REFERENCE DOC. : SSGP-PL-(GEN)-12-04-(SP024) ( SPECIFICATION FOR BUILDINGS )
ISSUE : ITEM NOT COMPLY WITH COMPRESSOR BUILDING DESIGN.
Refer to above spec. copy from ITB BUILDING SPECIFICATION few item inside this specification not apply inside compressor building design,
1. Floor drains shall also provide underneath the gas turbine / compressor skid.Actual at site not construct.
2. Discharge from the floor drain shall be collected and conveyed by drain pipes to an oil-water separator / water holding tank. (ITB drawing refer SSGP-CR-(CS)-12-04-(DA016) PAGES 1 OF 1)Actual at site not construct.