Relay ControlProgramming Basics

Page 3: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Offsets and Differentials, 2 Setpoints

HeatSetpointOffset

DifferentialOutput turns OFF

Output turns ON

Offset

Differential Output turns OFF

Output turns ON

CoolSetpoint

"COOLING" or"HIGH ALARM"

"HEATING" or"LOW ALARM"

Page 4: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Offsets and Differentials, 1 Setpoint

Offset

DifferentialOutput turns OFF

Output turns ON

Setpoint

Offset

Differential Output turns OFF

Output turns ON"COOLING" or"HIGH ALARM"

Deadband

"HEATING" or"LOW ALARM"

Deadband

Page 5: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Proportional ControlProgramming Basics

Page 6: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Direct Acting - Output 12mA @ Setpoint

Page 7: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Reverse Acting - Output 12mA @ Setpoint

Page 8: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Direct Acting - Output 4 or 20mA @ Setpoint

Cooling Heating

Page 9: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Reverse Acting - Output 4 or 20mA @ Setpoint

Cooling Heating

Page 10: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Controller Programming

Page 11: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

2100 Series Controller Programming

• Menu-by-Menu Examples– Follow Along Onscreen– Some Slides Printed in Handout– Product Manuals in Reference Section

• Sub-Systems in Ubiquity Manual Sect. 12

• www.tcsbasys.com

• www.ubiquitysystems.net

Page 12: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Programming Basics

• Factory Defaults Preprogrammed• MUST Change Address – Default is 000

2100 Default is 10X (SL2108 => 108)

• NO LCD on Device – Must Use:– Revelation Professional 2.4– Ubiquity on Standalone QD2040– Ubiquity on Internet

– Ubiquity Mobile ****available for downloadavailable for download****

Page 13: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Programming Options

Page 14: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

PC Based Software -- Revelation Professional

• Menu Driven Programming• Use for Network Setup & Testing, Commissioning,

& Load Balancing• “Read” Before Making Changes• “Write” Before Going to NEXT Menu• “Write” vs. “Write Half / Write Page”• “Load All” & “Save All” Options

*** NOT SUPPORTED AS OF JAN 2009 ***

Page 15: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

PC Based Software -- Insight

Similar to Revelation Professional…

• Tab Driven Interface

• Uses Same Datasheets as Ubiquity

• Use for Network Setup & Testing, Commissioning, & Load Balancing

• Shows Current Values (no “read” required)

• “Write Page” Before Going to New Tab

*** NEW SOLUTION AS OF JAN 2009 ***

Page 16: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Internet Style Software – Ubiquity

• Similar to Revelation Professional

• Single Page for all Programming Info

• Shows Current Values (no “read”)

• Writes all Values on “Submit”

• “Read Controller” Option if Needed

• Same for Internet Based Site and Standalone QD2040

Page 17: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

QD2040 Multi-Function Site Comm. Center

• Stand-Alone/Dial-In, Dial-Out, or Ethernet

• Configuring the Controller Network

• Controller Addressing

• Setup Web Page

• Veris Meter (ModBus) Support

• XML Support

• Several Models Available– REG & –MAX

Page 18: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Where to Get Help or Answers

• Instructions Sent with Product

• TCS Basys Controls Catalog

• Ubiquity Manual

• Training & Reference Manual

• www.tcsbasys.com

• www.ubiquitysystems.net

• Call TCS Directly – 800-288-9383

Page 19: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

2100 Series Controllers

Page 20: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2105 - Five Channel Lighting Module

• Independent, 365-Day Scheduling for ALL 5 Channels

• Digital & Analog Light Sensor Inputs• Analog Current or kW Input• 5 Relay Outputs• 2 “Demand Limit” Outputs• Astronomical Clock

Page 21: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 - Eight Channel Lighting Module

• Independent, 365-Day Scheduling for ALL 8 Channels

• Digital & Analog Light Sensor Inputs• Analog Current or kW Input• 8 Relay Outputs• 2 “Demand Limit” Outputs• Astronomical Clock

Page 22: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2105 & SL2108 Applications

• Indoor or Security Lighting

• Outdoor or Landscape Lights

• Parking Lot Lights and Signs

• Daylight Harvesting

• Lighting Load Shedding

• Power Monitoring

Page 23: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 24: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 25: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 26: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Skip to Next Controller

Page 27: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 28: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 29: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 30: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 31: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 32: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 33: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 34: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 35: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 36: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 37: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SL2108 – eight channel lighting controller

Page 38: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

• Control 1 Cooler with Defrost & 2 Freezers with Defrost and Fan

• 6 RTD Inputs (-40 to 160°F)

• 5 Analog Inputs (4 to 20mA)

• 6 Digital Inputs

• 8 Relay Control Outputs

• 1 Relay Alarm Output

Page 39: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 40: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 41: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 42: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 43: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 44: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Skip to Next Controller

Page 45: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 46: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 47: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 48: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 49: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2141 - Refrigeration Controller

Page 50: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

• 3 RTD (-40 to 160°F) or Thermistor (-20 to 120°F) Inputs

• 3 RTD Inputs (20 to 220°F)

• 2 Analog Inputs (4 to 20mA) • 3 Analog Inputs (0 to 5V)

• 8 Digital Inputs• 1 Relay Output (local alarm)

Page 51: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 52: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 53: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 54: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 55: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 56: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Skip to Next Controller

Page 57: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 58: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 59: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 60: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 61: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2144 – Large Refrigeration Monitor

Page 62: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

• Control 4 Boilers with Chiller Support

• Automatic Rotation of Boilers & Pumps

• 365-Day Scheduling

• 6 RTD & 5 Digital Inputs

• 1 Analog Input (4 to 20mA) • 2 Analog Outputs (4 to 20mA)

• 9 Relay Outputs

Page 63: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 Application

One or Two Boilers with Reset

SZ2165 - Boiler Controller

Page 64: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 65: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 66: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 67: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 68: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 69: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 70: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 71: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Skip to Next Controller

Page 72: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 73: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 74: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 75: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 76: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 77: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 78: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2165 - Boiler Controller

Page 79: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

• Stage 4 Chillers with Boiler Support

• Automatic Rotation of Chillers & Pumps

• 365-Day Scheduling

• 6 RTD Inputs

• 5 Digital Inputs • 2 Analog Outputs (4 to 20mA)

• 9 Relay Outputs

Page 80: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 81: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 82: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 83: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 84: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 85: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 86: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 87: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Skip to Next Controller

Page 88: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 89: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 90: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 91: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 92: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 93: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 94: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2166 - Chiller Controller

Page 95: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

• Control 4 Boilers & a Water Tower

• Automatic Rotation of Boilers & Pumps

• 365-Day Scheduling

• 6 RTD Inputs

• 5 Digital Inputs

• 12 Relay Outputs• 2 Analog Outputs (4 to 20mA)

Page 96: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 Application

Cooling Tower

Page 97: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 98: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 99: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 100: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 101: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 102: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Skip to Next Controller

Page 103: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 104: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 105: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 106: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 107: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 108: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2161 - Heat Pump Water Loop Controller

Page 109: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Loop Control Setup Guide

1. Click “Create Loop System” button 2. Select sub-system definition (Loop Controls)3. Enter a descriptive name for sub-system4. Select master & secondary master

controllers from drop-downs (only appropriate, available controllers will be shown)

5. Select fallback flow switch & related control point from drop-downs

6. Select the desired master controller schedule from drop-down

7. Click the “Submit” button

Page 110: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Loop Control

Page 111: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Loop Control

Page 112: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Loop Control

Page 113: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

• Enthalpy Based Economizer Option

• 365-Day Scheduling

• 6 RTD & 5 Digital Inputs• 4 Analog Inputs (4 to 20mA)

• 3 Analog Outputs (4 to 20mA)

• 2 Heat & 2 Cool Stages

• 2 Selectable Heat and/or Cool Stages

Page 114: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2182 – Advanced AHU Controller

• Enthalpy Based Economizer Option

• 365-Day Scheduling

• 6 RTD & 5 Digital Inputs• 4 Analog Inputs (4 to 20mA)

• 4 Analog Outputs (4 to 20mA)

• 2 Heat & 2 Cool Stages

• 2 Selectable Heat and/or Cool Stages

Page 115: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2182 Applications

• Dehumidification

• Face & Bypass Damper Control

• Static Pressure Control

• Heat Pump with Economizer Control

Page 116: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 117: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 118: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 119: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 120: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 121: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Screenshots or Live View…

Page 122: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 123: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 124: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 125: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 126: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 127: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

SZ2181 - Air Handling Unit Controller

Page 128: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – VAV System Setup Guide

1. Click “Create VAV System” button 2. Click “Add Sub-system” button3. Click “Controllers” to expand table of

options4. Click “Controller Selection” to expand table5. Select controllers to include in sub-system

(only allowable controllers are selectable in this list)

6. Click “Controller Detail” to expand table7. Select units for Discharge Air Temp. Sharing8. Click “System Parameters” to expand table9. Enter a descriptive name for sub-system

Page 129: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – VAV System Setup Guide

10.Select master/main controller from drop-down (only appropriate, available controllers will be shown)

11. Set other “System Parameter” options:1. Occupied Mode Operation2. Unoccupied Mode Operation3. VAV System Type (pressure independent for this example)

4. Duct Static Pressure Controller5. Backup Discharge Air Sensor6. Warm Up Mode Operation7. Morning Warm Up Termination Time/Temp & Options8. Secondary Boiler & Chiller Master Controllers

12.Click “Submit” button

Page 130: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – VAV System

Page 131: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – VAV System

Page 132: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – CZS System Setup Guide

1. Click “Create Superzone System” button 2. Click “Add Sub-system” button3. Click “Controllers” to expand table of

options4. Click “Controller Selection” to expand table5. Select controllers to include in sub-system

(only allowable controllers are selectable in this list)

6. Click “Controller Detail” to expand table7. Select units for Discharge Air Temp Sharing

& for Voting functions8. Click “System Parameters” to expand table

Page 133: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – CZS System Setup Guide

9. Enter a descriptive name for sub-system10.Select master/main controller from drop-

down (only appropriate, available controllers will be shown)

11. Set other “System Parameter” options:1. Occupied Mode Operation2. Cool Priority Mode Operation3. Heat Priority Mode Operation4. Voting Mode Operation5. Unoccupied Mode Operation6. Backup Discharge Air Sensor7. Bypass Damper Controller8. Minimum Demand

Page 134: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – CZS System Setup Guide

11. Set other “System Parameter” options: (cont’d)

9. Tie Break Controller10.Priority Zone Controller11.Majority Maximum Run Time12.Minority Maximum Run Time13.Enable Hot Deck/Cold Deck14.Secondary Boiler and Chiller Master Controllers15.Hot Deck/Cold Deck Unoccupied Options

12.Click “Demand Proportioning” to expand table & set desired options

13.Click “Submit” button

Page 135: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Superzone™ System

Page 136: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Superzone™ System

Page 137: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

HVAC Sub-Systems – Superzone™ System

Page 138: Relay Control Programming Basics Offsets and Differentials, 2 Setpoints

Where to Get Help or Answers

• Instructions Sent with Product

• TCS Basys Controls Catalog

• Ubiquity Manual

• Training & Reference Manual

• www.tcsbasys.com

• www.ubiquitysystems.net

• Call TCS Directly – 800-288-9383