95
Institut Latihan Sultan Ahmad Shah (ILSAS) Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa PROTECTION & LOCAL CONTROL DRAWINGS Aminuddin bin Musa

Protection and Control Drawings

Embed Size (px)

Citation preview

Page 1: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PROTECTION & LOCAL CONTROL DRAWINGS

Aminuddin bin Musa

Page 2: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PURPOSE OF DRAWINGS

Provide information about equipment or system (such as Protection & Control) in a form which Users will easily understandDescribe the full operation of the systemEnable system to be designed, constructed, installed, tested, commissioned, operated, managed and maintained

Page 3: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PURPOSE OF DRAWINGS

Provide information for various tasks and functions throughout system life cycle;

Engineering Design WorkManufacturingErection and InstallationTesting and CommissioningFault InvestigationOperation and MaintenanceTrainingFuture Extension, Modification or Upgrade

Page 4: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DRAWING CLASSIFICATIONS

Drawings and Documentation Classifications based on IEC 61082 Series Standard;

Function Oriented Documents,Location Documents,Connection Documents,Items Lists.Installation-specific documentsCommissioning-specific documentsOperation-specific documents, andMaintenance-specific documents

Covered Under this Lecture

Page 5: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DRAWING TYPES

Function Oriented DocumentsOverview Diagram – e.g. Single Line DiagramBlock Diagram - e.g. Protection Block DiagramLogic-function Diagram - e.g. Protection Logic Diagram, Control Logic DiagramCircuit Diagram - e.g. Circuit or Schematic DiagramTerminal-function Diagram - e.g. Device Terminal Diagram, Apparatus/Device Drawing List

Location DocumentsInstallation Drawing / Plan - e.g. Layout DrawingsArrangement drawings - e.g. Panel Arrangement DrawingsAssembly Drawings - e.g. Panel Assembly Drawings

Page 6: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DRAWING TYPES

Connection DocumentsConnection Diagram/Table

Unit Connection Diagram/Table - e.g. Internal Connection Table, Internal Multi-core Cable ScheduleInterconnection Diagram/Table - e.g. Inter Panel Connection Diagram, Inter Panel Multi-core Cable Schedule

Cable Diagram/TableItems Lists

Parts List - e.g. Material ListsSpare Parts List

Page 7: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

OVERVIEW – SINGLE LINE DIAGRAM

Starting Point For New Substation Work And To Understand the Scheme

Enable To Easily Check Equipment General Arrangement and Requirements

Various Elements (CTs, VTs, CB, DS, etc.)Shown Symbolically Superimposed

on the SLD)

Complete Substation Seen or Visualized in Semi-pictorial Form

Page 8: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

BLOCK DIAGRAM

PROTECTION BLOCK DIAGRAM

Type of Protection Scheme Used

CT Details (Ratio, Class, etc.) andLocation for Each Protection

Functions

Page 9: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

LOGIC-FUNCTION DIAGRAM

PROTECTION LOGIC DIAGRAM

Describe ProtectionTripping Logic

Page 10: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CIRCUIT OR SCHEMATIC DRAWING

PROTECTION CIRCUIT OR SCHEMATIC DRAWING- CT CIRCUIT

CT Circuit For Overhead Line Main 1 Current Differential Protection

CT Circuit Connection to Current Differential Protection Relay and Test Block

Page 11: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CIRCUIT OR SCHEMATIC DRAWING

PROTECTION CIRCUIT OR SCHEMATIC DRAWING- TRIPPING CIRCUIT

Main 1 Current Differential Protection Tripping

Explain the Circuitry and Mode of Operation

Allow Circuits to be “Followed Through” when Trying to Understand

Scheme and Tracing Fault

Trip Coil 1

Describe System and ImplementedScheme

Page 12: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TERMINAL-FUNCTION DIAGRAM

CURRENT DIFFERENTIAL PROTECTION RELAY TERMINAL-FUNCTION DIAGRAM

Describe Protection RelayTerminal Information such as CT/VT Terminals, Input/Output Contacts, etc.

Describe Protection Relay Particulars such as Relay Model, Version, Order

Number, etc.

Page 13: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL LAYOUT DRAWING

CONTROL AND PROTECTIONPANEL LAYOUT

132kV Control PanelLayout

132kV Protection Panel Layout

Panel Top View Arrangement

Page 14: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL ARRANGEMENT DRAWING

PROTECTION PANELARRANGEMENT DRAWING

Panel Front View Arrangement

Position of Panels With Respect To Each Other

Arrangement Normally Followthe Substation Switchyard Layout

Page 15: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL ASSEMBLY DRAWING

PROTECTION PANELASSEMBLY DRAWING – FRONT VIEW

Assembly of Devices and Componentson the Panel Front Surface

Page 16: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL ASSEMBLY DRAWING

PROTECTION PANELASSEMBLY DRAWING – REAR VIEW

Assembly of Devices and Componentson the Panel Rear and Side Surfaces

Page 17: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL PARTS LIST

PROTECTION PANELPARTS LIST

Device or ComponentItem Code Designation

Device or ComponentManufacturer, Type and Model

Device or ComponentSpecification

Page 18: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GRAPHICAL SYMBOLS

Based on International Standard IEC 60617 Series Standard and TNB PracticesBasic Rules

Symbols (Switchgear Unit, Relays and Contacts) in Circuit/Schematic Drawings are presented in de-energized (non-energized) stateSymbols selected appropriate for the particular purpose of DrawingsSymbols Orientation depends on drawing layout signal flow directionSymbols Legend provided in separate diagram shall be referredAny Exception to the Rules must be clearly marked on the Diagram

Page 19: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GRAPHICAL SYMBOLS

Shown in Non-Energized State

Normally Open State

Normally Close State

Page 20: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GRAPHICAL SYMBOLS

Shown in Non-Energized

State

Page 21: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GRAPHICAL SYMBOLS

Shown in Non-Energized

State

Example of Contactor Relay

Page 22: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GRAPHICAL SYMBOLS

Measuring Relay

Based on TNB Practice (Non IEC Std)

Page 23: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GENERAL DRAWING FORMAT AND STYLE

Variety of Different Drawing Presentation StylesBased on National Standard and Manufacturer Standard

Combined Wiring and Cabling DiagramAll Drawn on Large Sheet of A0 or A1 size paperAdvantage For Simpler Scheme

British PracticeDrawn on Large Sheet of A0 or A1 size paperSeparate Drawings for HV/CT/VT circuits and DC/Auxiliary AC CircuitsDC/Auxiliary AC Circuits Drawn from +ve to –ve, left to rightWires identified by Wire Numbers (Alphabetic Prefix to identify Circuit Type

Page 24: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GENERAL DRAWING FORMAT AND STYLE

Variety of Different Drawing Presentation StylesBased on National Standard and Manufacturer Standard

European PracticeDrawn in Multiple Sheets of A3 or A4 size paperNormally Drawn using Computer Added DraftingTwo types of Presentation Style, i.e. Functional and “Unit” or “Device” Oriented DrawingsFunctional Drawings, e.g. IEC Influence such as Siemens, Areva“Unit” or “Device” Orientated Drawings, e.g. ABB

Page 25: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

FUNCTIONAL ORIENTED DRAWING EXAMPLE

Drawing Based on Function132KV Overhead Line

CB Closing Circuit

Page 26: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

UNIT OR DEVICE ORIENTED DRAWING EXAMPLE

DC Supplies

Control & Indications

Overcurrent Protection

Circuit Breaker

Page 27: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GENERAL DRAWING FORMAT AND STYLE

Variety of Different Drawing Presentation StylesBased on National Standard and Manufacturer Standard

TNB Standard Practice Refer To TNB Transmission Guidelines and Standard DrawingsFunctional DrawingsDrawn in Multiple Sheets of A3 or A4 size paperNormally Drawn using Computer Added DraftingBased on IEC and TNB Practice

Ensure Manufacturer Provide Drawing Legend of Standard Symbols and Codes used

Lecture Based on the Guideline

Page 28: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

GENERAL DRAWING FORMAT AND STYLE

TNB Drawing Format GuideCover Sheet and Title BlockBorders and FrameReference Grid SystemsDiagram Component Layout with Graphical Symbols, Electrical Connections and Linkage LinesReference DesignationsSignal and Location ReferencesCircuit Function ReferencesTechnical Data (if applicable)Explanatory Marking (if applicable)Terminal-Function

Page 29: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

COVER SHEET

First Sheet of DrawingsLocated at Right Hand Side of Drawing SpaceLeft Hand Side – Vacant SpaceIncludes Drawing Identification and Project Information

Page 30: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TITLE BLOCK

Located at Bottom Right-Hand Corner of Drawing Space

Page 31: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

REFERENCE GRID

Start at Upper-Left CornerNumber of Grid Division depends on Drawing Complexity, e.g. 6 by 8 DivisionsRectangle of Grids – Capital Letter along Vertical Edge and Numerals along Horizontal Edge

Starting Point

XPosition E5

Page 32: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DIAGRAM LAYOUT

Signal Flow Direction -Top to Bottom, +ve to -veControlling System at Top of Function-oriented Group Application for Overview, Function and Circuit DiagramsPreferred

Flow

Dire

ctio

n

Page 33: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DIAGRAM LAYOUT

Alternative Signal Flow Direction - Left to RightControlling System at Left of Function-oriented Group Application for Logic-Function DiagramsIf Not Clear, Connecting Line to be with Arrowhead

Flow Direction

Page 34: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

SIGNAL AND REFERENCE LOCATION

Connecting Line in Same Sheet (Signal Y)

Presenter
Presentation Notes
Signal Y, Reference A5 and B1
Page 35: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

SIGNAL AND REFERENCE LOCATION

Device –F21Z Located at Drawing Sheet 32

Presenter
Presentation Notes
Normally Refer to Terminal-function Diagram
Page 36: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CROSS REFERENCING

Device –K1 Located at Circuit Drawing Sheet 5 and Terminal-Function

Drawing Sheet 7

Presenter
Presentation Notes
Cross Referencing on Multiple Sheets
Page 37: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CROSS REFERENCING - ALTERNATIVE

Device –K1 Located at Circuit Drawing Sheet 5and Terminal-Function Drawing Sheet 7.

Relay Coil and Contacts shown below –K1 Device

Presenter
Presentation Notes
No Cross Referencing to Terminal-Function Diagram
Page 38: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CROSS REFERENCING

Cross Referencing To Different Sheet of Same Bay

Sheet 16, Bay E01

Sheet 33, Bay E01

Page 39: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CROSS REFERENCING

Cross Referencing To Different Sheet of Different Bay

Sheet 5, Bay E01

Sheet 2, Bay E05

Page 40: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TERMINAL FUNCTION DIAGRAM

Prepare for All Circuit Devices

Indicate Number of Relay Coil and Contacts Used

Indicate Relay Type, Model,Version, Rating, etc.

Indicate Relay Configurations

Page 41: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CIRCUIT FUNCTION REFERENCE

Main Protection OperatedCircuit Function

Main Protection Operated Contact

Page 42: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

REFERENCE DESIGNATION SYSTEM

Based on International Standard - IEC 61082 Series StandardStandardized and Uniform Reference Designation System to Identify All Devices or Components of Electrical Equipment/SystemsClear and Unique Identification of Devices using Alphanumeric Codes of the Reference Designation

Page 43: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

REFERENCE DESIGNATION SYSTEM

Reference Designation Block Structure and Format (May be Omitted if Obvious or Definitely Clear Identification Available)

Qualifying Symbols= , + , - , :

Alphanumeric Characters‘A’ represents an alphabetical letter‘N’ represents a numerical digit

Format;

Page 44: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DESIGNATION BLOCK

275kV Bay 1, at Relay Panel R1, of Relay F21Z and Terminal Number 10

Page 45: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PLANT/HIGH LEVEL DESIGNATION

Qualifying Symbol =

Page 46: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PLANT/HIGH LEVEL DESIGNATION - EXAMPLE

=E01132kV Bay No.1

=E02132kV Bay No.2

Page 47: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PLANT/HIGH LEVEL DESIGNATION

Page 48: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PLANT/HIGH LEVEL DESIGNATION - EXAMPLE

=E01132kV Bay No.1

=E04132kV Bay No.4

Page 49: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

LOCATION DESIGNATION

Qualifying Symbol +

Page 50: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL LOCATION DESIGNATION - EXAMPLE

Qualifying Symbol +

Page 51: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL LOCATION DESIGNATION - EXAMPLE

=E01+R132kV Protection

Panel No.1

=E02+R132kV Protection

Panel No.2

=E03+R132kV Protection

Panel No.3

=E04+R132kV Protection

Panel No.4

=E05+R132kV Protection

Panel No.5

Page 52: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

LOCATION DESIGNATION

275kV Relay & Control Panel

(AIS Station withSCS Facilities)

AlternativeDesignation

Page 53: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

LOCATION DESIGNATION

132kV Relay & Control Panel(AIS Station)

Page 54: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DEVICE DESIGNATION

Qualifying Symbol -

Note:

For Protective Device, the “NN” is based on TNB Protective Device Code

Page 55: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DEVICE DESIGNATION

Page 56: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DEVICE DESIGNATION

Page 57: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DEVICE DESIGNATION

Q – HV Circuit Breaker, Isolator, Switching Devices

Different From TNB Switching Device Number

(Based on BS 7354)

Page 58: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PROTECTIVE DEVICE CODE

The Device Numbers are based on IEEE Standard –IEEE Std C37.2 – 1996 (IEEE Standard Electrical Power System Device Function Numbers and Contact Designations)The Device Numbers represent standard protective device functionsCustomized to TNB Practice – Alphabet used as Suffix of the Device Code, in combination with IEEE Device Number

For Example, 21Z21 Z

IEEE Device Function Number 21 Impedance Relay

Page 59: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PROTECTIVE DEVICE CODE

The Codes are not replacing the existing protection names

Include as the Device Reference Designation for Protective RelaysFor Example, -F21Z

F - Protection Relay

Page 60: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PROTECTIVE DEVICE CODE - EXAMPLE

Page 61: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PROTECTIVE DEVICE CODE - EXAMPLE

Page 62: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

DEVICE DESIGNATION - EXAMPLE

-F87LLine Differential Protection Relay

-F21ZDistance

Protection Relay

-F79/25Auto-Reclose and

Synchronizing Relay

Page 63: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TERMINAL DESIGNATION

Qualifying Symbol :

This Qualifying Symbol is Normally Omitted as Terminals are Obvious or Clearly Identified in Drawings

Page 64: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TERMINAL BLOCK GROUP

TERMINAL BLOCK

Device Designation:First Code Letter for Terminal Block is XSecond Code Letter for Terminal Block is based on BS158

Page 65: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TERMINAL BLOCK GROUP

Based on Function, For Example, -XP for Protection Circuit

BS158Marking and Arrangement

Main Connection and Small Wiring

-X P

X – Terminal Block Group

Page 66: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TEST TERMINAL FACILITY – TEST BLOCK

X – Terminal Block, Plug, Socket, Relay Test Block

Page 67: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TEST TERMINAL FACILITY

Device Designation:First Code Letter for Relay Test Terminal Facility or Relay Test Block is XSecond Code Letter for Relay Test Block is based on TNB Protective Device Code

For Example; -X21Z

Page 68: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TEST BLOCK DESIGNATION - EXAMPLE

-X87LTest Block For

Line Differential Protection Relay

-FX1ZTest Block For

Distance Protection Relay

-X79/25Test Block For

Auto-Reclose and Synchronizing Relay

Page 69: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CONDUCTOR DESIGNATION

Based on Obsolete British Standard BS158:1961 (Specification For The Marking And Arrangement Of Switchgear Busbars Main Connections and Small Wiring)Widely Practice by TNB – Inherited from British PracticeConductor Designation Not Specified in IEC StandardAdopted for Internal Multi-core Wiring in PanelsStructure and Format

Prefix Letter Representing the Conductor or Wiring FunctionWire Number

Page 70: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CONDUCTOR DESIGNATION

For Example;A11 - Main Protection Red Phase CT Wire NumberJ1, J2 – DC Supply

Page 71: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CONDUCTOR DESIGNATION

Page 72: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CONDUCTOR DESIGNATION - EXAMPLE

Main Protection Current TransformerWiring or Conductor

Numbers

Page 73: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

WIRING MARKING

Adopted For External Multi-core Wiring (Panel to Panel Wiring)Based on Cable and Terminal Block InformationUtilizing Ferrule Markers

Page 74: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

WIRING MARKING

Ferrule Marker For each Group – Differentiated by Use of Alternate White and Yellow Ferrule Markers

Alternate Ferrule Marker Colour

Page 75: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CABLE MARKING

“A” is defined by the voltage levelFirst Numeric “NN” Group Represents the Bay NumberSecond Numeric “NN or NNN” Group Represents the Number proposed in the Table

Second Numeric “NN” or “NNN”

Cable Number Marking Designation

Page 76: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CABLE DIAGRAM - EXAMPLE

Example of Cable Diagram Using Cable Marking275kV Bay No1 (D01)

D01

Page 77: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CABLE DIAGRAM - EXAMPLE

Example of Cable Diagram Using Cable Marking275kV Bay No1 (D01)

Cable MarkingExample From MK +V To CB Q0, “NN” 36-40

Cable Particulars;Cable Size,

Number of Cores, Colour, etc.

Presenter
Presentation Notes
Optical Fibre typically using a letter F follows by a running number is used
Page 78: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CABLE SCHEDULE

Example of Cable Schedule, Showing the Cable Connections (in Table Form) Between Different Panel Locations (Location A to Location B)Include Information about the Multi-Core Cables

Cable NumberCore NumberTerminal Numbers at Each EndsCable SizeCable Functions

Page 79: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PANEL LABELLING AND LOCATION

Panel LabelExample For Indoor Relay Panel

Presenter
Presentation Notes
Indoor panel label designation, with panel label locations
Page 80: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL DRAWINGS REQUIRED IN A TNB PROJECT

Conceptual Design Documents

Page 81: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL DRAWINGS REQUIRED IN A TNB PROJECT

Conceptual Design Documents

Page 82: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL DRAWINGS REQUIRED IN A TNB PROJECT

Conceptual Design Documents

Page 83: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL DRAWINGS REQUIRED IN A TNB PROJECT

Detailed Design Documents

Page 84: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL DRAWINGS REQUIRED IN A TNB PROJECT

Detailed Design Documents

Page 85: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL DRAWINGS REQUIRED IN A TNB PROJECT

Additional Documents Required During Installation

Page 86: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

UNDERSTANDING CIRCUIT OR SCHEMATIC DIAGRAM

Starting Point with Overview and Block DiagramUnderstand the Scheme and Logic-FunctionSymbols (Switching Devices, Relays and Contacts) presented in de-energized (non-energized) stateCircuit Arrangement shown according to Functional Aspect“Follow through” the circuit to understand scheme. Flow Direction from +ve to –ve, top to bottom, left to rightComplex Electronic Functional Block such as Numerical Relay often represented as “Black Box”, input/output clearly identified (Terminal Function Diagram)Main HV circuitry shown in Full Three Phase presentation. Drawn from power source (top) to load (bottom)

Page 87: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

BASIC ELECTRICAL CIRCUIT

110 V

Switch or Other Device Contact

Relay

RelayContact(NO –NormallyOpenContact)

DC SystemBattery

Relays and Contacts shown in de-energized (non-energized) state

Page 88: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

BASIC ELECTRICAL CIRCUIT

110 V

Close Switch or Other Device Contact

RelayOperated

RelayContactClose

DC SystemBattery

Actions initiated or controlled by closing switch, complete the electrical circuitry – Relay change StateRelay contact close

Page 89: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

BASIC CIRCUIT EQUIVALENT

110 V

+

-Representation in Circuit or Schematic Diagram FormatCircuitry based on Circuit FunctionSignal Flow direction from +ve to –ve, Top to Bottom

Controlling System on Top (Contact)

Relay at Bottom

Page 90: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CIRCUIT LOGIC

A B CZ+ve -ve

AND gate, Contacts in SeriesCircuitry More Secure

Presenter
Presentation Notes
Check
Page 91: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

CIRCUIT LOGIC

Z+ve-ve

A

B

C

OR gate, Contacts in ParallelCircuitry More Dependable

Page 92: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL CIRCUIT DIAGRAM – CT CIRCUIT

Page 93: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL CIRCUIT DIAGRAM – PROTECTION TRIPPING

TRIPPING CIRCUIT 1

Page 94: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

TYPICAL CIRCUIT DIAGRAM – PROTECTION TRIPPING

TRIPPING CIRCUIT 2

Page 95: Protection and Control Drawings

Institut Latihan Sultan Ahmad Shah(ILSAS)

Unit Perlindungan, Seksyen Latihan Penghantaran - 2007 Aminuddin Musa

PRACTICAL

REFER TO TNB STANDARD DRAWINGS