22
REPORT TO INTERIOR PLANTSCAPE ASSOCIATION (IPA) (Revised Re-submitted June 2016) Towards Development of Indoor Plant Walls for Improved Indoor Air Quality Research team Researcher: Mr Michael Zavattaro (MSc. Scholar) Compiler & for correspondence: Prof. Margaret Burchett ([email protected] ) Program Director: Dr Fraser Torpy Plants and Urban Air Quality Group School of Life Sciences University of Technology Sydney PO Box 123, Broadway, NSW 2007, Australia

REPORT TO INTERIOR PLANTSCAPE ASSOCIATION (IPA)(diams. 2.5 μm or less: at or below 1/200 the thickness of a hair). The PM 10 fraction is known as the ‘coarse particulates’, and

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • REPORT TO

    INTERIOR PLANTSCAPE ASSOCIATION (IPA)

    (Revised – Re-submitted – June 2016)

    Towards Development of Indoor Plant Walls for

    Improved Indoor Air Quality

    Research team

    Researcher: Mr Michael Zavattaro (MSc. Scholar)

    Compiler & for correspondence: Prof. Margaret Burchett

    ([email protected])

    Program Director: Dr Fraser Torpy

    Plants and Urban Air Quality Group

    School of Life Sciences

    University of Technology Sydney

    PO Box 123, Broadway, NSW 2007, Australia

    mailto:[email protected]

  • SUMMARY

    Over the last three decades, international research (including our own) has demonstrated that

    indoor plants can reduce levels of all types of urban air pollutants tested and, of particular

    importance, carbon dioxide and air toxics (e.g. volatile organic compounds, VOCs), which

    are always in higher concentrations indoors than outside, even in the city centre. Indoor plants

    have the potential to improve indoor environmental quality as a whole, and hence the health

    and well-being of building occupants. The use of indoor plants to refresh indoor air in air-

    conditioned city buildings could also reduce the energy load on the building, and its footprint,

    contributing to the goal of urban sustainability. The UN estimates that the building sector

    accounts for about 40 % of global energy use, and that the proportion needs to be reduced.

    Aims of the project reported here are to contribute to the baseline scientific information

    needed to underpin the development of indoor plant-walls and equivalent living-green

    installations, as a means of bringing about significant reductions in air pollution levels in

    commercial buildings. The reductions would also lower costs of building air-conditioning

    ventilation systems. This is a preliminary study; there have been extremely few reports of in-

    situ investigations on this aspect of plant-wall benefits.

    Air sampling was conducted in seven Sydney city buildings, which all had indoor plant-wall

    (IPW) installations and were also equipped with building-wide air-conditioning systems. As it

    happened, the buildings all housed different types of business enterprises. In each building

    comparisons were made of air pollutant levels on the floor containing the plant-wall, which

    also had numbers of human occupants, and on a ‘reference’ floor with no plants. The plant-

    wall dimensions were found to vary greatly, ranging from 72 m2 down to 5 m

    2.

    Results In the two buildings with the largest plant-walls, the planted floors showed reductions

    in CO2 levels of from 13 to 23 percent, while two other buildings showed some minor CO2

    reductions. In the three buildings with the largest plant-walls, there was a trend towards

    reductions of extremely fine airborne particulate matter (PM10 and PM2.5), which are known

    to be serious health hazards of urban air. The results are encouraging, since they were

    obtained in the presence of continuous air-conditioning, the systems of which had unknown

    ‘refresh’ ventilation rates.

    Future R&D Our studies are continuing for the development of the horticultural technology

    needed to ensure that plant-walls and equivalent living-green interiorscapes become standard

    installations in city buildings. This will improve urban energy efficiency and the health of

    urban dwellers.

  • 1. BACKGROUND

    Over the last three decades there has been increasing evidence of the benefits of living plants

    in the work-place, including:

    Reducing indoor air pollution (e.g. Tarran et al., 2007; Burchett et al., 2008; Irga et al, 2013; Torpy et al., 2013a, 2014, 2015);

    Providing a peaceful aesthetic (e.g. Aitken & Palmer, 1989; Dijkstra et al., 2008);

    Improving attitudes and performance of staff, students, clients (e.g. Fjeld, 2002; Dravigne et al., 2008).

    The last two decades have also seen increasing development and use of several types of plant-

    walls (Loh, 2008) (also called biowalls; vertical gardens; green-walls, etc.; here called

    ‘Indoor Plant-Walls’- IPWs). Over the same time there have been advancements in more

    conventional indoor plantscape designs, which will remain more flexible in various

    interiorscape situations.

    Our own research findings (e.g. Wood et al., 2002, 2006; Orwell et al., 2006; Tarran et al.,

    2007; Burchett et al., 2008, Irga et al., 2013; Torpy et al., 2013 (a), (b); 2014; 2015), and

    those of other investigators (e.g. Yoo et al., 2006; Yang et al., 2009; Llewellyn & Dixon,

    2011) indicate that now is the time to spearhead the development of IPW installations in

    city buildings, in order to provide significant reductions in indoor air pollution. At

    present it is standard building practice to rely on the central Heating, Ventilation and Air-

    Conditioning (HVAC) systems to remove air pollutants. Although effective, this system is

    very energy intensive since, for example, outdoor air brought in for air refreshment must be

    heated or cooled to the building’s normal temperature (even if the building is already at that

    temperature). If part of the ventilation process were to be replaced with IPWs, the building

    energy load could be reduced, which would lower its carbon-footprint, and contribute to the

    goal of urban sustainability in this country (Aust. Gov., 2011).

    The aim of our research program is to advance the information needed for the continuing

    development of indoor plant-walls, to bring about significant improvements in IAQ in urban

    commercial buildings. This will lower costs of building air-conditioning, through a lessening

    of ventilation requirements. The development and utilisation of IPWs will contribute to

    achieving our national sustainability goal of the ‘Triple-bottom-line: For People-Profits-

    Planet’.

    Urbanisation and the ‘Indoor Habitat’ According to UN estimates (2001), in the year 1800 only 2 % of the world’s population lived

    in urban areas. Until then, almost everyone was perforce surrounded by living greenery –

    farms, village greens, home gardens, church or temple gardens, grasslands, forests or

    woodlands (apart from sparse desert dwellers which comprised of very little food and water).

    The UN also estimated that now, 54 % of global population lives in urban areas, with the

    proportion expected to rise to about 65-70 % by 2050. It is perhaps not surprising that Hartig

    et al., (2014), in the Ann. Rev. of Public Health, reported that: “urbanization, resource

  • exploitation, and lifestyle changes have diminished possibilities for human contact with

    nature”.

    The authors reviewed a wide range of research articles which showed relationships between

    contact with nature and the maintenance or improvement of health and wellbeing, including:

    better air quality;

    more opportunity for physical activity;

    promoting social cohesion, with parks, other open planted-areas, street trees, etc.; and

    stress reduction.

    There are numbers of advantages to urban living, but there are also adverse health and

    wellbeing issues arising from urban dwellings. There is an increasing incidence of chronic

    conditions from sedentary living - obesity, diabetes, cardiovascular disease (Manson et al.,

    2004; Aust. Gov., 2015); plus increased street and domestic violence (Winton, 2004); and

    mental illness (WHO, 2001, Srivastava, 2009). There are also negative effects from what has

    been termed a widespread “disengagement with nature” (Gladwell et al., 2013), which may

    be adversely affecting a new generation of city dwellers (Grinde & Grindal Patil, 2009;

    National Trust UK, 2012). Anecdotally, we have been told that some Sydney primary-school

    children are reluctant to go on class excursions to parks or nature-reserves, because they

    believe that: “Plants are dangerous - and there may be animals too, that can get on you”

    (Educ. Officer, Bicentenn. Park Authority; pers. comm).

    Health Hazards of Urban Air Pollution

    In Australia, as in much of the western world, 80 % of us already live in urban areas, and

    spend about 90 % of our time indoors (Environ. Aust., 2003; USEPA, 2016). Consequently

    indoor environmental quality is crucial to our health and wellbeing. It was estimated by the

    OECD (2014) that the costs of deaths from urban air pollution (UAP) in Australia (3,000 per

    annum; Begg et al., 2003) are almost $6 billion p.a. and there are similar cost levels caused

    by illness and associated loss of productivity (Olesen, 2006; Bernstein et al., 2008). Acute

    responses to air pollution include asthma, strokes, heart attacks and other sudden

    cardiovascular malfunctions (NSW Health, 2009). Chronic effects include lung and other

    cancers, more cardiovascular problems, pre-term births and low birth weights (Bobak, 2000;

    NSW State of Environ, 2015). Lung and cardiovascular disease, as well as the increasing

    incidence of autism, have been linked in particular with levels of airborne particulate matter

    (PM) (Volk et al., 2013).

    Gaseous pollutants Approximately 90 % of UAP comes from fossil fuel combustion. The

    emissions include a mixture of nitrogen and sulfur oxides, carbon dioxide and monoxide, a

    cluster of ‘air toxics’ from partial burning of fuel, including a range of volatile organic

    compounds (VOCs), and ‘secondary’ photochemical products e.g. ozone and peroxyacetyl

    nitrate (PAN). The commonest VOCs (produced from vehicle emissions), are the lightest -

    the BTEX group - Benzene, Toluene, Ethylbenzene, and Xylene.

    Suspended particulate matter (PM) – is the primary cause of city haze. The main health

    hazards are from the most minute particulates: PM10 (diameters 10 micrometres [μm] or less:

    at and down from just 1/50 the thickness of a human hair); and PM2.5 (diams. 2.5 μm or less:

  • at or below 1/200 the thickness of a hair). The PM10 fraction is known as the ‘coarse

    particulates’, and PM2.5 as the ‘fine particulates’. Both these (overlapping) size ranges can

    lodge in lungs and cause disease. PM2.5 particles also move easily from lungs into the blood

    stream, causing not only more vascular disease but lowered brain function as well ( alder n-

    arcidue as et al., 2008). PM comprises continually changing mixtures of the tiny solid and

    liquid particles derived from fossil fuel emissions; fragments thrown up from tyres and

    roadways; natural dust from soils, and ‘bio-particles’ - fungal spores and, more seasonally,

    pollens. The character of the mixtures also varies with city, local industry, and seasons.

    Indoor air pollution Air pollution levels inside buildings are always higher than those

    outdoors, even in the CBD - often 2 to 10 times higher, and sometimes up to 100 times higher

    than outdoors (US EPA, 2015a). This is because, as air enters the building it brings its

    ‘outdoor’ air pollution load, which mixes with more pollutants emanating from indoor

    sources (WHO, 2000; 2005). The indoor-sourced pollution is mainly composed of more

    VOCs, which are continually outgassing from synthetic furnishings, finishes, paints, solvents,

    and equipment; plus higher CO2 concentrations from occupants’ breathing (and any non-flued

    gas appliances). Excess CO2 causes drowsiness, and VOCs, even at imperceptibly low levels

    (less than 250 parts per billion; ppb), cause some occupants to experience ‘sick building

    syndrome’ pstein, orb ck ordstr m, 2008). SBS produces symptoms

    such as headaches, dizziness, nausea, loss of concentration, and/or sore eyes, nose or throat.

    From a 100-building study by the USEPA, it was found that for every increase in CO2

    concentration of 100 parts per million (ppm), there was a 10 to 20 % increase in mucous

    membrane and lower respiratory “building-related symptoms” [‘ R ’ or ‘SBS’] among

    occupants (Erdmann & Apte, 2004).

    Plants Improve Indoor Air Quality (IAQ)

    Since the pioneering work of Wolverton and colleagues (1989; 1993) on removal of VOCs by

    indoor plants, numerous studies have shown that plants can reduce concentrations of all urban

    air pollutants tested. These include carbon monoxide (Bidwell et al., 1972; Sanhueza et al,

    1998); nitrogen oxides (Coward et al., 1996); sulfur dioxide (Lee & Sim, 1999); ozone

    (Elkiey & Ormrod, 1981), single and mixed VOCs (Yoo et al, 2006; Wood et al, 2006;

    Orwell et al., 2006; Irga et al., 2013); formaldehyde (testing 86 species; Kim et al., 2008);

    ammonia (Yoneyama et al, 2002); PM (Lohr & Pearson-Mims, 1996); PAHs and other

    organic compounds (Barro et al., 2009). A laboratory study by Oyabu et al. (2003) using

    three plant species, found they could also reduce concentrations of three pollutants classified

    in Japan as “offensive odours” i.e. not from fossil fuel combustion, but from human

    occupants: ‘bioeffluents’ .

    All air pollutants from fossil fuel sources are toxic, and numbers of VOCs are known to be

    carcinogenic (Berkeley Laboratory, 2016). Our previous laboratory chamber studies, with

    approximately 20 plant species/varieties, have shown that VOC removal by indoor plants in

    the same- sized pots, in either potting-mix or hydroculture, achieve almost equal removal

    rates after a second or third ‘inducing’ dose (no more than a week). We also found that VOC

    removal rates remain equal day and night, and rise further if a higher dose concentration is

    applied. It is the normal bacteria in the root-zone that are the primary removal agents, the

    plant contributing mainly by secreting various sugars into the substrate so that its soil

  • microbial community will flourish (a symbiotic plant-microbe relationship). Odours from

    occupants, and from cosmetics (in the form of VOCs), can also be degraded by indoor plants

    and their root-zone microflora. Since bacteria can reproduce about every 20 minutes if

    stimulated by a whiff of an organic contaminant, the species that can best digest the airborne

    VOCs present will quickly increase their numbers to enjoy the feast thereby increase rates of

    VOC removal.

    Ventilation in Big Buildings

    The problems of IAQ in commercial buildings are more complex than at home, where one

    can usually just open a window. The primary aim of air-conditioning in city buildings is to

    keep the indoor environment at a comfortable temperature for staff and clients (22-23 oC).

    However, where whole-building HVAC mechanical ventilation systems are used, which is

    usually the case, the buildings must be sealed. This means the HVAC also has to supply the

    indoor air, which must be of acceptable quality. This involves regularly removing the

    increasingly stale, polluted indoor air, and bringing in ‘fresh’ outside air, in an effort to

    maintain healthy IAQ. Maximum CO2 levels are used as an indicator of overall indoor air

    pollution concentrations (incl. VOCs, PM, and inorganics). As in the USA, the guidelines for

    indoor maximum CO2 concentrations in Australia are 800-1,000 ppm (ASHRAE, 2001; Petty,

    2015). The HVAC is designed either to maintain CO2 levels significantly below the

    building’s set maximum, or to trigger increased ventilation rates whenever the maximum is

    reached. Both the thermal and air quality requirements of city buildings are costly of fuel

    energy and budgets.

    2. SAMPLING METHODS

    Access to the seven buildings studied was made available by Mr Jock Gammon, Founder &

    Managing Director of Junglefy Pty Ltd (Aust.), who designed, installed and maintains the

    plant-walls sampled. The IPWs were all of different dimensions (Table 1), and had a

    somewhat varied species composition (Table 2). There was no assisted ventilation to either

    the plants or substrate in any of the plant-walls sampled. Permission for access was also

    obtained from individual building managers. The buildings all had HVAC systems, and each

    building was involved in a different type of business activity (Table 1).

    Sampling methods Air sampling was conducted over a two-week period in July 2015, and

    always between 10.00 am to 3.00 pm, to minimise any complications that might arise from

    differences in seasonal conditions. A set of portable monitors was used for all measurements.

    In each building sampling was carried on two floors, as follows.

    the floor with the plant-wall installation, which also had numbers of occupants, including on the sampling days;

    a ‘reference’ floor –a mainly unoccupied space on another level of the building, e.g. in a boardroom or corridor (no plants).

  • Pollutants sampled The pollutants selected are found world-wide in urban air, and are under

    surveillance by the NSW EPA. They are all toxic (hazardous), producing adverse health

    effects at very low concentrations. Individual air-sampling period for each pollutant was 2

    minutes. Samplings included:

    Gases (ppm): Carbon dioxide (CO2), Carbon monoxide (CO), Nitrous oxide (NO), Nitrogen

    dioxide (NO2), Sulfur dioxide (SO2), and Total VOCs.

    PM10 & PM2.5 (as micrograms per cubic metre of air; μg /m3).

    Physical measurements Temperature (oC); relative humidity (RH %); and light intensity

    using the Internat. Units System (IU) - micromoles of light quanta (or micro-Einsteins), per

    square metre, per second μmol q/m2/s).

    Sampling pattern In each building sets of three replicate readings were made for each of the

    11 contaminants, at each of 3 heights from the floor: 7.5, 130, & 180 cm, respectively*, as

    follows:

    on the plant-wall floor - 60 cm out from the foliage surface, and at the centre of the room-space.

    on the reference floor - at the centre of the room-space.

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - **Following the USA/ASHRAE Standard, ANSI/ASHRAE Standard 62.1-2013. The 3 sampling heights ‘from the floor’, are taken to represent air quality measured at: 7.5 cm - ‘floor level’ (but clearing carpets, etc);

    130 cm - ‘breathing zone’ at head height when seated at desk; and 180 cm - breathing zone at standing height.

    3. FINDINGS Some low pollution levels The concentrations of carbon monoxide, nitrogen and sulfur

    oxides, and total VOCs, were found to be from very low almost to zero, in all the buildings.

    They were therefore of negligible health risk, so are not tabulated here. This was a pleasing

    result, since gaseous pollutants are not removed by HVAC filters or other A/C systems. The

    results indicate that in general air pollution levels in Sydney as a whole, were low over the

    sampling period.

    Table 1 shows the major results obtained from the investigation:

    Column 1. lists the commercial use of each building. It seems that a growing range of

    business types are choosing to install IPWs as part of their interior design.

  • Col. 2. shows the plant-wall dimensions. Areas varied from 72 m2 down to 5 m

    2 – a 14-fold

    difference. The range presumably reflects differences in available space, outlook regarding

    aesthetic value, aims for enhancing staff and client satisfaction, costs, or a combination of

    factors. The modules were 50 x 50 x 13 cm, each with 16 cavities for single plants (see Plates

    1-7), and used a hydroculture, coco-fibre substrate. Each IPW was irrigated via channels

    along the tops of the modules, with multiple holes at the bottom for easy drainage, collection,

    and recycling as appropriate. Col. 3. lists the room-spaces sampled on IPW and reference floors.

    Col. 4. presents the average light intensities for IPW and reference floors in each building,

    both near (60 cm out from) the plant-wall, and in the centre of the room-space. The reference

    spaces could be expected to have low light intensities, depending on use, or non-use, of those

    areas. All the plant-walls were fitted with some type of targeted lighting, installed

    individually by building management. However, over-all the light intensities of the room-

    spaces were variable and rather low.

    Outdoor sunlight at noon has a light intensity of approximately 2,000 μmol q/m2/s (about

    100,000 Lux). Our previous studies (Torpy et al, 2014) have found that average UTS office

    lighting levels range from about to 1 μmol q/m2/s (10 μmol q/m

    2/s equals ~380 Lux). The

    State Government of Victoria (2009) recommends minimum light levels for “routine office

    work” of from 3 –400 Lux (8.5-10.5 μmol q/m2/s). In the tested buildings values of from

    4.5 to 9.7 μmol q/m2/s were recorded within 60 cm from the plant-walls, however levels from

    2.3 to 6.5 μmol q/m2/s, which were recorded in the centre of occupied spaces, are

    unsatisfactorily low for office occupants. The results also indicate that although the plant-wall

    lighting provides highlights over the planted surfaces (Plates 1-7), it evidently has little effect

    on room-space illumination as a whole.

    Cols. 5, 6 list concentrations of PM10 and PM2.5 respectively. All the values for PM10 were at

    or below the Australian tandard maximum of 5 μg/m3. However, as can be seen from

    Table 1, the pairs of concentrations for PM10 and PM2.5 were very similar to each other, which

    indicates that a majority of the particles captured in the PM10 sampling were in fact extremely

    fine, in the PM2.5 range (Harrison et al., 1997). HVAC systems are equipped with filters that

    remove some of the dust that would otherwise come indoors, but some particulates are not

    captured by the filters, as exemplified by these results. The PM results also point to possible

    health risks in Sydney at these concentrations. The Australian maximum for 24-hour-

    averaged outdoor concentration for PM2.5 is 5 μg/m3 (Aust. Gov., 1998; 2013 - under review,

    towards stricter limits).

    Cols. 7,8 show CO2 levels in the sampled buildings, and percentage differences between

    planted and reference floors. The current ambient global CO2 concentration (May 2016;

    Scripps Inst. Oceanography, Mauna Loa Observatory) is fluctuating between 405-408 ppm.

    The CO2 values on reference floors in the 7 buildings ranged from 480 ppm (not too far

    above world ambient) to 835 ppm (nearly twice ambient, and above the trigger values for

    increased ventilation in some Sydney buildings, e.g. UTS). These differences reflect a

    mixture of different HVAC settings and cycles, and/or different occupant numbers and

    activities at particular times. No HVAC system can provide identical air conditions

    throughout a building at any given moment, although floors with occupants might normally

  • have higher CO2 levels than unoccupied spaces. However, the results in Col. 7 show some

    variations from the expected norm. In the first building, the Library, on the floor which held

    the largest plant-wall installation, CO2 concentrations both near the plant-wall and in the

    centre of the room-space were 13 % lower than on the reference floor. In the second building,

    the Insurance office, with a plant-wall area only 35 % that of the Library, CO2 levels near the

    plant-wall remained equal to those on the reference floor, and were 23 % lower in the centre

    of the room-space than on the unoccupied floor.

    In this project it was not possible to disentangle the operations of the HVAC systems in the

    various buildings and the potential contribution of the plant-walls in reducing CO2 by

    photosynthetic uptake or dissolution in water associated with the substrate. However, the CO2

    reductions recorded on planted floors in these first two buildings suggest that these plant-

    plant installations indeed have the capacity to make a contribution to refreshing indoor air. In

    the next three buildings, which had diminishing plant-wall areas, CO2 values were higher

    near the plant-walls than on reference floors, though in two of the three buildings, values

    were lower in the centre of planted space than near the plant-walls. The two buildings with

    the least planted areas, the Childcare Centre and UTS Conference Centre, maintained near-

    equal levels of CO2 on planted and reference floors. A combination of light intensity and

    species-specific light threshold levels for CO2 uptake, are major determinants of plant CO2

    responses in indoor air.

    Table 2 lists plant species found in each of the seven buildings. A total of 15 species/varieties

    were used, with highest diversity, 11 species, being found in the Insurance building. The three

    commonest species were Philodendron spp. (3 spp; 6 buildings); C. comosum (5 buildings);

    and E. aureum (5 buildings). Two ferns, Davallia sp. and Phlebodium aureum were used in 2

    buildings.

  • Table 1: Sites and dimensions of plant-walls in the 7 buildings; light intensities; concentrations of

    PM10 and PM2.5; CO2; percentage differences in CO2 concentrations between plant-walled floors

    (60 cm from plants & in centre of space) and reference floors (centre space only).

    (Where PM and CO2 concentrations on IPW floors are equal to, or lower than, those on reference

    floors, values are shown in blue).

    1. Sites 2.Plant-

    wall areas

    (m2)

    3. Spaces:

    Ref. flr;

    IPW flr;

    Near-wall

    / Centre.

    4. Light

    Intensity

    μmol

    q/m2/s)

    5. PM10

    Conc.

    (μg/m3)

    6. PM2.5

    Conc.

    (μg/m3)

    7. CO2

    Conc

    (ppm)

    8. % Diffs.

    CO2 Ref. fl./

    IPW fl.

    i. Public Library 72 Ref. spce.

    IPW spce:

    60 cm

    Centre

    2.7

    4.5

    3.7

    30

    20

    20

    30

    20

    20

    570

    500

    500

    -13

    -13

    ii. Insurance 24.5 Ref. spce.

    IPW spce:

    60 cm

    Centre

    1.1

    9.0

    3.0

    40

    30

    30

    30

    30

    30

    835

    845

    570

    =

    -23

    iii. Couriers-

    Packaging

    21 Ref. spce.

    IPW spce:

    60 cm

    Centre

    10.5

    6.0

    6.5

    20

    20

    20

    20

    20

    20

    610

    750

    570

    +23

    -7

    iv. Café

    Hunter St

    12.3 Ref. spce.

    IPW spce:

    60 cm

    Centre

    6.5

    7.3

    6.0

    50

    50

    50

    50

    40

    -

    520

    710

    585

    +20

    v. UTS

    Admin Centre

    12 Ref. spce.

    IPW spce:

    60 cm

    Centre

    1.8

    9.7

    2.3

    30

    50

    40

    30

    40

    30

    480

    660

    650

    +36

    +35

    vi. Childcare

    Centre

    6 Ref. spce.

    IPW spce:

    60 cm

    Centre

    3.5

    7.2

    3.0

    30

    40

    40

    20

    40

    40

    600

    -

    655

    +9

    vii. UTS

    Conf. Centre

    5 Ref. spce.

    IPW spce:

    60 cm

    Centre

    9.5

    6.5

    5.7

    40

    -

    20

    40

    20

    20

    545

    550

    585

    =

    +8

  • Table 2. Plants used among buildings in the IPW modules.

    Building Species/variety

    Public library Chlorophytum comosum

    Epipremnum aureum

    Philodendron bipinnatifidum

    Philodendron scandens

    Philodendron xanadu

    Neomarica sp.

    Peperomia sp.

    Spathiphyllum cochlearispathum

    Insurance Chlorophytum comosum.

    Philodendron bipinnatifidum

    Philodendron xanadu

    Anthurium sp.

    Aglaonema sp.

    Davallia sp.

    Iresine sp.

    Peperomia sp.

    Phlebodium aureum

    Spathiphyllum cochlearispathum

    Syngonium podophyllum

    Couriers/Packaging Chlorophytum comosum (varigated)

    Epipremnum aureum.

    Philodendron bipinnatifidum

    Philodendron xanadu

    Peperomia sp.

    Davallia sp

    Phlebodium aureum

    Spathiphyllum cochlearispathum

    Syngonium podophyllum

    Café, Hunter Street Chlorophytum comosum

    Chlorophytum comosum (variegated)

    Epipremnum aureum

    Ctenanthe sp.

    Peperomia sp.

    Phlebodium aureum

    UTS 10, Admin. Epipremnum aureum

    Ctenanthe sp.

    Neomarica sp.

    Childcare Centre Chlorophytum comosum (variegated)

    Philodendron xanadu

    Ctenanthe sp.

    Peperomia sp.

    UTS Conf. Centre Epipremnum aureum

    Philodendron scandens

    Philodendron xanadu

    Neomarica sp.

  • 4. SIGNIFICANCE OF FINDINGS

    PM pollution The results in Col. 5, 6, show that airborne PM contamination in these Sydney

    buildings was largely composed of very fine particulates – the PM2.5 fraction. Although only

    from ‘snapshot’ sampling, the values suggest that only three of the buildings, the Library,

    Couriers, and the UTS Conference Centre, would be under the Australian PM2.5 maximum. In

    these buildings planted floors had lower PM2.5 levels than reference floors, which point to

    plant presence possibly being involved. The other four buildings were significantly above the

    Australian PM2.5 limit, and by the USA standards would be classed as ‘Unhealthy for

    Sensitive Groups’. The PM10 and PM2.5 risk categories have been developed internationally

    over the last two decades, as it has become recognised that suspended fine and ultrafine

    particles are considerably more hazardous to health than previously understood (NSW Health,

    2015; NSW EPA, 2015).

    Indoor CO2 levels – relationships with photosynthesis in indoor plants. In this era of

    concern over rising CO2 levels and climate change, the world now appreciates that all green

    plants can absorb carbon dioxide. With adequate lighting for the particular species, any

    green shoot will open its leaf stomates (pores), which will simultaneously start:

    a flow of water (and minerals) up from its roots (‘translocation’) the dragging force being evaporation of water from the leaves; and

    uptake of CO2, as the starting-material of photosynthesis.

    Non-green parts - brown stems, coloured flowers or fruit, roots and root-zone

    microorganisms (bacteria and fungi) do not photosynthesise. They continually respire

    (24/7), emitting CO2 (and their cellular-respiration chemistry is almost identical with our

    own). Hence with respect to net CO2 uptake and sugar production, there are opposed

    processes at play in the plant, as follows:

    Light energy

    PHOTOSYNTHESIS: 6CO2 + 6H2O ------------> [C6H12O6] + 6O2-----

    Chlorophylls [sugar] (Oxygen– by-product) -- (+enzymes)

    Day & Night

    RESPIRATION: [C6H12O6] +6O2 ---------------> 6CO2 + 6H2O + [36 ATP]

    [sugar] (+other enzymes) [‘ nergy’ molecules]

    A successful plant is one which always produces more photosynthetic product (glucose

    sugar) during lighted hours, than it uses to power continuous whole-plant respiration. The

    ‘Light Compensation Point’ (LCP) of a plant is the light intensity at which the green shoot’s

    rate of CO2 uptake exactly equals the whole-plant’s respiratory CO2 output. The light level

    must be routinely higher than the LCP for the plant to survive. Our studies have shown that a

    number of indoor species need light intensities of ~15 to 3 μmol q/m2/s to show any

  • measurable net CO2 uptake (Torpy et al., 2014). Light intensities near the surface of the plant-

    walls of from 4.5 to 9.7 μmol q/m2/s (avr. about 7.5; Tab. 1, Col. 4) suggest that some species

    might be at or below their LCPs. Every species has its own LCP, its own optimum light

    intensity, and its intrinsic photosynthetic processing rate. The photosynthetic capacity of a

    species depends on a range of other factors as well, including leaf area; temperatures; water

    balance; fertilisation; and rates of sugar transport from leaves to other parts of the plant.

    Is variegated foliage useful in CO2 reduction? The IPWs surveyed included variegated C.

    comosum in three buildings (Table 2), and some other species showed some variegation also.

    For optimising CO2 removal, it must be remembered that white-striped or patchy leaves have

    less photosynthetic ability than green leaves. The white areas, caused by mutations, are

    ‘albino’, lacking chlorophyll and associated pigments (carotenes and xanthophylls). The

    Botanic Gardens of the University of California LA, 15 states that: “Variegated leaves

    occur rarely in nature but are extremely common among indoor and outdoor ornamentals,

    where they have been saved as horticultural oddities”. In more kindly vein, Ombrello 15

    comments: “We as a species, however, protect and perpetuate these [variegated] oddities of

    nature. Our interest in the unusual assures their survival under our care”. To advance the

    ‘plant-wall for indoor air-cleansing’ program, more detailed information is needed on

    the photosynthetic propensities of popular indoor species (both green and variegated).

    Indoor plants and HVACs. In comparing planted and reference floors in the seven buildings

    (Table 1), clear CO2 reductions were found in the first two buildings, of from 13 to 23 %.

    However, there was considerable CO2 variability generally among the buildings, as follows:

    - Among reference floors alone;

    - On planted floors alone, between those near the IPW, and those in the centre of the space;

    - For either of the two sampling points, i.e near-IPW and centre.

    The differences provide some idea of possible plant responses to the indoor air conditions,

    and also something of the flexibility of HVACs and the different settings under which they

    are operating in different buildings.

    5. FUTURE RESEARCH

    Towards urban sustainability

    The horticultural development of indoor plants for improved Indoor Environmental Quality

    (IEQ) is less than three decades old, whereas for roses, carnations, pomegranates, etc., there

    have been thousands of years of selection and cultivation. However, there is now evidence

    that indoor plants are already, and will increasingly be, needed to cleanse indoor air and help

    ensure future urban sustainability (Hartig et al., 2003; Sahely et al., 2005; Aust. Gov, 2011;

    Specht et al, 2014; Dunham et al., 2014). It has also been estimated that improved

    productivity gains from simply having plants in the nearby space, more than repay the cost of

  • indoor plant presence, in terms of occupant wellbeing and performance (Lohr et al., 1996;

    Rodgers et al., 2012). Nieuwenhuis et al. (2014) concluded, from a 3-part investigation of

    offices with and without plants, that: “The results demonstrate how office landscaping

    strategies that involve transforming a lean office into a green one, contribute not only to

    employee welfare, but also to organizational output. Lean, it appears, is meaner than

    green, not only because it is less pleasant but also because it is less productive.”

    Species strengths and weaknesses

    (i) CO2 uptake The next step is to profile the CLPs and photosynthetic capacity of the most

    used indoor species/varieties, so that they can be reliably utilised to bring about significant

    reduction of CO2. For each species, laboratory trials would be made of:

    - Leaf- and whole-plant CO2 removal responses to a range of light intensities;

    - Leaf areas and biomasses, and the pot or module sizes involved;

    - CO2 uptake with varying numbers of plants in an experimental room-space.

    (ii) Occupant-related VOCs (ORVOCs) This project with would investigate to what extent

    plants of various species can reduce or remove levels of household spray cleaners, room

    deodorants perfumes, after-shaves, etc. While generally considered safe, recent evidence has

    shown that some of the chemicals commonly used as fragrances can be converted to toxic

    VOCs in the air (eg. Limonene).

    (iii) PM reduction This study would estimate the proficiency of species to reduce levels of

    PM10 and PM2.5. Outdoor plant leaves accumulate particulates and so contribute to cleaning

    city air (Beckett et al., 1998; Irga et al 2015). There has also been one report of indoor plants

    reducing particulate concentrations by up to 20 percent in some indoor sampling zones (Lohr

    & Pearson-Mims, 1996). It is likely that not only leaf area but also leaf surface

    characteristics, and possible growth medium factors, would influence PM accumulation

    abilities.

    Performance in the ‘Real –World’

    (iv) CO2 uptake This would involve in situ studies of CO2 concentrations on floors with and

    without plant-walls, in selected buildings with and without HVAC systems. Investigations

    would involve:

    Obtaining details of the HVACs/alternative air-conditioning systems, and their operations in each building;

    Measuring CO2 levels at sampling points similar to those used in the present study;

    Measuring CO2 uptake of IPWs in the buildings, at various light intensities, using a portable, adjustable, lighting stand.

    (v) PM10 & PM2.5 reductions Sampling of particulates would be conducted in buildings at the

    same times as the CO2 uptake trials are taking place.

    (vi) Are indoor-plants a possible source of fungal spores?

    High concentrations of airborne fungal spores, such as those found in damp buildings, are a

    health hazard which can lead to symptoms of sick-building syndrome (Takeda et al., 2009).

    Pathogenic fungi such as Aspergillus fumigatus can cause serious allergic reactions, and in

    severely immunocompromised individuals fungal infections can lead to death (Maschmeyer

  • et al., 2007). Several authors (Staib et al. 1978, Summerbell et al. 1989, Engelhart et al. 2009)

    have stated that indoor plants are therefore a serious health risk that should never be used

    inside buildings. It is clearly essential that immunocompromised patients (e.g. after organ

    transplants, or suffering from HIV) must be protected from exposure to any ‘raw’ natural

    biological material, such as salad vegetables, fruit, cut-flowers, or potted-plants. However, for

    the vast majority of building occupants, indoor plants have been shown not only to reduce air

    pollution, but also to lower noise levels (Costa & James, 1999), reduce sick-leave, improve

    job-satisfaction and performance, increase pain tolerance (Park et al., 2002), and lift spirits

    (Kaplan, 1995; Bringslimark et al., 2009).

    We have conducted what appears to be the first systematic study of the possible effects of

    indoor plants on indoor airborne fungal spore counts (Torpy et al., 2013b). Over 50 single-

    staff offices, in two UTS buildings, were supplied with 0, 1, or 3 potted plants of Dracaena

    deremensis or Spathiphyllum wallisii ‘Petite’. No significant differences were found with the

    presence or different amounts of plant material, in terms of fungal spore numbers or their

    species composition. In addition, all the indoor spore concentrations were some three to ten

    times lower than in parallel ‘reference’ samples taken outdoors in adjacent streets. New

    research in this area would include:

    a laboratory study of possible emission rates of fungal spores from ‘IPW’ species plus-

    an in situ study into possible airborne fungal loads in buildings with plant-walls, to assess whether there might be some limit to the advisable area of IPW in any given

    volume of room-space.

    Goal of research directions

    The central aim of our research is to harness the use plant photosynthesis to help reduce

    indoor CO2 levels in HVAC and similarly air-conditioned city buildings. Other benefits

    would also accrue. If the energy load of a building’s air-con system could be lowered by

    perhaps 10 %, the C-footprint of the building would be substantially reduced, and ventilation

    costs reduced by a similar percentage. The U P 11 states that: “The Buildings sector of

    today has an oversized ecological footprint. The buildings sector is the single largest

    contributor to global greenhouse gas emissions (GHG), with approximately one third of

    global energy end use taking place within buildings..... There are significant opportunities to

    improve energy-efficiency in buildings”.

    Indoor plants can play a significant role in improving building efficiency, while making

    the ‘indoor habitat’ a much more pleasant place in to live and work. Research funding

    would be required for the proposed studies, and we are currently seeking funding sources.

    ACKNOWLEDGEMENTS

    We thank Interior Plantscape Association (IPA) and the previous New Zealand Association

    (PAWA) for funding the Indoor-Plant-Walls project. Special thanks to Ms Nerida Hills,

    President, and Ms Elaine Tunn, IPA Executive Officer, for their assistance and patience as

    the work has very slowly been completed. We thank Mr Jock Gammon, Junglefy Pty Ltd., for

  • advice and providing access to the plant-wall installations studied. The co-operation of

    Junglefy staff member Mr Andrew Wands, and the building managers, in assisting with

    building access and sampling arrangements, are also much appreciated. This project, although

    short-term and limited in scope, has produced valuable information, which has helped propel

    our Plants and Urban Air Quality Group, UTS, into new phases of indoor plant research.

    References Aitken JR, Palmer RD, 1989, The use of plants to promote warmth and caring in a business environment, Procs.

    11th Ann, Meeting of Amer. Culture Assocn., St Luis, MO.

    Arden-Pope III C, Burnett RT, Thun MJ, Calle EE, Krewski D, Ito K, Thurston GD, 2002, Lung cancer,

    cardiopulmonary mortality, and long-term exposure to fine particulate air pollution, JAMA 287, 1132-1141.

    ASHRAE, 2001, ANSI/ASHRAE Standard 62-2001, Ventilation for Acceptable Indoor Air Quality. ASHRAE

    Inc., Atlanta, GA, USA.

    Aust. Gov., 1998, Dept Environ, NEPM, Air Quality Standards (now under amendment for PM10/ 2.5),

    accessed 28/08/2015.

    Aust. Gov., 2011, Dept Sustain., Environ., Water, Popn & Communities, Sustainable Australia – Sustainable

    Communities, http://www.environment.gov.au/ resource/sustainable-australia-sustainable- communities-

    sustainable-population-strategy-australia, accessed 04/09/2015

    Aust. Gov., 2015, Overweight and Obesity, Aust. Institute of Health and Welfare, http://www.

    aihw.gov.au/overweight- and-obesity/ accessed 12/08/2015.

    Barro R, Regueiro J, Llompart M, Garcia-Jares C, 2009, Analysis of industrial contaminants in indoor air: Part

    1. Volatile organic compounds, carbonyl compounds, polycyclic aromatic hydrocarbons and polychlorinated

    biphenyls, J.Chromatography A, 1216, 3, 540-566. (Tools for REACH Programme - analytical methods for

    the evaluation of industrial contaminants)

    Beckett KP, Freer-Smith PH, Taylor G,1998, Urban woodlands: their role in reducing the effects of particulate

    pollution, Environmental Pollution, 99, 3, 1998, 347–360

    Begg S, et al., The burden of disease and injury in Australia 2003, in AIHW cat. no. PHE 82.2007, Aust. Inst.

    Health and Welfare: Canberra.

    Berkeley Laboratory, 2016, VOCs and Cancer, Indoor Air Quality: Scientific Findings Resource Bank

    (Sponsoring Office US EPA), https://iaqscience.lbl.gov/voc-cancer, accessd 20/04/16.

    Bernstein JA, Alexis N, Bacchus H, Bernstein IL, Fritz P, Horner E, et al., 2008, The health effects of

    nonindustrial indoor air pollution. J Allergy Clin Immunol 121(3), 585–591

    Bidwell RGS, Fraser DE, 1972, Carbon monoxide uptake and metabolism by leaves, Canad. J Bot., 50(7): 1435-

    1439. Bobak M, 2000, Outdoor air pollution, low birth weight and prematurity, Environ Health Perspectives,

    108 (2), 167- 176.

    Bringslimark T, Hartig T, Patil GC, 2009, The psychological benefits of indoor plants: a critical review of the

    experimental literature. J Environ Psychol 29:422–433

    Burchett MD, Torpy F, Tarran J, 2008, Interior plants for sustainable facility ecology and workplace

    productivity, Procs Ideaction’08 - Enabling Sustainable Communities; 7-9 May, Qld.

    alder n- arcidue as , olt A , enr que -Rold n , Torres-Jard n R,5 Nuse B, Herritt L, et al., 2008,

    Long-term air pollution exposure is associated with neuroinflammation, altered innate immune response,

    disruption of blood-brain barrier, ultrafine particulate deposition, & accumulation of Amyloid β-42 and α-

    Synuclein in children and young adults, Toxicol Path., 36:289-310.

    Chang C, Chen P. Human response to window views and indoor plants in the workplace. HortScience 2005; 40:

    1354-1359.

    Costa PR and James RW, 1999, Air conditioning and noise control using vegetation, Proc. 8th Internat Conf on

    Indoor Air Quality & Climate, Edinburgh Scotland, Vol. 3, 234-239

    Coward M, Ross D, Coward S, Cayless S, Raw G, 1996, Pilot study to assess the impact of green plants on NO2

    levels in homes; Building Res. Establishment Note N154/96. Watford, UK

    https://iaqscience.lbl.gov/voc-cancer

  • Darlington A, Dat JF, Dixon MA, 2001,The biofiltration of indoor air: air flux and temperature influences the

    removalof toluene, ethylbenzene, and xylene. Environ Sci Technol 35:240–246

    Dijkstra K, Pieterse ME and Pruyn A, 2008, Stress-reducing effects of indoor plants in the built healthcare

    environment: The mediating role of perceived attractiveness, Preventive Medicine, 47:3, 279-283.

    Dravigne A, Waliczek TM, Lineberger RD, Zajicek JM, 2008, The effect of live plants and window views of

    green spaces on employee perceptions of job satisfaction. HortScience 43:183–187

    Dunham B, Hutzel W, Hahus I. Biowall: a Sustainable Approach to Indoor Air Quality. ASHRAE Transactions

    120, 2014; XI – X8.

    Engelhart, S., Rietschel, E., Exner, M., & Lange, L. (2009). Childhood hypersensitivity pneumonitis associated

    with fungal contamination of indoor hydroponics. Internat. J Hygiene, Environ Health, 212(1), 18–20.

    Elkiey T, Ormrod DP,1981, Absorption of ozone, sulphur dioxide, and nitrogen dioxide by Petunia plants.

    Environ Exp Bot 21:63–70

    Environment Australia, 2003, BTEX personal exposure monitoring in four Australian Cities. Technical paper

    No. 6 (Aust. E ed.), Canberra, ACT, Australia

    Epstein Y, 2008, Sick building syndrome [review], Harefuah, 147, 7:607-608, 662, reprinted PubMed, U.S. Nat.

    Library of Med, Nat. Institutes of Health, accessed 03/01/2010.

    Erdmann CA, Apte MG, 2004, Mucous membrane and lower respiratory building related symptoms in relation

    to indoor carbon dioxide concentrations in the 100-building BASE dataset. Indoor Air 14:127–134

    Fjeld T, 2002, The effects of plants and artificial daylight on the well-being and health of office workers, school

    children and health-care personnel, Proc. Internat. Plants for People Symposium, Floriade, Amsterdam, NL.

    Gladwell VF, Brown DK, Wood C, Sandercock GR, Barton JL, 2013, The great outdoors: how a green exercise

    environment can benefit all, Extreme Physiol. & Med., 2, 3, doi: 10.1186/2046-7648-2-3

    Grinde B, Grindal Patil G, 2009, Biophilia: Does visual contact with nature impact on health and well-being?

    Int. J. Environ. Res. Public Health, 6(9), 2332-2343

    Harrison RM, Deacon AR, Jones MR, Appleby RS, 1997, Sources and processes affecting concentrations of

    PM10 and PM2.5 particulate matter in Birmingham (U.K.), Atmos Environ, 31, 24, 4103–4117.

    Hartig T, Evans GW, Jamner LD, Davis DS, Garling T, 2003, Tracking restoration in natural and urban field

    settings. J Environ Psychol 23(2):109–123

    Hartig T, Mitchell R, de Vries S, Frumkin H, 2014, Nature and health, Ann Rev Pub Health, 35: 207-228

    Irga PJ, Torpy FR, Burchett MD, 2013, Can hydroculture be used to enhance the performance of indoor plants

    for the removal of air pollutants? Atmos. Environ., 77, 267-271

    Kaplan S, 1995, The restorative benefits of nature: towards an integrative framework, J. Environ Psychol, 15,

    169-182.

    Lee J-H, Sim W-K, 1999, Biological absorption of SO2 by Korean native indoor plants. In: Burchett MD, Tarran

    J, Wood R (eds) Towards a new millennium in people-plant relationships—Contributions from the Internat

    People- Plant Symp.Syd., July. UTS Print. Serv., Syd., Aust., pp 101–108

    Llewellyn D, Dixon M, 2011, Can plants really improve indoor air quality? In: Murray MY (ed) Comprehens.

    Biotechnol, 2nd ed. Acad Press, Burlington MA USA, pp 331–338

    Lohr VI, Pearson-Mims CH, 1996, Particulate matter accumulation on horizontal surfaces in interiors: influence

    of foliage plants. Atmos Environ 30(14):2565–2568

    Lohr VL, Pearson-Mims CH, Goodwin GK, 1996, Interior plants may improve worker productivity and reduce

    stress in a windowless environment. J Environ Hort 14:97–100

    Liu Y-J, Mu Y-J, Zhu Y-G, Ding H, Arens NC, 2007, Which ornamental plants species effectively remove

    benzene from indoor air? Atmos Environ 41:650–654

    Loh S. Living walls: A way to green the built environment. Environment Design Guide, 1(TEC 26), Australian

    Institute of Architects, 2008, pp. 1-10

    Manson JE, Skerrett PJ, Greenland P, Theodore B. VanItallie TB, 2004, The escalating pandemics of obesity

    and sedentary lifestyle: A call to action for clinicians, Archives Intern Med., 164 (3), 249-258

    Maschmeyer, G., Haas, A., & Cornely, O. A. (2007). Invasive aspergillosis: epidemiology, diagnosis and

    management in mmunocompromised patients. Drugs, 67(11), 1567–1601.

    Nat. Health Service UK, 2015, SBS Symptoms,( http://www.nhs.uk/Conditions/Sick-building-

    syndrome/Pages/Introduction.aspx, accessed 04/08/ 2015).

    Nat. Trust UK, 2012, Reconnecting Children with Nature: Findings of the Natural Childhood Enquiry, (39 pp)

    (accessed 22/08/2015)

    Nieuwenhuis M, Postmes T, Knight C, Haslam SA, 2014, The relative benefits of green versus lean office space:

    Three field experiments, J Experim.Psychol.: Applied, 20, 3, 199–214

  • orb ck , ordstr m K, 2008, Sick building syndrome in relation to air exchange rate, CO2, room

    temperature and relative air humidity in university computer classrooms: an experimental study. Int Arch

    Occup Environ Health 82:21–30

    NSW Health, 2009, Air Pollution Health Risks, http://www.health.nsw.gov.au/

    PublicHealth/environment/air/air_pollution.asp , accessed 15/10/2009.

    NSW Health, 2015, Particulate matter (PM10 and PM2.5), http://www.health.nsw.gov.au

    /environment/air/Pages/particulate-matter.aspx, accessed 09/08/2015

    NSW EPA, 2015, Air - NSW Overview, http://www.epa.nsw.gov.au/air/, accessed 08/08/2015.

    NSW State of Environment, 2015, Doc. 8 - Air Quality, NSW EPA.

    OECD, 2014, The Cost of Air Pollution, www.oecd-ilibrary.org/.../the-cost-of-air-pollution, accessed

    20/06/2015.

    Olesen B, 2006, Productivity and Indoor Air Quality, Internat Centre Indoor Environ. & Energy; Tech. Univ.,

    Denmark.

    Orwell RL, Wood RA, Tarran J, Torpy FR, Burchett M, 2004, Removal of benzene by the indoor plant/

    substrate microcosm and implications for air quality. Water Air Soil Pollut 157:193–20

    Orwell RL, Wood RA, Burchett MD, Tarran J, Torpy F, 2006, The potted-plant microcosm substantially reduces

    indoor air VOC pollution: II. Laboratory study. Water Soil Air Pollut 177:59–80

    Oyabu T, Sawada A, Onodera T,. Takenaka K, Wolverton B, 2003, Characteristics of potted plants for removing

    offensive odors. Sensory Actuators - B Chem. 89:131–136.

    Park S-H, Mattson RH, Kim E, 2002, Pain tolerance effects of ornamental plants in a simulated hospital patient

    room, Acta Hort., 639, 50-52.

    Petty S, 2015, Summary of Ashrae’s Position On Carbon Dioxide (CO2) Levels In Spaces,

    www.eesinc.cc/ accessed 25/06/2015.

    Rodgers K, Hutzel W, Dana M, Handy R, 2012, Can plants save money: A look at the Biowall. In: Procs

    Internat. High Perform. Buildings Conf, West Lafayette, Indiana

    Sahely HR, Kennedy CA, Adams, Barry J, 2005, Developing sustainability criteria for urban infrastructure

    systems, Canadian J Civil Eng., 32, 1, 72.

    Sanhueza E, Dong Y, Scharffe D, Lobert JM, Crutzen PJ, 1998, Carbon monoxide uptake by temperate forest

    soils: the effects of leaves and humus layers, Tellus, 50B, 51–58

    Specht K, Siebert R, Hartmann I, Freisinger UB, Sawicka M, Werner A, et al., 2014, Urban agriculture of the

    future: an overview of sustainability aspects of food production in and on buildings, Agric & Human Values,

    31:33–51

    Srivastava K, 2009, Urbanization and mental health, Indust. Psychiatry J, 18 (2): 75–76.

    Staib, F., Tompak, B., Thiel, D., & Blisse, A. (1978). Aspergillus fumigatus and Aspergillus niger in two potted

    ornamental plants, cactus (Epiphyllum truncatum) and clivia (Clivia miniata). Biological and

    epidemiological aspects. Mycopath., 66(1), 27–30.

    Summerbell, R. C., Krajden, S., & Kane, J. 1989. Potted plants in hospitals as reservoirs of pathogenic fungi.

    Mycopath., 106, 13–22.

    Takeda M, Saijo Y, Yuasa M, Kanazawa A, Araki A, Kishi R, 2009, Relationship between sick building

    syndrome and indoor environmental factors in newly built Japanese dwellings, Internat. Archives Occup.

    Environ Health, 82, 5, 583-593.

    Tarran J, Torpy F, Burchett MD, 2007, Use of living pot-plants to cleanse indoor air. Research Review. In: 6th

    Internat Conf. on indoor air quality, ventil. and energy conservation, sustain. built environ.t, Sendai, Japan,

    pp 249–256

    Torpy FR, Irga PJ, Moldovan D, Tarran J, Burchett MD, 2013, Characterization and biostimulation of benzene

    biodegradation in the potting-mix of indoor plants. J Appl Hort, 15(1):10–15

    Torpy FR, Irga PJ, Brennan J, Burchett MD, 2013, Do indoor plants contribute to the aeromycota in city

    buildings? Aerobiologia 29:321–331

    Torpy FR, Irga PJ, Burchett MD, 2014, Profiling indoor plants for the amelioration of high CO2 concentrations,

    Urban Forestry & Urban Greening, 13, 2, 227–233

    Torpy FR, Irga PJ, Burchett, MD, 2015, Reducing indoor air pollutants through biotechnology, In: F Pacheco

    Torgal et al. (eds.), Biotechnols, & Biomimetics for Civil Eng., pp 181-209, Springer Internat., Switz.

    UN, 2001, Urbanization: Facts and figures, Urban Millennium, Special Session of General Assembly for an

    Overall Review and Appraisal of the Implementation of the Habitat Agenda, NY, accessed 01/05/2015

    UNEP, 2011, Climate Change Mitigation, http://www.unep.org/climatechange /mitigation/ Buildings/

    tabid/104348/ accessed 11/05/16 .

    http://www.unep.org/climatechange%20/mitigation/%20Buildings/%20tabid/104348/http://www.unep.org/climatechange%20/mitigation/%20Buildings/%20tabid/104348/

  • USEPA, 1995, Particulate Matter (PM-10); AIRTrends Summary; http://www.epa.gov

    /airtrends/aqtrnd95/pm10.html, accessed 03/19/2015.

    USEPA, 2015, The National Ambient Air Quality Standards for Particle Pollution, http://www.epa.gov/

    airquality/particlepollution/actions.html, accessed 03/09/2015.

    USEPA, 2015, Questions About Your Community: Indoor Air, http://www.epa.gov/ region1/

    communities/indoorair.html, accessed 08/08/2015

    USEPA, 2016, Air and Radiation: Basic information, https://www3.epa.gov/air/basic.html, accessed 20/05/16.

    Volk HE, Lurmann F, Penfold B, Hertz-Picciotto I, McConnell R. Traffic-related air pollution, particulate

    matter, and autism. JAMA Psychiatry 2013;70(1)71-77

    Winton A, 2004, Urban violence: a guide to the literature, Environment & Urbanization, 16, 2, 165-184.

    WHO, 2000, The Right to Healthy Indoor Air, In: Report on WHO meeting - European Health Targets,

    Bilthoven, Netherlands.

    WHO, 2001, The Mental Health Context, Mental Health Policy and Service Guidance Package ISBN 92 4

    154594 1(NLM classification: WM 30

    WHO, 2003, Health Aspects of Air Pollution with Particulate Matter, Ozone and Nitrogen Dioxide. Report of

    WHO Working Group, Bonn, Germany.

    WHO, 2005, Indoor Air Pollution and Health, Fact Sheet No. 292.

    Wolverton BC, Johnson A, Bounds K, 1989, Interior Landscape Plants for Indoor Air Pollution Abatement,

    Final Report, NASA Stennis Space Centre MS, USA.

    Wolverton BC, Wolverton JD, 1993, Plants and soil microorganisms: removal of formaldehyde, xylene, and

    ammonia from the indoor environment, J. Mississippi Acad. Sci. 38: 2, 11–15.

    Wood RA, Orwell RL, Tarran J, Torpy FR, Burchett MD, 2002,Potted-plant/growth media interactions and

    capacities for removal of volatiles from indoor air. J Hort Sci Biotechnol 77(1):120–129

    Wood RA, Burchett MD, Alquezar R, Orwell RL, Tarran J, Torpy F, 2006, The potted-plant microcosm

    substantially reduces indoor air VOC pollution: I Office field-study. Water Air Soil Pollut 175 (1–4):163–

    180

    Yang DS, Pennisi SV, Son K-C, Kays SJ, 2009, Screening indoor plants for volatile organic pollutant removal

    efficiency. HortSci 44 (5): 1377–1381

    Yoneyama T, Kim HY, Morikawa H, Srivatava HS, 2002, Metabolism and detoxification of nitrogen dioxide

    and ammonia in plants. In: Omasa K, Saji H, Youssefian N, Kondo N (eds) Air pollution & plant

    biotechnol— Prospects for Phytomonitoring and Phytoremed. Springer, Tokyo, pp 221–234

    Yoo MH, Kwon YJ, Son K-C, Kays SJ, 2006, Efficacy of indoor plants for the removal of single and mixed

    volatile organic pollutants and the physiological effects of the volatiles on the plants. J Amer Soc Hort Sci

    131:452–458

  • Figure 1: Public library.

    Figure 2: Insurance company.

  • Figure 3: Couriers-packaging facility.

    Figure 4: Hunter St café.

    Figure 5: UTS Administration Centre.

  • Figure 6: Childcare centre.

    Figure 7: UTS Conference Centre.