Upload
others
View
13
Download
0
Embed Size (px)
Citation preview
Pressure and Temperature
Transducer (PTX)
This manual contains important information for the safe and effective operation of the Swagelok® Pressure and Temperature Transducer, PTX series. Users should read and understand its contents before operating the transducer.
User’s Manual
www.swagelok.com
2 Pressure and Temperature Transducer User’s Manual
ContentsIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Product Information . . . . . . . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . 4
Control Drawing . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . 7
DeviceNet™ Network Cable . . . . . . . . . . . . . . . . 7
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Node Setup. . . . . . . . . . . . . . . . . . . . . . . . . 8
Parameter Setup . . . . . . . . . . . . . . . . . . . . . . 9
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Zero Compensation . . . . . . . . . . . . . . . . . . . . 13
Poll Request . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 14
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 15
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Pressure and Temperature Transducer User’s Manual 3
IntroductionThe Swagelok Pressure and Temperature Transducer (PTX) is an industrial pressure and temperature transducer for monitoring fluid pressure and temperature in automated fluid systems using a MEMS pressure‑sensing technology. It communicates pressure and temperature data via the DeviceNet industrial network protocol. The PTX is available with a 1.5 in. Swagelok Modular Platform Component (MPC) surface mount in accordance with ANSI/ISA 76.00.02 or with 1/4 in. Swagelok tube fitting connections.
Product Information
Fig. 1 PTX with MPC Modular Surface Mount front view
Module LED
Fig. 2 PTX with 1/4 in. Swagelok Tube Fitting End Connections
Network LEDM12 Network Connector Plug
Mounting holes
back view
4 Pressure and Temperature Transducer User’s Manual
SpecificationsPower
Voltage 24 V (dc), nominalCurrent < 100 mA (dc) at 24 V (dc)Wattage < 2.4 W at 24 V (dc)
Temperature (environment)
Operating (Ambient)Minimum 23°F (–5°C)
Maximum 158°F (70°C)
Media Minimum 32°F (0°C)
Maximum 158°F (70°C)
StorageMinimum ‑40°F (–40°C)
Maximum 158°F (70°C)
Temperature Measurement
Measurement Range 23 to 158°F (–5 to 70°C)
Accuracy, including: Repeatability
Hysteresis Nonlinearity
± 2.2°C absolute accuracy
Full-scale Range0 to 50 psig (0 to 3.4 bar)
0 to 250 psig (0 to 17.2 bar)
0 to 500 psig (0 to 34.4 bar)
Pressure Measurement
Accuracy at 77°F (25°C) including:
Repeatability Hysteresis
Nonlinearity
± 1 % of full scale pressure, following steps in accordance with setup procedures described in this manual
Over Pressure 2 × full scaleBurst Pressure 5 × full scale
Weightwith MPC process connections 0.83 lb (375 g)
with 1/4 in. Swagelok tube fitting connections 1.26 lb (570 g)
Certifications
■ ANSI/ISA 12.12.01‑2011 Non‑incendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
■ UL 61010‑1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use—Part 1, Edition 2
■ CSA C22.2 No. 213‑M1987, Non‑incendive Control Equipment for use in Class I, Division 2 Hazardous Locations
■ CSA C22.2 No 61010‑1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use—Part 1, Edition 2
Ingress Protection IP64
Electromagnetic Compatibility
EN 61326‑1:2006■ RF Emissions: EN 55011■ ESD Immunity: EN 61000‑4‑2■ RF Immunity: EN 61000‑4‑3■ EFT Immunity: EN61000‑4‑4■ Conducted Immunity: EN 61000‑4‑6
VibrationSinusoidal 9 to 200 Hz, 5 g acceleration
Random 20 to 500 Hz, 15.5 g average accelerationShock Pulse 70 m/s2 (7.2 g)Entity Parameters See Control Drawing: PTX‑DN‑0006‑SCHEDULESupported Communication Baud Rates
Auto‑baud function, allowing the device to detect the speed of network traffic. It is compatible with 125 kbaud, 250 kbaud, and 500 kbaud rates.
Note: Before installing the PTX in a hazardous location, review the control drawing on page 5. This will help ensure all electrical connections to and from the PTX comply with safety requirements.
Pressure and Temperature Transducer User’s Manual 5
Control Drawing
OR
123 45
Not
es:
(1)
The
Entit
y C
once
pt a
llow
s int
erco
nnec
tion
of n
onin
cend
ive
appa
ratu
s with
as
soci
ated
app
arat
us n
ot sp
ecifi
cally
exa
min
ed in
com
bina
tion
as a
syst
em w
hen
the
appr
oved
val
ues o
f Voc
and
Isc
of th
e as
soci
ated
app
arat
us a
re le
ss th
an o
r equ
al to
V
max
and
Imax
of t
he n
onin
cend
ive
appa
ratu
s and
the
appr
oved
val
ues o
f Ca
and
La
of t
he a
ssoc
iate
d a
ppar
atus
are
gre
ater
than
Ci+
Cca
ble
and
Li+
Lcab
le re
spec
tivel
y fo
r the
non
ince
ndiv
e ap
para
tus.
(2) C
apac
itanc
e an
d in
duc
tanc
e of
the
field
wiri
ng fr
om th
e no
ninc
end
ive
equi
pmen
t to
the
asso
ciat
ed a
ppar
atus
shal
l be
calc
ulat
ed a
nd m
ust b
e in
clud
ed in
the
syst
em
calc
ulat
ions
as s
how
n in
Tab
le 1
. C
able
cap
acita
nce,
Cca
ble,
plu
s non
ince
ndiv
e eq
uipm
ent c
apac
itanc
e, C
i, m
ust b
e le
ss th
an th
e m
arke
d c
apac
itanc
e (L
cabl
e, L
i an
d L
a or
Lo,
resp
ectiv
ely)
. W
here
the
cabl
e ca
paci
tanc
e pe
r foo
t are
not
kno
wn,
the
follo
win
g va
lues
shal
l be
used
: C
cabl
e =
60 p
F/ft.
, Lca
ble
= 0.
2 µ H
/ft.
TA
BLE
1:
TA
BLE
2:
Non
ince
ndiv
e Eq
uipm
ent
A
ssoc
iate
d A
ppar
atus
V
max
(or U
i) ≥
Voc
(or U
o)
I max
(or I
i) ≥
Isc (o
r lo)
P
max
(or P
i) ≥
Po
C
i ≤
Ca
(or C
o)
Li ≤
La (o
r Lo)
If Po
of t
he a
ssoc
iate
d a
ppar
atus
is n
ot k
now
n, it
may
be
calc
ulat
ed u
sing
the
form
ula:
Po
= (V
oc *
Isc)
/4 =
(Uo
* Io
)/4.
(3) A
ssoc
iate
d a
ppar
atus
mus
t be
inst
alle
d in
acc
ord
ance
with
its m
anuf
actu
rer's
co
ntro
l dra
win
g an
d A
rticl
e 50
4 of
the
Nat
iona
l Ele
ctric
al C
ode
(AN
SI/N
FPA
70)
, the
C
anad
ian
Elec
trica
l Cod
e, o
r oth
er lo
cal in
stal
latio
n co
des
, as a
pplic
able
. Th
e re
sista
nce
of th
e gr
ound
pat
h m
ust b
e le
ss th
an 1
ohm
.
(4) W
hen
requ
ired
by
the
man
ufac
ture
r's c
ontro
l dra
win
g, th
e as
soci
ated
app
arat
us
mus
t be
conn
ecte
d to
a su
itabl
e gr
ound
ele
ctro
de
per t
he N
atio
nal E
lect
rical
Cod
e (A
NSI
/NFP
A 7
0), t
he C
anad
ian
Elec
trica
l Cod
e, o
r oth
er lo
cal in
stal
latio
n co
des
, as
appl
icab
le.
The
resis
tanc
e of
the
grou
nd p
ath
mus
t be
less
than
1 o
hm.
(5) T
he P
TX is
pow
ered
by
two
sepa
rate
non
ince
ndiv
e ci
rcui
ts, d
esig
nate
d P
ower
and
Si
gnal
as i
ndic
ated
in T
able
1.
Cab
le a
nd w
iring
for t
hese
two
circ
uits
mus
t mai
ntai
n th
e se
para
tions
for d
iffer
ent n
onin
cend
ive
circ
uits
requ
ired
by
Arti
cle
504
of th
e N
atio
nal E
lect
rical
Cod
e (A
NSI
/NFP
A 7
0), I
SA R
P12.
6 fo
r ins
tallin
g no
ninc
end
ive
circ
uits
, or
oth
er lo
cal c
odes
, as a
pplic
able
.
(6) A
ssoc
iate
d a
ppar
atus
mus
t not
be
used
in c
ombi
natio
n un
less
per
mitt
ed b
y as
soci
ated
app
arat
us c
ertif
icat
ion.
(7) W
ARN
ING
: Su
bstit
utio
n of
com
pone
nts m
ay im
pair
safe
ty.
(8)
The
ambi
ent o
pera
ting
(Tam
b) ra
nge
for t
his p
rod
uct i
s -5C
to 7
0C.
(9) E
ach
unit
mus
t be
conn
ecte
d to
an
IP64
or h
ighe
r rat
ed c
onne
ctor
or I
P ra
ting
will
be
void
.
HAZA
RDO
US L
OC
ATIO
NC
lass
I, D
iv. 2
, Gro
ups A
, B, C
, D
Any
ass
ocia
ted
app
arat
us p
ower
su
pply
with
Ent
ity C
once
pt
Para
met
ers (
1) a
ppro
pria
te fo
r co
nnec
tion
to a
n no
ninc
end
ive
dev
ice
with
Ent
ity c
once
pt
para
met
ers l
isted
in T
able
1.
Any
non
ince
ndiv
e or
ass
ocia
ted
ap
para
tus c
omm
unic
atio
n co
ntro
ller w
ith E
ntity
Con
cept
pa
ram
eter
s (1)
(Vm
ax, I
max
, Ci,
Li) a
ppro
pria
te fo
r con
nect
ions
to
noni
ncen
div
e d
evic
es w
ith E
ntity
C
once
pt p
aram
eter
s list
ed in
Ta
ble
1.
NO
N-H
AZA
RDO
US L
OC
ATIO
N
CO
NTR
OL
EQUI
PMEN
T
NO
NIN
CEN
DIV
E FI
ELD
WIR
ING
- PO
WER
CIR
CUI
T(P
INS
2,3)
NO
NIN
CEN
DIV
E FI
ELD
/A
SSO
CIA
TED
APP
ARA
TUS
WIR
ING
- SI
GN
AL
CIR
CUI
T(P
INS
4,5)
Fiel
d W
iring
Dia
gram
1 - D
rain
bar
e2
- V+
r
ed3
- V-
b
lack
4 - C
AN
_H
whi
te5
- CA
N_L
b
lue
WA
RNIN
G: A
NY
CHA
NG
ES M
AD
E TO
THI
S D
OC
UMEN
T M
UST
BE R
EVIE
WED
AN
D A
PPRO
VED
BY
SWA
GEL
OK
CO
MPL
IAN
CE
DPT
MA
TERI
AL:
NA
DES
CRI
PTIO
N: S
WA
GEL
OK
DEV
ICEN
ET P
TX C
ON
TRO
L D
RAW
ING
Mal
e
DW
G.
NO
.PT
X-D
N-0
006-
SCHE
DUL
E
TITLE
DRA
WN
BY
CHE
CK/
APR
BY
JEK
DW
G.
NO
.PT
X-D
N-0
006-
SCHE
DUL
E
THIS
PRI
NT
IS T
HE E
XCLU
SIV
E PR
OPE
RTY
OF
SWA
GEL
OK
CO
MPA
NY.
IT
MUS
T BE
RET
URN
ED O
N
REQ
UEST
ALO
NG
WITH
AN
Y D
OC
UMEN
TS C
ON
TAIN
ING
INFO
RMA
TION
OBT
AIN
ED F
ROM
THI
S PR
INT.
NEI
THER
THI
S PR
INT
NO
R A
NY
PART
OF
IT N
OR
AN
Y IN
FORM
ATIO
N C
ON
CER
NIN
G IT
MA
Y BE
CO
PIED
, D
ISC
LOSE
D T
O O
THER
S O
R US
ED F
OR
AN
Y PU
RPO
SE E
XCEP
T IN
FUR
THER
AN
CE
OF
YOUR
BUS
INES
S W
ITH S
WA
GEL
OK.
THE
PA
RTS
REFE
RRED
TO
ON
THI
S PR
INT
MA
Y BE
THE
SU
BJEC
T O
F PA
TEN
TS A
ND
/OR
PEN
DIN
G A
PPLIC
ATIO
NS
AN
D M
AY
NO
T BE
MA
NUF
AC
TURE
D
WITH
OUT
PER
MIS
SIO
N F
ROM
SW
AG
ELO
K C
OM
PAN
Y.
SCA
LEN
ON
ERE
V.-
SHEE
T 1
of 1
REVI
SIO
NS
TOLE
RAN
CE
ON
EN
GLIS
H D
IMEN
SIO
NS
UNLE
SS O
THER
WIS
E SP
ECIF
IED
76
54
32
1
D C B A
8 87
65
43
21
ABCD
APP
ROV
AL/
SCHE
DUL
E D
RAW
ING
.X
X
.0
31
.XXX
.015
A
NG
LES
1
DEG
REE
DC
N R
EV.
Jul-5
-11
DA
TE
DA
TEBR
MJu
l-29-
11--
DIM
ENSI
ON
S A
RE IN
CHE
S N
EXT
TO [M
ILLIM
ETER
S].
© S
wag
elok
Com
pany
All R
ight
s Res
erve
d
Fig. 3 PTX-DN-0006 SCHEDULE
6 Pressure and Temperature Transducer User’s Manual
InstallationMountingA PTX with 1/4 in. Swagelok tube fitting process end connections should be installed in the system according to Swagelok Tube Fitting Instructions for 1 in. (25 mm) and smaller fittings, MS‑12‑01.
A PTX with a 1.5 in. Swagelok MPC modular surface mount should be installed in the system according to the surface mount assembly instructions in the MPC Series Modular Platform Components Assembly and Service Instructions, MS‑12‑39.
Dimensions, in inches (millimeters), are for reference only and subject to change.
Fig. 4 Product Dimensions
MPC Modular Surface Mount Swagelok Tube Fitting End Connections
M12 connector
5.77 (147)
0.25 (6.4)
0.59 (15.0)
1.50 (38.2)
Four mounting holes, 0.21 (5.3) dia
1.50 (38.2)
Front FrontBottom
Top Top
M12 connector
1.49 (37.8)
6.35 (161)
2.54 (64.5)
Pressure and Temperature Transducer User’s Manual 7
Power SupplyThe PTX requires voltage supplied to be within the range of the DeviceNet standard, which states: 24 volts ±1 % or adjustable to 0.2 %. Use of a lower voltage network power supply will decrease the reliability of the network and may make it inoperable. Swagelok validated the performance of the PTX operating at 11, 24, and 28 V (dc).
Hazardous Location Power SupplyIt is required that a Class 2 power supply be used when the PTX is used in Class I, Division 2 hazardous locations. Class 2 power supplies have a maximum power outlet of 100 W.
DeviceNet Network Cable
Cable LengthDeviceNet network cable lengths are defined in ODVA’s Planning and Installation Manual: DeviceNet Cable System, chapter 1, www .odva .org. Using cable lengths longer than those recommended can result in degradation of signal integrity and decrease of supply voltage.
Hazardous Location Cable LengthThe power supply used determines the maximum capacitance and inductance for the network. The total network inductance and capacitance can be determined by adding together the inductance and capacitance values of the devices on the network along with that of the cable.
The Swagelok PTX adds 0 µH and 0 µF to the network.
Cable parameters can be determined from the manufacturer’s data sheet. Worst case values of 60 pF/ft and 0.2 µH/ft can be assumed when that information is not available.
Cable Bend RadiusThe DeviceNet network cable should not be bent too tightly, as this causes excess strain on the cable and the attachment point on the device. After the cable has been installed, the bend radius can be adjusted so long as it is no smaller than its fixed radius. Typical cables and their bend radii can be found in ODVA’s Planning and Installation Manual: DeviceNet Cable System, chapter 1.
Connecting the CableConnect the micro M12 connector end of the network cable to the network interface plug on the PTX. Connect the opposite end to the system network.
1
2 3
4
5
V‑V+
CAN_L
CAN_H
Mechanical key
Drain
Fig. 5 M12 Female Connector End
V+ = 24 V (dc) supply V– = Ground CAN_H = High signal of CAN differential
signal CAN_L = Low signal of the CAN differential
signal Drain = Cable shield, ground at the power
supply end
8 Pressure and Temperature Transducer User’s Manual
Setup Node Setup
Register the Electronic Data Sheet (EDS)1. Download the electronic data sheet (EDS) and the icon file (PTX.ico) from www .swagelok .com. (path TBD)
Save both files to the same directory.
Note: Altering the EDS in any way voids the product warranty.
2. Open your network configuration tool. The screen captures in this manual use RSNetWorx™ for DeviceNet. Alternatives include OMRON® DeviceNet Configurator and Anybus® NetTool.
3. Register the EDS using the network configuration tool.
4. Connect the PTX to the network.
5. Scan the network for the PTX and once found, open the properties interface for the device.
6. Set the device address (MAC ID) of the device to the desired value.
Device Address (MAC ID)The PTX will have a factory set address of 63 when initially powered on. Addresses between 0 and 63 are valid DeviceNet addresses. Do not duplicate addresses. Duplicate addresses will cause the devices at that address to be unable to communicate with the network. As noted, new devices will be set to address 63, so it is recommended to leave that address open to accommodate new hardware.
Assign higher priority devices a low network address as the lowest network address will be given priority during network arbitration.
Fig. 6 General Tab
Pressure and Temperature Transducer User’s Manual 9
Parameter SetupOpen the parameters menu after the device is recognized by the configuration software. Set the parameters that follow as desired for use with your network.
Fig. 7 Parameters Tab
10 Pressure and Temperature Transducer User’s Manual
Message FormatThe PTX supports several message formats as defined below. Each message format contains different information and results in a different amount of network traffic. The truncated integer values use fewer bytes to encode, resulting in less network traffic.
Name I/O Type* Bytes Format
Status, Pressure, Temperature (REAL)
(factory default)Polled Input 9
Status Byte (See Operation)Pressure (Real)
Temperature (Real)
Status, Pressure (REAL) Polled Input 5Status Byte (See Operation)
Pressure (Real)
Status, Pressure, Temperature (Integer) Polled Input 5
Status Byte (See Operation)Pressure (Integer)
Temperature (Integer)
Status, Pressure (Integer) Polled Input 3Status Byte (See Operation)
Pressure (Integer)
Alert Reset Polled Output 1 Reset Byte
Note: Input and output are defined from the standpoint of the DeviceNet network.
Fig. 8 Setting Message Format
Pressure and Temperature Transducer User’s Manual 11
Fig. 9 Set Units
Fig. 10 Set Alarms
Set UnitsThe PTX can report the pressure and temperature values to the network in a variety of units.
Pressure Units Temperature Units
psig (factory default)
°F (factory default)
bar °C
kPa % full scale
% full scale
Set AlarmsThe PTX can be set to send an alarm when the pressure or temperature falls below, or rises above, a certain value. Additionally, alarm hysteresis and settling time can be set.
Note: The units for the alarms will be the same as those set in Set Units.
The factory default setting is zero for these fields.
Alarm Description
Alarm Trip Point High Value above which an alarm occurs.
Alarm Trip Point Low Value below which an alarm occurs.
Alarm HysteresisThe amount by which the value must
recover to clear an alarm.
Alarm Settling TimeThe amount of time that the value
must exceed the trip point before an alarm is triggered (in msec).
12 Pressure and Temperature Transducer User’s Manual
Fig. 11 Maintenance Dates
Set Averaging TimeThe PTX allows the averaging time of the measured value to be set. This allows the user to implement a type of low pass filtering on the measured data, removing transient measurements from the reported values. This parameter is entered as the amount of time over which the measurements will be averaged in milliseconds (msec). The factory default is 0 msec.
Alarm Enable The alarm enable sets whether the alarms are activated.
Maintenance DatesThe last and next maintenance date can be set by the user. The factory set default for both fields is the date of manufacture.
Parameter Name Description
Last Maintenance DateDocuments the date maintenance
was performed.
Next Maintenance Date
Documents the next date maintenance will be performed. This would be determined by the system
calibration schedule.
Pressure and Temperature Transducer User’s Manual 13
OperationZero CompensationTo achieve the specified pressure accuracy from the PTX, under all conditions, the following zero compensation procedure must be performed. Zero compensation for the PTX is essentially equivalent to the tare function on a weight scale.
1. Apply 0 psig (i.e. ambient atmospheric pressure) to the PTX.
2. Allow the PTX to stabilize to the temperature and atmospheric pressure of the environment in which it is installed.
3. With 0 psig applied to the PTX, retrieve a series of measurements (10 or more) from the PTX and average them together. This average is call the zero compensation offset.
4. Zero compensate subsequent PTX measurements by subtracting the zero compensation offset from them.
Zero compensated PTX measurements are guaranteed to be less than 1 % of full scale away from the actual pressure applied to the PTX. The span of the PTX never needs adjusted or calibrated.
NOTE: Excessive over pressure conditions may require the zero compensation procedure to be repeated to maintain the PTX’s high accuracy.
14 Pressure and Temperature Transducer User’s Manual
Poll RequestSend a poll request to the configured PTX’s MAC ID in order to receive data. The PTX will return a status message in the format set for Message Format, Units, and Alarms in Setup.
For example:
If the value has been set up to be returned as an integer, a pressure value of 100 psig (6.8 bar) would be converted to a hexadecimal as 0x0064, then transmitted by the PTX to the network as 0x6400. The last byte (0x00) represents the most significant byte while the lower byte encodes the least significant byte.
If the value has been set up to be returned as a real number, a pressure value of 100.00 psig (6.8 bar) would be converted to a IEEE‑754 compliant real value of 0x42C80000, then transmitted by the PTX to the network as 0x0000C842.
Notice that the integer data format is shorter, which will result in less network traffic. However, the real number format contains decimal values, which results in higher measurement resolution.
The status byte will return the status of the alarms in the following format.
Status Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 PUR POR TUR TOR Power
1 = true; 0 = false
Bits 1 through 4 refer to alarms set to show true when the measured pressure or temperature value exceed preset levels:
Bit 4: PUR—Pressure Under Alarm Trip Point
Bit 3: POR—Pressure Over Alarm Trip Point
Bit 2: TUR—Temperature Under Alarm Trip Point
Bit 1: TOR—Temperature Over Alarm Trip Point
The alarms on the PTX can be reset by sending a Reset Byte to the device. The format should be as follows:
Reset Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0 1
MaintenanceAdditional assembly hardware for the MPC surface mount is available. Refer to Modular Platform Components (MPC), MS‑02‑185, for ordering information.
There are no field‑maintainable parts within the PTX. Contact your authorized Swagelok representative for assistance.
Pressure and Temperature Transducer User’s Manual 15
TroubleshootingProblem Cause Remedy
Module (MOD) Light
Off No power applied to the device. Connect power.
Green Normal operation. No action needed.
Flashing Green Device needs to be configured. Configure device.
Red Device has an unrecoverable fault.Cycle power to device. If device fails to
recover, contact your authorized Swagelok representative.
Flashing Red Device has invalid configuration. Check configuration setup.
Network (NET) Light
Off
The device has no power or the channel is disabled for communication due to bus off
condition, loss of network power, or has been intentionally disabled.
Power‑up the DeviceNet scanner, provide network power to channel, and make sure
channel is enabled in both the scanner configuration table and module command
word.
Green Normal operation. No action needed.
Flashing Green
The channel is enabled but no communication is occurring.
The two‑digit numeric display for the channel on the DeviceNet scanner indicates an error
code that provides more information about the condition of the channel.
Configure scan list table for channel to add device.
Red
The communication channel has failed.The two‑digit numeric display for the channel on the DeviceNet scanner indicates an error
code that provides more information about the condition of the channel.
This may indicate a defective DeviceNet scanner.
Reset DeviceNet scanner. If failures continue, replace DeviceNet scanner.
Flashing Red
At least one of the devices in the DeviceNet scanner’s scan list table has failed to
communicate with the DeviceNet scanner. The network has faulted.
The two‑digit numeric display for the channel on the DeviceNet scanner indicates an error
code that provides more information about the condition of the channel.
Examine the failed device and examine the scan list table for accuracy.
General
System displays pressure when process media
supply has been turned off.
Measurement is within of tolerance band.
The PTX measures pressure within a tolerance of ± 1 % of the full scale range of the device. A reading of 0.5 psig (0.03 bar) for a 50 psig (3.4 bar) PTX is normal even when system
pressure is at zero.
Ambient temperature is outside of specification.The pressure measurement will not be thermally compensated when the ambient temperature is
outside the specified range.
Process media is trapped within the system. Ensure the system has been properly vented.
The sensor element has been damaged. Replace the PTX.
The PTX goes offline periodically. The M12 connector is loose. Ensure that the M12 connector has proper
thread engagement and is firmly attached.
Contact your authorized Swagelok representative for additional assistance.
GlossaryTerm Definition
CAN Controller Area Network, a message based communication protocol
DeviceNet Scanner Device that provides the bridge between the DeviceNet network and the PLC
EDSElectronic data sheet, a file used by node commissioning tools to interpret parameters on the device
Entity Parameters Values used to determine the suitability of the device for use in hazardous environments
LED Light Emitting Diode
MAC ID Media access controller identifier
MOD LED Module LED, a light that provides feedback on the status of the module
NET LED Network LED, a light that provides feedback on the status of the PTX network connection
PLC Programmable Logic Controller
Swagelok—TM Swagelok CompanyDeviceNet—TM ODVARSNetWorx—TM Rockwell Automation, Inc.OMRON —TM OMRON CorporationAnybus—TM HMS Industrial Networks AB© 2012‑2019 Swagelok CompanyMS‑13‑222, RevA, December 2019