Corrugate COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) www.metalcraftroofing.co.nz Architectural / Specification Enquiries Ph: 09 274 0408 Mobile: 027 603 1096 Email: [email protected] CHCG 00 / 23 COVER SHEET 01 / 23 PARAPET AND BALUSTRADE CAPPING 02 / 23 SOFFIT 03 / 23 FLUSH WINDOW HEAD 04 / 23 FLUSH WINDOW SILL 05 / 23 FLUSH WINDOW JAMB 06 / 23 RECESSED WINDOW HEAD 07 / 23 RECESSED WINDOW SILL 08 / 23 RECESSED WINDOW JAMB 09 / 23 BUTT WINDOW HEAD 10 / 23 BUTT WINDOW SILL 11 / 23 BUTT WINDOW JAMB 12 / 23 METERBOX HEAD 13 / 23 METERBOX SILL 14 / 23 METERBOX JAMB 15 / 23 INTERNAL CORNER 16 / 23 EXTERNAL CORNER 17 / 23 INTERNAL CORNER BOX TYPE 18 / 23 EXTERNAL CORNER BOX TYPE 19 / 23 SOAKER FLASHING 20 / 23 VERTICAL BUTT JOINT 21 / 23 BOTTOM OF CLADDING (FLUSH) 22 / 23 BOTTOM OF CLADDING (RECESSED) 23 / 23 3D WINDOW FLASHINGS DETAIL LIST

S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

CorrugateCOMMERCIAL HORIZONTAL CLADDING

0800 ROOFNZ (0800 766 369)www.metalcraftroofing.co.nz

Architectural / Specification EnquiriesPh: 09 274 0408

Mobile: 027 603 1096Email: [email protected]

00 / 23 COVER SHEET01 / 23 PARAPET AND BALUSTRADE CAPPING02 / 23 SOFFIT03 / 23 FLUSH WINDOW HEAD04 / 23 FLUSH WINDOW SILL05 / 23 FLUSH WINDOW JAMB06 / 23 RECESSED WINDOW HEAD07 / 23 RECESSED WINDOW SILL08 / 23 RECESSED WINDOW JAMB09 / 23 BUTT WINDOW HEAD10 / 23 BUTT WINDOW SILL11 / 23 BUTT WINDOW JAMB12 / 23 METERBOX HEAD13 / 23 METERBOX SILL14 / 23 METERBOX JAMB15 / 23 INTERNAL CORNER16 / 23 EXTERNAL CORNER17 / 23 INTERNAL CORNER BOX TYPE18 / 23 EXTERNAL CORNER BOX TYPE19 / 23 SOAKER FLASHING20 / 23 VERTICAL BUTT JOINT21 / 23 BOTTOM OF CLADDING (FLUSH)22 / 23 BOTTOM OF CLADDING (RECESSED)23 / 23 3D WINDOW FLASHINGS

DETAIL LIST

Page 2: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER SHOWN DASHED

PRE-FINISHED SELF DRILLING / TAPPINGSCREW WITH RUBBER WASHER

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

METALCRAFT MSS PURLINBY ENGINEER

MIN

. 5.00°

20mm CAVITY

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

CLE

ARAN

CE

25m

m

PRE-FINISHED PARAPET CAP FLASHINGNO FIXINGS ON TOP OF FLASHING

CONTINUOUS H3.1 TIMBER PACKING

BUILDING PAPER TO PROVIDESEPARATION OF METAL CAPPING ANDCLADDING WITH TIMBER SHOWN DASHED

CLE

ARAN

CE

25m

m

BIRDS BEAK EDGE FORDECK SIDE OF CAPPING

5 GAP

20

15

MIN

. 2 C

OR

RU

GAT

ION

S

MIN

. 2 C

OR

RU

GAT

ION

S

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 01 / 23

PARAPET AND BALUSTRADE CAPPING

2014

Page 3: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER OVERFLASHING SHOWN DASHED

INTERNAL WALL LINING

METALCRAFT MSS PURLINBY ENGINEER

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

PRE-FINISHED SOFFIT FLASHING BARGE BOARD

SOFFIT LINING

METALCRAFTMSS PURLIN BYENGINEER

PRE-FINISHED SELFDRILLING/TAPPING SCREWWITH RUBBER WASHER

INTERNAL CEILING LINING

CO

VER

CLA

DD

ING

40 m

m (M

IN. 3

5mm

)

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED20mm CAVITY

5mm GAP MIN. 50mm

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 02 / 23

SOFFIT

2014

Page 4: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER DRESSED INTOOPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TOCORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

INTERNAL WALL LINING

METALCRAFT MSS PURLIN BY ENGINEER

METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

DOUBLE GLAZING WINDOW JOINERY

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILLAND JAMB

WINDOW HEAD LINER

LINE OF WINDOW JAMBLINER BEHIND

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

METALCRAFT MSS PURLIN BYENGINEER

5mm

GAP

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

PVC CAVITY CLOSER

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

MIN

. 10m

m C

OVE

RDR

IP E

DG

E TO

CLA

DD

I NG

MIN

. 15m

m G

AP

MIN

. 75m

m W

ITH

OU

T H

EM

ED

GE

MIN

. 50m

m C

OVE

R

SU

GG

EST

MIN

. 50m

m

DIM

ENS

ION

TO

SU

IT

COMPRESSIBLE FOAM SEAL TO FILLOVERLAP OF FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 03 / 23

FLUSH WINDOW HEAD

2014

Page 5: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

BUILDING PAPER SHOWN DASHED

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW JAMBLINER BEHIND

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

WINDOW SILL SUPPORT BAR

METALCRAFT MSS PURLIN BY ENGINEER

INTERNAL WALL LINING

STOPENDS TO SILL FLASHING

LINE OF JAMB FLASHING BEHIND

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL

PRE-FINISHED WINDOW SILLFLASHING

5mm GAP MIN

. 8m

m C

OV

ER

20mm CAVITY

CO

VER

CLA

DD

ING

50m

m(M

IN. 3

5mm

)

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

PRE-FINISHED SECONDARY FLASHING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 04 / 23

FLUSH WINDOW SILL

2014

Page 6: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

BUILDING PAPER SHOWN DASHED

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW SILL LINER BELOW

WINDOW JAMB LINER

TIMBER PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

20mm JAMB BATTEN

INTERNAL WALL LINING

LINE OF SILL FLASHING BELOW

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

METALCRAFT MSS PURLIN BYENGINEER

LINE OF SILL FLASHING BELOW

PRE-FINISHED WINDOW JAMBFLASHING

PRE-FINISHED SECONDARYFLASHING

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

MIN. 10mm COVER

20mm CAVITY

BUILDING PAPER TO PROVIDESEPARATION OF FLASHINGAND CLADDING WITH TIMBERSHOWN DASHED

5mm

GAP

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.

SUGGEST MIN. 50mm

DIMENSION TO SUIT

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

LINE OF HEAD FLASHING ABOVE

PRE-FINISHED POP RIVET BEDDEDIN SILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

COMPRESSIBLE FOAM SEAL TO FILLOVERLAP OF FLASHING

LINE OF HEAD FLASHING ABOVE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 05 / 23

FLUSH WINDOW JAMB

2014

Page 7: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER DRESSED INTOOPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TOCORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

INTERNAL WALL LINING METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

DOUBLE GLAZING WINDOW JOINERY

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

WINDOW HEAD LINER

LINE OF WINDOW JAMBLINER BEHIND

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

DR

IP E

DG

E TO

CLA

DD

I NG

MIN

. 15m

m G

AP

MIN

. 10m

m C

OVE

R

5mm

GAP M

IN.7

5mm

WIT

HO

UT

HE

M E

DG

E

MIN

. 50m

m C

OVE

R

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

SU

GG

EST

MIN

.50m

m

DIM

ENS

ION

TO

SU

IT

PVC CAVITY CLOSER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 06 / 23

RECESSED WINDOW HEAD

2014

Page 8: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

BUILDING PAPER SHOWN DASHED

PRE-FINISHED WINDOW SILL FLASHING

LINE OF WINDOW JAMBLINER BEHIND

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

WINDOW SILL SUPPORT BAR

INTERNAL WALL LINING

STOPENDS TO SILL FLASHING

LINE OF JAMB FLASHING BEHIND

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

20mm CAVITY

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

DOUBLE GLAZING WINDOW JOINERY

METALCRAFT MSS PURLIN BY ENGINEER

5mm

GAP

MIN

. 8m

m C

OV

ER

PRE-FINISHED SECONDARY FLASHING

BUILDING PAPER DRESSED INTOOPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TOCORNERS AT SILL

CLA

DD

ING

CO

VER

50m

m(M

IN. 3

5mm

)

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 07 / 23

RECESSED WINDOW SILL

2014

Page 9: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

PRE-FINISHED POP RIVET BEDDED IN SILICONEOR PRE-FINISHED 8g WAFER-TEK SCREW DOUBLE GLAZING WINDOW JOINERY

LINE OF HEAD FLASHING ABOVE

PRE-FINISHED SELFDRILLING/TAPPING SCREWWITH RUBBER WASHER

PRE-FINISHED SECONDARYFLASHING

20mm CAVITY

INTERNAL WALL LINING

BUILDING PAPER SHOWN DASHED

LINE OF WINDOW SILL LINER BELOW

WINDOW JAMB LINER

TIMBER PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

20mm JAMB BATTEN

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

METALCRAFT MSS PURLIN BYENGINEER

5mm

GAP

5mm GAP

MIN. 10mm COVERMETALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.

SUGGEST MIN. 50mm

DIMENSION TO SUIT

LINE OF SILL FLASHING BELOW

LINE OF HEAD FLASHING ABOVE

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

PRE-FINISHED WINDOW JAMBFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 08 / 23

RECESSED WINDOW JAMB

2014

Page 10: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

20mm CAVITY

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PRE-FINISHED WINDOW HEADFLASHING WITH 15° FALL

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

DOUBLE GLAZING WINDOW JOINERYWINDOW HEAD LINER

LINE OF WINDOW JAMB LINERBEHIND

STOPENDS TO HEAD FLASHING

LINE OF JAME FLASHING BEHIND

BUILDING PAPER DRESSED INTOOPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TOCORNERS AT HEAD

INTERNAL WALL LINING

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

METALCRAFT MSS PURLIN BY ENGINEER

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

MIN

.75m

m W

ITH

OU

T H

EM

ED

GE

MIN

. 50m

m C

OVE

R

DR

IP E

DG

E TO

CLA

DD

ING

MIN

. 15m

m G

AP

METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

5mm

GAP

MIN

.10m

m C

OVE

R

SU

GG

EST

MIN

. 50m

m

DIM

ENS

ION

TO

SU

IT

PVC CAVITY CLOSER

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FORFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 09 / 23

BUTT WINDOW HEAD

2014

Page 11: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

PRE-FINISHED SECONDARY FLASHING

STOPENDS TO SILL FLASHING

LINE OF JAMB FLASHING BEHIND

DOUBLE GLAZING WINDOW JOINERY

LINE OF WINDOW JAMBLINER BEHIND

WINDOW SILL LINER

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

BUILDING PAPER SHOWN DASHED

20mm CAVITY

INTERNAL WALL LINING

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

METALCRAFT MSS PURLIN BY ENGINEER 5mm

GAP

MIN

. 8m

m C

OV

ER

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

WINDOW SILL SUPPORT BAR

PRE-FINISHED WINDOW SILL FLASHING

SU

GG

EST

MIN

.50m

m

DIM

ENS

ION

TO

SU

IT

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

5mm GAP

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 10 / 23

BUTT WINDOW SILL

2014

Page 12: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

PRE-FINISHED SELFDRILLING/TAPPING SCREWWITH RUBBER WASHER

DOUBLE GLAZING WINDOW JOINERY

LINE OF SILL FLASHING BELOWCONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

INTERNAL WALL LINING

BUILDING PAPER SHOWN DASHED

LINE OF WINDOW SILL LINER BELOW

WINDOW JAMB LINER

TIMBER PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

20mm JAMB BATTEN

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

METALCRAFT MSS PURLIN BYENGINEER

5mm GAP 5mm GAP

MIN. 50mm

MIN. 10mm COVER

5mm

GAP

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED WINDOW JAMBFLASHING

SUGGEST MIN. 50mm

DIMENSION TO SUIT

LINE OF HEAD FLASHING ABOVE

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

LINE OF HEAD FLASHING ABOVE

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 11 / 23

BUTT WINDOW JAMB

2014

Page 13: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER DRESSED INTOOPENING WITH FLEXIBLE FLASHINGTAPE INSTALLED OVER WRAP TOCORNERS AT HEAD

TEMPORARY PACKER IF REQUIRED,REMOVED AFTER FIXING

EXTRA BUILDING PAPER OVER WINDOWHEAD FLASHING SHOWN DASHED

METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

PRE-FINISHED HEAD FLASHINGWITH 15° FALL

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD, SILLAND JAMB

METER BOX

STOPENDS TO HEAD FLASHING

LINE OF JAMB FLASHING BEHIND

PRE-FINISHED FLASHING

METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.

INTERNAL WALL LINING

METALCRAFT MSS PURLIN BY ENGINEER

DR

IP E

DG

E TO

CLA

DD

ING

MIN

. 15m

m G

AP

5mm

GAP M

IN. 7

5mm

WIT

HO

UT

HE

M E

DG

E

MIN

. 50m

m C

OVE

R

PRE-FINISHED 'U' BRACKET FIXED TOMETERBOX BEFORE INSTALLATION

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWN DASHED

PVC CAVITY CLOSER

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 12 / 23

METERBOX HEAD

2014

Page 14: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATE HORIZONTALWALL CLADDING

BUILDING PAPER SHOWN DASHED

METER BOX

INTERNAL WALL LINING

MIN. 8mm PACKER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

METALCRAFT MSS PURLIN BYENGINEER

INTERNAL WALL LINING

LINE OF JAMB FLASHING BEHIND

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER FORWINDOW SUPPORT BAR

20mm CAVITY

FLEXIBLE FLASHING TAPE OVERBUILDING PAPER FOR FULLWIDTH/DEPTH SILL

METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.

PRE-FINISHED FLASHING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

STOPENDS TO SILL FLASHING

CO

VER

CLA

DD

ING

50m

m(M

IN. 3

5mm

)

PRE-FINISHED SECONDARYFLASHING

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 13 / 23

METERBOX SILL

2014

Page 15: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER SHOWN DASHED METER BOX

TIMBER PACKER

20mm JAMB BATTEN

PRE-FINISHED WINDOW JAMBFLASHING FIXED TO METERBOXBEFORE INSTALLATION

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

FLEXIBLE FLASHING TAPE OVER BUILDINGPAPER FOR FULL WIDTH/DEPTH SILL

LINE OF HEAD FLASHING ABOVE

20mm CAVITY

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

METAL ANGLE TO BE CONTINUOUSAROUND METER BOX.

INTERNAL WALL LININGMETALCRAFT MSS PURLIN BY ENGINEER

AIRSEAL ON BACKING ROD TO RUNCONTINUOUSLY AROUND HEAD,SILL AND JAMB

CONTINUOUS COMPRESSIBLE FOAMSEAL. REFER TO MRM CODE OFPRACTICE VERSION 2.2 /2012 FORREQUIRMENT.

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEKSCREW

SUGGEST MIN. 50mm

DIMENSION TO SUIT

LINE OF SILL FLASHING BELOW

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 14 / 23

METERBOX JAMB

2014

Page 16: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

20mm CAVITYPRE-FINISHED POP RIVETBEDDED IN SILICONE ORPRE-FINISHED 8g WAFER-TEK SCREW

INTERNAL WALL LINING

PRE-FINISHED FIXING BRACKETWITH PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

BUILDING PAPER SHOWNDASHED

STRUCTURAL COLUMN BYENGINEER

METALCRAFT MSS PURLIN BYENGINEER

SU

GG

EST

MIN

. 75m

m

DIM

ENS

ION

TO

SU

IT

SUGGEST MIN. 75mm

DIMENSION TO SUIT

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT.

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED INTERNALCORNER FLASHING

PRE-FINISHED SECONDARYFLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 15 / 23

INTERNAL CORNER

2014

Page 17: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT MSS PURLIN BYENGINEER

20mm CAVITY

PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER

PRE-FINISHED EXTERNALCORNER FLASHING

BUILDING PAPER SHOWN DASHEDBUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

STRUCTURAL COLUMN BYENGINEER

SUGGEST MIN. 75mm

DIMENSION TO SUIT

SU

GG

EST

MIN

. 75m

m

DIM

ENS

ION

TO

SU

IT

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

PRE-FINISHED POP RIVETBEDDED IN SILICONE ORPRE-FINISHED 8g WAFER-TEK SCREW

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRM CODEOF PRACTICE VERSION 2.2 /2012FOR REQUIRMENT.

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

PRE-FINISHED SECONDARY FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 16 / 23

EXTERNAL CORNER

2014

Page 18: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

20mm CAVITY

INTERNAL WALL LINING

PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER

BUILDING PAPER SHOWNDASHED

STRUCTURAL COLUMN BYENGINEER

METALCRAFT MSS PURLIN BYENGINEER

MIN. 50mm COVER

MIN

. 50m

m C

OVE

R

5mm

GAP5mm GAP

PRE-FINISHED INTERNAL CORNERFLASHING

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT.

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 17 / 23

INTERNAL CORNER BOX TYPE

2014

Page 19: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

20mm CAVITY

PRE-FINISHED SELFDRILLING/TAPPING SCREWWITH RUBBER WASHER

PRE-FINISHED EXTERNALCORNER FLASHING

BUILDING PAPER SHOWNDASHED

STRUCTURAL COLUMNBY ENGINEER

MIN. 50mm COVER

MIN

. 50m

m C

OC

ER5mm

GAP

5mm GAP

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBERSHOWN DASHED

CONTINUOUS COMPRESSIBLEFOAM SEAL. REFER TO MRMCODE OF PRACTICE VERSION 2.2/2012 FOR REQUIRMENT.

PRE-FINISHED FLAT HEADWAFER-TEK SCREW FORFLASHING

METALCRAFT MSS PURLIN BYENGINEER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 18 / 23

EXTERNAL CORNER BOX TYPE

2014

Page 20: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER SHOWNDASHED

METALCRAFTCORRUGATEHORIZONTAL WALLCLADDING

PRE-FINISHED FLAT HEADWAFER-TEK SCREW FORFLASHING

INTERNAL WALL LINING

METALCRAFT MSS PURLINBY ENGINEER

PRE-FINISHED SOAKERFLASHING BELOWWINDOW JAMBS

METALCRAFT MSS PURLINBY ENGINEER

BUILDING PAPER TOPROVIDE SEPARATIONOF FLASHING ANDCLADDING WITH TIMBERSHOWN DASHED

SOAKER FLASHING ONLY REQUIRED TOLINE UP WITH WINDOW JAMB ABOVE.REFER TO MRM CODE OF PRACTICEVERSION 2.2 /2012 FOR REQUIRMENT.

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 19 / 23

SOAKER FLASHING

2014

Page 21: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER SHOWNDASHED

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

PRE-FINISHED SELFDRILLING / TAPPING SCREWWITH RUBBER WASHER

INTERNAL WALL LINING

METALCRAFT MSS PURLIN BYENGINEER

PRE-FINISHED SOAKERFLASHING

METALCRAFT MSS PURLINBY ENGINEER

5mm GAP

MIN. 50mm COVER

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBERSHOWN DASHED

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 20 / 23

VERTICAL BUTT JOINT

2014

Page 22: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

20mm CAVITY

INTERNAL WALL LINING

BUILDING PAPER OVER FLASHINGSHOWN DASHED

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

PRE-FINISHED FLAT HEAD WAFER-TEK SCREW FOR FLASHING

PRE-PRIMED SKIRTING

CONCRETE SLAB

METALCRAFT MSS PURLIN BYENGINEER

DR

IP E

DG

E TO

CLA

DD

I NG

MIN

. 15m

m G

AP

MIN

. 50m

m L

AP

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER FOR FLASHING

PVC CAVITY CLOSER

VEN

TILA

TIO

N G

AP

3-5m

m

PRE-FINISHED NON-PERFORATEDCLOSER FLASHING WITH 10° FALL

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 21 / 23

BOTTOM OF CLADDING (FLUSH)

2014

Page 23: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

BUILDING PAPER OVER FLASHINGSHOWN DASHED

METALCRAFT CORRUGATEHORIZONTAL WALL CLADDING

PRE-FINISHED SELFDRILLING/TAPPING SCREW WITHRUBBER WASHER

PRE-FINISHED FLAT HEAD WAFER-TEKSCREW FOR FLASHING

INTERNAL WALL LINING

20mm CAVITY

PRE-PRIMED SKIRTING

CONCRETE SLAB

MIN

. 75m

m C

OV

ER

VEN

TILA

TIO

N G

AP

3-5m

m

MIN

. 50m

m L

AP

BUILDING PAPER TO PROVIDESEPARATION OF FLASHING ANDCLADDING WITH TIMBER SHOWNDASHED

ALTERNATIVE OPTIONBIRDS BEAK EDGE

5 GAP

20

15

HEMMED EDGE

PRE-FINISHED NON-PERFORATEDCLOSURE FLASHING WITH 10° FALL

PVC CAVITY CLOSER

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG

- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.

1 : 2 22 / 23

BOTTOM OF CLADDING (RECESSED)

2014

Page 24: S: 5 Metalcraft Roofing01 BIMDetailsCorrugateCHCG ...€¦ · COMMERCIAL HORIZONTAL CLADDING 0800 ROOFNZ (0800 766 369) Architectural / Specification Enquiries Ph: 09 274 0408 Mobile:

ScaleDate Sheet

Corrugate

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.

COMMERCIAL HORIZONTAL CLADDING

CHCG 23 / 23

3D WINDOW FLASHINGS

2014

HEAD FLASHING

JAMB FLASHING

SILL FLASHING

FLUSH WINDOW FLASHINGS RECESSED WINDOW FLASHINGS

HEAD FLASHING

JAMB FLASHING

SILL FLASHING

METALCRAFTCORRUGATEVERTICALCLADDING

ALUMINIUMWINDOWJOINERY

COMPRESSIBLEFOAM SEALBEHIND TO FILLOVERLAP OFFLASHING

METALCRAFTCORRUGATEVERTICALCLADDING

ALUMINIUMWINDOWJOINERY