PowerCube 1000 V300R003C00

Solution Description

Issue 02

Date 2013-05-02

HUAWEI TECHNOLOGIES CO., LTD.

Page 2: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

i

Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved.

No part of this document may be reproduced or transmitted in any form or by any means without

prior written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

All other trademarks and trade names mentioned in this document are the property of their respective

holders.

Notice

The purchased products, services and features are stipulated by the contract made between Huawei and

the customer. All or part of the products, services and features described in this document may not

be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all

statements, information, and recommendations in this document are provided "AS IS" without warranties,

guarantees or representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the

preparation of this document to ensure accuracy of the contents, but all statements, information, and

recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.

Address: Huawei Industrial Base

Bantian, Longgang

Shenzhen 518129

People's Republic of China

Website: http://www.huawei.com

Email: [email protected]

Page 3: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description About This Document

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

ii

About This Document

Purpose

The PowerCube 1000 V300R003C00 (PowerCube 1000 for short) is a competitive solution

that integrates the mains, diesel generators, Solar Power System, and storage batteries.

This document describes PowerCube 1000 in terms of its functions, features, architecture,

application scenarios, configurations, model number description, and components.

Intended Audience

This document is intended for:

System engineers

Network planning engineers

Site engineers

Sales engineers

Symbol Conventions

The symbols that may be found in this document are defined as follows.

Symbol Description

Alerts you to a high risk hazard that could, if not avoided,

result in serious injury or death.

Alerts you to a medium or low risk hazard that could, if not

avoided, result in moderate or minor injury.

Alerts you to a potentially hazardous situation that could, if not

avoided, result in equipment damage, data loss, performance

deterioration, or unanticipated results.

Provides a tip that may help you solve a problem or save time.

Provides additional information to emphasize or supplement

important points in the main text.

Page 4: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description About This Document

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

iii

Change History

Changes between document issues are cumulative. The latest document issue contains all the

changes made in earlier issues.

Issue 02 (2013-05-02)

Update the security cordon and the appearance of ECC500.

Issue 01 (2012-09-14)

This issue is the first official release.

Page 5: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description Contents

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

iv

Contents

About This Document .................................................................................................................... ii

1 PowerCube 1000 Overview ......................................................................................................... 1

1.1 Context ............................................................................................................................................................. 1

1.2 Positioning ....................................................................................................................................................... 1

1.3 Benefits ............................................................................................................................................................ 1

2 Functions and Features ................................................................................................................ 3

3 Application Scenarios and Product Series ............................................................................... 4

3.1 Application Scenarios ....................................................................................................................................... 4

3.2 Product Series................................................................................................................................................... 4

4 Architecture .................................................................................................................................... 6

4.1 Introduction ...................................................................................................................................................... 6

4.2 EPS ................................................................................................................................................................... 7

4.3 ICC ................................................................................................................................................................... 7

4.4 ESS ................................................................................................................................................................... 8

4.5 Cabinet System ................................................................................................................................................. 8

4.6 Network Monitoring and Management System................................................................................................ 9

5 Model Number Description ...................................................................................................... 11

6 Component Description ............................................................................................................. 12

6.1 Cabinet System ............................................................................................................................................... 12

6.2 ICC Components ............................................................................................................................................ 13

6.2.1 IDU ....................................................................................................................................................... 13

6.2.2 ECC500 ................................................................................................................................................. 17

6.2.3 S4850G1 ............................................................................................................................................... 18

6.2.4 R4850N3 ............................................................................................................................................... 18

6.2.5 ATS Main Control Box ......................................................................................................................... 19

6.2.6 BCU-1203A .......................................................................................................................................... 21

6.2.7 BC1203 ................................................................................................................................................. 22

6.2.8 DJN1000-S ............................................................................................................................................ 23

6.3 EPS ................................................................................................................................................................. 24

6.3.1 D.G. ....................................................................................................................................................... 24

Page 6: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description Contents

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

v

6.3.2 PV Module ............................................................................................................................................ 24

6.3.3 PV Module Support .............................................................................................................................. 25

6.3.4 SJB ........................................................................................................................................................ 25

6.4 ESS ................................................................................................................................................................. 26

A Glossary ....................................................................................................................................... 27

B Acronyms and Abbreviations .................................................................................................. 28

Page 7: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 1 PowerCube 1000 Overview

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

1

1 PowerCube 1000 Overview

1.1 Context

Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian

market. The PowerCube 1000 is a competitive solution that integrates the mains, diesel

generators, Solar Power System, and storage batteries. This solution solves the problems of

low D.G. load power, high fuel consumption, heavy D.G. maintenance workload, and

component theft. It uses multiple energy sources and supports rapid development, power

supply monitoring, and remote intelligent management.

1.2 Positioning

The PowerCube 1000 is used in the areas with Class 3 electrical grids and is applicable to the

scenarios of mains absence, low mains quality, and mains unsteadiness.

NOTE Mains absence: The outage duration is 24 hours per day.

Mains unsteadiness: The outage duration is less than 12 hours per day.

Low mains quality: The outage duration is greater than or equal to 12 hours per day.

1.3 Benefits

The PowerCube 1000 has the following benefits:

Cost Reduction High integration

− By integrating components into a PowerCube, the floor area is reduced by 60% to

80%.

Intelligent power combination

− D.G.-mains-battery hybrid power system minimizes the use of fuel by scheduling

energy intelligently.

Page 8: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 1 PowerCube 1000 Overview

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

2

Standardization Standard platform

− Controller platforms such as the energy control center (ECC) and solar supply unit

(SSU)

− Standard element management system, namely, the Network Ecosystem (NetEco)

(Note:HTTP is not a secure protocol)

Flexible combination

− The total cost of ownership (TCO) is minimized by combining the D.G., Solar Power

System, and storage batteries flexibly. The D.G. Power System can be used as the

active power source based on site requirements.

− Smooth capacity expansion and evolution are supported.

Intelligent Management Power network management

− Uses the NetEco to recognize energy equipment, collects data about energy

equipment, and creates lists on which equipment and data are displayed.

− Records equipment running information and prompts for routine maintenance.

− Ensures electrical safety and security by using a theft prevention design and alarm

generation function for fuel and solar energy.

− Allows equipment of multiple customers to share electricity.

Page 9: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 2 Functions and Features

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

3

2 Functions and Features

Table 2-1 describes the PowerCube 1000 functions and features.

Table 2-1 PowerCube 1000 functions and features

Function or Feature Description

Standard and

scenario-dedicated

solution

Three scenarios: mains absence, low mains quality, and mains

unsteadiness

Propositional solutions:

Combination of the D.G., mains, storage batteries, and PV

modules (PV modules being the active power source)

Reuse Supports reused local diesel generators.

High integration and

rapid installation

Allows module fast deploy, and the module with high density

and efficiency, reducing the equipment volume and floor area.

Site load sharing and

electricity selling

Allows four operator to share the PowerCube 1000, allows

amount of electricity to be remotely recorded.

Value added features Provides value added features such as service management,

asset management, operation and maintenance management,

recording of amount and fee of electricity, fuel theft

prevention design.

NOTE

Site load sharing: several client share the site matched equipment which include the tower and power

system, and billing respectively.

Page 10: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 3 Application Scenarios and Product Series

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

4

3 Application Scenarios and Product Series

3.1 Application Scenarios

The PowerCube 1000 used in the areas with Class 4 electrical grids. The sites can be without

mains, with unsteady mains, and with low mains quality.

Table 3-1 describes the scenarios that the PowerCube1000 applies to.

Table 3-1 Scenario description

Scenario Feature Active Power

Solution Type Networking Mode

No mains D.G. D.G.-mains-battery

power system

D.G.+ ESS

Solar energy Solar-D.G.-battery

hybrid power system

PV+D.G.+ ESS

Low mains quality Solar energy Solar-D.G.-Mains-bat

tery hybrid power

system

Mains+PV+D.G.+ ESS

Mains unsteadiness

3.2 Product Series

Table 3-2 describes the solution product series configurations for modernized sites.

Table 3-2 Solution configurations for sites

Page 11: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 3 Application Scenarios and Product Series

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

5

Product Series Description

Configurations Principia Max Power(W) List

SBOM Description

Product Series

EPS ICC ESS

1 S531D-D0 V33 S

PV Module

235W*9PCS,Ma

ins, Reused DG

ICC510(direct-

cooling),

PSU*3,SSU*1

ESS

400AH(d

irect-

cooling)

1250W

2 S532D-D0 V33 S

PV Module

235W

*9PCS,Mains,

Reused DG

ICC510(direct-

cooling),

PSU*6,SSU*1

ESS

600AH(d

irect-

cooling)

1550W

3 S552D-D0 V33 S

PV Module

235W

*18PCS,Mains,

Reused DG

ICC510(direct-

cooling),

PSU*6,SSU*2

ESS

600AH(d

irect-

cooling)

1850W

4 S552D1-D0 V33 S

PV Module

235W

*18PCS,Mains,

Reused DG

ICC510(direct-

cooling),

PSU*6,SSU*2

ESS

800AH(d

irect-

cooling)

2350W

5 D501D V33 D Reused DG,Main

s

ICC510(direct-

cooling),

PSU*3

ESS

400AH(d

irect-

cooling)

1250W

6 D502D V33 D Reused DG,

mains

ICC510(direct-

cooling)

PSU*6

ESS

600AH(d

irect-

cooling)

1850W

7 D502D1V33 D Reused DG,

mains

ICC510(direct-

cooling)

PSU*6

ESS

800AH(d

irect-

cooling)

2350W

Page 12: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 4 Architecture

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

6

4 Architecture

4.1 Introduction

The PowerCube consists of the following systems by function: Integrated Controller and

Converter (ICC), energy storage system (ESS), energy plant system (EPS), cabinet system,

and network monitoring and management system. Figure 4-1 shows the network diagram of

the systems.

Figure 4-1 Network diagram

Page 13: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 4 Architecture

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

7

4.2 EPS

The EPS supplies power to the ICC for power conversion and distribution.

Table 4-1 describes EPS component functions.

Table 4-1 EPS component functions

Subsystem Component Function

D.G. system Supplies alternating current (AC) power by

converting chemical energy into electric energy.

Photovoltaic

(PV) system PV module Converts solar energy into electric energy.

PV module support Supports PV modules and uses a theft prevention

design.

SJB Allows PV arrays to be connected in parallel and

supplies solar power to the ICC.

4.3 ICC

The ICC, as the core of the PowerCube 1000, schedules energy logically, monitors running

status of other systems, and reports information to the NetEco.

Table 4-2 describes ICC component functions.

Table 4-2 ICC component functions

Component Function

Integrated

distributio

n unit

(IDU)

ECC ECC function:

Schedules energy.

Provides a liquid crystal display (LCD) screen to query system

information and set system control parameters.

Implements remote management in out-of-band mode.

Provides ports for connecting signal cables.

Provides scheduling logic for the hybrid power system.

Distribut

ion unit

Input and output distribution function:

Provides input ports for PV modules.

Provides ports for direct current (DC) power distribution.

Provides ports for AC power distribution.

ATS Switches between AC power sources.

SSU Regulates the voltage of PV modules with MPPT technology.

PSU Converts AC input into –48 V DC output.

Page 14: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 4 Architecture

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

8

Component Function

BCU Converts –48 V DC input into 12 V DC output to charge the D.G.

storage battery.

Inverter (optional) Converts DC input into AC output.

4.4 ESS

The energy storage system (ESS) stores backup power and works as a power source in the

PowerCube 1000.

Table 4-3 describes ESS component functions.

Table 4-3 ESS component functions

Component Function

Storage battery Stores energy and converts between electric energy

and chemical energy alternately.

4.5 Cabinet System

The cabinet houses and protects the ICC, and ESS, and ensures that they work at an

appropriate temperature.

Table 4-4 describes cabinet configurations.

Table 4-4 Cabinet configurations

Cabinet of the ICC

Temperature Control Mode for the Energy Control Cabin

ESS Temperature Control Mode

Supported Storage Battery

Supported Energy Control Subrack

ICC510-D

D2

Natural-ventilat

ion unit

Natural-ventilat

ion unit

one batteries

strings

IDU-300E1

IDU-300D1

Page 15: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 4 Architecture

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

9

4.6 Network Monitoring and Management System

Network Diagrams

The network monitoring and management system is a logical system that consists of the EPS,

ESS, ICC, cabinet, and a NetEco. The NetEco provides the site status and data and allows you

to remotely control sites.

Figure 4-2 Network monitoring and management system

Principle of Electricity to be Remotely Recorded

Figure 4-3 shows the principle of electricity to be remotely recorded. The user get user’s

power data by NetEco.

Page 16: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 4 Architecture

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

10

Figure 4-3 Principle of Electricity to be Remotely Recorded

Page 17: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 5 Model Number Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

11

5 Model Number Description

Table 5-1 describes the models of the subsystems and major components of the PowerCube

1000.

Table 5-1 Models of the subsystems and major components

Subsystem or Component Acronyms Model

Integrated Controller and

Converter

ICC ICC510-DD2

Integrated Distribution Unit IDU IDU-300E1

IDU-300D1

Energy Plant System EPS N/A

Energy Storage System ESS N/A

Energy control center ECC ECC500

Solar Supply Unit SSU S4850G1

Power Supply Unit PSU R4850N3

Storage battery N/A N/A

Battery Charger Unit BCU BCU-1203A

Solar Junction Box SJB N/A

Inverter N/A DJN1000-S

Page 18: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

12

6 Component Description

6.1 Cabinet System

An ICC510 series cabinet consists of an ESS and energy control cabin. Table 6-1 lists the

technical specifications of an ICC510 series cabinet.

Table 6-1 Technical specifications of an ICC510 series cabinet

Item Description

Dimensions (H x W x D) 2100 mm x 1800 mm x 750 mm

Color Gray

Installation Installed on a floor

Cable routing Routed from the bottom

Maintenance Maintained from the front

TCU ICC510-DD2: natural-ventilation unit (both in the ESS and

energy control cabin)

Protection level ICC cabin: IP55

ESS cabin: IP45

Figure 6-1 show an ICC510 series cabinet.

Page 19: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

13

Figure 6-1 ICC510 series cabinet exterior

Figure 6-2 ICC510 cabinet with equipment interior view

6.2 ICC Components

6.2.1 IDU

Appearance

An IDU-300E1 integrates the functions of the ACDU, DCDU, ATS, and PVDU (optional) and

reserves space for the ECC500, SSU, PSU. Figure 6-3 shows an IDU-300E1.

Page 20: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

14

Figure 6-3 IDU-300E1

(1) DC load output circuit

breakers (2) D.G. AC input circuit

breakers (3) ECC500

(4) SSU (5) PSU (6) Battery charger unit (BCU)

(7) ATS main control box (8) Mains AC input circuit

breakers (9) PV input circuit breakers

(10) Battery fuses (11) RTN+

Page 21: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

15

Figure 6-4 IDU-300D1

(1) DC load output circuit

breakers (2) D.G. AC input circuit

breakers (3) ECC500

(4) BC1203 (5) PSU (6) ATS main control box

(7) Mains AC input circuit

breakers (8) Battery fuses (9) RTN+

Functions

Table 6-2 describes IDU functions.

Table 6-2 IDU functions

Function Description

AC automatic

transfer

Switches between the D.G. and the mains by using the controller and

detects inputs from the two power sources.

Multiple energy

input

Supports inputs from the D.G, mains, and solar energy and other

power inputs such as the reused DC power supply.

Communication,

control, and alarm

reporting

Performs functions of communication and alarm reporting, supports

remote management and online upgrade, monitors and controls the

operating status of the power system, and reports fault alarms in a

timely manner (over the ECC500).

–48 V DC power

supply

Is configured with hot-swap PUS to perform AC/DC conversion.

Is configured with hot-swap SSUs to perform DC/DC conversion.

Provides multiple DC outputs with powering off functions to

power Huawei base stations and transmission equipment.

Page 22: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

16

Function Description

Protection Provides overvoltage, undervoltage, and open-phase protection

for the D.G. and mains supply.

Integrates a surge protection unit to provide reliable protection for

the AC/DC power port, monitoring alarm ports and

communications port.

Alarm generation Generates alarms for mains open phase and D.G. open phase.

Maintenance Allows all external ports and connected cables to be maintained from

the front of the IDU.

Electrical label

function

Indicates the ECC500, PSU, SSU, power distribution port board, and

ATS main control box.

Battery

management

Manages storage batteries effectively to ensure their proper operation

(over the PMU).

Technical Specifications

Table 6-3 IDU Technical Specifications description

Component Description

IDU-300D1 IDU-300E1

Application

Scenarios

D.G.+storage battery Mains+D.G.+storage battery

Solar+D.G.+storage battery

PSU R4850N3 with a rated output of 50 A

SSU None S4850G1 with a rated output of 50

A

SSU subrack None 1 U high (optional, space reserved)

Monitoring

module

ECC500+monitoring unit of the ATU+interface board of the DCDU

Monitoring

module subrack

2 U high

AC power

distribution

2 input ways: One 3-pole 63 A input circuit breakers and one input

terminals (UT16 terminals) (D.G.+mains)

DC power

distribution

Two 160 A battery fuses Two 160 A battery fuses

Can supply total 16 circuit

breaker with 8 users, per user

circuit breaker is:

Major loads: 32A/1P x 1

Minor loads: 80A/1P x 2+32A/1P

x 1

Can supply total 8 circuit

breaker with 2 users, per user

circuit breaker is:

Major loads: 32A/1P x 1

Minor loads: 80A/1P x 2+32A/1P

x 1

Page 23: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

17

Component Description

IDU-300D1 IDU-300E1

Common load: 16A/1P x 2 +

32A/1P x 1

Common load: 16A/1P x 2 +

32A/1P x 1

PV power

distribution

(optional)

None Standard configure is: 63A/1P x

1+UT16 x 1

Can spread to 4 input ways.

Battery switch Used for connecting battery contactors manually.

6.2.2 ECC500

Appearance

Figure 6-5 shows an ECC500.

Figure 6-5 ECC500

(1) Main control module (2) Extension DO module (3) GPRS module

(4) Extension IO module (5) D.G. IO module (6) Basic IO module

Functions

The ECC500 schedules energy. The main control module monitors other PowerCube

components by working with the basic I/O module, GPRS module, and D.G. control module.

Features

The ECC500 has the following features:

Performs comprehensive power management, battery management, and intelligent

control device management locally or remotely. For example, it can communicate with

power supply units (PSUs) over RS485 or CAN ports, communicate with a host over an

RS485 or RS232 port, and monitor equipment remotely over a 10/100M autonegotation

Ethernet port.

Reports the data collected by the water sensor, smoke sensor, door status sensor, ambient

temperature and humidity sensor, battery temperature sensor over reserved analog

parameter ports and dry contacts.

Monitors power distribution and reports alarms.

Displays the AC status and DC status of the power system as well as the operating

parameters, operating status, alarm information, preset parameters, and control

Page 24: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

18

parameters of modules and storage batteries on the liquid crystal display (LCD) in real

time.

6.2.3 S4850G1

Appearance

The S4850G1 panel provides a Run indicator, a Protection indicator, and a Fault indicator.

Figure 6-6 shows an S4850G1.

Figure 6-6 S4850G1

Functions

The S4850G1 is a DC-DC converter that uses maximum power point track (MPPT)

technology. It tracks the highest solar power point based on the output features of PV modules

to maximize the use of solar energy.

Technical Specifications

The S4850G1 has the following features:

Is 1 U high, 2.5 U wide, fan-cooled, and hot-swappable.

Works at –20°C to +75°C (power derated above 55°C).

Maximum input power: 3100 W.

Output voltage: 43.2–58 V DC.

Rated voltage: 53.5 V DC.

Maximum output power: 3000 W.

Is protected against input reverse connection.

6.2.4 R4850N3

Appearance

The R4850N3 is 2 U high. Figure 6-7 shows an R4850N3.

Page 25: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

19

Figure 6-7 R4850N3

Functions

R4850N3 convert AC power into –48 V DC power.

Features

R4850N3 have the following features:

Work at high efficiency and run stably.

Are hot-swappable.

Are protected against input overvoltage, input undervoltage, input overcurrent, output

overvoltage, output short circuit, output current limiting, and overtemperature.

6.2.5 ATS Main Control Box

Figure 6-8 shows an ATS main control box.

Figure 6-8 ATS main control box

(1) COM_IN port (2) COM_OUT port (3) RS232 port

(4) Indicators (5) ATS no-AC output (6) Dry contact outputs for

monitoring the D.G. status

(7) Dry contact output for ATS

alarms

(8) Dry contact output for mains

failures

(9) Dry contact output for D.G.

1 start/stop control

(10) Dry contact output for D.G.

2 start/stop control

Table 6-4 describes indicators on the ATS main control box.

Page 26: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

20

Table 6-4 ATS Indicators on the ATS main control box

Indicator Color Status Meaning

RUN Green Blinking at 4 Hz (on for 0.125s

and then off for 0.125s)

The communication is

faulty.

Blinking at 0.5 Hz (on for 1s and

then off for 1s) The ATS runs properly.

ALM Red Steady on A fault occurs.

Steady off A fault is rectified.

DG1 Green Steady on D.G. supplies power.

Steady off D.G. supplies no power.

MAIN

(DG2)

Green Steady on The mains supplies power.

Steady off The mains is unavailable,

supplies no power.

BYPASS Green Steady on The transfer switch is

BYPASS.

Steady off The transfer switch is

AUTO.

Table 6-5 describes the communications ports on the ATS main control box.

Table 6-5 Communications ports on the ATS main control box

Port Definition Function

COM_IN Active and standby protocol ports.

COM_IN and COM_OUT ports are

cascaded internally.

Communicates with the energy

control center (ECC) components. COM_OUT

RS232 COM port Communicates with a PC for

maintenance and local upgrade.

Table 6-6 describes dry contacts on the ATS main control box.

Table 6-6 Dry contacts on the ATS main control box

Dry contact Definition Default Status

Remarks

NO1/COM1/NC1 Controls D.G. 1 startup

and shutdown.

Normally

open (NO)

or normally

closed (NC)

The default status is NC.

NO2/COM2/NC2 Controls D.G. 2 startup

and shutdown

Page 27: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

21

Dry contact Definition Default Status

Remarks

AMF Reports mains failure

alarms.

NC If the dry contact is NO,

no mains failure alarm

is generated.

If the dry contact is NC,

an mains failure alarm

is generated.

DG_Run Monitors the diesel

generator (D.G). status.

NO If the dry contact is NO,

no D.G. is running.

If the dry contact is NC,

the D.G. is running.

ALM Reports ATS fault

alarms.

NO If the dry contact is NO,

no alarm is generated.

If the dry contact is NC,

an alarm is generated.

AC_FAULT Monitors the AC power

supply

NO If the dry contact is NO,

the ATS has no AC

input.

If the dry contact is NC,

the ATS has AC input.

6.2.6 BCU-1203A

Appearance

A BCU-1203A is installed in the IDU subrack. Figure 6-9 shows a BCU-1203A.

Figure 6-9 BCU-1203A

Functions

A BCU-1203A converts –48 V DC to +12 V DC to charge the D.G. storage battery.

Page 28: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

22

Features Provides two outputs with typical power being 81 W.

Is protected against input overvoltage.

Is protected against output current limiting.

Is protected against output short circuits.

Is protected against output reverse connection.

Is protected against overtemperature.

Is isolated from the power supply network if it is faulty.

Indicates alarms by indicators.

Communicates with the backplane over a CAN bus or Huawei master/slave protocol,

reports electrical labels, protection information, and fault information, and supports

remote upgrade.

6.2.7 BC1203

Appearance

Figure 6-10 shows a BC1203.

Figure 6-10 BC1203

Functions

The BC1203 is installed in the DCDU and converts –48 V DC to +12 V DC to charge the D.G.

storage battery.

Features

The BC1203 has the following features:

Provides two outputs with typical power being 81 W.

Is protected against input overvoltage, output current limiting, output short circuit,

reverse output connection, and overtemperature.

Is isolated from the power supply network if it is faulty.

Indicates alarms by indicators.

Communicates with the backplane over a CAN bus or Huawei master/slave protocol,

reports electrical labels, protection information, and fault information, and supports

remote upgrade.

Page 29: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

23

6.2.8 DJN1000-S

Appearance

Figure 6-11 shows a DJN1000-S.

Figure 6-11 DJN1000-S

(1) DC input port (2) Switch (3) Air exhaust vents

(4) SPD (5) All-purpose output socket (6) Indicator

(7) Dry contact (8) AC input and output terminal

Functions

The DJN1000-S converts DC input into AC output.

Technical Specifications

DJN1000-S technical specifications

Item Specifications

Rated capacity 1000 VA/700 W

AC input Rated voltage 230 V AC

Rated frequency 45–55 Hz

DC input Rated voltage 48 V DC

Rated voltage 20 A

AC output Output voltage 220 V AC (tolerance: ±3%)

Output frequency 50 Hz (tolerance: ±1%)

Output mode One AC output wiring terminal and one all-purpose

socket

Dimensions (H x W x D) 43.5 mm x 440 mm x 286 mm

Page 30: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

24

6.3 EPS

6.3.1 D.G.

The PowerCube 1000 used reused D.G..

6.3.2 PV Module

Appearance

Figure 6-12 shows a PV module.

Figure 6-12 PV module

Functions

A PV module, as an important component for light-to-electricity conversion in the Solar

Power System, supplies power to loads. It is resistant to corrosion, wind, and rain. PV

modules are connected in series or parallel to meet load voltage and current requirements.

Features

A PV module has the following features:

Good light transmission.

Double-layer solar cell, with high circuit reliability.

Long service life (25 years).

Multi-layer polyolefin compressed circuit, which is moisture-proof, well-insulated

and works stably under undervoltage conditions.

Certified by the TUV, Underwriters Laboratory (UL), International Organization for

Standardization (ISO), CE, and International Electrotechnical Commission (IEC).

Page 31: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

25

6.3.3 PV Module Support

Appearance

A PV module holds one or more PV modules in position. PV module supports are classified

into standard supports, scalable low supports, and scalable high supports. Their appearance is

shown in Table 6-7.

Table 6-7 PV module support appearance and features

Support Type

Appearance Feature

PV module

support

It supports Huawei PV modules and

SJBs.

Three PV modules form one basic

unit.

The PV modules installed on the

support all have a 25-degree

angle with the floor. The angle

cannot be adjusted.

Customer equipment can be installed

under the PV modules. The upper

edge of the PV modules is 3300 mm

above the floor, and the lower edge is

2000 m above the floor.

6.3.4 SJB

Appearance

Figure 6-13 shows an SJB.

Figure 6-13 SJB

Page 32: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description 6 Component Description

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

26

Functions

An SJB allows outdoor PV arrays to be connected in parallel and provides surge protection

for PV modules. It consists of input and output wiring terminals, a protection device for PV

module inputs and outputs, an SPD, and a ground bar. To decrease cable voltage drop and

facilitate installation, multiple SJBs can be used based on site requirements.

6.4 ESS

Appearance

Figure 6-14 shows a storage unit.

Figure 6-14 Storage unit

Features

A storage battery has the following features:

Supports fast charging and helps to maximize the use of mains and minimize the use

of D.G.

Is well designed to withstand high temperatures.

Technical Specifications Can be charged and discharged 1600 times at 27ºC when the DOD is 60%.

Discharging temperature: –20°C to +55°C

Charging temperature: –20°C to +55°C

Maximum charge current: 0.3C

Capacity of a single unit string: 400 Ah, and 600 Ah

Page 33: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description A Glossary

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

27

A Glossary

L

low mains quality Pertaining to the outage duration greater than 12 hours per day.

M

mains absence Pertaining to the outage duration 24 hours per day.

mains unsteadiness Pertaining to the outage duration less than 12 hours per day.

N

new site A site where all equipment is provided by Huawei.

Page 34: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description B Acronyms and Abbreviations

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

28

B Acronyms and Abbreviations

A

AC alternating current

ACDU alternating current distribution unit

ATS AC transfer switch

B

BC battery charger

C

CAPEX capital expenditure

D

DC direct current

DCDB direct current distribute box

DCDU direct current distribute unit

DOD depth of discharger

DTS direct current transfer switch

D.G. diesel generator

E

ECC energy control center

EPS energy plant system

ESS energy storage system

Page 35: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description B Acronyms and Abbreviations

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

29

G

GPRS general packet radio service

I

ICC Integrated Controller and Converter

IDU Integrated Distribution Unit

L

LLVD load low voltage disconnection

M

MPPT maximum power point track

N

NetEco Network Ecosystem

O

OPEX operating expense

P

PSU power supply unit

PV photovoltaic

PVDU photovoltaic distribution unit

S

SOH state of health

SPD surge protection device

SSU solar supply unit

T

TCO total cost of ownership

V

Page 36: PowerCube 1000 V300R003C00 Solution Description - huawei… · Huawei launches PowerCube 1000 V300R003C00 (PowerCube 1000 for short) for the Indian ... The EPS supplies power to the

PowerCube 1000

Solution Description B Acronyms and Abbreviations

Issue 02 (2013-05-02) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

30

VRLA valve regulated lead acid

W

WEEE waste electrical and electronic equipment