduction ..................................................................... 159

6.6 Solar Cooling System Initial Parameters Calculations ......................................... 160

6.6.1 Chiller Cooling Capacity ............................................................................ 160

6.6.2 Solar Collector Calculation ......................................................................... 161

6.6.3 Cooling Systems Reference Model ................................................................ 162

6.7 Solar Cooling System Simulation ........................................................................ 163

6.7.1 Solar Cooling Process................................................................................. 163

6.7.2 Evacuated Tube Collector ............................................................................ 165

6.7.3 Hot Water Storage Tank ............................................................................... 167

6.7.4 Absorption Chiller ....................................................................................... 169

6.7.5 Cooling Coil ................................................................................................ 171

6.7.6 Cooling Tower ............................................................................................. 173

6.7.7 Pumps .......................................................................................................... 173

6.7.8 Fan .............................................................................................................. 174

6.7.9 Pipes ............................................................................................................ 176

6.7.10 Weather Data Reading and Processing ........................................................ 177

6.7.11 Controllers .................................................................................................. 178

6.8 Solar Cooling Simulation System ........................................................................ 181

6.9 Conclusion .......................................................................................................... 182

Chapter 7: Results and Discussion ................................................................................. 184

7.1 Introduction ........................................................................................................ 184

7.2 Evacuated Collector Energy Yield....................................................................... 184

7.3 Evacuated Tube Collector Efficiency .................................................................. 185

7.4 Room Cooling Load ............................................................................................ 186

7.5 Room Air Temperature ....................................................................................... 187

7.6 Storage Tank Heat Loss ...................................................................................... 188

7.7 Storage Tank Internal Energy Change ................................................................. 190

7.8 Pipe Heat Loss .................................................................................................... 191

7.9 The Solar Cooling System’s Electrical Energy Consumption .............................. 192

7.10 Cooling Tower ................................................................................................ 193

7.11 Absorption Chiller ........................................................................................... 194

7.12 Validation of Simulated Results ....................................................................... 195

7.12.1 Simulation Tool Validation .......................................................................... 196

7.12.2 Simulation Inputs Validation ....................................................................... 196

6

7.12.3 Simulation Results Validation ...................................................................... 196

7.13 Parametric Analysis ......................................................................................... 201

7.13.1 Collector Area and Flow .............................................................................. 203

7.13.2 Storage Tank Volume: .................................................................................. 205

7.13.3 Chilled Water Outlet Temperature ............................................................... 205

7.14 Conclusion ...................................................................................................... 208

Chapter 8: Conclusions and Recommendations ............................................................. 210

8.1 Summary ............................................................................................................ 210

8.2 General Discussion ............................................................................................. 210

8.2.1 Main Finding: Feasibility of Solar Thermal Cooling of a Building in Pakistan

210

8.2.2 Building Model and Energy ......................................................................... 211

8.2.3 Methodology ................................................................................................ 211

8.2.4 Solar Cooling System and Operational Parameters ...................................... 211

8.2.5 System Optimisation ..................................................................................... 213

8.2.6 Results Validation and Sensitivity Analysis................................................... 213

8.2.7 Conclusions and Recommendations ............................................................. 214

8.2.8 Addition to Knowledge ................................................................................. 215

8.3 Conclusions ........................................................................................................ 215

8.4 Recommendations ............................................................................................... 218

8.4.1 Energy and Solar Energy Data .................................................................... 218

8.4.2 Building Energy and Efficiency .................................................................... 218

8.4.3 Solar Thermal Cooling ................................................................................. 219

8.5 Further Studies .................................................................................................... 219

8.5.1 Building Energy and Efficiency .................................................................... 219

8.5.2 Solar Cooling System ................................................................................... 220

References 222

Appendices 243

Appendix A: Annual and Monthly Maximum Average Temperature and Relative

Humidity for District Cities of Pakistan ......................................................................... 243

Appendix B: World and Pakistan Solar Energy Maps with Solar Insolation for District

Cities of Pakistan .......................................................................................................... 246

Appendix C: Equipment Operation Parameters .......................................................... 253

Appendix D: System Heat Balance ............................................................................ 259

7

Abstract

This research investigates the potential of a solar powered cooling system for single family

houses in Pakistan. The system comprises water heating evacuated tube solar collectors, a hot

water storage tank, and an absorption chiller.

A literature review was carried out covering:

• Energy situation, climate, and renewable energy potential in Pakistan;

• Energy and thermal comfort in buildings, particularly for hot climates;

• Solar collectors and solar cooling systems, particularly for hot climates;

• Dynamic thermal simulation and weather data for solar energy systems and buildings.

It was found that Pakistan is short of energy and that there is a great need to cool buildings.

Renewable energy cooling systems are, therefore, of interest. The system described above

was selected, as it was found that solar energy is abundant in Pakistan when cooling is

required; thermal systems can be more economical than photovoltaics for hot climates and

suitable components (collectors, absorption chillers, etc.) are commercially available. The

TRNSYS dynamic thermal simulation program was selected as the main research tool, as it

has been tested for solar energy and building applications by many researchers and suitable

experimental facilities were not available.

A simple typical building in Pakistan with a solar cooling system was simulated. Optimum

values for key parameters were found by repeated simulations. It was concluded that the

system would be able to provide cooling when required without an auxiliary heat source, and

that an evacuated tube collector with a gross area of 12 m2, a collector flow rate of 165 kg/h,

and a storage tank volume of 2 m3 would provide satisfactory performance for a 3.52 kW

absorption chiller integrated with 42m3 single room. The results were in good agreement with

published results from other researchers.

Sensitivity analysis was carried out for the collector area, collector flow rate and storage tank

size. It was found that varying the collector area had the largest effect on system

performance, followed by varying the storage tank volume. Varying the collector flow rate

had the smallest effect.

It is recommended that solar cooling systems should be considered for Pakistan, and that

further research should be carried out into reducing building cooling loads, using surplus heat

for other loads, improving the performance of the proposed solar cooling system, and

comparing it with other systems such as photovoltaics.

8

Declaration

No portion of the work referred to in the thesis has been submitted in support of an

application for another degree or qualification of this or any other university or other institute

of learning.

9

Copyright Statement

i. The author of this thesis (including any appendices and/or schedules to this thesis) owns

certain copyright or related rights in it (the “Copyright”) and s/he has given The University of

Manchester certain rights to use such Copyright, including for administrative purposes.

ii. Copies of this thesis, either in full or in extracts and whether in hard or electronic copy,

may be made only in accordance with the Copyright, Designs and Patents Act 1988 (as

amended) and regulations issued under it or, where appropriate, in accordance with licensing

agreements which the University has from time to time. This page must form part of any such

copies made.

iii. The ownership of certain Copyright, patents, designs, trademarks and other intellectual

property (the “Intellectual Property”) and any reproductions of copyright works in the thesis,

for example graphs and tables (“Reproductions”), which may be described in this thesis, may

not be owned by the author and may be owned by third parties. Such Intellectual Property

and Reproductions cannot and must not be made available for use without the prior written

permission of the owner(s) of the relevant Intellectual Property and/or Reproductions.

iv. Further information on the conditions under which disclosure, publication and

commercialisation of this thesis, the Copyright and any Intellectual Property and/or

Reproductions described in it may take place is available in the University IP Policy (see

http://documents.manchester.ac.uk/DocuInfo.aspx?DocID=487), in any relevant Thesis

restriction declarations deposited in the University Library, The University Library’s

regulations (see http://www.manchester.ac.uk/library/aboutus/regulations) and in The

University’s policy on Presentation of Theses.

10

Acknowledgement

All praises to Almighty Allah who bestowed upon me the capabilities to complete this work.

I extend my sincerest thanks to my praise worthy supervisor Dr. Jonathan Dewsbury for his

precious time, valuable guidance, continuous support, constructive criticism, motivations and

incredible encouragements.

Finally, I am grateful to all of my family members who always support and pray for my

success. It is all because of their encouragements, prayers and support that enabled a

successful completion of this endeavor. I would also like to thank all of my colleagues and

friends for their continuous support.

Last but not least I am thankful to the University of Engineering and Technology, Lahore,

Pakistan for supporting me financially to carry on this research work

11

List of Publications

1. Muhammad Asim, Jonathan Dewsbury, Safwan Kanan, . TRNSYS Simulation of a

Solar Cooling System for the Hot Climate of Pakistan in SHC 2015, International

Conference on Solar Heating and Cooling for Buildings and Industry. 2015. 2-4

December, 2015, Turkey: Elsevier. (No publication details)

2. Safwan Kanan, Jonathan Dewsbury, Gregory F.Lane-Serff, Muhammad Asim,. The

Effect of Ground Conditions under a Solar Pond on the Performance of a Solar Air-

Conditioning System. in SHC 2015, International Conference on Solar Heating and

Cooling for Buildings and Industry. 2015. 2-4 December Turkey: Elsevier. (No

Publication details)

3. Safwan Kanan, Muhammad Asim, Rohan Kumar. A Simple Salt Gradient Solar Pond

Model for Lahore.Technical Journal, UET Taxila Pakistan, (Accepted, No Publication

details)

12

List of Tables

Table 1-1: Latest details of future electricity generation projects by fuel type ..................... 29

Table 2-1: Hydroelectric energy potential in Pakistan ......................................................... 39

Table 2-2: Solar energy application and types of collector used .......................................... 44

Table 3-1: Heat Index and its effects .................................................................................. 58

Table 3-2: Climate zones of Pakistan for comfortable temperature ..................................... 64

Table 3-3: Designed indoor (Td) globe temperature for selected cities ................................ 65

Table 3-4: Potential energy conservation areas ................................................................... 69

Table 4-1: History of solar thermal cooling development ................................................... 81

Table 5-1: Comparison of differences between experimental & TRNSYS simulation data 128

Table 6-1: Properties of materials assigned to walls and roof surfaces .............................. 156

Table 6-2: Room envelope heat conduction calculations ................................................... 159

Table 6-3: COP of absorption chillers ............................................................................... 160

Table 6-4: Pumps power and flow rates ............................................................................. 174

Table 6-5: Pipes size and flow rates................................................................................... 177

Table 6-6: Collector pump controller inputs ...................................................................... 178

Table 7-1: Comparison of simulated vs published results………………………………….197

Table 7-2: Summary of parameters used by researcher for parametric analysis……………202

Table 7-3: Sensitivity of storage tank volume on tank heat loss and internal energy and

collector efficiency………………………………………………………………………….205

13

List of Figures

Figure 1-1: Global energy source consumption growth % from 2012 to 2013 ..................... 23

Figure 1-2: Global energy source consumption growth from 2012-2035 .............................. 24

Figure 1-3: World primary energy demand projection ........................................................ 25

Figure 1-4: Pakistan’s primary energy consumption by fuel 2013 ........................................ 26

Figure 1-5: Electricity generation by fuel type 2015 ............................................................ 28

Figure 1-6: Electricity demand and supply 2012-19 ............................................................ 29

Figure 1-7: Electricity consumption by economic groups ................................................... 30

Figure 1-8: Activities most affected by power outage ......................................................... 31

Figure 2-1: Wind energy potential of Pakistan .................................................................... 37

Figure 2-2: Solar energy spectrum distribution ................................................................... 39

Figure 2-3: Solar energy balance on earth ........................................................................... 40

Figure 2-4: Solar insolation over Pakistan .......................................................................... 42

Figure 2-5: PV and solar thermal power systems power range and global irradiation .......... 43

Figure 2-6: Regions of world appropriate for solar thermal power plants ............................ 43

Figure 3-1: Geography of Pakistan ..................................................................................... 53

Figure 3-2: Administrative areas of Pakistan ...................................................................... 53

Figure 3-3: Area distribution of Pakistan ............................................................................ 54

Figure 3-4: Population distribution of Pakistan ................................................................... 54

Figure 3-5: Population density in 2010 ............................................................................... 55

Figure 3-6: Pakistan annual mean daily temperature ........................................................... 56

Figure 3-7: Pakistan normal mean heat index distribution ................................................... 58

Figure 3-8: Areas of moderate and severe heat wave frequency in South Asia .................... 60

Figure 3-9: ASHRAE standard comfort temperature zone .................................................. 61

Figure 3-10: Acceptable temperature ranges for naturally conditioned spaces ASHRAE 55

rev. 2003 ............................................................................................................................ 63

Figure 3-11: 30 years average monthly mean daily temperatures ........................................ 64

Figure 3-12: Climate zone map of Pakistan………………………………………………….68

Figure 3-13: Outside air and inside temperature with solution comparison during day time..71

Figure 3-14: Comparison of outside air and inside temperature with solutions at midnight...72

Figure 3-15: Initial cost of different solutions ..................................................................... 73

Figure 3-16: 10 years cost of different solutions ................................................................. 73

Figure 4-1: Schematic overview of solar electric cooling system ........................................ 77

14

Figure 4-2: Schematic diagram of vapour compression refrigeration system ....................... 78

Figure 4-3: Solar light spectrum used in a PV system ......................................................... 80

Figure 4-4: Overview of thermal cooling system ................................................................ 83

Figure 4-5: Solar energy collector’s application .................................................................. 84

Figure 4-6: Types of solar thermal collectors ...................................................................... 84

Figure 4-7: Construction of flat plate collector ................................................................... 85

Figure 4-8: Schematic diagram of compound parabolic collector ........................................ 86

Figure 4-9: Schematic diagram of evacuated tube collector ................................................ 87

Figure 4-10: Linear Fresnel reflector (Left) & compact linear Fresnel reflector (Right) ...... 89

Figure 4-11: Schematic overview of power tower (central receiver system) ........................ 90

Figure 4-12: Schematic of a parabolic trough collector ....................................................... 91

Figure 4-13: Parabolic trough collector tracking mechanism .............................................. 92

Figure 4-14: Schematic of a parabolic dish ......................................................................... 93

Figure 4-15: Yearly thermal performance of stationary and tracking collectors ................... 94

Figure 4-16: Schematic overview of solar absorption cooling system ................................. 96

Figure 4-17: Schematic diagram of solar adsorption system ............................................... 98

Figure 4-18: Desiccant cooling process .............................................................................. 99

Figure 4-19: Principle of desiccant cooling ......................................................................... 99

Figure 4-20: An illustration of solar assisted solid desiccant cooling system ..................... 100

Figure 4-21: A Solar assisted liquid desiccant cooling system .......................................... 102

Figure 4-22: Schematic view of solar ejector cooling system ............................................ 103

Figure 5-1: Building model and low zero carbon technologies analysis ............................ 122

Figure 5-2: Model diagram in TRNSYS simulation studio view ....................................... 124

Figure 5-3: TRNSYS simulation result plot overview ....................................................... 125

Figure 5-4: TRNBuild wall and windows types and area selection .................................... 126

Figure 5-5: TRNBuild wall type manager with construction materials .............................. 126

Figure 5-6: Climatic comparison between Lahore and Amritsar ....................................... 132

Figure 5-7: Amritsar daily mean temperature (EPW vs WMO) ......................................... 133

Figure 5-8: Lahore temperature comparison (WMO vs TMY2) ........................................ 134

Figure 5-9: Pakistan’s cities maximum average temperature from TMY2 .......................... 134

Figure 5-10: Pakistan’s cities average relative humidity from TMY2 ............................... 135

Figure 5-11: Pakistan’s cities average global horizontal radiation from TMY2 .................. 135

Figure 6-1: Typical single storey house in urban Punjab ................................................... 140

Figure 6-2: Typical single storey house in rural Punjab .................................................... 140

15

Figure 6-3: Model building location ……………………………………………………….141

Figure 6-4: Trnsys-3d two zone (room) model back and top views. ................................... 142

Figure 6-5: Trnsys-3d two zone (room) model front view .................................................. 142

Figure 6-6: Import of Tnsys3d model into simulation studio step-1 ................................... 143

Figure 6-7: Import of Trnsys3d model step- 2.................................................................... 143

Figure 6-8: After import of Tnsys3d model final window in simulation studio .................. 144

Figure 6-9: Parameters for heat transfer co-efficients......................................................... 146

Figure 6-10: Standard and user defined inputs ................................................................... 146

Figure 6-11: Building outputs ............................................................................................ 147

Figure 6-12: Room1volume, surface and areas calculated by TRNSYS ............................. 148

Figure 6-13: Properties of material assigned to external roofs ........................................... 149

Figure 6-14: Properties of windows assigned..................................................................... 150

Figure 6-15: Radiation and geometry modes ..................................................................... 152

Figure 6-16: Initial result, room 1 and room2 air temperatures .......................................... 153

Figure 6-17: Ambient and room 1 temperature comparison ............................................... 153

Figure 6-18: Ambient and room 2 temperature comparison ............................................... 154

Figure 6-19: Room1 air temperature with initial gain, infiltration, and ventilation ............. 155

Figure 6-20: ASHRAE standard materials assigned to walls, roof and floor ..................... 157

Figure 6-21: ASHRAE standard properties of windows 1001 ............................................ 157

Figure 6-22: Room 1 temperature after assigning walls and windows materials ................. 158

Figure 6-23: Solar cooling system ..................................................................................... 164

Figure 6-24: Evacuated tube collector TYPE 71 efficiency curve for I =1000 W/m2 .......... 165

Figure 6-25: Collector solar data input .............................................................................. 167

Figure 6-26: Operation of hot water storage tank ............................................................... 168

Figure 6-27: Tank inlet and outlet connections .................................................................. 169

Figure 6-28: Absorption chiller input and out connections ................................................. 170

Figure 6-29: Cooling coil connections ............................................................................... 172

Figure 6-30: Auxiliary cooler connections ......................................................................... 173

Figure 6-31: Pumps connection ......................................................................................... 174

Figure 6-32: Fan connections ............................................................................................ 175

Figure 6-33: Pipes connections .......................................................................................... 176

Figure 6-34: Weather data processor connections .............................................................. 177

Figure 6-35: Collector pump controller connection ............................................................ 180

Figure 6-36: Room air fan controller connections .............................................................. 181

16

Figure 6-37: Complete process diagram of solar cooling system ........................................ 182

Figure 7-1: Solar collector monthly yield (kWh) ............................................................... 185

Figure 7-2: Collector monthly and annual efficiency (%) .................................................. 186

Figure 7-3: Room monthly cooling load and solar energy availability (kWh) .................... 187

Figure 7-4: Ambient (Blue) and room (Red) temperature comparison (°C) ........................ 188

Figure 7-5: Tank heat loss (kWh) ...................................................................................... 189

Figure 7-6: Tank heat loss as percentage of energy collected (%).........................................189

Figure 7-7: Ambient and tank temperature with solar radiation available in July-August…190

Figure 7-8: Tank internal energy change (kWh) ................................................................ 191

Figure 7-9: Pipes heat loss to and from ambient air (kWh) ................................................ 192

Figure 7-10: Monthly Electrical Energy Load (kWh) ........................................................ 193

Figure 7-11: Auxiliary cooler heat rejected (kWh) ............................................................. 194

Figure 7-12: Chiller actual and rated COP ......................................................................... 194

Figure 7-13: Chilled water outlet temperature with the TRNSYS provided data file ......... 198

Figure 7-14: Chilled water outlet temperature with referenced data file ............................. 199

Figure 7-15: Energy balance of solar cooling system ......................................................... 200

Figure 7-16: Annual input and output energy distribution………………………………….200

Figure 7-17: Sensitivity of collector area and annual energy collected and efficiency…….204

Figure 7-18: Sensitivity of collector flow rate and annual energy collected and efficiency..204

Figure 7-19: Variation of maximum chilled water temperature and number of hours above set

point with collector area…………………………………………………………………….206

Figure 7-20: Variation of maximum chilled water temperature and number of hours above set

point with tank storage volume……………………………………………………………..207

Figure 7-21: Sensitivity of storage tank volume and maximum chilled water temperature and

number of hours above set point……………………………………………………………208

17

Abbreviations and Symbols

$ Dollar

£ Pound Sterling

Coefficient of Transmittance

€ Euro

µm Micro metre

3D Three Dimensional

A Area

ACH Air changes per hour

AEDB Alternative Energy Development Board

ASHRAE American Society of Heating Refrigerating and Air-Conditioning

Engineers

a-Si Amorphous Silicon

a-SiC Amorphous Silicon Carbide

a-SiGe Amorphous Silicon Germanium

a-SiN Amorphous Silicon-Nitride

BECP Building Energy Code of Pakistan

BEE Bureau of Energy Efficiency (India)

BLAST Building Load Analysis And System Thermodynamics

BP British Petroleum

CDA Capital development Authority (Islamabad)

CdS Cadmium Sulphide

CdTe Cadmium Telluride

CH4 Methane gas

CIBSE Chartered Institution for Building Services Engineers

CIGS Copper Indium Gallium Selenide

CIS Copper Indium Selenide

CLFR Compact Linear Fresnel Reflectors

CNG Compressed Natural Gas

CO2 Carbon dioxide

Coll. Collector

COP Coefficient of Performance

CP Specific Heat at Constant Pressure

CPC Compound Parabolic Collectors

CPV Concentrating Photo Voltaic

CRS Central Receiver System

c-Si Crystalline Silicon

CSP Concentrating Solar Power

CSU Colorado State University

18

CTZ California Climate Zones

Cu2S Cuprous sulphide

CuInSe2 Copper Indium Diselenide

CWEC Canadian Weather for Energy Calculation

DC Direct current

DDY Design Day Data

DHW Domestic hot water

DNI Direct Normal Irradiation

DOE Department of Energy (US)

DSG Direct Steam Generation

DSSC Dye-sensitised solar cell

E East

ECBC Energy conservation building code(India)

EME College of Electrical and Mechanical Engineering (Pakistan)

ENERCON National Energy Conservation Centre (Pakistan)

EPW Energy Plus Weather

ESTIF European Solar Thermal Industry Federation

ETC Evacuated Tube Collectors

ETP Energy Technology Prospective

FATA Federally Administrated Tribal Area

FPC Flat Plate Collector

GaAs Gallium Arsenide

GBP British Pound Sterling

Gt Giga ton

GUI Graphic User Interface

g-value Solar energy transmittance of transparent material (glass) (%)

GW Giga Watt

GWh Giga watt hour

GWp Giga Watt Peak

GWth Giga Watt Thermal

H2O Water

HI Heat Index

hr Hour

HVAC Heating Ventilation and Air Conditioning

HW Heat Wave

HX Heat exchanger

I Incident solar Insolation

IAM Incidence Angle Modifiers

ID Identification

IEA International Energy Agency

IES Integrated Environment Solution

19

In Inlet

ISO International organisation for standardisation

IT Total incident solar Insolation

IWEC International Weather for Energy Calculation

J Joule

k Kilo

K Kelvin

kg Kilo gram

kJ Kilo joule

km Kilo metre

KPK Khyber Pakhtun Khwa (Pakistan)

KSK Kala Shah Kaku (Lahore)

kW Kilo Watt

kWC Kilo Watt cooling

kWh Kilo Watt Hour

LED Light Emitting Diode

LEED Leadership in Energy and Environmental Design

LFR Linear Fresnel Reflectors

LiBr Lithium Bromide

LPG Liquefied Petroleum Gas

m Mass flow rate / metre

m2 Square metre

m3 Cubic metre

MENR Ministry of energy and natural resources (Turkey)

mh Fluid flow rate to and from heat source

MJ Mega Joule

mL Fluid flow rate to and from load source

Mt Mega ton (metric)

MW Mega Watt

MWh Mega Watt Hour

MWP Mega Watt Peak

N North

N2O Nitrous Oxide

NASA National Aeronautics and Space Administration

NCDC National Climatic Data Centre

NED Nadirshaw Edulji Dinshaw (Pakistan)

NEPRA National Electric Power Regulatory Authority (Pakistan)

NESPAK National Engineering Services Pakistan

NGO Non-Governmental Organisation

NH3 Ammonia

20

NIST National Institute of silicon Technology (Pakistan)

nm Nano metre

NOAA National Oceanic and Atmospheric Administration

NOx Nitrogen Oxides

NREL National Renewable Energy Laboratory

NSRDB National solar radiation date base (US)

NUST National University of Science and Technology (Islamabad)

OCA Optical Coupling Agent

Out Outlet

Pa Pascal

PCAT Pakistan council for appropriate technologies

PCRET Pakistan Council for Renewable Energy Technologies

PCSIR Pakistan Council for Scientific and Industrial Research

PEC Pakistan Engineering Council

PMD Pakistan Meteorological Department

PMISP Prime Minister’s Initiative for Solar Power (Pakistan)

PMV Predicted mean vote

PPD Predicted percentage of dissatisfaction

PSVEP Parliamentarian Village Electrification Program (Pakistan)

PV Photo Voltaic

Qc Condenser heat rate

Qe Evaporator heat rate

Qg Generator heat rate

QS Solar energy incident on panel

Qu Useful heat energy rate

RC Reinforced Concrete

R-value Thermal resistance of insulator

SHGC Solar Heat Gain Coefficient

SHS Solar Home System

SOx Sulphur Oxides

SRCC Solar Rating and Certification Commission

SSE Surface meteorology and solar energy (NASA)

SWH Solar Water Heating

Ta Air temperature

Tamb Ambient temperature

Tc Comfortable Temperature

Tc Collector temperature

Td Design Indoor Temperature

TEG Tri-Ethylene Glycol

Tenv Environment temperature

TESS Thermal Energy Systems Specialists

21

Tg Indoor Globe Temperature

TH Upper Input temperature

Ti Indoor Temperature

TIN Temperature for high limit monitoring

TiO2 Titanium Dioxide

TL Lower Input temperature

TMAX Maximum Input temperature

TMY Typical Meteorological Year

TO Operative temperature

TOLT Outdoor Long Term Temperature

TR Ton of Refrigeration

Tr Mean radiant temperature

TRNSYS TRaNsient SYstem Simulation

TRY Test reference year

TWh Tera Watt Hour

TWhth Terra Watt Hour Thermal

UAE United Arab Emirates

UET University of Engineering and Technology (Pakistan)

UK United Kingdom

UN United Nation

UNEP United Nation Environment Program

USA United states of America

USAID United States Agency for International Development

USD United States Dollar

U-value Overall heat transfer co-efficient (W/m2.K)

VE Virtual Environment

W Watt

w Work rate

WMO World Meteorological Organization

wPV Photo voltaic work rate

wT Total work rate

γI Input control function

γo Output control function

ΔT Change in Temperature

ΔTH Upper dead band temperature difference

ΔTL Lower dead band temperature difference

η cool Cooling efficiency

ηsol.cool Solar cooling efficiency

θc Acceptance Angle

μc-Si Microcrystalline Silicon

22

Chapter 1: Introduction

1.1 Background

Titled “Solar Cooling”, although this study has been done for the climatic conditions of

Lahore, Pakistan, it is expected that the results will also be useful for other countries in the

south Asia region which have similar climate and building construction styles.

The main aim of this work (as explained in more detail in later sections of this chapter) is to

investigate the potential and operational feasibility of a solar cooling system for buildings in

the context of Pakistan’s climate and location. The thermal performance of a solar collector,

solar energy availability, building cooling load profile with existing construction materials

and performance of an absorption chiller were investigated.

This chapter gives brief information about world energy consumption and a background to

the energy crisis in Pakistan, current status and future electricity generation plans to

overcome the energy crisis through the contribution of renewable energy in primary energy

consumption. The future electricity demand and impact of the energy crisis on domestic users

is also presented. At the end of the chapter, detailed aims and objectives, as well as the

structure of the thesis, are given.

1.2 Energy

Energy is an important commodity for continued human development and economic growth.

The availability of sufficient, affordable energy is a vital key to eradicating poverty,

improving human welfare and raising living standards worldwide. Historically, fossil fuels

have been the main source of energy supply and have contributed a major part in fulfilling

human energy demands. Renewable energy sources have also been important for humans

from early times. For example, biomass has been used for heating and cooking, and wind

energy for transport and, later, for electricity production [1, 2].

The current sources of energy, with a major contribution from fossil fuels, have three main

concerns: depletion of resources, environmental impacts and the security of energy supply.

The increasing demand and limited reserves have led to the exploration of alternative sources

of energy. The continuous consumption of fossil fuels has had various impacts on the natural

environment. The global implications include global warming and local impacts, such as an

effect on human health and the ecology. Onshore oil and gas drilling, exploration and

23

production waste (fluids and solids) have contaminated the surroundings. Coal mining and

exploration has resulted in land degradation through mine fires and the impact of mining on

forest areas is of particular concern. Nuclear energy is linked to real threats of radioactive

emissions and is also of concern due to its possible association with military use, the impact

of mining nuclear fuel and nuclear waste hazards. Renewable energy sources (biomass, solar,

wind, geothermal and hydropower) are cleaner energy sources. Renewable energy sources

have the potential to provide energy with zero or almost zero emissions of air pollutants and

greenhouse gases [1, 2].

1.3 World Energy

The BP Statistical Review of World Energy 2014 reveals that the world’s primary energy

consumption grew by 2.3% in 2013 compared to the previous year. As such, the global oil,

gas, and coal reserves at the end of 2013 are predicted to last 53.3, 55.1 and 113 years,

respectively, at current production rates. The affirmed reserves are quantities that geological

and engineering information indicate, with reasonable certainty, can be recovered in the

future. The global consumption growth rate (%) from year 2012 to 2013, of oil, gas and other

sources is shown in Figure 1-1[3].

Figure 1-1: Global energy source consumption growth % from 2012 to 2013 [3]

Figure 1-1 shows that renewables are growing annually at a higher rate than other fuels.

Renewables now account for 2.7% of global energy consumption, up from 0.8% a decade

ago[3].

0

2

4

6

8

10

12

14

16

18

oil Gas Coal Nuclear Hydel Renewables

% C

han

ge

Global energy source consumption growth rate from 2012 to 2013

24

According to BP’s Energy Outlook 2035, published in January 2014, world primary energy

demand is expected to increase by 41% from 2012 to 2035, with an annual average growth

rate of 1.5%. The major consumer is expected to be the residential sector, in the form of

electricity consumption. Global CO2 emissions from energy use are growing at 1.1% annually

and are expected to double from 1990 to 2035[4]. The projected global annual average

consumption growth rate (%) of different fuels from 2012-2035 is shown in Figure 1-2.

Figure 1-2 shows that, by 2035, the annual growth rate of renewables will be higher than all

other fuels.

Figure 1-2: Global energy source consumption growth from 2012-2035[4]

According to the International Energy Agency’s (IEA) World Energy Outlook 2013, world

energy demand will increase by 33% by 2035 with reference to year 2011. There will be an

increase in energy source consumption of oil by 13%, coal by 17%, natural gas by 48%,

nuclear by 66% and renewables by 77%. In the buildings sector, energy use will grow at an

average rate of 1% per year till 2035 and households will account for almost 60% of the

increase in energy demand. The increase will be in the form of electricity used for lighting,

space heating and cooling[5].

Energy-related CO2 emission rise will be 20% by 2035, and most increase in energy will be

in electricity demand. About half of the net increase in electricity will be generated by

renewables and the total share of renewables in electricity generation will be about 30% by

2035. The share of renewables in primary energy will be increased to 18% by 2035 under the

new policies scenario, as shown in Figure 1-3[5].

0

1

2

3

4

5

6

7

oil Gas Coal Nuclear Hydel Renewables

An

nu

al

av

erag

e g

ro

wth

(%

)

Global energy source consumption average growth rate projection 2012-2035

25

Figure 1-3: World primary energy demand projection [5]

Although this is a significant proportion, it will take many years for renewables to surpass the

proportion of fossil-based energy under current policy. The new policies scenario takes

account of policy commitments to reduce greenhouse gas emissions.

Solar energy is an emerging source of energy with worldwide potential. It is seen to have the

potential to contribute a major proportion of renewable energy sources in the future. Solar

energy is not a new idea and has been implemented effectively for many years. Solar energy

applications, like domestic hot water and space heating, have proven economic and useful

compared to conventional energy systems for these purposes [6]. Solar energy has many

benefits: it cannot be monopolised by a few countries, as with fossil fuels, for example. It has

no conversion processes producing emissions and can be easily integrated into buildings.

Solar energy could be the largest source of energy by 2050 [6].

1.4 Pakistan and Energy

The availability of energy in any country is linked with its economic and social strength.

Pakistan is an energy-deficient country, wherein the majority of the population has no

provision of basic energy facilities such as electricity and gas [2]. Pakistan is also facing

0

200

400

600

800

1000

1200

1400

1600

1800

2011 New Policies 2035 Current Policies 2035

Other Renewables Bioenegy Hydro Nuclear Gas Oil Coal

En

erg

y D

em

an

d (

TW

h)

World primary energy demand

26

serious threats due to global warming. Under the United Nations Environment Program

(UNEP) [2], Pakistan’s thousand kilometre-long coasts are classified as particularly

vulnerable to the effects of sea level rise.

According to BP’s Statistical Energy Review 2014, the primary energy consumption of

Pakistan during 2013 was 809.33 TWh, whereas for the UK it was 2360 TWh for the same

duration. Pakistan’s CO2 emission was 166.41Mt in 2013. The CO2 emission was 0.9321

tonnes per capita in 2010 [3]. The primary energy consumption per capita was 5.60 MWh in

2011, whereas, in developed countries like the UK, it was 34.60 MWh for the same period

[7]. Pakistan’s CO2 emission of electricity generation and transmission is 0.4733kg/kWh and

0.1419kg/kWh, respectively. Electricity consumed emissions are 0.01798g/kWh and

0.00316g/kWh for CH4 and N2O, respectively[8].

The primary energy consumption by source for year 2012-13 is shown in Figure 1-2. It is

clear that most of the energy consumed is from fossil fuels and the contribution of renewables

other than hydroelectric is negligible (less than 0.05% of total)[3]. Biomass consumption is

excluded, because reliable statistics of its use are not available.

Figure 1-4: Pakistan’s primary energy consumption by fuel 2013[3].

Figure 1-4 shows that most of the primary energy is shared by oil, coal, and natural gas, but

Pakistan has few reserves of fossil fuel. Pakistan had oil and natural gas reserves of 342

million barrels and 803 billion m3, respectively, as of the end of December 2013. These

reserves will last for 15 and 27 years respectively under the current production rate[9]. Oil,

coal, and gas are imported to meet requirements and, during the year 2013-14, 66% oil and

50%

32%

10%

6% 2%

Pakistan's primary energy consumption by fuel (2013)

GAS OIL HYDRO ELECTRIC COAL NUCLEAR

27

45% coal of total consumption were imported. The natural gas domestic production is 66% of

total consumption and different plans are proposed for the import of natural gas to meet

demand [10].

1.4.1 Electricity Generation History

At independence in 1947, Pakistan had 60MW of electricity generation capacity. Electricity

supply has fallen short of demand due to rapid industrialisation, population growth, and

urbanisation. The supply is often unable to meet demand due to poor governance, weak

institutions, incompatible power tariffs and poor load management and future planning. The

national grid system still supplies electricity to only 65% of the total population. The

electricity supply system is not reliable to maintain a consistent supply to the consumers[11].

The first major electricity shortage crisis was triggered in 1994, when the country was facing

a shortage of 2000 MW between peak demand and supply. Under the new power policy in

1994, an attractive incentive was given to electricity generation companies to overcome the

demand and supply gap. This policy was successful and the country’s generation was more

than demand till the end of 2006[12].

In 2005, the planning commission of Pakistan announced a plan vision for 2030 with key

targets for future energy of the country. Considering energy as a key factor for the

development and sustainability of the country, a detailed plan was made to make Pakistan

self-sufficient in power and reduce its dependence on a single source, especially imported

fossil fuels. This was the first policy to utilise renewable energy technologies (other than

hydroelectric power) in Pakistan to provide an energy mix in the national energy supply

system. It was estimated to add a minimum of 9,700 MW (5%) of total electricity generation

capacity from renewables (hydroelectric , wind and solar) by 2030 [13, 14].

The current power policy was announced in 2013, aiming to develop highly efficient power

generation, transmission, and distribution in a sustainable and economical manner. Special

consideration was given to renewable energy utilisation and wind and solar energy-based

electricity generation projects were initiated: 3432 MW of wind power projects are planned

to be completed by the end of 2016; 341MWP of solar energy projects are planned to be

completed by the end of 2015 and hydroelectric power projects of total capacity 3514 MW

are planned to be completed by the end of 2017 [15].

28

1.4.2 Current Status and Future Plans

According to BP’s Statistical Energy Review 2014, Pakistan’s total electricity generation was

96.20 TWh in 2006 and 93.20 TWh in 2013 [3]. More than 30% of the population do not

have access to electricity[5].

Due to poor implementation of energy policy, poor management and distribution losses,

Pakistan is in a situation where electricity demand has been greater than supply since

2007[12]. In Pakistan, electricity transmission and distribution losses are very high, ranging

from 9.5% to 34.3%. It is less in urban areas and higher, due to electricity theft and non-

payments of bills, in Sindh, Balochistan and FATA areas [11, 16].

The electricity generation growth rate was less than the growth rate of consumption in the last

decade. This demand and supply gap was about 1912 MW in 2007 and 6518MW in 2012,

equivalent to 29% of total demand in summer peak hours[17]. This gap resulted in power

supply cuts of about 8-10 hours and 12-16 hours per day in the winter and summer seasons,

respectively [5, 15, 18]. The electricity power generation by fuel type in Pakistan is shown in

Figure 1-5[19].

Figure 1-5: Electricity generation by fuel type 2015[19]

The details of electricity generation future projects are shown in Table 1-1.

Hydroelectric

33%

Fossil fuels

63%

Nuclear

3% Wind

1%

Electricity generation by fuel type (2015)

29

Table 1-1: Latest details of future electricity generation projects by fuel type [19]

Completion Year Fuel Capacity (MW)

2014-2018

Gas 3147

Oil 425

Solar 1000

Hydroelectric 4222

Coal 7560

Nuclear 600

Wind 650

Total/ Fossil fuels 17604/11132

Figure 1-5 shows that, currently, most of the electricity is generated by fossil fuels and the

contribution of renewables is considerably less, other than hydroelectric. Table 1-1 shows the

future electricity generation projects, including wind, solar and hydroelectric. By the year

2018, the contribution of renewables will be sizeable, but the major contribution will still be

by fossil fuels. According to the National Electric Power Regulatory Authority (NEPRA)

2014 report, under current policy and planning, the projected electricity peak demand and

supply in Pakistan to year 2019 is shown in Figure 1-6[20].

Figure 1-6: Electricity demand and supply 2012-19 [20]

0

5000

10000

15000

20000

25000

30000

2012 2013 2014 2015 2016 2017 2018 2019

Actual (2012-14) and projected (2015-19) electricity peak demand and supply

Supply (MW) Demand (MW)

30

Figure 1-6 shows that demand is continuing to exceed supply, despite supply being

approximately double from 2012 to 2019. The annual average growth rate of electricity

consumption is 14.5%, which has been more than supply since 2007 [20].267

1.5 Impact of the Energy Crisis

In Pakistan, the domestic sector is the major consumer of electricity and the current crisis has

a direct impact on domestic consumers. Electricity consumption share by different sectors in

the country for year 2013-14 is shown in Figure 1-7.

Figure 1-7: Electricity consumption by economic groups [16]

The supply of natural gas also falls in the winter season, causing an energy shortage for

domestic heating and cooking facilities. Natural gas supplies also fall short due to use in

Compressed Natural Gas (CNG) based motor vehicles, urea production, power generation,

and textile industry consumption. In the summer season, energy demand increases, mainly

due to air conditioning, household appliances (refrigeration and deep freezers) and tube wells

(irrigation water for rice crop) [11].

The deficiency of energy supply has affected not only people’s psychology and health, but it

has also severely damaged economic activities across the country[21]. High level stress and

Domestic, 46.9%

Commercial, 6.7%

Industrial, 28.9%

Agriculture, 11.4%

Public Lighting, 0.5%

Others, 5.5%

Electricity consumption by economic group 2013-14

31

sleep deprivation among people are also observed in the population, as their daily schedule is

heavily influenced by planned power outage. An increase in the crime rate is also associated

with planned and unplanned power outage. The other impacts include closure of healthcare

facilities and other services, which disrupts the everyday life of millions [21].

A study carried out in 2013 showed that the overall power outage cost to urban areas’

domestic consumers alone was estimated at GBP 1.30 billion per annum. The most affected

households belong to the income group from GBP 0-235 per month; those have no other

alternative supply system. This group constitutes 57% of the country total urban population.

The activities most disturbed by power outage, according to Pasha’s classification, are shown

in Figure 1-8[17].

Figure1-8: Activities most affected by power outage [17]

The most important activity affected is the heating /cooling used to maintain comfort inside

buildings. This is basic facility which is required most of the time inside buildings to live in.

The study has shown that a high percentage (42%) of households do not have alternate or

self-generation facilities. The annual average power outage cost per residential consumer is

£207 in terms of direct spoilage and adjustment costs. The average outage cost per kWh for a

residential consumer is £0.18. Residential customers’ average expenditure on electricity

jumped from 5% to 16% of total annual expenses after 2007, compromising basic necessities.

25%

18%

17%

15%

13%

8%

2% 2%

Activities most affected by power outage

Cooling/Heating

Studies (home work )of childern

Preparation for work/school

Regular household

work(cooking,cleaning)

water shortage

income generating activities (home

based)

Social activities

Entertainment, Leisure

32

The worst time of the year for power outage is summer and on Sundays, Mondays and

Fridays. About 29% of consumers showed willingness to pay above the current tariff, to

obtain a more reliable electricity supply[17].

Recent study shows that solar cooling systems in hot climates (Riyadh and Jakarta) can make

a significant contribution to reducing primary energy consumption. A solar energy-based

cooling system can reduce primary non-renewable energy consumption and CO2 emissions

by 30-79%, with a solar fraction of 22-80%. [22]. In European climates (Germany and

Spain), the use of solar thermal and solar electric systems can save 40-60% of primary energy

consumption [23].

Mateus and Oliviera [24] established that for single family house, solar integrated system

with 20-80% solar fraction is more economical and profit able than conventional ones for

south European locations.

According to European Solar Thermal Industry Federation (ESTIF) report on solar thermal

markets in Europe, trends, and market statistics 2014, single family houses are currently

largest market sector using thermal equipment. In European region the share of single family

houses is 40-46% and for multi-family houses its 27-29% [25].

1.6 Conclusion

Energy demand is increasing globally, including in Pakistan. Most of the energy resources

are based on fossil fuels. These fuels are damaging the environment and causing global

warming. To meet the energy demand without any or with minimum environmental damage

and, to address the issue of limited fossil fuel resources, policies have been recommended to

increase the share of renewable energy resources for clean and sustainable development.

Pakistan has also faced an energy crisis over the last few years and it is highly likely this

crisis will continue for years to come unless it is addressed properly. One of the major

reasons of the energy crisis is dependency on fossil fuels and its imports, as domestic

production is considerably less than requirements. In the past, no major project and plan has

been executed to reduce the dependency on fossil fuels by using alternative resources to deal

with the energy crisis.

In Pakistan the use of renewables for the primary energy and electricity generation is

negligible, except for hydroelectric power generation. To address the current energy crisis

33

and meet future energy demands, renewables will be a suitable option. The use of renewables

is clean and could provide a long-term solution to Pakistan’s energy issues, along meet the

global goal of decreasing CO2 emissions.

The energy statistics data showed that the use of solar energy is negligible in Pakistan’s

primary energy mix. There is a need for long-term and consistent plans and policies to meet

the country’s energy requirements, along with promotion of clean renewables, especially

solar energy. The potential of solar energy and its usage in Pakistan is described in detail in

Chapter 2.

The domestic sector is the major consumer of electricity and the electricity crisis has a direct

impact on domestic consumers. Electricity shortage has a major effect on comfort

(heating/cooling) in buildings. It is the worst in summer, when cooling is required due to the

high ambient temperature. There is need for a system which works to provide cooling and

heating during summer and winter. Solar energy-based systems are a reliable way of meeting

energy demand for lighting, cooling, and heating and help to reduce CO2 emission and

dependency on imported fuels[26] as the potential of solar energy is highest than any other

source of energy (Section 2.2).

1.7 Aims and Objective

The aim of this research is to investigate the potential of a solar powered cooling system and

the feasibility of achieving comfort in buildings in Pakistan.

The objectives of this work are to:

Investigate the energy scenario of Pakistan with respect to the electricity crisis, future

energy plans, and the potential and current status of renewable energy resources

application.

Carry out a detailed study of Pakistan’s solar energy potential, the annual and monthly

average solar insolation values for main cities and its current status of application.

Study climatic conditions, comfort temperatures, building energy consumption and

codes and possible techniques for improved efficiency in current building designs.

Carry out a literature review of photovoltaic systems, solar thermal systems and heat-

driven, low-energy cooling systems.

34

Design and analyse the building 3D model with current construction materials in

Pakistan and the simulation of a solar powered cooling system using suitable

simulation program.

Examine the simulation results, validation of input data, calculations, and results of

the solar cooling system with overall recommendations of solar cooling system

effectiveness to achieve building comfort in Pakistan.

1.8 Structure of the Thesis

The thesis has eight chapters and begins with an introduction, chapter 1, providing an

overview of world energy and a detailed analysis of current and future electricity demand and

generation in Pakistan. In addition, the generation based on different fuel types and effect of

current energy shortage crisis is also presented. Finally, aims and objectives of this research

are given.

Chapter 2 is about renewable energy resources in Pakistan. Renewables’ potential and the

application of solar energy in specific are presented. Institutional infrastructure for promotion

of renewables is also reviewed. Status and the application suitability of solar energy systems

in Pakistan are presented.

In chapter 3, climate and building energy use in Pakistan is investigated in detail. The mean

maximum temperature, thermal extremes, seasonal distribution, and comfort conditions are

examined. The current building energy code of Pakistan is analysed in terms of energy

efficiency. A United Nations project for energy efficiency improvement for existing houses

in Pakistan is also discussed and a conclusion is drawn from that project’s findings.

In chapter 4, solar energy cooling systems are reviewed. Efficiency, types, and the current

status of PV systems and IEA future targets are analysed. Solar thermal collector systems are

described in detail and different cooling systems suitable for solar thermal energy application

are described. A summary of application of solar cooling system in hot climates is also

presented. Status of solar cooling system in Pakistan is also reviewed.

In chapter 5, a detailed literature about experimental and simulation studies of solar cooling

system are presented. Solar energy systems and building energy simulation programs are

35

reviewed. Program suitable for a solar cooling system integrated with a building model is

studied in detail. A conclusion is drawn for the selection of a suitable simulation program.

Weather data types are reviewed and suitability of each data type with the different energy

simulation program is discussed. Weather data files available for Pakistan cities are also

analysed and data are selected to model typical weather in summer. A conclusion is drawn for

the selection of data to be used in the simulation.

Chapter 6 is about the building model, a description of solar cooling components and

operating parameters. Initial simulation results and modifications in building materials are

also presented. Mathematical calculations for operating parameters of the solar cooling

system are carried out and used to estimate simulation initial parameters.

In chapter 7, the final results of simulations, carried out for a typical building model with a

solar cooling system, are given. All the results are discussed in detail with results validation

and parametric sensitivity analysis. A conclusion is drawn regarding the feasibility aspect of

solar cooling in Pakistan.

Chapter 8 is the final chapter, results are summarised and conclusions, general discussions

with recommendations, are presented. The possible scope of further work, which will be

valuable to carry out, is expressed.

36

Chapter 2: Renewable Energy Resources in

Pakistan

2.1 Introduction

In chapter 1 it was shown that fossil fuels (oil, coal, and natural gas) are a major source for

primary energy consumption in Pakistan. This is causing environmental damage due to

emissions of carbon dioxide and other gases promoting global warming and disturbing

climatic conditions. Energy demand and prices are consistently rising and volatility has

caused a severe energy crisis in Pakistan. Many techniques and technologies are used to

convert renewable energy into a useable energy form for environmental and climate

protection. At present, the use of renewable technologies in Pakistan is small as compared to

other sources of energy. Only hydroelectric energy is being used, whose relative share is

decreasing in primary energy. There is a need to increase the use of renewable and

sustainable energy resources like solar, wind and hydroelectric energy resources in Pakistan.

Pakistan is enriched with renewable energy resources; an overview of the potential of

renewables for current and future use in Pakistan is described in the following sections.

Related to this research, solar energy will be discussed in detail.

2.2 Renewable Energy Potential

Pakistan has sufficient potential for wind, hydroelectric and solar energy to meet the

country’s present and future energy demands [2, 27]. At present the share of renewables is

very low (except in the case of hydroelectric energy) compared to the use of fossil fuel based

energy systems. The Pakistan government is making an effort to promote renewable energy

to increase the share of renewable energy in the country’s energy mix [2, 28].

For residential applications at a micro level in remote or undeveloped areas, the viable and

sustainable options are off-grid hydroelectric, solar and wind power systems. These options

are sufficient for electricity and cooking needs and would help to reduce de-forestation [29].

2.2.1 Wind Energy

In Pakistan the potential areas for wind energy are very limited as shown in Figure 2-1.

Pakistan is rich in wind energy only in the coastal areas of Sindh, Balochistan and some

Northern areas. One part of the coastal area in Sindh is only 60 km wide and 170 km long and

37

has the potential for about 60,000 MW of capacity. The annual average wind speed of this

corridor is from 5.9 to 7.1 m/s. Most of the remote villages in coastal area can have electricity

through micro wind turbines. The first wind energy project with 6 MW of capacity was

installed in 2009 and the installed capacity is now 106 MW [28, 30].

According to the Alternative Energy Development Board (AEDB), 5 wind farms with a total

power capacity of 255.4 MW are operational and 9 farms with 479 MW of capacity are under

construction. Fourteen projects 814 MW of capacity are in the process of being planned and

there are no details of the completion time for these projects [30].

Figure 2-1: Wind energy potential of Pakistan [27]

Wind energy associated environmental issues such as noise, effects on animals, deforestation

and soil erosion and visual impact cause concerns about utilising it. Variation in wind speed

and inconsistent power output are considered drawbacks for the promotion of wind energy

[31].

38

In Pakistan, the availability of wind energy is less during the 8 months from September to

April. Capacity from the available wind is significantly low, with an annual average of 0.20-

0.25 being quoted by AEDB for Pakistan [2].

The data presented above for wind energy shows that wind energy is limited to a small area

of the country. The annual available capacity is much less and its contribution to meet the

peak demand would not be dependable. Wind energy cannot be the main source of electricity

generation.

2.2.2 Hydroelectric Energy

Pakistan has identified a potential of about 60,000 MW of hydroelectric power, which can be

harvested. About 86% of this hydropower potential is still untapped. The total installed

capacity by the end of June 2014 was only 7097 MW. In 1960 the share of hydroelectric was

70% of the total electricity generation capacity whereas it was only 30% in 2014. The cost of

hydroelectric electricity generation is lower and it is the cheapest source of energy than any

other source in Pakistan[28]. The availability of hydroelectric energy depends on seasonal

variation. It also depends upon reservoir levels and in flow and out flow from reservoirs [28].

According to an economic survey of Pakistan 2013-14, ninety-seven micro hydroelectric

projects with a total capacity of 758 MW are being planned for different locations around the

country; feasibility studies and construction are being carried out. The micro hydropower

projects with a capacity of about 110 MW, have been operating in different parts of the

country [32].

Hydroelectric energy projects could be a source for future clean energy. High initial costs, the

length of time to build dams and environment damage linked with hydroelectric energy have

raised concerns about the implementation of such projects. The main hydroelectric energy

sites in Pakistan lie in earthquake danger zones and since 2005 earthquake investment risks

have discouraged national and international investors from initiating large capacity projects

for hydroelectric energy. The Indus water treaty with India has involved a lot of risks and

delays in project initiation. The hydro politics (rift among provinces) in Pakistan regarding

construction of larger hydroelectric power based dams is also a major hurdle in addition to

new capacities [33].

The hydroelectric energy potential of Pakistan is shown in Table 2-1.

39

Table 2-1: Hydroelectric energy potential in Pakistan [34]

Description

Project Under Implementation Projects with

Feasibility Study

Completed

(MW)

Projects

with Raw

Sites (MW)

Total

Resources

(MW) Public

Sector (MW)

Private Sector (MW)

Province

Level

Federal

Level

Total 23309 468 12742 4286 18751 59796

The data for hydroelectric energy shows that sufficient potential for clean and cheap energy

exists. The potential could provide sustainable energy to meet future demands. High initial

costs, political rifts, the Indus water treaty with India, security risks and environmental issues

are major concerns when considering harnessing hydroelectric energy potential.

2.2.3 Solar Energy

Solar energy is the most abundant renewable energy resource on earth and it is available for

use in its direct (solar radiation) and indirect (wind, biomass, hydro, ocean) forms. The

energy radiated by the sun is around 5% ultraviolet light, 43% visible light and 52% infra-red

light as shown in Figure 2-2 [35]. The solar radiation spectrum spans a wide range of

wavelengths, and resembles black body radiation at 5500K.

Figure 2-2: Solar energy spectrum distribution [35]

40

The black body radiation spectrum is shown by a black solid line in Figure 2-2.Most shorter

wavelength 0-400 (nm) ultraviolet radiation is absorbed in the atmosphere. Water vapour and

carbon dioxide absorbs longer wavelength energy while dust particles scatter more radiation,

dispersing some of it back into space. Clouds also reflect radiation into space [36]. The

energy balance of the earth, based on the incoming solar radiation, is explained in Figure 2-3.

Figure 2-3: Solar energy balance on earth [36]

Considering all these factors, around 52% of the incoming radiation energy, 700 Million

TWh annually, reaches the earth’s surface as solar radiation [37]. The global annual energy

consumption in 2014 is approximately 0.156 Million TWh which is only a small fraction

(0.02%) of the solar energy availability [38].

Sunlight reaches Earth’s surface directly and indirectly by numerous reflections and

deviations in atmosphere. On clear days, direct irradiance represents 80-90 % of the solar

energy reaching the earth’s surface whereas, on a cloudy or foggy day, the direct component

is zero. The indirect or diffused radiations are received on earth after its direction has been

changed by scattering the atmosphere. The direct component of solar irradiance is of the

41

greatest interest for high temperature solar thermal systems because it can be concentrated on

small areas using mirrors or lenses, whereas diffuse components cannot be. For concentrating

solar rays, clear sky is required, which is usually in semi-arid areas or regions with hot

climates [39, 40].

Solar energy systems can be used anywhere on the earth but some regions are better than

others. Pakistan is richer with solar energy than other renewable energy sources. The

available estimated solar energy potential of Pakistan is about 2900GW [the source is not

clear whether it is average or peak available capacity[41].

Solar energy can provide a power supply all over the country even in remote areas. Solar

energy available in Pakistan is sufficient for use all year in summer and winter seasons for

both cooling and heating with small and large scale applications. A comparison of solar and

wind energy prospects indicates that solar energy has an advantage over wind energy for a

number of reasons including potential, availability and acceptability by locals. Solar energy is

much more economical than wind energy for Pakistan [2].

Pakistan can take advantage of using solar energy technologies. This energy source has wide

and uniform distribution, throughout the country. Detailed solar energy maps of Pakistan and

the world are shown in Appendix A. A solar energy map of Pakistan is shown in Figure 2-4.

The mean global insolation on a horizontal surface in Pakistan is about 4-6 kWh/m2day with

enough sunshine hours (10-12) required for harnessing solar energy. The south western part,

from Baluchistan, is richer in solar energy with annual average global insolation of 5.1 - 6.0

kWh/m2/day with annual average daily sunshine hours of 8 - 10 hours. These are favourable

conditions for photovoltaic and solar thermal applications. The global insolation for district

cities in Pakistan is listed in Appendix A [42].

Sukhera et al.[43, 44] Raja and Twidell [45-47] and Muneer et al. [48] analysed measured

solar radiation data of five main cities of Pakistan. The annual average solar insolation is

19MJ/m2/day (5.26kWh/m

2/day). The annual average solar energy map of Pakistan is shown

in Figure 2-4.

42

Figure 2-4: Solar insolation over Pakistan [49]

Solar energy data shows that solar energy is abundant in Pakistan. The available energy is

suitable for applications in both solar PV and solar thermal systems. There is no political or

legal or climatic issue linked with solar energy usage. It can be used both for off grid or grid

connected energy supplies as well. It is suitable both for micro and large scale energy

generation.

2.3 Solar Energy Systems and Pakistan

The application of solar energy systems (photovoltaic and solar thermal systems) depends on

system capacity and available solar irradiation in that area. The relationship between solar

irradiation range and solar power system application selection is shown in Figures 2-5 and 2-

6. The areas where both technologies can be used overlap in a narrow range. Photovoltaic

operation covers a wide range from less than one watt to several megawatts. Photovoltaics

can be used as standalone as well as grid-connected systems [50].

43

Figure 2-5: PV and solar thermal power systems power range and global irradiation [50]

Solar thermal systems are used in high irradiation areas. There are areas in which one of the

two technologies should be preferred over the other for technical and economic reasons.

Figure 2-6: Regions of world appropriate for solar thermal power plants [51]

44

Considering Figures 2-5 and 2-6, it is clear that Pakistan lies in an area of high potential for

both photovoltaic and solar thermal technologies. The annual average global irradiation

varies from 1800 - 2200 kWh/m2

in most of the country. Research work in the field of PV and

solar thermal applications can help the country to overcome the current power crisis and use

clean energy sources. A list of application for solar energy technologies and the solar energy

systems used is shown in Table 2-2.

Table 2-2: Solar energy application and types of collector used [37]

Application System Collector

Solar Water Heating

Thermosyphon system Passive Flat Plate

Integrated collector storage Passive Compound Parabolic

Direct circulation Active Flat Plate, Compound Parabolic , Evacuated Tube

Indirect water heating systems Active Flat Plate, Compound Parabolic , Evacuated Tube

Air systems Active Flat Plate

Space Heating And Cooling

Space heating & service hot water Active Flat Plate, Compound Parabolic , Evacuated Tube

Air systems Active Flat Plate

Water systems Active Flat Plate, Compound Parabolic , Evacuated Tube

Heat pump systems Active Flat Plate, Compound Parabolic , Evacuated Tube

Absorption systems Active Flat Plate, Compound Parabolic , Evacuated Tube

Desiccant cooling Active Flat Plate, Compound Parabolic , Evacuated Tube

Adsorption units Active Flat Plate, Compound Parabolic , Evacuated Tube

Industrial Process Heat

Industrial air & water systems Active Flat Plate, Compound Parabolic , Evacuated Tube

Steam generation systems Active Parabolic Troughs, Linear Fresnel Reflector

Solar Desalination

Multi stage flash Active Flat Plate, Compound Parabolic , Evacuated Tube

Multiple effect boiling Active Flat Plate, Compound Parabolic , Evacuated Tube

Solar Thermal Power Systems

Parabolic trough collector systems Active Parabolic Troughs

Parabolic tower systems Active Solar Towers

Parabolic dish systems Active Parabolic Dish

Solar furnaces Active Solar Towers, Parabolic Dish

As Pakistan receives high levels of solar radiation, all these technologies can potentially be

applied to use solar energy.

45

2.4 Current Status of Solar Energy Application

Pakistan has a huge potential for photovoltaic and solar thermal applications, but there is no

solar thermal power plant or any specific industrial or commercial application of these

technologies. In recent years under the new power policy 2013, there has been a trend

towards the use of PV systems for domestic and commercial electricity generation. The first

PV system electricity generation project of 1000MWP was initiated in 2013 and the 1st phase

of 100MWP has been completed and is in operation. The details of solar energy applications

in Pakistan are summarised here.

2.4.1 Photovoltaics

Photovoltaic systems generate electricity directly. They are suitable for small and large

electricity generation projects. The areas of Baluchistan and Sindh (especially Thar Desert)

are most suitable for photovoltaic energy generation due to their high levels of solar

radiation[52]. Balochistan is the largest area province with the least population density of

about 22 people per square kilometre and most inhabitants live in rural areas as scattered

tribes. Most of these villages and areas are still to be electrified. The houses here require 100-

200 watts of power for lighting purposes. Transmission and distribution lines are difficult and

not economical for these low power scattered populations in hilly areas. Off-grid or local

power generation through solar PV systems is a possible solution as conventional fuels are

also costly to transport into these areas [52].

In the early 1980s, the government installed eighteen photovoltaic systems for the

electrification of remote village areas in different parts of the country[52]. Due to improper

operation and maintenance, these systems failed to produce the desired output. Similarly, the

public health department installed twenty solar water pumps in Northern areas and

Balochistan but these pumps did not perform well due to a lack of operation and maintenance

knowledge and trained, skilled operators. Currently solar photovoltaic energy technologies

are used in the country only for rural telephone exchanges, highways, and motorways’

emergency telephones. In late 2005, Solar Energy International and the National University

of Sciences and Technology (NUST) were jointly awarded a USAID project to provide solar

pumping systems for drinking water supplies in six villages in the Federally Administrated

Tribal Areas (FATA) in the Northwest of Pakistan [52].

46

In April 2012, the government allowed duty free import of all types of PV based system.

Both private and public sectors are financially contributing towards implementation and

promotion of clean energy photovoltaic systems in the country. Many companies are

involved in both trading and manufacturing photovoltaic based home appliances including

lamps, battery chargers, lights and torches [52].

According to the Pakistan economic survey 2013-14, about 65 MWP of electricity is

generated by PV systems. Approximately 793 MWP from Grid solar PV power plants are

under development and in different phases of planning. Under the Prime Minister’s directive

on solar electricity, a supply programme for 3,000 homes in 400 villages across the country

has been started [32].

Solar PV technology use in Pakistan is being promoted on a small and large scale. The first

stage for a 1000MWP solar PV electricity generation plant is operational and some other

projects are under construction. The use of solar PV is increasing but it is very small

compared to the potential that can be harnessed.

2.4.2 Solar Thermal

Solar thermal technology converts solar energy into heat energy and is used for many

applications in heat exchange processes. These technologies are simple, economical and

hazard free. The applications are cooking, heating, cooling and steam for electricity

generation for domestic, commercial, and industrial purposes. The use or application of solar

thermal energy technologies in the Pakistan is reviewed here.

2.4.2.1 Solar Cooker

A number of public and Non-Government Organisations (NGOs) are actively participating in

the promotion of solar cookers. Both box and concentrator type cookers are in use in the

Northern and North West Mountain areas of the country. The use of solar cookers can be

increased to save precious forest wood used for cooking. 67% of the total population is living

in rural areas and the estimated consumption of biomass energy is 27% of their total energy

consumption. The biomass is mainly firewood and crop residues [52].

47

2.4.2.2 Solar Water Heater

Solar water heating is very popular and a commonly used solar thermal application but in

Pakistan, its use is very limited. It is used only in the Northern areas during the winter season

due to a shortage of supply of natural gas and Liquefied Petroleum Gas (LPG). In the past

few years, due to the crisis in electricity throughout year and shortage in the natural gas

supply during the winter season, the use of solar water heaters is increasing throughout the

country for domestic hot water in the winter season [52].

According to the Pakistan economic survey 2013-14, approximately 16,715 units of solar

water heaters are in use in Northern areas, Balochistan, North Punjab and Khyber Pakhtun

Khwa (KPK) [32].

2.4.2.3 Solar Dryers

Solar energy can be effective in drying agricultural products especially fruits and grains. It

can produce a clean, high quality taste and quick drying and cost economic products. Solar

dryers are in use to dry fruits and preserve fruits for off-season use. Both public and NGOs

are actively participating in promoting solar dryers in all parts of the country [52] .

2.4.2.4 Solar Desalination

A large part of the population in the country, especially in Balochistan, Sindh, and south

Punjab has no clean drinkable water facilities. The available water is polluted or, saline due

to a high concentration of sodium chloride. This saline water is not suitable for drinking,

cooking, and washing. Solar energy can be effective and economical for desalination of this

polluted and saline water. Solar desalination technologies are very simple, low cost, and easy

to use for people with little technical training. The government has installed two plants with a

production capacity of 23 m3 / day, which converts sea water into sweet water in Gawadar

city. Some other projects are still under consideration for implementation in Sindh [52].

2.5 Institutional Infrastructure

In Pakistan most of the research and development work is carried out by public sector

organisations. Public sector organisations, which were and are involved in research regarding

solar energy applications, are described here.

48

2.5.1 Pakistan Council for Renewable Energy Technologies

The Pakistan Council for Renewable Energy Technologies (PCRET) was established in 2001

as a result of the merger of National Institute of Silicon Technology (NIST) and the Pakistan

Council for Appropriate Technologies (PCAT). The aim was to have more effective and

beneficial results for renewable technology research. The selected renewable sources were

micro hydropower generation, wind energy, biogas, photovoltaic and solar thermal

technologies. This organisation contributed to the application of different renewable

technologies. With regard to solar energy, the achievements were as follow [52]:

100 kW electricity for 500 houses, mosques, schools and 265 street/garden lights

through use of a 300 Solar PV system

Installation of 21 solar dryers with a total capacity of 5230 kg/day

Completed pilot scale production of solar cells

Testing laboratory for PV and solar thermal appliances

2.5.2 Alternative Energy Development Board (AEDB)

The Alternative Energy Development Board (AEDB) deals with alternative energy resources,

which include wind, micro wind, micro hydro, solar photovoltaic, solar thermal, bio-diesel,

biomass and energy from waste and fuel cells. AEDB, with the assistance of the World Bank,

will convert 100,000 agricultural water pumps for irrigation to run off solar energy within the

next five years. There are 1,100,000 water pumps across the country of which 250,000

electric pumps share, on average, 3000 MW peak electric loads during the day. The World

Bank has approved a pilot project under which initially 25 water pumps will run off solar

energy [52, 53]. According to the Economic survey of Pakistan 2013-14, about 1,429 units of

a solar water pumping system are working in the country both for agriculture and community

drinking water systems [32].

2.5.3 Educational Institutes

The educational institutes of Pakistan have made only a limited contribution to research,

development, and application of renewable energy technologies. So far there are no special

courses that have been started by universities, technical and vocational training institutes

regarding renewable energy technologies. For solar thermal and photovoltaic energy, the

activity in different institutes is minor. At present, the College of Electrical and Mechanical

Engineering (EME), the National University of Science and Technology (NUST) Rawalpindi

49

is carrying out research on solar thermal power generation and solar thermal devices for

heating purposes. The Nadirshaw Edulji Dinshaw (NED) University of Engineering and

Technology, Karachi, has research facilities for solar thermal and photovoltaic energy with

funding for research in this area. The University of Engineering and Technology (UET)

Lahore has established a centre for energy research and development both at Lahore and Kala

Shah Kaku (KSK) campus [54-58].

2.5.4 Pakistan Engineering Council (PEC)

Under the clean energy initiative an on grid solar power generation system with a capacity of

100 kWP will be installed under grant aid from the Government of Japan at the PEC head

office building at Islamabad. This will be the first of its kind in the country and will be an

example to prove an effective measure to overcome energy shortages. The government of

Pakistan under the Prime Minister’s Initiative for Solar Power (PMISP) has approved a grant

of GBP 0.50 Million for PEC. Under this project, PEC is installing 0.50 to 5.0 kWP stand-

alone solar power systems at various engineering universities, commercial areas, and

religious places [53].

2.6 Doctoral Research on Solar Energy Potential in Pakistan

In 1992, Raja [45] completed doctoral research on “Assessment of solar radiation in

Pakistan”. Mean monthly maps of distribution of daily global, diffuse, and direct solar

insolation for Pakistan were presented, using measured data for five cities and sunshine hours

data of thirty seven other stations. The solar insolation measured data was from 1957-

81(except Quetta 1957-87) and the sunshine hour’s duration was from 13-37 years until 1987.

The global solar insolation was calculated from sunshine duration using Angstrom type

insolation-sunshine relation. It was found that the annual mean daily global solar insolation in

the major parts of the country from 16.0 to 21.5 MJ/m2/day (4.4 to 6.0 kWh/m

2/day) with

mean of 19.0 MJ/m2/day (5.26 kWh/m

2/day). It was also reported that all five station have

mean daily insolation more than 10.0 MJ/m2/day (2.77 kWh/m

2/day) with at 85% probability.

Raja also presented data for distribution of monthly mean daily diffuse and direct (beam)

solar insolation for Pakistan. It was reported that measured data for diffused insolation was

available for one city (Quetta) of three year duration (1960-62) and for other cities it was

predicted using empirical relationships. The direct insolation for 40 stations was computed by

the difference of global and diffuse insolation.

50

The main limitation of Raja’s work is that the country’s solar energy potential is estimated on

the basis of five stations measured data. For solar energy applications, long term solar data

from high resolution satellite data or measured data for more cities would provide confidence

for design and operation.

In 2012, Shah [59] completed doctoral research on the “Analysis of solar energy production,

utilisation, and management for facilitating sustainable development in and around the

deserts of Pakistan.” It was established that available solar energy potential utilisation could

provide socioeconomic development and benefits (fresh water, electricity) to the population

in desert areas of Pakistan. The daily solar energy potential of 90,000 km2 of desert would be,

on average, about 30-65GW/m2 [59-61] of electricity. It was concluded that an area of 60

km2 would be sufficient to meet energy demand for the daily needs for water and electricity

for 500 persons village [62].

It was concluded that 0.70 kg per person per day of CO2 emissions could be avoided if a solar

power generation process were used instead of fossil fuels [59]. It has also been found that

solar assisted water desalination for coastal areas of Pakistan is feasible and potential

utilisation could contribute to the development of a 1,046 km long coastal area with a

population of more than 10 million [63].

Pakistan’s solar energy potential is sufficient for solar PV and thermal application as shown

in Figure 2-6 and Appendix B. There is a need to improve the data on solar energy

availability, principally by collecting data for more locations. Doctoral and academic research

into solar cooling systems in Pakistan and India will be described in Section 4.6.1

2.7 Conclusion

Renewables are the source of clean and sustainable energy resources. Use of renewables can

help to meet the global goals for control of carbon emissions and global warming. Pakistan

has sufficient potential in renewables which could provide clean and sustainable energy to

meet the current and future energy demands. In the past and at the moment only hydroelectric

energy and biomass are extensively used; wind and solar energy need to be promoted. As

presented in Section 1.4, in Pakistan the amount of renewables for primary energy

consumption is very low compared to the potential.

51

Solar energy is the largest available renewable source of energy. The use of solar energy is

much less than its availability. It could provide clean energy amounting to many times more

than world energy consumption (0.154 Million TWh for year 2013) for years if it could

capture only 1% of the total available 700 Million TWh.

Solar energy has several advantages over wind, biomass, and hydroelectric energy.

Environmental and political problems are linked with the promotion of these other renewable

technologies in Pakistan. The solar energy potential covers almost all of the country and the

technology can be used on a large scale, which would be economically viable and with the

same standards of service and maintenance.

Pakistan lies in a location with annual solar insolation of 1800-2200kWh/m2. This insolation

is suitable for micro to mega solar energy generation by all types of solar PV and solar

thermal systems. Pakistan is suitable for application of all types of PV and solar thermal

technologies for heating, cooling, power generation and industrial applications. Public and

private sector partnership along with special incentives can promote the application of solar

energy technologies. The application of solar energy systems can help in the improvement of

social and economic values in remote areas of Sindh, Punjab, and Balochistan.

Solar energy is widely available in all areas of Pakistan. It is the only undisputed and short

and long term solution to the current crisis which is a source of green and clean energy. The

use of solar at a micro scale at the domestic level could help to meet demand for daily energy

consumption both for lighting and hot water.

Institutional level infrastructure (technical training) is available in the country which could

contribute a lot to the promotion of solar energy based domestic appliances. The institutional

contribution is much less compared to its potential. The benefit of solar energy use would be

apparent throughout the country’s population both in urban and rural areas. It would help to

develop remote areas in all provinces and facilitate the extremely dense populated cities.

Solar energy can be the best alternative to both electricity and natural gas shortages for

domestic use both for heating and cooling applications (Section 1.5).

52

Chapter 3: Pakistan’s Climate and Buildings’

Energy

3.1 Introduction

In chapter 1, world energy data shows that the predicted annual average growth in energy

consumption in the buildings sector will be 1% till 2035 and major consumption will be for

lighting and space cooling due to increases in population and urbanisation. Pakistan energy

data shows that 54% of total electricity is being consumed by the domestic and commercial

sectors. The climatic conditions in Pakistan are hot and sunny for most of the year. The major

energy consumption in buildings is for cooling systems in summer. In this chapter geography,

population, climatic conditions, comfort temperature, thermal extremes, and building energy

in Pakistan will be described in detail. All these parameters are important in comfort, cooling

system design and cooling demand in the future.

3.2 Geography of Pakistan

Pakistan lies in South Asia between latitude 24◦ N to 38

◦ N and longitude 61

◦ E to 78

◦ E and

the total area is 796,096 km2. The neighbouring countries are China in the north, India in the

east, Afghanistan and Iran in the west and the Arabian Sea to the south. It has a varied

landscape with flat Indus and Punjab rich plains, deserts and the Plateau of Balochistan in the

west and mountains in the north and North West as shown in Figure 3-1.The economy is

agriculture based, and the total arable land in the country is about 28% of the total area.

About 80% of the cultivated land is irrigated through the world’s largest irrigation system

linked with five main rivers [64].

53

Figure 3-1: Geography of Pakistan [65]

Pakistan is divided into seven main administrative areas, which are Punjab, Sindh,

Balochistan, Khyber Pakhtun Khwa (KPK, formally North West Frontier Province) Federally

Administrated Tribal Areas (FATA), Gilgit Baltistan, and Jammu & Kashmir. These

administrative areas are shown in Figure 3-2.

Figure 3-2: Administrative areas of Pakistan [66]

54

The area and population distribution for each administrative unit is shown in Figures 3-3 and

3-4 respectively.

Figure 3-3: Area distribution of Pakistan [67]

Figure 3-4: Population distribution of Pakistan [67]

The above Figures 3-3 and 3-4 show that about 76% of the total population lives in the

Punjab and Sindh provinces, although these provinces constitute only 39% of the total land

area. Balochistan and KPK cover 49% of the area of the country but the population share is

19%. The other administrative areas have less than 12% of the land area and 5% of the total

population.

23%

16%

9%

40%

1%

3%

8%

Pakistan's area distribution

Punjab

Sindh

Khyber Pakhtunkhwa

Balochistan

Azad Kashmir

FATA

Gilgit Baltistan

53% 23%

14%

5% 2% 2% 1% Pakistan's population distribution (2010)

Punjab

Sindh

Khyber Pakhtunkhwa

Balochistan

Azad Kashmir

FATA

Gilgit Baltistan

55

3.2.1 Population

Pakistan is one of the most populated countries in the world. Since 2003 it has been ranked as

number 6 most populated country in the world [5]. The population density is increasing

continuously. The population density of the provinces and country in 2010 is shown in Figure

3-5.

Figure 3-5: Population density in 2010 [68]

According to the Pakistan Bureau of Statistics, the country population has reached more than

184 million. It is estimated that Pakistan’s population will be about 260.06 and 375.25

million by 2030 and 2050 respectively [69].

In 2013, about 33% of the total population was living in urban areas and this number was

expected to rise to 50% by 2025. Presently cities suffer from a housing deficit of about 3

million units and 50% of the current urban population lives in slums. There will be an

increase in demand for houses and electricity for lighting and cooling systems [70].

3.3 Climate of Pakistan

Climate plays an important role in building design, energy demand, heating and cooling

system requirements, and operational hours for these systems. There are different climatic

conditions in the different parts of the country. Ambient temperature and relative humidity

are important for cooling load calculation and they are described here as climatic conditions

396.1

252.5

283.5

22

341.9

131

15.62

221

0

50

100

150

200

250

300

350

400

450

Punjab Sindh Khyber

Pakhtunkhwa

Balochistan Azad Kashmir FATA Gilgit Baltistan Pakistan

Pakistan population density per km2

56

[71]. The climate of Pakistan is generally arid with hot summers and cool or cold winters

with wide variations between extremes of temperature at given locations [72].

3.3.1 Temperature and Humidity

On the basis of temperature experienced, the country is divided into three main seasons:

summer, monsoon, and winter. The summer season lasts from April to June and monsoon

from mid-June to mid-September. In southern and eastern areas the temperature is highest

and decreases towards the north and west, and reaches a minimum in the northern and

western parts. In the summer season the average temperature in the north is below 15°C

whereas in the south it is more than 35°C. About 80% of the population of the country lives

in climatic condition with hot summer seasons and requires cooling systems for comfort [73].

The mean minimum and maximum temperatures for all major district cities of Pakistan are

shown in Appendix B [42]. The annual mean daily temperature of the country from years

1971 to 2000 is shown in Figure 3-6.

Figure 3-6: Pakistan annual mean daily temperature [74]

57

The annual average relative humidity for most of the areas of the Pakistan is from 40% to

70%. It is higher than 70% at the Makran coast and lower than 40% in south-eastern

Balochistan, and in the extreme north [73].The annual average relative humidity for district

cities in Pakistan is shown in Appendix B [42].

3.4 Heat Index and Pakistan

Most of the areas in Pakistan have hot weather conditions in the summer. Continuous high

temperatures and high relative humidity for long periods become a significant hazard and

pose a health risk. Different climate models’ projections show that global air temperature will

increase in the future due to long wave’s radiative effects of increasing greenhouse gases,

especially CO2 emissions (These gases absorbs and re-emit the long wave infrared radiation

emitted by earth thus increasing the atmospheric temperature). The heat-related damage and

casualties are likely to increase due to global warming effects and increasing heat waves

during summer seasons. Cooling systems are required to create comfort inside buildings [75,

76].

The heat index [75] is a measure of stress caused to humans by increases in humidity and

temperature. As the moisture increases, the ability of the human body to release heat through

evaporation decreases which creates stress and discomfort, heat stroke or even death to

humans. The heat index is a simplified relationship between ambient temperature and relative

humidity versus apparent temperature.

The Heat Index (HI) Equation (1) is: [77]

HI = - 42.379 + 2.04901523T + 10.14333127R - 0.22475541TR - 6.83783x10-3

T2 - 5.481717×10

-2R

2

+ 1.22874 × 10-3

T2R + 8.5282 × 10

-4TR

2 - 1.99x10

-6T

2R

2 (1)

Where

T= Ambient dry bulb temperature (°F)

R= Relative Humidity (%)

The above Equation (1) is applicable when air temperature and humidity are above 26°C and

39% respectively. A relation of different heat index temperature ranges and their effects on

humans is shown in Table 3-1.

58

Table 3-1: Heat Index and its effects [75, 78]

Heat Index Health effects

27 - 32 °C Fatigue possible with prolonged exposure and/or physical activity.

32 - 41 °C Heat cramp and heat exhaustion possible with prolonged exposure and/or physical activity.

41 - 54 °C Heat cramp or heat exhaustion likely & heat stroke possible with prolonged exposure and/or

physical activity.

> 54 °C Heatstroke highly likely with continuous exposure.

In Pakistan the heat index and its possible effects start in summer from May to September.

The heat index range from 27-32°C is tolerable for the people of Pakistan. The normal heat

index for summer seasons based on recorded real time data of mean monthly maximum

temperatures and relative humidity from 1971-2000 in Pakistan is shown in Figure 3-7.

Figure 3-7: Pakistan normal mean heat index distribution [75]

Figure 3-7 shows that most of the areas of the eastern side (Punjab and Sindh) and south

eastern Balochistan are in danger and the extreme danger zones of the heat index, which

poses serious threats to health. Buildings in these areas require cooling system for health as

well as comfort.

The analysis of 1961-2007 recorded weather data shows that there is an increase in

temperature and humidity causing a rise in the heat index and for the summer season the heat

index is increased by 3°C. For this period in the country, on average the increase in humidity

59

is 6.2% and the increase in maximum temperature is 0.25°C. The summer season has been

prolonged while winters have become shorter in Pakistan [75].

3.5 Thermal Extremes in Pakistan

Heat waves (HW) are the by-product of climate extremes. These are now more frequent and

intense during summer in most parts of the world. Recent studies[79-83] on heat waves

reported a risk of more intense and frequent heat waves in the near future. A heat wave is

defined as very high temperatures over a sustained number of days [84]. Heat wave-related

causalities are increasing and in 2003 more than 70,000 were recorded in Europe [85, 86].

Heat waves are the most prominent cause of weather-related human mortality in the U.S. and

Europe [87]. Asia is not far behind in terms of the impact of prolonged spells of heat waves.

The hottest summer in China for the last fifty years was recorded in Shanghai in 2003 when

the mortality rate was at its maximum due to cardiovascular and respiratory disorders [88].

Heat waves generally develop during pre-summer (March/April) and pre-monsoon

(May/June) in Pakistan. Heat wave conditions have been frequent during pre-summer after

the 1990’s due to climate change [84]. The country weather data from 1960-2007 shows there

has been an increase of 0.47°C in the annual mean daily temperature with an average of

0.099°C per decade [64]. The frequency of continuous hot days and hot nights has increased

annually since 1960, and on average there has been an increase of 20 days of continuous hot

days from 1960 to 2003 (hot day or hot night is defined by temperatures exceeding 10% of

average day or night temperatures in the given climate for that region or season). Similarly,

the frequency of hot nights per year has increased by 23 nights for the same period. The

frequency of cold days and nights has decreased significantly since 1960 (cold days or cold

nights are defined as those with temperatures 10% below the average day or night

temperatures for the given climate for that region or season). On average the number of cold

days has decreased by 9.7 days and the number of cold nights by 13 from 1960 to 2003 [71].

Heat waves with temperatures between 40°C and 45°C and durations of 5 and 7 consecutive

days have been increasing in all regions of Pakistan from 1961 to 2009. There is an increase

in the spell of 10 consecutive days at temperatures of more than 40°C in the Punjab, Sindh,

and Balochistan regions. The heat wave periods with temperatures of more than 45°C for 10

consecutive days has increased in the Punjab, Sindh, Balochistan, and Khyber Pakhtun Khwa.

The moderate and severe thermal extremes for temperatures between 40°C and 45°C have

60

increased more for 5 and 7 days than for 10 consecutive days. The area of moderate and

severe heat wave frequency in South Asia is shown in Figure 3-8 [84].

Figure 3-8: Areas of moderate and severe heat wave frequency in South Asia [84]

It is expected that continuous increases in temperatures may make heat waves more frequent

and intense than they are at present. Severe damage to people’s lives is expected, unless

adaptation measures are taken to mitigate heat-related discomfort [84].

3.6 Comfort Temperature

3.6.1 Standard Comfort Temperature

Comfort temperature, is a temperature at which people feel on average neither cool nor warm.

It can vary with varying ambient or climatic conditions. The main factors which influence

thermal comfort and determine heat gain and loss are metabolic rate, clothing insulation, air

temperature, mean radiant temperature, air speed, and relative humidity. The American

Society of Heating, Refrigeration and Air-conditioning Engineers (ASHRAE) standard -55

defines the acceptable standard comfort temperatures and is shown in Figure 3-9 [89]. Figure

3-9 shows the ASRAE standard comfort temperature is 21.2 – 26.7°C and relative humidity

is 30-60 %.

61

Figure 3-9: ASHRAE standard comfort temperature zone [89]

Operative temperature (To), is uniform temperature of an imaginary black enclosure in which

occupants would exchange the same amount of heat by radiation plus convection as in the

actual non-uniform environment. The empirical relation is expressed as Equation 2 [90, 91].

To= (Ta + Tr ) / 2 (2)

Where,

Ta= Air temperature of surroundings (°C)

Tr = Mean Radiant Temperature (°C)

The mean radiant temperature (Tr) is the uniform surface temperature of an imaginary black

enclose in which an occupant would exchange the same amount of radiant heat as in the

actual non-uniform space. The empirical relationship is expressed as Equation 3 [90].

Tr = Tg + 2.42 × va (Tg-Ta) (3)

Where,

Tg = Globe temperature (°C)

va = Air velocity (m/s)

62

Globe temperature (Tg) is a value, which is measured directly by globe thermometer at

thermal equilibrium with the environment, when heat gain by radiation is equal to heat loss

by convection [91].

3.6.1.1 ISO 7730

International standard ISO 7730 is used to predict the thermal sensation and degree of

discomfort of peoples exposed to a moderate thermal environment. It is also used to specify

acceptable thermal comfort conditions. It is based on two techniques: Predicted Mean Vote

(PMV) and Predicted Percentage of Dissatisfied (PPD) [92, 93].

PMV is an environmental index commonly used to specify thermal comfort conditions in

moderate thermal environments. It predicts the mean value of votes of large groups of people

on the ISO thermal sensation seven point scale from +3 to -3 from hot to cold respectively.

The comfort zone is specified by PMV between -0.50 to +0.50 [92, 94].

The PPD index establishes a quantitative prediction of the number of thermally dissatisfied

persons. It predicts the percentage of a large group of peoples likely to feel too hot or too cold

in a given environment as in the PMV scale. The PMV value is used to calculate PPD in

terms of percentage of dissatisfaction [92, 94].

3.6.1.2 Limitations of ISO 7730

Laboratory studies have often supported the validity of ISO 7730 whereas field studies have

not. The standard is also criticised for a lack of theoretical validity [93]. The ISO 7730

standard does not adequately describe comfort conditions for tropical and hot climates. Air

temperatures above 30°C and air velocities of more than 1m/s are common in buildings in

tropical countries. Many field studies have found that occupants can be comfortable at

temperatures over 30°C if fans are in use, even though the PMV is over 2. PMV over

estimates discomfort in hot conditions and under estimates it in cold conditions [95, 96].

Francis and Edward investigated and found errors incurred through the use of ISO 7730. It is

found that for annexe E, linear interpolation can generate small errors. A correction factor

was proposed as, without correction, relative humidity can lead to errors of up to 20% of

comfort span at 30% relative humidity for low activity levels [94].

3.6.2 Adaptive Thermal Comfort

People have a natural tendency to adapt to changing conditions in their environment. This

tendency is expressed in the adaptive thermal comfort approach. The adaptive thermal

63

comfort approach is based on findings of surveys on thermal comfort conducted in the field.

Analysis of international field studies shows that peoples adapt to temperatures they

experience and are comfortable over a greater range of temperatures other than predictions of

ISO 7730 and ASHRAE standard temperatures. For the air-conditioned building the comfort

temperature is different from that in naturally ventilated buildings [97, 98]. The adaptive

approach is used to estimate the indoor temperature at which building occupants are more

likely feel comfortable. Most occupants are comfortable with +/-2°C of the comfort

temperature [32].

Acceptable operative temperature ranges for naturally conditioned spaces according to

ASHRAE 55rev-2003, for different climatic areas is shown in Figure 3-10 [99].

Figure 3-10 Acceptable temperature ranges for naturally conditioned spaces ASHRAE 55 rev. 2003 [99]

Figure 3-10 shows that for naturally conditioned spaces (no mechanical cooling) people are

adapted to higher temperatures than the ASHRAE standard comfort zone. For New Delhi the

range is between 26°C to 30°C, when the mean monthly outdoor temperature is between

33°C and 35°C. These conditions are also applicable to Lahore as the climatic conditions of

New Delhi and Lahore are similar. For a period of 30 years, recorded data for mean monthly

temperature for both Lahore and New Delhi is shown in Figure 3-11. The mean monthly

64

temperature in Lahore is slightly lower than in Delhi from February to June. The acceptable

comfortable temperature for Lahore will be in the same range as for New Delhi.

Figure 3-11: 30 years average monthly mean daily temperatures [100]

In Pakistan two thermal comfort surveys were conducted to find out adaptive comfortable

temperatures in Pakistan by Nicol et al. [97, 101, 102]. One was longitudinal, conducted in

summer and winter, and the other was transverse conducted each month over the year. The

results were close and it was established that there is a relationship between outdoor

conditions and indoor comfort in line with adaptive thermal comfort. For comfortable

temperature observations in Pakistan, the country is divided into five climatic zones, which

are shown in Table 3-2 [97].

Table 3-2: Climate zones of Pakistan for comfortable temperatures [97]

Climate zone Representative

city

Monthly mean outdoor temperature range (°C)

Zone I: Tropical Coastland Karachi 18.1-31.4

Zone II: Subtropical Continental, Lowland arid Multan, Lahore 12.8-35.5

Zone III: Subtropical Continental, Highland Semiarid / Sub-humid Quetta 4.9-27.8

Zone IV: Subtropical Continental, Lowlands / Sub-humid Islamabad, Peshawar 10.1-31.2

Zone V:Subtropical Continental, Highland humid Gilgit, Saidu Sharif 8.2-28.7

Most of the population (more than 60%) in Pakistan lives in climatic zone II, which needs

cooling systems in the summer for comfort inside buildings.

0

5

10

15

20

25

30

35

40

January February March April May June July August September October November December

Tem

peratu

re (

ᵒC)

Lahore vs New Delhi nean daily temperature

Lahore

New Delhi

65

Nicol used Equation (4) to calculate design indoor temperature (Td) or set point for air-

conditioned buildings in Pakistan, from records of monthly mean outdoor long term

temperatures TOLT [97, 103].

Td = 18.5 + 0.36 ToLT (4)

The calculated indoor or set point temperature (Td) for selected cities in Pakistan is shown in

Table 3-3.

Table 3-3: Designed indoor (Td) temperature for selected cities [97, 101]

Month City

Gilgit Islamabad Karachi Lahore Multan Peshawar Quetta Saidu Sharif

January 19.7 22.1 25.0 23.1 23.1 22.5 20.3 21.5

February 20.7 22.9 25.8 24.0 24.0 23.1 20.6 21.9

March 22.7 24.6 27.3 25.9 26.1 24.8 22.4 23.4

April 24.5 26.6 28.7 28.1 28.4 26.9 24.6 25.5

May 25.7 28.4 29.5 29.7 30.2 28.8 26.2 27.4

June 27.4 29.7 29.8 30.7 31.3 30.4 27.7 28.8

July 28.4 29.2 29.4 29.8 30.7 30.1 28.5 28.8

August 28.1 28.8 28.9 29.6 30.4 29.6 28.2 28.3

September 26.5 28.2 28.9 29.2 29.7 28.9 26.3 27.4

October 24.2 26.6 28.5 27.7 28.0 27.0 23.9 25.8

November 21.8 24.4 27.1 25.5 25.6 24.8 22.1 23.7

December 20.0 22.7 25.5 23.6 23.6 23.0 20.5 22.1

Annual average 24.1 26.20 27.9 27.2 27.6 26.9 24.3 25.4

The annual average adopted indoor set point temperature is higher than the ASHRAE

standard of 26ºC in summer and 21ºC in winter. This data will help to use passive or low

energy solutions and also reduce cooling load when designing cooling systems.

3.7 Building Energy in Pakistan

According to the IEA, during 2011, global final energy consumption in all buildings is

33,610 TWh and expected increase to up to 42,915 TWh by 2035. Currently buildings share

29% of total electricity consumption and this figure will increase to 38% in 2035. Currently

space heating and cooling contribute about 60% of total energy consumption in buildings.

The IEA suggests the possibility of saving 3% of total energy consumption by improving

energy efficiency in buildings and making a major contribution by reduction in electricity

consumption [5].

66

In Section 1.5, it is shown that in Pakistan about 54% of total electricity is consumed in

domestic and commercial buildings. Pakistan has increasing demand for air conditioning

systems due to the rising heat index and thermal extremes as discussed in Sections 3.4 and

3.5. Energy demand in buildings is increasing by 15% per annum; high energy use also leads

to more carbon emissions due to combustion of fossil fuels to meet the energy demands

[104]. The ongoing energy crisis has added difficulties in maintaining comfort inside the

buildings as discussed in Section 1.5.

3.7.1 Energy Efficient Buildings:

The present buildings in Pakistan have the following problems [105]:

Poor comfort in peak summer and winter seasons

High cooling and heating loads

Poor energy efficiency

The current buildings in Pakistan have the potential for increasing energy efficiency and

about 50% of energy demand can be saved through comprehensive measures [105]. Energy

can be saved in existing buildings by insulation of the building envelope (walls, roof and

ground floor), glazing of windows, installation of energy efficient heating and cooling

systems, annual service of appliances, installation of temperature controllers and thermostats.

Effective use of day light in building has multiple benefits including occupants feeling

comfortable, more productivity at work, improved aesthetics and energy saving compared to

inefficient buildings [106].

Turkey has successfully implemented energy efficiency policy for buildings and achieved

electricity reduction by about 25-30% in buildings. The policy was prepared and

implemented in 2004, by the Ministry of Energy and Natural Resources (MENR) with the

help of internal donors [107].

In India, the Bureau of Energy Efficiency (BEE) was established in 2001 and has

implemented an Energy Conservation Building Code (ECBC) in 2007 and aims to achieve

energy savings of 25-30% in different buildings [5, 108].

The estimated potential of energy savings in Pakistan’s buildings is described in Section

3.7.3. This estimated potential is higher than actually achieved by Turkish building energy

policy implementation as there is no building energy code in practice in general.

67

3.7.2 Building Energy Code of Pakistan

In Pakistan for energy efficiency in buildings, the Ministry of Environment has updated the

1986 Building Energy Code of Pakistan (BECP) in 2008 with the support of the National

Engineering Services Pakistan (NESPAK) under contract with the National Energy

Conservation Centre (ENERCON). This code was implemented by the Pakistan Engineering

Council (PEC) in February 2014 for buildings with a total connected energy load of 100kW

or greater, 900m2 of conditioned space or greater or unconditioned space of 1200m

2 or

greater. The purpose of this code is to provide minimum requirements for energy efficient

design and construction of buildings in Pakistan [109]. It is mainly focussed on:

a) New buildings and their systems

b) New systems and equipment in existing buildings

This code is not applicable to

a) Buildings using no electricity or fossil fuels

b) Equipment and portions of building systems that use energy primarily for

manufacturing industry and processes

A critical analysis of this energy code, bearing in mind energy efficiency and cooling

systems, in the context of solar cooling is carried out and presented here.

Section IV of the code, describes mandatory requirements for building energy usage but does

not provide guidance on improving energy efficiency in existing buildings and systems.

There is no description for building materials application for energy efficiency or passive

heating, cooling and natural ventilation systems, although the majority of the population lives

in rural areas having no mechanical systems for building comfort [110].

Section V of the code describes heating, ventilating and air conditioning requirements.

Mandatory requirements for natural and mechanical ventilation, equipment minimum

efficiencies, temperature and humidity controls are described. An air leakage limit is

mentioned but no procedure is mentioned for how it varies in winter and summer with

comfortable conditions. For natural ventilation, it is not mentioned which section of the

national building code of Pakistan and ASHRAE should be followed. Mechanical cooling

systems of more than 28 kW must have automatic control systems, whereas most of the

domestic and commercial systems are less than this in capacity. The set point for summer and

winter should not be less than 25ºC or more than 21ºC respectively. Temperature and

humidity ranges for restaurants, office building, museums and communication centres and

68

airport terminals are prescribed, but for schools, domestic buildings, hospitals, mosques and

other public services buildings they are not described [110].

Section XIV of the code describes the climate zones of Pakistan and temperature ranges

measured in these climate regions. The climate zone of Pakistan in the building energy code

map is not in accordance with tabulated zones in the code. The correct climate zone map in

accordance with Table 3-2 climatic zones of Pakistan is shown in Figure 3-12.

Figure 3-12: Climate zone map of Pakistan [110]

The building energy code does not cover all types of buildings and equipment efficiency

standards but still has the potential to reduce building energy consumption, which is

discussed in the next section.

3.7.3 Benefits of Introducing Building Energy Code in Pakistan

ENERCON presented a study on the benefits of implementing the energy code in buildings.

It is estimated that implementation of the code can save about 29% on overall energy use in

buildings. Using an energy code standard for building envelopes of U-value for walls and

windows can save 56% and 38% of energy usage respectively. It is also estimated that with

69

changes in window to wall ratios from 0.38 to 0.33, about 200-300kWh of energy can be

saved on average [111].

Currently air conditioning systems represent 25% of total electricity consumption in

buildings. By implementing the energy code about 18% of the total air conditioning systems’

electricity consumption could be saved. The energy code recommends that using a summer

temperature set point of not less than 25ºC can save 35%, using solar cooling can save 25%

and using occupancy sensors can save 15% of total energy consumption in buildings [111].

Some other areas for potential savings are shown in Table 3-4.

Table 3-4: Potential energy conservation areas [105]

Conservation Areas Saving Potential (%)

Overall lighting 29

High efficiency lighting (LEDs) 72

Fluorescent tube ballasts 83

Lamp fixtures 50

Printers 19

Heaters 17

Copiers 10

Fans 5

Computers 2

The overall potential for 29% of savings is in line with the Turkish energy efficiency policy,

which saved 25-30% on energy use in buildings. This saving potential is just an estimate as

no experimental evidence has been described by ENERCON.

3.8 Case Study of Energy Efficiency Improvement in Existing Houses in

Pakistan

In 2010, UN-HABITAT (United Nation Settlement Programme) in partnership with the

Ministry of Environment, National Energy Conservation Centre (ENERCON) and Capital

Development Authority (CDA), demonstrated and tested measures to improve the thermal

performance of housing with Reinforced Concrete (RC) flat roofs [112]. This project’s phase

one had three steps as explained below:

70

Roof Preparation

The roofs were prepared and repaired for leakage removal, water proofing with bituminous

coating and plain cement concrete (1:2:4) toppings.

Thermal Improvements

Three techniques were used to improve the thermal performance of RC slab roofs which

were: insulative techniques, reflective surface techniques and radiant barrier techniques.

Insulative material reduces heat transfer between objects of different temperatures. The

reflective surface bounces back the incident light and a radiant barrier inhibits heat transfer

by thermal radiation.

Performance Criterion

The thermal performance was monitored for 20 days in the month of July 2010 during the

summer season. The thermal comfort level was set below 34°C. This temperature was set as a

target to reduce the room temperature below it.

3.8.1 Results of the Case Study

During daytime with peak ambient temperatures, the highly effective materials are

paperboard false ceilings (radiative) and jumbolon extruded polystyrene (insulative)

respectively. They reduced room temperature on average by 4°C as compared to rooms with

no solution. Three reflective and four insulative materials also showed good effectiveness in

temperature reduction in the range of 2.5-3°C. The other solutions, three radiative, two

reflective and five insulative, gave average efficiency as shown in Figure 3-13 [112].

71

Figure 3-13: Outside air and inside temperature with solution comparison during day time [112]

The performance of the material at midnight is shown in Figure 3-14. All the materials

reduced the room temperature as compared to rooms with no solutions; the most effective

materials were paperboard false ceilings (radiative) and jumbolon extruded polystyrene

(insulative) and smart concrete tiles (insulative) respectively. The reduction in room

temperature was about 4.7 °C. The other materials gave a temperature reduction of 1.5 - 4°C

[112].

36.2

35.3

33.6

33.1 32.2

34.7

34 33.7

33

34.1

35.1

33.1

33.7

33.1

34.2

34.7

34.6

34.9

32.2

34.4

30

32

34

36

38

40

42Temperature comparison at day

Out Side AirTemperature at 3 PM

With Solution Inside Room Temperature

72

Figure 3-14: Comparison of outside air and inside temperature with solutions at midnight [112]

The initial cost analysis shows that reflective materials are cheaper, insulative materials

are expensive and radiative barrier materials are in between. For initial cost per square

metre the lime wash, weather sheet paint, and enamel paints are the cheapest (£0.24 -

£0.64). For initial cost per square metre, Alnoor tiles, Munawar AC tiles, and smart

concrete tiles are the most expensive (£6.38 - £10.76). The initial cost of all materials is

shown in Figure 3-15 [112].

36.7

35.4

34.1 33.9

32.0

35.6

34.0

32.0

33.4

33.8 33.7

32.6 32.6

32.9

33.4

33.6

34.9

34.5

31.7

33.6

30.0

31.0

32.0

33.0

34.0

35.0

36.0

37.0

38.0 Temperature comparison at night

outside air temperature at mid night

with solution inside room temperature

73

Figure 3-15: Initial cost of different solutions [112]

The 10 year cost analysis of these materials showed mixed results. Two reflective, two

insulative and four radiative barrier materials have 10 year cost ranges of £1.75-£4 per

square metre. The 10 year costs of these solutions is shown in Figure 3-16 [112].

Figure 3-16: 10 years cost of different solutions [112]

0

2

4

6

8

10

12C

OS

T /

SQ

. M

TR

GB

P (

£)

Initial cost of solution

. Reflective Material

. Radiative barrier material

. Insulative material

0

2

4

6

8

10

12

14

CO

ST

/SQ

. M

TR

GB

P (

£)

10 years cost of solution

. Reflective

. Radiative barier

. Insulative

74

3.8.2 Findings on the Basis of Energy Efficient Housing Reports

All the solutions improved comfort and indoor temperature decreased by 2-4°C on

average. This improvement in passive building cooling measures helps to reduce

electricity consumption and saves on CO2 emissions. This decrease in cooling load is

favorable for any cooling system especially for application in solar cooling systems.

Paperboard false ceilings are cheapest for both initial and 10-year costs and highly

efficient in reducing indoor temperature both at day and midnight. They are highly

recommended to improve thermal comfort and reduce cooling loads in summer. In

current and new buildings, this material and solar cooling systems can both help to

provide sustainable cooling systems for comfort in summer.

Some solutions/techniques are equally effective both in summer and winter seasons

for improved infiltration and leakages. These techniques are more effective in areas

with hot summers and cold winters. Such solutions include Jumbolon (polystyrene),

brick tiles with stabilised mud, insulating paper board, stabilised mud, mud with

thermopole and thermopole false ceilings.

Some new materials, specifically insulative (polystyrene, insulating paper board,

smart concrete tiles and Munawar tiles), are more efficient in reducing cooling load

and add aesthetics to the inside of rooms.

None of the solutions provide comfortable indoor conditions during hot weather as

occur in the summer in Pakistan.

3.9 Conclusion

Punjab and Sindh are the most populated provinces of Pakistan. The population of the two

provinces is more than 75% of the country’s population.

The climate of Pakistan is mostly hot and dry. Most of the areas have hot summers with a

mean daily maximum temperature of more than 34°C and they require cooling systems for

comfort. The annual average relative humidity for most of the areas is from 40% to 70%.

In the past four decades there is an average increase of 3°C in the heat index. There is an

increase in the frequency of thermal extremes of temperature values of more than 40°C and

45°C. This high temperature climatic zone is mostly in the Punjab and Sindh regions which

are home to majority of the country’s population.

75

The ASHRAE standard comfort temperature is about 26°C. The comfort zone specified by

PMV is between -0.50 to +0.50. The ISO 7730 standard does not adequately describe comfort

conditions for tropical and hot climates when air temperature is above 30°C and air velocities

of more than 1m/s.

For New Delhi (Lahore) ASHRAE adaptive comfort temperature range is between 26°C to

30°C, when the mean monthly outdoor temperature is between 33°C and 35°C. Similar

temperature range was obtained by Nicol et al. [97, 101, 102] adaptive thermal comfort in

Pakistan. Use of an adaptive comfort temperature as a set point compared to an ASHRAE

standard temperature can help to reduce the building cooling load and improve the efficiency

of cooling systems.

In Pakistan there is overall potential for 29% of savings in building energy. The Turkish

building energy efficiency code’s success shows that after the application of building energy

codes and standards in Pakistan’s buildings the following benefits may be achieved:

Decreased cooling and heating loads

Improved energy efficiency

Comfortable livings

Improved and healthier life styles

Improved productivity

The case study of the building thermal performance improvement project showed a potential

for improving existing buildings for comfort in summer with the application of a few

techniques. With nominal expense using insulative and other techniques a lower cooling load

and electricity consumption reduction could be achieved in existing buildings.

As discussed in Chapter 1, the energy crisis and very hot climate in the summer are adding

hardships to the lives of the majority of the population and the most significant factor is the

absence of cooling systems during power cut periods. Long term and sustainable clean energy

systems should be introduced to solve the energy crisis and create comfort conditions during

the summer.

76

Chapter 4: Solar Cooling Systems

4.1 Introduction

In the previous chapters, the literature has discussed in detail of energy demand, electricity

crisis, and the effects of energy crises, solar energy potential, climate, and building energy in

Pakistan. The literature showed there is demand for sustainable energy system which can

provide comfort in buildings, especially during the hot summer season. Solar energy is

widely available in most areas of the country, and its application can provide sustainable,

clean energy. As cooling demand increases in line with increases in solar radiation intensity

increases, solar cooling could provide a logical solution. This research’s aim is to investigate

the potential of a solar energy powered cooling system for the climate of Pakistan.

Solar energy is already widely used as an energy source for cooling [113-117]. Solar cooling

technologies are mainly categorised into passive solar and active solar systems based on the

process of capturing, converting, and distributing solar energy. Active solar technologies are

photovoltaic and solar thermal systems [118]. A variety of solar cooling technologies have

been developed and many are already available in the market [119, 120]. Passive solar

techniques include orienting a building towards the Sun, selecting materials with favourable

thermal properties for heat gain or designing light dispersing properties and spaces for natural

ventilation to provide cooling effects [121].

This research is carried out using an active solar technique for cooling in buildings. Active

solar cooling can be achieved by integrating photovoltaic (solar electric) or solar thermal with

the cooling generation system [117, 122]. The efficiency of the thermal collector improves as

the ambient temperature increases whereas the solar PV modules’ efficiency reduces [120,

123]. The economic study shows that solar thermal cooling is more viable than solar electric

cooling in hot climates and annual costs are location dependent. So, for Pakistan, hot climate

solar thermal will be preferable. The solar thermal cooling system specific cost per kWh of

cooling in Spanish locations is between 0.13 and 0.30 €/kWh. In hot climates like Jakarta and

Riyadh, the specific costs are as low as 0.09 to 0.15 €/kWh[22].

Solar thermal cooling has better compatibility with supply and demand, with cheap storage

compared to solar electric cooling. The investment cost of both solar electric and solar

77

thermal cooling systems is similar[124]. The average CO2 emission saving for solar cooling

in European region is 226kg/kWC per year by saving on the consumption of primary energy

[24].

4.2 Solar Electric Cooling

In solar electric cooling systems, photovoltaic (PV) panels are mostly used to power

conventional vapour compression based cooling machines [125-127]. A Stirling refrigerator

can also be connected to PV panels for cooling. The COP of Stirling refrigerators is less than

that of a vapour compression cooling system [128-130]. The main components of solar

electric cooling are PV panels, a direct current (DC) motor and vapour compression chiller,

cooling tower, chilled water pump, condenser water pump, and air handling unit, as shown in

Figure 4-1. The PV panels are sized to provide necessary electric power to motor, driving the

compression chiller. When the PV panels cannot supply the required power due to weather

conditions or at night, a power regulator is used to draw auxiliary power from the grid

connected supply system. The power regulator is capable of tracking the maximum power

from solar panels and minimises the use of power from a grid connection [117, 118, 120,

131].

Figure 4-1: Schematic overview of solar electric cooling system [132]

The vapour compression cycle consists of four components which are used to remove heat

from a lower temperature (cold reservoir) to higher temperature (hot reservoir) space. These

components include the evaporator, compressor, condenser, and expansion valve as shown in

Figure 4-1[132].

78

These components are connected in a close loop as the refrigerant is continuously circulated

to all of the components. The operation of the vapour compression system is shown in Figure

4-2.The refrigerant starts from stage 1, with a low temperature and pressure at inlet to the

compressor. The refrigerant exits the compressor with a high temperature and pressure in a

gas phase. The super-heated refrigerant enters the condenser at stage 2 and exchanges heat to

a lower temperature secondary fluid. The refrigerant exits the condenser as liquid at stage 3

and enters the expansion valve. In the expansion valve, the pressure of liquid is decreased

through a throttling effect and the sudden decrease in pressure reduces the temperature of

refrigerant[133].

Figure 4-2: Schematic diagram of vapour compression refrigeration system[133]

The refrigerant exits the expansion valve as a mixture of liquid and gas, with a low

temperature and pressure at stage 4. After stage 4, the refrigerant enters the evaporator and

absorbs the heat from the primary fluid. The refrigerant exits the evaporator at a slightly

higher temperature in the gas phase [131-133].

The co-efficient of the performance (COP) of the refrigeration system is defined as the

cooling power (Qe), divided by work in ‘w’, as expressed in Equation 1.

79

COP = η cool = Qe / w (1)

The primary fluid is usually indoor air, or water which then cools the air through a cooling

coil. Similarly, the secondary fluid is usually outdoor air or water which then rejects heat to

the ambient air through a cooling tower [118, 132].

PV modules are devices which convert sunlight directly into electricity without any

intermediate systems [134]. PV cells are normally semiconductors and produce direct current,

details of the types and efficiency of solar cells will be discussed in the next section. The

main disadvantage of PV systems is their low efficiency.

The power produced (wPV) by a PV panel is calculated by using the efficiency of the PV

panel (ηPV ) and solar energy incident on the panel (QS) as shown in Equation 2 [119, 132].

wPV = ηPV × QS (2)

And

QS = I ×A (3)

Where

I = Incident solar Insolation (W/m2)

A= Area of PV collector (m2)

The overall efficiency of solar electric cooling system is expressed in Equation 4.

ηsol.cool = ηPV × η cool = Qe / QS (4)

In solar electric system compressors, power consumption (w) should be provided by the PV

panels. The total area (A) of the solar PV panels can be calculated to cover the total daily

power consumption (wT) of the compressor by using total daily solar radiation (IT) and daily

total PV power production (WPV)T [135, 136].

A = wT / ηPV . IT (5)

The PV system is suitable for small sized refrigeration systems used for medical or food

applications in remote areas, with no conventional energy resources and a high level of solar

radiation [120, 137]. Solar tracking systems can be used to obtain maximum power from

sunrise to sunset time [135].Solar electric vapour compression cooling systems are limited

and few systems are available in literature [138].

80

4.3 Solar Thermal Cooling

Solar thermal systems produce heat energy gained from solar radiation through the heating of

a fluid circulated through a collector. Solar thermal systems are able to exploit both direct and

diffused radiation, and therefore can be installed anywhere [120, 139].

The use of solar thermal energy for cooling in hot and sunny climates is a promising

application of solar thermal collectors in buildings. The main advantage is that in solar air

conditioning applications, cooling loads and solar gains occur at about the same time in

summer. Solar cooling has the potential to significantly reduce electricity consumption,

contribute to fossil fuel energy saving and electrical peak load reduction. Solar thermal

cooling can help in achieving carbon emission reduction and promoting clean and

environmentally friendly refrigerants used in thermal cooling systems compared to

conventional vapour compression cooling systems [140]. The solar cooling technology has

not been widely applied and needs more research and development to achieve competitive

levels of reliability and cost with conventional cooling technologies [120, 141].

Solar thermal systems can use more incoming solar radiation than PV systems. When a solar

light strikes with a PV system, about 35% of the total incident spectrum (Ultraviolet to

Yellow) can be utilised to generate electricity and rest spectrum of about 65% (Orange to

Infrared) is converted to heat, as shown in Figure 4-3 [40].

Figure 4-3 Solar light spectrum used in a PV system[40]

As the solar thermal system converts solar energy to heat energy, collectors have no such

limitation. A solar thermal collector can absorb over 95% of the incoming radiation spectrum

ULTRAVOILET

10%

VOILET

5%

BLUE

5%

GREEN

10%

YELLOW

5%

ORANGE

5% RED

15%

INFRARED

45%

Solar light spectrum used in PV system

useful in a

Si based PV

~35%

Converted to

heat ~65%

81

depending on the absorbing materials [40]. Due to losses and inefficiencies, not all absorbed

energy is converted to useful energy. The collection efficiency of commercially available

solar thermal collectors is more than double compared to PV systems [142, 143].

4.3.1 History of Solar Thermal Cooling Systems Development

The application of solar thermal system for cooling is about five decades old. A summary of

important developments in solar thermal cooling systems is described in Table 4-1.

Table 4-1: History of solar thermal cooling development

Year Development Of Solar Thermal Cooling System.

1962 First Study of the use of solar thermal energy for cooling purpose [144].

1970 First commercial single effect absorption chiller for solar cooling [145].

1974 First simulation of a solar heating and cooling system [146].

1975 First TRNSYS simulation of solar processes and its application [147].

1976 Experimental study of a hybrid solar air condition system [148, 149].

1977 Experimental study of home heating and cooling with flat plate collector [150].

1978 Experimental study of a Yazaki solar cooling system for solar house one [151].

1979 Design of a residential solar heating & cooling system using the evacuated tube collector [152].

1981 Development of a double effect absorption chiller for solar assisted cooling [153].

1982 Development and test of solar Rankine cycle heating and cooling systems [154].

1985 Fortran-based modelling and simulation of a solar absorption cooling system [155].

1990 Development of a solar cooling absorption chiller with 5-10kW capacity [156].

1994 Experimental study of a solar liquid adsorption cooling system [157].

1998 Study of the performance improvement of a solar cooling unit [158].

2001 Experimental studies of a solar air conditioning system with a partitioned hot water storage tank [159].

2002 Grossman established triple & double effects are better than single effect solar powered chillers [160].

2004 R114 replaced by R142b in solar ejector system for better efficiency and environmental effect [161].

2005 Simulation & optimization of LiBr solar absorption cooling system with evacuated tube collector [162].

2007 Investigation of liquid desiccant system for solar air conditioning [163].

2008 Simulation study of solar LiBr-H2O absorption cooling system with parabolic trough collector [164].

2009 Study of an air-cooled LiBr-H2O absorption chiller cooling system in extremely hot weather [165].

2010 Experimental investigation of solar absorption cooling system without backup in tropical climate [166].

2012 Study of alternative designs for 24-h operating solar powered absorption refrigeration technology [167].

2012 Study of solar cooling systems utilising concentrating solar collectors [168].

2013 Experimental comparison of two solar driven air cooled LiBr-H2O absorption chillers [169].

2013 A theoretical & experimental study of the solar ejector cooling system with R236fa carried out [170].

2014 Design of solar ejector cooling system for a COP of 0.32 [171].

2014 Techno-economic review of solar cooling technologies based on location-specific data [172].

82

4.3.2 World Solar Thermal Cooling Status 2014 and IEA Road Map 2050

The global solar cooling market grew at an average annual rate of about 40% from 2004 to

2014. About 1,200 systems of different types and sizes were installed worldwide by 2014 and

most of these systems are in Europe (75%). The use of solar cooling is rising in many regions

with sunny, dry climates, including Australia, India, the Mediterranean islands, and the

Middle East. The availability of small (less than 20 kW) cooling kits for residential use has

increased for the residential sector in Central Europe [173].

One of the market drivers for solar cooling is the potential to reduce peak electricity demand,

particularly in countries with significant cooling needs. The cost of solar cooling kits

continues to fall, declining by 45–55% (depending on system size) over the period 2007–

2012 [173]. Solar cooling could avoid the need for additional electricity transmission

capacity caused by higher peak loads from the rapidly increasing cooling demand in many

parts of the world [174].

According to the IEA 2050 roadmap, up to 2050, solar thermal energy use for cooling could

contribute to 417 TWhth per year. The installed capacity of more than 1000 GWth for cooling

will account for nearly 17% of energy use for cooling in 2050 [174].

4.3.3 Solar Thermal Cooling Systems

A solar thermal cooling system consists of four basic components: a thermal collector,

thermal storage, thermal chiller, and heat exchanging system to exchange heat with a

conditioned space [117, 120]. An overview of solar thermal cooling system is shown in

Figure 4-4.The other components normally required are a hot water pump, auxiliary heater,

chilled water pump, cooling tower, condenser water pump, and air handling unit [5, 6].

83

Figure 4-4: Overview of thermal cooling system[123]

The types of solar thermal collectors and thermal cooling systems are discussed in detail here

as these are important components of a solar thermal cooling system.

4.4 Solar Thermal Collectors

Solar thermal collectors are heat-exchanging devices that transform solar radiation into

internal energy in a fluid (air or water). The collected solar energy is carried away by

circulating fluid either directly to hot water or space conditioning equipment or to a thermal

energy storage system for use at night and or in cloudy days [175].

On the basis of temperature spectrum application, solar collectors are divided into three

categories, as shown in Figure 4-5 [176].

Low temperature (Domestic Hot Water)

Medium temperature (Solar Heating and Cooling of Buildings)

High temperature (Industrial Process Heating and Electricity generation)

84

Figure 4-5: Solar energy collector’s application [176]

There are two basic types of solar collectors; stationary and concentrating, as shown in Figure

4-6. Stationary collectors have same area and do not track solar radiation whereas

concentrating collectors have concave reflective surfaces to intercept and focus the solar

radiation to a small area for an increased solar energy flux [37, 177].

Figure 4-6: Types of solar thermal collectors [178]

Normally, concentrating collectors are used for power generation rather than solar heating or

cooling. These collectors will be covered in the review of collectors for the purpose of

comparison.

4.4.1 Stationary Collectors:

These collectors are normally permanently fixed in a position and do not track the sun. Three

collectors fall into this category;

85

a) Flat Plate Collector (FPC)

b) Compound Parabolic Collectors (CPC)

c) Evacuated Tube Collectors (ETC)

4.4.1.1 Flat Plate Collectors (FPC)

A typical flat-plate solar collector is shown in Figure 4-7. When solar radiation passes

through a transparent cover and impinges on the black absorber surface, a large portion of the

incoming energy is absorbed by the plate and is transferred to a transport medium in fluid

tubes for storage or direct use [141, 177].

Figure 4-7: Construction of flat plate collector [37]

The underside of the absorber plate and the side of casing are well insulated to reduce

conduction losses. The liquid tubes are connected at both ends by large diameter header

tubes. A transparent cover used to reduce convection losses from the absorber plate through

the restraint of a stagnant air layer between the absorber plate and glass. It also reduces

radiation losses from the collector [141, 177].

FPC’s are available in a wide range of designs and materials. These are the most used type of

collector. The major purpose is to collect more solar energy with a lower cost. These are

normally used for low temperature applications of up to 80°C. FPC is usually fixed in

position, oriented directly towards the equator, facing south in the Northern hemisphere and

north in the Southern Hemisphere. The optimum tilt angle of the collector is equal to the

latitude of the location with angle variations of (10–15) ° more or less [37, 177].

86

4.4.1.2 Compound Parabolic Collectors (CPC)

CPC’s have the capability of reflecting nearly all of incident radiation to the absorber. The

necessity of moving the collector to accommodate the changing solar orientation is reduced

by using a trough with two sections of parabolic sides facing each other, as shown in Figure

4-8. CPC’s accept incoming radiation over a relatively wide range of angles. Due to multiple

internal reflections, the incident radiation within the collector acceptance angle (θc) is

directed to the absorber surface at the bottom of collector. The shown reflector has a lower

portion which is circular (AB and AC) and the upper portions (BD and CE) are parabolic.

The upper part of the collector truncated to increase the radiation passage to the absorber.

CPC’s are usually covered with glass to avoid dust and other materials from entering the

collector [37, 177].

Figure 4-8: Schematic diagram of compound parabolic collector [37]

The orientation of a CPC collector is relative to its acceptance angle. The collector can be

oriented along its long axis in either a north-south or east -west direction and its aperture

tilted directly towards the equator at an angle equal to the local latitude. When oriented along

the north-south direction, the collector must track the sun by turning its axis continuously. As

the acceptance angle is wide along its long axis, the seasonal tilt adjustment is not required.

When oriented with its long axis along the east-west direction, a little seasonal tilt adjustment

is required. For stationary CPC collectors, the minimum acceptance angle is 47° in order to

cover the declination of the sun from summer to winter. In practice, bigger angles are used to

enable the collector to collect diffuse radiation with a lower concentration ratio [37, 177].

87

CPC collectors are useful for sunny and warm climates. For higher temperature applications,

a tracking CPC can be used. These are not favourable for cold, cloudy, and windy days [37,

177].

4.4.1.3 Evacuated Tube Collectors (ETC)

Evacuated tube collectors are highly efficient in circumstances where there is a lower

radiation and a higher difference between the absorber and ambient temperature. Evacuated

tubes collectors are more expensive than glazed flat plate collectors. Evacuated tube

collectors use glass tubes with a vacuum. This vacuum works as insulation, reducing heat loss

from the collector and thus increasing the efficiency of the collector. Some ETCs use liquid-

vapour phase change materials for efficient heat transfer [37, 177].

Figure 4-9: Schematic diagram of evacuated tube collector [37]

The sealed copper pipe is attached to black copper fins that fill the tube (absorber plate). The

heat pipe contains a small amount of fluid (e.g. methanol) that undergoes an evaporating

condensing cycle. In this cycle, solar heat evaporates the liquid and the vapour travels to the

heat sink region where it condenses and releases its latent heat. The condensed fluid returns

back to the solar collector and the process are repeated. These tubes are connected to a heat

exchanger (manifold), as shown in Figure 4-9. Water or glycol flows through the manifold

and picks up the heat from the tubes. The heated liquid is stored or heats the load, directly or

through a heat exchanger [37, 177].

88

4.4.2 Concentrating Solar Power (CSP)

In concentrating collectors, solar energy is optically concentrated before it is transformed into

heat. Concentration is obtained by the reflection or refraction of solar radiation by use of

mirrors or lens. This reflected or refracted radiation is concentrated in a focal area, thus

increasing the energy flux per unit area in receiver. CSP systems are designed to produce

medium (400-550°C) to high high-temperature (600-1000°C) heat for electricity generation

or for the co-generation of electricity and heat[179]. These systems are capable of exploiting

only Direct Normal Irradiation (DNI), which is the energy received directly from the Sun (not

scattered by the atmosphere) on a surface tracked perpendicular to the Sun’s rays. Arid or

semi-arid areas with strong sunshine and clear skies are suitable for CSP application [39].

CSP are of following four types;

a) Linear Fresnel Reflectors

b) Power Towers (Central Receiver Systems)

c) Parabolic Troughs

d) Parabolic Dish

4.4.2.1 Linear Fresnel Reflectors: (Line Focus, Fixed Receiver)

Linear Fresnel Reflectors (LFR) are curved trough systems made by using long rows of flat

or curved mirrors to reflect the solar rays onto a downward facing linear, fixed receiver as

shown in Figure 4-10. The receiver can attain temperature of up to 250°C.The main

advantage of the LFR system is its simple design of flexibly bent mirrors and fix receivers

with low-cost direct steam generation. LFR plants have low efficiency in the conversion of

solar energy to electricity [37, 177, 179, 180].

Giorgio Francia was the pioneer in developing both a linear and two-axis tracking Fresnel

reflector system in 60s. For higher temperatures, he used two-axis tracking as modern optics

and coatings were not available [177].

89

Figure 4-10: Linear fresnel reflector (Left) & compact linear fresnel reflector (Right) [37]

The difficulty with LFR is that in order to avoid shading and blocking between adjacent

reflectors, the space needs to be increased between reflectors. The most recent design is for

Compact Linear Fresnel Reflectors (CLFR), two parallel receivers for each row of mirrors as

shown in Figure 4-10. The classical LFR system has only one receiver and there is no choice

of the direction and orientation of reflector. The interleaved arrangement minimises beam

blocking by adjacent reflectors and allows high reflector density and low tower height [37,

177, 180].

4.4.2.2 Solar Towers (Point Focus, Fixed Receiver)

Solar towers are also known as Central Receiver Systems (CRS). Large numbers of small

reflectors called heliostats are used to concentrate the solar rays on a central receiver placed

on top of a fixed tower, as shown in Figure 4-11. Each heliostat has a 50-150 m2 area of

reflective surface. Some new commercial tower plants use Direct Steam Generation (DSG)

system in receivers, in which slightly concave mirror segments on the heliostats directed rays

into the cavity of a steam generator to produce high pressure and temperature steam. The heat

energy absorbed by the receiver is transferred to be circulated for use. The main advantages

of central receivers are: [177, 179]

It minimises the thermal energy transportation as it collects solar energy optically and

transfers it to a single receiver.

The concentration ratio of 300-1500 is achieved and has high efficiency, both in

energy collection and in electricity conversion.

90

Figure 4-11: Schematic overview of power tower (central receiver system) [37]

In addition, the concept is highly flexible with a wide variety of heliostats, receivers, transfer

fluids, and power blocks. The average solar flux impinging on the receiver values from 200

to 1000 kW/m2. This high flux helps to achieve high temperatures of more than 1500

◦C. The

heat transfer and storage fluid may be water /steam, molten sodium or molten nitrate salt

(sodium nitrate / potassium nitrate) [37, 177, 180].

4.4.2.3 Parabolic Troughs (Line Focus, Mobile Receiver)

This system has light structures and low cost technology for process heat applications of up

to 400°C. A parabolic trough system consists of parallel rows of mirrors (reflectors) curved in

one dimension to focus the solar radiation on a linear receiver, as shown in Figure 4-12. The

mirror array can be more than 100m long with the curved surface at 5-6m across. A linear

tube is placed along the focal line to form an external surface receiver. Stainless steel pipes

(absorber tubes) with a selective coating serve as heat collectors. The coating allows pipes to

absorb high levels of solar radiation while emitting much less radiation. A glass cover tube is

placed around the receiver tube to reduce the convective heat loss. The tube may be

evacuated to further reduce convective heat loss. The disadvantage of a glass cover tube is

that the reflected light from the concentrator must pass through glass to reach absorber,

adding a transmittance loss. The glass envelope has an antireflective coating to improve

transmissivity [37, 177, 179, 180].

The reflectors move in tandem with the Sun as it crosses the sky. It is sufficient to use single

axis tracking of the Sun and thus a long collectors’ module is produced. The collector can be

oriented in an east–west direction, tracking the sun from north to south or oriented in a north-

south direction and tracking the sun from east to west. Over a period of year, a horizontal

91

north –south, trough field usually collects slightly more energy than a horizontal east-west

one. However, the north-south field collects a lot of energy in the summer and much less in

the winter. The east-west field collects more energy in winter than a north-south field and less

in the summer, providing a more constant annual output. Therefore, the choice of orientation

usually depends on the application and energy needed during summer or winter [37, 177,

179, 180].

Figure 4-12: Schematic of a parabolic trough collector [37]

The tracking mechanism of a parabolic trough collector is shown in Figure 4-13. The tracking

system must be reliable and able to follow the Sun with certain degree of accuracy and it

returns to its original position at the end of the day or at night. The tracking mechanism is

also used to protect collectors from hazardous environmental working conditions such as

wind gusts, overheating, and the failure of the thermal fluid flow system, by turning the

collector out of focus.

The tracking mechanism has two categories: mechanical and electrical/electronic. The

electronic system is more reliable and accurate in tracking [37, 177].

92

Figure 4-13: Parabolic trough collector tracking mechanism [37]

All parabolic trough plants currently in commercial operation rely on synthetic oil as the fluid

for heat transfer from the collector pipes to the heat exchangers, where water is preheated,

evaporated, and then superheated. The superheated steam runs a turbine, which drives the

generator to produce electricity. After condensation, water returns to the heat exchangers.

Parabolic troughs are the most mature system among CSP technologies and mostly used in all

commercial plants. A recent development in parabolic troughs collectors is the design and

manufacture of the Euro trough with a lightweight structure to achieve cost effective solar

power [37, 177, 180].

4.4.2.4 Parabolic Dish Collectors (Point Focus, Mobile Receiver)

Parabolic dishes concentrate on the solar radiation at a focal point above the centre of the

dish. The entire apparatus tracks the Sun in two axes, with the dish and receiver moving in

tandem, as shown in Figure 4-14. Most dishes have an independent engine/generator (Stirling

machine or micro turbine) at the focal point. Dishes have the highest solar to electric

conversion efficiency over any other CSP system. The salient features of dishes make it

competitive with PV modules, and other CSP technologies. A parabolic system can achieve

temperatures in excess of 1000°C [37, 177, 179, 180].

The salient features of parabolic dishes are; [177]

They always pointing towards the Sun, these are the most efficient of all collectors.

93

The concentration ratios are in the range of 600-2000, making it more efficient in

solar energy absorption and power conversion systems.

These have modular collector and receiver units that can function independently or as

part of a large system.

Figure 4-14: Schematic of a parabolic dish [37]

Parabolic dishes are limited in size (tens of kW or smaller) and each produces electricity

independently, which means that hundreds or thousands would need to be co-located for

large-scale production [37, 180].

4.4.3 Comparison of Thermal Collectors

For solar thermal cooling, most concentrating collectors are expected to be too expensive as

an input thermal energy system for building integrated solar cooling system. The high cost is

mainly due to the complexity of the tracking system [123].

However, tracking can provide a significant increase in energy output. A 10-year comparison

of stationary and tracking solar collectors is shown in Figure 4-15. The stationary collector

was tilted at 40° at Askov, Denmark. The annual energy output of the single axis vertical and

horizontal tracking is about 7% and 55% more than the stationary collector. The two axis

tracking collector has about 75% more energy output compared to the stationary collector

[181].

94

Figure 4-15: 10 year thermal performance of stationary and tracking collectors [181]

A thermal cooling system operates with an input heat at a temperature of between 60°C and

100°C, so a high temperature output of concentrating collectors is not required. For solar

thermal cooling, both flat plate and evacuated tube collectors are used [123].

Evacuated tube collectors are preferred over flat plate collectors due to the higher thermal

efficiency and to produce higher temperature output [182, 183]. Higher efficiency at low

incidence angles making them more suitable for daylong performance [177, 183].

Flat plate collectors are the most used collectors in solar cooling installations. Although

Evacuated tube collectors are expensive, they need less collector area compared to flat plate

collectors. The average collector area for a flat plate collector is 4.6m2/kWC, whereas for an

evacuated tube collector it is 2.5m2/kWC [132, 184].

4.5 Thermal Cooling Systems

Thermal cooling systems are driven by heat, instead of electric power to run the compressor

in a conventional vapour compression cooling system [132]. Thermal cooling systems are

always preferred when a large amount of waste heat energy is available. To couple with a

renewable energy system, such as solar thermal energy, these cooling systems are used for

solar assisted cooling and air-conditioning [185].

0

100

200

300

400

500

600

700

800

2001 2002 2003 2004 2005 2006 2007 2008 2009 2010

An

nu

al

en

erg

y o

utp

ut

(kW

h/m

2.y

ear)

Thermal performance of collectors

Stationary

Vertical

Tracking

Horizontal

Tracking

vertical+Horiz

ontal Tracking

95

In thermal cooling systems, sorption technology is used. In this technology, the cooling

effect is obtained by physical or chemical changes between a pair of substances (the sorbate

and the sorbent). The sorption system is classified into open and closed sorption systems. The

open sorption system includes a solid and liquid desiccant system whereas absorption and

adsorption systems are closed sorption systems [117, 120, 132].

There are of four main types of thermal cooling systems, which are:

Absorption system

Adsorption system

Solid and Liquid desiccant dehumidifiers

Ejector system

4.5.1 Absorption System

Absorption is a process in which two substances in different states are mixed into each other.

These two different states form a solution called a mixture. This process is reversible and can

occur by the addition or removal of heat. The first absorption system was introduced in 1895

[117, 120, 132].

Absorption system-based machines are the most commonly used thermal driven cooling

systems in solar cooling installations. In absorption systems, an absorbent, on the low-

pressure side, absorbs an evaporating refrigerant. The two most used combinations of fluids

include lithium bromide-water (LiBr–H2O), where water is the refrigerant and ammonia-

water (NH3 –H2O) systems, where ammonia is the refrigerant. The first pair is used for

building cooling and the second for low temperature applications [37, 117, 120, 132].

96

Figure 4-16: Schematic overview of solar absorption cooling system[120]

In the absorption refrigeration system, low pressure refrigerant vapour from the evaporator is

dissolved in the absorbent in the absorber, as shown in Figure 4-16. Then, the solution is

pumped to a high pressure with an ordinary liquid pump. The addition of heat in the

generator is used to separate the refrigerant from the solution. In this way, the refrigerant

vapour is compressed with less mechanical energy than the vapour compression systems

demand. The weak solution is then returned to the absorber through a heat exchanger to

recover heat. The remainder of the system consists of similar components to a vapour

compression system (a condenser, expansion valve, and evaporator [37, 120, 185].

The LiBr–H2O system operates at a generator temperature in the range of 70–95°C with water

used as a coolant in the absorber and condenser. The limitation of the LiBr–H2O systems is

that their evaporator cannot operate at temperatures much below 5°C since the refrigerant is

water vapour. Commercially available absorption chillers for air conditioning applications

usually operate with a solution of LiBr–H2O and use steam or hot water as the heat source

[37, 117, 132].

The single effect absorption chillers are mainly used for building cooling loads, where chilled

water is required at 6–7°C. The COP of single effect absorption system varies from 0.60 to

0.80. This variation is due to the heat source and the cooling water temperature. Single effect

chillers can operate with hot water temperatures ranging from about 65 to 150°C [37, 117,

120, 132].

97

The double effect absorption chiller has two stages of generation to separate the refrigerant

from the absorbent. The temperature of the heat source needed to drive the high-stage

generator is essentially higher, and is in the range of 155–205°C. Double effect chillers have a

higher COP of about 0.90–1.35. The triple effect machines can have a COP of about 1.70 [37,

117, 120, 132]. Absorption systems can use flat plate or evacuated tube collectors for single

and double effect machines, and evacuated tube or concentrated parabolic collectors for triple

effects cases [132].

From the literature, it is established that LiBr–H2O absorption systems are a mature

technology and have a good perspective for energy efficient cooling in buildings [124].

4.5.2 Adsorption System

Adsorption technology was first used for cooling systems in the early 1990s. The adsorption

process is surface phenomenon whereas absorption is a volumetric phenomenon [117, 120].

In adsorption systems, a solid (the adsorbent) and gas (the refrigerant) interact with each

other. The adsorbents are porous solids, and can reversibly adsorb large volumes of a vapour.

This interaction can be chemical or physical and depends upon adsorption forces. In chemical

adsorption, there is an exchange of electrons which occurs between solids and gas. In

physical adsorption, molecules of a refrigerant come to fix to the surface of the absorbent [37,

117, 120, 132, 185].

Solar adsorption’s practical application in the field of refrigeration is relatively recent. The

concentration of adsorbate vapours in a solid adsorbent is a function of the temperature of the

mixture (adsorbent and adsorbate), and the vapour pressure of the latter. Under constant

pressure conditions, it is possible to adsorb or desorb the adsorbate by varying the

temperature of the mixture. This forms the basis of the application of this phenomenon in the

solar-powered adsorption refrigeration, as shown in Figure 4-17 [37, 117, 120].

A number of different solid adsorption pairs, such as activated carbon–ammonia, zeolite–

water, zeolite–methanol, activated carbon–methanol, and silica gel-water are used. The

efficiency of adsorption systems is low. Many systems integrate the adsorbent bed and the

solar collector together by packing the adsorbent in the collector. For continuous operation,

two adsorption cycles are combined and such systems can have a COP of 0.60 [37, 117, 120,

132, 185].

98

Figure 4-17: Schematic diagram of solar adsorption system[95]

The activated carbon–methanol working pair was found to perform the best. Complete

physical property data is available for a few potential working pairs, but the optimum

performance remains still unknown. The advantages of adsorption system include: no danger

of damage due to high temperatures, environmentally friendly materials use, less usage of

electricity and low maintenance costs. The disadvantages are: a lower COP than absorption

systems, higher initial costs, and requiring a high vacuum tightness of the container [37, 117,

120, 132].

4.5.3 Solid and Liquid Desiccant Cooling System

A desiccant cooling system is the combination of evaporative cooling and dehumidification.

These are best suitable for application where humidity is low. These are open sorption

cooling systems as water is used as a refrigerant in direct contact with the ambient air. The

desiccants are natural or synthetic substances capable of absorbing or desorbing water vapour

due to difference of water vapour pressure between the surrounding air and desiccant surface

[117, 132, 185].

The driving force for the desiccant process is the difference in vapour pressure between the

air and the desiccant surface. When the water vapour pressure on the desiccant surface is

99

lower than air, water is absorbed by the desiccant. When the water is absorbed, the vapour

pressure in the desiccant is equal to that in the air, as shown in Figure 4-18.

Figure 4-18: Desiccant cooling process [186]

To allow for the repeated use of the desiccant, regeneration is required. This is accomplished

by heating the desiccant to increase its water vapour pressure. The heat required for

regeneration is supplied at a low temperature (60–110°C). Both solid and liquid desiccant

materials are used. These include lithium chloride, tri-ethylene glycol, silica gels, aluminium

silicates (zeolite), aluminium oxides, lithium bromide solution, and lithium chloride solution

with water [117, 186].

A desiccant cooling system comprises of three components; regeneration heat source, the

dehumidifier (desiccant material), and the cooling unit as shown in Figure 4-19 [186, 187].

Figure 4-19: Principle of desiccant cooling [186]

100

4.5.3.1 Solid Desiccant System

A solid desiccant cooling system uses rotating wheels made of silica gel, zeolite, or lithium

chloride as sorption materials. Figure 4-20 illustrates a solar-driven solid desiccant cooling

system. The system has two, slowly revolving wheels and several other components between

the two air streams and a conditioned space. The return air from the conditioned space first

goes through a direct evaporative cooler and enters the heat exchange wheel with a reduced

temperature (A-B). It cools down a segment of the heat exchange wheel when it passes

through (B-C) and is heated as it does so. This warm air stream is further heated to an

elevated temperature by the solar heat in the heating-coil (C-D). The heating-coil has a

temperature of between 50°C to 75°C. The resulting hot air regenerates the desiccant wheel

and is rejected to ambient (D-E). On the other side, fresh ambient air enters the regenerated

part of the desiccant wheel (1-2). Dry and hot air comes out of the wheel as the result of

dehumidification. This air is cooled down by the heat exchange wheel (2-3). Depending on

the temperature level, it is directly supplied to the conditioned space or further cooled in an

after cooler (3-4). If no after cooler is used, the cooling effect is created only by the heat

exchange wheel that was previously cooled by the humid return air at point B on the other

side. The temperature at point 3, T3, cannot be lower than TB, which in turn is a function of

the return air condition at point A, as shown in Figure 4-20 [117, 119, 132, 185].

Figure 4-20: An illustration of solar assisted solid desiccant cooling system [119]

101

This system allows a saving of up to 50% of primary energy compared to the vapour

compression system and is environment friendly. However, further improvements in the

efficiency of this system are required [132].

4.5.3.2 Liquid Desiccant System

In the liquid desiccant cooling system, dehydration is obtained by absorption. The desiccant

wheel is replaced by a dehumidifier and regenerator. The air is cooled down by spraying an

absorbent solution into the air. Generally, the solution consists of water and lithium chloride

or calcium chloride. The liquid desiccant assisted air conditioning can achieve up to 40% of

energy savings with regards to the traditional air conditioning system and savings become

even greater when regeneration energy is drawn from waste heat, solar energy or any other

free energy sources. Liquid desiccant can also store a large amount of energy by storing

concentrated solutions. This storage can make it a more promising future cooling system with

solar energy [117, 119, 132, 185].

In a liquid desiccant cooling system, the liquid desiccant circulates between an absorber and a

regenerator in the same way as in an absorption system. The main difference is that the

equilibrium temperature of a liquid desiccant is determined not by the total pressure but by

the partial pressure of water in the humid air to which the solution is exposed. A typical

liquid desiccant system is shown in Figure 4-21. In the dehumidifier, the concentrated

solution is sprayed at point A over the cooling coil at point B, while ambient or returns air at

point 1 is blown across the stream. The solution absorbs moisture from the air and

simultaneously cools down by the cooling coil. The results of this process are the cool dry air

at point 2 and the diluted solution at point C. An after cooler at point 3, cools down this air

stream further to the lower temperature, as shown in Figure 4-21 [117, 119, 132].

102

Figure 4-21: A Solar assisted liquid desiccant cooling system [119]

In the regenerator, the diluted solution from the dehumidifier sprayed over the heating coil at

point E, connected to solar collectors and the ambient air at point 4, is blown across the

solution stream. Some water is taken away from the diluted solution by the air while the

diluted solution is heated up by the heating coil E. The result is a concentrated solution

collected at point F and the hot humid air is rejected to the ambient at point 5. A recuperative

heat exchanger preheats the cool diluted solution from the dehumidifier using the waste heat

of the hot concentrated solution from the regenerator, resulting in a higher COP [119].

The liquid desiccants have an advantage because of their operational flexibility and capability

of absorbing pollutants, and bacteria, and being regenerated at relatively low temperatures.

Other advantages are high energy storage and the ability to continuously pass a large volume

of air through a close system. The disadvantages of liquid desiccant cooling systems include

less dehumidification in humid climates, a relatively larger size, and heavier and reduced

efficiency due to air leaks [117, 119, 132, 140].

A study of a hybrid cooling system, conventional electrical and desiccant cooling systems in

four different locations worldwide (Hamburg, Chicago, Sao Paulo, and Singapore), showed

that the solar cooling system is not yet economically viable [124, 188].

103

4.5.4 Ejector System

A solar ejector cooling system is a low grade thermal energy driven technology. The ejector

is a thermally driven compressor that operates on a vapour compression refrigeration cycle.

The generator and ejector take the place of the electric compressor; it uses heat rather than

electricity to produce the compression effect in a vapour compression system. A solar ejector

system is shown in figure 4-22 [132].

Figure 4-22: Schematic view of solar ejector cooling system [132]

The ejector cycle start from the generator exit, where the refrigerant is in a superheated state.

Under these conditions, the internal geometry of the ejector sucks the evaporator vapour for

its compression at an intermediate pressure. The working fluid enters the condenser and it is

cooled down to a saturated liquid state. After the condenser fluid is divided into two streams;

the first stream is pumped to the evaporator generator. The other stream is passed through an

expansion valve, to create a cooling effect and then enters the evaporator. In the evaporator it

exchanges heat for space cooling [117, 185].

Ejectors have been used in evacuating air from low-pressure steam condensers. An ejector in

this application acts as a vacuum pump, driven by low pressure steam. Efficiency was not as

important as reliability. It was a small step to form a vapour compression heat pump using an

ejector as a heat driven compressor. Steam-driven ejector heat pumps became common in air

conditioning, particularly in hotels and ships during the early 20th century. Ejector systems

were found to be low cost, very reliable and maintenance free. The main advantages are the

absence of moving parts, being smaller in size, having lower initial costs, and the simplicity

in design. They also consume less electricity compared to other refrigeration systems. The

104

main disadvantage of the ejector is its low COP compared to other cooling systems. The COP

of ejector systems is in range of 0.20-0.33, which is much lower than vapour compression or

absorption systems. Due to low COP, ejector systems’ use is not preferred [132, 140].

From the literature presented on solar thermal cooling systems, it is observed that absorption

cooling systems are most commonly used in all of the installations. Single effect absorption

systems can be used with both flat plate and evacuated tube collectors. As presented in

Section 4.4.3, evacuated tube collectors are more efficient and require less space than the flat

plate collectors, therefore in this research, the absorption cooling system with an evacuated

tube collector will be investigated for the feasibility of a solar cooling system for the climate

of Pakistan.

4.6 Solar Cooling for Hot Climates

Locations across the world with minimum annual solar insolation of 2000 kWh/m2 and a

location between 40° north and south latitude are considered suitable and favourable for the

installation of solar thermal system applications. The suitable locations include Australia,

Africa, Europe (Mediterranean countries), China, Russian federation, Middle East, India,

Pakistan, Iran, South and Central America and USA (South-Western) [140].

In hot climates, air conditioning in buildings is increasing and conventionally provided by

electric driven cooling systems. To reduce the load on an electrical network during peak

loading time, thermal driven cooling systems powered by solar energy can be used [22].

Many researchers have investigated solar cooling systems for hot climates. As early as the

1960s Chinnapa [144] and Tablor [189], concluded from experimental studies that flat plate

collectors could be used to drive heat-operated cooling systems. In the 1970s, Ward et al.

[149, 152, 190-193], studied the operations of a solar cooling system installed at a CSU solar

house in the USA. Muneer [194], Uppal [195], presented a feasibility and design study of a

solar cooling system for Libya. The collector tilt angle for maximum energy output and

capacity of the absorption chiller was proposed. Ayyash [196], and Homoud et al. [197]

presented feasibility and experimental studies of solar vapour absorption cooling systems

with a flat plate collector for Kuwait. It was found that the COP of the cooling system and the

saving in electricity consumption was 0.60 and 25-40% respectively.

105

Yueng at al. [198] and Fong et al. [118] presented experimental and comparative studies for

solar-powered cooling systems for Hong Kong. The experimental absorption system, with a

flat plate collector showed an annual efficiency of 7.8%, with an average solar fraction of

55%. The later compared the performance of five different cooling systems for buildings. On

the basis of a year-long operation, for the best total primary energy consumption, the order of

solar systems is; solar electric compression refrigeration, solar absorption refrigeration, solar,

adsorption refrigeration, solar solid desiccant cooling and solar mechanical compression

refrigeration. For solar collectors, the primary energy consumption of the evacuated tube

collector is 29.2% less than the flat plate collector for absorption refrigeration. For the same

area, the evacuated tube collector collected 81% more energy than the flat plate collector

during a one-year operation. It is concluded that a solar absorption cooling system (either

with a flat plate or with evacuated tube collectors) can save 15.6% to 48.3% in annual energy

compared to conventional electric compression systems.

Sorour [199], Elsafty [200], and Schwerdt [201], investigated the feasibility, economic and

experimental studies of a solar cooling system for Egypt. It is found that solar cooling

systems with both flat plate and evacuated tube collectors can provide sufficient energy for

operation. The economic study showed that the total cost of a double effect vapour absorption

system is 45% and 37% lower than a single effect and vapour compression cooling system,

respectively. The experimental study for the adsorption system showed that the COP of the

system in the summer was 0.25 to 0.30. The thermal efficiency of the CPC collectors was

observed from 50-65%. Izquirdo et al. [202], Syed et al. [203] and Martinez et al. [204],

presented experimental and test results of designed, solar absorption cooling systems for

Spain. Solar cooling systems with flat plate collectors and hot water storage systems showed

a COP from 0.34 to 0.691. The specific collector area was from 1.5-2.2 m2/kWC.

Balghouthi et al. [205, 206], presented a feasibility and optimisation study of the solar

cooling system for Tunisia. A system consists of 11kW LiBr-H2O absorption chiller with

30m2 flat plate collector tilted at 35° with a 0.80m

3 hot water storage tank, was proposed.

Pongtornkulpanich et al. [207], presented an experimental study of a 35.2kW LiBr-H2O

single-effect absorption cooling system in Thailand. The evacuated tube collector of area

72m2 provided an 81% solar fraction. Kim [165] studied the performance of an air cooled

Libr-H2O absorption chiller in extremely hot weather at 35°C and 50°C ambient temperature.

It is observed that at 50°C, the COP of the direct and indirect air cooled chiller was decreased

to 81.6% and 75% and the cooling power also decreased by 37.5% and 35.6% respectively

106

compared to 35°C. It is established that the direct air cooled chiller design is better in terms

of energy efficiency.

Alili et al. [208, 209], optimised and proposed a solar cooling system for Abu Dhabi. The

optimisation carried out for a 10kW absorption system with evacuated tube collectors of area

3.4m2/kWC and it was established that it could save up to 35% in energy compared to

conventional electric compression systems. Another model was proposed of the same

capacity, with an evacuated tube collector specific area 6m2/kWC and a hot water storage tank

with a specific volume of 0.1m3/kWC. The proposed system can save 47% in primary energy

and 12 metric ton/year of CO2 emission. Ssebataya et al. [210], investigated the performance

of a solar cooling system in UAE conditions. A 35.2kW solar absorption system with a

128m2 evacuated tube collector and 1m

3 hot water storage was used to cool 96.75m

2 floor

areas with 22°C indoor set point. The COP of the cooling system was observed from 0.60 to

0.80.

Tsoutsos et al. [211], proposed the design of a solar absorption cooling system for a Greek

hospital. The performance of the system in four different cities in Greece was analysed.

500m2 solar collectors provided 74.23% solar fraction with 15m

3 hot water storage. The

efficiency of the solar cooling system was highest in the most southern locations. Praene et

al. [212], carried out simulation and experimental investigations of a solar absorption cooling

system in Reunion Island. A solar-driven 30kW LiBr-H2O single effect absorption chiller

with 90m2 double glazed flat collectors and 1.5m

3 hot water storage was investigated. The

room temperature set point was 25°C and a 100% cooling load was provided by the solar

cooling system. It was concluded that the solar assisted cooling system could save CO2

emission of 0.23kg /kWC compared to a conventional electric compression system.

Ayadi et al. [213], presented a performance assessment for a solar cooling system for office

buildings in Italy. A 17.6kW absorption chiller with flat plate collectors of a 61.6m2 absorber

area, and 5m3 hot and 1m

3 cold water storage was installed. The thermal efficiency of the

collector was 30% to 40% and the absorption chiller COP was 0.55. Fasfous et al. [214],

studied the potential of utilising solar cooling in the University of Jordan. The analysis was

performed using an 8kW solar cooling system. A flat plate collector with an area of 40m2,

and 2.3m3 hot water storage tanks was used and provided a 15-25% solar fraction. The

economic analysis showed the system pay back is assumed 24 years and concluded that the

solar cooling system is not feasible with the proposed system.

107

Eicker et al. [22, 124], studied the energy and economic performance of solar cooling

systems worldwide. Six different locations were selected and it was found that the evacuated

tube collectors can reduce the collector area by 50% compared to flat plate collectors. It is

found that both solar electric and thermal cooling can reduce primary energy consumption by

21-70% depending on location, building standard and internal load conditions. Solar thermal

systems showed a better match to the demand and supply compared to the solar PV electric

system. It is established that in hot regions, solar cooling costs are quite comparable with

conventional cooling costs. It is found that in the hot climates of Jakarta and Riyadh, the

specific costs are as low as 0.09 to 0.15 €/kWh. The solar cooling systems can save CO2

emissions from 30-79%.

Assilzadeh et al. [162] simulated and optimised a 3.5kW solar absorption cooling system for

Malaysia, Sim [215] modelled and simulated 4.5kW solar thermal cooling system for Qatar,

Sharkawy et al. [216] investigated the potential application of a solar cooling system for

Egypt and Saudi Arabia, Ozgoren et al. [217] investigated the performance of a 3.5kW solar

absorption cooling system for Turkey and Mazloumi [164], simulated 17.5kW solar

absorption cooling system for Iran. The results of these studies are similar to the literature

presented earlier.

The literature of studies presented above are both simulation and experimental. The literature

showed that in most of the studies flat plate collector is used, however, it was also established

evacuated tube collector uses less than half area for same energy output compared to flat

plate collector [22, 124, 198]. It was also established that vapour absorption cooling system is

most widely used and has higher COP than other cooling systems[118]. The building

integrated systems have successfully maintained the selected set point for room

temperature[210, 212]. It was also found that energy consumption and CO2 emission saving

by all solar cooling systems is significant [22, 118, 124, 208, 209]. It was also proved that for

hot climates solar thermal cooling system performance is better than solar electric cooling

system[22, 124].

These studies presented differ in many aspects as performance indicators vary by location.

The literature presented is for different climatic conditions worldwide with different solar

energy potential. The systems and results are different for; collector area (30-500 m2),

collector type (Flat plate or evacuated tube), collector efficiency (7.8-65%), collector tilt (at

108

location latitude), collector specific area (1.5-6m2/kWC), hot water storage tank volume (0.8-

15m3), water storage type (hot-cold),chiller type (absorption or others), Chiller capacity

(3.52-35.2kW), chiller COP (0.25-0.80), building integration and room set point (22-25ᵒC),

solar fraction (15-81%), electrical energy saving (15.6-70%) and cooling tower types (wet or

air cooled) and comparison of different mode of operations and different systems.

All these studies were beneficial for the selection of different components for current

research. This include selection of type of collector, type of storage tank, type of chiller,

mode of operation of chiller (single or double), cooling tower type (dry or wet) and other

operational parameters for these components. The detailed justification for each of these

components is given in Chapter 6. The data of these studies is also used for results validation

and parametric analysis as no experimental data for Pakistan and neighbouring country is

available for solar powered absorption cooling system.

4.6.1 Solar Cooling System Research for Pakistan and India

Little literature is available on the doctoral, and academic published research on solar cooling

systems in Pakistan and India. Most of the research work carried out is on solar desiccant

cooling systems.

Khalid at al. [54, 55], presented a study of a solar assisted hybrid desiccant cooling system

for the climate of Pakistan. Khalid et al. [218], presented an experimental and simulation

study of a solar assisted pre-cooled hybrid desiccant cooling system for Pakistan. The

experiments were performed on a gas fired pre-cooled hybrid solid desiccant cooling system

test rig for highly humid Karachi weather. The TRNSYS model of the same system was

validated by experimental results. Both experimental and simulation results were in good

agreement with each other and other research studies. The experimental data were used as

input for the TRNSYS model. The economic assessment of the system showed a payback

period of 14 years.

Gupta et al. [219] carried out research on an open cycle 10.5kW desiccant solar air

conditioner-concept, design and cycle analysis. Bansal et al. [220] carried out experimental

study of performance testing and evaluation of solid desiccant solar cooling unit in Delhi.

The system had very low cooling capacity of 1.5kWh/day. The theoretical and experimental

COP of the system was 0.143 and 0.081. It was concluded that for Delhi climatic condition

the unit needs to be re-designed. Jani et al.[221] simulated solar assisted solid desiccant

109

cooling systems using TRNSYS. The system was designed for 60kW cooling load with inside

set point condition at 50% RH and 25ᵒC. It was observed that system in recirculation mode

showed higher COP than in ventilation mode. Mittal et al.[222] investigated modelling and

simulation of a solar absorption cooling system for India. The performance of 10.5kW solar

driven LiBr-H2O absorption cooling system with flat plate collector was investigated. It is

found that system performance was highest at 80ᵒC temperature from the storage tank.

Kumar[223] in 1990, completed doctoral research on “Thermal design and performance

evaluation of vapour absorption/adsorption solar space conditioning systems”. It was

concluded that open cycle absorption cooling system with solution storage option is feasible

for continuous air-conditioning in India [224]. A comparative study with methanol-

LiBr.ZnBr2, methanol- LiI.ZnBr2 and H2O-LiBr mixtures has also been undertaken. It was

found that the COP of the methanol-LiI.ZnBr2 and methanol-LiBr.ZnBr2 mixtures are almost

the same, while for the H2O-LiBr mixture, the COP is slightly higher than other mixtures

[225]. It is also concluded that double absorption solar cooling systems are better in

performance than conventional systems [226]. It was found that a desiccant cycle is more

efficient under high latent heat load and higher ambient humidity conditions and uses less

energy compared to conventional vapour compression cooling systems[227]. Habib et

al.[228] simulated a solar heat driven adsorption chiller for Indian city of Durgapur. The

result showed that this chiller is capable of providing cooling throughout the year under the

climatic condition of studies location. The literature also showed that combination of

different collectors and cooling system from 30kW to 350kW capacity, solar powered

cooling systems are in operation in India [229]. The detail of operational parameters and

other specification is not available.

The literature presented showed that most of the research was carried out on desiccant and

adsorption cooling system for hot and humid climatic conditions [218-221]. This limitation

(hot humid climate) creates a need and potential of solar powered cooling system for hot and

dry climatic conditions for the current research, as the climatic condition of Lahore is hot and

dry.

Mittal et al.[222], Kumar [223], and Habib et al.[228] studied systems suitable for hot dry

climates (absorption and adsorption); their work shows that these systems are capable of

providing cooling using solar energy. The current research is detailed analysis of solar

powered cooling system with building integration as their work does not provide details and

validation.

110

4.7 Conclusion

Cooling systems share a major part of total energy consumption in buildings through

electricity. Solar energy-based cooling systems can significantly reduce the grid consumption

of fossil fuel-based generated electricity and help to reduce CO2 emissions. Solar cooling

systems can help to promote environmentally friendly refrigerants. The main advantage of

solar cooling is that maximum solar energy is available when the cooling load is required in

the summer. The use of solar cooling systems is increasing in line with clean energy goals

and under IEA policy and solar cooling will contribute to 17% of total energy use in cooling

by 2050.

Solar electric systems are suitable for small size refrigeration or in remote areas with no grid

supply. The application of solar electric cooling systems is limited and only a few systems are

available in the literature. Solar PV systems can only use about 35% of the spectrum of

incident solar light. Solar electric systems have showed lower performance in hot climates as

the efficiency of solar to electric conversion is reduced by an increase in ambient

temperature.

Solar thermal cooling systems’ use and development started in the 60s. Different techniques

have been developed as being suitable to solar energy availability and output capacity. Solar

thermal systems work efficiently in high ambient temperatures and use about 95% of the

spectrum of incident solar radiation.

Concentrating solar collectors are normally used for electricity generation only. CSP systems

are designed to produce medium (400-550°C) to high (600-1000°C) temperature heat for

electricity generation or for the co-generation of electricity and heat.

Flat plate collectors are the most used collectors in solar cooling installations. Evacuated tube

collectors have high efficiency with low radiation and have a wide range of applications

compared to other stationary collectors. Although evacuated tube collectors are expensive,

but they need less specific collector area compared to flat plate collectors. The average

collector area for flat plate collectors is 4.6m2/kWC whereas for evacuated tube collectors its

2.5m2/kWC. For this research, the solar cooling evacuated tube collector will be used for hot

water to be used in the cooling system.

111

Four types of cooling systems are being used for solar thermal cooling. From the literature it

is established that the absorption system is the most efficient, mature and widely used due to

its commercial availability. Single, double, and triple effect absorption systems have been

developed for applications and efficiency range. For this research, a single effect vapour

absorption cooling system will be used.

The use of desiccants and adsorption systems is new for solar cooling and research is ongoing

to improve process efficiency. An ejector system-based cooling technique is not new but it is

not favourable as compared with compression and absorption systems due to lower

efficiency. Research is being carried out on ejector systems for efficiency improvement with

different refrigerants and effective use for solar cooling.

Despite its attractiveness, solar thermal cooling technology is still in the development stage.

Most installations currently in operation showed differences in the collector area per kilowatt

of cooling capacity. The general range of collector area for thermal cooling system is

between 2m2 to 10m

2 per kWC.

For hot climates, solar cooling is economical compared to conventional compression cooling

using electricity. For Pakistan’s climatic conditions, the experimental and simulated solar

assisted desiccant cooling system showed feasibility of the system operation to meet the

cooling loads in summer.

112

Chapter 5: Methodology

5.1 Introduction

A detailed literature review for solar cooling systems has been presented in chapter 4. Types

of solar cooling systems, solar collectors, and thermal cooling systems were described. This

chapter is about the methodology available and adopted for research into building integrated

solar thermal cooling systems for Pakistan’s climatic conditions.

The proper sizing of a solar cooling system is a complex task which includes both predictable

(collector and other component performance characteristics) and unpredictable (temperature

and humidity) components. The system can be used either as a standalone system or with

conventional air conditioning [211, 230]. To evaluate the feasibility and performance of a

solar cooling system two widely-used techniques are the manufacturing of a prototype and

experimental evaluation, and dynamic simulation. In this chapter a detail of literature is

presented about experimental and simulation studies for solar cooling systems and

meteorological data types are explained. The selected technique with details is presented in

the next sections.

The problem in designing a new solar cooling facility is that there are no standard

specifications and configurations to follow due to variation in climatic conditions and

building characteristics. Every case is a specific, and detailed study (optimisation) is required

to achieve maximum efficiency of the system. Different tools and systems are used by

researchers for solar cooling system studies worldwide [231].

The solar cooling system can be designed and evaluated by two possible criteria. One

criterion is where solar cooling system contributes according to its capacity and providing a

share of total cooling demand. The second criterion is where solar cooling system provides

total cooling demand with solar energy. a system based on the first criterion can produce the

most cooling energy from a given system. The second criteria based system is more complex

to obtain an optimum configuration as there is the need to meet the total cooling demand.

Such systems are best for thermal comfort in small scale facilities for domestic applications

[231].

This research is aimed to evaluate performance of a building integrated solar powered

absorption cooling system. The goal is to use the solar energy to meet the whole cooling

113

demand of the selected building with actual construction materials and standards used in

Pakistan. The building energy in Pakistan has been described in the Sections 3.7 and 3.8. The

principal techniques available for the study of solar cooling systems are by experiment or by

dynamic simulation. As described in Section 4.8.1, there is no experimental or installed solar

absorption cooling system facility in Pakistan; dynamic simulation will therefore be the

adopted methodology for this research.

For dynamic simulation of a building integrated solar absorption cooling system, a realistic

3D building model with actual building construction (construction standards, materials,

glazing fraction, size, etc.) will be chosen and the solar powered cooling system will be sized

so that it can maintain room temperature level at the required set point all the time. To

evaluate building cooling load, internal gains by persons and equipment will be considered.

The selected solar absorption cooling system will be optimised for the most efficient

configuration and operation parameters. The optimisation will consider all the main system

variables (collector area, tilt and energy gain, storage tank volume, pump, and fan flowrate)

and the criteria for most efficient will be the least collector area with maximum energy gain,

storage tank volume with minimum heat loss and fan flow to maintain room set point

temperature.

The results of the dynamic simulation will be validated by published results, and the more

important system parameters will be analysed through parametric analysis of the system to

evaluate the effect of these parameters on whole system performance. The detailed

methodology with system design and results will be presented in next chapters.

5.2 Experimental Study

An experiment can be characterised as an investigative activity that involves intervening in a

system in order to see how the properties of interest in the system change. Experiments play a

central role in scientific practice and are considered to have a more direct relationship with

the object of study, contributing to establishing a valid reference about real systems. It is well

established that experiments are designed to test and validate hypotheses. Field experiments

have an advantage over laboratory experiments as they take place in natural conditions, but

the choice of type of experiment depends on the type of experiment outcomes. Field

experiments are more realistic, but there may be many uncontrolled variables that affect the

results. Laboratory experiments allow known variables to be controlled [232].

114

More than 1,000 solar thermal cooling systems have been installed worldwide. The available

literature shows that often hybrid systems with free cooling support are installed and

evaluated [124]. Most installations in operation are part of demonstration projects and most

of the systems are in European countries [204].

The first experimental study of solar cooling systems was carried out by Chinnappa in 1962

using a flat plate collector [144]. The first design and construction of a residential solar

cooling and heating system was presented in 1975 by Ward et al. [190]. Some other

researchers also presented experimental results for different solar cooling systems in the late

1970s and early 1980s [150-152, 191, 192]. The first experimental study using an evacuated

tube collector for solar heating and cooling was presented by Ward et al. in 1979 and some

other researchers in later years [152, 193, 233]. In the 1980s many experimental studies were

presented with different designs and arrangements for solar cooling systems [154, 234-239].

In the 1990s studies were presented to show the performance of some existing systems and

some newly installed absorption and adsorption cooling systems in different locations

worldwide [158, 197, 198, 202, 220, 240-243]. In the 2000s experimental work was carried

out with all four types of solar cooling systems, hot and cold water storage, all stationary

collectors and both stand alone and fossil fuel heat energy back up [159, 163, 203, 207, 244-

249]. Some studies were carried out to analyse the performance of stratified storage tank use

in solar cooling systems [250, 251]. In the late 2000s and after 2010 experimental studies

were fewer in number as most of the studies were carried out as dynamic simulations [169,

201, 214, 252-262]. Some experimental studies were performed to verify and validate

different simulation results. [169, 204, 212, 213, 255, 263-266].

All the experimental studies were carried to evaluate the potential of solar cooling systems,

the economics, the parametric analysis, the efficiency of solar thermal collectors and cooling

systems for a specific location. Most of the systems were building integrated and to be used

for both heating and cooling purposes.

In Pakistan research on the application of solar energy cooling systems is limited. As

presented in Section 4.8.1, one solar assisted desiccant cooling experimental set up and the

TRNSYS simulation program is available at NED University Karachi (Pakistan). The

experimental results are limited to a humid area as the climate of Karachi is different from the

typical climate of the rest of the country [55, 218]. In first year of research, contacts were

made consistently with Dr. Khalid (the author of the above references) for equipment

specification and possible experimental work on solar cooling, but no answer was received.

115

The application of solar thermal systems for cooling is not setup or available for experimental

work at the present author’s university in Lahore.

In the early months of the second year of study, contact was made to try to establish the use

of experimental facilities at UAE University Al-Ain, but due to time limitations, the

experimental set up could not be arranged so a simulation option was selected as suitable

simulation program was available at the University of Manchester.

5.2.1 Limitations of Experimental Study

Experimental studies provide opportunity to identify cause and effect relations. One major

limitation of experimental study is that experiments are conducted in a particular environment

and results may be hard to generalise except field and natural experiments [267]. Another

limitation is that the environment is likely to affect the results, but perfect controlled

conditions are generally not possible. The experimental research may be able to tell that one

method, design, etc. is better than other, but may not able to explain the reason [268].

The experimental studies carried out on solar cooling have described, collector area, collector

type, collector tilt, collector yield and efficiency, storage type and volume, chiller type and

capacity, chiller COP, solar fraction , Solar COP and Electrical COP. The most common used

equipment is flat plate and evacuated tube collector, hot water storage and vapour absorption

chiller. Use of other collector types, cold water storage, stratified tank, other types of cooling

systems and parametric study of the systems is limited.

The studies of solar cooling systems mentioned in previous section have several limitations.

The duration of the studies was limited to few hours or days only in most of the

research and only few have been carried out for a season or year [159, 166, 198, 233,

234].

All the studies are based on components temperatures and the heat balance of the

whole solar thermal cooling system is not presented in details from heat input to the

heat rejection at each component or system level [212, 213, 245, 253, 264].

The room temperature set point and relative humidity of the building integrated

systems have not been described, in all of the studies. Only building conditioned area

is described no information is provided about the building construction materials,

windows, door, and orientation [201, 214, 220, 234, 240, 247, 269].

116

The experimental studies described the size and type of hot and cold water storage but

no detail is provided about heat loss /gain from these tank and average temperature

[193, 220, 234, 240, 241, 244, 247].

The solar energy collectors type, area and tilt is described but no detail is provided

about collector efficiency curve, flow control, pump capacity and effect of tilt on

collector energy yield [253, 260].

Most of the studies are without building integration and studies with integration have

no description about cooling coil and fan specification [201, 214, 220, 234, 240, 247,

269].

Most of the studies have solar fraction less than 50% and no study was carried out

about 100% solar fraction [159, 163, 203, 207, 214, 244-249, 260].

The experimental studies results do not enable us to predict performance of the proposed

system of the current research.

5.3 Simulation Study

Simulation is the production of a computer model for a system and it complements a physical

experiment. Simulations are numerical experiments and give system performance information

similar to physical experiments. These are relatively quick, inexpensive, and produce

information on the effect of design variables and system performance. Simulation can be used

for exploring new conditions not present in particular real world settings. Using cost data and

economic analysis, simulation results can be used to find economical systems. Simulation is a

powerful tool for research, development and design of systems [40, 270].

Computer modelling of thermal systems has many advantages. It is effective for parametric

studies and helps to investigate the effects of system variables on performance. A wide range

of climatic data can be used to determine the effects of weather on design. It eliminates the

expense of building prototypes, and provides complete understanding of system operations. It

makes it easy to optimise systems and output estimation [40, 141, 230].

The use of simulation for study of solar processes has been used since the late 1960s [40].

The first simulation study was carried out by Sheridan et al. in 1967 for solar water heaters

[271]. Many other researchers carried out simulation for different solar heating and solar

cooling systems in the late 1960s and early 1970s [146, 272-277]. The first simulation study

on design and optimised systems for residential heating and cooling by solar energy was

carried out in 1974 [278]. The first simulation study for hybrid solar air conditioning was

117

presented in 1976 [148]. In the 1980s many studies were carried out for simulation of solar

cooling systems and thermal performance and economics were analysed [155, 279]. In the

1990s feasibility studies, design optimisation, modelling and technical assessment of solar

cooling systems was simulated [199, 280, 281]. In the 2000s most of the simulation research

was carried out on solar cooling systems based on absorption, for which integrated systems

were built with different collectors, energy and carbon emission saving with solar cooling

systems [24, 162, 164, 205, 206, 282-286]. Some studies were carried out to compare

simulation results with actual installation data [287, 288]. After 2010 most of the simulation

studies were on design, performance, optimisation, and sensitivity analysis of solar cooling

systems and comparisons of different solar cooling systems [22, 23, 118, 178, 188, 204, 208-

211, 215, 265, 289-310].

Simulation studies are nearly as old as the experimental studies for solar thermal heating and

cooling systems[40]. After 2000, most of the literature available about solar thermal cooling

systems relates to simulation of solar cooling systems more than experimental studies. The

literature referred shows that TRNSYS is the most widely used simulation program.

The literature presented above described collector area and yield, collector tilt, collector flow,

storage tank type, heat loss, and capacity, pumps power and flow, type of cooling tower,

chiller type, capacity and COP, results validation and sensitivity analysis of the system,

building geometry, materials, heat gains and infiltration. Some other advantages of the

simulation studies include the comparison of different building materials, change of locations

worldwide, different cooling systems, collector’s type change, storage types, and other

parametric variation in the system operation.

The literature showed that solar cooling system simulation studies are flexible, detailed, and

can help to study different and maximum efficient system design for any location worldwide.

However, none of the studies in the literature cover the proposed system for Pakistan.

5.3.1 Limitations of Simulation Study

Simulations are powerful tools for system design and analysis but there are some limits in

simulation use. It is easy to make mistake by assuming incorrect values for system

parameters, and neglecting important factors. A high level of skill and scientific judgement is

required for useful results. Physical problems such as leaks, plugged or restricted pipes, scale

118

on heat exchangers, failure of controllers, poor installation of collectors and poor insulation

cannot easy modelled or accounted [40, 141].

Simulations programs deal only with thermal process but mechanical and other factors can

also affect the thermal performance of solar systems. There is no substitute to carefully

conducted experiments. A combination of simulation and practical experiment can lead to

better understanding of the system [141].

5.4 Solar Energy System Simulation Programs

Simulation programs should ideally offer computational speed, low cost and ease of use.

Over the years many programs have been developed for modelling and simulation of solar

energy systems. The most popular programs are WATSUN, Polysun, f-Chart, and TRNSYS.

TRNSYS is used for both solar energy and building energy systems so its details are

presented in Section 5.5.

5.4.1 WATSUN

Watsun simulates active solar systems and was developed by the Watsun simulation

laboratory at the University of Waterloo, Canada in the early 1970s. It models two kinds of

systems: solar water heating systems without storage and solar water heating with storage. It

combines collection, storage, and load information with the hourly weather data for a

location. Both hourly and monthly reports include data about solar radiation, energy

collected, load, and auxiliary energy. It can calculate long-term performance and economic

analysis to assess the costs and profits of the solar heating system [141, 230].

WATSUN uses TMY weather data with hourly values for global radiation on a horizontal

surface, dry bulb temperature, wind speed, and relative humidity. It uses a synthetic weather

generator WATGEN, which uses monthly average values and generates hourly data for a

given location. The user defines one input file called simulation data files and Watsun

generates three output files: a listing file, an hourly data file, and a monthly data file. The

systems that can be modelled include domestic hot water, pool systems, and industrial

process heating. The program models each component in the system, such as the collector,

pipes and tanks [141, 230].

The program was validated by developers against the TRNSYS program using several test

cases. The comparisons were very favourable; differences in predictions for yearly energy

delivered were less than 1.2% in all configurations tested [311].

119

WATSUN was not used for this research because it cannot simulate solar cooling systems

and building energy together at once.

5.4.2 Polysun

This program provides dynamic annual simulations of solar thermal systems and helps

optimisation of the system. The basic systems that can be simulated include: domestic hot

water, space heating, swimming pools, process heating, and cooling. It provides simulation

with a dynamic time step from 1 second to 1 hour. Worldwide meteorological data for 6,300

locations are available. Polysun has a claimed accuracy within 5-10% variation. It is a

program with economic viability and ecological balance, which includes emissions of the

eight most significant greenhouse gases. The emissions for a solar integrated system and the

conventional fuels can be compared [141, 230].

Polysun was not used for this research because it cannot simulate building integrated solar

thermal cooling systems and building energy.

5.4.3 f-Chart Method and Program

The f-chart method provides a mean for estimating the annual thermal performance of active

heating systems common in residential applications, using air, or liquid as a working fluid.

The f-chart is used to estimate the fraction of a total heating load that can be provided by a

solar system. The f-chart was developed by Klein et al. [147, 312] and Beckman et al. [313].

The primary design variable is the collector area and the secondary variables are the collector

type, storage capacity, fluid flow rates, and load and collector heat exchanger sizes. This

method correlates the results of many hundreds of thermal performances of solar heating

system simulations performed on TRNSYS, in which the simulation conditions were varied

with practical system designs. The resulting correlations give f, the fraction of the monthly

load supplied by solar energy as a function of two dimensionless parameters. One is related to

the ratio of collector losses to heating load, and the other to the ratio of absorbed solar

radiation to heat loads. The f-chart system was developed for three standard system

configurations: liquid and air systems for space and hot water heating, and systems for

service hot water only [141, 230].

120

The f-chart program was developed by the developers of TRNSYS and the model is intended

only for solar heating systems. This program can be used to estimate performance for all

stationary solar collectors, and one or two axis tracking concentrated collectors. This

program, however, does not provide the flexibility of detailed simulation and performance

investigation in the same way that TRNSYS does[230].

f-chart was not used for this research because it cannot simulate solar cooling systems and

building energy. Also it cannot be used for detailed simulation of solar thermal systems as it

is used to simulate fractions only.

5.5 Building Energy Simulation Programs

Building energy system simulation programs can calculate the behaviour of building thermal

control systems and the resultant impact on energy use, peak energy demand, equipment

sizing and occupant comfort as well as providing performance details. An energy efficient

and effective design, detailed analysis of building energy demand, energy savings, and supply

technologies can be tested and optimised by such programs. Many building energy simulation

programs for evaluation of energy efficiency, renewable energy, and sustainability are

developed. Here the popular programs that are commonly used for simulation of energy

systems in buildings are the only ones discussed.

5.5.1 Energy Plus

Energy plus is an energy analysis and thermal load simulation program. Energy Plus is

derived from both the Building Loads Analysis and System Thermodynamics (BLAST) and

DOE–2 programs and was released in 1996. BLAST and DOE–2 both were developed for

building energy and load simulation after the energy crisis of the early 1970s, when it was

realised that building energy consumption is a major component of American energy

consumption. The programs were used by design-engineers and architects to design and size

heating, ventilation and air-conditioning (HVAC) equipment and for equipment life cycling

cost analyses and energy performance optimisation. Energy Plus comprises completely new,

modular, structured code written in Fortran 90 [314, 315].

Using this program, the user can define building envelopes, a building’s physical make-up,

and related mechanical systems. It can calculate heating and cooling loads necessary to

maintain thermal control set points, conditions throughout a secondary HVAC system, coil

121

loads, and energy consumption of equipment as well as verifying that simulation is in

accordance with actual building operation. Some of the main features of the Energy Plus

program are [314, 315].

Sub-hourly, user-definable time steps.

Text based weather input and output files.

Heat balance based solutions.

Atmospheric pollution calculations.

Energy Plus is used to simulate many buildings and HVAC design options directly or

indirectly through links to other programs to calculate thermal loads and energy consumption

on a specific design day or for a certain period [314, 315].

Many researchers have used Energy Plus for modelling and simulation of building energy

performance and improving building energy models [316-324].

The most important limitation of Energy Plus for the present research is that it lacks solar

collector models although it does have models for absorption chillers and storage tanks. Users

can create their own collector model through codes but it might be a lot of work to validate it

and link it correctly to the main program.

5.5.2 Integrated Environment Solutions (IES) Virtual Environment (VE)

IES-VE is used for building and system design. It creates a 3D building model with data such

as materials, constructions, internal heat gains, systems, and controls. IES-VE is used to build

a model and collects information on building geometry, occupancy, climate and installed

equipment [325].

IES-VE is used to design low energy and high performance systems. Energy and carbon

analyses are carried out under the tool Apache Simulation. This is a central simulation

processer that assesses thermal performance, simulates solar gain on surfaces, surface

temperatures, and radiant exchanges. Building and room-level annual, monthly, hourly, sub-

hourly and up to one minute time step analysis is possible. It contains an extensive database

of global weather. It calculates sensible and latent gains from lights, natural ventilation,

mechanical ventilation and infiltration [325].

122

In IES-VE three tools are used for HVAC calculations; Apache HVAC, Apache Loads, and

Apache Calc. Apache HVAC simulate system prototypes and models and the system library

contains a variety of model systems. Apache Loads simulates heat loss and gains, heating and

cooling loads using the ASHRAE heat balance method. It can simulate the cooling load for

buildings and zones and peak cooling loads. Apache calc. simulates heat gains to calculate

the cooling load for a selected day and month with chartered institution of building services

engineer (CIBSE) guidance. It can simulate climate, daylight, natural resource availability,

energy and carbon with low/zero carbon technologies as shown in Figure 5-1 [325].

Figure 5-1: Building model and low zero carbon technologies analysis [325]

Many researchers have used the IES-VE tool to simulate building design, construction

materials, daylight characteristics, solar shading, low energy buildings, and occupant’s

behaviour [326-335]. Like Energy Plus, the main problem with IES for this research is its

lack of solar energy system models. Also, the user cannot create any model and add it to the

IES. 5.5.3 TRNSYS

TRaNsient SYstem Simulation (TRNSYS) is a widely used, thermal process dynamic

simulation program. It was originally developed for solar energy applications, and can now

be used for a wider variety of thermal processes. TRNSYS was developed at the University

of Wisconsin by the members of the solar energy laboratory and the first version was released

in 1977 [40]. TRNSYS can be used for simulation of solar PV, solar heating and cooling and

building energy. It has the capability to interconnect system components in any desired

manner, solving differential equations and information output. Given OUTPUT from one

component is used as an INPUT to other components [336]. Each component has a unique

TYPE number, and components from the standard library of TRNSYS were validated. In the

123

volume4- Mathematical reference of TRNSYS, reference to validation of each TYPE is

included [337]. The components in TRNSYS include solar collectors, heating and cooling

loads, thermostats, absorption chillers, fans, hot water storage, heat pumps and many more.

TRNSYS provides an error of less than 10% between simulation results and actual operating

systems; details of TRNSYS accuracy are described in Section 5.5.4. The simulation time

step can be as short as 1/1000 of an hour (3.6s) and can be helpful for detailed instantaneous

micro analysis. The short time step (less than one hour) can be useful as it may be necessary

for computational stability in the simulation and it can be used to simulate the dynamic

response of the systems that respond faster in seconds or minutes [147, 312, 313, 338] .

In addition to the main TRNSYS components, an engineering consulting company

specialising in the modelling and analysis of innovative energy systems and buildings,

Thermal Energy System Specialists (TESS), developed libraries of components for use with

TRNSYS. The TESS library includes more than 500 TRNSYS components [230].

Numerous applications for the program are mentioned in the literature and described in

Section 5.3. Some typical examples are for the modelling of a thermosiphon system [339,

340], modelling and performance evaluation of solar DHW systems [341], investigation of

the effect of load profile [342], modelling of industrial process heat applications [343] and

modelling and simulation of a lithium bromide absorption system [284].

5.5.3.1 Interface

TRNSYS operates in a graphic interface environment called Simulation Studio. In this

environment, icons of ready-made components are dragged and dropped from a list and

connected together according to the real system configuration [230]. The standard library

includes approximately 150 models ranging from photovoltaic panels, multizone buildings,

solar collectors, storage tanks, weather data processors and HVAC equipment [344]. The

interface is shown in Figure 5-2.

Each component of the system requires a set of inputs (from other components or data files)

and a set of constants parameters, specified by the user. Each component has its own set of

output parameters, which can be saved in a file, plotted, or used as input for other

components.

124

Figure 5-2: Model diagram in TRNSYS simulation studio view [344]

Output values can be seen on an online plotter as the simulation progresses. A typical output

plot is shown in Figure 5-3. The project area also contains a weather processing component,

printers, and plotters through which output data are viewed or saved to data files [230, 344].

125

Figure 5-3: TRNSYS simulation result plot overview [344]

TRNSYS has some built-in and supported tools which are described here.

5.5.3.2 TRNBuild

In version 17, TRNSYS includes Trnsys3d, a plug-in for Sketch Up that allows multizone

buildings to be drawn and imports the geometry directly from the Sketch Up interface into

TRNSYS.

“TRNBuild is an interface for creating and editing all of the non-geometry information

required by the TRNSYS building model. It allows extensive flexibility in editing wall and

layer material properties, creating ventilation and infiltration profiles, adding gains, defining

radiant ceilings and floors, and positioning occupants for comfort calculations” [344]. A

TRNBuild interface for the model materials is shown in Figures 5-4 and 5-5.

126

Figure 5-4: TRNBuild wall and windows types and area selection [344]

Figure 5-5: TRNBuild wall type manager with construction materials [344]

5.5.3.3 Weather Data

TRNSYS contains a variety of weather data with different weather data types. The main

types available are TMY, TMY2 and TMY3 (for US), EPW, CWEC, IWEC and Meteonorm

for all the major cities of the world. A detail of these weather types is presented in section

5.6.

In TRNYS for Pakistan TMY2 weather data is available for the five major cities Karachi,

Lahore, Peshawar, Multan, and Quetta. The climatic conditions are different for all the cities.

127

A detailed monthly average minimum, maximum dry bulb temperature and monthly average

humidity ratio is shown in Appendix B and discussed in the weather data Section 5.6.

5.5.4 TRNSYS Validity

Mitchell et al. [345] compared the measured and TRNSYS simulated performance of solar

energy systems for CSU house–I, for three different time periods. It found that simulated

energy data was in agreement with measured data. The agreement was generally within 2ºC.

It has also been recommended that simulation models can be used to predict long term system

performance. For different components the difference between measured and TRNSYS

simulated data was between 0.7% and 7% [40]. Beckman et al. [346] described TRNSYS as

the most complete solar energy system modelling and simulation program. Kalogirou et al.

[339] performed TRNSYS modelling and validation of a thermosiphon solar water system. It

was found that the mean deviation between TRNSYS predicted and actual experimental

values was 4.7%.

Monfet et al. [347] performed TRNSYS simulation for large heating and cooling plants and

calibration with monitored data. It was found that there was a good agreement between the

simulated and monitored data with less than 8% variation. Hang et al. [348] conducted a

TRNSYS study of the optimisation method for a solar assisted double effect absorption

system installed in USA and the results showed that the actual system result was in excellent

agreement with the physical model in TRNSYS. Ayompe et al. [265] validated the TRSNSY

model for a forced solar water heating system with a flat plate and evacuated tube collectors

for three representative days of weather conditions in Ireland. The results showed that the

model overestimated the heat collected by 7.4% and 12.4% for a flat plate and the evacuated

tube collectors respectively. Martinez et al. [204] investigated the TRNSYS design and test

results for a low capacity solar cooling system in Spain. It was observed that the level of

agreement between experimental and simulated values was high. The difference between

experimental and simulation parameters was between 2% and 5.50%.

Ssembatya et al. [210] carried out TRNSYS simulation studies on the performance of solar

cooling systems in UAE conditions. It was observed that, overall, the trends for experimental

values were close to TRNSYS simulation. Almeida et al. [337, 349] performed dynamic

testing of systems using TRNSYS. It was observed that comparison of simulation and

measured system energy yield showed very good agreement with a +/-3 % variation. Banister

et al. [350] validated a multi-mode single tank TRNSYS model with experimental data. The

128

agreement between simulation and experiment was found to be very strong, with typical

differences in tank temperatures of less than 1ºC. He et al. [351] studied low temperature

solar thermal cooling system application in China. The comparison between four days of

TRNSYS simulated and measured data for heat gain using a collector and system COP,

showed that the measured data was 7% and 5% higher than simulated data respectively. Bava

et al. [352] carried out a TRNSYS simulation of a solar collector array with two types of solar

collectors. It was found that simulated energy transferred in one year from collectors was

only 1.2% higher than the measured energy amount. The simulated collector’s outlet

temperatures were in good agreement with measured ones. Eicker et al. [353] simulated heat

rejection and primary energy efficiency for solar driven absorption cooling systems. Palacin

et al. [354] also observed the variation to be in the range of 1-7%. The comparison between

the simulated and experimental systems showed a variation of between 1% and 4%.

A summary of the above described work is shown is Table 5-1.

Table 5-1: Comparison of differences between experimental and TRNSYS simulation data

Author Parameters

Difference between

Experimental and TRNSYS simulation (%)

Mitchel et al Collected and Delivered energy, Auxiliary energy, Air heated heat flow 0-7.0

Kalogirou et al Hot water tank initial and final temperatures 4.7

Monfet et al Chilled water temperature, Condenser water temperature, Pumps, Chiller

and cooling tower electricity consumption, COP of chiller, 2.4-4.8

Ayompe et al Heat energy collected 7.4-12.4

Martinez et al Collector and storage tank outlet temperature 2.0-5.5

Almedia et al Energy yield, (+/-3.0)

He et al Collector yield, Total cooling energy, Auxiliary energy demand, Collector efficiency, System COP, Average room temperature and Solar fraction

5.0-7.0

Bava et al Collector energy collected 1.2

Eicker et al Collector energy, Evaporator and generator power, 1-4

Palacin et al Collector energy, Evaporator and generator energy, Electrical energy 1-7

The above Table 5-1 shows that the variation in TRNSYS results from measured data for

solar thermal systems is less than 10%. The TRNSYS simulation proved reasonably accurate

for solar thermal systems modelling. T. He at el.’s work was on solar thermal cooling systems

similar to those in this research. The comparison was for four days of data and it can be

expected that the annual average comparison will show the variation to be lower. As Bava et

al.[352] observed that the annual average variation between simulated and measured data was

1.2%, whereas the seasonal variation was higher at +7% (Jun-Dec) and -8% (Jan-May).

129

Antoni et al. [355] validated the TRNSYS simulation solar combi+ system model with

measured data. The simulated results for storage fluid temperatures and heat transfer rates

were in good agreement with a difference of less than 2%. Keizer et al. [356] used TRNSYS

as a tool for long term fault detection in solar thermal systems. The average variation between

simulated and measured solar yield was up to 5 %.

5.6 Meteorological Data for Simulation Program

Weather conditions and loads are factors that affect cooling system performance. Loads are

dependent on weather for heating and cooling in buildings, and also other factors which are

not related to weather. Meteorological data, including ambient temperature, solar radiation

and wind speed, wind direction and relative humidity are measured at the weather recording

station around the world [357, 358].

5.6.1 Weather Data Types

For simulation of solar cooling systems, weather data with the important parameters and

derived data is used. All simulations in this research are performed with real meteorological

data and it is important to select a suitable data set [357]. The data set type depends upon the

simulation program to be used. To compare the full range of system performance, it is best to

use a full year of data or a full season of data if the process is seasonal [358]. Klein [312]

developed the concept of a design year for first time, which helped to create different types of

weather data for building energy calculations.

The available data sets differ according to the process by which they are compiled, the

amount and type of data presented. A brief description of some important weather data sets

are presented here.

5.6.1.1 Test Reference Year (TRY)

The earliest hourly weather data set specifically designed for use in building energy

simulation is the Test Reference Year (TRY) derived from measured data at the National

Climatic Data Centre (NCDC). The data was available for 60 locations in the US for the

period from 1948-1975. The limitations of the TRY were the exclusion of solar radiation and

extreme high or low temperatures [358].

130

5.6.1.2 Typical Metrological Year (TMY)

Hall et al.’s [359] detailed study of 23 years of data for solar radiation at 26 stations in the US

and resulted in the generation of typical meteorological year data for those and others

locations. This TMY data was used to simulate heating systems and added data which was

not available with TRY [357].

A TMY is a data set for hourly values of meteorological elements and solar radiation for a

period of one year. It consists of typical months of real weather data selected from different

years and combined to form a data set of a year of typical weather. It provides hourly data for

meteorological elements that contribute to performance comparisons for different types for

single or multiple locations. It is not a good indicator for predicting the system parameters for

the next one or five years as selected data is data for a typical month. It is useful to represent

typical conditions judged for a longer period such as 30 years. It is not useful to design

systems and their components to fulfil extreme weather conditions for a location as it

represents typical conditions instead of extreme conditions. A typical meteorological year is

classified into three categories [360, 361].

TMY: This consists of data sets derived from the NCDC of National Oceanic and

Atmospheric Administration (NOAA) with measured data for 26 US locations

from years 1952-1975.

TMY 2: This consists of data sets derived from years 1961-1990, from the

National Solar Radiation Data Base (NSRDB) of US National Renewable Energy

Laboratory for 239 stations.

TMY3: This consists of data sets derived from years 1991-2005, from the NSRDB

of the US National Renewable Energy Laboratory for 1,020 stations worldwide.

The TMY, TMY2 and TMY3 data sets cannot be used interchangeably due to differences in

time (local versus solar), formats, data types and units [357, 360, 361]. Schmitt et al. [362]

have developed algorithms to generate weather data for extreme conditions.

5.6.1.3 International Weather for Energy Calculations (IWEC):

IWEC was generated as a result of the ASHRAE research project RP-1015 for the ASHRAE

technical committee. The purpose was to represent more typical weather than a single

representative year could give. These files contain typical weather data suitable for use in

131

building energy simulation software for 227 locations outside Canada and the US. Data for

all locations is available in an energy plus weather format [358, 363, 364].

All files of IWEC data are derived from 18 years (1982-1999) of DATASAV3 hourly

weather data originally archived in the US, at the National Climatic Data Centre (NCDC).

The solar radiation data is estimated on an hourly basis from earth-sun geometry and hourly

weather elements particularly cloud amount data [311, 363].

Like TMY files the IWEC files are typical years that normally avoid extreme conditions.

Sizing of heating, ventilation, and air conditioning systems that require the consideration of

extreme conditions cannot use the IWEC files.

5.6.1.4 Energy Plus Weather (EPW):

Energy plus weather (EPW) data is generated by the United States Department of Energy.

EPW is compiled from TMY, TMY2, TMY3, and other international data sets. This format

data is now available on the Energy Plus website for more than 2,100 locations; 1,042

locations in the US, 71 in Canada and more than 1,000 locations in another 100 countries

throughout the world [363].

The EPW format has generalised weather data for use in energy simulation programs. The

data includes dry bulb, dew point temperature, relative humidity, station pressure, solar

radiation (global, extra-terrestrial, horizontal, direct and diffuse) illuminance, wind direction

and speed and cloud cover [363].

Each EPW file is named using an ISO standard three-letter country code, followed by the

location name, World Meteorological Organization (WMO) and the source format such as

California Climate Zones 2 (CTZ2), Canadian Weather for Energy Calculations (CWEC)

[363].

There are three files associated with each location: energy plus weather files (EPW), a

summary report on data (STAT) and a compressed file (zip) which contains the EPW, STAT

and Design Day Data (DDY) files for the location [363].

5.6.2 Pakistan Weather Data

Official weather data for Pakistan is recorded and maintained by the Pakistan Meteorological

Department (PMD). It is a scientific and public service department managed by the Ministry

132

of Defence to provide meteorological data services. Data available is not in any of the

standards described in the previous section, which can be used for building energy simulation

programs. The available data is for a few weather stations and contains ambient temperature,

wind speed, and humidity only. NASA SSE provides complete satellite data for any location

across the world with parameters for solar energy calculations. In Appendices A and B, the

annual and monthly daily mean maximum temperature, humidity ratio and solar insolation on

a horizontal surface for Pakistan district cities is derived from NASA surface meteorology

and solar energy (SSE).

In a solar cooling simulation program, two important weather data sets used are energy plus

weather (EPW) and typical meteorological year (TMY). For Pakistan the details of

availability of these two types of data set are described here.

5.6.2.1 EPW Weather Data for Pakistan

The available EPW data is only for one city - Karachi. Karachi is a coastal city with a hot and

humid climate. The population density in coastal areas is much lower than in other climatic

regions apart from Karachi city, which is the most populous city in Pakistan. For this research

Lahore city has been selected as its climate represents typical conditions in the country.

Lahore is the second most populous city in Pakistan and more than 50% of the population of

Pakistan lives in climatic conditions similar to those in Lahore [68]. For Lahore EPW data is

not available but it is available for the nearest Indian city, Amritsar, which is about 40

kilometres away from Lahore with similar climatic conditions. Comparison from the WMO

provided 30 years of typical weather data for both cities and is shown in Figure 5-6.

Figure 5-6: Climatic comparison between Lahore and Amritsar [100]

0

10

20

30

40

50

JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC

TE

MP

ER

AT

UR

E (

ᵒC)

LAHORE MEAN MAXIMUM LAHORE MEAN MINIMUM

AMRITSAR MEAN MAXIMUM AMRITSAR MEAN MINIMUM

133

Figure 5-6 shows that the maximum average temperature is similar for both cities (blue and

green). This is important as this research is based on cooling systems, required in hot climatic

conditions during the summer season from April to September.

The EPW data for Amritsar, India is available at the energy plus weather data official

website. The data is obtained from the site and read through the program Climate Consultant

5.5 [365]. A comparison between EPW and WMO data is carried out for Amritsar. This

comparison clearly shows a difference of 4-6ºC on average maximum and minimum

temperatures as shown in Figure 5-7. The discrepancy implies that EPW data for Amritsar

may be unsuitable for Lahore. A detailed study would be required to explain the discrepancy

and thereby, perhaps, show whether the Amritsar EPW data is suitable for the present

research.

Figure 5-7: Amritsar daily mean temperature (EPW vs WMO) [100, 363]

5.6.2.2 TMY2 Data for Pakistan

As there is variation in EPW and WMO typical weather data for Amritsar, some other data

types for Pakistan cities was sought. It was discovered that TRNSYS contains TMY2 weather

data files for five main cities in Pakistan along with 1,036 cities worldwide. This weather

data is provided by METEONORM [344]. The data is for the years 1961-90 and was

obtained from about 7,400 stations worldwide. This data contains mean air temperature,

humidity, sun shine duration and solar radiation [358].

0

5

10

15

20

25

30

35

40

45

JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC

TE

MP

ER

AT

UR

E (

ᵒC)

MEAN MAXIMUM(WMO) MEAN MINIMUM(WMO)

MEAN MAXIMUM(EPW) MEAN MINIMUM(EPW)

134

For Lahore, a comparison between WMO data and TMY2 data is carried out and it shows a

minor (less than 1ºC on average) variation in the data values for both sets. This comparison is

shown in Figure 5-8. The good agreement between the two data sets gives confidence that the

TMY2 data can be used to perform valid simulation.

Figure 5-8: Lahore temperature comparison (WMO vs TMY2) [100, 344]

A comparison of TRNSYS available TMY2 data of global horizontal radiation, mean

maximum dry bulb temperature and relative humidity for the five major cities was carried out

to analyse the climatic conditions in these cities and is shown in Figures 5-9, 5-10, and 5-11.

Figure 5-9: Pakistan’s cities maximum average temperature from TMY2[366]

0

5

10

15

20

25

30

35

40

45

JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC

TE

ME

PR

AT

UR

E (

ᵒC)

MEAN MINIMUM(TMY) MEAN MAXIMUM(TMY)

MEAN MINIMUM(WMO) MEAN MAXIMUM(WMO)

0

5

10

15

20

25

30

35

40

45

JAN FEB MAR APR MAY JUNE JUL AUG SEP OCT NOV DEC

TE

MP

ER

AT

UR

E(°

C)

LAHORE MULTAN KARACHI QUETTA PESHAWAR

135

Figure 5-10: Pakistan’s cities average relative humidity from TMY2 [366]

Figure 5-11: Pakistan’s cities average global horizontal radiation from TMY2[366]

The analysis of the data shows that Lahore, Multan, and Peshawar have very similar climatic

conditions. So data for Lahore is suitable for use as typical weather data for Pakistan.

Quetta’s climate is different, characterised by low temperatures and humidity both in summer

and winter. Karachi’s climate is not typical for Pakistan due to high humidity in April, May,

and June. Karachi also has low solar radiation, is the lowest of all the cities in summer and

the highest in winter which is not suitable to represent typical conditions for solar cooling

applications. Also, the annual average solar insolation for Quetta and Karachi is higher than

other cities as shown in Appendix A.

0

10

20

30

40

50

60

70

80

90

JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC

RE

LA

TIV

E H

UM

IDIT

Y (

%)

LAHORE MULTAN KARACHI QUETTA PESHAWAR

0

50

100

150

200

250

300

350

JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC

GL

OB

AL

HO

RIZ

ON

TA

L R

AD

IAT

ION

(w

/m2

)

LAHORE MULTAN KARACHI QUETTA PESHAWAR

136

5.7 Conclusion

5.7.1 Methodology

To evaluate the feasibility and performance of a solar cooling system widely used techniques

are experimental evaluation or the dynamic simulation. Experiments play central role in

scientific studies and are considered a direct relationship with real systems. Field experiments

have advantage over laboratory experiments as they take place in natural conditions. More

than 1000 solar cooling systems are installed worldwide and most are in European countries.

First experimental study of solar cooling system was carried out in 1962 and after mid 2000s

the number of experimental studies is limited compared to dynamic simulation studies. The

history of simulation studies is as old as experimental studies. For this research an

experimental system is not available in Lahore, so the adopted methodology will be dynamic

simulation.

From among the available dynamic simulation programs, TRNSYS was selected as the most

suitable for this research. It is a comprehensive program used for simulation of both solar

energy and building energy systems. A 3D building model can easily be created using

Sketchup and building materials and geometry (walls and windows) can be assigned in

Trnsys3d. It simulates both solar PV and thermal systems in details. It can integrate buildings

with solar and cooling components and contains more than 500 models of different

components. The TRNSYS library contains a variety of components for detailed and real

system simulations. These component’s parameters are from tested data components from

Thermal Energy Systems Specialists (TESS). The outputs from each component can be

plotted both in graphical and excel data formats. This can be easy to use for heat balance and

other calculations. TRNSYS supports all types of weather data formats and it contains

weather data for all main cities in the world. For Pakistan, TMY2 data is available for five

cities.

The literature presented for use of different simulation programs shows that TRNSYS is the

most widely used for solar energy cooling (also heating) system worldwide. The literature

available for use of other programs is limited. Many researchers have validated TRNSYS

simulation results with the experimental results and established that TRNSYS results are in

good agreement with experiments. The accuracy of TRNSYS is high, within 10% variation

from experimental results. For solar energy collected, chilled water temperature, chiller COP

and storage tank temperature simulations TRNSYS results are 4%, 3%, 3%, and 3.5%

137

different from experimental data on average. For solar cooling system simulation this

variation is less than 5% on average, which means TRNSYS can be used to perform solar

cooling system with confidence.

The sequence of the methodology used for this research will begin with the creation of

building model for part of a typical single family house in Pakistan. The building model will

be imported in TRNSYS and will be assigned typical materials, heat gains, and inside

operational conditions to calculate the cooling load. According to the cooling load a solar

thermal cooling system will be designed and connected to the building model to maintain the

desired set point during the peak summer time. An important system performance criterion is

that it will be designed to meet the cooling load without an auxiliary energy source, other

than electricity for pumps; fan etc. the system design will be optimised by trial and error to

minimise the component sizes while maintaining the desired performance. The final results

will be drawn for the optimised system and validated by previous published results. A

parametric analysis will be carried out in TRNSYS for the most important parameters for the

solar thermal cooling system and sensitivity of the system performance to these parameters

will be examined. Finally, overall conclusions will be drawn.

5.7.2 Weather Data

Weather data is a key input for solar cooling systems and building energy simulation as

system design and operation depends on climatic conditions and variation. For simulation of

solar energy systems different weather data types have been developed from the measured

data across the world. The most important data types are TMY, EPW, and IWEC.

EPW weather data is comprehensive data derived from various other weather data set.

Unfortunately, for Pakistan this type data is available only for Karachi, which is not

representative of the typical climate in Pakistan due to high humidity and less solar insolation

during the summer season.

Lahore is the city of most interest for this research, as its climate is typical of where more

than 50% of the population lives. EPW weather data is available for the Indian city of

Amritsar, which has a similar climate to that of Lahore. Therefore, Amritsar data was

selected and analysed but there is difference of 4-6ºC on average in the temperatures for

138

Amritsar between EPW and WMO data. This difference makes it unsuitable to use this

(Amritsar) EPW weather data as an input for simulation without a detailed study to explain

the discrepancy.

TMY2 data is useful for long term predictions of solar and building energy systems.TMY2

data for five main cities in Pakistan are available in TRNSYS. The available TMY2 data

represent climate zones for all areas of the country. The climatic conditions of Karachi and

Quetta are different and limited to these areas only although the solar energy availability of

these cities is higher than other cities.

Lahore, Multan and Peshawar data show that these cities have about similar climatic

conditions. The mean daily temperatures show that during the summer season from April to

September, these areas require cooling systems to maintain comfort during times of peak

temperature. The calculations and simulation of results will, therefore, be performed using

the TMY2 weather data for Lahore, as typical for Pakistan.

139

Chapter 6: Building Model and Simulation

6.1 Introduction

In Pakistan most areas experience hot summer seasons with high ambient temperatures as

described in Section 3.3. In cities during the summer, people spend more time indoors so

buildings should be made comfortable for hot weather conditions. Most residential buildings

are 1-2 storeys, with fired bricks walls and flat reinforced concrete (RC) slab roofs [97, 367]

and most of the houses have 2-4 rooms [368]. These RC roofs retain heat absorbed in the

daytime and emit it during the night affecting comfort in buildings, when all family members

are in. This is worst for congested areas and houses with cooling systems (fans, coolers, and

air conditioners) combined with poor ventilation, making sleeping difficult, affecting

people’s comfort and health [112]. Rooms are uncomfortable during the peak summer season

(also in winter) due to many hours of electricity cuts (gas in winter) although cooling (also

heating) systems are in place [112].

For simulation of building cooling load in the climatic conditions of Lahore, a simple two-

zone building was selected as TRNSYS ‘TYPE 56’ required a minimum of two thermal

zones. This model was based on a common, typical construction design and materials of

single storey houses in Lahore, Punjab (the largest area with more than 50% of the total

population) [67] and other areas[97].

The model used in the research is an actual existing building with current building materials

and dimensions. The details of typical construction materials used in different cities of

Pakistan are described in Appendix C [97]. The selected single storey model house was

similar to that selected by the UN energy efficient housing project in Pakistan, both in terms

of construction material and size as described in Section 3.8. Typical single storey houses in

urban and rural Punjab are shown in Figures 6-1 and 6-2.

140

Figure 6-1: Typical single storey house in urban Punjab[369]

Figure 6-2: Typical single storey house in rural Punjab [370]

6.2 Building Model

TRNSYS supported Sketchup (Google Sketchup) was used to model an existing building

near Lahore airport and the location is shown in Figure 6-3. It’s a newly built (2010) house

with a concrete roof and double bricks walls. The model used 3D building geometry for a

space to be used for solar thermal cooling simulation. The model created was imported to

TRNSYS for integration with solar thermal cooling system simulation and analysis. The

Trnsys3d plug-in was used to add the geometric information into the building model, which

was necessary for detailed energy calculations. Sketchup zones are different fromTrnsys3d

zones. In Sketchup, interior walls separate one zone from another. In Trnsys3d zones are

divided by the dynamic flow of energy which is indicated by infiltration, shades, solar gain,

and other energy-based parameters. The designed model is a two-zone building with zones

separated by a wall in Sketchup and by different energy flow in Trnsys3d.

141

Figure 6-3: Model building location

The selected building consisted of two room/zones (rooms are representing zones) having the

same volume, door and windows areas with doors and windows at different locations in both.

Room1 has one window and one door, whereas Room 2 had two doors and one window. This

is a typical construction with a drawing room with a door on the street side and courtyard side

and a bedroom with one door on the courtyard side. The average room size in urban and rural

areas is from 20-70m3 with 1-2 windows [371] and the model used these measurements for

analysis. A two zone simple model drawn in Sketchup with Trnsys-3d plug-in was created

and its description and view are shown in Figures 6-4 and 6-5.

Some others parameters are as follows:

Floor area = 14m2

Zone volume (V) = 42 m3

Location: 31.54° N, 74.40° E,

Proportion of window area in external wall = 10%

Window area: 1.5m2

142

Figure 6-4: Trnsys-3d two zone (room) model back and top views

Figure 6-5: Trnsys-3d two zone (room) model front view

143

6.3 TRNSYS Simulation Studio

The 3D building model created in Sketchup was imported to the TRNSYS simulation studio.

The simulation studio is the main simulation engine of TRNSYS with graphical plotting and

output with spreadsheet facilities. TRNSYS components are called ‘Types’ and each Type is

assigned a number; for the building model, ‘Type56’ was used. The systematic import of 3D

building models to simulation studio is shown in Figures 6-6 and 6-7.

Figure 6-6: Import of the Trnsys3d model into the simulation studio step-1

Figure 6-7: Import of the Trnsys3d model into the simulation studio step-2

144

In the above Figures 6-6 and 6-7, the building rotation was set to a default value of zero and

the location was set to Lahore, Pakistan by selecting TMY2 weather data for Lahore available

in TRNSYS weather data.

Figure 6-8: After import of Trnsys3d model, the final window in the simulation studio

The screen after the import of the building model and components are shown in Figure 6-8.

During the import, TRNSYS calculates the volume of zones, number of surfaces, view factor

to sky calculation, sorting of zones/air nodes and surfaces. It generates a *.BUI file and opens

it in TRNBuild and *_b17_IDF (this file can be used to go back from TRNBuild to Trnsys3d

GUI) with the same order of zones and surface numbers. All Building-related materials,

geometry and thermal properties are viewed and modified in the TRNSYS plug-in called

TRNBuild. TRNBuild opens independently or by right clicking on building Type 56 using

‘edit building’.

6.3.1 The Building’s Initial Parameters

In TRNBuild, building materials, thermal calculation parameters and the model construction,

with details of walls and windows for zones, are assigned according to selected standards. In

TRNBuild American/ASHRAE, French, German, Japanese, Spanish and TESS standard

145

libraries are available and American/ASHRAE is selected as a default standard. The initial

values for building materials, thermal comfort and other parameters were used from

TRNBuild pre-defined ‘default’ values selected within the American/ASHRAE standard. The

details of some default and initial parameters used in the simulation are described here.

In TRNBuild the settings menu is used to set up some general settings for the simulation.

These basics settings include data files location, selected standard libraries, import and export

model applications, TRNSYS input data files, and some other parameters required for the

TRNSYS program applications for simulation.

The other important building settings in TRNBuild are the project settings which include

building orientations and miscellaneous settings. The orientations menu shows the

orientation of building surfaces. Each orientation is described by direction (N, S, E, W or H),

Azimuth angle of orientation (0-South, 90-West, 180-North and 270-South) and slope of

orientation (0-Horizontal, 90-Vertical and 180- Facing down). When the initial building

rotation is set (shown in Figure 6-7) the orientations are assigned to the model surfaces by the

TRSNYS program.

The miscellaneous settings include properties, inputs and outputs. The properties are material

thermal properties; some are general properties and others are parameters for internal

calculation of heat transfer co-efficients as shown in Figure 6-9. Heat transfer co-efficients

depend heavily on the temperature difference between surface and fluid and direction of heat

flow. TRNBuild automatically selects ‘default’ values for properties during the model

import.

For thermal calculations, the general values used are: air density (1.204kg/m3), air specific

heat (1.012kJ/kg.K) and air pressure (101325Pa), water vaporisation heat (2454kJ/kg), Stefan

Boltzmann constant (5.67e-8

W/m2K

4) and approximate average surface temperature

(293.15K).

146

Figure 6-9: Parameters for heat transfer co-efficients

The miscellaneous settings include inputs and outputs other than properties. TRNBuild

calculates and creates standard inputs during the Trnsys3d model import. The inputs can be

added and removed unless related to building description. Most of the inputs used are from

weather data and building location as shown in Figure 6-10.

Figure 6-10: Standard and user defined inputs

Outputs are the last step in the building description and the desired parameters are defined to

be plotted from the simulation results. Outputs can be added and deleted as required

simulation result parameters for analysis. The Outputs window for Type56 in TRNBuild is

shown in Figure 6-11. The default outputs are zone air temperature and sensible heat

(positive for cooling and negative for heating).

147

Figure 6-11: Building outputs

6.3.2 Zones’ Thermal and Material Properties

The zones window contains all information for thermal zones in the building model. A

thermal zone may have more than one air node. The air nodes can move within a zone for

multi air nodes zones. The Zones window describes an air node’s regime data, walls,

windows and optional building equipment and operation specifications including infiltration,

ventilation, cooling, heating, gains and comfort and geometry modes as shown in Figure 6-

12.

Regime Data

Regime data includes volume of air node, total thermal capacitance kJ/K (standard is 1.2 ×

zone volume), initial temperature, initial relative humidity and humidity model for air nodes.

The zone initial temperature and initial relative humidity used were 20°C and 50%

respectively. In the case of the building model, TRNBuild takes a zero value for capacitance

as its default. For initial simulation all default parameters are used.

Walls

For the building model, TRNBuild calculates parameters and assigns materials including wall

type, wall area, wall category (external, internal, adjacent and boundary) surface number and

148

wall gain. TRNBuild contains a library according to the selected standard for walls and a new

wall type can be defined. It also calculates total wall thickness and standard u-value

according to wall material. The summary of walls is shown in Figure 6-12.

Figure 6-12: Room1 volume, surface and areas calculated by TRNSYS

Similarly, for wall layer, a standard library is available and the user can define a new layer.

New layer definition has four category options that are: massive (normal construction), mass

less (to neglect thermal mass), active (concrete core cooling and heating) and chilled ceiling

(chilled ceiling panel).

In addition to wall constructions the co-efficient of solar absorptance is also required as

shown in Figure 6-13. It depends upon properties of wall finish and the standard value for

each surface is available in the library. TRNBuild uses default values automatically and

changes are possible if required. Finally, the convective heat transfer co-efficient of the wall

required and standard vales are: inside - 11kJ/h m2

K and outside - 64kJ/h m2

K.

149

Figure 6-13: Properties of material assigned to external roofs

The properties of materials used for an external roof are shown in Figure 6-13. The detailed

description of other wall types and materials is as follows. By default TRNBuild assigned

standard materials to the adjacent wall (partition between zones) front/inside with three

materials layers (plasterboard, fiberglass and plasterboard) with a total thickness of 0.090m

and u-value of 0.508W/m2K. The external wall was assigned with three material layers

(plasterboard, ASHRAE fiberglass and ASHRAE wooden sidings) with a total thickness of

0.087m and a u-value of 0.510W/m2K.The solar absorptance of all walls is 0.6 for both sides.

The long wave emission coefficient of all walls is 0.90 for both sides.

Windows

In TRNBuild, windows can be defined for external and adjacent walls. Windows can be

added, edited or deleted depending upon the geometry mode settings. The specifications for

windows geometry and materials include windows type, area, category, surface number, gain,

orientation and shading device. The TRNBuild standard and default setting for windows is

shown in Figure 6-14.

150

Figure 6-14: Properties of windows assigned

When the *.BUI file is written during model transfer, the windows area is automatically

subtracted from the wall area by considering it an extra surface with area. This window can

be assigned different materials, glazing, frame and optional properties of shading devices

including convective heat transfer co-efficients for a window (glazing + frame) as shown in

Figure 6-14.

TRNBuild contains a standard library for windows according to the available standards. In

the library, each type is assigned with an ID number, u-value, g-value, convective heat

transfer coefficient, frame properties and optional properties of shading devices. The selected

default settings for windows are shown in Figure 6-14.

Infiltration

Airflow into the zone from outside is specified by infiltration. In TRNBuild, infiltration is

optional and it can be a constant value, an input or scheduled value. The infiltration is defined

in terms of number of air changes per hour (ACH). By default, infiltration is off for the initial

simulation parameter.

Ventilation

Airflow from external heating or cooling equipment into the zone is specified by ventilation.

In TRNBuild, ventilation is optional and it can be defined by airflow (air change rate or mass

flow rate), temperature of airflow (outside or other) and humidity of airflow (relative or

151

absolute humidity and outside or other). By default, ventilation is off and the user can create

different types of ventilation. For initial simulation default parameters are used.

Heating

Heating requirements and heating control in any zone are defined by heating type. Using

heating in a zone is optional and by default it is off. Heating control is defined by set

temperature, heating power (unlimited or limited) and humidification (off or on with relative

or absolute humidity). For initial simulation default parameters are used.

Cooling

Cooling requirements and cooling control in any zone is defined by cooling type. Use of

cooling in the zone is optional and, by default, it is off. Cooling control is defined by set

temperature, cooling power (unlimited or limited) and humidification (off or on with relative

or absolute humidity). For initial simulation default parameters are used.

Gains

Internal gains including persons, electrical devices and lighting are defined by gains. Gains

are optional and by default, they are off. A person’s activity gains are defined according to

the ISO 7730 standard. Use of computer and artificial lighting is optional. Gains are from a

standard library and the user defines other gains which are available according to selected

standards. For initial simulation default parameters are used (no gain at all).

Comfort

Thermal comfort calculations are based on the ISO 7730 standard. Specification of comfort is

optional and by default the comfort setting is off. The user can define the comfort type based

on clothing factor, metabolic rate, external work and relative air velocity. The internal

calculation based on comfort is calculated by a simple model (based on area weighted mean

surface temperature) or a detailed model (based on view factor of reference point). For initial

simulation default parameters are used, which is that no comfort standard is used.

Schedule

TRNBuild offers a scheduling system for infiltration, cooling, heating, ventilation, gains and

comfort. The schedule types are, day-night, and light, set off, use, weekend, workday and

152

work light. Frequency is daily or weekly with any start stop times during the 24 hour

duration. For initial simulation no schedule is used.

Geometry and Radiation Modes

Radiation modes of thermal zones are for direct and diffuse shortwave and long wave

radiation distribution within zones. The available options are beam radiation and diffuse

radiation distribution with standard and detailed models, and long wave radiation exchange

with a zone offering standard, simple and detailed models as shown in Figure 6-15.

Figure 6-15: Radiation and geometry modes

TRNBuild supports different levels of geometric surface information for each zone.

Geometry modes use manual, mixed and 3D data. If the geometry mode is set to manual data

for all three dimensions will be deleted. Detailed models for radiation mode selections work

only if geometry is set to 3D data. For the initial simulation 3D data is used when 3D model

is imported into TRNSYS.

6.4 Building Model Initial Simulation Results

After the model import in TRNSYS with all the default settings and parameters selected as

initial parameters for the building model with Lahore TMY2 data, a simulation was executed

and initial results were obtained. The TRNBuild default building model outputs were zone air

temperatures and sensible heat required for the zone (positive for cooling and negative for

153

heating). For initial results only zone temperatures were plotted to study the room’s

temperatures with (American/ASHRAE) TRNBuild pre-selected default parameters. For

better plot results, temperature ranges were set from 0°C to 55°C and sensible heat ranges

were set from zero to 5000 kJ/hr. The default simulation time-step was one hour and the total

duration was 8760 hours for a year (365 days). For the purpose of simplicity only the room’s

temperatures were plotted to observe the inside air temperature with default materials and

others parameters. The initial results are shown in Figures 6-16, 6-17 and 6-18.

Figure 6-16: Initial results, room1 and room2 air temperatures

Figure 6-17: Ambient and room 1 temperature comparison

154

Figure 6-18: Ambient and room 2 temperature comparison

Figure 6-16 shows that both rooms have very high temperatures in the summer season with a

peak temperature of more than 45°C which is higher than the ASHRAE standard comfort

temperature. It also shows there is a need for a cooling system for comfort, which is realistic

for Pakistan weather conditions. The pattern and range of temperature for both rooms is

similar. Figures 6-17 and 6-18 show the comparison between room 1 and room 2

temperatures with the ambient temperatures respectively. It is clear that both rooms have

temperatures higher than ambient temperature both in summer and winter seasons. For the

current research concern is with temperatures in the summer season as research relates to

cooling load for comfort temperatures in the summer season.

Default (initial) building properties were assigned by TRNSYS to both rooms. For simplicity

and reference, all the modifications and changes were made in room 1 only. The reference

was there, so that it was possible to check (as an aid to trace errors) if the results detected

something was wrong while modifying room 1. The cooling system was designed for room 1

and could be multiplied for a multi-rooms building.

6.4.1 Internal Gains and Infiltration Addition

The first change made in the building parameters was the addition of internal gains,

infiltration and ventilation to room 1 as the TRNSYS default settings do not use any gain or

infiltration. This addition made the simulation results more realistic and estimated the

maximum room temperature and cooling load with gains and losses. Internal gain used the

155

default ISO 7730 standard with the presence of one person with light activity from 4 pm to

9am and a 100 W/m2 incandescent lamp and one TV/computer of power 140W as the internal

gains. Infiltration was set according to the LEED standard as 0.2 (ACH) and ventilation as

2.0 (ACH) with ambient temperature and humidity [372]. The simulation results after

addition of gains and losses showed an increase in room 1 air temperature, which is shown in

Figure 6-19.

Figure 6-19: Room1 air temperature with internal gain, infiltration, and ventilation

Figure 6-19 shows an increase in room air temperature due to an increase in internal heat gain

and infiltration of ambient air. The peak temperature during the summer is more than 50°C.

Ventilation is heat input to the room in the middle of the day when ambient temperature is

high and heat removal is at night when the ambient temperature is lower, which lowers the

room temperature.

The initial results showed that there is a need to modify building construction materials and

operating parameters to improve building comfort levels and minimise the cooling load

before designing a cooling system to maintain the standard comfort conditions inside the

room.

156

6.5 Building Model Modification

6.5.1 Construction Materials

Walls

Room 1 was assigned actual construction materials from the TRNBuild library according to

the ASHRAE Standard to make the model more realistic according to constructions

commonly used in Pakistan as described in Sections 6.1 and 6.2. The construction included

reinforced cement and concrete for roof and floor, and solid brick walls.

In TRNBuild, normally the roof is considered as a roof surface with external conditions and

the floor as a roof surface with boundary conditions. Boundary condition is the temperature

of a node to which surface back is connected through pure resistance. For a simple model, the

roof and floor are both simulated as a roof with external conditions. The library for walls and

roof materials is the same. The detailed properties of three materials assigned to walls, roof

and floor are shown in Table 6-1. The composition of the wtype115 and wtype11 are

different, although both are heavy concrete.

Table 6-1: Properties of materials assigned to walls and roof surfaces

Surface Library No. Type Description

External Roof 25 wtype 115 200 mm heavy weight concrete

External Floor 11 wtype 11 300 mm heavy weight concrete

External/Adjacent Wall 64 wtype 20 Solid brick wall (200mm)

Solar absorptance of wall Front:0.60 and back:0.60

Convective heat transfer coefficient of wall Front:11 kJ/h.m2K back: 60kJ/h.m2K

Others wall parameters include solar absorptance and convective heat transfer co-efficients of

the wall for the front and back sides. Solar absorptance and connective heat transfer co-

efficients are the same for all the walls and roof surfaces. The thermal capacitance of the

room was set to a standard value which is 1.2 times room volume and is 54.60kJ/K. The

summary of material assigned to walls, roof and floor surfaces is shown in Figure 6-20.

157

Figure 6-20: ASHRAE standard materials assigned to walls, roof and floor

Windows

Windows ID-1001 was selected from the ASHRAE library as an external window 1. It is a

single glaze window, which is the most commonly used window type in Pakistan (author’s

own observation). All the properties were according to the ASHRAE standard and selected

window properties and other parameters are shown with details in Figure 6-21. The u-value

and g-value of TRNBuild default windows (ID: 6001, u-value 2.89W/m2.K, g-value 0.789)

are less than the selected single glazed window.

Figure 6-21: ASHRAE standard properties of window ID-1001

158

Gains

Room cooling or heating load was based on room envelope conduction and internal heat

gains. The gains were set for occupancy according to the ISO7730 standard with light

activities of 170W (75W sensible heat 95W latent heat) total heat and , a computer with 50W

of power and artificial lighting with a total heat gain of 19 W/m2. These were updated

according to the best energy efficient available equipment and were different to the default

described in Section 6.4.1.

6.5.2 Modified Building Model Results

After assigning materials to walls, roof, floor and windows, simulation results for zone 1

(room 1) air temperature were derived to observe the effect of assigning commonly used

materials in Pakistan. The results showed a decrease in the room 1 air temperature in

comparison to previously assigned TRNBuild default materials. This decrease in temperature

occurs both in summer and winter. This indicates a decrease in energy transfers from the

outside to the inside of the room. The room peak temperature during summer decreased to

less than 43°C as shown in Figure 6-22.

Figure 6-22: Room 1 temperature after assigning walls and windows materials

Further modification required is integration of the cooling system with the building. The

building materials and internal gains used were the same and the final results were plotted for

standard room comfort conditions.

159

6.5.3 Building Envelope Conduction

TRNBuild is lacking only in defining the doors created in the Trnsys3d model. It considers

doors to be parts of walls. The area of doors is included in the wall area. If the difference

between doors and walls is important, doors may be modeled as windows. For actual

assigned materials, the heat conduction through walls, roof, floor and door was carried out in

detail to compare the heat conduction effect from doors. The heat conduction of actual

materials is shown in Table 6-2.

The U-value for floor was higher than for roof in spite of being thicker, because of the

difference in composition of both materials. Similar construction materials with a U-value

(2.15-5.78 W/m2K) were used by Montero et al. [302] for solar assisted cooling systems for

the climate of Guayaquil, Ecuador.

The thermal conductivity of wood across the grain, yellow pine, timber =0.147 W/m.K [373].

The normal thickness of a door according to (Indian standard) IS4021-95 = 0.060 m [374].

The heat loss co-efficient for the door = 2.45 W/m2K.

Table 6-2: Room envelope heat conduction calculations

Surface Area (m2) U-Value (W/m

2K) Heat loss UA (W/K)

Front wall 12.5 2.09 26.12

Back wall 14 2.09 29.26

Adjacent wall 10.5 2.09 21.94

Side wall 10.5 2.09 21.94

Roof 12 1.97 23.64

Floor 12 2.45 29.48

Window 1.5 5.68 8.52

Door 2 2.45 4.90

Total 165.80

If the door is considered part of the wall (the U value is 2.09 W/m2K instead of wood

2.45W/m2K) the total UA value decreases by 0.72W/K (4.90- 4.18) or about 14% only.

Therefore, neglecting the door and considering it as part of the wall did not have a large

effect on the results.

160

6.6 Solar Cooling System Initial Parameters Calculations

6.6.1 Chiller Cooling Capacity

In the previous sections, the conditioned zone was not comfortable. Therefore, to make it

suitable for the comfort of residents in the summer a cooling system needed to be designed.

To start the TRNSYS simulation for a solar cooling system an estimation of initial parameters

was required for all components of the solar cooling system. In this section some calculations

are performed to get initial parameters to start the simulation.

The selected building model was an existing building with typical construction with two

rooms each with a space volume of 42m3. An air-conditioning unit about 3.52kW (1 Ton of

refrigeration) capacity was expected to be sufficient for comfort during the peak summer

season for the room with a volume of 42m3.

Estimated installed capacity = 3.52 kW ~12660 kJ/hr.

The TRNSYS default value for the Type107 chiller gives a difference between the hot water

inlet and the outlet temperature from the chiller at 46°C but for low temperature heat sources,

such as solar collectors, it is assumed to be 33°C. The standard COP for absorption chillers is

shown in Table 6-3.

Table 6-3: COP of absorption chillers [375]

Chiller Type Heating Source C.O.P Range

Single effect Hot water or steam 0.60 to 0.75

Double effect Hot water or steam 1.19 to 1.35

Double effect Direct fired 1.07 to 1.18

COP of chiller = 0.60 (lower as a conservative estimate)

The COP of a chiller is expressed as Equation 1.

COP = Qe ÷ Qg (1)

Qe = 3520 W

So, Qg = 3520 ÷ 0.60

= 5867W~21100 kJ/hr

The hot water flow rate (m) from the tank to the chiller was estimated from Equation 2.

Qg = m × CP × (ΔT) (2)

161

5867 = m × 4190 × 33

m = 0.0424 kg/sec ~ 153kg/hr

Where, CP is the specific heat capacity of water and it is 4190 J/kg.K

6.6.2 Solar Collector Calculation

Solar energy availability varies each month due to seasonal changes. For the solar collector

initial parameters, from the summer season a month was selected with the highest solar

energy availability to meet the cooling load of the building. All the calculations were made

for a single day, and then the simulation was run to optimise the system for one day (24 hr)

then for the whole year (8760 hrs).

According to NASA, SSE data as shown in Appendix A, the month of May has the maximum

daily average insolation incident in Lahore on a horizontal collector and is measured at

approximately, 7.34 kWh/m2 [42].

Assuming May 15th (day number 135, hours 3216-3240) to be a clear day with no clouds and

with 14 hours of bright sunshine day length, the average incident radiation received per

square metre during each hour would be:

7.34 ÷14 = 0.524kW/m2 = 524 W/m

2

This means that the total incident energy rate available on the surface of a collector with an

area of 1m2, would be 524W.

The efficiency of an evacuated tube collector ranges from 50% to 85% [376]. Supposing the

mean efficiency of the evacuated tube collector is 67% (a conservative value). The energy

absorbed at the collector and water flow rate would be as follows.

The energy rate absorbed/available from collector = 524 × 0.67

= 351 W/ m2 ~ 1264 kJ/hr. m

2

So, 1m2 area of evacuated tube collector could produce a maximum energy rate = 351 W/ m

2

Assuming there is no heat loss from the collector outlet to the tank storage and the tank to the

absorption chiller, the energy output required from the collector would be equal to Qg

calculated from Equation 1:

162

Qcoll.out = Qg = 5867 W

The area of the collector would be = required energy output ÷ energy available per unit area

=5867÷ 351 ~17 m2

Zambolin et al. [377] did experimental work on the performance of a flat plate and an

evacuated tube collector for a single day, showing the difference between the collector inlet

and the outlet temperature to be 30°C. The water flow rate for a collector can be calculated

from Equation 3.

Qcoll.out = m × CP × (ΔT) (3)

5867 = m × 4190 × 30

m = 0.0466 kg/sec ~ 168 kg/hr

This is approximately the same as the flow rate from the tank to the chiller, because ΔT is

about the same.

Theoretically, 5.867kW (21100 kJ/hr) of heat energy is required by a chiller generator for

3.52kW (3520W) refrigeration cooling output. The energy supplied by a solar collector to a

storage tank is 5.967kW (21481kJ/hr). This is sufficient heat energy to run the cooling system

by assuming zero tank heat losses at the start of the simulation. Later on in the optimisation

process the tank and pipes losses were introduced.

6.6.3 Cooling Systems Reference Model

In the above basic calculation, parameters were referenced from the literature mentioned.

Some other parameters were referenced from the literature are described here.

Eicker et al. [353] analysed heat rejection and primary energy efficiency of solar driven

absorption systems. They analysed an 18kW solar cooling absorption system installed at the

Solar Next Company in Rimsting, Germany. The solar cooling system had hot and chilled

water storage, flat plate and evacuated tube collectors, a wet cooling system (dry cooling is

also possible) with fan coils for the distribution of cooling air.

163

All the electrical loads of the chiller, fan, pumps and cooling system were referenced from

[353] , adjusted in proportion to the rated cooling capacity. All other parameters were either

TRNSYS standards or optimised values according to the system energy balance.

For a TYPE 71 collector, the collector test reports representative data is available on the web

from testing institutes. The evacuated tube collector model CALDORIS-58-30 was selected

from different available models due to a nominal flow rate of 180 kg/hr as most suitable. It is

manufactured by Caldoris Polska Sp.Zo.o and tested for performance and quality in

accordance with the EN12975-2:2006 standard. The efficiency a0 (0.769) and loss co-

efficients a1 (2.52 W/m2K), a2 (0.0106W/m

2K

2) were selected from this tested model [378].

6.7 Solar Cooling System Simulation

Different types of component are available in TRNSYS to simulate solar cooling systems. As

described in Section 4.4.3, the evacuated tube collectors are more efficient than flat plate

collectors. Also absorption chillers are the most commonly used chillers. For the simulation

both of these two components were selected. For small capacity and low temperature heat

input applications a dry cooler is a better choice than a wet cooler [353] . To store heat for

load after sunset and the smooth operation of the chiller, a hot water storage tank was

selected [379].

6.7.1 Solar Cooling Process

A simplified summary and process flow diagram involved in the simulated solar cooling

system is shown in Figure 6-23 and explained here. It should be noted that the lines in the

diagram represent logical connections in the simulation rather than physical pipes etc.

The process of solar cooling starts from the solar heat collection through an evacuated tube

collector Type71. The cold water from a stratified water storage tank Type4a bottom is

pumped to the collector and hot water returns to the top of the storage tank. The collector

pump Type3d is controlled by a timer controller (not shown) and turns on during the day

when energy is available. The controller working parameters are described in Section

6.7.11.The hot water from the top of the tank is pumped to the chiller Type107 and returns to

the bottom of the storage tank through a pump Type3d-2.

164

The chiller absorbs heat from the cooling coil Type697 by circulating chilled water through a

pump Type3d-4. The returned chilled water from the cooling coil exchanges heat with the

absorption solution inside the chiller. The absorption solution is cooled by cooling water from

the auxiliary dry cooler Type1246.

Figure 6-23: Solar cooling system

The hot cooling water from the chiller is circulated by a pump Type3d-3 to the auxiliary

cooler Type1246. It is a dry cooler and cools hot water by exchanging heat with ambient air.

The cooled water is returned to the chiller to absorb heat from the absorption solution.

The chilled water in the cooling coil Type697 exchanges heat with the air coming from the

fan Type112b. The fan takes air from the building Type56 which is cooled down through a

cooling coil and returned to the building. The fan is controlled by the controller Type108 (not

shown) which monitors the inside temperature of the building. As the temperature goes above

the set point the fan turns on. The detailed description of the controller is in Section 6.7.11

The components used for the simulation of solar energy collection, storage and cooling

systems integrated with the building are described here with some important operating

parameters. The details of all components, parameters, and inputs are shown in Appendix C.

165

6.7.2 Evacuated Tube Collector

An evacuated tube solar collector of TYPE 71 is used for TRNSYS simulation. It is a

TRNSYS TESS standard collector with experimental data validation [344]. The loss

coefficients a1 and a2 used are from the collector (SPF No.C1586: CALDORIS-58-30) as a

reference [378]. This reference collector model is selected as the nominal flow rate is in the

same range as this research design (Section 6.6.2).

The collector’s efficiency depends on the collector inlet or average or outlet temperature (Tc).

In Type 71 input parameters, one (1) is for the collector efficiency parameters given as a

function of the inlet temperature. Two (2) is for a function of the collector mean temperature

and three (3) is for a function of the collector outlet temperature. In this research, two (2) is

used as a collector average temperature (Tm) for collector efficiency calculations.

The efficiency of a collector is written as Equation 4.

Collector efficiency = a0 – [a1 × (Tc-Tamb)/I] – [a2 × (Tc-Tamb)2 /I] (4).

The efficiency of the collector type with the selected a0 (0.769), a1 (2.52W/m2K) and a2

(0.0106 W/m2K

2) and I=1000 W/m

2, using Equation 4, is shown in Figure 6-24.

Figure 6-24: Evacuated tube collector TYPE 71 efficiency curve for I=1000 W/m2

The Solar Ratings and Certification Commission (SRCC) define the efficiency of an

evacuated tube collector using the same equations as for a flat plate; the main difference

(from a modelling point of view) is in the treatment of Incidence Angle Modifiers (IAM).

Type71 reads a text file containing a list of transversal and longitudinal IAM’s. IAM is the

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125

Co

llecto

r e

ffic

ien

cy

Tm-Ta

166

variance in output performance of a solar collector as the angle of the sun changes in relation

to the surface of the collector.

Transversal IAM measures change the performance of the collector as the angle of the sun

changes at right angles to the collector tube axis. Longitudinal IAM measures change in

performance as the angle of the sun changes along the collector tube axis. The default number

of IAM’s in TRNSYS is 5 and the optimised number for maximum energy yield and

efficiency results is also 5. The reference values used for TYPE 71 are shown in Appendix C.

Figure 6-24 shows that collector efficiency decreases as the difference between a collector’s

mean temperature and ambient air temperature increases. The higher the difference the higher

the heat loss to ambient will be. For a temperature difference of 30ºC the efficiency of a solar

collector is about 67%, which is higher than the initially selected collector efficiency of 60%

in Section 6.6.2.

Simulation Parameters

The inputs to the collector Type71 simulation model are fluid properties, flow rate and

weather data. Collector inlet fluid temperature and flow is the outlet of a storage tank cold

side. The flow is controlled by a controller, which cuts off flow if fluid temperature

difference between inlet and outlet is less than 2°C. The operation of the controller is

explained in Section 6.7.11. The collector slope is zero (lying flat on the roof) and other input

data is shown in Figure 6-25.

167

Figure 6-25: Collector solar data input

Collector Outputs

The collector gave three outputs which were outlet temperature, outlet flow rate, and useful

energy gain. The outlet temperature is at the exit of the array and the outlet flow is the same

as the inlet flow rate. The rate of useful energy gain by the solar collector fluid was calculated

by Equation 5.

Qu = m × CP × (Tcoll.out – Tcoll.in) (5)

6.7.3 Hot Water Storage Tank

The hot water storage tank Type 4a was used to simulate the thermal storage tank in

TRNSYS. It is a stratified storage tank with fixed inlets and uniform losses with an auxiliary

heating system. The stratified tank delivers water at a slightly higher temperature than an un-

stratified tank [357]. This is a simple stratified tank suitable only as a storage tank without

auxiliary heating. The tank volume is 2m3 with a total height of 1m and an area of 2m

2 and a

diameter of 1.6m. This volume is sufficient to provide energy for 24 hour operation of an

absorption chiller with about 12 hour back up. Tank Type4a includes two auxiliary heating

elements and auxiliary heating elements are not used in this simulation so their maximum

heating capacity is set to zero.

168

Figure 6-26: Operation of hot water storage tank

Fluid is hot on the top side and cools down as it moves downwards and is cold at the bottom

of the tank. The tank is divided into ten equal heights (each 0.10m). It was assumed that

losses from each tank node are equal. The hot water from the collector enters the tank top and

leaves from the top to the chiller. The cold side water enters at the bottom of the tank

returning from the chiller and leaves the tank bottom for the inlet to the collector as shown in

Figure 6-26, where, mh and mL are the fluid flow rates to and from the heating side and load

side respectively and the temperature difference from top to bottom is about 10°C.

Inputs and Outputs

The inputs to the tank are the hot side inlet (collector outlet) fluid flow rate and temperature

and cold side (Chiller outlet) fluid flow rate and temperature. The ambient/environment

temperature is an input for heat loss calculations. The input and output connections for hot a

water storage tank are shown in Figure 6-27.

For storage tank heat loss calculation it is assumed that the tank is well insulated with

minimum heat loss. For storage tank with fiber glass insulation of thickness 0.050m [380]

and R-value 6m2K/W, the tank average heat loss co-efficient is about 0.167W/m

2.K [381].

The boiling point temperature of the fluid in the storage tank is set to 100°C. When the tank

temperature reaches the boiling temperature, venting of steam occurs to keep the fluid at

boiling temperature. The venting is assumed to occur with negligible loss of mass.

169

Figure 6-27: Tank inlet and outlet connections

The tank outputs include the fluid flow rate, temperature to the heating source (collector

inlet), energy rate, fluid flow rate, and temperature to load (chiller inlet). Internal energy

change (kJ), auxiliary heating rate, energy rate from the heating source (collector), tank

thermal losses rate, average tank temperature, and temperature of any specified node are also

outputs from the storage tank.

6.7.4 Absorption Chiller

A hot water fired single effect absorption chiller Type 107 is used in TRNSYS simulation.

Type107 uses a normalised catalogue data, lookup approach to model a single-effect hot

water fired absorption chiller. Hot water-fired indicates that the energy supplied to the

machine generator comes from a hot water stream. Because the data files are normalised, it

can operate for a variable set of inlet fluid temperatures, cooling capacities and outlet chilled

water temperatures.

The chiller capacity is set at 3.52kW with COP of 0.60 as described in Section 6.6.2. The

chiller cooling water inlet temperature is from a cooling tower and the chilled water set point

is at 7°C. Many parameters are linked with the TRNSYS library supplied data file. These

include a number of hot water temperatures, a number of cooling water steps, a number of

chilled water set points and a number of design load fractions. The TRNSYS default values

were used for all these four parameters as they are parameters tested by the Thermal Energy

System Specialists (TESS).

170

The specific heat capacity for hot water, cooling water and chilled water is 4.190kJ/kg.K. The

auxiliary electrical power required by an absorption chiller to operate a solution pump and

refrigerant pumps is set to 0.061kW. This parameter is taken from a reference absorption

chiller model [353].

Figure 6-28: Absorption chiller input and out connections

Inputs and Outputs

The TRNSYS default and selected set-point temperature for the chilled water stream is set to

7°C, which is the design temperature for commercially available chillers [297, 382]. If the

chiller has the capacity to meet the current load, it will modulate to meet the load and a

chilled water stream will leave at this temperature.

Inputs to a chiller are hot water flow rate and temperature from a storage tank, cooling water

flow rate and temperature from a cooling tower and chilled water flow rate and temperature

returned from a cooling coil.

The chilled water flow rate was set to 250 kg/hr and the inlet hot water from the tank hot

temperature with a flow set to 150 kg/hr in accordance with chiller performance. For the

cooling water from the cooling tower, the flow was set to 800 kg/hr. All these flowrates are

used to maintain to a chiller set of 7°C.

171

Outputs from the chiller are hot water flow, temperature return to the storage tank, cooling

water flow, temperature to the cooling tower and chilled water flow, as well as temperature to

the cooling coil. Hot, cooling, and chilled water energies and electrical energy required are

also outputs from the chiller simulation. The chiller input and output connections for a chiller

Type107 are shown in Figure 6-28.

6.7.5 Cooling Coil

A conventional cooling coil model Type697 is used in TRNSYS to model building air

cooling through chilled water from a chiller. This component models a cooling coil where air

cools down as it passes across a coil containing a cooler fluid (typically water). This model

relies on user-provided external data files that contain the performance of the coil as a

function of the entering air and fluid conditions.

Type697 models a simple air-cooling device that removes energy from an air stream

according to performance data found in a combination of three external data files and based

upon the flow rates and inlet conditions of the air stream and a liquid stream. In Type697,

three data files are required. The first provides water temperature correction factor

performance data. The second provides correction factor data for the performance based on

varying air temperatures while the third provides correction factor data for the performance

based on varying airflow rates. The default values are used for all these three parameters as

they are parameters tested by the TESS and shown in Appendix C.

At each time step, Type697 performs a call to the TRNSYS psychrometric routine in order to

obtain air properties for the inlet air stream not specified by the user among the component’s

inputs.

172

Figure 6-29: Cooling coil connections

Inputs and Outputs

The Type 697 model works on two types of humidity modes used for inlet air. These modes

are both for an absolute humidity ratio and the percentage of relative humidity. Some

parameters are linked with the TRNSYS library and supplied in three data files. These are the

number for water flow rates, the number for water temperatures, the number for air flows, the

number for dry bulb temperatures, and the number for wet bulb temperatures. The rated

volumetric flow rate for air is input from a fan. The total cooling capacity is 2.5kW and the

sensible cooling capacity is 2.0kW. These settings are in accordance with chiller performance

to maintain room temperature below the set point. For the Type 697, the TRNSYS default

ratio of total cooling capacity to sensible cooling capacity is 1.26.

The inputs to the coil are chilled fluid flow and temperature from the chiller, as well as

airflow, temperature, pressure and percentage of relative humidity from a building through a

fan Type112b. Inlet air pressure is 1 atm and the air-side pressure drop is set to zero.

The outputs include outlet fluid flow and temperature back to the chiller, outlet airflow,

temperature and pressure and percentage of relative humidity to the building. The total heat

transfer rate, sensible heat transfer, fluid heat transfer, condensate temperature, and flow are

outputs from a coil. Input and output connections for the cooling coil Type 697 are shown in

Figure 6-29.

173

6.7.6 Cooling Tower

The air-cooled cooling tower Type1246 is used to model an external proportionally

controlled fluid cooler. Type1246 is a low-temperature heat-distributing unit such as

radiators, convectors, and finned-tube units. This unit transfers heat through a combination of

radiation and convection without a fan.

Figure 6-30: Auxiliary cooler connections

The rated capacity of the cooler is set to 5.83kW and the heat capacity of fluid is

4.190kJ/kg.K. The inputs to the auxiliary coolers are fluid flow and temperature from the

chiller, heat loss coefficient and the temperature of the environment. The control function

controls the on/off operation of the cooler. The loss coefficient (UA) for the fluid cooler

during operation is set to zero.

The outputs are outlet fluid flow and temperature to the chiller, cooling rate, thermal losses

and useful cooling rate. The input and output connections of the auxiliary cooler Type1246

are shown in Figure 6-30.

6.7.7 Pumps

For water flow simulation in TRNSYS, pump Type 3d was selected. This is a simple, single

speed and constant flow pump with only inputs of fluid flow and pump electrical power. The

TRNSYS library contains multiple pump types which are complex and meet different criteria.

This pump model computes a constant mass flow rate using a variable control function,

which must have a value of 1 or 0. The pump will be on when it is 1 and off when it is 0. A

user-specified portion of the pump power is converted to fluid thermal energy. This

174

component sets the flow rate for the rest of the components in the flow loop by mult iplying

the maximum flow rate from the control signal. All the four pumps used for water flow from

the solar collector to the storage tank, the storage tank to the absorption chiller, the absorption

chiller to the cooling coil and from the absorption chiller to the auxiliary cooler are Type3d

pumps as shown in Figure 6-31.

Figure 6-31: Pump connections

The inputs to the pumps are fluid maximum flow rate, fluid temperature and control signal.

The outputs are outlet fluid temperature, fluid flow rate and pump power consumption. These

inputs and outputs are common parameters for all pumps used. The flow rate and power

consumption [353] for all the pumps are shown in Table 6-4.

Table 6-4: Pumps, powers and flow rates

Pump Connection Maximum Power (W) Maximum Flow (kg/hr)

Type3d Tank-Collector 27 165

Type 3d-2 Tank-Chiller 14 150

Type 3d-3 Chiller-Cooler 63 800

Type 3d-4 Chiller-Coil 14 250

Chiller Solution pump 61

6.7.8 Fan

TRNSYS Type112b was selected to model a fan to transfer air from building Type56 to

cooling coil Type697. It is a simple, single speed fan with relative humidity inputs. The

humidity mode for the cooling coils Type697 is relative humidity so Type12b was selected.

Type112b models a fan which spins at a single speed and maintains a constant mass flow rate

175

of air. As with most pumps and fans in TRNSYS, Type112b takes mass flow rate as an input.

Type112b sets the downstream flow rate based on its rated flow rate parameter and the

current value of its control signal input which must have a value of 1 or 0.

Figure 6-32: Fan connections

The inputs to the fan are humidity mode, rated flow rate, rated power, motor efficiency and

motor heat loss fraction. The selected humidity mode is 2, which is a percentage of relative

humidity and the air flow rate is 300kg/hr (~ 250m3/hr) sufficient to maintain room

temperature below a set point. The rated power is 23W and the default standard motor

efficiency and heat loss fraction were selected. The default standard motor efficiency is 0.90

and the motor heat loss fraction is zero.

The fan inlet air temperature and percentage of relative humidity is room 1 air temperature

and percentage of relative humidity. The input control signal to the fan is the output from the

thermostat Type108. The fan is OFF when the control signal value is 0 and the fan is ON if

the control signal value is 1.

The fan outputs are outlet air temperature, pressure, flow rate, humidity ratio, and percentage

of relative humidity, power consumption, and air heat transfer. The outlet air temperature,

flow rate, and percentage of relative humidity are input to the cooling coil Type 697. Fan

input and output connections are shown in Figure 6-32.

176

6.7.9 Pipes

To simulate pipe connections between components Type31 pipe was selected. This

component models the thermal behaviour of fluid flow in a pipe and thermal losses are also

considered for realistic operation. The pipe connections are used between the storage tank

Type4a and pumpType3d, solar collector Type71 and storage tank Type4a, chiller Type107

and auxiliary cooler Type1246 and between the chiller Type107 and cooling coil Type 697.

The simplified layout of pipe connections is shown in Figure 6-33.

Figure 6-33: Pipe connections

Inputs and Outputs

As the same type of pipe is used, all inputs and outputs are the same except for pipe diameter

and length, fluid temperature and flow rate. The pipe diameters were selected from the

TRNSYS default standard sizes to sizes with optimal losses and fluid flow. The lengths of

pipes were estimated from the room dimensions. The heat loss co-efficient for pipes is used

as for the storage tank, namely 0.167W/m2.K [381]. Fluid density and specific heat capacity

value are 1000kg/m3 and 4.190 kJ/ kg.K. The same ambient temperature is used for the pipes

which is output from weather data for thermal losses of the pipes.

The outputs included fluid outlet temperature and flow, environment losses, change in

internal energy, average temperature, and rate of change of internal energy. The outlet

temperature and flow were input for the components these pipes are connected to. Only

environment losses were considered for heat balance calculations. Input parameters used for

the pipes are shown in Table 6-5.

177

Table 6-5: Pipe sizes and flow rate

Pipe Connection Diameter(m) Length (m) Maximum Flow (kg/hr)

Collector supply Collector-Tank 0.025 6 165

Type 31 Tank-Pump 0.025 6 165

Type 31-2 Chiller-Cooler 0.075 10 800

Type 31-3 Chiller-Coil 0.030 8 250

6.7.10 Weather Data Reading and Processing

For weather data reading and processing TRNSYS Type15 was used. This component can

read data at regular time intervals from an external weather data file, interpolating the data

(including solar radiation for tilted surfaces) at time steps of less than one hour, and this data

output is used in other TRNSYS components.

This component reads weather data files in the following formats: Typical Meteorological

Year all formats (.TMY), (.TMY2) and (.TMY3), International Weather for Energy

Calculations (IWEC) format, Canadian Weather for Energy Calculations (CWEC) format,

Energy Plus format (.EPW), Meteonorm files for TRNSYS (.TM2) and German 2004 and

2010 TRY formats. The connections for weather data Type15 output are shown in Figure 6-

34.

Figure 6-34: Weather data processor connections

178

6.7.11 Controllers

Two different types of controller were used for the current TRNSYS simulation. Controller

Type2d was used to control the collector pump flow into the collector from the storage tank.

Controller Type108 (thermostat) was used to control the fan air flow from room 1 to the

cooling coil. Controller Type108 (thermostat) cannot be used with other components, as a

simulation error occurs when it is connected with a chiller. Controller Type2d monitors and

compares three parameters whereas Type 108 monitors only two parameters.

6.7.11.1 Collector Pump Flow Controller

A differential controller with hysteresis for Type2d was selected for the collector pump flow

control.

This ON/OFF differential controller generates a control function γο. The value of this control

function is either 0 or 1. The new value of γ0 is dependent on whether γi = 0 or 1. If γi = 0

then it will compare the difference (TH - TL) with ΔTL. If γi = 1 then it will compare the

difference (TH - TL) with ΔTH. It will use either ΔTH or ΔTL for comparison. The controller

settings are shown in Table 6-6.

The controller is normally used with γ0 connected to γi giving a hysteresis effect. For safety

considerations, a high limit cut-out is included with the Type2d controller. Regardless of the

dead band conditions, the control function is set to zero if the high limit condition is

exceeded. This controller is not restricted to sensing temperatures, even though temperature

notation is used.

Table 6-6: Collector pump controller inputs

Input Symbol Value

Upper input value TH Collector outlet temperature (Tcoll.out)

Lower input value TL Collector inlet temperature (Tcoll.in)

Monitoring value TIN Tank average temperature

Input control function 1

Upper dead band ΔTH 4

Lower dead band ΔTL 2

High cut limit Tmax 100

179

Where,

ΔTH = Upper dead band temperature difference

ΔTL =Lower dead band temperature difference

TH = Upper input temperature = Collector outlet temperature (ᵒC)

TIN = Temperature for high limit monitoring = Collector inlet temperature (ᵒC)

TL =Lower input temperature (ᵒC)

TMAX =Maximum input temperature (ᵒC)

γI =Input control function

γo = Output control function

Mathematically, the control function is expressed as follows:

IF THE CONTROLLER WAS PREVIOUSLY ON

If γi = 1 and ΔTL ≤ (TH - TL), γo = 1

If γi = 1 and ΔTL > (TH - TL), γo = 0

IF THE CONTROLLER WAS PREVIOUSLY OFF

If γi = 0 and ΔTH ≤ (TH - TL), γo = 1

If γi = 0 and ΔTH > (TH - TL), γo = 0

However, the control function is set to zero, regardless of the upper and lower dead band

conditions, if TIN > TMAX. This situation is often found in hot water systems where the pump

is not allowed to run if the tank temperature is above some prescribed limit. In this simulation

100ºC is the high cut limit.

Inputs and Outputs

The inputs for the collector pumps controller are shown in Table 6-6 and connections are

shown in Figure 6-35. For this simulation, the controller’s initial value was selected as 1,

meaning the pump is ON at the start of the simulation. The pump will remain ON as long as

the temperature difference in the collector outlet and inlet water temperature is more than or

equal to 2 and the pump will turn OFF when the difference (TH - TL) is less than 2. The pump

will remain OFF until the difference (TH - TL) is more than 4.

180

Figure 6-35: Collector pump controller connection

6.7.11.2 Fan Controller

Room thermostat Type 108 was selected for the current simulation in TRNSYS. This is the

only thermostat controller in the TRNSYS library. Type108 is a five stage room thermostat

modeled to give five output ON/OFF control functions that can be used to control a system

with a two stage heating system, an auxiliary heater and a two-stage cooling system. The

controller commands first stage cooling at moderately high room temperatures and second

stage cooling at room temperatures higher than the 1st stage. First stage heating starts at a low

room temperature, second stage heating at a lower room temperature, and auxiliary heating at

an even lower room temperature. There is an option to disable first stage heating during the

second stage, disable both first and second stage heating during auxiliary heating, and disable

first stage cooling during second stage cooling.

Inputs and Outputs

In the simulation only first stage cooling is used and no second stage cooling and no heating

(both first and second stage) are required at all. First stage cooling is set to ON when second

stage cooling is ON as only first stage cooling is always used. The first stage cooling input is

a set point in such a way that the system maintains room temperature at less than 26°C. The

second stage cooling set point is 30°C (which will never be reached and second stage cooling

is not available) and the monitoring temperature is the room 1 air temperature inside building

Type56. The fan controller connections are shown in Figure 6-36.

181

Figure 6-36: Room air fan controller connections

The first stage heating was set to be off in the second and third stage and the second stage to

be off in the third stage. The first and second stage heating and auxiliary heating were set to

10°C which was not achieved during the simulation 8760 hours. Therefore, heating is always

off all the time of simulation.

The controller outputs are control signals for first, second and third stage heating and control

signals for first and second stage cooling. The first stage cooling signal is used to give a

signal to a fan for air flow control.

6.8 Solar Cooling Simulation System

The solar cooling components and operation sequence was described in Section 6.7.1. The

complete final solar cooling system with all its components is shown in Figure 6-37. This

includes some printers and plotters to get output graphs and an excel data sheet for energy

calculations and heat balance. It also shows the complete layout of connections of all

components and flow sequences. The red lines shown represent the hot water flow cycle, the

blue lines represent the chilled water cycle, the green line represents cooling water, and sky

blue lines represent the ambient temperature connections. The red dotted lines are for

representation of control signals from the controller to the equipment. The remaining black

lines are the output data from the system to the online plotter and printers.

182

Figure 6-37: Complete process diagram of the solar cooling system

6.9 Conclusion

The model building used is a typical single family house in Pakistan. The 3D model

was created in Sketchup and imported to TRNSYS for simulation. The simulation

studio is the main simulation engine of TRNSYS program with graphical plotting and

output with spreadsheet facilities. TRNBuild is used to assign building model

materials and thermal properties.

The model initial results with Lahore weather conditions and ASHRAE standard

materials showed the room temperature is higher than 40°C without any internal gain

and with internal gains it is higher than 40°C in summer season.

Building materials were changed to make the model more realistic by replacing

ASHRAE standard materials with referenced actual materials. The results with actual

materials showed the room temperature was still higher than 40°C and the building

needs a cooling system to maintain comfort in summer.

Solar cooling system’s initial parameters were calculated for a typical cooling

capacity (3.52kW). Referenced and standard data is used to estimate the initial

parameters.

183

Details of solar thermal cooling system components and operating parameters are

described. All the components input and output parameters details are described, with

the sequence of system operation.

184

Chapter 7: Results and Discussion

7.1 Introduction

In the previous chapter 6, key operational parameters are described to estimate the collector

energy output, collector water flow, collector area, and hot water flow to the chiller. All the

components were connected in the TRNSYS model and operated for realistic parameters

(referenced from literature). The cooling system was operated to maintain a standard

comfortable temperature inside the room during the summer season. The system parameters

were optimised on the basis of the TRNSYS simulation results. This optimisation was

achieved on the basis of several hundred simulations by trial and error using repeated

simulations.. The final results, after the system optimisation, are presented and discussed here

in detail. The results of the numerical analysis are validated by previously published results.

A parametric analysis is performed to study the effect of collector area, flow rate, and storage

tank volume on the system performance.

7.2 Evacuated Collector Energy Yield

The TRNSYS simulation output includes the collector heat gain (i.e. yield) and energy

available (incident solar radiation). The final gross collector’s area is 12m2 to meet the

building cooling load. Figure 7-1 shows the energy collected and available monthly from the

collector.

As expected, the energy available is greater in mid-summer and least in mid-winter. This is

because the collector tilt is zero, in order to maximise the energy available in the summer

when cooling is required and the sun is approximately overhead at noon.

Also, as expected, the yield is greatest in mid-summer and least in mid-winter. In winter there

is less energy available, heat loss from the collector is greater due to the lower ambient

temperature, and less heat is required as the building does not need cooling and the heat from

the collector only keeps the system hot so it will be able to operate when required.

185

Figure7-1: Solar collector monthly yield (kWh)

7.3 Evacuated Tube Collector Efficiency

The monthly and annual average collector efficiency is shown in Figure 7-2. Some key

results are described here.

Collector efficiency is maximum (86%) in the month of July and minimum (18%) in January,

and the annual average efficiency is 61%. This general pattern is as would be expected from

the energy available and collected (Figure7-1).

The calculated maximum efficiency for the collector is slightly greater than the value of the

maximum efficiency parameters a0 in the month of July. This can be accounted for by the fact

that the incident angle modifier values are more than 1 for some angles.

0

500

1000

1500

2000

2500

Solar energy available and collected (kWh)

Energy Collected

Energy available

Collector area (gross) = 12m2

186

Figure 7-2: Collector monthly and annual efficiency (%)

7.4 Room Cooling Load

Room load is calculated from the heat removed from the room air which passes through the

cooling coil. A thermostat controller Type108 is used to control air flow from a fan into the

room to maintain the room temperature below 26°C [297] and all the parameters of the room,

fan and cooling coil are explained in Chapter 6 and in Appendix C. The monthly room load is

shown in Figure 7-3; this load is only for cooling, not for heating.

As expected, the room cooling load is greater in mid-summer and least (zero) in the middle of

winter.

The room cooling load is higher in the months when the solar energy availability is also high;

this is an advantage for a solar energy based cooling system.

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%Evacuated tube collector efficiency

187

Figure 7-3: Room monthly cooling load and solar energy availability (kWh)

7.5 Room Air Temperature

For comfort, the room temperature is maintained by the fan air controlled by an on-off

thermostat. The system is sized so that the room temperature is always under thermostatic

control (less than 26°C) during the summer season. The room temperature and ambient

temperature for the whole year are shown in Figure 7-4. The number of hours shown on the

x-axis is the number of hours at approximately one monthly interval, from January to

December.

The system maintains the room temperature below the ambient temperature throughout the

summer season. The maximum room temperature is between 25-26°C in the months of April,

May, June, July, August, and September (2160-6552 hours).

0

500

1000

1500

2000

2500Total room load (kWh)

room load

solar energy available at collector

188

Figure 7-4: Ambient (Blue) and room (Red) temperature comparison (°C)

In the winter, although there is no heating in the simulation, the minimum room temperature

is always above 11°C, and higher than the ambient temperature that is between 4-7°C.

7.6 Storage Tank Heat Loss

A stratified hot water tank is used for storage of thermal energy obtained from the collector.

The monthly heat losses for the tank are shown in Figure 7-5 and some findings are described

here.

The heat loss depends upon the temperature difference between the tank water and the

ambient air temperature (which TRNSYS takes as the outside air temperature) and it is clear

from Figure 7-5 that heat loss is maximum in winter and lowest in summer, as would be

expected.

189

Figure 7-5: Tank heat loss (kWh)

Tank heat loss is low during the cooling season (May to October) and highest in winter

season when cooling is not required and the temperature difference between the tank and

ambient temperature is higher. The tank heat loss as percentage of energy collected is shown

in Figure 7-6.

Figure7-6:Tank heat loss as percentage of energy collected

-100

0

100

200

300

400

500

600

January February March April May June July August September October November December

Tank heat loss (kWh)

TANK HEAT LOSS

-5%

15%

35%

55%

75%

95%

115%

135%

155%

175%

195%

Tank heat loss to energy collected (%)

190

From June to August (between 3984-5832 hrs), there is some heat absorbed by the tank

instead of heat loss. This is due to monsoon season with some rainy cloudy days. The tank

cools down on these days due to less solar radiation and tank temperature increases again

when solar energy is available as shown in Figure 7-7.

Figure 7-7:Ambient and tank temperature with solar radiation available in July-August

Tank heat loss is also linked with tank volume; less volume leads to less heat loss as shown in

Table 7-2.

7.7 Storage Tank Internal Energy Change

The tank’s internal energy is the energy contained in the tank in relation to some reference

condition. The change in internal energy is the difference between the total energy added and

the total energy removed from the tank. The internal energy change is an output parameter

from the tank. The tank’s internal energy change at the start of the simulation and at the end

of each month is shown in Figure 7-8.

The result shows that the tank’s internal energy change is positive (heat gain) in spring and

early summer and negative (heat loss) in autumn and winter.

191

Figure 7-8: Tank internal energy change (kWh)

The maximum monthly changes in internal energy are +76 kWh in May and -97 kWh in

January. The annual net change in internal energy is -100 kWh, which means the tank lost

more energy than it gained due to winter season operation. These energy changes are

equivalent to changes of 32.6°C, 41.6°C, and 42.9°C respectively in the mean tank

temperature. The internal energy changes will be affected by the tank temperature at the start

of the simulation, which was set to 50°C for all simulations.

7.8 Pipe Heat Loss

Pipes are used in the simulation for water flow between different components. The pipes loss

is heat transferred to and from pipes due to temperature difference with the ambient outside

air in TRNSYS. The monthly heat loss for pipes is shown in Figure 7-9.

Some pipes carry hot water, while some carry chilled water. The overall pipe heat loss is the

net figure when some pipes have lost heat and some have gained heat.

Pipe heat loss patterns are similar to tank heat loss. Heat loss is higher in the winter season

and negative (i.e. heat gain) in the summer season. The annual net heat loss from all pipes is

114 kWh.

-120

-100

-80

-60

-40

-20

0

20

40

60

80

100

Monthly net change in internal energy (kWh)

NET INTERNAL ENERGY

CHANGE

192

Figure 7-9: Pipe heat loss to and from ambient air (kWh)

7.9 The Solar Cooling System’s Electrical Energy Consumption

Electrical energy is required to run the pumps for water flow between components, fan air

flow and chiller solution pump. The monthly total electrical energy consumption is shown in

Figure 7-10.

The electrical energy supply is almost constant as all the pumps are ON continuously except

the collector pump and the air fan. In January, February and December the fan is off when the

room temperature is lower than the thermostat control temperature range (21-26°C). The

solar collector water pump works only when solar energy is available during the day time.

There is a small variation from month to month due to the different number of days in each

month.

The total annual electrical energy consumption for the solar cooling system is 1575 kWh and

the total cooling load is 7291 kWh. Electrical energy represents about 21% of the total

cooling load. In practice, the electrical energy consumption could be reduced by additional

control as only the fan and collector pump are controlled and other equipment is always on

for the sake of simplicity in the simulation

-20

-10

0

10

20

30

40

50 Pipes to air heat loss (kWh)

PIPES TO AIR HEAT LOSS

193

Figure 7-10: Monthly electrical energy load (kWh)

The maximum electrical energy consumption (137 kWh per month) is during the summer

season. The lowest energy supply (114 kWh per month) is in February due to the lowest

number of days compared to other months and the fan is off for the first two weeks and

restarts when room temperature is in range of thermostat control.

7.10 Cooling Tower

An air cooled dry cooler is used for the simulation of cooling water for the chiller. The

operating parameters are described in Chapter 6 and in Appendix C. The heat rejected by the

cooler is simulation output and shown in Figure 7-11.

The heat rejected by the cooler is equal to the heat input from the tank hot water to the chiller,

heat absorbed from the air in the room, and the electrical energy input into the system.

The annual total heat energy rejected from the cooler is 19,836 kWh. The maximum heat

rejected (3,122 kWh) is in the month of June against its total capacity of 4,200 kWh. The

minimum heat rejection (48 kWh) is in January which is the heat input from the electrical

energy of the pumps.

0

20

40

60

80

100

120

140

160

Monthly electrical energy consumption (kWh)

Monthly electrical energy Load

194

Figure 7-11: Cooling tower heat rejected (kWh)

7.11 Absorption Chiller

A hot water operated absorption chiller with a rated cooling capacity of 3.52 kW is used. The

performance of the chiller is shown in Figure 7-12.

Figure 7-12: Chiller actual and rated COP

0

500

1000

1500

2000

2500

3000

3500

Cooling tower heat rejected (kWh)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70Chiller COP

ACTUAL RATED

195

The chiller performed at a rated COP (0.60) only from May to August during the peak

summer season. It is 0.59 in April, September, and October. In March and November the

COP is 0.58 and 0.57. In December, January and February it is very much less as cooling is

not required in these months. The reason for the COP being less than 0.60 is that the chiller is

always on even when cooling is not required.

The COP of the absorption chiller is same during cooling season as expected and calculated

in Chapter 6.

The maximum cooling load is 1165 kWh in June whereas the cooling capacity is 2535 kWh.

This difference is more than 50% due to variation in heat supply and hot water temperature to

the chiller as there is no backup heat source is installed. The over size of the absorption

chiller will increase the economics of the system. The cooling load of the room is already

explained in the room load Section 7.4.

7.12 Validation of Simulated Results

Validation is the act of comparing some data with reference data and drawing conclusions

from this comparison. Although most models are based on physical laws and material

properties, modellers needs some experimental data to test the model’s predictions. The

comparison is used to establish confidence that the model can be used to predict performance

where experimental data does not exist. In the comparison, the model can be evaluated by

system parametric analysis. An advantage of simulation is the ability to perform parameter

optimisation, which is difficult to do through experiments; however, a validated model allows

optimisation with confidence at minimal cost [383].

Anand et al. [384] carried out the first presented study for validation methodology for solar

heating and cooling systems and proposed a four level validation methodology. The first level

includes: use of measured system parameters (component data) and measured weather data

for simulation, to gain confidence in a known system under known conditions. Level two

validation deals with performance prediction accuracy when the input data used represent a

particular system. Level three includes the parametric variability for system performance to

establish the model validity for the field system which is yet to be installed. Level four is the

verification of simulation results from level three using field performance data.

196

The system variables they compared were: energy provided by solar, solar fraction, energy

supplied by auxiliary and collection efficiency. They proposed that variation of +/-10 %

between simulated and measured results for any program is satisfactory for the validation of

solar heating and cooling [384].

Thacker et al. [385] presented a study on concepts of modelling and validation. In this it is

established that it is desirable for a model to be accurate to within 10%. Bales [386] states

that a TRNSYS simulation for a heat exchanger with variation of more than 20% is

unacceptable. Kaplan et al. [387] recommend that for simulation of HVAC systems the

maximum allowable difference between the simulated and measured data should be 15-25%

(on a monthly basis) and 25-35% (on a daily basis), whereas for seasonal and annual periods

the simulated outputs should be within 25% and 10% respectively of the measured amounts.

7.12.1 Simulation Tool Validation

Many researchers have validated TRNSYS model simulation results with

experimental/measured results. For the current research TRNSYS has been used as the

simulation tool. The validation and accuracy of TRNSYS is described in Section 5.5.4 and it

shows maximum variation between simulation and experimental/measured data of less than

10%. The variation is in the acceptable range as described by the above references [384-387],

therefore it can be established that the methodology for the current research is valid and

accurate enough to simulate a solar cooling system.

7.12.2 Simulation Inputs Validation

According to Anand et al. [384] for validation of solar heating and cooling system, use of the

measured data inputs and measured weather data provide a confidence in the known system

under known conditions. For this research all of the input parameters of the solar cooling

system are from measured and validated literature data as described in Section 6.6. The

building model in section 6.1-6.2 and 6.5 is also an actual existing building. There are neither

hypothetical or assumed data used nor any which is not from any previous research work.

7.12.3 Simulation Results Validation

In the literature experimental and simulated data for a solar thermal absorption cooling

system with 3.52-4.5kW capacity is limited. Only four published references [162, 215, 217,

260] are available for this capacity range for climatic conditions in Malaysia, Qatar, UK, and

Turkey. None are available for Pakistan.

197

The results from the current simulation are, therefore, compared with these and other

published data for solar cooling systems of various sizes installed around the world. Priority

was given to comparison with the above mention similar capacity systems and, where

parameter data is mentioned, other literature is used. The current results are in close

agreement with these published results. The detail of this comparison is presented in Table 7-

1.

Table 7-1 Comparison of simulated vs published results

Parameter Current

simulation Published results Reference

Collector efficiency (%) 61 60, 63 Rosiek et al. [248]

Ayompe et al.[265]

Collector specific area (m2/kWc) 3.41 3.6 European commission SACE

[388]

Slope of collector (ᵒ) for maximum energy yield in summer

0 0 NASA, SSE[42]

Collector monthly yield (kWh/m2) 85 80 Blackman et al. [310]

Collector flow (kg/h) 165 150-200 Ssembatya et al. [210]

Collector outlet temperature (°C) 60-105 70-95 Agyenim et al. [260]

Tank volume specific volume (m3/kWc) 0.57 0.22 Agyenim et al. [260]

Tank volume to collector area (l/m2) 166 83 Agyenim et al. [260]

Storage tank heat loss co-efficient 0.20W/m2K 0.83W/m2K Shirazi et al. [389]

Chilled water outlet temperature (°C) 7-12 7-12 European commission

SACE[388]

Chiller COP 0.57-0.60 0.58, 0.60 Agyenim et al. [260]

Rosiek at al. [248]

Chiller electrical power (kWh/kWc) 0.020 0.018-0.027 European commission SACE

[388]

Room temperature set point (°C) 26 24, 25.5 Sim [215]

Fong et al. [390]

Solar fraction (%) 100 55, 83 Assilzadeh et al. [162]

Fong et al. [390]

Solar COP (COPth* ηcoll) 0.36 0.36-0.46 European commission SACE

[388]

Total electrical energy consumption to total cooling produced (%)

21% 24% Rosiek at al. [248]

Chiller operation hours /day (hrs) 24 7.5, 9 Agyenim et al. [260]

Sim [215]

System COP (Thermal +Electrical) 0.51 0.47 Agyenim et al. [260]

Electrical COP 4.62 3.62 Agyenim et al. [260]

Hot water storage capacity (hrs) 12 2 Sim [215]

Annual energy balance difference (%) 1.15 1 Thomas and Andre [391]

198

The comparison between simulated and published parameters shows good agreement with

each other. The exception is only in tank volume and solar fraction which is higher in the

current simulation for two reasons: i) the simulated system works as a standalone system

without any fossil fuel backup and ii) the chiller is operated continuously. The systems

studied previously by researchers were not standalone and operated for fewer hours.

7.12.3.1 Chiller Parameters Validation

TRNSYS, Type107 is used to model a hot water operated absorption chiller which uses an

external performance data file to simulate chiller performance. The results presented so far

are based on chiller operation using the TRNSYS provided chiller data file. The chilled water

outlet temperature data file for TRNSYS is shown in Figure7-13.

Figure 7-13: Chilled water outlet temperature with the TRNSYS provided data file

Reference [392] details the performance of an actual 17.6kW cooling capacity hot water

operated chiller. This data was used to generate a chiller data file which was used in the

TRNSYS simulation. The actual chiller data file is shown in Appendix C. The simulated

chilled water outlet temperature, by using the reference data file, is shown in Figure 7-14.

199

Figure 7-14: Chilled water outlet temperature with referenced data file

From Figures 7-13 and 7-14 it is observed that there is a good agreement between TRNSYS

and referenced data based chiller performance. There are minor differences in the chilled

water outlet temperature during summer and spring time, which is in total for 12 hours higher

than set point. However, this variation has not had any effect on the inside air temperature of

the building, which was below the set point in both cases at all times.

7.12.3.2 Energy Balance for the Solar Cooling System

The model solar cooling system integrated with the building includes many components with

energy loss and gain associated with each component. The energy inputs are cooling

delivered to the room, solar energy absorbed by the solar collector, heat gains by the heat

storage tank and pipes and electricity used by the pumps, chiller, and fan. The main energy

losses are heat rejected at the cooling tower and heat losses from the storage tank and pipes.

The solar cooling system simulation is validated by the energy balance of the system.

The total monthly energy input and output for the system is shown in Figure 7-15. The total

monthly input and output increase and decrease together as would be expected from the

200

variation of solar energy available and the cooling load. However, they are not quite equal.

The details of monthly energy input and output are in Appendix D.

Figure 7-15: Energy balance of solar cooling system

The distribution of the annual input and output for the solar cooling system energy is shown

in Figure 7-16.

Figure 7-16: Annual input and output energy distribution

0

500

1000

1500

2000

2500

3000

3500

System energy balance (kWh)

Total input Total output

0

5000

10000

15000

20000

25000

Input Output

Tank Heat Loss

Pipes Heat Loss

Cooler Heat Rejection

Heat from Room

Electrical Energy

Collector gain

Input output energy distribution (kWh)

201

Major input energy is from the collector (59%) and the room cooling load (34%), which is

93% of the total input. Major output energy is the heat rejected by the cooling tower, which is

about 93% of the total output (it is only coincidence that 93% occurs twice here).

The total annual energy input to the system is 21526 kWh and the total energy output is

21378 kWh. Annual energy input is more than output and the system surplus energy is 148

kWh.

In the simulation, the only energy storage in the solar cooling system is in the tank. The

difference between energy input and output should, therefore, correspond to the change in the

tank’s internal energy. The tank output data showed an annual net change in internal energy,

namely a decrease of 100 kWh. Thus the total discrepancy is 148 + 100 = 248 kWh, which is

1.15% of the total energy input. This discrepancy shows that there are some minor energy

losses in the simulation which were not accounted for.

A similar energy balance discrepancy was described by Thomas and Andre [391] in the range

of 90kWh to 370kWh due to the storage tank. TRNSYS technical support was contacted to

assist and it was confirmed that no system is present to investigate such discrepancies.

However, technical support described heat balance as a way of simulation validity.

As the energy balance discrepancy is well within the range generally regarded as an

acceptable error (Section 7.12), and it could not be explained despite exhaustive

investigation, it was decided to accept it.

7.13 Parametric Analysis

Saltelli et al. [393] defined the objective of parametric sensitivity analysis of a model to

investigate how a given model (numerical or otherwise) depends on its input factors. This

analysis is important in verification and validation of a simulation model.

The characteristics of a solar thermal system are the combination of variables acting together

with a changing pattern due to solar radiation variation. For operational parameter

optimisation, it is necessary to make rational choices between parameters such as collector

area, fluid flow rate and storage volume. The preference for operational parameter is not

sufficient; the effect on system performance must be judged quantitatively so that it can be

compared with the cost effect. Parametric studies refers to the investigation of performance

parameters such as collector area, flow rate and storage tank volume [394].

202

Parametric analysis of a solar thermal system is carried out by few researchers. The summary

of available important studies is shown in Table7-2 and described here.

Table 7-2: Summary of parameters used by researcher for parametric analysis

Researchers Parameters

Collector area Tank volume Collector flow Other parameters

Saltelli et al. √ √ √

Lunde √ √ √

Calise √ √ √

Hang et al. √ √

Villar et al. √ √ √

Sim √ √

Ssembatya et al. √ √

Arsalis √ √ √

He et al. √

Shirazi et al. √ √ √

Lunde [394] describes that the important parameters for parametric analysis are collector

area, storage capacity, collector orientation and collector type. Venegas et al. [264] carried

out parametric analysis for solar absorption of a cooling system and observed that a major

effect on solar COP, cooling energy produced and duration of cooling production, is due to

radiation. Calise [297] carried out a parametric sensitivity analysis for a solar heating and

cooling system for the collector area, collector outlet temperature and tank volume to solar

collector area for different European cities. Hang et al. [395] carried out a parametric

sensitivity analysis for solar fraction with the change in storage tank to collector area ratio

for a solar cooling system. Villar et al. [300] carried out a sensitivity analysis for storage tank

volume, collector area and slope, chiller COP and solar energy collected for a solar

absorption cooling system in different configurations. Sim [215] performed a parametric

sensitivity analysis for collector slope and area, storage tank volume and effectiveness of a

heat exchanger for a solar cooling system. Praene et al. [396] carried out a parametric

sensitivity analysis to optimise a solar absorption cooling system for distance between

collector and hot water storage tank, chiller and collector inlet temperature. Ssembatya et al.

[210] did a parametric analysis for collector area, water flow rate and slope with chiller inlet

temperature to improve solar fraction for a solar cooling system. Arsalis [397] performed a

203

parametric study for collector area and tilt angle and storage tank volume for a solar heating

and cooling system. He et al. [351] carried out a parametric analysis of heat storage tank

volume for solar yield. Shirazi et al. [389] performed a parametric analysis for storage tank to

collector area ratio, collector specific area on primary energy saving, collector area and heat

storage tank volume on a solar assisted heating and cooling absorption system.

From the above referenced literature, it is clear that the parameters most commonly regarded

as important are storage tank volume, collector area and collector water flow rate. For the

current research work these three most common parameters were selected for parametric

sensitivity analysis and results were observed annually. It is reasonable to assume that the

chiller, cooling coil, cooling tower and their associated pipes, pumps and fans would be sized

for the building's design cooling load. The details of the parametric analysis for the collector

area, collector flow and storage tank volume are described here. During the parametric

analysis it was observed that when the room temperature increases above the thermostat

upper limit (26°C), the simulation stops working (controller stuck error from TRNSYS) due

to significantly less heat input compared to cooling load. However, for optimised parameters

simulation works normally and no error was observed.

7.13.1 Collector Area and Flow

Collector area directly affects the solar energy gained. The collector area and flow rate are

varied and the change in collector energy gain and efficiency is observed. The results are

shown in Figure 7-17.Figure 7-17 shows that increasing the collector area increases both,

energy collected and collector efficiency for same flow. With a change of area from 6m2 to

12m2, the annual energy collected varies from 9.7 MWh to 12.66 MWh and the collector

efficiency from 54% to 61%. The reason is collector efficiency increases as the collector

outlet temperature decreases with increase in area keeping constant flow. The evacuated tube

collector efficiency with collector and ambient temperature difference is shown in Figure 6-

24.

For a collector area less than 6m2, the simulation also stops working (mathematical error

from TRNSYS) as the heat input is significantly less than the cooling load during summer

season.

204

Figure 7-17: Sensitivity of collector area and annual energy collected and efficiency

The change in collector flow rate effect on collector energy gain and collector efficiency is

shown in Figure 7-18.

Figure 7-18: Sensitivity of collector flow rate and annual energy collected and efficiency

Figure 7-18 shows that increasing the collector flow slightly increases the energy yield and

efficiency. The change of flow rate from 40 to 165 (kg/h), changes the annual energy

collected from 12.30MWh to 12.66MWh and collector average efficiency from 58.5 to 61%

respectively. The reason is as the flow increases the collector outlet temperature decreases for

constant area, which increases efficiency.

8

9

10

11

12

13

14

52

53

54

55

56

57

58

59

60

61

62

6 8 10 12

Ener

gy (

MW

h)

Eff

icie

ncy

(%

)

Area (m2)

Collector area

Collector efficiency (%)

Energy collected (MWh)

12.25

12.3

12.35

12.4

12.45

12.5

12.55

12.6

12.65

12.7

58

58.5

59

59.5

60

60.5

61

61.5

20 60 100 140 180

Ener

gy (

MW

h)

Eff

icie

ncy

(%

)

Mass flowrate (kg/h)

Collector Flow Collector efficiency (%)

Energy collected (MWh)

205

7.13.2 Storage Tank Volume:

A change in heat energy storage tank volume and its effect on annual tank heat loss, collector

efficiency, and change in internal change is shown in Table 7-3. Table 7-3 shows that

increasing the storage tank volume increases the tank heat loss reduces collector efficiency

and increases the tank internal energy change. As with less volume surface area is less, the

heat loss is lower from the tank. Whereas, lower volume results in less thermal storage and

tank water temperature will be lower so with lower collector input water temperature and

increase collector efficiency.

Table 7-3: Sensitivity of storage tank volume on tank heat loss and internal energy and collector efficiency

Tank volume (m3) Tank heat loss (kWh) Collector efficiency (%)

0.40 723 66

0.80 1003 64

1.20 1174 63

1.60 1293 62

2.00 1428 61

7.13.3 Chilled Water Outlet Temperature

The simulated chilled water outlet temperature is a key system variable , because it only rises

above its set point if the chiller is unable to meet load due to lower heat energy input. The

simulated room temperature does not respond so clearly or quickly because of varying room

heat gains, thermostat settings, and room thermal capacity. The simulation also stops working

when the room temperature is above the thermostat upper limit (error message from

TRNSYS).

206

Figure 7-19: Variation of maximum chilled water temperature and number of hours above set point with collector area

The effect of collector area on maximum chilled water outlet temperature and number of

hours during the year when chilled water outlet temperature is above set point (7°C) is shown

in Figure 7-19. From Figure 7-19 it is clear that both the maximum chilled water temperature

and number of hours when the chilled water temperature is above the set point, increases with

a decrease in collector area.

The effect of collector flow rate on the maximum chilled water outlet temperature and

number of hours during the year when the chilled water outlet temperature is above set point

(7°C) is shown in Figure 7-20.

0

50

100

150

200

250

300

350

6 8 10 12

6

7

8

9

10

11

12

Tem

peratu

re (

C)

Collector area (m2)

Ho

urs

Maximum Chilled water temperature

Maximum Chilled water temperature

Number of hours temperature above setpoint

207

Figure 7-20: Variation of maximum chilled water temperature and number of hours above set point with tank

storage volume

From Figure7-20 it is clear that both the maximum chilled water temperature and number of

hours when the chilled water temperature is above the set point, increases with a decrease in

collector flow rate. Chilled water temperature and number of hours when it is above set point

remains the same when the collector water flow rate is decreased from 65kg/h to 40kg/h.

The effect of hot water storage volume on maximum chilled water outlet temperature and

number of hours during the year when the chilled water outlet temperature is above set point

(7°C) is shown in Figure 7-21.

Figure7-21 shows that both the maximum chilled water temperature and the number of hours

when the chilled water temperature is above the set point, increases with a decrease in storage

tank volume.

6

6.5

7

7.5

8

8.5

9

9.5

10

10.5

11

0

20

40

60

80

100

120

40 65 90 115 140 165

Tem

peratu

re (

C)

Hou

rs

Collector Flow (kg/h)

Maximum chilled water temperature

Number of hours temperature above setpoint

Maximum chilled water temperature

208

Figure 7-21: Sensitivity of storage tank volume and maximum chilled water temperature and number of hours

above set point

It was concluded that an evacuated tube collector area of 12 m2, collector flow rate of 165

kg/h and storage tank volume of 2m3 would provide satisfactory performance of 3.52kW

absorption chiller. These values were used for the final results described in Sections 7.2 to

7.11.

7.14 Conclusion

A solar thermal cooling system integrated with a building model for one room of a single

family house in Pakistan was simulated to maintain a comfortable room temperature. The

house was of standard construction and did not include any measures to reduce the cooling

load.

The values of three key design variables (collector area, collector flow rate and storage tank

volume) were initially found through simplified calculations and then optimised by trial and

error using repeated simulations. The optimum values were the minimum values which

enabled the system to maintain the required room temperature throughout the cooling season,

with no auxiliary heat input in addition to the solar collector. It was found that the optimised

values were close to the initial values.

6

7

8

9

10

11

12

0

50

100

150

200

250

300

0.4 0.8 1.2 1.6 2

Tem

peratu

re(C

)

Ho

urs

Storage tank Volume (m3)

Maximum chilled water temperature

Number of hours temperature above setpoint

Maximum Chilled water temperature

209

For the optimised system:

• The required collector area (gross), flow rate, and storage tank size were respectively

12 m2, 165 kg/h and 2 m

3.

• The annual electricity consumption for the system was 21% of the cooling load, but

this could be reduced by improved controls.

• The annual heat loss from the storage tank was 11.30 % of the total energy collected

and most of this was in winter.

• The simulation results showed good agreement with published results from other

researchers.

• The energy balance of the system showed a small discrepancy (approximately 1%)

between the annual energy input and output, which was in the same range as reported by

other researchers.

A parametric analysis was performed on the collector area, collector flow rate and storage

tank volume. It was found that varying the collector area had the largest effect on system

performance, followed by varying the storage tank volume. Varying the collector flow rate

had the smallest effect.

The overall results showed that Pakistan’s climate has a potential for solar powered thermal

space cooling systems. It is feasible to use a solar thermal powered cooling system to meet

the space cooling load for a single family house in the summer season.

210

Chapter 8: Conclusions and Recommendations

8.1 Summary

The use of solar energy for cooling purposes is an attractive prospect; the key factor for this

application is the availability of solar energy for a specific location and climate and suitable

cooling technology. Currently, flat plate or evacuated tube collectors with absorption cooling

technology could be used for solar cooling systems, as an alternative to fossil fuel based

conventional electrical powered cooling systems. For hot climates like Pakistan, a solar

cooling system could be a sustainable, clean, and viable system to meet cooling energy

demand.

8.2 General Discussion

8.2.1 Main Finding: Feasibility of Solar Thermal Cooling of a Building in Pakistan

The results showed that solar thermal cooling for a typical existing building in Pakistan is

feasible; the main aim of this research was to test whether this was so. The designed solar

cooling system successfully maintained the room temperature below 26°C throughout the

year without any backup heat source. The final system configuration and equipment sizes are

comparable to previous published work and are shown in Chapter 7. The final solar powered

cooling system for a 42m3 room with 100% solar fraction consists of 12m

2 (gross area) of

evacuated tube collectors lying horizontally, a 2m3 hot water storage tank and a 3.52kW

capacity absorption chiller. It was noted that published simulated and experimental studies

generally mention collector aperture area, which is less than gross area.

Strength of this research is that all the building dimensions, materials, heat gains, solar

thermal cooling equipment operation parameters are based on published or actual data. None

of the input parameters are assumed or hypothetical, which helps to ensure the validity of the

research as described in Chapter 7.

The major limitation of this research is that it is a theoretical study carried out with one

building model and one solar thermal cooling system. Different building models, solar

collectors, and thermal cooling systems are possible. A variant mentioned by most

researchers is that the system cost and component sizes can be reduced by adding a backup

heat source. A designer of a real system would need to consider the advantages and

disadvantages (e.g. capital cost, running costs, and availability) of a system with or without

possible backup heat sources before choosing the most suitable configuration.

211

8.2.2 Building Model and Energy

One of the research objectives was to gather information needed to construct a suitable

building model for the simulation work, including information on building constructions,

building energy efficiency and indoor comfort conditions in Pakistan; these are discussed in

Chapters 3 and 5. It was observed that in previous studies of solar cooling, no detail is

provided about the building dimensions, thermal properties, or internal heat gains. Building

energy efficiency is key factor for cooling system design and performance but is not

mentioned by many researchers when reporting research into solar thermal cooling systems.

An advantage of the current research is that all these details are provided.

Existing buildings in Pakistan are generally not energy-efficient. As the building model in

this research was intended to represent a typical existing building, there is scope for reducing

the heat gains and cooling equipment sizes by improving the thermal properties of the

building. The UN-habitat program [112] showed that there is potential for this in existing

buildings. Future research work can be carried out to improve building energy efficiency,

thermal comfort and cooling system sizes.

8.2.3 Methodology

As suitable experimental facilities were not available, it was decided to investigate the

feasibility and performance of the solar thermal cooling system by simulation. TRNSYS

software was selected for this; details are presented in Chapter 5. Many researchers have

validated TRNSYS simulation results with experimental results for solar thermal systems and

established that it is a suitable tool for such simulations. Another advantage is that TRNSYS

contains suitable typical weather data for Pakistan, which is not conveniently available from

any other source. The main limitation of using simulation for this research is that no

experimental data is available for Pakistan for comparison and validation.

To test the validity of the simulation results, they were compared with published results from

other researchers and a chiller performance data file was created to validate the chiller

operation. It was found that all the results agreed well with those from other researchers and

Validation is described in Chapter 7.

8.2.4 Solar Cooling System and Operational Parameters

The details of solar cooling systems and operational parameters are described in Chapter 4

and 6 respectively. The selected components are well tested by other researchers, and data is

available for operation and results validation. The selected components have relatively high

212

thermal efficiency and low heat losses compared to others in similar categories. A limitation

is that comparisons cannot be drawn for different components for Pakistan climatic

conditions; future work could be carried out for this.

The component sizes for the solar energy collection and building cooling systems were

estimated by simple mathematical calculation using reference data as described in Chapter 6.

It was decided to investigate the feasibility of a system with no auxiliary heat source, as

electricity outage hours are high as mentioned in Chapter 1. Having no backup heat source

requires increased sizes of some components, which would increase some costs and energy

losses. On the other hand, the costs and energy losses associated with a backup heat source

are avoided.

Solar electricity generation and storage using photovoltaic panels and batteries is now a well

proven technology, and the electrical energy consumption of a solar thermal cooling system

should be comparatively low. It was therefore decided not to investigate the supply of solar

photovoltaic electricity for operating the solar cooling system's pumps, fan, and controls.

The system's thermal losses and electricity consumption in the simulation results are higher

than they would need to be in reality, as most of the simulated components operated

continuously even when cooling was not required (for convenience in constructing the

simulation model). The COP of the absorption chiller was also set to a lower conservative

value (0.60) rather than the manufacturer's rated value (0.70), which led to a higher energy

input, larger collector area and larger storage tank. Most previous studies have used a higher

COP; however, with these limitations the results of this research are better than those found

by other researchers in terms of specific sizes and efficiencies, as described in Chapter 7.

Most researchers have set the collector tilt angle to the location latitude; in this research the

collector tilt is set to zero, as this maximises the available energy during the hottest summer

months at the location of interest (Lahore). It was observed that none of the researchers have

mentioned Incident Angle Modifiers (IAMs), which are important parameters for evacuated

tube collector operation. IAMs were incorporated into the collector model in this research,

and were found to increase the collector efficiency.

Other important system parameters which are not available in the cited literature but are

provided here include the building cooling fan and coil capacities and operational parameters,

and the hot water storage tank and pipes heat loss coefficients and insulation details.

213

8.2.5 System Optimisation

Chapter 6 presents the calculations for the solar thermal cooling system initial parameters,

which were used to start the simulation work. Initial parameter value calculations are not

available from other authors. When the simulation was configured so that it operated

successfully with all the components connected, it was run for different durations (one

month, six months, and one year) with different time steps (one hour, 30 minutes, 15 minutes

and 5 minutes). It was found that 15 minutes time step and one year continuous operation

yielded satisfactorily detailed and stable results.

Advantages of this research are that the system behaviour during a whole year was analysed,

whereas in all experimental and simulation studies by other researchers the operation duration

is limited to few hours, days, weeks or months only, and that different time steps and

durations have been tested, whereas other researchers have used only single time step (mostly

one hour) and duration for their results.

System parameters were changed by trial and error for repeated simulations to find optimum

parameter values, as presented in Chapter 7. A limitation of this methodology was the time

taken, as there is no specific standard for solar cooling systems to guide the choice of

parameter values. To obtain the final results hundreds of different combinations were

simulated and analysed to find the best configuration.

During simulation it was noted that a higher hot water storage temperature gave better chiller

performance but reduced the collector efficiency. Most researchers have not mentioned this

relationship in their publications.

It was observed that the values of some parameters (e.g. collector flow and chiller capacity)

were almost unchanged from the initial estimates to the final optimised values. This means

that simple calculations can be used to obtain good estimates of some required parameters.

8.2.6 Results Validation and Sensitivity Analysis

All the results are in good agreement with the published results, as described in Chapter 7.

The hot water storage tank size is larger than reported by other researchers, which is because

in this research the system operates continuously and meets the entire cooling load.

The results are more detailed than those provided by previous researchers. A detailed chiller

performance data sheet was constructed to validate chiller operation, which was performed

214

before only by two researchers. The number of parameters validated (more than 10) is more

than considered by previous researchers.

Energy balances were constructed as part of the validation, and showed that energy inputs

and outputs were equal within less than 1%. This is within the acceptable range reported by

other researchers. An energy balance of the whole system was constructed, which has not

been reported by any other researcher.

A sensitivity analysis was carried out for the effect of selected parameters of the solar energy

system (collector flow, collector area and storage tank volume) on the system performance.

These were chosen because they were expected to have the largest effect. This analysis

showed that their order of importance was firstly collector area, then storage tank volume,

and finally collector flow rate. Few researchers have performed sensitivity analysis on solar

thermal cooling systems; their results are similar to those found here.

The system performance measure used in this analysis was the chilled water outlet

temperature, as it was found that this was maintained at its set point in the simulation

provided the chiller was not overloaded and had sufficient heat available. Room temperature

was a less useful measure of performance, as this was affected by room heat gains and losses,

and control action. For experimental studies, on the other hand, researchers have used chiller

inlet hot water temperature as a solar energy system performance criterion, as this can be

changed with a backup heat source.

8.2.7 Conclusions and Recommendations

The conclusions mentioned above and described in more detail in Section 8.3 are validated,

and can provide confidence to designers for the application of solar thermal cooling systems

in Pakistan. However, the simulation results are limited to one combination of system

components, and do not provide system selection or design guidelines. Further research is

required to study different combinations of systems and components to select the most

suitable ones for Pakistan's conditions.

The recommendations of the research are described in Section 8.4. The most important are

related to Pakistan's energy crisis, the importance of building energy and comfort, solar

powered cooling systems, and alternative and sustainable energy sources. The main

advantage of implementation of these recommendations is that these would not only help to

overcome the energy shortage but also provide an alternative, sustainable, and reliable energy

215

source. The limitation will be that the cost of the proposed system may be higher, and

subsidies and supportive plans may be required for implementation as mentioned by some

researchers. There is a need for sincere commitment and persistent policies, which will

probably be difficult to maintain in view of the history of energy management in Pakistan.

8.2.8 Addition to Knowledge

This research is the first study of a building integrated solar absorption cooling system for

Pakistan or India. Continuous operation without a backup heat source is also an advance on

previous knowledge, worldwide and in the region, as most studies have been for a few hours

or days operation and with a backup heat source. More detailed results than other similar

research, and detailed validation of the simulation at each step, are prominent features of this

research. The results can be applied to existing buildings, but this research also shows that

existing buildings are not energy-efficient and there is potential for improvement. Details of

solar collector incident angle modifiers, storage tank and pipes heat losses, and the system

energy balance are also additions to previous available knowledge.

8.3 Conclusions

The research presented here demonstrates that cooling through a single-effect absorption

chiller connected to a solar collector with a hot water storage tank can maintain room comfort

for the climate in Pakistan.

The first objective was to analyse energy scenarios, supply and demand, and the renewable

energy potential in Pakistan. The literature on Pakistan’s energy data showed that the primary

source of energy is fossil fuels and the use of renewables is negligible except in the case of

hydroelectric energy [3]. The domestic sector is badly impacted upon by energy crises and

building indoor comfort is often not achievable in the hot summer season due to power cuts

[17]. The future demand and supply data showed that the country will be energy deficient in

meeting the demand until 2019 [20]. It is concluded that there is a need for an alternative and

sustainable source to meet energy demand in the country. It is important that a newly-

developed system can save electricity and help meet domestic sector comfort demands.

The second objective was to review renewable resources, specifically solar energy. In

Pakistan, the resource potential of about 60GW from each hydroelectric and wind energy

216

source has been identified [27, 28]. The wind energy potential is mainly limited to relatively

small coastal areas, while political rifts and environmental issues are significant hurdles in the

utilisation of hydroelectricity[33]. The solar energy potential of Pakistan is greater than that

of any other renewable source with a daily average insolation of 4-6kWh/m2/day and 8-10

sunshine hours/day all over the country [49]. Pakistan is suitable for the application of all

types of solar energy technologies as there is no political or environmental problem with solar

energy as with wind and hydroelectric power. This potential could provide sustainable energy

for current and future demand.

The third objective was to study climatic conditions, indoor comfort conditions and their

relationship to the building energy code of Pakistan. The climate of Pakistan is generally arid

with hot summers and relatively cold winters. About 80% of population (total 184 million)

[69], in the country lives in climatic condition with hot summer season, required cooling

systems for comfort. Extreme high temperatures have increased in frequency and severity in

the past decades and this is increasing energy demand for cooling [84]. Energy demand in

buildings is increased by 15% per annum in Pakistan [104]. There is a negligible application

of building energy codes and most buildings are energy inefficient. There is the overall

potential to save about 30% of energy in buildings by applying building energy codes and

other measures [111]. Simple radiative, insulative, and reflective materials can decrease the

room temperature in the summer season and reduce a building’s cooling energy demand

[112].

The fourth objective was a literature review of solar cooling systems and especially solar

cooling in hot climates, and this was aimed at identifying the current state of knowledge

about solar cooling system technology relevant to the climate of Pakistan. Solar thermal

cooling application started in the early 1960s and more than 1,200 systems have been

installed worldwide [173]. In hot climates such as Pakistan, solar thermal is preferable to

solar electric cooling both in terms of efficiency and load compatibility [24]. The climate of

Pakistan is favourable for solar cooling applications as the greatest cooling loads and solar

energy availability occur at about the same time in summer. Stationary collectors, flat plate

and evacuated tube, are most commonly used for solar cooling applications as they are much

cheaper than concentrating (tracking) collectors, and can generate sufficiently high

217

temperatures for solar cooling. Evacuated tube collectors are preferred over flat plate

collectors due to their higher thermal efficiency and higher temperature output [183]. The

average area required for a flat plate collector is 4.6m2/kWC, whereas for an evacuated tube

collector it is 2.5m2/kWC [184]. An absorption cooling system is more efficient than other

thermal cooling systems [132].

The fifth objective of the research was the selection of a suitable analysis methodology.

TRNSYS is a comprehensive computer program which is widely used for dynamic

simulation of building integrated solar energy systems. The accuracy of TRSNSY for solar

energy systems has been tested by many researchers and found to be within +/- 10% variation

of experimental data [336]. Weather data is a key input for solar cooling systems and building

energy simulation. Suitable typical weather data (TMY2) for five cities in Pakistan is

provided with TRNSYS [361]. A building model was created to simulate part of a typical

house in Pakistan with actual dimensions and construction materials.

The last objective was to perform a simulation, analyse the results and produce

recommendations. The simulation was performed for a solar powered cooling system with an

evacuated tube collector, hot water storage tank, absorption chiller, and dry cooler. The

simulation was performed in the TRNSYS environment and the system operated

continuously for 1 year (8,760 hours).The simulations results showed that a final optimum

system for a 42m3 room consists of 12m

2 (gross area) of evacuated tube collectors lying

horizontally with 2m3 of hot water storage tank for 3.52kW absorption chiller capacity. It is

concluded from the simulation of the system that, on an annual basis without a backup heat

source, 100% of the heat input demand can be covered with solar energy and the system can

meet the building cooling loads.

The component model of the absorption chiller needs a specific data sheet for its performance

description. An actual chiller performance data sheet was constructed specifically for the

current research [392]. The results showed a very good agreement of chiller performance

between TRNSYS default chiller data and actual data.

The accuracy of the model was investigated by validating the results with published and

standard parameters. All the inputs are referenced to increase the model validity and

218

accuracy. All the results are in good agreement with the published results. A sensitivity

analysis was carried out for the effect of selected parameters on collector flow, collector area

and storage tank volume on the chilled water outlet temperature. This showed that the order

of importance of these parameters for system performance was, firstly, the collector area,

then the storage tank volume and, finally, the collector flow rate.

8.4 Recommendations

8.4.1 Energy and Solar Energy Data

There should be one agency which should publish authentic and accurate energy statistics

data for research and other use. Similarly, CO2 and other greenhouse gases emission and

country population data for Pakistan are not available from any public agency of the country

[69]. The available data is years old and need verified up to date from public agency.

The theft, transmission, and distribution losses and less recovery of bills are main contributor

of current crisis which need to be overcome with better policies and management as done in

many developed countries.

The renewable energy resource (Solar, wind and hydroelectric energy) should be utilised to

help meet current and future energy demand. The future energy projects plans should target

the use of these green energy resources with countable share in energy mix. The use of solar

energy based products can help to meet basic needs for light and other utilities.

The use of off grid PV systems in the remote areas of Balochistan, KPK, Sindh, and south

Punjab can provide electricity in areas which are not connected to national grid system due to

low population density.

There should be comprehensive solar energy potential mapping for the country as Raja’s

work is confined to five cities[46]. The reliable and long term data are mandatory for

successful solar energy system design and operation.

8.4.2 Building Energy and Efficiency

Buildings in Pakistan are not energy efficient due to a lack of the application of any building

energy code and standard. The building sector is a major consumer of electricity in the

country; energy savings in buildings would reduce electricity demand and improve the

comfort of buildings in the summer [111].

219

New building codes (as in Turkey) should be introduced for energy efficient buildings in

Pakistan to improve energy efficiency in existing buildings.

The materials and techniques used by UN-HABITAT for improving energy efficiency of

existing buildings have improved the comfort inside. The best material was paper board in

term of cost and comfort [112]. This material should be used in current building to reduce

cooling load and increase comfort.

The building simulation results showed the use of double glazed windows in place of

currently used single glazed windows or steel shutters can improve comfort, infiltration and

heat gains and losses in buildings.

8.4.3 Solar Thermal Cooling

Solar absorption cooling systems can be a sustainable and green solution as cooling demand

for the building and solar radiation intensity take place more or less at the same time. It is

recommended to promote use of these systems for cooling in Pakistan.

The simulation results showed that in the proposed solar thermal cooling system, heat energy

collected is not used in winter months. This excess energy can be used for domestic hot water

in winter season when there is shortage of natural gas supply.

8.5 Further Studies

8.5.1 Building Energy and Efficiency

The research work on building energy, efficiency, and efficient building materials in Pakistan

is limited. Building heating and cooling load with current materials should be investigated in

details for all five climatic regions of Pakistan.

The results for a typical building are specific and depend upon building geometry,

construction material and the cooling system in use. The cooling load also depends upon

human occupancy and activities. Cooling is required only in the summer and the simulation

was carried out for a year. The results may be further split into summer and winter seasons

for separate analysis of cooling and heating output for future research.

Further work could be carried out to identify the energy efficient building materials with the

minimum heat gains and cooling load for the all the climatic regions of Pakistan.

220

The current research was carried out for ASHRAE standard thermal comfort condit ion.

Further research can be carried out for adopted thermal conditions for each climatic region of

Pakistan for small sizes of cooling systems and economics.

8.5.2 Solar Cooling System

In the current research, only two components were controlled and operated and only when

required. All other components (chiller, fan, cooling tower, and cooling coil) were working

continuously. Further research could be carried out to improve the system control so it

includes realistic controls for pumps and the chiller to reduce the electricity consumption.

Further research work could be carried out to investigate the effect of different types of

collectors and cooling systems on system efficiency and energy consumption for the climate

of Pakistan.

This research is carried out using vapour absorption cooling system for Lahore climate.

Further research can be carried out by using different cooling system in all climatic regions to

establish the most suitable technology for each region.

Further research can be carried out by using backup heat source and optimise the share of

solar energy in the total energy supply with minimum collector and storage sizes.

Further research can be carried out for hybrid solar thermal heating and cooling system for

different climatic regions of Pakistan in combination with wind, micro hydroelectric and geo

thermal energy.

An experimental setup can be to assess the performance of actual solar cooling system and

can be optimised using the TRNSYS results and the performance of both systems can be

compared.

In this research the tilt angle of the solar collector was fixed to zero. Further research can be

carried out for monthly, seasonal, and annual tilt angle for maximum energy yield of

collector.

This work was performed for a solar thermal cooling system with grid supplied electricity.

Further research could be carried out by providing solar PV based electrical energy for a

standalone and self-sufficient solar powered cooling system.

221

The economic analysis of solar cooling system can be carried out for Pakistan climate. The

most economical configuration for solar cooling system can be figured out. Furthermore the

economics of each solar cooling system for specific region can be established.

Further research can be carried out to compare the solar thermal and solar electric cooling for

different climatic regions of Pakistan and suitable system can be recommended.

222

References

1. Muneer, Tariq, Muhammad Asif and Saima Munawwar, Sustainable production of

solar electricity with particular reference to the Indian economy. Renewable and

Sustainable Energy Reviews, 2005. 9(5): p. 444-473.

2. Muneer, T. and M. Asif, Prospects for secure and sustainable electricity supply for

Pakistan. Renewable and Sustainable Energy Reviews, 2007. 11(4): p. 654-671.

3. British Petroleum, Statistical review of world energy June 2014. 2014.

4. British Petroleum, BP energy outlook 2035. BP stats, Jan, 2014.

5. Birol, F, World Energy Outlook 2013. International Energy Agency, Paris, France, ,

2013.

6. Haukkala, Teresa, Does the sun shine in the High North? Vested interests as a barrier

to solar energy deployment in Finland. Energy Research & Social Science, 2015. 6: p.

50-58.

7. World Bank. Energy use per capita. 2014 [cited November 2014.

8. Brander, Matthew, Aman Sood, Charlotte Wylie, Amy Haughton, and Jessica Lovell,

Technical Paper| Electricity-specific emission factors for grid electricity. 2011,

Ecometrica.

9. Eni., World oil and gas review. 2014.

10. Ministry of Finance Pakistan, Economic survey of Pakistan 2014-15. 2015: Islamabad

Pakistan.

11. Qasim Mubashir, Kotani Koji, An empirical analysis of energy shortage in Pakistan.

Asia Pacific Development Journal, 2014. 21(1): p. 29.

12. Aftab, Safia, Pakistan's energy crisis:causes , consequences and possible remedies, in

NOREF Expert Analysis. 2014, Norwegian Peacebuilding Resource Centre (NOREF):

Oslo, Norway.

13. Government of Pakistan, Policy for development of renewable energy for power

generation, employing small hydro, wind anfd solar technologies. 2006, Ministry of

water and power: Islamabad Pakistan.

14. Amer, Muhammad and Tugrul U Daim, Selection of renewable energy technologies

for a developing county: a case of Pakistan. Energy for Sustainable Development,

2011. 15(4): p. 420-435.

15. Government of Pakistan, National power policy 2013. 2013, Ministry of Water and

power: Islamabad Pakistan.

16. National Transmission & Dispatch Company, Power Systems Statistics 2013-14.

2014, Planning Power NTDC: Lahore. p. 70.

17. Pasha, Hafiz A and Wasim Saleem, The Impact and Cost of Power Load Shedding to

Domestic Consumers. The Pakistan Development Review, 2013. 52(4): p. 355-373.

18. Sher, Hadeed Ahmed, Ali F. Murtaza, Khaled E. Addoweesh, and Marcello

Chiaberge, Pakistan’s progress in solar PV based energy generation. Renewable and

Sustainable Energy Reviews, 2015. 47: p. 213-217.

19. Government of Pakistan, Annual plan 2015-16. 2015, Planning comission of Pakistan:

Islamabad Pakistan. p. 121-137.

20. Nepra, State of industry report 2014. 2014: Islamabad Pakistan. p. 9-10.

21. Pokharel, Bipin, Mark A Curtis, Gordon M Hickey, and Michel A Bouchard, Power

shortage, its impacts and the hydropower sustainability assessment protocol: in the

context of South Asia. 2010, Masters Thesis submitted to the Depart of Natural

Resource Sciences, McGill University, MacDonald Campus, Montreal, QC, Canada.

223

22. Eicker, Ursula, Dirk Pietruschka, Maximilian Haag, and Andreas Schmitt, Energy and

Economic Performance of Solar Cooling Systems World Wide. Energy Procedia,

2014. 57: p. 2581-2589.

23. Hartmann, N, C Glueck and Fp Schmidt, Solar cooling for small office buildings:

Comparison of solar thermal and photovoltaic options for two different European

climates. Renewable Energy, 2011. 36(5): p. 1329-1338.

24. Mateus, Tiago and Armando C. Oliveira, Energy and economic analysis of an

integrated solar absorption cooling and heating system in different building types and

climates. Applied Energy, 2009. 86(6): p. 949-957.

25. Welling, Robin M., Solar Thermal Markets in Europe, in Trends and Market

Statistics 2014. 2015, European Solar Thermal Industry Federation (ESTIF): Brussels.

p. 1-20.

26. Kalkan, Naci, Ea Young and Ahmet Celiktas, Solar thermal air conditioning

technology reducing the footprint of solar thermal air conditioning. Renewable and

Sustainable Energy Reviews, 2012. 16(8): p. 6352-6383.

27. Pakistan Meteorological Department. PMD wind energy project. 2015 [cited 2015 15

April]; Available from: http://www.pmd.gov.pk.

28. Nepra, State of industry report 2013. 2013: Islamabad Pakistan.

29. Ali, Jawad, Tor A Benjaminsen, Ahmed A Hammad, and Øystein B Dick, The road to

deforestation: An assessment of forest loss and its causes in Basho Valley, Northern

Pakistan. Global Environmental Change, 2005. 15(4): p. 370-380.

30. Aedb Pakistan. wind resource potential. 2015 [cited 2015 25 June]; Available from:

www.aedb.org.

31. Dai, Kaoshan, Anthony Bergot, Chao Liang, Wei-Ning Xiang, and Zhenhua Huang,

Environmental issues associated with wind energy–A review. Renewable Energy,

2015. 75: p. 911-921.

32. Ministry of Finance Pakistan, Economic survey of Pakistan 2013-14. 2014: Islamabad

Pakistan.

33. Khalid, Iram and Ishrat Begum, Hydro Politics in Pakistan: Perceptions and

Misperceptions. South Asian Studies, 2013. 28(1): p. 7-23.

34. Ppib Pakistan, hydro power resources of pakistan. 2011, Ministry of water and power:

Pakistan. p. 9-10.

35. Biernat, Krzysztof, Artur Malinowski and Malwina Gnat, The Possibility of Future

Biofuels Production Using Waste Carbon Dioxide and Solar Energy. 2013.

36. Trenberth, Kevin E, John T Fasullo and Jeffrey Kiehl, Earth's global energy budget.

Bulletin of the American Meteorological Society, 2009. 90(3): p. 311-323.

37. Bent Sørensen, Solar Power, in Renewable Energy Focus Handbook. 2009, Academic

press: USA. p. 341-382.

38. Ener Data. Global energy statistical year book 2015. 2015 [cited 2015 15 July ];

Available from: www.enerdata.net.

39. Philibert, Cédric, Technology roadmap: concentrating solar power. 2010:

OECD/IEA.

40. Duffie, J.A. and W.A. Beckman, Solar Engineering of Thermal Processes. 2006:

Wiley.

41. Awan, Ahmad Bilal and Zeeshan Ali Khan, Recent progress in renewable energy–

Remedy of energy crisis in Pakistan. Renewable and Sustainable Energy Reviews,

2014. 33: p. 236-253.

42. Nasa. Surface Meteorology and Solar Energy. Renewable Energy Source website

2014 [cited 2014 30-11-2014]; 6.0:[

224

43. Sukhera, Mb and Mar Pasha, Solar radiation maps for Pakistan. Solar & wind

technology, 1987. 4(2): p. 229-238.

44. Sukhera, Mb, Mar Pasha and Ms Naveed, Solar radiation over Pakistan—

Comparison of measured and predicted data. Solar & wind technology, 1986. 3(3): p.

219-221.

45. I.A.Raja, Assessment of Solar Radiation in Pakistan, in Energy Studies Unit,. 1992,

University of Strathclyde, Glasgow: U.K.

46. Raja, I. A. and J. W. Twidell, Distribution of global insolation over Pakistan. Solar

Energy, 1989. 43(6): p. 355-357.

47. Raja, I. A. and J. W. Twidell, Statistical analysis of measured global insolation data

for Pakistan. Renewable Energy, 1994. 4(2): p. 199-216.

48. Muneer, T, S Maubleu and M Asif, Prospects of solar water heating for textile

industry in Pakistan. Renewable and Sustainable Energy Reviews, 2006. 10(1): p. 1-

23.

49. Malik, Sidra Nisar and Osama Rafiq Sukhera, Management of natural gas resources

and search for alternative renewable energy resources: A case study of Pakistan.

Renewable and Sustainable Energy Reviews, 2012. 16(2): p. 1282-1290.

50. Quaschning, Volker and M Blanco Muriel, Solar power-photovoltaics or solar

thermal power plants? VGB POWERTECH-INTERNATIONAL EDITION-, 2002.

82: p. 48-52.

51. World Energy Council, 2010 survey of energy resources. 2010: United Kingdom.

52. Mirza, Umar K, M Mercedes Maroto-Valer and Nasir Ahmad, Status and outlook of

solar energy use in Pakistan. Renewable and Sustainable Energy Reviews, 2003.

7(6): p. 501-514.

53. Pakistan Engineering Council, energy updates, in newsletter. 2010, PEC: Islamabad

pakistan. p. 38.

54. A. Khalid, M Mahmood, Energy conservation using desiccant cooling system, in 12th

HVACR national conference on air conditioning systems pakistan. 2005, Pakistan

HVACR society: Islamabad.

55. A. Khalid, M Mahmood, M Asif, T.Muneer, solar assisted hybrid desiccant cooling

system for the climate of pakistan, in 3rd international conference on solar radiation

and day lighting. 2007: New delhi, India.

56. Mehmood, Aamir, Adeel Waqas and Hafiza Tahira Mahmood, Stand-alone PV

System Assessment for Major Cities of Pakistan Based on Simulated Results: A

Comparative Study. NUST Journal of Engineering Sciences (NJES) Islamabad, 2013.

6(1): p. 33-37.

57. Raja, Nusrat Kamal, M Shahid Khalil, Syed Athar Masood, and Muhammad Shaheen,

Design and manufacturing of parabolic trough solar collector system for a

developing country Pakistan. Journal of American Science, 2011. 7(1).

58. Khan, T, Ia Chaudhry and A Rehman, Design of a Solar Updraft Tower Power Plant

for Pakistan and its Simulation in TRNSYS. 2014.

59. Shah, Sadiq Ali, Analysis of solar energy production, utilisation and management for

facilitating sustainable development in and around the deserts of Pakistan. 2012,

University of Manchester.

60. Shah, Sadiq Ali, Yang Zhang and Rodger Edward Edwards, Hybrid Energy Based

and CO2 Sequestration Capable Desert Potential Development. NUST Journal of

Engineering Sciences (NJES), 2010. 3(1): p. 39-45.

61. Shah, Sadiq Ali and Yang Zhang, The impact of desert solar power utilization on

sustainable development. Applied Solar Energy, 2011. 47(4): p. 336-341.

225

62. Shah, Sadiq Ali and Rodger Edwards, Sustainable energy generation processes in the

deserts of solar-rich countries. International Journal of Sustainable Energy, 2013.

32(3): p. 196-203.

63. Shah, Sa and Y Zhang, Prospects of coastal solarization for freshwater and electricity

production. ISESCO Science and Technology Vision, 2010. 10: p. 82-87.

64. Chaudhry, Q-U-Z, A Mahmood, G Rasul, and M Afzaal, Climate change indicators

of Pakistan. Pakistan Meteorological Department, Islamabad. Technical Report No.

PMD-22/2009, 2009: p. 1-43.

65. Khan, Fazle Karim, A geography of Pakistan: environment, people and economy.

1991: Oxford University Press.

66. Survey of Pakistan. Adminitrative Areas of Pakistan. 2015 [cited 2015 15 March ].

67. Pakistan Statistical Pocket Book, Islamabad: Federal Bureau of Statistics Division.

Government of Pakistan, 2006.

68. Pakistan Population. The world gazetteer. 2010 [cited 2010 15 August]; Available

from: http://www.grida.no/geo/GEO/Geo-2-234.htm.

69. Desa, Un, World population prospects: The 2012 revision. Population Division of the

Department of Economic and Social Affairs of the United Nations Secretariat, New

York, 2013.

70. Kugelman, Michael, urbanisation in pakistan: causes and consequences, in NOREF

Expert Analysis. 2013: Oslo, Norway.

71. Mcsweeney, Carol, Gil Lizcano, Mark New, and X Lu, The UNDP Climate Change

Country Profiles: Improving the accessibility of observed and projected climate

information for studies of climate change in developing countries. Bulletin of the

American Meteorological Society, 2010. 91(2): p. 157-166.

72. Chaudhry, Qz and G Rasul, Agroclimatic classification of Pakistan. Science Vision,

2004. 9(3-4): p. 59-66.

73. Khan, Saif Ullah, Mu Hasan, Fk Khan, and A Bari, Climate classification of Pakistan.

Balwois-Ohrid, Republic of Macedonia, May, 2010. 29.

74. Pakistan Meteorological Department. normal temperature. climate data processing

center 2014 [cited 2014 10 june].

75. Zahid, Maida and Ghulam Rasul, Rise in summer heat index over Pakistan. Pakistan

Journal of Meteorology, 2010. 6(12): p. 85-96.

76. Delworth, Thomas L, Jd Mahlman and Thomas R Knutson, Changes in heat index

associated with CO2-induced global warming. Climatic Change, 1999. 43(2): p. 369-

386.

77. Rothfusz, Lans P and Nws Southern Region Headquarters, The heat index equation

(or, more than you ever wanted to know about heat index). Fort Worth, Texas:

National Oceanic and Atmospheric Administration, National Weather Service, Office

of Meteorology, 1990: p. 90-23.

78. Gadiwala, Muhammad Sohail and Naeem Sadiq, The apparent temperature analysis

of Pakistan using bio-meteorological indices. Pakistan Journal of Meteorology Vol,

2008. 4(8).

79. Meehl, Gerald A and Claudia Tebaldi, More intense, more frequent, and longer

lasting heat waves in the 21st century. Science, 2004. 305(5686): p. 994-997.

80. Schär, Christoph, Pier Luigi Vidale, Daniel Lüthi, Christoph Frei, Christian Häberli,

Mark A Liniger, and Christof Appenzeller, The role of increasing temperature

variability in European summer heatwaves. Nature, 2004. 427(6972): p. 332-336.

81. Clark, Robin T, Simon J Brown and James M Murphy, Modeling northern

hemisphere summer heat extreme changes and their uncertainties using a physics

226

ensemble of climate sensitivity experiments. Journal of Climate, 2006. 19(17): p.

4418-4435.

82. Rasul, Ghulam, Qin Dahe and Qz Chaudhry, Global warming and melting glaciers

along southern slopes of HKH range. Pak. Jr. of Meteorology, 2008. 5(9).

83. Dousset, Bénédicte, Françoise Gourmelon, Karine Laaidi, Abdelkrim Zeghnoun,

Emmanuel Giraudet, Philippe Bretin, Elena Mauri, and Stéphanie Vandentorren,

Satellite monitoring of summer heat waves in the Paris metropolitan area.

International Journal of Climatology, 2011. 31(2): p. 313-323.

84. Zahid, Maida and Ghulam Rasul, Changing trends of thermal extremes in Pakistan.

Climatic Change, 2012. 113(3-4): p. 883-896.

85. Robine, Jean-Marie, Siu Lan K Cheung, Sophie Le Roy, Herman Van Oyen, Clare

Griffiths, Jean-Pierre Michel, and François Richard Herrmann, Death toll exceeded

70,000 in Europe during the summer of 2003. Comptes rendus biologies, 2008.

331(2): p. 171-178.

86. Rebetez, Martine, Olivier Dupont and M Giroud, An analysis of the July 2006

heatwave extent in Europe compared to the record year of 2003. Theoretical and

Applied Climatology, 2009. 95(1-2): p. 1-7.

87. Luber, George and Michael Mcgeehin, Climate change and extreme heat events.

American journal of preventive medicine, 2008. 35(5): p. 429-435.

88. Huang, Wei, Haidong Kan and Sari Kovats, The impact of the 2003 heat wave on

mortality in Shanghai, China. Science of the Total Environment, 2010. 408(11): p.

2418-2420.

89. Handbook, Ashrae Fundamentals, Thermal comfort. Atlanta, GA: American Society

of Heating, Refrigerating and Air-conditioning Engineers, 2005.

90. Standard, Ashrae, Standard 55-2013. Thermal environmental conditions for human

occupancy. ASHRAE. Atlanta, USA, 2013.

91. Kazkaz, Mohammad and Milan Pavelek, Operative temperature and globe

temperature. Engineering MECHANICS, 2013. 20(3/4): p. 319-325.

92. Standard, Iso, 7730. Moderate thermal environments–Determination of the PMV and

PPD indices and specification of the conditions for thermal comfort, 1994.

93. Olesen, Bjarne W and Kc Parsons, Introduction to thermal comfort standards and to

the proposed new version of EN ISO 7730. Energy and buildings, 2002. 34(6): p. 537-

548.

94. Francis, J and Re Edwards, Speedy comfort assessment using ISO 7730. Building

Services Engineering Research and Technology, 1995. 16(3): p. 165-168.

95. Nicol, Fergus, Adaptive thermal comfort standards in the hot–humid tropics. Energy

and Buildings, 2004. 36(7): p. 628-637.

96. Humphreys, Michael A. and J. Fergus Nicol, The validity of ISO-PMV for predicting

comfort votes in every-day thermal environments. Energy and Buildings, 2002. 34(6):

p. 667-684.

97. Nicol, J Fergus, Iftikhar A Raja, Arif Allaudin, and Gul Najam Jamy, Climatic

variations in comfortable temperatures: the Pakistan projects. Energy and Buildings,

1999. 30(3): p. 261-279.

98. Nicol, J Fergus and Michael A Humphreys, Adaptive thermal comfort and sustainable

thermal standards for buildings. Energy and buildings, 2002. 34(6): p. 563-572.

99. Olesen, Bjarne W, Kw Tham, C Sekhar, and D Cheong. International standards for

the indoor environment. Where are we and do they apply to Asian countries? in 7th

International Conference on Healthy Buildings 2003. 2003.

100. World Meteorological Organization. world weather Information Service. 2015 [cited

2015 15 September]; Available from: http://worldweather.wmo.int.

227

101. Nicol, J. Fergus and Iftikhar A. Raja, Indoor thermal comfort: the Pakistan study.

Energy for Sustainable Development, 1997. 3(5): p. 50-60.

102. Nicol, Fergus and Susan Roaf, Pioneering new indoor temperature standards: the

Pakistan project. Energy and Buildings, 1996. 23(3): p. 169-174.

103. Bouden, C and N Ghrab, An adaptive thermal comfort model for the Tunisian context:

a field study results. Energy and Buildings, 2005. 37(9): p. 952-963.

104. Eiswerth, Mark E, Kurt W Abendroth, Robert E Ciliano, Azedine Ouerghi, and

Michael T Ozog, Residential electricity use and the potential impacts of energy

efficiency options in Pakistan. Energy policy, 1998. 26(4): p. 307-315.

105. Ahmed, Ajaz, Energy Smart Buildings: Potential for Conservation and Efficiency of

Energy. 2013.

106. Drewe, David, Energy conservation in traditional buildings. 2007.

107. Keskin, Tülin, Energy management in the building sector: Turkish experience. World

Energy Council, Turkish Committee, , 2008.

108. Jha, Is, Subir Sen and S Victor P Selvakumar. Energy Efficiency—Potential solution

for bridging demand supply gap. in Power Systems Conference (NPSC), 2014

Eighteenth National. 2014. IEEE.

109. Enercon. Launch of BEC. 2014 [cited 2014 15 October]; Available from:

www.enercon.gov.pk.

110. Enercon, Building energy code of Pakistan. 2008: Islamabad Pakistan.

111. Enercon. Implementation of the building energy code potential and needs. [cited

2015 10 September]; Available from: www.enercon.gov.pk.

112. Un-Habitat, Energy efficient housing:improvement of thermal performance of RC slab

roof. 2010, ENERCON: Islamabad Pakistan.

113. Kattakayam, Thomachan A and K Srinivasan, Lead acid batteries in solar

refrigeration systems. Renewable energy, 2004. 29(8): p. 1243-1250.

114. Henning, Hans-Martin, Solar assisted air conditioning of buildings–an overview.

Applied Thermal Engineering, 2007. 27(10): p. 1734-1749.

115. Axaopoulos, Petros J and Michael P Theodoridis, Design and experimental

performance of a PV Ice-maker without battery. Solar Energy, 2009. 83(8): p. 1360-

1369.

116. Fumo, N, V Bortone and Jc Zambrano, Comparative Analysis of Solar Thermal

Cooling and Solar Photovoltaic Cooling Systems. Journal of Solar Energy

Engineering, 2013. 135(2): p. 021002.

117. Sarbu, Ioan and Calin Sebarchievici, Review of solar refrigeration and cooling

systems. Energy and Buildings, 2013. 67: p. 286-297.

118. Fong, Kf, Tin Tai Chow, Chun Kwong Lee, Z Lin, and Ls Chan, Comparative study

of different solar cooling systems for buildings in subtropical city. Solar Energy,

2010. 84(2): p. 227-244.

119. Kim, Ds and Ca Infante Ferreira, Solar refrigeration options–a state-of-the-art

review. International Journal of refrigeration, 2008. 31(1): p. 3-15.

120. Ullah, Kr, R Saidur, Hw Ping, Rk Akikur, and Nh Shuvo, A review of solar thermal

refrigeration and cooling methods. Renewable and Sustainable Energy Reviews,

2013. 24: p. 499-513.

121. Chan, Hoy-Yen, Saffa B Riffat and Jie Zhu, Review of passive solar heating and

cooling technologies. Renewable and Sustainable Energy Reviews, 2010. 14(2): p.

781-789.

122. Reichardt, Till Felix, Technical and Economic Assessment of Medium Sized Solar-

Assisted Air-Conditioning in Brazil. 2010, Departamento de Engenharia Civil, PUC-

Rio.

228

123. Otanicar, Todd, Robert A Taylor and Patrick E Phelan, Prospects for solar cooling–

An economic and environmental assessment. Solar Energy, 2012. 86(5): p. 1287-

1299.

124. Eicker, Ursula, Dirk Pietruschka, Maximilian Haag, and Andreas Schmitt, Systematic

design and analysis of solar thermal cooling systems in different climates. Renewable

Energy, 2015. 80: p. 827-836.

125. Cherif, Adnene and Ahmed Dhouib, Dynamic modelling and simulation of a

photovoltaic refrigeration plant. Renewable Energy, 2002. 26(1): p. 143-153.

126. Modi, Anish, Anirban Chaudhuri, Bhavesh Vijay, and Jyotirmay Mathur,

Performance analysis of a solar photovoltaic operated domestic refrigerator. Applied

Energy, 2009. 86(12): p. 2583-2591.

127. Peyton-Levine, Tobin, Jonathan Sherbeck, Beth Magerman, and Patrick E Phelan.

Solar Cooling With Ice Storage. in ASME 2012 International Mechanical

Engineering Congress and Exposition. 2012. American Society of Mechanical

Engineers.

128. Ewert, Michael K, Marty Agrella, Dan Demonbrun, Jim Frahm, David J Bergeron,

and David Berchowitz. Experimental evaluation of a solar PV refrigerator with

thermoelectric, stirling and vapor compression heat pumps. in Proceedings of Solar.

1998.

129. Berchowitz, David M, Jarlath Mcentee and Steven Welty. Design and testing of a 40

W free-piston Stirling cycle cooling unit. in Proceedings of 20th International

Congress of Refrigeration, Sydney, Australia. 1999.

130. Kribus, Abraham, Thermal integral micro-generation systems for solar and

conventional use. Journal of solar energy engineering, 2002. 124(2): p. 189-197.

131. Li, Y., G. Zhang, G. Z. Lv, A. N. Zhang, and R. Z. Wang, Performance study of a

solar photovoltaic air conditioner in the hot summer and cold winter zone. Solar

Energy, 2015. 117: p. 167-179.

132. Allouhi, Amine, Tarik Kousksou, Abdelmajid Jamil, Pascal Bruel, Youssef Mourad,

and Youssef Zeraouli, Solar driven cooling systems: An updated review. Renewable

and Sustainable Energy Reviews, 2015. 44: p. 159-181.

133. Zhao, Lei, Wenjian Cai, Xudong Ding, and Weichung Chang, Model-based

optimization for vapor compression refrigeration cycle. Energy, 2013. 55: p. 392-402.

134. Gude, Veera Gnaneswar and Nagamany Nirmalakhandan, Sustainable desalination

using solar energy. Energy Conversion and Management, 2010. 51(11): p. 2245-

2251.

135. Bilgili, Mehmet, Hourly simulation and performance of solar electric-vapor

compression refrigeration system. Solar Energy, 2011. 85(11): p. 2720-2731.

136. Yamankaradeniz, R, I Horuz, O Kaynakli, S Coskun, and N Yamankaradeniz,

Refrigeration techniques and heat pump applications. 2009, Dora Publication

Company, Bursa, Turkey,(in Turkish).

137. Mastrullo, R and C Renno, A thermoeconomic model of a photovoltaic heat pump.

Applied Thermal Engineering, 2010. 30(14): p. 1959-1966.

138. Rudischer, R, J Waschull, W Hernschier, and C Friebe. Available solar cooling

applications for different purposes. in International Conference ‘Solar Air

Conditioning’, Bad Staffelstein. 2005.

139. Tian, Yuan and Chang-Ying Zhao, A review of solar collectors and thermal energy

storage in solar thermal applications. Applied Energy, 2013. 104: p. 538-553.

140. Ghafoor, Abdul and Anjum Munir, Worldwide overview of solar thermal cooling

technologies. Renewable and Sustainable Energy Reviews, 2015. 43: p. 763-774.

229

141. Sørensen, Bent, Paul Breeze, Truman Storvick, Shang_Tian Yang, Aldo V Da Rosa,

Harsh K Gupta, Roy Sukanta, Mukesh Doble, P Maegaard, and Gianfranco Pistoia,

Renewable Energy Focus Handbook. 2009, Academic Press, .

142. Choudhury, B, Pk Chatterjee and Jp Sarkar, Review paper on solar-powered air-

conditioning through adsorption route. Renewable and Sustainable Energy Reviews,

2010. 14(8): p. 2189-2195.

143. Joshi, Anand S, Ibrahim Dincer and Bale V Reddy, Performance analysis of

photovoltaic systems: a review. Renewable and Sustainable Energy Reviews, 2009.

13(8): p. 1884-1897.

144. Chinnappa, Jcv, Performance of an intermittent refrigerator operated by a flat-plate

collector. Solar Energy, 1962. 6(4): p. 143-150.

145. Bolocan, S and I Boian, SOLAR COOLING FOR ENERGY SAVING. CAN WE

AFFORD NOT TO USE THE HEAT OF THE SUN? Bulletin of the Transilvania

University of Braşov• Vol, 2010. 3: p. 52.

146. Butz, Lw, Wa Beckman and Ja Duffie, Simulation of a solar heating and cooling

system. Solar Energy, 1974. 16(3): p. 129-136.

147. Klein, Sa, Pi Cooper, Tl Freeman, Dm Beekman, Wa Beckman, and Ja Duffie, A

method of simulation of solar processes and its application. Solar Energy, 1975.

17(1): p. 29-37.

148. Costello, Frederick A, A hybrid solar air conditioning system. Solar Energy, 1976.

18(2): p. 149-152.

149. Ward, Dan S, Thomas A Weiss and George Og Löf, Preliminary performance of CSU

Solar House I heating and cooling system. Solar Energy, 1976. 18(6): p. 541-548.

150. Nakahara, Nobuo, Yasuyuki Miyakawa and Mitsunobu Yamamoto, Experimental

study on house cooling and heating with solar energy using flat plate collector. Solar

Energy, 1977. 19(6): p. 657-662.

151. Ishibashi, Toshihiro, The result of cooling operation of Yazaki experimental solar

house “one”. Solar Energy, 1978. 21(1): p. 11-16.

152. Ward, Dan S and John C Ward, Design considerations for residential solar heating

and cooling systems utilizing evacuated tube solar collectors. Solar Energy, 1979.

22(2): p. 113-118.

153. Grossman, Gershon, Joseph R Bourne, Jonathan Ben-Dror, Yigal Kimchi, and Isaiah

Vardi, Design improvements in LiBr absorption chillers for solar applications.

Journal of Solar Energy Engineering, 1981. 103(1): p. 56-61.

154. Biancardi, Fr, Jw Sitler and G Melikian, Development and test of solar Rankine cycle

heating and cooling systems. International Journal of Refrigeration, 1982. 5(6): p.

351-360.

155. Muneer, T and Ah Uppal, Modelling and simulation of a solar absorption cooling

system. Applied energy, 1985. 19(3): p. 209-229.

156. Gommed, K and G Grossman, Performance analysis of staged absorption heat

pumps: water-lithium bromide systems. 1990: American Society of Heating,

Refrigerating and Air-Conditioning Engineers.

157. Meunier, F, Sorption solar cooling. Renewable Energy, 1994. 5(1): p. 422-429.

158. Hammad, M and Y Zurigat, Performance of a second generation solar cooling unit.

Solar Energy, 1998. 62(2): p. 79-84.

159. Li, Zf and K Sumathy, Experimental studies on a solar powered air conditioning

system with partitioned hot water storage tank. Solar Energy, 2001. 71(5): p. 285-

297.

160. Grossman, Gershon, Solar-powered systems for cooling, dehumidification and air-

conditioning. Solar energy, 2002. 72(1): p. 53-62.

230

161. Arbel, A and M Sokolov, Revisiting solar-powered ejector air conditioner––the

greener the better. Solar Energy, 2004. 77(1): p. 57-66.

162. Assilzadeh, F, Sa Kalogirou, Y Ali, and K Sopian, Simulation and optimization of a

LiBr solar absorption cooling system with evacuated tube collectors. Renewable

Energy, 2005. 30(8): p. 1143-1159.

163. Gommed, K and Gershon Grossman, Experimental investigation of a liquid desiccant

system for solar cooling and dehumidification. Solar Energy, 2007. 81(1): p. 131-138.

164. Mazloumi, M, M Naghashzadegan and K Javaherdeh, Simulation of solar lithium

bromide–water absorption cooling system with parabolic trough collector. Energy

Conversion and Management, 2008. 49(10): p. 2820-2832.

165. Kim, Ds and Ca Infante Ferreira, Air-cooled LiBr–water absorption chillers for solar

air conditioning in extremely hot weathers. Energy Conversion and Management,

2009. 50(4): p. 1018-1025.

166. Marc, Olivier, Franck Lucas, Frantz Sinama, and E Monceyron, Experimental

investigation of a solar cooling absorption system operating without any backup

system under tropical climate. Energy and Buildings, 2010. 42(6): p. 774-782.

167. Said, Syed Am, Maged Ai El-Shaarawi and Muhammad U Siddiqui, Alternative

designs for a 24-h operating solar-powered absorption refrigeration technology.

international journal of refrigeration, 2012. 35(7): p. 1967-1977.

168. Ayadi, Osama, Marcello Aprile and Mario Motta, Solar cooling systems utilizing

concentrating solar collectors-An overview. Energy Procedia, 2012. 30: p. 875-883.

169. Lizarte, R, M Izquierdo, Jd Marcos, and E Palacios, Experimental comparison of two

solar-driven air-cooled LiBr/H 2 O absorption chillers: Indirect versus direct air-

cooled system. Energy and Buildings, 2013. 62: p. 323-334.

170. Zhang, B, Js Lv and Jx Zuo, Theoretical and experimental study on solar ejector

cooling system using R236fa. International Journal of Low-Carbon Technologies,

2014. 9(4): p. 245-249.

171. Zhang, Wei, Saffa B Riffat, Xiaoli Ma, and Siddig A Omer. Optimum Design of a

Solar-Driven Ejector Cooling System. in Proceedings of the 8th International

Symposium on Heating, Ventilation and Air Conditioning. 2014. Springer.

172. Ferreira, Carlos Infante and Dong-Seon Kim, Techno-economic review of solar

cooling technologies based on location-specific data. International Journal of

Refrigeration, 2014. 39: p. 23-37.

173. Ren21, Renewables 2015 Global Status Report. 2015: Paris, REN21 Secretariat.

174. Iea, Technology Roadmap:Solar Heating and Cooling. 2012: Paris. p. 50.

175. Duffie, John A and William A Beckman, Solar Collectors. Solar Engineering of

Thermal Processes, Fourth Edition, 2013: p. 3-42.

176. A.Brown, A.Eisentraut And, Heating Without Global Warming,Market Developments

and Policy Considerations for Renewable Heat, in FEATURED INSIGHT. 2014,

International Energy Agency: Paris, France.

177. Kalogirou, Soteris A., Processess and Systems, in Solar Energy Engineering (Second

Edition), S.A. Kalogirou, Editor. 2014, Academic Press: Boston. p. 125-540.

178. Noro, M and Rm Lazzarin, Solar cooling between thermal and photovoltaic: An

energy and economic comparative study in the Mediterranean conditions. Energy,

2014. 73: p. 453-464.

179. Baharoon, Dhyia Aidroos, Hasimah Abdul Rahman, Wan Zaidi Wan Omar, and

Saeed Obaid Fadhl, Historical development of concentrating solar power

technologies to generate clean electricity efficiently–A review. Renewable and

Sustainable Energy Reviews, 2015. 41: p. 996-1027.

180. Iea, Technology roadmap: concentrating solar power. 2010: OECD/IEA.

231

181. Murphy, Pamela, IEA solar heating and cooling programme. 2015.

182. Wang, Zhangyuan, Wansheng Yang, Feng Qiu, Xiangmei Zhang, and Xudong Zhao,

Solar water heating: From theory, application, marketing and research. Renewable

and Sustainable Energy Reviews, 2015. 41: p. 68-84.

183. Sabiha, Ma, R Saidur, Saad Mekhilef, and Omid Mahian, Progress and latest

developments of evacuated tube solar collectors. Renewable and Sustainable Energy

Reviews, 2015. 51: p. 1038-1054.

184. Navarro Rivero, P and B Ehrismann, Durability issues, maintenance and cost of solar

cooling systems. Task report 5.3. 2. Quality Assurance in Solar Heating and Cooling

Technology, 2012.

185. Best, R and W Rivera, A review of thermal cooling systems. Applied Thermal

Engineering, 2015. 75: p. 1162-1175.

186. Daou, Kadoma, Rz Wang and Zz Xia, Desiccant cooling air conditioning: a review.

Renewable and Sustainable Energy Reviews, 2006. 10(2): p. 55-77.

187. Kumar, Naresh, G Srivastava and Brijesh Gangil, Heat and mass transfer study of

liquid desiccant with heat exchange by solar cooling technology. Int. J. Eng. Studies,

2010. 2: p. 105-118.

188. Wrobel, Jan, Pablo Sanabria Walter and Gerhard Schmitz, Performance of a solar

assisted air conditioning system at different locations. Solar Energy, 2013. 92: p. 69-

83.

189. Tabor, H, Use of solar energy for cooling purposes. Solar Energy, 1962. 6(4): p. 136-

142.

190. Ward, Dan S and George Og Löf, Design and construction of a residential solar

heating and cooling system. Solar Energy, 1975. 17(1): p. 13-20.

191. Ward, Dan S, George Og Löf, Charles C Smith, and Ll Shaw, Design of a solar

heating and cooling system for CSU Solar House II. Solar Energy, 1977. 19(1): p. 79-

85.

192. Ward, Ds, Cc Smith and Jc Ward, Operational modes of solar heating and cooling

systems. Solar Energy, 1977. 19(1): p. 55-61.

193. Ward, Ds, Ws Duff, Jc Ward, and Gog Löf, Intergration of evacuated tubular solar

collectors with lithium bromide absorption cooling systems. Solar Energy, 1979.

22(4): p. 335-341.

194. Muneer, T and M Hawas, Efficiency of solar energy use for residential heating and

cooling. Energy, 1981. 6(6): p. 519-527.

195. Uppal, Ah and T Muneer, Solar operated absorption air-conditioner for a Kufra

house. Applied energy, 1984. 16(4): p. 259-281.

196. Ayyash, S, An assessment of the feasibility of solar absorption and vapor

compression cooling systems. Energy Conversion and Management, 1981. 21(2): p.

163-169.

197. Al-Homoud, Aa, Rk Suri, Raed Al-Roumi, and Gp Maheshwari, Experiences with

solar cooling systems in Kuwait. Renewable energy, 1996. 9(1): p. 664-669.

198. Yeung, Mr, Pk Yuen, A Dunn, and Ls Cornish, Performance of a solar-powered air

conditioning system in Hong Kong. Solar Energy, 1992. 48(5): p. 309-319.

199. Sorour, Mm and Aa Ghoneim, Feasibility study of solar heating and cooling systems

at different localities in Egypt. Renewable energy, 1994. 5(1): p. 489-491.

200. Elsafty, A and Aj Al-Daini, Economical comparison between a solar-powered vapour

absorption air-conditioning system and a vapour compression system in the Middle

East. Renewable Energy, 2002. 25(4): p. 569-583.

201. Schwerdt, Peter and Ahmed Hamza H Ali, German/Egyptian demonstration project

on solar cooling in a hot arid climate. Energy Procedia, 2014. 48: p. 991-996.

232

202. Izquierdo, M, F Hernandez and E Martin, Solar cooling in Madrid: available solar

energy. Solar energy, 1994. 53(5): p. 431-443.

203. Syed, A, M Izquierdo, P Rodriguez, G Maidment, J Missenden, A Lecuona, and R

Tozer, A novel experimental investigation of a solar cooling system in Madrid.

International Journal of refrigeration, 2005. 28(6): p. 859-871.

204. Martínez, Pedro J, José C Martínez and Manuel Lucas, Design and test results of a

low-capacity solar cooling system in Alicante (Spain). Solar Energy, 2012. 86(10): p.

2950-2960.

205. Balghouthi, Moncef, Mohamed Hachemi Chahbani and Amenallah Guizani, Solar

powered air conditioning as a solution to reduce environmental pollution in Tunisia.

Desalination, 2005. 185(1): p. 105-110.

206. Balghouthi, M, Mh Chahbani and A Guizani, Feasibility of solar absorption air

conditioning in Tunisia. Building and Environment, 2008. 43(9): p. 1459-1470.

207. Pongtornkulpanich, A, S Thepa, M Amornkitbamrung, and C Butcher, Experience

with fully operational solar-driven 10-ton LiBr/H 2 O single-effect absorption cooling

system in Thailand. Renewable Energy, 2008. 33(5): p. 943-949.

208. Al-Alili, A, Y Hwang, R Radermacher, and I Kubo, Optimization of a solar powered

absorption cycle under Abu Dhabi’s weather conditions. Solar Energy, 2010. 84(12):

p. 2034-2040.

209. Al-Alili, A, Md Islam, I Kubo, Y Hwang, and R Radermacher, Modeling of a solar

powered absorption cycle for Abu Dhabi. Applied Energy, 2012. 93: p. 160-167.

210. Ssembatya, Martin, Manoj K Pokhrel and Rajesh Reddy, Simulation studies on

performance of solar cooling system in UAE conditions. Energy Procedia, 2014. 48:

p. 1007-1016.

211. Tsoutsos, T, E Aloumpi, Z Gkouskos, and M Karagiorgas, Design of a solar

absorption cooling system in a Greek hospital. Energy and Buildings, 2010. 42(2): p.

265-272.

212. Praene, Jean Philippe, Olivier Marc, Franck Lucas, and Frédéric Miranville,

Simulation and experimental investigation of solar absorption cooling system in

Reunion Island. Applied Energy, 2011. 88(3): p. 831-839.

213. Ayadi, Osama, Alberto Mauro, Marcello Aprile, and Mario Motta, Performance

assessment for solar heating and cooling system for office building in Italy. Energy

Procedia, 2012. 30: p. 490-494.

214. Fasfous, A, J Asfar, A Al-Salaymeh, A Sakhrieh, Z Al_Hamamre, A Al-Bawwab, and

M Hamdan, Potential of utilizing solar cooling in The University of Jordan. Energy

conversion and management, 2013. 65: p. 729-735.

215. Sim, Lik Fang, Numerical modelling of a solar thermal cooling system under arid

weather conditions. Renewable Energy, 2014. 67: p. 186-191.

216. El-Sharkawy, Ibrahim I., Hossam Abdelmeguid and Bidyut Baran Saha, Potential

application of solar powered adsorption cooling systems in the Middle East. Applied

Energy, 2014. 126: p. 235-245.

217. Ozgoren, Muammer, Mehmet Bilgili and Osman Babayigit, Hourly performance

prediction of ammonia–water solar absorption refrigeration. Applied Thermal

Engineering, 2012. 40: p. 80-90.

218. Khalid, A, M Mahmood, Muhammad Asif, and T Muneer, Solar assisted, pre-cooled

hybrid desiccant cooling system for Pakistan. Renewable Energy, 2009. 34(1): p. 151-

157.

219. Gupta, Mc and P Gandhidasan. Open cycle 3-ton solar airconditioner-Concept,

design and cycle analysis. in Sun: Mankind's Future Source of Energy. 1978.

233

220. Bansal, Nk, J Blumenberg, Hj Kavasch, and T Roettinger, Performance testing and

evaluation of solid absorption solar cooling unit. Solar Energy, 1997. 61(2): p. 127-

140.

221. Dilip Batukray Jani, Manish Mishra and P.K.Sahoo, Simulation of Solar Assisted Slod

Desiccant Cooling Systems Using TRNSYS., in 22nd National and 11th International

ISHMT-ASME Heat and Mass Transfer Conference. 2013: IIT Kharagpur, India.

222. Mittal, V, Ks Kasana and Ns Thakur, Modelling and simulation of a solar absorption

cooling system for India. Journal of Energy in Southern Africa, 2006. 17(3): p. 65-70.

223. Kumar, Yogender, Thermal design and performance evaluation of vapour

absorption/adsorption solar space conditioning systems. 1990, Indian Institute of

Technology, Delhi New Delhi.

224. Kaushik, S. C., Y. Kumar and J. V. Kaudinya, Feasibility of an open cycle absorption

solar cooling system with solution storage for continuous operation. International

Journal of Ambient Energy, 1991. 12(2): p. 101-106.

225. Kaushik, S. C., S. M. B. Gadhi, R. S. Agarwal, and Y. Kumar, Feasibility studies on

an alcohol-salt mixture for absorption refrigeration systems. Energy Conversion and

Management, 1991. 31(5): p. 459-469.

226. Kaushik, S. C. and Y. Kumar. Yadav, Thermodynamic design and assessment of

hybrid double absorption solar cooling systems. Heat Recovery Systems and CHP,

1991. 11(4): p. 255-262.

227. Yadav, Y. K. and S. C. Kaushik, Psychometric technoeconomic assessment and

parametric studies of vapor-compression and solid/liquid desiccant hybrid solar

space conditioning systems. Heat Recovery Systems and CHP, 1991. 11(6): p. 563-

572.

228. Habib, Khairul, Biplab Choudhury, Pradip Kumar Chatterjee, and Bidyut Baran Saha,

Study on a solar heat driven dual-mode adsorption chiller. Energy, 2013. 63: p. 133-

141.

229. Cabrera, Fj, A Fernández-García, Rmp Silva, and M Pérez-García, Use of parabolic

trough solar collectors for solar refrigeration and air-conditioning applications.

Renewable and Sustainable Energy Reviews, 2013. 20: p. 103-118.

230. Kalogirou, Soteris A., Chapter 11 - Designing and Modeling Solar Energy Systems, in

Solar Energy Engineering (Second Edition), S.A. Kalogirou, Editor. 2014, Academic

Press: Boston. p. 583-699.

231. Mangual, Rafael a Salgado, Optimized solar cooling facility configurations for the

Mediterranean warm climate. 2008, Universidad Carlos III de Madrid. p. 166.

232. Parke, Emily, Experiments, Simulations, and Lessons from Experimental Evolution.

2015.

233. Hinotani, Katsuhiro, Keiichi Kanatani and Masato Osumi, An evacuated glass tube

solar collector and its application to a solar cooling, heating and hot water supply

system for the hospital in Kinki University. Solar Energy, 1979. 22(6): p. 535-545.

234. Ayyash, S, Rk Suri and H Al-Shami, Performance results of solar absorption cooling

installation. International journal of refrigeration, 1985. 8(3): p. 177-183.

235. Van Hattem, D and P Actis Data, Description and performance of an active solar

cooling system, using a LiBr H 2 O absorption machine. Energy and Buildings,

1981. 3(2): p. 169-196.

236. Sayigh, Aam and Mk Saada. A three and a half ton solar absorption air conditioner's

performance in Riyadh, Saudi Arabia. in Proceedings of the International Solar

Energy Society Congress. 1981.

234

237. Ward, Hs, Zc Huang, Wc Wong, Cy Chu, Zh Zheng, and Hh Huang. Shenzhen solar

cooling and hot water supply system. in Proceedings of the Biennial Congress of the

International Solar Energy Society. 1987. ISES Hamburg, Germany.

238. Bong, Ty, Kc Ng and Ao Tay, Performance study of a solar-powered air-

conditioning system. Solar Energy, 1987. 39(3): p. 173-182.

239. Mak, Kwok-Keung, Design and operation of a solar-powered air-conditioning system

in Hong Kong. 1989, The University of Hong Kong (Pokfulam, Hong Kong).

240. Lazzarin, Rm, P Romagnoni and L Casasola, Two years of operation of a large solar

cooling plant. International journal of refrigeration, 1993. 16(3): p. 185-190.

241. Boubakri, A, M Arsalane, B Yous, L Ali-Moussa, M Pons, F Meunier, and Jj

Guilleminot, Experimental study of adsorptive solar-powered ice makers in Agadir

(Morocco)—1. Performance in actual site. Renewable Energy, 1992. 2(1): p. 7-13.

242. Hammad, M. A., Experimental study of the performance of a solar thermal-

photovoltaic integrated system. Renewable Energy, 1994. 4(8): p. 897-905.

243. Hammad, M. A. and M. S. Audi, Performance of a solar LiBr-water absorption

refrigeration system. Renewable Energy, 1992. 2(3): p. 275-282.

244. Sumathy, K, Zc Huang and Zf Li, Solar absorption cooling with low grade heat

source—a strategy of development in South China. Solar energy, 2002. 72(2): p. 155-

165.

245. Le Pierrès, Nolwenn, Nathalie Mazet and Driss Stitou, Experimental results of a solar

powered cooling system at low temperature. International Journal of Refrigeration,

2007. 30(6): p. 1050-1058.

246. Hidalgo, Mc Rodríguez, P Rodríguez Aumente, M Izquierdo Millán, A Lecuona

Neumann, and R Salgado Mangual, Energy and carbon emission savings in Spanish

housing air-conditioning using solar driven absorption system. Applied Thermal

Engineering, 2008. 28(14): p. 1734-1744.

247. Ali, Ahmed Hamza H, Peter Noeres and Clemens Pollerberg, Performance

assessment of an integrated free cooling and solar powered single-effect lithium

bromide-water absorption chiller. Solar Energy, 2008. 82(11): p. 1021-1030.

248. Rosiek, S and Fj Batlles, Integration of the solar thermal energy in the construction:

Analysis of the solar-assisted air-conditioning system installed in CIESOL building.

Renewable Energy, 2009. 34(6): p. 1423-1431.

249. Helm, M, C Keil, S Hiebler, H Mehling, and C Schweigler, Solar heating and cooling

system with absorption chiller and low temperature latent heat storage: energetic

performance and operational experience. International journal of refrigeration, 2009.

32(4): p. 596-606.

250. Li, Zf and K Sumathy, Performance study of a partitioned thermally stratified storage

tank in a solar powered absorption air conditioning system. Applied Thermal

Engineering, 2002. 22(11): p. 1207-1216.

251. Shin, Mi-Soo, Hey-Suk Kim, Dong-Soon Jang, Sang-Nam Lee, Young-Soo Lee, and

Hyung-Gi Yoon, Numerical and experimental study on the design of a stratified

thermal storage system. Applied thermal engineering, 2004. 24(1): p. 17-27.

252. Zhong, Li, Nie Jingjing, Zhang Xinyu, Li Guoli, Li Changling, Wei Lifeng, and

Zheng Ruicheng, Application of solar cooling system in a campus library in Hainan,

China. Energy Procedia, 2012. 30: p. 730-737.

253. Yin, Yl, Zp Song, Y Li, Rz Wang, and Xq Zhai, Experimental investigation of a mini-

type solar absorption cooling system under different cooling modes. Energy and

Buildings, 2012. 47: p. 131-138.

254. Balghouthi, M, Mh Chahbani and A Guizani, Investigation of a solar cooling

installation in Tunisia. Applied Energy, 2012. 98: p. 138-148.

235

255. Allouche, Yosr, Chiheb Bouden and Saffa Riffat, A solar-driven ejector refrigeration

system for Mediterranean climate: experience improvement and new results

performed. Energy Procedia, 2012. 18: p. 1115-1124.

256. Ajib, Salman and Wolfgang Günther, Solar thermally driven cooling systems: Some

investigation results and perspectives. Energy Conversion and Management, 2013.

65: p. 663-669.

257. Helm, Martin, Kilian Hagel, Werner Pfeffer, Stefan Hiebler, and Christian

Schweigler, Solar Heating and Cooling System with Absorption Chiller and Latent

Heat Storage–A Research Project Summary. Energy Procedia, 2014. 48: p. 837-849.

258. Yong, Cui, Wang Yiping and Zhu Li, Performance analysis on a building-integrated

solar heating and cooling panel. Renewable Energy, 2015. 74: p. 627-632.

259. Armanasco, Fabio, Luigi Pietro Maria Colombo, Andrea Lucchini, and Andrea

Rossetti, Performance analysis of a solar cooling plant based on a liquid desiccant

evaporative cooler. International Journal of Refrigeration, 2015. 53: p. 163-176.

260. Agyenim, Francis, Ian Knight and Michael Rhodes, Design and experimental testing

of the performance of an outdoor LiBr/H 2 O solar thermal absorption cooling system

with a cold store. Solar energy, 2010. 84(5): p. 735-744.

261. Huang, Bj, Cw Yen, Jh Wu, Jh Liu, Hy Hsu, Vo Petrenko, Jm Chang, and Cw Lu,

Optimal control and performance test of solar-assisted cooling system. Applied

Thermal Engineering, 2010. 30(14): p. 2243-2252.

262. Bermejo, Pablo, Francisco Javier Pino and Felipe Rosa, Solar absorption cooling

plant in Seville. Solar Energy, 2010. 84(8): p. 1503-1512.

263. Qu, Ming, Hongxi Yin and David H Archer, A solar thermal cooling and heating

system for a building: experimental and model based performance analysis and

design. Solar energy, 2010. 84(2): p. 166-182.

264. Venegas, M, Mc Rodríguez-Hidalgo, R Salgado, A Lecuona, P Rodríguez, and G

Gutiérrez, Experimental diagnosis of the influence of operational variables on the

performance of a solar absorption cooling system. Applied Energy, 2011. 88(4): p.

1447-1454.

265. Ayompe, Lm, Aidan Duffy, Sj Mccormack, and Michael Conlon, Validated TRNSYS

model for forced circulation solar water heating systems with flat plate and heat pipe

evacuated tube collectors. Applied Thermal Engineering, 2011. 31(8): p. 1536-1542.

266. Boudéhenn, François, Hélène Demasles, Joël Wyttenbach, Xavier Jobard, David

Chèze, and Philippe Papillon, Development of a 5 kW cooling capacity ammonia-

water absorption chiller for solar cooling applications. Energy Procedia, 2012. 30: p.

35-43.

267. Joseph Luzzi Experimental Research. 2005. 1.

268. Odle, Teresa and Richard Mayer, Experimental Research. 2011. p. 1-7.

269. Best, R and N Ortega, Solar refrigeration and cooling. Renewable Energy, 1999.

16(1): p. 685-690.

270. Druckman, Daniel, Doing research: Methods of inquiry for conflict analysis. 2005:

Sage.

271. Sheridan, Nr, Kj Bullock and Ja Duffie, Study of solar processes by analog computer.

Solar Energy, 1967. 11(2): p. 69-77.

272. Gupta, Cl, On generalizing the dynamic performance of solar energy systems. Solar

Energy, 1971. 13(3): p. 301-310.

273. Close, Dj, A design approach for solar processes. Solar Energy, 1967. 11(2): p. 112-

122.

274. Gupta, Cl and Hp Garg, System design in solar water heaters with natural circulation.

Solar Energy, 1968. 12(2): p. 163-182.

236

275. Buchberg, H and Jr Roulet, Simulation and optimization of solar collection and

storage for house heating. Solar Energy, 1968. 12(1): p. 31-50.

276. Oonk, Rl, Wa Beckman and Ja Duffie, Modeling of the CSU heating/cooling system.

Solar Energy, 1975. 17(1): p. 21-28.

277. Lof, Gog and Ra Tybout, Model for optimizing solar heating design. 1972.

278. Löf, George Og and Richard Alton Tybout, The design and cost of optimized systems

for residential heating and cooling by solar energy. Solar Energy, 1974. 16(1): p. 9-

18.

279. Lorsch, Harold G, Active solar heating and cooling systems: II. Performance and

cost. Energy and Buildings, 1981. 3(2): p. 137-167.

280. Enibe, So and Oc Iloeje, Design optimization of the flat plate collector for a solid

absorption solar refrigerator. Solar energy, 1997. 60(2): p. 77-87.

281. Ghaddar, Nk, M Shihab and F Bdeir, Modeling and simulation of solar absorption

system performance in Beirut. Renewable Energy, 1997. 10(4): p. 539-558.

282. Li, Zf and K Sumathy, Simulation of a solar absorption air conditioning system.

Energy Conversion and management, 2001. 42(3): p. 313-327.

283. Florides, Ga, Sa Kalogirou, Sa Tassou, and Lc Wrobel, Modelling and simulation of

an absorption solar cooling system for Cyprus. Solar Energy, 2002. 72(1): p. 43-51.

284. Florides, Ga, Sa Kalogirou, Sa Tassou, and Lc Wrobel, Modelling, simulation and

warming impact assessment of a domestic-size absorption solar cooling system.

Applied Thermal Engineering, 2002. 22(12): p. 1313-1325.

285. Atmaca, Ibrahim and Abdulvahap Yigit, Simulation of solar-powered absorption

cooling system. Renewable Energy, 2003. 28(8): p. 1277-1293.

286. Eicker, Ursula and Dirk Pietruschka, Design and performance of solar powered

absorption cooling systems in office buildings. Energy and Buildings, 2009. 41(1): p.

81-91.

287. Casals, Xavier Garcia, Solar absorption cooling in Spain: Perspectives and outcomes

from the simulation of recent installations. Renewable energy, 2006. 31(9): p. 1371-

1389.

288. Zambrano, Darine, Carlos Bordons, Winston Garcia-Gabin, and Eduardo F Camacho,

Model development and validation of a solar cooling plant. International Journal of

Refrigeration, 2008. 31(2): p. 315-327.

289. Calise, F, M Dentice D'accadia and R Vanoli, Dynamic simulation and parametric

optimisation of a solar-assisted heating and cooling system. International Journal of

Ambient Energy, 2010. 31(4): p. 173-194.

290. Calise, F, A Palombo and L Vanoli, Maximization of primary energy savings of solar

heating and cooling systems by transient simulations and computer design of

experiments. Applied Energy, 2010. 87(2): p. 524-540.

291. Sanjuan, C, S Soutullo and Mr Heras, Optimization of a solar cooling system with

interior energy storage. Solar Energy, 2010. 84(7): p. 1244-1254.

292. Fong, Kf, Chun Kwong Lee, Tin Tai Chow, Z Lin, and Ls Chan, Solar hybrid air-

conditioning system for high temperature cooling in subtropical city. Renewable

energy, 2010. 35(11): p. 2439-2451.

293. Calise, F, Thermoeconomic analysis and optimization of high efficiency solar heating

and cooling systems for different Italian school buildings and climates. Energy and

Buildings, 2010. 42(7): p. 992-1003.

294. Calise, F, M Dentice D’accadia and A Palombo, Transient analysis and energy

optimization of solar heating and cooling systems in various configurations. Solar

Energy, 2010. 84(3): p. 432-449.

237

295. Fong, Kf, Chun Kwong Lee, Z Lin, Tin Tai Chow, and Ls Chan, Application potential

of solar air-conditioning systems for displacement ventilation. Energy and Buildings,

2011. 43(9): p. 2068-2076.

296. Soutullo, S, C San Juan and Mr Heras, Comparative study of internal storage and

external storage absorption cooling systems. Renewable Energy, 2011. 36(5): p.

1645-1651.

297. Calise, Francesco, High temperature solar heating and cooling systems for different

Mediterranean climates: dynamic simulation and economic assessment. Applied

Thermal Engineering, 2012. 32: p. 108-124.

298. Hassan, Hz, Aa Mohamad and R Bennacer, Simulation of an adsorption solar cooling

system. Energy, 2011. 36(1): p. 530-537.

299. Calise, F, M Dentice D’accadia and L Vanoli, Thermoeconomic optimization of solar

heating and cooling systems. Energy Conversion and Management, 2011. 52(2): p.

1562-1573.

300. Molero-Villar, Natividad, Jm Cejudo-López, F Domínguez-Muñoz, and Antonio

Carrillo-Andrés, A comparison of solar absorption system configurations. Solar

energy, 2012. 86(1): p. 242-252.

301. Henning, Hans-Martin and Jochen Döll, Solar systems for heating and cooling of

buildings. Energy Procedia, 2012. 30: p. 633-653.

302. Montero, Andrés, Jesús López-Villada, Carlos Naranjo-Mendoza, and Jerko Labus.

Comparative Study of Solar Assisted Cooling Technologies for Two Different

Climates. in ASME 2014 8th International Conference on Energy Sustainability

collocated with the ASME 2014 12th International Conference on Fuel Cell Science,

Engineering and Technology. 2014. American Society of Mechanical Engineers.

303. Hallström, Olof, Gerrit Füldner, Hans-Joseph Spahn, Lena Schnabel, and Frank Salg,

Development of collector integrated sorption modules for solar heating and cooling:

Performance simulation. Energy Procedia, 2014. 48: p. 67-76.

304. Eicker, Ursula, Antonio Colmenar-Santos, Lya Teran, Mariela Cotrado, and David

Borge-Diez, Economic evaluation of solar thermal and photovoltaic cooling systems

through simulation in different climatic conditions: An analysis in three different

cities in Europe. Energy and Buildings, 2014. 70: p. 207-223.

305. López-Villada, Jesús, Dereje S Ayou, Joan Carles Bruno, and Alberto Coronas,

Modelling, simulation and analysis of solar absorption power-cooling systems.

International Journal of Refrigeration, 2014. 39: p. 125-136.

306. Chargui, R and H Sammouda, Modeling of a residential house coupled with a dual

source heat pump using TRNSYS software. Energy Conversion and Management,

2014. 81: p. 384-399.

307. Eicker, Ursula, Dirk Pietruschka, Andreas Schmitt, and Maximilian Haag,

Comparison of photovoltaic and solar thermal cooling systems for office buildings in

different climates. Solar Energy, 2015. 118: p. 243-255.

308. Fong, Kf and Ck Lee, Investigation of separate or integrated provision of solar

cooling and heating for use in typical low-rise residential building in subtropical

Hong Kong. Renewable Energy, 2015. 75: p. 847-855.

309. Lamnatou, Chr, Jayanta Deb Mondol, D Chemisana, and C Maurer, Modelling and

simulation of Building-Integrated solar thermal systems: Behaviour of the coupled

building/system configuration. Renewable and Sustainable Energy Reviews, 2015. 48:

p. 178-191.

310. Blackman, Corey, Chris Bales and Eva Thorin, Techno-economic Evaluation of

Solar-assisted Heating and Cooling Systems with Sorption Module Integrated Solar

Collectors. Energy Procedia, 2015. 70: p. 409-417.

238

311. D. Thevenard. A simple tool for the simulation of active solar systems: WATSUN

reborn. in Third Solar Building Conference. 2008. Fredericton N.B.

312. Klein, Sanford Alan, Wa Beckman and Ja Duffie, A design procedure for solar

heating systems. Solar Energy, 1976. 18(2): p. 113-127.

313. Beckman, Wa, Ja Duffie and Sa Klein, Simulation of solar heating systems, in

Applications of Solar Energy for Heating and Cooling of Buildings, Chap. IV. 1977,

ASHRAE New York.

314. Energy Plus, Getting Stared with EnergyPlus, in Energy Plus Documentation. 2015,

NREL: United States. p. 1-78.

315. Crawley, Drury B., Linda K. Lawrie, Frederick C. Winkelmann, W. F. Buhl, Y. Joe

Huang, Curtis O. Pedersen, Richard K. Strand, Richard J. Liesen, Daniel E. Fisher,

Michael J. Witte, and Jason Glazer, EnergyPlus: creating a new-generation building

energy simulation program. Energy and Buildings, 2001. 33(4): p. 319-331.

316. Arasteh, Dariush, Modeling windows in energy plus with simple performance indices.

Lawrence Berkeley National Laboratory, 2010.

317. Rhodes, Joshua D, William H Gorman, Charles R Upshaw, and Michael E Webber,

Using BEopt (EnergyPlus) with energy audits and surveys to predict actual

residential energy usage. Energy and Buildings, 2015. 86: p. 808-816.

318. Zhao, Jie, Khee Poh Lam, B Erik Ydstie, and Vivian Loftness, Occupant-oriented

mixed-mode EnergyPlus predictive control simulation. Energy and Buildings, 2015.

319. Logue, Jennifer M, William Jn Turner, Iain S Walker, and Brett C Singer, A

simplified model for estimating population-scale energy impacts of building envelope

air tightening and mechanical ventilation retrofits. Journal of Building Performance

Simulation, 2015(ahead-of-print): p. 1-16.

320. Ng, Lisa C., Andrew K. Persily and Steven J. Emmerich, Improving infiltration

modeling in commercial building energy models. Energy and Buildings, 2015. 88: p.

316-323.

321. Blight, Thomas S and David A Coley, Sensitivity analysis of the effect of occupant

behaviour on the energy consumption of passive house dwellings. Energy and

Buildings, 2013. 66: p. 183-192.

322. Attia, Shady, Elisabeth Gratia, André De Herde, and Jan L. M. Hensen, Simulation-

based decision support tool for early stages of zero-energy building design. Energy

and Buildings, 2012. 49: p. 2-15.

323. Ham, Sang-Woo, Min-Hwi Kim, Byung-Nam Choi, and Jae-Weon Jeong, Energy

saving potential of various air-side economizers in a modular data center. Applied

Energy, 2015. 138: p. 258-275.

324. Ascione, Fabrizio, Nicola Bianco, Rosa Francesca De Masi, Filippo De’rossi, and

Giuseppe Peter Vanoli, Energy refurbishment of existing buildings through the use of

phase change materials: energy savings and indoor comfort in the cooling season.

Applied Energy, 2014. 113: p. 990-1007.

325. Ies, Ve, Virtual Environment (VE) by Integrated Environment Solutions (IES), 2009.

326. Aldossary, Naief A., Yacine Rezgui and Alan Kwan, Consensus-based low carbon

domestic design framework for sustainable homes. Renewable and Sustainable

Energy Reviews, 2015. 51: p. 417-432.

327. Aldossary, Naief A., Yacine Rezgui and Alan Kwan, Domestic energy consumption

patterns in a hot and humid climate: A multiple-case study analysis. Applied Energy,

2014. 114: p. 353-365.

328. Shameri, Ma, Ma Alghoul, Omkalthum Elayeb, M Fauzi M Zain, Ms Alrubaih,

Halizawati Amir, and K Sopian, Daylighting characterstics of existing double-skin

façade office buildings. Energy and Buildings, 2013. 59: p. 279-286.

239

329. Al-Tamimi, Nedhal A and Sharifah Fairuz Syed Fadzil, The potential of shading

devices for temperature reduction in high-rise residential buildings in the tropics.

Procedia Engineering, 2011. 21: p. 273-282.

330. Kamarudin, Mohd Salleh, Ahmad Kamil Kamarudin, Sabarinah Sh Ahmad, and Elias

Salleh, Efficiency of monitor roof in maintaining the thermal conditions of indoor air

and water in a medium scale enclosed tropical prawn hatchery building. Asian

Fisheries Science, 2015. 28(2): p. 71-82.

331. Ozdenefe, Murat and Jonathan Dewsbury, Simulation and real weather data: A

comparison for Cyprus case. Building Services Engineering Research and

Technology, 2015: p. 0143624415603581.

332. Ghasemi, Mohsen, Maliheh Noroozi, Marzieh Kazemzadeh, and Mohsen Roshan, The

influence of well geometry on the daylight performance of atrium adjoining spaces: A

parametric study. Journal of Building Engineering, 2015. 3: p. 39-47.

333. Adam, Alexandros, Eric S Fraga and Dan Jl Brett, Options for residential building

services design using fuel cell based micro-CHP and the potential for heat

integration. Applied Energy, 2015. 138: p. 685-694.

334. Kirimtat, Ayca, Basak Kundakci Koyunbaba, Ioannis Chatzikonstantinou, and Sevil

Sariyildiz, Review of simulation modeling for shading devices in buildings.

Renewable and Sustainable Energy Reviews, 2016. 53: p. 23-49.

335. Gill, Zachary M, Michael J Tierney, Ian M Pegg, and Neil Allan, Measured energy

and water performance of an aspiring low energy/carbon affordable housing site in

the UK. Energy and Buildings, 2011. 43(1): p. 117-125.

336. Kalogirou, Soteris A., Optimization of solar systems using artificial neural-networks

and genetic algorithms. Applied Energy, 2004. 77(4): p. 383-405.

337. Almeida, P, Mj Carvalho, Ricardo Amorim, J Farinha Mendes, and V Lopes,

Dynamic testing of systems–Use of TRNSYS as an approach for parameter

identification. Solar Energy, 2014. 104: p. 60-70.

338. Klein, Sh and Wa Beckman, TRNSYS, a Simulation program. ASHRAE Trans, 1971.

76.

339. Kalogirou, Soteris A. and Christos Papamarcou, Modelling of a thermosyphon solar

water heating system and simple model validation. Renewable Energy, 2000. 21(3–4):

p. 471-493.

340. Kalogirou, Soteris, Thermal performance, economic and environmental life cycle

analysis of thermosiphon solar water heaters. Solar Energy, 2009. 83(1): p. 39-48.

341. Oishi, Masahiro and Tetsuo Noguchi. The evaluation procedure on performance of

SDHW system by TRNSYS simulation for a yearly performance prediction. in

Proceedings of Eurosun. 2000.

342. Jordan, Ulrike and Klaus Vajen, Influence Of The DHW Load Profile On The

Fractional Energy Savings:: A Case Study Of A Solar Combi-System With TRNSYS

Simulations. Solar Energy, 2001. 69: p. 197-208.

343. Kalogirou, Soteris, The potential of solar industrial process heat applications.

Applied Energy, 2003. 76(4): p. 337-361.

344. S.A. Klein, W.A. Beckman , J.A. Duffie, TRNSYS version 17 program manual, S.E.

Laboratory, Editor. 2010: University of Wisconsin, Madison.

345. Mitchell, Jw, Wa Beckman and Mj Pawelski, Comparisons of measured and

simulated performance for CSU house I. Journal of Solar Energy Engineering, 1980.

102(3): p. 192-195.

346. Beckman, William A, Lars Broman, Alex Fiksel, Sanford A Klein, Eva Lindberg,

Mattias Schuler, and Jeff Thornton, Trnsys the most complete solar energy system

modeling and simulation software. Renewable energy, 1994. 5(1): p. 486-488.

240

347. Monfet, Danielle and Radu Zmeureanu. Simulation of a large central cooling and

heating plant using TRNSYS and calibration with monitored data. in Proceeding.

2009.

348. Hang, Yin, Ming Qu and Satish Ukkusuri, Optimizing the design of a solar cooling

system using central composite design techniques. Energy and Buildings, 2011. 43(4):

p. 988-994.

349. Almeidaa, Patrícia, Ricardo Amorim, Maria João Carvalho, João Farinha Mendes,

and Vitor Lopes, Dynamic testing of systems–use of TRNSYS as an Approach for

Parameter Identification. Energy Procedia, 2012. 30: p. 1294-1303.

350. Banister, Carsen J, William R Wagar and Michael R Collins, Validation of a single

tank, multi-mode solar-assisted heat pump TRNSYS model. Energy Procedia, 2014.

48: p. 499-504.

351. He, Tao, Xinyu Zhang, Conghui Wang, Min Wang, Bojia Li, Ning Xue, Kazuo

Shimizu, Kenji Takahashi, and Youyi Wu, Application of Solar Thermal Cooling

System Driven by Low Temperature Heat Source in China. Energy Procedia, 2015.

70: p. 454-461.

352. Bava, Federico, Simon Furbo and Bengt Perers, Simulation of a Solar Collector Array

Consisting of two Types of Solar Collectors, with and Without Convection Barrier.

Energy Procedia, 2015. 70: p. 4-12.

353. Eicker, Ursula, Dirk Pietruschka and Ruben Pesch, Heat rejection and primary energy

efficiency of solar driven absorption cooling systems. International Journal of

Refrigeration, 2012. 35(3): p. 729-738.

354. Palacín, F., C. Monné and S. Alonso, Improvement of an existing solar powered

absorption cooling system by means of dynamic simulation and experimental

diagnosis. Energy, 2011. 36(7): p. 4109-4118.

355. D’antoni, Matteo, Gabriele Ferruzzi, Davide Bettoni, and Roberto Fedrizzi,

Validation of the numerical model of a turnkey Solar Combi+ system. Energy

Procedia, 2012. 30: p. 551-561.

356. De Keizer, Corry, Stefan Kuethe, Ulrike Jordan, and Klaus Vajen, Simulation-based

long-term fault detection for solar thermal systems. Solar Energy, 2013. 93: p. 109-

120.

357. Duffie, John A and William A Beckman, Solar Engineering of Thermal Processes,

Fourth Edition. 2013, USA: John Wiley & Sons. 928.

358. Forejt, L, Jlm Hensen, Frantisek Drkal, and P Barankova. Weather data around the

world for design of field hospital HVAC. in Proc. 17th Int. Air Conditioning and

Ventilation Conference, Prague, CZ. 2006.

359. Hall, Irving J, Rr Prairie, He Anderson, and Ec Boes, Generation of a typical

meteorological year. 1978, Sandia Labs., Albuquerque, NM (USA).

360. Diego Ibarra, Understanding Weather Files and Visualizing Data Using

Computerized Tools, in Digital Workshops Series. 2009, Havard university.

361. Hong, Tianzhen, Wen-Kuei Chang and Hung-Wen Lin, A fresh look at weather

impact on peak electricity demand and energy use of buildings using 30-year actual

weather data. Applied Energy, 2013. 111: p. 333-350.

362. Schmitt, David D, Sanford A Klein and Douglas T Reindl, Automated generation of

hourly design sequences. 2000, Univ. of Wisconsin, Madison, WI (US).

363. Us Department of Energy. Weather Data Sources. Energy Efficiency & Renewable

Energy 2015 12-October-2015]; Available from:

http://apps1.eere.energy.gov/buildings/energyplus/weatherdata_sources.cfm.

241

364. Thevenard, Didier J and Alfred P Brunger, The development of typical weather years

for international locations: Part I, algorithms. ASHRAE Transactions, 2002. 108: p.

376.

365. Liggett, R and M Milne, Climate Consultant, version 5.5. UCLA Design Tool Group,

USA, 2014.

366. Remund, Jan and Stefan Kunz, METEONORM: Global meteorological database for

solar energy and applied climatology. 2003: Meteotest.

367. Ahmed, Tauseef and S Mubashir Ali, Characteristics of Households and

Respondents. Pakistan Demographic and Health Survey, 1992. 1: p. 990-991.

368. Nazli, Hina, Syed Hamza Haider, Stephanie Hausladen, Asjad Tariq, Hassan Shafiq,

Saqib Shahzad, Amina Mehmood, Asma Shahzad, and Edward Whitney, Pakistan

Rural Household Panel Survey 2012 (Round 1): Household characteristics. 2012,

International Food Policy Research Institute (IFPRI).

369. Zafar, Nabeel. 5 Marla Single Storey House Safari Villas Bahria Town Lahore 2012

[cited 2014 15 October]; Available from: http://www.kirayadaar.com/.

370. Khan, Kamran Muzaffar, Sustainability of Different Pakistani Building Systems.

International Poster Journal of Science and Technology. 1(2-3): p. 52-55.

371. Colbeck, Ian, Zaheer Ahmad Nasir and Zulfiqar Ali, Characteristics of

indoor/outdoor particulate pollution in urban and rural residential environment of

Pakistan. Indoor air, 2010. 20(1): p. 40-51.

372. Lee, W. L., Benchmarking energy use of building environmental assessment schemes.

Energy and Buildings, 2012. 45: p. 326-334.

373. Tenwolde, Anton, J Dobbin Mcnatt and Lorraine Krahn, Thermal properties of wood

and wood panel products for use in buildings. 1988, Oak Ridge National Lab., TN

(USA); Forest Service, Madison, WI (USA). Forest Products Lab.

374. Mathur, V. K., Composite materials from local resources. Construction and Building

Materials, 2006. 20(7): p. 470-477.

375. Sakraida, Va, Basics for absorption chillers. Engineered Systems, 2009. 26(3): p. 36-

48.

376. Brunold, Stefan, R Frey and Ulrich Frei. Comparison of three different collectors for

process heat applications. in Optical Materials Technology for Energy Efficiency and

Solar Energy Conversion XIII. 1994. International Society for Optics and Photonics.

377. Zambolin, E. and D. Del Col, Experimental analysis of thermal performance of flat

plate and evacuated tube solar collectors in stationary standard and daily conditions.

Solar Energy, 2010. 84(8): p. 1382-1396.

378. Institute for Solar Technology. SPF Online Collector Catalogue. Test Reports 2014

[cited 2014 January 10]; Available from: www.spf.ch.

379. Hang, Yin and Ming Qu, The impact of hot and cold storages on a solar absorption

cooling system for an office building. 2010.

380. Raab, S., D. Mangold and H. Müller-Steinhagen, Validation of a computer model for

solar assisted district heating systems with seasonal hot water heat store. Solar

Energy, 2005. 79(5): p. 531-543.

381. Heatec, TEC-NOTE, in Publication No.8-03-108. 2003: USA. p. 1-4.

382. Pokhrel, Manoj Kumar, Gaurav Pravinkumar Raval and Sujata Dahal, Experimental

Analysis on Performance of Solar Cooling System in UAE Conditions.

383. Kennish, William J, An approach to the validation of computer simulation codes.

1978: Department of Energy.

384. Anand, Dk, Wj Kennish, Tm Knasel, and Ac Stolarz, Validation methodology for

solar heating and cooling systems. Energy, 1979. 4(4): p. 549-560.

242

385. Thacker, Ben H, Scott W Doebling, Francois M Hemez, Mark C Anderson, Jason E

Pepin, and Edward A Rodriguez, Concepts of model verification and validation. 2004,

Los Alamos National Lab., Los Alamos, NM (US).

386. Bales, Chris, Parameter identification manual for TRNSYS models at SERC. 2001:

SERC, Högskolan i Dalarna.

387. Kaplan, Michael, Phoebe Caner and Gw Vincent, Guidelines for energy simulation of

commercial buildings. 1992: Bonneville Power Administration.

388. Balaras, Constantinos A., Gershon Grossman, Hans-Martin Henning, Carlos A.

Infante Ferreira, Erich Podesser, Lei Wang, and Edo Wiemken, Solar air conditioning

in Europe—an overview. Renewable and Sustainable Energy Reviews, 2007. 11(2): p.

299-314.

389. Shirazi, Ali, Robert A Taylor, Stephen D White, and Graham L Morrison, Transient

simulation and parametric study of solar-assisted heating and cooling absorption

systems: An energetic, economic and environmental (3E) assessment. Renewable

Energy, 2016. 86: p. 955-971.

390. Fong, Kf and Ck Lee, Performance advancement of solar air-conditioning through

integrated system design for building. Energy, 2014. 73: p. 987-996.

391. Thomas, Sébastien and Philippe André. Dynamic simulation of a complete solar

assisted conditioning system in an office building using TRNSYS. in Proceedings of

11th International IBPSA Conference, Glasgow, Scotland. 2009. Citeseer.

392. Yazaki. Yazaki WFC-SC5 Specification. 2014 [cited 2014 15 November];

2007:[Available from: http://www.yazaki-airconditioning.com.

393. Saltelli, Andrea, Stefano Tarantola and Kp-S Chan, A quantitative model-independent

method for global sensitivity analysis of model output. Technometrics, 1999. 41(1): p.

39-56.

394. Lunde, Pj, Solar thermal engineering: Space heating and hot water systems. New

York, John Wiley and Sons, Inc., 1980. , 1980. 1: p. 353-385.

395. Hang, Yin, Ming Qu and Fu Zhao, Economical and environmental assessment of an

optimized solar cooling system for a medium-sized benchmark office building in Los

Angeles, California. Renewable Energy, 2011. 36(2): p. 648-658.

396. Praene, Jean Philippe, Olivier Marc, Habiba Ennamiri, and Hery Tiana

Rakotondramiarana, Sensitivity analysis to optimize a solar absorption cooling

system. Energy Procedia, 2014. 57: p. 2636-2645.

397. Arsalis, Alexandros and Andreas N Alexandrou, Parametric study and cost analysis

of a solar-heating-and-cooling system for detached single-family households in hot

climates. Solar Energy, 2015. 117: p. 59-73.

243

Appendices

Appendix A: Annual and Monthly Maximum Average Temperature

and Relative Humidity for District Cities of Pakistan

244

Sr.No City Latitude Longitude Elevation Jan Feb Mar Apr May Jun July Aug Sep Oct Nov Dec Annual1 Mirpur khas 25.32 69 20 24.8 27.3 32.8 36.3 38.2 36.8 34.1 33.3 34.3 34.8 31 26.8 32.602 Nawabshah /Sanghar/Shahdadkot/Nosheroferoz 26.15 68.25 33 23.3 26.1 31.8 36.2 39.2 38.7 35.5 34.4 35.3 34.6 30.1 25.3 32.603 Sukkur / Larkana/ Shikarpur/khairpur 27.42 68.52 51 22.1 25 30.9 35.8 39.6 40 36.7 35.1 36 34.3 29.4 24.2 32.404 Umar kot 26.15 69.4 51 23.4 26.1 31.9 36.1 38.7 37.9 35 33.8 34.7 34.5 30.1 25.4 32.305 Hyderabad / Jamshoro 25.23 68.25 26 24.6 27.1 32.4 26 37.8 36.6 34 33.2 34.1 34.7 30.9 26.6 32.206 Tharparker 25 70.15 125 24.7 27.2 32.7 36 38 36.2 33.5 32.6 33.9 34.3 30.7 26.6 32.207 Badin 24.39 68.5 6 25.8 27.9 32.6 35.4 36.4 35.1 32.9 32.2 33.1 34.5 31.5 27.7 32.108 Dadu 26.44 67.47 244 22.1 24.9 30.7 35.4 38.9 38.4 35.1 34.3 35 33.8 29.2 24.2 31.909 Ghotki 28.05 69.21 150 20.6 23.5 29.5 34.4 38.2 38.6 35.5 33.7 34.7 33.2 28.2 22.9 31.10

10 Rahim yar khan 28.26 70.19 84 20.8 23.6 29.8 34.5 38 38.1 35.1 33.5 34.3 33.3 28.4 23 31.1011 Karachi city / Thatta 24.54 67.08 12 25.3 27.3 31.5 33.9 34.7 33.6 31.7 31 31.5 33.6 31 27.2 31.0012 Bahawalpur 29.2 71.47 108 19.9 22.8 29.1 34.1 38 38.7 35.5 33.7 34.2 32.8 27.7 22.2 30.8013 Multan / Muzaffargarh 30.12 71.26 124 18.6 21.6 28 33.3 37.7 39.5 36.2 34 34.1 31.9 26.7 21.1 30.3014 Jafarabad /Nasirabad /Jhal Magsi 28.16 67.86 390 18.7 21.5 27.3 32.7 37.3 38.7 35.8 34 34.6 31.3 26.4 21.1 30.0015 Okara /Sahiwal /Vehari /Pakpatan 30.49 73.27 162 19 22 28.1 33.6 37.6 38.5 35 33.2 33 31.5 26.9 21.5 30.0016 Kech (Turbat) 26 63 782 19.3 21.6 26.5 32.2 36.2 38 34.3 33.5 33.5 31.2 26.6 21.7 29.6017 Jhang /Rajanpur /Toba Tek Singh 31.16 72.19 164 17.9 20.8 26.8 32.8 37.4 39.5 36.1 33.8 33.1 30.8 25.8 20.4 29.6018 Awaran 26.1 65.3 692 19.9 22.2 27.2 32.3 36 36.7 33 32.3 33 31.1 26.7 22.1 29.4019 Bhakkar / Layyah 31.4 71.05 165 17.3 20.2 26.5 32.2 37.1 39.6 36.4 33.9 33.4 30.7 25.4 20 29.4020 Panjgur 26.58 64.06 925 19.5 21.8 26.6 32.1 35.9 37.3 33.3 32.6 33.1 31 26.6 21.8 29.3021 Faisalabad 31.26 73.08 186 18 20.9 26.7 32.7 37 38.6 35.1 33.1 32.4 30.4 25.8 20.4 29.3022 Lasbella 25.45 66.35 88 22.5 24.1 27.9 31.1 33.3 32.7 30.6 29.9 30.4 30.9 28.1 24.5 28.8023 Gawadar 25.07 62.19 76 22 23 26.4 30.4 33.3 34.2 31.4 30.1 30.4 30.5 27.6 23.9 28.6024 Chaghi 28.52 63.33 623 15.1 17.9 23.5 30.2 35.2 39 38.2 37.1 34.5 29 23.6 17.9 28.5025 Dera bugti / Barkhan 29.02 69.09 906 17.5 20.3 26.3 31.4 35.8 36.8 33.8 31.9 32.7 30.4 25.4 20.1 28.5026 Khuzdar 27.1 66.2 1299 17.3 20 25.5 30.9 35.5 37.2 34.1 33 33.1 29.4 24.6 19.6 28.4027 Kharan 28 64.3 832 15.2 18 23.4 30 35 38.8 37.2 36.4 34.3 28.9 23.6 18.1 28.3028 Lahore 31.33 74.2 206 17.7 20.4 26.1 32 36 37 33.4 31.6 30.9 29.2 25 20.1 28.3029 Sargodha 32.05 72.4 373 16.4 19.1 24.8 31 35.8 38.4 35.3 33 31.9 29.2 24.3 19 28.2030 DG Khan 30.03 70.38 492 16.5 19.4 25.6 30.8 35.4 37.2 34.2 32.1 32.4 29.8 24.6 19.1 28.1031 Jacobabad 28.2 68.29 888 14.5 16.9 21.5 27.7 32.2 35.6 36.9 37.7 35.8 30.3 22 16.4 27.4032 Jhelum 32.56 73.44 248 16.2 18.7 24.2 30.3 34.8 36.7 33.5 31.6 30.7 28.5 23.9 18.8 27.4033 Karachi Keemari 24.54 66.56 1 22.9 23.5 25.7 27.9 29.5 29.6 28.9 28 27.8 28.6 27.4 24.9 27.1034 Sibi / Bolan / 29.33 67.53 805 15 17.7 23.5 29.2 34.2 36.1 33.6 31.9 32 28 23.1 17.8 26.9035 Bannu 32.59 70.36 517 12.7 15.4 21.3 27.3 32.5 35.7 33.8 31.8 30.7 26.7 21.4 15.7 25.5036 Chakwal/ Attock 33.54 72.15 420 23.8 16 21.3 27.8 32.7 35.5 32.5 30.4 29.2 26.6 21.9 16.7 25.4037 Hangu / Karak / Kohat 33.32 71.04 655 12.8 14.9 20.4 26.9 32.3 35.7 33.3 31.2 30 26.5 21.4 15.7 25.1038 Mastung / Kalat/Nushki 29.5 66.56 1789 12.3 15.1 20.7 26.9 32.2 35.1 33.1 31.7 30.9 26 20.7 15.3 25.0039 Sialkot / Narowal / Gujrat/Mandi Bahuddin 32.3 74.13 280 14.4 16.6 21.8 27.8 32 33.3 30.3 28.7 27.9 25.8 21.7 17.1 24.8040 Gujranwala/Hafizabad/Shekhupura 32.09 74.11 280 14.4 16.6 21.8 27.8 32 33.3 30.3 28.7 27.9 25.8 21.7 17.1 24.8041 Chaman / Qilla Abdullah 30.58 66.25 1522 10.5 13.2 18.9 25.4 31 34.4 33.3 32 30.3 24.7 19.3 13.7 23.9042 Qilla Saifullah / Loralai 30.43 68.21 1608 11.9 14.5 20.1 25.7 30.8 33 31.3 29.8 29.3 25 20 14.8 23.9043 Quetta / Pishin 30.2 67 2073 10.2 12.6 18.3 24.4 29.8 32.5 31.2 29.8 28.7 23.7 18.6 13.2 22.8044 Islamabad / Rawalpindi 33.4 73.1 770 11.8 13.7 18.8 24.9 29.6 31.8 29.1 27.6 26.6 24 19.7 14.8 22.7045 Zhob 31.1 68.5 2065 8.65 11 16.6 22.4 27.7 30.7 30.3 29 27.2 22 16.9 11.6 21.20

46 Peshawar/charsadda/noshera 34.01 71.33 913 6.57 8.08 13.3 19.8 25.5 29.9 29.8 28.4 25.9 20.7 15.4 9.65 19.50

47 Mardan / Swabi 34.2 72 1016 7.02 8.44 13.5 20.1 25.4 29 27.8 26 24 20.1 15.4 10 18.90

48 Muzaffarabad / Balakot 34.22 73.29 2275 3.7 4.91 9.28 15.5 20.9 24.3 23.7 22.3 20.4 16.3 11.6 6.78 15.00

22 Year Monthly & Annual Average Maximum Temperature Degree Centigrade (at 10 m from surface) for District cities of Pakistan

245

Sr.No City Latitude Longitude Elevation Jan Feb Mar Apr May Jun July Aug Sep Oct Nov Dec Annual1 Karachi Keemari 24.54 66.56 1 46.6 53.1 60.7 64.2 69.7 76 79.2 79.1 74.3 62.5 52.1 45 63.602 Muzaffarabad / Balakot 34.22 73.29 2275 65.6 67.4 62.3 50.7 43.2 43.1 61 69.1 58.8 45.8 45.7 55.9 55.703 Karachi city / Thatta 24.54 67.08 12 37.6 41.5 46.4 50.9 58.5 66.5 72.6 72.3 65.8 49.9 39.6 34 53.004 Gawadar 25.07 62.19 76 49.5 49.3 49.3 45.4 47.1 53.9 69.1 70.7 60.4 45.9 44.3 47.3 52.705 Lasbella 25.45 66.35 88 40.6 42.7 45.3 47 52.7 65 74.3 73.6 64.2 47.3 40.9 37.5 52.606 Mardan / Swabi 34.2 72 1016 60 62 56.6 44.5 36.5 35.9 54.2 63 54.4 41.8 41.4 52.3 50.207 Islamabad / Rawalpindi 33.4 73.1 770 54.4 54.3 47.7 37.5 33.8 38.9 62.6 69.8 58.5 39.5 36.9 45.6 48.308 Sialkot / Narowal / Gujrat 32.3 74.13 280 53.1 51.5 43.8 33.3 31.7 40.1 64.7 72.1 61.4 41.4 37.2 44.3 47.909 Gujranwala/Hafizabad/Shekhupura 32.09 74.11 280 53.1 51.5 43.8 33.3 31.7 40.1 64.7 72.1 61.4 41.4 37.2 44.3 47.90

10 Lahore 31.33 74.2 206 53.9 49.2 40 30.2 30 39.4 63.5 71 61.8 42.3 38.2 45.9 47.1011 Badin 24.39 68.5 6 34 34.6 36.6 42 51.3 60.9 68.6 68.3 59.3 41.6 32.2 30.7 46.8012 Attock / Chakwal 33.54 72.15 420 52.9 52 45.4 35.3 30.9 34.2 57.1 65.9 56.5 37.8 35.6 45.1 45.7013 Okara /Sahiwal /Vehari /Pakpatan 30.49 73.27 162 51.8 44.4 35.1 28.7 29.9 40.4 61.3 68.6 58.4 38.7 36.1 44.9 44.9014 Jhelum 32.56 73.44 248 52.4 49.2 41.4 31.7 29.2 35.4 58.4 66.6 56.8 37.8 35.7 44.1 44.9015 Faisalabad 31.26 73.08 186 53.1 47.3 38.5 29.7 28.6 36.3 58.9 67.2 57.7 38.8 36.7 45.7 44.9016 Peshawar/charsadda/noshera 34.01 71.33 913 58.8 60.6 55.6 44.3 34.1 29.4 40 44.6 38.3 35.6 39 51.5 44.2017 Sargodha 32.05 72.4 373 52 48.2 40.7 32.1 28.9 33.4 54.9 63.9 55.2 36.9 35.3 44.2 43.8018 Hyderabad / Jamshoro 25.23 68.25 26 34.4 32.8 32 36.2 44.7 55.7 65.2 65.4 55.7 37 30.5 30.3 43.4019 Jhang /Rajanpur /Toba Tek Singh 31.16 72.19 164 51.1 45.3 37 29.8 28.2 34.7 56.5 65.7 55.8 36.9 35.1 43.7 43.3020 Hangu / Karak / Kohat 33.32 71.04 655 51.8 51.5 44.7 35.4 29.5 30 50.1 58.2 46.8 33.3 33.2 43.9 42.3021 Mirpur khas 25.32 69 20 33 30.1 28.1 33 42.2 54.3 64.5 65.3 54.2 34.6 27.7 29.4 41.4022 Tharparker 25 70.15 125 32.7 28.8 25.6 30.7 40.3 54.6 65.6 66.8 54.3 33.8 26.6 29.5 40.9023 Bhakkar / Layyah 31.4 71.05 165 47.1 41.9 33.8 28.9 26.8 31.9 53.1 63.2 51.2 31.8 30.7 39.2 40.0024 Bahawalpur 29.2 71.47 108 42.4 35.8 27.7 26.4 28.7 40.6 58.9 65.5 51.9 30.1 29.2 36.3 39.5025 Multan / Muzaffargarh 30.12 71.26 124 44.8 38.5 30.3 27.2 27.1 35.3 55.6 64.1 50.9 30.5 29.7 37.6 39.3026 Umar kot 26.15 69.4 51 34.2 29.6 25.4 28.9 36.4 49.3 61.7 64 51.4 30.8 26.7 29.8 39.1027 Bannu 32.59 70.36 517 49.4 46.1 39.2 33.1 28.3 29 47.1 54.9 41.1 29 30.5 40.9 39.1028 Awaran 26.1 65.3 692 39 35.4 32.2 28.6 29.9 42 62.1 61.7 46.1 28.9 29.2 33.6 39.1029 Panjgur 26.58 64.06 925 42.1 37.9 34.2 28.3 28.7 38.2 59.9 59.4 44.2 28.1 30 36.2 39.0030 Nawabshah /Sanghar/Shahdadkot/Nosheroferoz 26.15 68.25 33 34.4 30 26 28.3 34.3 47 60.1 61.7 49.3 29.9 26.7 29.4 38.2031 Rahim yar khan 28.26 70.19 84 38 31.8 25 25.9 29.6 43.1 59.5 65.5 50.6 28.3 27 32.7 38.1032 Kech (Turbat) 26 63 782 44.6 39.6 35.1 27.4 37.1 33.6 55.3 55.1 41.1 27.2 30.5 38.6 38.0033 DG Khan 30.03 70.38 492 42.8 37 29.7 27.5 26.4 34.6 55.4 64.1 46.6 27.1 27 35.4 37.8034 Dadu 26.44 67.47 244 34.4 30.5 27 27.3 31.6 45.3 59.7 60.1 47.4 29.1 26.6 29.5 37.4035 Dera bugti / Barkhan 29.02 69.09 906 39 33.4 26.5 25.6 25.3 36.7 56.7 64.3 44.8 25.2 25.1 32.6 36.3036 Zhob 31.1 68.5 2065 51.8 46 39.9 31.8 25.2 28.1 41.1 44.8 29.2 23.5 29.1 42.8 36.1037 Ghotki 28.05 69.21 150 36.4 30.3 24 24.6 26.6 39.2 56.7 63.3 46.6 25.9 25.3 30.9 35.9038 Quetta / Pishin 30.2 67 2073 52.4 45.3 36.6 27.6 21.2 27.3 45.4 50.3 30.6 22 27.7 42.3 35.7039 Qilla Saifullah / Loralai 30.43 68.21 1608 46.5 40.2 32.8 27.6 23.3 30.6 49.4 54.7 34.7 22.9 26.2 38 35.6040 Sukkur / Larkana/ Shikarpur/khairpur 27.42 68.52 51 34.8 28.6 23.1 23.4 26 38.2 54.6 58.9 43.6 25.2 24.5 29.4 34.3041 Chaman / Qilla Abdullah 30.58 66.25 1522 56 47.4 37.7 26.1 18.4 21 38.2 41.8 24.4 20.2 28 44.4 33.6042 Mastung / Kalat/Nushki 29.5 66.56 1789 51.5 42.4 33.2 24.3 18.1 23.2 43.8 47.8 28.4 20.5 26.9 41 33.4043 Sibi / Bolan / 29.33 67.53 805 43.1 36.1 28 23.2 19.7 28.5 49.1 55.5 34 20.9 23.9 35.2 33.1044 Khuzdar 27.1 66.2 1299 40 33.2 27.2 22.6 20.8 30.1 51.3 53.1 35.6 22.4 25 33.4 32.90

45 Jafarabad /Nasirabad /Jhal Magsi 28.16 67.86 390 37.6 30.7 23.8 21.1 19.6 29.2 48.9 54.6 35.4 20.6 22.4 31.2 31.30

46 Jacobabad 28.2 68.29 888 50.3 39.1 33.3 25.2 18.8 17.7 19 19.7 20.3 28.9 43.7 51.8 30.60

47 Kharan 28 64.3 832 49.5 40.1 32.3 21.1 15.6 15.7 33.2 32.6 20.3 18.9 26 39.7 28.70

48 Chaghi 28.52 63.33 623 51.1 41.8 33.2 20.7 15.2 13.5 27.3 26.9 17.8 19 27 41.6 27.90

25 Year Monthly & Annual Average Relative Humidity (%) for Districtcities of Pakistan

246

Appendix B: World and Pakistan Solar Energy Maps with Solar

Insolation for District Cities of Pakistan

247

248

249

250

251

252

Sr.No City Latitude Longitude Elevation Jan Feb Mar Apr May Jun July Aug Sep Oct Nov Dec Annual1 Karachi Keemari 24.54 66.56 1 4.76 5.67 6.68 7.31 7.6 7.23 6.3 6.11 6.32 5.91 5.11 4.53 6.122 Jacobabad 28.2 68.29 888 3.87 4.84 5.72 6.48 7.13 7.98 7.67 7.12 6.18 4.88 3.9 3.52 5.773 Kech 26 63 782 4.18 4.95 5.62 6.56 6.83 6.89 6.47 6.27 5.92 5.28 4.44 3.81 5.604 Chaman / Qilla Abdullah 30.58 66.25 1522 3.57 4.48 5.36 6.41 7.2 7.6 7.17 6.72 6.08 5.03 3.91 3.3 5.575 Panjgur 26.58 64.06 925 4.13 4.93 5.62 6.49 6.75 6.91 6.41 6.16 5.83 5.27 4.38 3.78 5.556 Awaran 26.1 65.3 692 4.15 4.99 5.68 6.44 6.74 6.79 6.29 6.06 5.86 5.28 4.44 3.86 5.547 Mastung / Kalat/Nushki 29.5 66.56 1789 3.63 4.4 5.19 6.48 7.13 7.41 6.97 6.56 6 5.08 3.99 3.39 5.528 Khuzdar 27.1 66.2 1299 4.01 4.87 5.54 6.34 6.81 6.82 6.4 6.11 5.64 5.14 4.29 3.69 5.479 Chaghi 28.52 63.33 623 3.74 4.61 5.18 6.28 6.84 6.89 6.67 6.42 6.1 5.18 4.07 3.39 5.45

10 Karachi city / Thatta 24.54 67.08 12 4.38 5.18 5.93 6.65 6.67 6.4 5.44 5.27 5.62 5.24 4.5 4.11 5.4411 Kharan 28 64.3 832 3.8 4.62 5.26 6.23 6.76 6.85 6.56 6.26 5.95 5.15 4.12 3.47 5.4212 Quetta / Pishin 30.2 67 2073 3.61 4.46 5.34 6.23 6.94 7.14 6.67 6.21 5.76 4.99 4.08 3.42 5.4013 Lasbella 25.45 66.35 88 4.13 4.88 5.61 6.42 6.72 6.69 5.95 5.65 5.62 5.09 4.24 3.85 5.4014 Sukkur / Larkana/ Shikarpur/khairpur 27.42 68.52 51 3.97 4.78 5.44 6.25 6.64 6.73 6.21 5.81 5.66 4.99 4.12 3.64 5.3515 Sialkot / Narowal / Gujrat 32.3 74.13 280 3.2 4.12 5.22 6.51 7.37 7.47 6.15 5.75 5.77 5.19 4.03 3.15 5.3316 Gujranwala/Hafizabad/Shekhupura 32.09 74.11 280 3.2 4.12 5.22 6.51 7.37 7.47 6.15 5.75 5.77 5.19 4.03 3.15 5.3317 Mirpur khas 25.32 69 20 4.12 4.88 5.61 6.3 6.51 6.56 5.85 5.57 5.55 4.95 4.2 3.9 5.3318 Lahore / Qasur 31.33 74.2 206 3.31 4.3 5.41 6.53 7.34 7.26 6.14 5.69 5.58 5.04 4.01 3.24 5.3219 Zhob 31.1 68.5 2065 3.53 4.49 5.36 6.08 6.79 6.85 6.55 6.07 5.78 4.96 3.99 3.36 5.3220 Mardan / Swabi 34.2 72 1016 3.08 3.77 4.76 6.18 7.31 7.88 6.96 6.21 5.87 5.01 3.76 2.86 5.3121 Qilla Saifullah / Loralai 30.43 68.21 1608 3.65 4.55 5.25 5.99 6.75 6.83 6.41 5.95 5.62 4.91 3.98 3.46 5.2822 Dadu 26.44 67.47 244 3.88 4.62 5.32 6.29 6.67 6.72 6.08 5.83 5.46 4.91 4.01 3.61 5.2823 Hyderabad / Jamshoro 25.23 68.25 26 3.7 4.42 5.41 6.41 6.88 6.98 6.2 5.95 5.62 4.54 3.7 3.42 5.2724 Ghotki 28.05 69.21 150 3.76 4.47 5.09 6.22 6.94 7.01 6.42 5.93 5.28 4.55 3.77 3.4 5.2425 Nawabshah /Sanghar/Shahdadkot/Nosheroferoz 26.15 68.25 33 3.99 4.71 5.41 6.09 6.42 6.41 5.77 5.6 5.56 5 4.21 3.75 5.2426 Islamabad / Rawalpindi 33.4 73.1 770 3.18 3.87 4.95 6.31 7.27 7.54 6.44 5.72 5.69 5.07 3.89 2.77 5.2427 Sibi / Bolan / 29.33 67.53 805 3.59 4.34 4.96 6.15 6.72 6.92 6.43 6.02 5.65 4.78 3.91 3.29 5.2328 Peshawar/charsadda/noshera 34.01 71.33 913 3.09 3.79 4.78 5.99 7.07 7.68 6.96 6.19 5.69 4.86 3.72 2.88 5.2329 Badin 24.39 68.5 6 4.19 4.92 5.64 6.38 6.5 6.4 5.41 5.12 5.31 4.91 4.24 3.84 5.2330 Jhelum 32.56 73.44 248 3.21 4.13 5.18 6.43 7.32 7.35 5.88 5.64 5.47 4.93 3.92 3.12 5.2131 Dera bugti / Barkhan 29.02 69.09 906 3.66 4.42 5.09 6.18 6.83 6.92 6.39 5.98 5.47 4.51 3.67 3.27 5.2032 Attock / Chakwal 33.54 72.15 420 3.19 3.92 4.87 6.22 7.16 7.43 6.48 5.75 5.51 4.93 3.84 2.97 5.1933 Rahim yar khan 28.26 70.19 84 3.65 4.46 5.13 6.11 6.82 6.86 6.41 5.89 5.26 4.58 3.77 3.39 5.1934 Gawadar 25.07 62.19 76 3.92 4.61 5.22 6.1 6.4 6.46 5.88 5.58 5.36 5 4.19 3.59 5.1935 Jafarabad /Nasirabad /Jhal Magsi 28.16 67.86 390 3.78 4.55 5.05 5.96 6.49 6.49 5.88 5.63 5.51 4.96 4.11 3.48 5.1636 Tharparker 25 70.15 125 4.08 4.74 5.47 6.1 6.4 6.36 5.47 5.21 5.32 4.87 4.15 3.15 5.1537 Bahawalpur 29.2 71.47 108 3.61 4.47 5.25 5.99 6.53 6.67 6.21 5.67 5.31 4.65 3.84 3.34 5.1338 Umar kot 26.15 69.4 51 3.93 4.61 5.26 5.96 6.32 6.39 5.77 5.51 5.44 4.79 4.01 3.62 5.1339 Sargodha 32.05 72.4 373 3.26 4.13 5.08 6.24 7.12 7.14 6.01 5.56 5.19 4.63 3.76 3.08 5.1040 Muzaffarabad / Balakot 34.22 73.29 2275 2.95 3.57 4.55 5.88 6.99 7.46 6.6 5.94 5.7 4.88 3.69 2.79 5.0941 Faisalabad 31.26 73.08 186 3.25 4.19 5.09 6.01 6.71 6.65 5.99 5.6 5.37 4.65 3.73 3.14 5.0342 Jhang /Rajanpur /Toba Tek Singh 31.16 72.19 164 3.35 4.29 5.12 5.84 6.78 6.92 6.19 5.67 5.16 4.33 3.53 3.09 5.0243 Hangu / Karak / Kohat 33.32 71.04 655 3.18 3.89 4.74 5.92 6.86 6.96 6.12 5.64 5.33 4.86 3.79 2.98 5.0244 Okara /Sahiwal /Vehari /Pakpatan 30.49 73.27 162 3.26 4.29 5.07 5.94 6.48 6.62 6 5.53 5.24 4.59 3.8 3.18 5.0045 Bannu 32.59 70.36 517 3.34 4.09 4.88 6.04 6.46 6.72 5.8 5.51 5.15 4.67 3.81 3.15 4.97

46 Bhakkar / Layyah 31.4 71.05 165 3.44 4.35 5.13 5.76 6.21 6.35 5.79 5.56 5.23 4.53 3.67 3.13 4.93

47 DG Khan 30.03 70.38 492 3.59 4.33 5.01 5.65 6.18 6.1 5.7 5.45 5.23 4.75 3.86 3.32 4.93

48 Multan / Muzaffargarh 30.12 71.26 124 3.44 4.22 4.99 5.78 6.19 6.36 5.76 5.44 5.21 4.69 3.79 3.19 4.92

22 year Monthly & Annual Average Solar Insolation (Kwh/m2/day) on a horizontal surface in District cities of Pakistan

253

Appendix C: Equipment Operation Parameters

Typical Construction Materials and Dimensions Used in Pakistan

254

Evacuated Tube Collector Type71 Parameters

Parameter Value Unit

Number in series 1 -

Collector area 12 m2 ( optimised value)

Fluid specific heat 4.19 kJ/kg.K

Efficiency mode 2 (optimised Value)

Flow rate at test conditions 3 kg/hr.m2

Intercept efficiency 0.7 (default)

Negative of first order efficiency coefficient 9 kJ/hr.m2.K (Reference Model)

Negative of second order efficiency coefficient 0.03 kJ/hr.m2.K2(Reference Model)

Logical unit of file containing biaxial IAM data 60 (default)

Number of longitudinal angles for which IAMs are provided 5 (default)

Number of transverse angles for which IAMs are provided 5 (default)

Inlet temperature °C (Storage tank cold side temperature)

Inlet flow rate 165kg/hr

Ambient temperature

Input from weather data

Incident radiation

Incident diffuse radiation

Solar incidence angle

Solar zenith angle

Solar azimuth angle

Collector slope 0 Degrees (optimised)

Collector azimuth 90 Degrees (optimised)

Auxiliary cooler Type 1246

Parameter Value Unit

Rated capacity 21000 kJ/hr (optimised)

Specific heat of fluid 4.19 kJ/kg.K

Inlet fluid temperature

°C (Chiller outlet cooling water)

Inlet flow rate 800 kg/hr (optimised)

Control function 1 -

Set point temperature 25 °C (optimised)

Overall loss coefficient 0 kJ/hr.K (default)

Temperature of surroundings

°C (Input from weather data)

255

Hot water storage tank Type4a

Parameter value Unit

Fixed inlet positions 1 default

Tank volume 2.0 m3 (optimised )

Fluid specific heat 4.19 kJ/kg.K

Fluid density 1000 kg/m3

Tank loss coefficient 0.6 kJ/hr.m2.K (Referenced)

Height of node-1 0.1 m

Height of node-2 0.1 m

Height of node-3 0.1 m

Height of node-4 0.1 m

Height of node-5 0.1 m

Height of node-6 0.1 m

Height of node-7 0.1 m

Height of node-8 0.1 m

Height of node-9 0.1 m

Height of node-10 0.1 m

Auxiliary heater mode 1 (off)

Node containing heating element 1 1 (top most element)

Node containing thermostat 1 1 (top most element)

Set point temperature for element 1 0 (off)

Dead band for heating element 1 5 delta °C (default)

Maximum heating rate of element 1 0 kJ/hr (off)

Node containing heating element 2 1 (top most element)

Node containing thermostat 2 1 (top most element)

Set point temperature for element 2 0 (off)

Dead band for heating element 2 5 delta °C (default)

Maximum heating rate of element 2 0 kJ/hr (off)

Not used (Flue UA) 0 W/K (not in use for storage tank)

Not used (T flue) 20 (not in use for storage tank)

Boiling point 100 °C

Hot-side temperature

°C (Collector Outlet water Temperature)

Hot-side flow rate 165 Kg/hr

Cold-side temperature

°C (Chiller Outlet water Temperature)

Cold-side flow rate 150 Kg/hr

Environment temperature °C(Input from weather data)

256

Chiller Type 107

Parameter Value Unit

Rated capacity 12660 kJ/hr (design)

Rated COP 0.6 - (Referenced)

Logical unit for S1 data file 40 (default)

Number of HW temperatures in S1 data file 5 (default)

Number of CW steps in S1 data file 3 (default)

Number of CHW set points in S1 data file 7 (default)

Number of load fractions in S1 data file 11 (default)

HW fluid specific heat 4.19 kJ/kg.K

CHW fluid specific heat 4.19 kJ/kg.K

CW fluid specific heat 4.19 kJ/kg.K

Auxiliary electrical power 220 kJ/hr (Referenced)

Chilled water inlet temperature

°C (chilled water outlet from Cooling coil)

Chilled water flow rate 250 kg/hr (optimised)

Cooling water inlet temperature

°C (Cooled water outlet from cooling tower)

Cooling water flow rate 800 kg/hr (optimised)

Hot water inlet temperature

°C (Hot water outlet from storage tank)

Hot water flow rate 150 kg/hr (optimised)

CHW set point 6.667 °C (default)

Chiller control signal 1 (default)

Fan Type 112b

Parameter Value Unit

Humidity mode 2 default -% relative humidity

Rated flow rate 300 kg/hr (optimised)

Rated power 80 kJ/hr (Referenced)

Motor efficiency 0.9 -(default)

Motor heat loss fraction 0 -(default)

Inlet air temperature

°C (Room air temperature)

Not used (w) 0.008 (default)

Inlet air %RH 0 % (base 100) (dry air)

Inlet air pressure 1 atm (default)

Control signal 1 (default)

Air-side pressure increase 0 Atm (default)

257

Cooling Coil Type 697

Parameter Value Unit

Humidity mode 2 default -% relative humidity

Logical unit - water corrections 52 (default)

Number of water flow rates 3 -(default)

Number of water temperatures 3 -(default)

Logical unit - air flow corrections 53 -(default)

Number of air flows 7 -(default)

Logical unit - air temperature corrections 54 -(default)

Number of dry-bulb temperatures 7 -(default)

Number of wet-bulb temperatures 6 -(default)

Fluid density 1000 kg/m3

Fluid specific heat 4.19 kJ/kg.K

Rated volumetric air flow rate 200 l/s (optimised)

Rated volumetric liquid flow rate 0.3 l/s (default)

Total cooling capacity 9000 kJ/hr (optimised)

Sensible cooling capacity 7150 kJ/hr (optimised)

Fluid inlet temperature 7 °C (Chilled water from chiller outlet)

Fluid flow rate 250 kg/hr

Inlet air temperature

Fan outlet air

Inlet air flow rate 300 kg/hr (Fan outlet flow rate)

Inlet air pressure 1 atm (default)

Air-side pressure drop 0 atm (default)

Thermostat Type 108

Parameter Value Unit

No of oscillations permitted 5 (default)

1st stage heating in 2nd stage? 0 No heating

2nd stage heating in 3rd stage? 0 No heating

1st stage heating in 3rd stage? 0 No heating

1st stage cooling in 2nd stage? 1 cooling

Temperature dead band 0.5 Delta °C (optimised)

Monitoring temperature Room air temperature

1st stage heating set point 10 °C

2nd stage heating set point 10 °C

3rd stage heating set point 10 °C

1st stage cooling set point 20.65 °C (optimised)

2nd stage cooling set point 28 °C (optimised)

258

YAZAKI (HWF-SC5) ABSORPTION CHILLER PERFORMANCE

CHARACTERISTICS

259

Appendix D: System Heat Balance

ENERGY IN PUTS (kWh)

Month Collector Heat Gain Heat from Room Pumps Electricity

January 192.18 0.00 120.81

February 288.16 63.01 114.46

March 762.33 453.27 137.35

April 1163.05 683.82 132.92

May 1584.59 998.43 137.35

June 1904.82 1165.58 132.92

July 1778.11 1085.48 137.35

August 1637.03 1008.11 137.35

September 1409.45 807.24 132.92

October 1065.22 669.86 137.35

November 667.41 332.05 132.92

December 208.03 24.04 120.81

Total 12660.38 7290.90 1574.48

ENERGY OUT PUT (kWh)

Month Cooler Heat Rejected Tank Heat Loss Pipes Heat Loss

January 48.65 319.97 41.63

February 210.81 520.45 39.76

March 1245.47 228.36 28.17

April 1854.15 90.51 7.94

May 2686.79 22.43 -4.75

June 3126.14 -56.26 -16.09

July 2916.40 -64.56 -16.26

August 2712.29 -30.49 -11.32

September 2180.42 5.81 -5.25

October 1818.59 23.96 0.12

November 924.24 71.98 11.40

December 112.51 295.93 38.40

Total 19836.46 1428.10 113.76

260

System Total Energy Balance (kWh)

Month Total input Total output Internal Energy

Change

Net Balance

(Input-Output)

January 313.00 410.24 -97.03 -97.25

February 465.63 771.02 12.07 -305.39

March 1352.95 1502.01 62.24 -149.06

April 1979.79 1952.60 4.83 27.19

May 2720.36 2704.48 76.04 15.89

June 3203.31 3053.78 2.39 149.52

July 3000.94 2835.59 -7.62 165.35

August 2782.49 2670.48 19.04 112.01

September 2349.60 2180.99 -63.87 168.62

October 1872.42 1842.67 54.40 29.76

November 1132.37 1007.62 -82.01 124.75

December 352.89 446.84 -80.87 -93.95

Total 21525.76 21378.32 -100.40 147.45