Upload
shakeb-amir
View
438
Download
14
Tags:
Embed Size (px)
DESCRIPTION
POWER CUBE 1000 AN ICC 500 -HA Quick
Citation preview
HUAWEI TECHNOLOGIES CO., LTD.
PowerCube 1000 V300R002C00
Quick Installation Guide (with an ICC500-HA)
Issue: 01
Date: 2012-08-29
1
Safety Precautions
To ensure safety of humans and the equipment, pay attention to the safety symbols on the equipment and all the
safety instructions in this document. The "NOTE", "CAUTION", and "WARNING" marks in other documents do not
represent all the safety instructions. They are only supplements to the safety instructions. When operating Huawei
equipment, in addition to following the general precautions in this document, follow the specific safety instructions
given by Huawei. Huawei will not be liable for any consequences that are caused by the violation of safety regulations
and design, production, and usage standards.
Local Safety Regulations
When operating Huawei equipment, you must follow the local laws and regulations.
Personnel Requirements
Only trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment.
You can modify default parameters only after being granted approval from Huawei technical support.
Symbols
■
Alerts you to a potentially hazardous situation that could, if not avoided, result in equipment damage, data loss,
performance deterioration, or unanticipated results.
Provides additional information to emphasize or supplement important points in the main text.
■
■
■
Precautions
Human Safety
To prevent electric shocks, get the tool insulated and wear insulated gloves when connecting cables.
To prevent inhalation or eye contact with dust, take adequate preventive measures when drilling holes.
To prevent body injuries, wear protective shoes when moving storage batteries.
■
Copyright © Huawei Technologies Co., Ltd. 2012. All rights reserved.
Tools
Flat-head screwdriver
(M3 and M4)
Phillips screwdriver
(M3 and M4) Adjustable wrench Claw hammer Diagonal pliers COAX crimping tool
Wire stripper Hydraulic pliers Fuse extracting unit PVC insulation tape Electrician's knife
Hammer drill Heat gun Socket wrench Marker Heat shrink tubing
Cable tie Clamp meter
Crane (with
a capacity
of greater
than 2 t)
Hoist clamp and
lifting rope (7 m)
Antitheft wrench
Torque wrench
ESD gloves Protective gloves
Insulated gloves Combination pliers Cable cutter Protective shoes
2
ICC500-HA+FCB Scenario
DC power cable (d)
Signal cable (s)
AC power cable (a) Mains +DG+ FCB
Network Diagram
(s1) Communications cable between the energy control
center 500 (ECC) and the transport network(BBU)
(s2) Signal cable to the battery temperature sensor
(s3) Signal cable(DG remote start) between ECC and
DG control panel(DSE 5110)
(s4) Signal cable(DG operation) between ECC and ATS
(s5) Signal cable(mains failure) between ECC and ATS
(s6) Signal cable(DG low fuel) between ECC and DG
(d1) DC power cable between fast cycle batteries (FCBs)
and the DCDU
(d2) DC power cable between the DCDU and the DC-
powered load
(a1) AC power cable between ATS and ACDU
Appearance
Heat exchanger
Air channel panel
Direct current distribution unit
(DCDU)
ECC500
Filler panel
Subrack
DCDU
ICC500-HA
Cable hole
Battery rack
Positive busbar
Negative busbar
Front view (interior) Front view (exterior)
BBU/BSC
NetEco
DC-powered load
FCB
Mains
s1
d1
DCDU
ECC500
d2 a1 ACDU
s2
s3
s4 s5
Air-flow
channel panel
s6
3
Rear view (interior)
ACDU Alternating
current
distribution unit
(ACDU)
ICC500-HA
Ground bar
Rear view (exterior)
ICC500-HA
(1) Main control module (2) Extension DO module (3) GPRS module (optional) (4)
Extension DI module (5) D.G. IO module (need to be installed )
(6) Basic IO module
Appearance(ECC500 )
4
Recommended Cable Routes in the ICC500-HA
DC
po
we
r ca
ble
AC
po
we
r ca
ble
Front view Rear view
DC
po
we
r ca
ble
Gro
un
d c
ab
le
Sig
na
l ca
ble
Sig
na
l ca
ble
1. Bind AC power cables, signal cables, and communications cables separately.
2. Route cables by referring to the following figure. Secure the cables to the nearest cable bridge or binding hole.
Left side Right side
Route cables by referring to the following figure.
5
DC
po
we
r ca
ble
an
d S
ign
al ca
ble
at
left
DC
po
we
r ca
ble
an
d S
ign
al ca
ble
at
rig
ht
Front view
Bind cables by referring to the following figure.
6
Rear view
AC
po
we
r ca
ble
G
rou
nd
ca
ble
7
1 Installing Equipment
Determining the Position for Installing the ICC500-HA a
Installing MUE03A and PSUs
c
Ф16
M12x60 (4
PCS)
Socket wrench
Bolt Spring washer Flat washer
Expansion tube
Mark hole positions. Install expansion bolts.
52–60 mm
≥ 1000 mm
Edge of the wall or platform Floor
Mounting hole
Installing and Securing the ICC500-HA
b
Front
Black
Remove filler panels.
Insert PSUs into slot 1, then slot 2, and so on, until all required PSUs are installed.
1. A PSU delivers a rated output current of 50 A. A maximum of six PSUs
can be configured as required.
2. The following figure is for reference only.
`
1 2 3 4
5 6 7 8
L1 L2 L3 L1
L2 L3 L1 L2
Site ground bar
Rear view
Ground the cabinet immediately after it is installed.
Socket
wrench
Use the marking-off template delivered with the ICC500.
Install an MUE03A in the ECC500
Installing other equipments
Notes Front view
Rear view
Bind
Water
Front view
8
9
Installing FCBs d
1. Fast cycle batteries (FCBs) must be placed in strict accordance with the figure.
2. When connecting cables to FCBs, wear protective gloves and use insulated tools (such as a wrench with its handle wrapped with PVC
insulation tape).
3. After connecting one battery cable, partially tighten the bolts first. After connecting all battery cables, tighten all the bolts. The
reference torque for tightening bolts is 20–25 N.m.
4. Before connecting a cable to an FCB, remove the protective lid from the FCB and reinstall the protective lid after connecting the cable.
Route the cable for connecting front and rear FCBs in serial under the bottom layer of the battery rack from the front side of the
integrated controller and converter-HA (ICC500-HA) to the rear side. Leave the red terminal at the front side and the blue
terminal at the rear side.
Front view Rear view
Cable for connecting front and rear FCBs in serial
Cable for connecting adjacent FCBs in serial
Cable for
connecting FCBs in
adjacent layers in
serial
Front view Rear view
Bottom
layer of the
battery rack
Cable for connecting front and rear FCBs in serial Cable for connecting front and rear FCBs in serial
Connect battery cables in a sequence from 1 to 24 as shown in the following figure.
1 2 3
4 5 6
7 8 9
10 11 12 13 14 15
16 17 18
19 20 21
22 23 24
Before installing the cable for connecting front and rear FCBs in
serial, do not remove PVC insulation tape or protective lids from
both ends of the cable.
–48 V RTN
Remove baffle plates.
Place FCBs onto the battery rack and reinstall baffle plates.
PVC
insulation
tape
PVC
insulation
tape
10
Installing DC Power Cables to the DC-powered Load
d
ma
jor
loa
d
min
or
loa
d
DC-powered load
Front view
Rear view Step 1: Install negative battery cables. Step 2: Install positive battery cables.
Install battery cables between negative battery terminals and the negative busbar in the ICC500-HA, and then install
battery cables between positive battery terminals and the positive busbar in the ICC500-HA.
–48 V RTN
L1
L2
L3
N
Installing AC Power Cable to the output of ATS
e
The following figure is for reference only.
Connect DC power cables to the circuit breakers for controlling major or minor loads based on site requirements.
ATS
11
2 Installing Cables
Switching Off All Circuit Breakers
a
Cord end terminal OT terminal Heat shrink tubing
COAX crimping tool Hydraulic pliers Heat gun
Prepare terminals as required before connecting cables.
Remove battery fuses by using a fuse extracting unit, and switch off the DC load circuit breaker in the DCDU and the AC
input and output circuit breakers in the ACDU.
OFF
DCDU
Installing Battery Cables
b
Rear view
Positive battery cable route
Route positive battery cables from the rear side of the cabinet to the front side through the left clearance in the equipment
compartment between the cabinet and the rack. See the following figure for reference.
Clearance for routing positive battery cables
OFF
OFF
ACDU
To the RTN busbar on the front side
Positive battery cables must be insulated
before being routed.
12
Install a communications cable for in-band communication.
The ECC500 can connect to a base transceiver station (BTS) for in-band communication. The BTS is required to be later
than GBSS12.0 and support in-band networking.
BBU
ECC500
Installing Communications Cables
f
13
ECC500(extension DI + basic IO + DG IO)+ATS+DG(DSE5110) diagram
DG remote start Mains failure DG1 operation
DSE 5110 ATS
ECC500
1 10
DI5 DI2
DG1_CTL
COM_NC
1
3
ATS:Move this
cable
from 4 to
3
1
Smoke Water
AC SPD
DC air conditioner
DG low fuel
Spare
DG2
operation
1:red/12V
2:green/signal
3:white/GND
ATS signal bar 43
2
3 4 5 6
8 7
14
3 Powering On and Commissioning the ICC500-HA
Checking Before Power-On
a
No. Check That
1 Cables to the cabinet are secured.
2 All cables are correctly connected.
Reinstall battery fuses by using a fuse extracting unit, and flip the DCDU maintenance button to BATON.
Check that the busbar voltage ranges from 44.5 V DC to 57.6 V DC by using a clamp meter.
Powering on FCBs
b
Remove the panel from the DCDU, and flip the DCDU maintenance button to Normal.
Check that the battery voltage ranges from 44.5 V DC to 57.6 V DC by using a clamp meter.
Reinstall the panel.
- V
Black
- V
Red
Black
Black
- V
Red
- V
- V
OFF Normal
OFF
BATON
Setting ECC500 Parameters on the LCD c
3. The data on the LCD is for reference only.
1. The default user name is admin, and the default password is 001.
2. The following table describes the buttons on the panel.
Button Name Description
▲ or ▼ Arrow key Allows you to view menu items and set the value of a menu item.
Cancel Returns to the previous menu without saving the settings of the current
menu item.
Enter Enters the main menu from the standby screen, enters a submenu from
the main menu, or changes or saves the settings of a submenu item.
Note:
After a menu is displayed, the standby screen is displayed and the LCD screen becomes dark if no button is
pressed for 5 minutes.
LCD
Method 1: Select ENGLISH when starting the ECC500.
Method 2: Set LUI Language to English after starting the ECC500.
Main Menu Second-Level Menu Third-Level Menu Fourth-Level Menu Value
Func Para Set Syst Para LUI Language - English
Set time, date, and time zone.
Set the display language.
Main Menu Second-Level Menu Third-Level Menu Fourth-Level Menu Value
Func Para Set Syst Para Set Date N/A Actual date
Set Time N/A Actual time
Set Time Zone - Actual time
zone
Site ID - Obtained from
the network
management
center (NMC)
15
16
Set D.G. and FCB parameters.
Main Menu Second-Level Menu Third-Level Menu Fourth-Level Menu Value
Device
Para Set
Site Summary Battery Type N/A FCB
EXTIO DI2 Cond Open/Close( Set based on
fuel sensor requirements)
DG 1-2 (non-
intelligent)
Rated Power N/A Set based on site
requirements
Set FCB and DG parameters.
Main Menu Second-Level Menu Third-Level Menu Fourth-Level Menu Value
Func Para
Set
Batteries Basic Para Rated Capacity 650
Charge Para Timed BC En Disable
Method 1: Select ENGLISH when starting the ECC500.
Method 2: Set LUI Language to English after starting the ECC500.
Main Menu Second-Level Menu Third-Level Menu Fourth-Level Menu Value
Func Para Set Syst Para LUI Language - English
Set time, date, and time zone.
Set the display language.
Main Menu Second-Level Menu Third-Level Menu Fourth-Level Menu Value
Func Para Set Syst Para Set Date N/A Actual date
Set Time N/A Actual time
Set Time Zone - Actual time
zone
Site ID - Obtained from
the network
management
center (NMC)
17
Main Menu Second-Level Menu
Third-Level Menu Fourth-Level Menu
Value Range and Option
DG Ctrl Para DG Start DOD - 40(Unit:%) 0 to 90
Batteries Rated Capacity 650(Unit:Ah) 0 to 5000
Charge Para BC Voltage 56.4(Unit:V) 42.0 to 58.0
FC Voltage 53.5(Unit:V) 42.0 to 58.0
Current Limit 0.3(Unit:C10) 0.05 to 0.25
Over Cur THR 0.35(Unit:C10) 0.15 to 0.50
Charge Para BC Voltage 56.4(Unit:V) 42.0 to 58.0
Disconnect Para BLVD Enabled Enable Enable/Disable
Syst Para LUI Language - - 中文/English
Set Date - - -
Set Time - - -
Set Time Zone - - -
Device Para Set Site Summary Control Mode - Auto Manual/Auto
Battery Type - FCB DCB-A/DCB-
B/SCB/FCB
DG Cfg Mode - Single DG/No DG As per actual
scenario
DG Control Mode - Cycle Mode Cycle
Mode/Traditional
Mode
Door Alm Level - Open Open/Close
Smoke Alm Level - Close Open/Close
Water Alm Level - Close Open/Close
GPRS DI1 Cond - Close Open/Close
GPRS DI2 Cond - Close Open/Close
GPRS DI3 Cond - Close Open/Close
GPRS DI4 Cond - Close Open/Close
GPRS DI5 Cond - Close Open/Close
DG 1 to 2 Rated Volt Ph-N - 230(Unit:V) 80 to 500
Rated Power - 16(Unit:kw) 2 to 5000
Set communications parameters.
14
Flipping the DCDU Maintenance Button to Normal e
OFF
Connecting the Mains Supply d
DCDU
Switch on the AC input and output circuit breakers on the ACDU. Check that the AC input voltage of the ACDU is between 85 V
AC and 290 V AC, and that the DCDU busbar voltage is between 44.5 V DC and 57.6 V DC.
ACDU
Powering On Loads f
ma
jor
loa
d
min
or
loa
d
DC-powered load
Switch on a circuit breaker and measure the busbar voltage by using a clamp meter. If the busbar voltage is between 44.5
V DC and 57.6 V DC, switch on another circuit breaker. Perform such operations until all circuit breakers are switched on.
Verify that the voltage and current of the mains, loads, and FCBs are displayed on the ECC500 standby screen, and all
alarm indicators are off. If any alarm indicator is on, rectify the fault by referring to the PowerCube 1000 V300R002C00
Engineer Manual.
~ V
Red
Black
~ V
Red Black
- V
If no exception occurs after the ICC runs for 5 minutes, the commissioning is complete. Then block the cable holes by using
fireproof mud and close and lock the cabinet door, and hand the keys over to the person in charge.
- V
Normal
18
19
Scenario 1: out-of-band communication (over the GPRS)
Main Menu Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Value
Func Para
Set
Comm Para NetWork Para Network Mode GPRS
APN Name Set based on site requirements
APN Number Obtained from the survey table
User Password Obtained from the survey table
User Password User name for accessing the GPRS
network (specified if the APN is used or
left blank if the APN is not used)
Active NMS IP Password for accessing the GPRS
network (specified if the APN is used or
left blank if the APN is not used)
Server Para Backup NMS IP Obtained from the NMC
Network Mode Obtained from the NMC
Set communications parameters.
Scenario 2: out-of-band communication (over the Ethernet)
Main Menu Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Value
Func Para Set Comm Para NetWork Para Network Mode IP
IP Address Set according to the network plan
Subnet Mask Set according to the network plan
Default GW Set according to the network plan
Server Para Active NMS IP Obtained from the NMC
Backup NMS IP Obtained from the NMC
Scenario 3: in-band communication
Main Menu Second-Level Menu
Third-Level Menu Fourth-Level
Menu
Value
Func Para Set Comm Para Host Para Host Addr 27