35

Power System in Vsp NEW

  • Upload
    pruddvi

  • View
    48

  • Download
    1

Embed Size (px)

DESCRIPTION

ppt vizag stel

Citation preview

Power system in vsp

POWER REQUIREMENTAverage Load : 240 MW / 266 MVAPeak Load : 275 MW / 305 MVA

SOURCES OF POWERCAPTIVE POWER PLANT

STATE ELECTRICITY GRID

DIESEL GENERATORS

VISAKHAPATNAM STEEL PLANT CAPTIVE POWER GENERATION

Thermal Power : 3x60 + 1x67.5MWBackpressure Turbine Gen 2x7.5MWGas Expn. Turbine Gen 2x12 MWTotal Gen. Capacity: 286.5 MW

DISTRIBUTION NETWORK(DNW)Its role is to supply reliable & quality power to all the sections in the plant

ACTIVITIES TAKEN BY THIS DEPARTMENT:

Operate, Inspect & Maintain EHT & HT Equipment of MRS, LBSS1, LBSS2, LBSS3, LBSS 4 & CPRS.Maintain all HT Power Distribution Equipment of other Sub Stations.Analyze the Breakdowns and take necessary Corrective & Preventive steps to avoid recurrence. Monitor Specific Energy Consumption of Major Shops.

SECTIONS OF DNWMain receiving station (MRS)Load block step-down substation-1 (LBSS-1)Load block step-down substation-2 (LBSS-2)Load block step-down substation-3 (LBSS-3)Load block step-down substation-4 (LBSS-4)Load block step-down substation-6 (LBSS-6)Load block step-down substation-7 (LBSS-7)

POWER REQUIRMENT OF INDIVIDUAL SHOPS

CAPTIVE GENERATION in MW

220 kV TRANSMISSION LINES IN VSPMRSLBSS 3LBSS 4LBSS 2LBSS 1LBSS 58.3 KM1.6 KM2.1 KM3.4 KM1.1 KM70 MW50 MW10 MW50 MW70 MW

MAIN RECEIVING STATION This is a 220kV substation which receives power from VSP SS of APTRANSCO and Captive Power Plant, TPP.

From here the power is distributed to various load block step down substations such as LBSS-2, LBSS-3, LBSS-4 and LBSS-6. Also supply power to township through CPRS (Construction Power Receiving Station) by stepping down from 220kV to 33kV and then 33kV to 11kV and further to 415V

Load Block Step down Substation 1(LBSS-1)a set of 220KV double circuit lines have been taken to LBSS-1 from LBSS-5

Three 80MVA 220kV 3-winding power transformers

The voltage is stepped down to 11kV and 6.6 kV The transformers are selected if one is failed other two will meet the loadAvg load 55-60 Mw

Load Block Step down Substation 2(LBSS-2)This 220kv substation step down voltage to 33kV,11kVand 6.6kV level four Transformers: 3 Transformers 220/11/6.6kV 80MVA star/delta/delta 4th Transformer 220/33 kV 31.5MVA star/star used for ladder furnace in SMS Avg load 70-80MW

Load Block Step down Substation 3(LBSS-3)This 220kv substation step down voltage to 33kV,11kVand 6.6kV level3 Transformers 220/11/11kV 80MVA star/delta/delta Avg load : 10MW

Load Block Step down Substation 4(LBSS-4)This 220kv substation step down voltage to 33kV,11kVand 6.6kV level3 Transformers 220/11/11kV 80MVA star/delta/delta Avg load : 40MW

Load Block Step up Substation 5(LBSS-5)The LBSS-5 receives the power at 11 KV level from TPP and is further steps up to 220 kV.5 transformers in LBSS-5: 4 two winding transformers 11/220 kV star/delta 5th is 3 winding transformer of 11/11/220 kV star/delta/delta. under the control of TPP but maintained by DNW.

Load Block Step down Substation 6(LBSS-6)It receives power from Main Receiving Station (MRS) through two 220 kV transmission lines3 transformers of rating 220 kV /11/11 kV star/delta/delta with a capacity of 63 MVAAnother 3 transformers of rating 220 kV /33 kV with a capacity of 110 MVA

Load Block Step down Substation 7(LBSS-7)It receives power from LBSS-6 through 11 kV cables and GSB-4. It consists of four transformers of rating 33 kV /11 kV with a capacity of 40 MVA. The main loads that are connected to it are BF3, SMS-2, Mills pump house etc.

Load Block Distribution Substation(LBDS)Electric power at 11/6.6 KV stepped down at above LBSS stations is distributed to smaller Load Block Distribution Station (LBDS) located in each unit. 11 KV motors (above 200 kW rating generally) are connected to LBDS. In LBDS, transformers which convert power form 11 KV to 415 V and distributed to low tension loads.

HIGH VOLTAGE DISTRIBUTIONTwo 220/33 kV Transformers installed at MRS feed power to Township step down station (called as CPRS) through 33 kV cablesHere the voltage is further stepped down to 11 KV by two nos. of 33/11 kV transformers11 KV overhead construction power lines to township network6.6 KV supply is mostly used for motors (of rating >200 and