OTI Recommendation

Embed Size (px)

Citation preview

  • 8/22/2019 OTI Recommendation

    1/24

    1

    Yunhyeong Kim : Haijun Liu [[email protected]] : 2012 8 27 11:32 : 'Yunhyeong Kim': ''; ''; ''; ''; ''; '': RE: [ETAP] Request teleconference for analyzing calculation result.

    DearKim:

    Aslongasyoumakesureapersonstandardsaroundtheequipmentdoesnotexposetomorethantolerabletouch

    voltagethedesignwillbeok.

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htm

    FAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain information

    that is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Monday, August 27, 2012 7:51 AMTo: Haijun LiuCc: ''; ''; ''; ''; ''; ''

    Subject: [ETAP] Request teleconference for analyzing calculation result.

    Dear Mr. Liu,

    We calculated touch voltage include the electrical equipment as per your recommendation.

    But result disposition is different with your calculation.

  • 8/22/2019 OTI Recommendation

    2/24

    2

    Modeling file also attached for your checking.

    In my opinion, this area is safe. Because area where electrical equipment is installed is safe, and area where the

    touch voltage is high is a region where a structure will not be dissipating the current into ground.

    Concerning the result of earthing calculation, we would like to have a teleconference meeting tomorrow at the

    time as below.

    Agenda : 1. Analyzing calculation result and confirming safety.

    2. Reason of high touch voltage at the area between earth grid and electrical equipment.

    3. Discussing technical solution if our design is un-safe.

  • 8/22/2019 OTI Recommendation

    3/24

    3

    Time : 2012-08-28 08:00 a.m. (pacific time)

    2012-08-28 07:00 p.m. (Abu-Dhabi)

    Please confirm your availability for the same.

    Thanks and regards

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Saturday, August 25, 2012 4:46 AMTo: 'Yunhyeong Kim'Cc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

    Youshouldaddsomebareconductors(suchasasquire)torepresenttheequipment.

  • 8/22/2019 OTI Recommendation

    4/24

    4

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htm

    FAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Thursday, August 23, 2012 10:02 PMTo: Haijun LiuCc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

  • 8/22/2019 OTI Recommendation

    5/24

    5

    Dear Mr. Liu,

    Thanks for your response.

    I tried to calculate as per your suggestion below.

    But ETAP still does not indicate the touch & step voltage at the area of installed PVC wire and additional rod.

    Step & touch voltage is less than tolerable voltage. And step & touch voltage has been lower since adding

    conductor and rod.

    Is it possible to understand that electrical equipment which is connected by PVC insulated wire is safe from

    touch voltage?

    Additional conductor

    and rod

    Additional conductor and

    rod is not indicated

  • 8/22/2019 OTI Recommendation

    6/24

    6

    I attached the modeling file for reference.

    Thank you very much and best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Thursday, August 23, 2012 9:22 PMTo: 'Yunhyeong Kim'

    Cc: ''; ''; ''; ''; ''; ''Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

    Sincetheequipmentisconnectedtothegrid,itcouldexposetotheGPR.Iftheequipmentisnotinsulatedandcould

    beexposedtohumantouching,thetouchvoltageshouldbeconsidered.Onesuggestionistoaddconductorsand

    rodstorepresenttheequipment.Inthisway,ETAPwillincludetheequipmentinthecalculation.

    Anotherthoughttomeisnottheconnecttheequipmenttothegrid.Usuallyoutdoorlightingpolesshouldbe

    insultedanddonotneedtobeconnectedtoagroundgrid.

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htmFAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================

    This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of this

    message, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any action

  • 8/22/2019 OTI Recommendation

    7/24

    7

    taken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Thursday, August 23, 2012 7:07 AMTo: Haijun LiuCc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Thanks for your valuable response.

    We are making progress in trying to convince our client but one doubt remains.

    Please see the sketch below, it is almost identical with the one that we had sent to you earlier; in this

    case we consider electrical metallic equipment next to a person. In the case below, the equipment is

    connected by PVC insulated wire to the earthing grid only.

    Do we have to verify the touch voltage for this equipment or metallic structure?

    If that is the case how to verify safety from touch voltage by using ETAP? PVC insulated wire is

    just considered as a conductor, but is not considered source of current dissipation by ETAP.Boundary extended length may not be solution for verifying touch potential to the equipment as shown

    below.

    Thank you very much & best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Sunday, August 19, 2012 8:40 PMTo: 'Yunhyeong Kim'

  • 8/22/2019 OTI Recommendation

    8/24

    8

    Cc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

    Pleaserefertotheattachedfortouchvoltagedefinition.

    ForaPVCinsulatedwire,ETAPtreatsitasaelectricconductorbutitdoesnotdissipatecurrentintoground.

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htmFAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================

    This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any views

    expressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Friday, August 17, 2012 2:47 AMTo: Haijun LiuCc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Thanks for your response.

    Could you provide the screen capture file about limitation of touch potential?

    We dont have IEEE80 due to the site condition.

    In addition, is it possible to understand that touch potential does not need to be considered at the area of

    grounded structure which is connected by PVC insulated wire.

    Because ETAP does not consider PVC insulated wire when calculate step & touch potential.

  • 8/22/2019 OTI Recommendation

    9/24

    9

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Friday, August 17, 2012 3:13 AMTo: 'Yunhyeong Kim'Cc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

    PleaserefertoIEEEStd80fordefinitionandlimitationoftouchpotential.

    Thereisnoglobaldefinitionforsafety.Itdependsonengineerjudgmentandorganizationpractice.Formy

    understandingaslongasahumandoesnotexposetothelimitedtouchpotentialitshouldbesafe.

    Sincerely,

    Haijun Liu, PhD, PE

    Principal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htmFAQ & Tutorials http://etap.com/support/faqs.htm

    Workshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================

  • 8/22/2019 OTI Recommendation

    10/24

    10

    This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Thursday, August 16, 2012 4:05 AMTo: Haijun LiuCc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Thanks for your valuable response.

    Could you inform us why the touch potential does not need to be considered?

    Please provide technical reasons for answer number 2.

    Once getting approval from our client, we shall provide technical reasons to them.

    Best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Wednesday, August 15, 2012 10:54 PMTo: 'Yunhyeong Kim'Cc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

    Regardingyour

    questions:

    1.Yes,itreferstocase1only.

    2.Yes,thisshouldbeok.Iassumethatthe70sqmmbarecopperconductorsareburiedunderground.Pleasemake

    suresteppotentialaroundthe70sqmmbarecopperconductorsaregood.

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

  • 8/22/2019 OTI Recommendation

    11/24

    11

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htm

    FAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain information

    that is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Wednesday, August 15, 2012 7:49 AMTo: Haijun LiuCc: ''; ''; ''; ''; ''; ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Thanks for your cooperations.

    We intend to finalize the selection of boundary extension. So please answer to below 2 questions.

    1. Could you please inform us what is an accurate meaning for "boundary extension for touch potential" ?

    We have represented 2 cases below. Is it matching to case 1? case 2? or both?

    Our understanding is that using boudary extension refers to case 1 only.

    2. We sketched conceptual earthing system as follows;We shall calculate step & touch potential for in-between earthing grid areas as per our client request.

  • 8/22/2019 OTI Recommendation

    12/24

    12

    But we divided the entire calculation into 17 calculations for performing calculation of 2 earthing grids only.

    Because we cannot calculate entirely plant because huge data processing is required.

    If we use 0m boundary extend, ETAP calculates the area limited as blue line below.

    Is it possible to verify that all in-between grids areas are safe from touch potential with earthing calculation

    using 0m boundary?

    We would appreciate your support in understanding precisely this matter, in order to proceed forward.

    Thanks in advance

    Best regards

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Thursday, July 26, 2012 9:44 PMTo: 'Yunhyeong Kim'Cc: ''; ;

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

  • 8/22/2019 OTI Recommendation

    13/24

    13

    ThebestreferenceistheIEEEStd80.

    Isthepiperackconnectedtothegroundgrid?Ifitis,thiscouldbeaproblembecauseitwillhavethesameGPRas

    thegrid.Otherwisethereisnodifferenceforapersonstandsonthesurfacecoveringthepiperack.

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)462

    0100

    main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htmFAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain information

    that is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any action

    taken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Wednesday, July 25, 2012 5:52 AMTo: Haijun LiuCc: ''; ;

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Thanks for your cooperation.

    Could you give me some technical basis of your response? (e.g. Some equations, Reference code and

    standard, or theoretical explanations)

    Our client still want to know why piperack is not need to be considered. If attached earthing calculation is

    correct, most dangerous area is outside of earthing grid where the piperack or another grounded structures are

    installed. Because touch voltage is the potential difference between the GPR and surface potential at the point

    where a person is standing while at the same time having a hand in contact with a grounded structure. They

    think grounded structure means all structure(e.g. pipe rack, tank, vessel) which is installed on the ground.

    All earthing grids in the site are connected to make one large earthing grid. And all grounded structure

    connected to earthing system. This is not only for the substations.

  • 8/22/2019 OTI Recommendation

    14/24

    14

    Im sorry for difficult question.

    Thanks & Best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Wednesday, July 18, 2012 9:47 PMTo: 'Yunhyeong Kim'

    Cc: ''; 'Harris Melvin (External)'Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearKim:

    Yes,youmayhave30masboundaryextensionforbothstepandtouchvoltagecalculation.Forthehighertouch

    potentialissue,justmakesureahumanstandatthepointswon'tbeabletotouchanequipmentinthesubstation

    oranythingconnectedtothegrid.Itisnotnecessarilytohaveaphysicalprotectivedevicesuchasafence.Cana

    personstandtheretotouchanequipmentinthesubstationwithhis/herarm(orwithastick)?

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htmFAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of this

    message, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any views

    expressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

  • 8/22/2019 OTI Recommendation

    15/24

    15

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Wednesday, July 18, 2012 4:55 AMTo: Haijun LiuCc: ''; 'Harris Melvin (External)'

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Thanks for your response.

    But please response after considering following conditions;

    - Our client want to verify safety of all plant area not only substations. Because IEEE80 explain that touch

    potential is the potential difference between the ground potential rise (GPR) and the surface potential at

    the point where a person is standing while at the same time having a hand in contact with a grounded

    structure. But we cannot physically protect for all structure in the plant (e.g. pipe rack).

    - We cannot calculate entirely plant because huge data processing is required. So we divided the entire

    calculation into 17 calculations for performing calculation of 2 earthing grid only.

    - I inputted 30m boundary extension limit as step potential calculation and 0m boundary extension limit as

    touch potential. But our client doesnt want different input data between touch potential and step

    potential. So I need verify that this input data is correct.

    - I attached example calculation which is using 30m extention boundary limit for reference. As per this

    result most dangerous area is 30m far from substation earthing grid perimeter. But most dangerous area

    shall be inside of substation earthing grid. Because any electrical equipment shall not be installed outside

    of substation rectangular earthing grid. Only small lighting panel shall be installed in outside of earthing

    grid.

    So please advise the specific input data of boundary extension limit without considering physical protection.

    And if some condition is wrong, please do not hesitate to advise it.

    Best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Wednesday, July 18, 2012 4:58 AMTo: '???'; 'Yunhyeong Kim'Cc: ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearMr.Kim:

  • 8/22/2019 OTI Recommendation

    16/24

    16

    Boundaryextensionisnotnecessary,ifoutsideoftherectangularareaisprotectedphysicallyasstatedinmy

    previousemail.

    Sincerely,

    Haijun Liu, PhD, PEPrincipal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htmFAQ & Tutorials http://etap.com/support/faqs.htmWorkshops http://www.etap.com/training/events.htmContact us [email protected]

    ===========================================This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any action

    taken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.===========================================

    From: [mailto:[email protected]]

    Sent: Tuesday, July 17, 2012 5:23 PMTo:; Haijun Liu; 'Yunhyeong Kim'

    Cc: ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Your valuable response is highly required.

    If I incorrect, please recommend the correct input data of boundary extension limit for touch potential.

    Best regards,

    kimyh187.

  • 8/22/2019 OTI Recommendation

    17/24

    17

    -----Original Message-----

    From: ""To: "Haijun Liu"; "'Yunhyeong Kim'";Cc: "''";Sent: 2012-07-18 () 02:48:12Subject: RE: [ETAP] Question about boundary extension limit for earthing calculationDear Mr. Liu,

    Yes. You right, Pipe racks shall be installed some in-between grid areas.

    But, my question is that boundary extention limit is required or not in case of touch potential calculation.

    As I know GPR is locally generated, but ETAP considered GPR is generated entirely in the calculated area.

    Any electrical equipment will be installed outside the grid area or in-between grid area.

    Hence in my opinion, 0m boundary extention limit shall be considered for touch potential calculation.

    Please advise it.

    Best regards,

    kimyh187.

    -----Original Message-----From: "Haijun Liu"To: "'Yunhyeong Kim'";Cc: "''"; "[email protected]";Sent: 2012-07-18 () 02:06:14Subject: RE: [ETAP] Question about boundary extension limit for earthing calculationDearMr.Kim:

    Yes,youneedmakesurethattouchpotentialsintheareasthatarenotphysicallyprotectedareinthetolerable

    limit.Youmaylookattheplotsorreports.

    Sincerely,

    Haijun Liu, PhD, PE

    Principal Electrical Engineer

  • 8/22/2019 OTI Recommendation

    18/24

    18

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

    Lib Downloads http://www.etap.com/support/downloads.htm

    FAQ & Tutorials http://etap.com/support/faqs.htm

    Workshops http://www.etap.com/training/events.htm

    Contact us [email protected]

    ===========================================

    This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain information

    that is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any action

    taken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.

    ===========================================

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Tuesday, July 17, 2012 9:56 AMTo: Haijun LiuCc: ''; [email protected]

    Subject: FW: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    My response can be answer your 2 emails.

    Please reply after considering our situations.

    And please include my private email address.

  • 8/22/2019 OTI Recommendation

    19/24

    19

    Many thanks for your prompt response.

    Best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Yunhyeong Kim [mailto:[email protected]]Sent: Tuesday, July 17, 2012 8:52 PMTo: 'Haijun Liu'Cc: ''

    Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    Dear Mr. Liu,

    Each earthing grid covers the hole substation and transformers. Moreover substation is building type andoutdoor transformers are protected by fence.

    But two interconnecting wire shall be installed in-between all the substations or process units earthing grid.

    Please refer to earthing block diagram.

    So we need to verify that this interconnecting area is safe. That area is not inside the substations. Hence, we

    cannot install the fence for this area.

    Please refer to attached modeling file.

    So I want to get your confirmation boundary extention limit shall not be used to calculate touch potential fornot only inside the substation but also normal field area.

    Best regards,

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +971-2-895-6119 Mobile : +971-50-773-9736E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

  • 8/22/2019 OTI Recommendation

    20/24

    20

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.

    From: Haijun Liu [mailto:[email protected]]Sent: Tuesday, July 17, 2012 8:20 PMTo: 'Yunhyeong Kim'

    Cc: ''Subject: RE: [ETAP] Question about boundary extension limit for earthing calculation

    DearYunhyeongKim:

    Yes,youonlyneedtomakesure:

    1.The

    touch

    and

    step

    potentials

    inside

    the

    grid

    area

    both

    meet

    the

    tolerable

    potential

    requirements.

    2.Thesteppotentialoutsidethegridareameetsthetolerablepotentialrequirement.

    3.Thehighertouchpotentialoutsidethegridshouldbeprotectedbyaphysicalmethodsuchasafence.Notethatif

    thereisequipment outsidethegridarea,thegridneedstobeextended.

    Doesyourgridcoverthewholesubstation?Isthereafencesurroundthesubstation?

    Sincerely,

    Haijun Liu, PhD, PE

    Principal Electrical Engineer

    OPERATION TECHNOLOGY, INC.

    17 Goodyear, Suite 100

    Irvine, CA 92618-1812

    (949)4620100main

    (949)4620200fax

  • 8/22/2019 OTI Recommendation

    21/24

    21

    Lib Downloads http://www.etap.com/support/downloads.htm

    FAQ & Tutorials http://etap.com/support/faqs.htm

    Workshops http://www.etap.com/training/events.htm

    Contact us [email protected]

    ===========================================

    This e-mail message is intended only for the use of the individual or entity to which it is addressed and may contain informationthat is privileged, confidential and exempt from disclosure under applicable law. If you are not the intended recipient of thismessage, you are hereby notified that any use, review, retransmission, dissemination, distribution, reproduction or any actiontaken in reliance upon this message is prohibited. If you received this message in error, please contact the sender. Any viewsexpressed in this message are those of the individual sender and may not necessarily reflect the views of the company.

    ===========================================

    From: Yunhyeong Kim [mailto:[email protected]]

    Sent: Tuesday, July 17, 2012 8:55 AMTo: Haijun LiuCc: ''

    Subject: [ETAP] Question about boundary extension limit for earthing calculation

    &

    wx

  • 8/22/2019 OTI Recommendation

    22/24

    22

    1(16MB) 30 / 100earthcalc_modelinzip16MB PC|N

    : 2012/07/18 ~ 2012/08/17

    *

    W

    +

    &

    E-mail :

    +

    , , .

    .

  • 8/22/2019 OTI Recommendation

    23/24

    23

    Thanks f or cont act i ng ETAP t echni cal suppor t .

    I n ETAP FEM, Boundar y Extensi on i s provi ded so t hat users can i nvest i gate t he st ep and

    t ouch pot ent i al s out si de t he gr i d. I t i s al ways t r ue t hat t he hi ghest t ouch pot ent i al

    i s around t he gr i d per i met er and t ouch pot ent i al wi l l be even hi gher out si de the gr i d.

    Thi s i s because t he t ouch potent i al i s t he potent i al between a person' s f eet and ar ms

    ( GPR) when he/ she t ouches equi pment s i n t he subst at i on. The di f f er ence i s get t i ng

    bi gger si nce t he act ual pot ent i al get t i ng l ower ( unt i l r each t o 0) when i t i s f ar away

    f r om t he subst at i on.

    The unacceptabl e t ouch potent i al outsi de t he gr i d usual l y i s not sol ved by enhanci ng

    t he gr i d. I t shoul d be physi cal l y ( such as wi t h a f ence) pr ot ect ed f r om human exposi ng

    t o thi s hi gh touch pot ent i al . Thi s means t hat a human won' t be abl e to touchequi pment s i n t he subst at i on when he/ she i s st andi ng out si de t he gr i d. Note t hat t he

    st ep pot ent i al out si de of t he gr i d needs t o be i n t he r equi r ed l i mi t .

    I f you need f ur t her assi st ance on t hi s i ssue pl ease f eel f r ee t o cont act me.

    Hai j un Li u

    ETAP Techni cal Suppor t

    From: [mailto:[email protected]]

    Sent: Tuesday, March 20, 2012 1:11 AM

    To:[email protected]

    Cc:

    Subject: ETAP. ()

  • 8/22/2019 OTI Recommendation

    24/24

    Yunhyeong Kim (Electrical Engineer)Electrical & Control System Engineering Dept.2 SAMSUNG ENGINEERING Co., Ltd.Office: +82-2-3458-3931 Mobile : +82-10-3293-1087E-mail : [email protected]

    Confidentiality Notice: This e-mail is intended for the addressee named in the above. The information contained in this e-mail is

    confidential and privileged. If you are not the intended recipient, you are hereby notified that any dissemination, distribution or copying of

    this communication is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately and destroy this e-

    mail message. Thank you.