Phan Anh Bien AP Transformers

Embed Size (px)

Citation preview

  • 7/31/2019 Phan Anh Bien AP Transformers

    1/29

    TRANSFORMERS

    Transformers are key elements in power systems. In order to

    effectively transmit power over long distances without prohibitive line

    losses, the voltage from the generator (a maximum of output voltage ofapproximately 25-30 kV) must be increased to a significantly higher level

    (from approximately 150 kV up to 750 kV). Transformers must also be

    utilized on the distribution end of the line to step the voltage down (in

    stages) to the voltage levels required by the consumer.

    Transformers also have a very wide range of applications outside the

    power area. Transformers are essential components in the design of DC

    power supplies. They can provide DC isolation between two parts of a

    circuit. Transformers can be used for impedance matching between sourcesand loads or sources and transmission lines. They can also be used to

    physically insulate one circuit from another for safety.

    Fundamentally, the transformer consists of two or more windings that

    are magnetically coupled using a ferromagnetic core. For a two-winding

    transformer, the winding connected to the AC supply is typically referred

    to as theprimary while the winding connected to the load is referred to as

    thesecondary. A time-varying current passing through the primary coil

    produces a time-varying magnetic flux density within the core. According

    to Faradays law, the time-changing flux passing through the secondary

    induces a voltage in the secondary terminals.

  • 7/31/2019 Phan Anh Bien AP Transformers

    2/29

    IDEAL TRANSFORMER

    The basic two-winding (single-phase) transformer is shown below.

    To simplify the initial analysis, the transformer will be assumed to be ideal.

    The following assumptions are made in the analysis of an ideal transformer:

    (1) The transformer windings are perfect conductors (zero winding

    resistance).

    (2) The core permeability is infinite (the reluctance of the core is

    zero).

    (3) All magnetic flux is confined to the transformer core (no

    leakage flux).

    (4) Core losses are assumed to be zero.

    The figure above shows the common convention for the primary and

    secondary voltage polarities and current directions. The voltage polaritiesand current directions shown above yield positive input power on the

    primary and positive output power on the secondary. The actual polarity

    relationship between the primary voltage and the secondary voltage is

    dictated by the orientation of the primary and the secondary coils. The

    transformer voltage relationship is obtained by applying Faradays law.

  • 7/31/2019 Phan Anh Bien AP Transformers

    3/29

    Applying Faradays law to both the primary and the secondary (noting the

    possibility of sources applied to either winding), yields

    where the line integrals of the electric fields are along the primary and

    secondary windings from the ! terminal to the + terminal, and thecorresponding surface integrals of the magnetic flux densities are over the

    cross-sections of the primary and secondary coils. The directions of the

    differential lengths and differential surfaces are related by the right-handrule. The total magnetic flux passing through the primary coil also passes

    through the secondary coil, assuming an ideal transformer (all of the flux

    is confined to the transformer core).

    Note that the orientations of the given coils yield differential surface

    vectors that point in the same direction around the magnetic circuit, such

    that

  • 7/31/2019 Phan Anh Bien AP Transformers

    4/29

    Dividing the equations forv1 and v2 gives

    where the ratio of the primary turns to the secondary turns (defined as theturns ratio a) is equal to the ratio of the primary and secondary voltages.

    According to the turns ratio equation, a transformer with more secondary

    turns than primary turns yields a secondary voltage that is larger than the

    primary voltage (step-up transformer) while a transformer with fewer

    secondary turns than primary turns yields a secondary voltage that is

    smaller than the primary voltage (step-down transformer).

    If the orientation of one of the transformer coils is reversed, then the

    differential surface vectors for the primary and secondary would be in

    opposite directions yielding

    If we apply Amperes law around the transformer core (clockwise, on

    the centerline of the core), we find

    Note that withL clockwise, the normal to the surface Sis inward, so that

    currents inward are positive and currents outward are negative. The total

    enclosed current is then

  • 7/31/2019 Phan Anh Bien AP Transformers

    5/29

    Assuming an ideal transformer core (:r= 4), the magnetic field inside thecore is zero (similar to the fact that the electric field is zero inside a perfectconductor with F = 4, but carries a current on the surface of the conductor).Thus,

    The conservation of power relationship for the ideal transformer (power in

    equals power out, given no losses) can be stated by multiplying the voltage

    ratio by the current ratio:

    Assuming sinusoidal excitation, the ideal transformer can be

    analyzed using phasor techniques. The ratios of the phasor voltages and

    phasor currents satisfy the same turns ratio relationships as the time-domain

    values.

  • 7/31/2019 Phan Anh Bien AP Transformers

    6/29

    Note that the complex power relationship is also valid for the ideal

    transformer.

  • 7/31/2019 Phan Anh Bien AP Transformers

    7/29

    Polarity of Transformer Windings

    The operation of the transformer depends on the relative orientation

    of the primary and secondary coils. We mark one of the terminals on the

    primary and secondary coils with a dot to denote that currents enteringthese two terminals produce magnetic flux in the same direction within the

    transformer core.

    The equivalent circuit diagram and phasor equations for this idealtransformer are

    If either coil orientation is reversed, the dot positions are reversed and the

    current and voltage equations must include a minus sign.

  • 7/31/2019 Phan Anh Bien AP Transformers

    8/29

    Input Impedance (Ideal Transformer)

    Consider an arbitrary load (Z2) connected to the secondary terminals

    of the ideal transformer as shown below.

    The input

    impedance seen looking into the primary winding is given by

    Thus, the input impedance seen looking into the primary of the ideal

    transformer is the load impedance times a2. Using this property, the

    secondary impedance of the ideal transformer can be reflected to the

    primary.

  • 7/31/2019 Phan Anh Bien AP Transformers

    9/29

    In a similar fashion, a load on the primary side of the ideal transformer can

    be reflected to the secondary.

  • 7/31/2019 Phan Anh Bien AP Transformers

    10/29

    Example (Ideal transformer)

    Determine the primary and secondary currents for the ideal

    transformer below ifZs = (18!j4) S and Z2 = (2+j1) S .

    The load impedance reflected to the primary of the transformer is

    The primary current is then

    The primary voltage is

    The secondary voltage is

    The secondary current is

  • 7/31/2019 Phan Anh Bien AP Transformers

    11/29

    TRANSFORMERRATING

    Transformers carry ratings related to the primary and secondary

    windings. The ratings refer to the power in kVA and primary/secondary

    voltages. A rating of 10 kVA, 1100/110 V means that the primary is rated

    for 1100 V while the secondary is rated for 110 V (a =10). The kVA ratinggives the power information. With a kVA rating of 10 kVA and a voltage

    rating of 1100 V, the rated current for the primary is 10,000/1100 = 9.09 A

    while the secondary rated current is 10,000/110 = 90.9 A.

    NON-IDEAL TRANSFORMEREQUIVALENT CIRCUITS

    The non-ideal transformer equivalent circuit below accounts for all

    of the loss terms that are neglected in the ideal transformer model. The

    individual loss terms in the equivalent circuit are:

    Rw1,Rw2 - primary and secondary winding resistances

    (losses in the windings due to the resistance of the wires)

    Xl1,Xl2 - primary and secondary leakage reactances

    (losses due to flux leakage out of the transformer core)

    Rc1 - core resistance(core losses due to hysteresis loss and eddy current loss)

    Xm1 - magnetizing reactance

    (magnetizing current necessary to establish magnetic flux

    in the transformer core)

  • 7/31/2019 Phan Anh Bien AP Transformers

    12/29

    Using the impedance reflection technique, all the quantities on the

    secondary side of the transformer can be reflected back to the primary side

    of the circuit. The resulting equivalent circuit is shown below. The primed

    quantities represent those values that equal the original secondary quantity

    multiplied by a (voltages), divided by a (currents) or multiplied by a2

    (impedance components).

    Approximate Transformer Equivalent Circuits

    Given that the voltage drops across the primary winding resistance

    and the primary leakage reactance are typically quite small, the shuntbranch of the core loss resistance and the magnetizing reactance (excitation

    branch) can be shifted to the primary input terminal. The primary voltage

    is then applied directly across the this shunt impedance and allows for the

    winding resistances and leakage reactances to be combined.

  • 7/31/2019 Phan Anh Bien AP Transformers

    13/29

    A further approximation to the transformer equivalent circuit can be

    made by eliminating the excitation branch. This approximation removes

    the core losses and the magnetizing current from the transformer model.

    The resulting equivalent circuit is shown below.

    Note that this equivalent circuit

    is referred to the primary side of

    the transformer (V1 and VN2).This circuit can easily be

    modified so that it is referred to

    the secondary side of the

    transformer (VN1 and V2).

  • 7/31/2019 Phan Anh Bien AP Transformers

    14/29

    DETERMINATION OF EQUIVALENT CIRCUIT PARAMETERS

    In order to utilize the complete transformer equivalent circuit, the

    values ofRw1,Rw2,Xl1,Xl2,Rc1,Xm1 and a must be known. These values canbe computed given the complete design data for the transformer including

    dimensions and material properties. The equivalent circuit parameters can

    also be determined by performing two simple test measurements. These

    measurements are the no-load(or open-circuit) testand theshort-circuit

    test.

    No-Load Test - The rated voltage at rated frequency is applied to

    the high-voltage (HV) or low-voltage (LV) windingwith the opposite winding open-circuited.

    Measurements of current, voltage and real power

    are made on the input winding (most often the LV

    winding, for convenience).

    Short-Circuit Test - Either the LV or HV winding is short-circuited and

    a voltage at rated frequency is applied to the

    opposite winding such that the rated current results.

    Measurements of current, voltage and real power

    are made on the input winding (most often the HV

    winding, for convenience, since a relatively low

    voltage is necessary to obtain rated current under

    short-circuit conditions).

  • 7/31/2019 Phan Anh Bien AP Transformers

    15/29

    Example (Equivalent circuit parameters / no-load / short-circuit tests)

    The approximate equivalent circuit parameters for a single-phase

    10kVA, 2200/220, 60 Hz transformer are required.

    The rated currents and voltages for the transformer windings are:

    VH,rated= 2200 V IH,rated= 10000/2200 = 4.55 A

    VL,rated= 220 V IL,rated= 10000/220 = 45.5 A

    No-load and short-circuit tests are performed on the transformer with the

    following results:

    No-load test (HV winding open, VL = VL,rated= 220 V)

    IL = 2.5 A,PL = 100 W

    Short-circuit test (LV winding shorted,IH=IH,rated= 4.55 A)

    VH= 150 V,PH= 215 W

    (a.) Determine the approximate equivalent circuit parameters from the test

    data (use the approximate equivalent circuit that includes core losses).

    Draw the equivalent circuit for this transformer referred to the LV side.

    (b.) Draw the equivalent circuit for this transformer referred to the HV

    side. (c.) From the no-load test results, express the excitation current as a

    percentage of the rated current in the LV winding. (d.) Determine the

    power factor for the no-load and short-circuit tests.

    Referred to LV side Referred to HV side

  • 7/31/2019 Phan Anh Bien AP Transformers

    16/29

    Equivalent circuit for no-load test (determineRcL andXmL)

  • 7/31/2019 Phan Anh Bien AP Transformers

    17/29

    Equivalent circuit for short-circuit test (determineReqHandXeqH)

    The values measured on the HV winding (primary) in the short-circuit

    test need to be referred to the LV side. Note that our turns ratio is given by

  • 7/31/2019 Phan Anh Bien AP Transformers

    18/29

    (a.)

    Referred to LV side

    (b.) To obtain the same equivalent circuit referred to the HV side(primary), we simply multiply all impedances by a2 (100). The

    resulting equivalent circuit is

    Referred to HV side

    (c.) From the no-load test results, the total excitation current is 2.5 A

    while the rated current in the LV winding is 45.5 A. Thus the

    excitation current is (2.5/45.5) or 5.5% of the rated current.

  • 7/31/2019 Phan Anh Bien AP Transformers

    19/29

  • 7/31/2019 Phan Anh Bien AP Transformers

    20/29

    TRANSFORMERVOLTAGE REGULATION

    For a given input (primary) voltage, the output (secondary) voltage

    of an ideal transformer is independent of the load attached to the secondary.

    As seen in the transformer equivalent circuit, the output voltage of arealistic transformer depends on the load current. Assuming that the

    current through the excitation branch of the transformer equivalent circuit

    is small in comparison to the current that flows through the winding loss

    and leakage reactance components, the transformer approximate equivalent

    circuit referred to the primary is shown below. Note that the load on the

    secondary (Z2) and the resulting load current (I2) have been reflected to the

    primary (ZN2, IN2).

    The percentage voltage regulation (VR) is defined as the percentage change

    in the magnitude of the secondary voltage as the load current changes from

    the no-load to the loaded condition.

    The transformer equivalent circuit above gives only the reflected secondary

    voltage. The actual loaded and no-load secondary voltages are equal to the

    loaded and no-loaded refelcted secondary values divided by the turns ratio.

  • 7/31/2019 Phan Anh Bien AP Transformers

    21/29

    Thus, the percentage voltage regulation may be written in terms of the

    reflected secondary voltages.

    According to the approximate transformer equivalent circuit, the reflected

    secondary voltage under no-load conditions is equal to the primary voltage,

    so that

    The secondary voltage for the loaded condition is taken as the rated

    voltage.

    Inserting the previous two equations into the percentage voltage regulation

    equation gives

    Note that this equation is defined in terms of the voltages given in the

    transformer approximate equivalent circuit. Also note that the rated

    secondary voltage reflected to the primary is the rated primary voltage.

    To determine the percentage voltage regulation, we may use the reflected

    secondary voltage as the voltage reference,

    and determine the corresponding value of *V1* from the approximateequivalent circuit.

  • 7/31/2019 Phan Anh Bien AP Transformers

    22/29

    The voltagesV1 andVN2 in the approximate equivalent circuit are related by

    where

    The reflected secondary current can be written as

    The expression forV1 becomes

    We can draw the phasor diagram relating the voltages V1 and VN2 to

    determine how the phase angles of the load and the transformer impedanceaffect the percentage voltage regulation. Note that the percentage voltage

    regulation can be positive or negative and the sign ofVR is affected by the

    phase angle in the expression above. Thus, the power factor of the load

    will affect the voltage regulation of the transformer.

  • 7/31/2019 Phan Anh Bien AP Transformers

    23/29

    The percentage voltage regulation is positive if*V1* > V1,ratedand negativeif*V1* < V1,rated. Note that with the limits on the angles of

    the worst case scenario for the percentage voltage regulation occurs when

    or when the load has a lagging power factor with the power factor angle

    equal to the transformer impedance angle ofZeq1.

  • 7/31/2019 Phan Anh Bien AP Transformers

    24/29

    Example (Transformer voltage regulation)

    Using the transformer for which the approximate equivalent circuits

    were found based on no-load and short-circuit test results, determine the

    percentage voltage regulation for (a.) a load drawing 75% of rated currentat a power factor of 0.6 lagging (b.) a load drawing 75% of rated current at

    a power factor of 0.6 leading.

    The approximate equivalent circuit for the transformer (10kVA,

    2200/220, 60 Hz) referred to the high voltage winding was found to

    be (neglecting the excitation branch of the model)

    Assume:Primary = HV winding

    Secondary = LV winding

    a =N1/N2 = 10

    VH,rated= 2200 V

    IH,rated= 10000/2200 = 4.55 A

    VL,rated= 220 V

    IL,rated= 10000/220 = 45.5 A

    (a.) The reflected voltage VLN on the HV side is given by

    so that the circuit to be analyzed becomes

  • 7/31/2019 Phan Anh Bien AP Transformers

    25/29

    Based on the information provided in the problem statement, the

    magnitude of the load current (and thus the current ILN) is 0.75 timesthat of the rated value.

    The phase angle ofILN is given by the load power factor.

    so that the phasor current ILN is

    The voltage VHand VLN are related by

    The percentage voltage regulation is thus

    (b.) For the leading power of 0.6, 2i = +53.13o so that the phasor currentILN is

    and VH is given by

  • 7/31/2019 Phan Anh Bien AP Transformers

    26/29

    The voltage regulation is

    The percentage voltage regulation results for these two cases shows

    that if this transformer is providing 75% of rated current (3.41 A-rms) to

    a load with a power factor of 0.6 lagging, and the load is suddenly

    removed, the load voltage magnitude rises from 220 V to 230.70V. For the

    load with a power factor of 0.6 leading, the load voltage magnitude drops

    from 220 V to 213.79 V.

  • 7/31/2019 Phan Anh Bien AP Transformers

    27/29

    TRANSFORMEREFFICIENCY

    The efficiency (0) of a transformer is defined as the ratio of the outputpower (Pout) to the input power (Pin). The output power is equal to the input

    power minus the losses (Ploss) in the transformer. The transformer losspower has two components: core loss (Pcore) and so-called copper loss (Pcu)

    associated with the winding resistances. The transformer efficiency in

    percent is given by

    Assuming a relatively constant voltage source on the primary of the

    transformer, the core loss can be assumed to be constant and equal to power

    dissipated in the core loss resistance (Rc1

    ) of the equivalent circuit for the

    no-load test. The copper loss in a transformer may be written in terms of

    both the primary and secondary currents, or in terms of only one of these

    currents based on the relationshipI2 = aI1.

    The output power of the transformer can be written in terms of the

    secondary voltage and current (real part of output complex power).

  • 7/31/2019 Phan Anh Bien AP Transformers

    28/29

    The transformer efficiency, written in terms of secondary values, is

    It can be shown that the maximum transformer efficiency occurs when the

    core losses equal the copper losses and the power factor is unity.

    Example (Transformer efficiency)

    Using the transformer for which the approximate equivalent circuits

    were found based on no-load and short-circuit test results, determine (a.)

    the transformer efficiency at 75% of rated output power with a power factor

    of 0.6 lagging (b.) the output power at maximum efficiency, the value of

    maximum efficiency, and at the percentage of full load power where

    maximum efficiency occurs.

    (a.) The rated power for this transformer is 10 kW at a power factor of

    unity. IfPout is 75% of the rated value at a power factor of 0.6, then

    From the no-load test, the core losses werePcore = 100 W. The copper

    losses for this transformer are

    The transformer efficiency is

  • 7/31/2019 Phan Anh Bien AP Transformers

    29/29

    (b.) At maximum efficiency YPCu=IL2ReqL =Pcore = 100 W,PF= 1

    The maximum efficiency is

    The maximum efficiency occurs at