4
This handout answers questions most often asked by homeowners. This information is a guide to the most common questions. It is not intended, nor shall it be considered, a complete set of requirements. The wiring must be done to the standards of the latest state-adopted National Electrical Code (NEC). Libraries and electrical supply dealers may have other books available to further assist you. An Electrical Permit is required for all electrical work, including wiring a garage. In a single-family residence, experienced owners/homesteaders may obtain the permit to do the work themselves. For other residential occupancies, such as rental properties, an electrical contractor must be hired to do the work and obtain the permit. Rules to operate by: 1. Most homeowners choose to run the electrical underground. The two most popular methods are direct-burial cable or PVC (plastic) conduit. Direct burial cable is designated as UF (Underground Feeder) or for larger sizes, USE (Underground Service Entrance). Direct-burial cables may be buried in the ground at 24 inches below grade. They must have mechanical protection, such as PVC conduit, wherever they are closer than 24 inches below grade. The most common point where this occurs is when the run is brought up above grade to enter the house and garage. PVC conduit must be approved as electrical conduit. Other types, such as PVC plumbing pipe, are not acceptable. Standard insulated conductors may be pulled inside the PVC. These single conductors must have a “W” (water-resistant) in the designation stamped on the jacket of the wire. Examples of such designations include: THWN, XHHW, etc. Type “Romex” or Non-Metallic Cable (NM-B) cannot be run inside underground conduit, because the outer jacket of the NM-B is not rated for wet locations. PVC conduit must be buried at 18 inches below grade. (This is measured to the top of the conduit, so the trench will have to be deeper than 18 inches.) 2. A disconnect must be installed in the garage to shut off all power to the building. This disconnect must be immediately inside the garage at the entrance point of the feed from the house. If you are using a multi-circuit panelboard in the garage and have no more than six breakers in the panel, these breakers may be used as the disconnecting means. When using more than six breakers, a main breaker is required in the panelboard. If you are running a single 15- or 20- ampere circuit from the house to feed a minimum number of lights and outlets, you may use a separate single-pole switch (such as a standard light switch) as a disconnect. This switch must be the first device that is on the circuit once it enters the garage; it may be used only as a disconnect and cannot be used to control lights or other equipment. This disconnect must be labeled as the disconnect switch on its box cover. See Detached Garage Supplied by a Three Wire Branch Circuit. 3. Romex or NM-B may be used inside the garage. It must be drilled and inserted through the studs, not run on the face of them. Also, never drill through factory roof trusses, run the Romex or NM-B on the top edge in a location where it will not be damaged. Romex or NM-B cable is to be routed so it is not subject to physical damage. 4. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in garages must be a Tamper- Resistant (TR) type and protected by a Ground Fault Circuit Interrupter (GFCI), including any receptacles for garage door openers or specific appliances. There are two forms of GFCI-protected devices. You may use a tamper-resistant receptacle-type, GFCI-protected device or a breaker-style GFCI protective device. Both devices are installed at the beginning of the circuit to be protected and several standard tamper-resistant outlets may be protected “downstream” by one GFCI outlet. See the manufacturer’s instructions for details. On a GFCI, the line is the power in and the load is the power out to other receptacles. TR receptacles are designed with a “shutter” over the slots so only a standard cord cap (plug) can be inserted. Add-on plug covers are not acceptable. Any receptacles on the exterior of the garage must be tamper-resistant (TR), GFCI-protected and Weather Resistant (WR). (There will be a “WR” visible on the face of the receptacle.) Residential Detached Garage Wiring Information Sheet Community Development Building and Inspection 1800 W. Old Shakopee Road Bloomington MN 55431-3027 PH 952-563-8930 FAX 952-563-8949 TTY 952-563-8740 www.ci.bloomington.mn.us web 53fff_detach_garage_wire pg 1 of 4 (08/09) This information is a guide to the most common q u e s tio ns . It i s n ot i n te nd e d , n o r s h a ll it be considered, a complete set of requirements.

Residential Detached Garage Wiring Info Sheet

Embed Size (px)

DESCRIPTION

Guide on How to properly run wire from Main Circuit Breaker Box of a Residential Home to a Detached Garage

Citation preview

Page 1: Residential Detached Garage Wiring Info Sheet

This handout answers questions most often asked byhomeowners. This information is a guide to the mostcommon questions. It is not intended, nor shall it beconsidered, a complete set of requirements. The wiringmust be done to the standards of the latest state-adoptedNational Electrical Code (NEC). Libraries and electricalsupply dealers may have other books available to furtherassist you.

An Electrical Permit is required for all electrical work,including wiring a garage. In a single-family residence,experienced owners/homesteaders may obtain the permit todo the work themselves. For other residential occupancies,such as rental properties, an electrical contractor must behired to do the work and obtain the permit.

Rules to operate by:

1. Most homeowners choose to run the electr icalunderground. The two most popular methods aredirect-burial cable or PVC (plastic) conduit. Directburial cable is designated as UF (UndergroundFeeder) or for larger sizes, USE (Underground ServiceEntrance).

Direct-burial cables may be buried in the ground at 24inches below grade. They must have mechanicalprotection, such as PVC conduit, wherever they arecloser than 24 inches below grade. The most commonpoint where this occurs is when the run is brought upabove grade to enter the house and garage.

PVC conduit must be approved as electrical conduit.Other types, such as PVC plumbing pipe, are notacceptable. Standard insulated conductors may bepulled inside the PVC. These single conductors musthave a “W” (water-resistant) in the designationstamped on the jacket of the wire. Examples of suchdesignations include: THWN, XHHW, etc. Type“Romex” or Non-Metallic Cable (NM-B) cannot be runinside underground conduit, because the outer jacketof the NM-B is not rated for wet locations. PVC conduitmust be buried at 18 inches below grade. (This ismeasured to the top of the conduit, so the trench willhave to be deeper than 18 inches.)

2. A disconnect must be installed in the garage to shut offall power to the building. This disconnect must beimmediately inside the garage at the entrance point ofthe feed from the house. If you are using a multi-circuit

panelboard in the garage and have no more than six breakers in the panel, these breakers may be usedas the disconnecting means. When using more thansix breakers, a main breaker is required in thepanelboard. If you are running a single 15- or 20-ampere circuit from the house to feed a minimumnumber of lights and outlets, you may use a separatesingle-pole switch (such as a standard light switch) asa disconnect. This switch must be the first device thatis on the circuit once it enters the garage; it may beused only as a disconnect and cannot be used tocontrol lights or other equipment. This disconnect mustbe labeled as the disconnect switch on its box cover.See Detached Garage Supplied by a Three Wire

Branch Circuit.

3. Romex or NM-B may be used inside the garage. Itmust be drilled and inserted through the studs, not runon the face of them. Also, never drill through factoryroof trusses, run the Romex or NM-B on the top edgein a location where it will not be damaged. Romex orNM-B cable is to be routed so it is not subject tophysical damage.

4. All 125-volt, single-phase, 15- and 20-amperereceptacles installed in garages must be a Tamper-Resistant (TR) type and protected by a Ground FaultCircuit Interrupter (GFCI), including any receptacles forgarage door openers or specific appliances. There aretwo forms of GFCI-protected devices. You may use atamper-resistant receptacle-type, GFCI-protecteddevice or a breaker-style GFCI protective device. Bothdevices are installed at the beginning of the circuit tobe protected and several standard tamper-resistantoutlets may be protected “downstream” by one GFCIoutlet. See the manufacturer’s instructions for details.On a GFCI, the line is the power in and the load is thepower out to other receptacles. TR receptacles aredesigned with a “shutter” over the slots so only astandard cord cap (plug) can be inserted. Add-on plugcovers are not acceptable.

Any receptacles on the exterior of the garage must betamper-resistant (TR), GFCI-protected and WeatherResistant (WR). (There will be a “WR” visible on theface of the receptacle.)

Residential Detached Garage Wiring

Information Sheet

Community Development Building and Inspection 1800 W. Old Shakopee RoadBloomington MN 55431-3027

PH 952-563-8930FAX 952-563-8949TTY 952-563-8740

www.ci.bloomington.mn.us web 53fff_detach_garage_wire pg 1 of 4 (08/09)

This information is a guide to the most common

questions. It is not intended, nor shall it be

considered, a complete set of requirements.

Page 2: Residential Detached Garage Wiring Info Sheet

5. If a single circuit with a grounding conductor (eithergreen or bare and attached to the grounding system inthe house) is run from the house to the garage, noground rod is required at the garage, see Detached

Garage Supplied by a Three Wire Branch Circuit. Forfeeders from the house to the garage, an eight-footground rod must be driven at the garage. A groundingconductor is required with the branch circuit or feeder.When a feeder or more than one circuit is supplyingthe garage, a grounding electrode is required at thegarage. If there is no existing grounding electrode,(metal underground water pipe) a ground rod isrequired and is connected to the equipment grounds inthe garage, see Detached Garage Supplied by a Four

Wire Feeder. This ground rod may be driven rightoutside the garage with a #6 copper ground wireattached to it. If the wire is subject to physical damageon the outside or inside of the garage, it must beprotected by conduit. The easiest method of protectionis typically 1/2-inch PVC. The #6 wire must be attachedto the grounding system for the electrical in the garage.

6. The minimum wiring required in a detached garagethat has electr icity would include a means todisconnect the power to the garage, switches at theservice door to control a light inside the structure, anda light outside the garage service door. Vehicular(overhead) doors of a garage are exempt from anylighting requirements. A minimum of one GFCI-protected readily-accessible receptacle somewhereinside the garage is also required.

web 53fff_detach_garage_wire pg 2 of 4 (08/09)

Garage

Disconnect

MAIN

DETACHED GARAGE SUPPLIED BY A THREE-WIRE BRANCH CIRCUIT

TO GARAGE LIGHTS

AND RECEPTACLES

Romex, NM-B cable.

DISCONNECT SWITCH

located close to where cable

or conduit comes into garage,

must be marked

“Garage Disconnect.”

NEW SINGLE

POLE BREAKER

added for garage.

EXISTING GROUNDING

ELECTRODES (Water

pipe and ground rod.)

NEUTRAL/GROUND BUS

White, green and bare wires.

Bonded to service enclosure.

UF CABLE, IMC

OR ELECTRICAL

PVC CONDUIT

to garage.

Detached garage supplied from a service panel in the house by way of a three-wire branch circuit: one hot (black),

neutral/grounded (white) and equipment ground (bare copper or green) conductor. This is an economical way to

wire a garage with UF cable buried a minimum of 24 inches deep or electrical PVC conduit buried 18 inches deep.

Page 3: Residential Detached Garage Wiring Info Sheet

web 52csubdiv pg 3 of 4 (02/09)

MAIN

DETACHED GARAGE SUPPLIED BY A FOUR-WIRE FEEDER

MINIMUM #6

CONDUCTOR

to electrode

(metal underground

piping). When no

underground

piping is present,

install a minimum

of 8-foot long

ground rod.

SUB-PANEL

IN GARAGE

with equipment

grounding

bus bonded to

sub-panel

enclosure.

ISOLATED

NEUTRAL BUS

for the neutral

conductors

(white wires.)

MAIN BREAKER

required in garage when more than

six breakers are in the panel.

NEW TWO POLE

BREAKERS

added for garage sub-panel.EXISTING GROUNDING

ELECTRODES (Water

pipe and concrete-encased

electrode or ground rod.)

NEUTRAL/GROUND BUS

White, green and bare wires.

Bonded to service enclosure.

FOUR-WIRE

UNDERGROUND

OR OVERHEAD

FEEDER.

Sub-panel in detached garage supplied from a service panel in a house by way of a

four-wire feeder: two hots (black), neutral (white) and a ground (bare copper or green).

Page 4: Residential Detached Garage Wiring Info Sheet

web 52csubdiv pg 4 of 4 (02/09)

Garage

Disconnect

DISCONNECT SWITCH

located outside or inside

nearest point of entrance

to the conductors, must

be marked “Garage

Disconnect.”

WIRE NUTS

required on all splices.

DETACHED GARAGE WIRING

DO NOT drill holes

in ceiling trusses.

RUNNING BOARDS

required when NM (Romex)

is run perpendicular

to the rafters.

All receptacles must be

TAMPER-RESISTANT and

GFCI-PROTECTED.

Drill holes

in studs and

ceiling plates.

RUNNING BOARDS

required when NM (Romex)

is run perpendicular to wall

studs and is readily accessible.

MINIMUM 6 INCHES

wire in boxes.

STRAPS ON NM (Romex)

within 8 inches of boxes and

every 4-1/2 feet thereafter.