141
On travelling-wave-based protection of high-voltage networks Citation for published version (APA): Bollen, M. H. J. (1989). On travelling-wave-based protection of high-voltage networks. Eindhoven: Technische Universiteit Eindhoven. https://doi.org/10.6100/IR316599 DOI: 10.6100/IR316599 Document status and date: Published: 01/01/1989 Document Version: Publisher’s PDF, also known as Version of Record (includes final page, issue and volume numbers) Please check the document version of this publication: • A submitted manuscript is the version of the article upon submission and before peer-review. There can be important differences between the submitted version and the official published version of record. People interested in the research are advised to contact the author for the final version of the publication, or visit the DOI to the publisher's website. • The final author version and the galley proof are versions of the publication after peer review. • The final published version features the final layout of the paper including the volume, issue and page numbers. Link to publication General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. • Users may download and print one copy of any publication from the public portal for the purpose of private study or research. • You may not further distribute the material or use it for any profit-making activity or commercial gain • You may freely distribute the URL identifying the publication in the public portal. If the publication is distributed under the terms of Article 25fa of the Dutch Copyright Act, indicated by the “Taverne” license above, please follow below link for the End User Agreement: www.tue.nl/taverne Take down policy If you believe that this document breaches copyright please contact us at: [email protected] providing details and we will investigate your claim. Download date: 06. Mar. 2020

On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

On travelling-wave-based protection of high-voltage networks

Citation for published version (APA):Bollen, M. H. J. (1989). On travelling-wave-based protection of high-voltage networks. Eindhoven: TechnischeUniversiteit Eindhoven. https://doi.org/10.6100/IR316599

DOI:10.6100/IR316599

Document status and date:Published: 01/01/1989

Document Version:Publisher’s PDF, also known as Version of Record (includes final page, issue and volume numbers)

Please check the document version of this publication:

• A submitted manuscript is the version of the article upon submission and before peer-review. There can beimportant differences between the submitted version and the official published version of record. Peopleinterested in the research are advised to contact the author for the final version of the publication, or visit theDOI to the publisher's website.• The final author version and the galley proof are versions of the publication after peer review.• The final published version features the final layout of the paper including the volume, issue and pagenumbers.Link to publication

General rightsCopyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright ownersand it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.

• Users may download and print one copy of any publication from the public portal for the purpose of private study or research. • You may not further distribute the material or use it for any profit-making activity or commercial gain • You may freely distribute the URL identifying the publication in the public portal.

If the publication is distributed under the terms of Article 25fa of the Dutch Copyright Act, indicated by the “Taverne” license above, pleasefollow below link for the End User Agreement:www.tue.nl/taverne

Take down policyIf you believe that this document breaches copyright please contact us at:[email protected] details and we will investigate your claim.

Download date: 06. Mar. 2020

Page 2: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

ON TRAVELLING-WAVE-BASED PROTECTION OF

HIGH-VOLTAGE NETWORKS

MATH BOLLEN

Page 3: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS

Page 4: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

CIP-GEGEVENS KONINKLIJKE BIBLIOTHEEK, DEN HAAG

Bollen, Mathias Henricus Johannes

On travelling-wave-based protection of high-voltage networks I Mathias Henricus Johannes Bollen. -[S.l. : s.n.]. Fig., tab. Proefschrift Eindhoven. Met lit.opg., reg. ISBN 90-9002955-9 SISO 661.55 UDC 621.316.925(043.3) NUGI 832 Trefw.: hoogspanningsnetten; beveiliging I transmissielijnen; elektrische overgangsverschijnselen.

Page 5: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

ON TRAVELLING-WAVE-BASED PROTECTION OF

HIGH-VOLTAGE NETWORKS

PROEFSCHRIFf

ter verkrijging van de graad van doctor aan de Technische Universiteit Eindhoven, op gezag van de Rector Magnificus prof. ir. M. Tels, voor een commissie aangewezen door het College van Dekanen in het openbaar te verdedigen

op vrijdag 15 september 1989 om 16.00 uur

door

Mathias Henricus Johannes Bollen

geboren te Stein (L)

&'uk wibr-o dicsertatie<:fr\.lkkerlj, holrnood

Page 6: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

Dit proefschrift is goedgekeurd door de promotoren:

Prof. Dr. Ir. W.M. C. van den Heuvel

en

Prof. Dr.-Ing. HJ. Butterweck.

Page 7: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

We can walk our road together

If our goals are all the same

We can run alone and free

If we persue a different aim

Let the truth of love be lighted

Let the love of truth shine clear

Sensibility

Armed with sense and liberty

With the heart and mind united

In a single perfect sphere

Neil Peart, 1978.

Page 8: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

TABLE OF CONTENTS:

1. Introduction ................................................ .

2. Travelling waves and high-voltage lines ...................... 7

3. Network modelling ............................................. 26

4. Testing of algorithms for travelling-wave-based protection ... 41

5. Directional detection ........................................ 58

6. Differential protection ...................................... 73

7. Other algorithms for travelling-wave-based protection ........ SO

8. A protective scheme for a double-circuit line ............... 102

9. Summary and conclusions ..................................... 114

10. References .................................................. 118

Samenvatting .................................................... 127

cxxx ............................................................ 130

Levens loop ...................................................... 131

Page 9: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-1-

1. Introduction

1.1. The protection of public supply systems

A public supply system is set up to transport and distribute electrical

energy from the generators to the users. Due to the interconnection of a

large number of generators (power plants) a high reliability is achieved. An

important role in maintaining this high reliability is played by the

power-system protection. The function of the protection is the disconnection

of defective lines and apparatus from the system. This thesis concerns the

detection and disconnection of faults1 on high-voltage lines.

Before the turn of the century, this was mainly achieved by using

fuses. This century showed the introduction of protective relays in

combination with circuit-breakers. The first to detect the fault, the latter

to disconnect it. The protective relay uses voltages or currents to detect a

fault. Upon detecting, a tripping signal is sent to the circuit breaker that

disconnects the fault. At first. simple relays were used, like time

overcurrent relays, directional-power relays and differential relays . By

using these relays it was difficult to maintain the selectivity (only

disconnecting the faulted line or apparatus), especially in the growing

high-voltage networks in Europe in the twenties. This led to the proposal of

a number of new protection principles drawing much attention from the

professional world. But all of them were overruled by the principle of

distance protection. The first distance relays were used in 1925 for the

100 kV double-circuit 1 ine betw:een the power plant of Seestadl and Prague

[Walter, 1967]. Nowadays the protection of high-voltage lines is largely

achieved by means of distance relays. From power frequency voltages and

currents measured at one line terminal an input impedance is determined for

the line. If this value is below a certain preset value, a tripping signal

is sent to the circuit breaker and the line is disconnected.

The main advantage of di,t}tcmce (Yl,otecUoo is the fact that no

communication link is needed. Each relay can determine the position of the

fault from voltages and currents measured at the relay position. Due to all

kinds of errors, the reach of a distance relay cannot be determined exactly.

It is therefore impossible to distinguish between a fault a 1 i ttle before

the next substation and a fault a little beyond that substation. But by

introducing different distance zones a highly reliable network protection

A fault (or short-circuit) is an inadvertent accidental connection between two or more phase conductors or between one or more phase conductors and ground [Blackburn, 1987].

Page 10: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-2-

has been achieved.

Zone 1 of each distance relay reaches up to about 90% into the

line-to-be-protected. zone 2 up to 50% into the next adjacent line and zone

3 approximately 25% into the adjacent line beyond [Blackburn, 1987]. If a

relay detects a fault in its zone 1 an instantaneous tripping signal will be

generated (no delay introduced on purpose). In case of a fault in zone 2 or

3 a tripping signal will be generated if the fault remains during a certain

time. This verification time is longer for more distant zones. A fault

somewhere on a line, not too close to one of the line terminals, (position 1

in Figure 1.1) will lead to an instantaneous tripping signal of both A and

B. In case of a fault at position 2 (i.e. close to one of the line

terminals) only B will generate an instantaneous tripping signal. Relay A

will generate a tripping signal if the fault lasts for longer than a certain

time. This time is longer than the time needed to disconnect a fault at

position 3 by relay C and its circuit breaker. In that way zone 2 of relay A

serves as a primary protection for faults close to the other line terminal

and as a remote backup for relay C in case of faults on the first half of

the next adjacent line. Zone 3 serves as a remote backup for faults on the

second half of the next adjacent line (e.g. position 4).

--- --· ZONE 3

ZONE2

Figure 1.1. Protection of a high-vottage tine by means of distance retays

When reliable communication links are available it is possible to use

information from both 1 ine terminals. In that case each fault on the 1 ine

wi 11 lead to an instantaneous trip. Two principles can be distinguished:

differential protection and directional detection. A attte~entiai ~tection

relay uses currents from both line terminals. If the difference between

corresponding currents exceeds a certain threshold a tripping signal is

generated. This principle is mainly used for short lines and for the

protection of busbars, as the current values must be transmitted from one

line terminal to the other. A simple communication link can be used

Page 11: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-3-

for dL'tecti.Oitai detecti.Oit. On each line terminal a "directional detector"

determines the direction to the fault (generally from the direction of the

power flow). By exchanging this result each relay decides whether a tripping

signal should be generated or not.

Protection needing communication links is

connections in the United States [I.andoll et al.,

used for important

1981] and is already

common practice in Japan [CIGRE, 1980]. In most cases distance protection is

used as a remote backup. In Europe, 50-Hz based distance protection is used

almost throughout the high-voltage network. In some protection schemes a

signal is transmitted to the relay on the other line terminal when a zone

fault is detected {a t'tan~fe't-t'ti.p ~cheme). Immediately upon receiving the

signal the relay on the other line terminal is prepared to generate a

tripping signal. An interruption of the communication link will not endanger

the reliability of these schemes.

In most protection schemes the final backup consists of a

tLme-o~e'tCU't'tent 'tel.~. In case the current exceeds a certain value during a

certain time, a tripping signal will be generated.

1.2. Why fast protection?

The first public supply network was built in 1882 on the initiative of

Thomas Alva Edison. An electrical power system supplied energy for a small

quarter of New York by means of a relatively low D.C. voltage. Within a few

years such networks arose all over the world. The protection took place by

means of a large fuse at the outlet of the generator.

Developments in A.C. technology like the invention of the transformer,

made it possible to connect power stations with each other. This led to an

enormous growth of the electric supply networks in the twenties. With the

larger transmitted power and the larger generators the need arose for faster

fault clearing. Where a disconnection (or clearing) time of 10 seconds was

still acceptable in 1910 a time below 2 seconds was asked for in 1925. In

later years a continued growth of the supply networks is observed. This does

not primarily concern the aerial extent but the generated and transmitted

power as well as the network complexity.

Fault clearing times have decreased ever more. In the present state of

the art fault detection times of 20 to 40 milliseconds are general practice,

leading to fault clearing times of 40 to 100 milliseconds depending on the

circuit breaker used [Blackburn, 1987]. In the past ten years there has been

a call for even shorter fault clearing times {and detection times). Three

causes for this can be given:

Page 12: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-4-

In case of a fault close to a generator, the disconnection of resistive

load will speed up the generator. The larger the pre-fault transmitted

power is, the larger the acceleration. If such a fault lasts too long,

this will lead to transient instability. The increasing power exchange

between networks thus calls for a decreasing fault clearing time or

additional high-voltage lines. The first solution is preferable from an

economic and environmental point of view. A fault clearing time of one

or two cycles is needed in some situations to prevent transient

instability [Hicks and Butt, 1980]. Utilizing 3/4-cycle breakers, this

leaves about 5 milliseconds for fault detection. This is the main cause

for research after faster fault detection in the late seventies and

eighties.

The large currents during a short circuit constitute a heavy mechanical

stress on the power systems apparatus. Since the electrodynamical

forces are proportional to the square of the current, reducing the

maximum current is an effective way of reducing the mechanical stress.

Because the first current maximum will be the highest {due to

exponential current terms) current limiting devices will only be

effective when action is taken before the first current maximum. This

calls for a fault detection within one or two milliseconds [Thuries and

Pham Van Doan, 1979].

The availability of fast and cheap microprocessors made microprocessor

based protection relays possible. A few of these relays are already

available, all of them using distance protection [-,1988]. But the

microprocessor also enables the use of other {better, faster)

protection principles. This triggers the call for fast protection. In

this context Chamia [1988] speaks about "technology-driven"

applications.

The development of one-cycle 500 kV air blast circuit-breakers prompted

Bonneville Power Administration, Portland, Oregon to launch a special

program in 1974 aiming at Ultra-High-Speed Relaying systems. The scope of

this program was to dev~lop a relaying system with an operating time of 4

milliseconds or less for multi-phase faults close to the relay position.

This resulted in a relay with an operating time of 4 milliseconds based on

travelling wave principles [Esztergalyos, Yee, Chamia and Liberman, 1978].

It will be discussed as Chamia's algorithm in Section 5.1.

At about the same time a japanese group developed a prototype of a

travelling-wave-based differential relay to solve some relaying problems

encountered in EHV and UHV networks [Takagi, Baba. Uemura, Sakaguchi, 1977].

Page 13: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-5-

Despite promising testing results presented in a number of papers, the relay

has not been applied in existing power systems. It will be discussed as

Takagi's algorithm in Section 6.1.

Since 1978 more algorithms for travelling-wave-based protection of

high-voltage lines have been proposed. But, except for Chamia's algorithm,

none of them has reached the state of commercial availability.

Also some non travelling-wave-based algorithms for fast protection have

been proposed. Most of them determine the stationary quantities from a time

window of less than one cycle of the power frequency. None of them is able

to determine the fault position with an acceptable accuracy within half a

cycle [Glavitsch, Btirki, Ungrad, 1987].

1.3. The aim of this study

2 As already noted several algorithms for travelling-wave-based protection of

high-voltage lines have been proposed. In the author's opinion none of them

has been sufficiently tested to answer the question ":J!J. /]a':J.t fJ'totectioo,

ba!J.ed oo, t'ta1!>eUing.-fl9(t1!>e fJ'tincipte':J. f;o!J.!J.i/..te?" On the other hand some of the

proposed algorithms are based on very simple principles making it (almost)

impossible to find even simpler algorithms. In view of this situation it is

not appropriate to search for a completely new algorithm.

First the existing algorithms must be subject to a thorough and

critical review. It must be investigated whether the algorithm will react

3 properly to all possible fault situations in the zone-to-be-protected .

Further it must be studied how the algorithm reacts on disturbances not

caused by faults in the zone-to-be-protected.

It is not possible to perform a large number of field experiments in

high-voltage networks. Therefore we have to resort to network models for the

testing of protection algorithms. ~he de1!>etopment ot netmo'tk modeL!J. j]o't the

!J.tudy- ot t'ta1!>eLUng,-wa1!>e-ba!J.ed pwtecti..oo, forms the first part of this

study. The models are described in Chapters 2 and 3. An existing model as

well as a newly developed model have been used.

2 A protection algorithm has been defined here as: "The way in which measured voltages and currents are used to calculate certain functions and the way how these functions are used to take decisions concerning protection".

3 For line protection, discussed here, the zone-to-be-protected consists in general of three phase-conductors (one circuit) between two substations. But for some relays the zone-to-be-protected consists of just one conductor, for others of two parallel circuits.

Page 14: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-6-

The second part of the study concerns the tell.Ung. ot the P"tePoll.ed

aLg.o'ti.thnlll., the introduction of simplications, changes and/or extensions

followed by a new round of testing. Also some new proposals have been

studied. Chapter 4 gives a list of situations that might lead to an

incorrect decision by the relay. It also describes how the network models

and the list of situations have been used for extensive testing of

protection algorithms. Chapters 5 through 7 give an overview of existing

algorithms as well as the results of the testing.

The third part of the study concerns the c'teatton ot a Li.nk ~eteeen the

P'toPoll.ed aig.o'ti.thnlll. ana a tata'te 'teL~ that is capable of protecting a high­

voltage line. The results of this part can be found in Chapter 8.

The conclusions of this study may form a next ll.tep. on the ~ to a

P.'tDtectton ll.cheme ~ll.ed on t~etti.ng.-~e P.'ti.nci.P.Lell..

Page 15: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-1-

2. Travelling waves and high-voltage lines

2.1. The line model

A high-voltage 4 line5 is a structure consisting of parallel conducting

wires, of towers to support the wires and of isolating chains to prevent

electrical contact between the wires and the towers. An example is depicted

in Figure 2.1.

Figure 2.1. A high-voltage line, consisting of 20 conductors. Six bundles of

3 conductors (6 phase conductors} are used to transport electrical energy .

Tile tlllO other conductors (shielding wires} are used to prevent a direct

lightning stroke to one of the phase conductors. Tile left set of phase

conductors can operate independently of the right set. Such a set of three

is called a circuit. The line shoun here is a "double-circuit line".

4

5

There are no internationally accepted standards to define the terms high voltage, extra high voltage and ultra high voltage. According to the IEEE standards board the term high voltage refers to voltage levels between 115 kV and 230 kV [Blackburn, 1987]. As the principles discussed in this thesis can be applied to any voltage level, the term "high voltage" is used here in a broader sense.

The term line is used here from the modelling point-of-view. All sets of electromagnetically coupled parallel conductors will be described as one transmission line . Such a line may consist, from the protection point-of-view, of several zones-to-be-protected.

Page 16: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-s-

A detailed electronagnetic analysis of an actual high-voltage line is

impossible and undesirable. As in any theoretical treatment of technical

systems we need an appropriate model which is

a. simple enough to yield basic insight and to allow fast calculations;

b. accurate enough to yield sufficient agreement with measured results.

Some remarks concerning the last item can be found in Section 3.6.

~~~~ ~ez ! . X .

• ~,'i';w-&/1

Figure 2.2. A si.x-}ilase transmission line:

Six paralleL conductors above a conducting

grCJl.llld.

The line model used in this thesis is characterized by the following

assumptions:

1. The high-voltage line is viewed as a homogeneous multi -phase

transmission line with constant parameters along the line, cf. Figure

2.2. Effects of towers and due to the sag of the conductors are

neglected. (Calculations concerning the electrical properties of towers

are given by Okumura and Kijima [1985], while Menemenlis and Zhu Tong

Chun [1982] propose a model that includes the sag of the conductors);

2. Only TEM waves propagate along the line. This requires that the

characteristic transverse dimensions are much smaller than the wave

length used. The TEM character implies that the total field can be

represented in terms of currents through the conductors and voltages

between them. The last assertion is due to the fact that the line

integral of the electric field vector evaluated between two points in a

transverse plane is the same for all paths in that plane;

3. Ground is considered as an additional conductor. With n aetaUtc

conductors we then haven independent currents iu, u=l .. n (the current

through the ground _being determined by Kirchhoff's current law) and n

independent voltages Vu, u=l. .n. between the metallic conductors and

ground (all other voltages can be expressed in terms of these voltages

with the aid of Kirchhoff's voltage law);

4. In due course suitable assumptions are introduced concerning the ohmic

losses of the conductors. Such assumptions are required to guarantee

the TEM character of the wave propagation at least in an approximate

way.

Page 17: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-9-

Sections 2.2 and 2.3. will discuss this model for the single-phase and

multi-phase line, respectively.

Assumption 2 applies if the condition

b < h/4. {2.1}

is satisfied [Lorenz, 1971]. Here i\ is the wavelength pertaining to the

frequency of interest and b is the maximum distance between the conductors

of the transmission line. Condition {2.1} results in an upper limit for the

frequency for which our model is valid. To estimate this upper limit we

consider the typical example b 50 m {maximum distance between metallic

conductor and ground} leading to a frequency limit of 1.5 MHz.

In the presence of losses the rEM-character of the wave propagation is

more or less disturbed. Lorenz [1971] has shown that this effect increases

with growing frequency. However it can be neglected for frequencies below

the limit given by (2.1).

Summarizing it can be stated that the model applies to the transmission

lines under study up to some hundreds of kHz.

2.2. The single-phase line

The telegraphist's equations for a lossless single-phase transmission line

have been derived from electromagnetic theory by Heaviside [1893]. They read

as

a i z

a v z

{2.2}

(2.3}

The constant parameters C and L denote the parallel {shunt) capacitance and

the series inductance per unit length, respectively.

If {weak) ohmic and dielectric losses have to be taken into account

(2.2) and (2.3} cannot be generalized in the time domain. Instead, we have

to confine ourselves to time-harmonic signals for which the phasors V and I

of voltage and current satisfy the pair of equations

d I -YV z

d v -ZI z

where G and R

conductance and

y G+jc.£

z R+jwL

denote the

series {ohmic}

{2.4}

(2.5)

frequency-dependent parallel {dielectric}

resistance per unit length, respectively6

6 A time-domain equivalent of (2.4} and (2.5) does not exist due to the frequency dependence of R and G, which represent integral operators in the time domain. It should be noted that in general also L and C can exhibit some form of frequency dependence.

Page 18: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-10-

Elimination of V or I leads to wave equations for current and voltage only

d2 V 2 w="Y v {2.6}

d 2 I 2 w="Y I (2. 7)

where "Y = J(R + jwL) (G + jc.>C) "propagation coefficient" . {2.8}

Equations {2.4} and (2.5) have travelling waves as solutions [e.g. King,

1955]

V(z) = y{+)exp(-"YZ) + v<-)exp{+"YZ)

I(z) = I(+}exp(-"Yz) + I(-)exp{+"Yz)

where y(+) = Z0

I{+) ,

y(-) = - Z0

I(-)

Z0 = ~ I G + jc.>C "wave impedance"

(2.9)

{2. 10}

{2.11}

(2.12}

(2. 13)

For a qualitative description of travelling-wave phenomena the losses

can be neglected, so that {2.2) and (2.3} apply. These equations have the

solutions

v(z,t) = v+(t - z/c) + v-{t + z/c) (2. 14)

i(z, t} = i+{t - z/c) + i-{t + z/c) (2. 15)

where v+(t) = Z0 i+{t} (2. 16)

v-{t} = - Z0 i ( t} (2.17}

c {LC}~ "velocity of propagation" (2.18}

Zo = (UC)~ "wave impedance" (2. 19}

Here v+(.} and v-(.) represent "travelling waves" in positive and negative

z-direction. From {2.14} through (2.17} it is possible to derive so-called

Bergeron s equations [Bergeron, 1950] for the terminal behaviour of a line

with length~ {cf. Figure 2.3):

v(~.t) + Z0 i{~.t) = v{O,t- ~/c)+ Z0 i(O,t- ~/c)

v(~.t) - Z0 i{~.t) = v{O,t +~/c) - Z0 i(O,t +~/c)

i(O,t}

+

v{O,t}

i{~. t)

+ v(~.t)

(2.20)

(2. 21)

Figure 2.3. A line of

finite length~-

Page 19: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-11-

For the study of protection algorithms we henceforth use the symmetrical

notation of Figure 2.4. Bergeron's equations then transform into the form

v 1 (t} + Zo i 1 (t} = v2(t + ~) - Z0 i 2(t + ~}

v1 (t} - Z0 i 1 (t) = v2(t - ~) + Z0 i 2(t- ~)

(2.22)

(2.23)

The quantities vv(t) + Zo iv(t) and vv(t) - Z0 iv(t) (v=l.2) will be

referred to as incoming and outgoing waves at port v, respectively.

Fi.gure 2.4. A finite

i,(t) ~ Une with traveLling

time ~. ... + v 1 ( t) v2(t)

2.3. The multi-phase line

In general a high-voltage line consists of n metallic conductors plus

ground. Such a system of (n+l} conductors can be described as an n-phase

transmission line through generalizing (2.4) and (2.5) [e.g. Bewley, 1933:

Wedepohl, 1963; Djordjevic et al., 1987]. The result reads as

{2.24)

(2.25)

The n-dimensional vectors y(P) and I(p) are formed by the phase voltages

(voltages between the metallic conductors and ground) and the phase currents

(currents through the metallic conductors), respectively. The nxn matrices

z(P) and y(P) are formed by the series (self or mutual) impedances and

parallel (self or mutual) admittances per unit length, respectively. Both

matrices z(P) and y(P) are symmetrical. Elimination of the current vector

from {2.24) and (2.25) gives rise to a second-order wave equation for the

voltage vector:

d2V{p) (p) (p) (p) ~=Z Y V {2.26)

Similarly the current vector satisfies

(2.27}

In the limit of a Lo~~Le~~ line we obtain a pure TEM wave for which a close

relation exists between z(P) and y{P), for the product of z(P) and y{P)

Page 20: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-12-

(which are both imaginary) equals the unit matrix times a scalar constant:

z(P) y(P) y(P) z(P) = 72 U

7 jw/c ,

(2.28)

where c denotes the velocity of light and U denotes the unit matrix. The

matrix equation (2.26} then represents a set of n ancoaPtea wave equations,

leading to n different waves having equal propagation coefficients (i.e.

equal velocities of propagation). the same holds for (2.27) describing the

phase currents. Olrrent and voltage for each phase satisfy {2.14) through

(2. 19).

For a to!l!lff line the matrix products z(P )y(P) and y(P )z(P) are no

longer diagonal so that (2.26) and (2.27) each represent n coaPtea wave

equations. To uncouple Equation {2.27) "component currents" I(c) are

introduced according to

(2.29)

where the. transformation matrix Q has to be chosen such that I(c) again

satisfies a set of uncoupled equations. Insertion of (2.29) into (2.27),

then leads to

d21(c) -1 y(P)z(P) Q 1(c) . w- = Q (2.30}

To achieve the above aim the transformation matrix Q has to be composed of

the (suitably normalized) eigenvectors of the matrix product y(P)z(P).

Equation {2.30) then transforms into

d 2 I(c) 2 {c) w- = 7 I {2.31)

where 72 = Q-1y(P)z{P)Q (2.32)

is a diagonal matrix. The general solution of (2.31) is

I(c){z) = exp(-7z} I{c+) + exp(72) I(c-) . (2.33}

From (2.33) together with (2.29) and (2.24) the general solution of the set

of equations (2.24) and {2.25) is found. It reads as

I(p)(z) = Q exp{-72) I(c+) + Q exp(72) I(c-). (2.34)

y(P){z) = [y(P)]-1

Q7 exp(-72) I(c+)_[y(P)]-1

Q7 exp(72) I(c-) (2.35}

The constant vectors I{c+) and I(c-) are determined by the boundary

conditions. The expression exp (7z) denotes a diagonal matrix whose elements

are formed by taking the exponent of the corresponding element of the

diagonal matrix 7Z·

In case all elements. except one, of I(c) equal zero, the resulting

current and voltage distribution travels along the multi-phase line without

Page 21: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-13-

changing its structure. Such a combination of voltages between and currents

through the conductors is called a mode or modal wave. So the elements of

the component current vector indicate which modes are present in the phase

currents. The current vector belonging to such a modal wave is an

eigenvector of the matrix product y(P)z(P), containing the coefficients of

the right-hand members of the coupled wave equations (2.27) for the currents

through the conductors. As expected the corresponding voltage vector is an

eigenvector of z(P)y(P), containing the coefficients of the wave equations

(2.26) for the voltages between the conductors.

Although {2.34) and (2.35) fully describe the wave behaviour of the

n-phase transmission line, some authors [e.g. Wedepohl. 1963] make use of

two transformation matrices instead of one. Apart from component currents

I(c), "component voltages" V(c) are introduced according to

y(P) = sv{c) . (2.36)

Such an introduction is only attractive if it is possible to derive

single-phase {frequency domain) equivalents of Bergeron's equations for the

component quantities. In that case each component can be described

independent of the others. From (2.34) and (2.35), together with {2.29} and

(2.36) the following equation is derived for the terminal behaviour of a

line of length~ (cf. Figure 2.3 and Equation 2.20):

y(c)(~) + z~c)I(c}(~) = exp(-~) {v(c)(O} + ~c)I(c)(O)} ,

where z1c} = s-t [y(P)r1

Q 7 "wave impedance matrix".

(2.37)

(2.38}

To obtain a set of single-phase equations, the voltage transformation matrix

S must be so chosen that the matrix ~c) becomes diagonal. It can be proved

that each matrix S leading to a diagonal matrix z~c), is a matrix of

eigenvectors of the matrix product z(P)y{P). Then {2.36) will uncouple the

wave equation for the voltage vector {2.26). Within the computer program EMTP {cf. Chapter 3) a voltage trans­

formation matrix S is derived from Q through the equation

{2.39)

where st denotes the transposed of s. Such a choice will lead to a diagonal

matrix z1c) if y{P) and z{P) are symmetrical and all eigenvalues of z{P)y(P)

are different. For an actual line the first condition will always be met,

the second one might not be fulfilled in a very limited number of

situations.

Page 22: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-14-

As the wave impedance matrix Z~c) depends on the choice of the

transformation matrices, their normalization deserves special attention.

Within EMTP, the matrix Q is normalized such that for each column (i.e. for

each eigenvector) the sum of the squares of the real parts equals unity and

the sum of the squares of the imaginary parts is minimal.

Recently it has been shown [Brandao Faria, 1988] that some transmission

line configurations have a non-diagonizable matrix product y(P)z(P)_ In that

case the above theory fails and the resulting travelling waves are no longer

of the form given in (2.34) and (2.35). A more general solution of the

multi-phase transmission line equations, covering this nondiagonalizable

case is given by Brandao Faria and Borges da Silva [1986]. Such a

degeneration is always 11mi ted to an isolated frequency for a lossy line.

Whether the degeneration also appears on a physical line or is just a

consequence of the approximations of the model is not yet clear [Luis

Naredo, 1986; Olsen, 1986].

2.3.1. The balanced single-circuit line

The balanced single-circuit 1 ine is a hypothetical line where all three

metallic conductors are considered to behave equally. Since in that case the

conductors need to have equal distances to each other and to the ground

plane, the balanced single-circuit line is physically impossible7 In

reality the differences in distance are relatively small so that the

balanced single-circuit line is useful as a first-order description. Due to

the symmetrical nature of the {hypothetical) structure the resulting

equations are of a simple form. These equations will be used as a basis for

most of the protection algorithms discussed in forthcoming chapters. For a

balanced single-circuit line the z{P) and y{P) matrices are of the following

structure (s stands for "self", m for "mutual"):

z zz l [y yy

z{P)= s m m

y{P) s m m

z z z • y y y {2.40) m s m m s m z z z y y y m m s m m s

The matrix products z{P)y(P) and y{P)z{P) are of the same symmetrical

structure. The eigenvalues 712 (1=1,2,3) are found as

2 71 (Zs + 2Zm){Ys + 2Ym)

732 = (Zs - Zm){Ys- Ym)

7 Such a symmetry is, however, possible for a three-phase cable.

(2.41)

{2.42)

Page 23: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-15-

while a general expression for the matrix of eigenvectors reads as

(2.43)

In this case there is a "homopolar" or "zero sequence" wave with equal

currents through all three phase-conductors. closing through ground and two

"aerial" waves restricted to the phase conductors. An often used

transformation matrix satisfying {2.43) is

1 "] 1

:.] -l 1 Q 1 a2 a2 Q =3 a2 (2.44)

1 a a a

with a=exp (j2Jr/3); Voltages and currents under this transformation are

known as "symmetrical components".

Another modal transformation, used in algorithms for travelling

wave-based protection is the following one:

[

1 1 2

Q = t 1 -2 -1

1 1 -1

(2.45)

By using this transformation, component quantities are derived from

(measured) phase quantities through simple calculations. Figure 2.5 shows

the current distributions for this transformation.

0 ® 0

0 0 0 0 0 ®

X X X

2.3.2 The balanced double-circuit line

Figure 2.5. Current distribu­

tions corresponding

homopotar unue (left)

aerial unues on a

stngte-circutt line.

to the

and the

balaru:ed

A balanced double-circuit line consists of six (metallic) phase conductors

and one reference conductor (ground). The phase conductors are divided into

two groups of three. called circuits. Each phase conductor is considered to

have the same distance to ground. The distances between each pair of

conductors within one circuit are equal. so are the distances between a

conductor in one circuit and a conductor in the other circuit. Again this

situation is physically impossible but it provides us with a simple line

Page 24: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-16-

model. For the balanced double-circuit line z<P) and y{P) are of the

following structure {d stands for "double circuit")

z z z zd zd zd s m m

z z z zd zd zd m s m

z z z zd zd zd m m s z{P)

zd zd zd z z z {2.46) s m m

zd zd zd z z z m s m

zd zd zd z z z m m s

y y y yd yd yd s m m

y y y yd yd yd m s m y y y yd yd yd m m s

y{P) yd yd yd y y y {2.47) s m m

yd yd yd y y y m s m

yd yd yd y y y m m s

Three different eigenvalues are found:

2 {Z + 2 z + 3 Zd) {Y + 2 y + 3 Yd) {2.48) "'t s m s m 2 {Z + 2 Zm - 3 Zd) {Y + 2 y - 3 Yd) {2.49) "12 s s m 2 2 2 = 'Ys2 = {Z - z ) {Y - Ym) {2.50) "!3 "14 "'s s m s

with the following general expression for the matrix of eigenvectors:

Q, Qt2 Qt3 Qt4 Qts Qt6

Q, Qt2 Q23 Q24 Q25 Q26

Q, Qt2 Q33 Q34 Q35 Q36

Q Q, -Qt2 Q43 Q44 Q45 Q46 {2.51)

Q, -Qt2 Q53 Q54 Q55 Q56

Q, -Qt2 Q63 Q64 Q65 Qss

where Q1j + ~j +Q3j = 0 and Q4 j + ~j + ~j = 0, j = 3,4,5,6.

"ft is the propagation coefficient of the "homopolar wave", "{2 of the

"double-circuit wave" going "up" in one circuit and "down" in the other. "{3

through "'s correspond to the "single-circuit waves" closing inside each

circuit. An example of such a transformation is found as {cf. Figure 2.6)

Page 25: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-17-

1 2 4 0 0 1

1 -4 -2 0 0 1 1 -1 -1 -1

Q=1/6 1 2 -2 0 0 Q-1_ . - 0 -1 1 0 0 0 (2.52)

1 -1 0 0 2 4 0 -1 0 0 0

1 -1 0 0 -4 -2 0 0 0 0 -1

1 -1 0 0 2 -2 0 0 0 1 0 -1

0 0 0 ®

0 0 0 0 0 0 e @

""" >< X :.

@ 0 0 0

0 0 0 0 @ 0 0 0

0 @ 0 0

0 0 0 0 0 0 @ 0

Figure 2.6. Current distributions corresponding to the homopoLar wave (top

Left), the doubLe-circuit wave (top right) and the singLe-circuit waves on a

balanced double-circuit line.

2.4. Travelling waves in high-voltage networks

2.4.1. A subdivision of transients, according to their origin

The transients occurring in a high-voltage network can be divided into three

groups, according to their origin.

1. ~~~~eat~ caa~ed ~ ~~LtchLn~ oPe~tLon~ Ln the netwo~

These can be called on-purpose operations, because there is always

someone or something giving a conunand to open or close the switch.

Typical examples are:

energizing an unloaded line:

deenergizing a short-circuited line:

connecting two separated high-voltage networks.

Page 26: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-IS-

2. ~~an~Lent~ ha~Ln~ theL~ caa~e out~Lde the net~k

High-voltage lines consist of very long wires (tens of kilometers or

more). These are very good antennas, so radio signals are easily picked

up. Other examples are very low frequency (0.01 Hz} currents induced by

ionospheric currents [e.g. Pirjola and Viljanen, 1989] and injected

signals with a frequency of some kHz used for communication purposes. A

more spectacular case is a lightning stroke to a high-voltage line or

somewhere in the vicinity of a high voltage line.

3. ~~~Lent~ caa~ed log. taait LnLUatLoo

Faults are inadvertent, accidental connections between phase wires or

between one or more phase wires and ground [Blackburn, 1987]. Causes

for faults (short circuits} are lightning (induced voltage or direct

strike}, switching overvoltages, wind, ice, earthquake, fire, falling

trees, flying objects, physical contact by animals or human beings,

digging into underground cables and so on.

These three groups will be further discussed in Section 2.4.3 through 2.4.5.

A number of studies have been performed during the last years to

determine the number of transient phenomena that occur in a high-voltage

network. All studies make use of a transient recorder that is· triggered by a

sudden change in voltage or current. The number of recorded phenomena

depends largely on the kind of measurement and on the position in the

network. Further the seasons turn out to have influence on the frequency of

recorded phenomena.

During a three-year monitoring period in a 500 kV substation and in a

138 kV substation a total of 341 phenomena has been recorded [EPRI, 1986];

190 of them were caused by switching operations, 114 by lightning strokes

and 37 by faults. A study by EdF (Electricite de France) in the 400 kV

network [Barnard et al., 1984] showed 93 transients caused by faults and 19

caused by switching operations in a period of about 2 years. Malewski,

Douville and Lavallee (1987] found a total of 300 transient phenomena during

a two year monitoring period in a 735 kV substation. A four-month

(july-october) monitoring period in the Dutch 220 kV network yielded 39

lightning-caused transients (27 occurring within one week), 1 due to a fault

and 3 due to switching operations [Koreman, 1988]. Johns and Walker [1988]

found 93 transient phenomena within 39 days (December '83 till February

'84), 29 of which occurred within 3 hours.

2.4.2 Superimposed quantities

A high-voltage network is fed by 50 or 60 Hz sources (in the remainder only

50 Hz will be used). During an undisturbed situation all voltages and

currents in the network are sinusoidal in time. The sinusoidal voltages and

Page 27: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-19-

currents as existing before a certain disturbance will be called

"un.di,(l.tu'tl.ect ~titLe().". After the disturbance this term denotes their

continuation, i.e. the fictitious voltages and currents that would have

occurred without disturbance.

After a transient due to some disturbance a new sinusoidal state will

be reached which may or may not differ from the undisturbed state. To study

the transient phenomenon it is sometimes attractive not to use the actual

voltages and currents but "(l.U/>e'tLIII(Jo(l.ed ~titLe().". Their values are

defined as the difference between the actual and the undisturbed values.

The disturbance can be any of those described in the previous section.

We illustrate the concept of superimposed quantities by means of a fault on

a single-phase line. The undisturbed network is shown in Figure 2.7.

Figure 2.7. Undisturbed values.

Undisturbed voltages at line terminal A. at the future fault position F

and at line terminal Bare given as

VA (t) =VA sin (~Uot + <PA) , (2.53}

VF (t) = VF sin {~Uot + <PF) • (2.54)

VB ( t) =VB sin (~Uot + <PB) (2.55)

respectively.

Figure 2.8 shows the network situation after the occurrence of the

fault at time-zero. Actual voltages at A, F. and Bare denoted by vA(t),

vF(t), and vB(t), respectively.

t:(tl F

Figure 2.8. Actual values: uF (t) = 0, t)O.

Page 28: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-20-

The superimposed quantities, being the difference between the actual

values of Figure 2.8 and the undisturbed values of Figure 2.7 are given in

Figure 2.9.

A . F

Figure 2.9. Superimposed vatues: vF (t) = 0, t<O.

Superimposed voltages at line terminal A, at the fault position F, and

at line terminal B are given as

VA (t) =VA (t) - ~A (t) (2.56)

{ -~F (t)

t < 0 VF (t) = VF (t) - ~F (t) t ) 0 (2.57)

VB (t) = VB (t) - \IB (t) {2.58}

respectively.

2.4.3. Transients caused by switching Olli!rations

Figure 2.10. Travetting waves initiated during tine energizing.

As an example Figure 2.10 shows the configuration for energizing one of the

circuits of a double-circuit line. Closing the circuit breaker (1) leads to

voltage jumps on both sides of it. This sets up travelling waves into the

line to be energized (2) as well as into the feeding network (3). At the

remote line-terminal (4) the circuit breaker in the line-to-be-energized is

open. At this discontinuity a part of the wave is reflected (5) and through

the coupling with the second circuit a part travels into the network behind

the remote line-terminal (6). The reflected wave (5) is again reflected at

the circuit breaker (1} and so gives rise to multiple reflections.

Figure 2.11 shows the voltages during 1 ina-energizing as measured on

the line side of the open circuit-breaker (4).

Page 29: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-21-

f 1.2

vr (pu)

0

0,8

f 1,

~r\1 Vs ~pu) -

1ms 0,4

lo,4 vto

(pu)

1,2

2.4.4. Transients caused by lightning

Figure 2.11. Voltages at the open

line terminal measured during

line energizing. Adopted from

[Kersten and Jacobs, 1988]

There are three different mechanisms for a lightning stroke to interfere

with a high-voltage line; dependent on the distance between the position of

the stroke and the phase conductors.

1. ~ LLghtnLng ~t~oke ~oaemhe~e Ln the ~LcLnLtv ot the LLne

This can be a stroke between a cloud and earth as well as a stroke between

two clouds. In most cases the waveform of the induced voltages is bipolar

with substantial amplitude being attained in the first few microseconds.

Theoretically amplitudes higher than 1 MV are possible for a 100 kA stroke

at a distance of a few hundreds of meters from the line [Eriks~on, 1976].

Lightning strokes to earth of high current amplitude in the vicinity of a

high-voltage line are rare due to the attractive effect of the line. But

high objects (e.g. trees) close to the line can increase this possibility.

Measurements show induced voltages up to 200 kV [Cornfield and Stringfellow,

1974].

Page 30: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-22-

De la Rosa et al. [1988] have installed a single-phase line in Mexico,

in a region with a high ground-flash density. Their measurements show that

lightning strokes tens of kilometers away from the line can induce voltages

of some kV. An overvoltage of 244 kV has been measured for a stroke at a

distance of 4.5 km. It appears that a stroke next to a line will create the

highest overvol tage some distance further down, which can be explained

electromagnetically [Cooray and De la Rosa, 1986].

l v

(kV)

-40

-SOL---------------------------------------------------~

Figure 2.12. TypicaL voLtage shape due to a Lightning stroke dose to a

high-vottage tine, adopted from [Koreman, 1988}.

A typical shape of the voltage pulse due to a nearby stroke is shown in

Figure 2.12. The superimposed voltages for the three phases are shown, with

the vertical axes shifted with respect to each other.

2. d LLghtnLng ~t~oke to a ~hLeLdLng ~L~e o~ to a t~e~

To prevent dangerous lightning strokes to phase conductors, shielding wires

are used. The so-called electro-geometric theory describes how a lightning

stroke develops [e.g. Eriksson, 1976]. According to this theory only

lightning strokes below a certain current amplitude can reach the phase

conductors. So all high-current strokes will reach the shielding wire or a

Page 31: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-23-

tower. This causes intense electromagnetic fields, leading in a few cases to

flashovers between phase conductors and ground.

When the lightning stroke does not lead to such a flashover the three

phases are influenced in about the same manner. i.e. the induced voltages

(and currents) in the three phases are of about equal shape and magnitude.

Mainly a homopolar wave is initiated. The voltage amplitudes are tens of

kilovolts.

3. Ell Ughtni.ng o.t'!.oke to a Pkao.e condu.ctO'l-

When the lightning strikes directly to a phase conductor. this will cause a

large voltage between that conductor and the other conductors {including

ground). If this voltage exceeds the breakdown voltage of the insulation a

flashover wi 11 occur leading to a fault. According to electro-geometric

theory such a flashover will never occur if the shielding wires are

correctly positioned. A direct stroke is often called a shielding failure,

although the word is sometimes reserved for direct strokes leading to a

flashover.

Figure 2.13 shows voltages due to a direct stroke leading to a fault.

They have been measured in a substation about 10 km from the fault. In phase

1 a negative spike is visible followed by a transient due to the

single-phase fault. At the fault position the spike must have been much

higher. The amplitude reduction takes place on the 10 km line between the

position of the stroke and the substation and in the substation between the

line being hit and the line being monitored. The negative slope of the spike

corresponds to the lightning current, the positive slope corresponds to the

flashover between the phase being hit and ground.

A stroke not leading to a fault causes a high voltage spike in the

phase that has been hit . The other phases show a 1 ower vo 1 tage spike.

Whether the spikes in the other phases are of the same polarity or of

opposite polarity is still a matter of debate. The coupling between the

phases would lead to a spike of equal polarity [e.g. Anderson, 1985] but the

release of the induced charge would lead to spikes of opposite polarity.

Figure 2.13 shows spikes of opposite polarity.

Kinoshita et al. [1987] present measurements of the simultaneous

occurrence of a positive spike in one phase and a negative in another. This

is caused by a negative stroke followed, almost immediately, by a positive

stroke somewhere else in the same cloud. If both strokes hit a phase

conductor the above phenomenon can be observed.

Page 32: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-24-

Q5 -1,0 t(ms}

t1 fase2

Q5 -1,0 Hms)

~~--------------------------------------------------~

Figure 2.13. Transient voltages caused by a. lightning stroke to a. JJw.se

conductor leading to a. Flashover. adopted from [Koreman. 1988].

2.4.5. Fault transients

A fault (short circuit) on a high-voltage line, normally implies a voltage

jump at the fault position. This voltage jump leads to travelling waves that

can be detected in a large part of the network. All protection principles in

this study use these travelling waves to retrieve information from the

fault.

In most studies of fault transients the resistance of the conducting

path at the fault post tion is neglected. Although there is always some

resistance present, the approximation is certainly acceptable for solid

faults or those with only a small arc distance. An analysis for longer arc

distances is given by Cornick. Ko and Pek [1981]. These authors also show

that the fault initiation (due to the spark) takes place within one

microsecond. After that it takes a few microseconds for the arc to develop.

During this time the arc voltage drops from 100 V/cm down to about 10 V/cm.

For arcs across wooden structures (wood-pole-lines, flashover to a tree) the

arc voltage-gradient drops from 800 to SO V/cm.

Page 33: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-25-

As long as the pre-fault voltage is large compared to the post-fault

(arc) voltage, the latter can be neglected. For an arc length of 10 meter

and an arc-voltage gradient of 10 V/cm, the pre-fault voltage must be much

higher than 10 kV. As the systems studied have voltage amplitudes of

hundreds of kilovolts, the arc voltage will not be of great influence on the

fault transients. Of course this is no longer true in case of a pre-fault

voltage close to zero. But then a high resistive fault (= long arc distance)

will (generally) not occur.

Faults on high-voltage lines can have many causes. The main cause for

faults on the high-voltage lines is lightning. According to a study of a

number of networks all over the world, about 40% of all faults are

lightning-caused [Anderson. 1985]. This value shows a large deviation for

different utilities. A large part of the lightning-caused faults are

multi-phase or double-circuit. According to Sargent and Darveniza [1970],

40% of the lightning-caused faults on double-circuit lines are double­

circuit faults. Figure 2.14 shows some double-circuit faults caused by

lightning. Other important fault causes are storm (10-30%} and galopping

conductors [Mackay, Barber and Rowbottom, 1976; Leppers, 1985].

R w X 0 0 0 X 0 0 X

s v 0 0 X X 0 0 0 0 X X

T u X X X 0 X 0 X 0 0

Figure 2.14. Examptes of doubte-circuit fautts caused by tightning [adopted

from Sargent and Dnrventza, 1970]. x:fautted phase, o=non-fautted phase, the

phase order is shown on the teft.

From a number of studies the following distribution of faults among

different types can be concluded [Anders, Dandeno and Neudorf, 1984, Light,

1979; Recker, Reisner and Waste, 1986; Liew and Darveniza, 1982].

Single-phase-to-ground 7o-90%

Phase-to-phase 10-20%

Two-phase-to-ground and three phase: 5-15%

single-circuit faults

Double-circuit faults

75-98%

2-25%

Page 34: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-26-

3. Network modelling

Chapter 2 dealt with the transition from a high-voltage line (an actual

physical inhomogeneous structure) to the simplified model "transmission

line". In this chapter we further elaborate the concept "multi-phase

transmission line" and present a number of pertinent data which are in

current use in modern computer programs. Two of these programs (cf. Section

3.2 and 3.3) have been used in this thesis to determine transient voltages

and currents in a high-voltage network. Such simulations are required to

test protection algorithms, as described in forthcoming chapters.

3.1. Impedance and admittance matrices

Extensive analysis is available concerning the determination of the z(P) and

y(P) matrices for configurations consisting of a set of thin metallic

conductors (cf. Figure 3.1). The basic situation studied in this context is

that of a single circular conductor above a homogeneously conducting

half-space (cf. Figure 3.2). Parameters for two or more metallic conductors

are approximately evaluated under the assumption that the electromagnetic

field can be viewed as a linear combination of the individual fields of the

single-conductor configurations. Minor possible refinements reckoning with

the vertical dependence of the conductivity of the ground (as discussed by

Wedepohl and Wasley [1966] and by Nakagawa, Ametani and Iwamoto [1973]) will

be left out of consideration.

'-0 0

transmtsston ltne consisting of three 0 Figure 3.1. The cross-section of a

conductors and a conducting half-space.

l///////J/l/77

Carson [1926] was one of the first who evaluated transmission line

parameters. He found expressions for the elements of the impedance matrix

z(P) that nowadays serve as a reference under the name "Carson's

equations". These are used in most modern computer programs for the analysis

of transients in high-voltage networks, including the programs used in our

study. The elements of the matrix y(P) are determined from .the electrostatic

fields.

Similar expressions for the transmission line parameters have been

found at about the same time by Rlidenberg [1925], Mayr [1925] and Pollaczek

[1926]. Whereas these authors only give integral expressions, Carson [1926]

Page 35: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-27-

rewrites his integral solution in the form of fast converging infinite

series. This series solution has certainly contributed much to the

widespread use of Carson's equations.

_yz

/

X

~-------------~--------~/

h

Figure 3.2. Configuration studied by

Carson [1926].

The configuration under study is depicted in Figure 3.2. Following

Carson [1926] {and in conformity with Chapter 2) we consider a time-space

dependence of the form exp(jwt-?£), where~ is the propagation coefficient

to be determined. While y(P) is assumed to have its {lossless, i.e.

imaginary) electrostatic value, expressions for the {complex) elements of

z(P) are evaluated under several low-frequency approximations.

In later years other authors have found expressions for the line

parameters under less simplifying approximations. Wise [1948] finds that the

elements of the admittance matrix y(P) have to be corrected as a consequence

of the finite conductivity of the ground. However his correction terms are

small for normal configurations and frequencies below 1 MHz [Hedmann, 1965].

Wedepohl and Efthymiadis [1978] evaluate the electromagnetic field due to a

current with an exponential time-space dependence and find a "modal

equation" which is solved numerically [Efthymiadis and Wedepohl, 1978]. For

practical high-voltage lines and frequencies up to a few hundreds of kHz,

their value of the propagation coefficient ~ again does not considerably

differ from that found from Carson s equations. Wait [1972] derives an even

more general modal equation that is solved by Olsen and Chang [Olsen, 1974;

Olsen and Chang, 1974; Chang and Olsen, 1975]. Contrary to Wedepohl and

Efthymiadis [1978] they find more than one solution. It appears that a

single wire above ground can support two discrete modes (apart from a

continuous mode spectrum). One of the discrete modes {the "transmission line

mode") corresponds to Carson's solution, the other (the "fast mode") is

associated with a high phase velocity and a low damping. According to Olsen

and Pankaskie [1983] it is safe to assume that only the transmission line

Page 36: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

mode is present when

h ( i\/20 .

-28-

(3. 1)

where h is the height of the conductor and A is the wavelength pertaining to

the frequency under consideration. For a height of 50 meters a limit of 300

kHz is found. This admits the final conclusion that for a high-voltage line

Carson's equations are valid up to a few hundreds of kHz.

3.2. The computer program EMTP.

3.2.1. The solution method used in EMTP

The "Electromagnetic transients program" (EMTP) is a universal computer

program for the calculation of electromagnetic transients in high-voltage

networks. It has been developed in the late sixties by Bonneville Power

Administration, Portland, Oregon and the University of British Columbia,

Vancouver, Canada. After a few years it was in widespread use through

computers all over the world, where many people provided the program with

extensions. This rapid growth in use as well as in size can be described to

the compatibility (it only uses standard FORTRAN) and the availability (it

was public domain software). Although the term EMTP is already used as a

standard, there still exist many program versions. In order to create one

real standard version, Leuven EMTP Center8 has started to co-ordinate all

improvement efforts. As long as this standard does not exist, it is

necessary to tell what version has been used. All EMTP calculations

described in this thesis are performed with the M39 version on an

APOLLO-domain computer.

EMTP is able to calculate voltages and currents in networks consisting

of resistances, inductances, capacitances, single and multi-phase

~-circuits, transmission lines9 and other elements. Each network element is

represented by means of an equation that relates a node voltage at time t to

node voltages and branch currents at times t-kAt, k=l,2, ... By combining

all element equations and the pertinent Kirchhoff's equations a matrix

equation is derived for a network of n nodes:

G.v(t) = j(t) hist(t) - Ge e(t)

8 Leuven EMTP Center Kard. Mercierlaan 94 3030 Heverlee Belgium.

(3.2)

9 In the EMTP-related literature the name "distributed-parameter lines" is used instead of transmission lines.

Page 37: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-29-

where v( t} vector of unknown voltages,

j(t} vector of current sources,

e(t} vector of voltage sources,

hist(t} vector of "history terms" taking into account voltages

from the past,

G, Ge nxn matrices determined by the network topology and the

values of the elements.

Starting from a (given} situation voltages are calculated for equidistant

points in time. Finally, the currents can be determined with the aid of the

element equations. More details on EMTP are given by Dommel [1986].

3.2.2. The LINEa:>NSTANTS routine

32.4 31.4

0 24.4 0

• • s 17.4 w

• • • • R ~T v u

/}\0.~ \tf..--~ , __ .7

('I) ~~ ,...: ...

Figure 3.3. Cross-section of

a specific

tine. The

transmission

open circLes

correspond to the shielding

wires, with an outer

diameter of 2.2 em and an

inner df.am.eter10 of 0.8 em.

The cLosed circLes corres­

pond to a bundLe of three

conductors as sholm. in the

insert. Each conductor has

outer and inner diameters of

2.8 and 0.8 em, respectiveLy. ALL dimensions are given in meters.

From Carson's equations it is possible to determine impedance and admittance

matrices for a multi-phase transmission line. This is done by EMT~ s

LINECONSTANTS routine. We illustrate the routine by means of the 20-phase

transmission line depicted in Figure 3.3. It is a model of the high-voltage

line of Figure 2.1. The average height of the sagging conductors in the

transmission line model is determined as:

h = t ht + ~ hm ' (3.3}

10 Within EMT~ s LINEmNSTANTS routine wires are considered to be tubular conductors with certain inner and outer diameters. In reality the wires consist of a good conducting mantle and a core with a lower conductivity. Due to eddy-current effects the current will concentrate in the mantle.

Page 38: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-30-

where ht is the height at the tower position and hm is the height midway

between two towers. The resistivity of the ground is taken to be 100 Qm,

which is an acceptable value for over 50% of the world land area. Higher

values might be needed for mountainous terrain and permafrost areas

[OCIR.19SS]. The 20 x 20 matrices y(P) and z(P) are reduced to 6 x 6

matrices by assuming:

the voltage between a shielding wire and ground is zero;

- the voltage between two conductors in one bundle is zero.

From the resulting 6x6-matrices a current transformation matrix Q, a

(diagonal) wave-impedance vector zic) and propagation coefficients 7 are

determined, according to the theory of Section 2.3.

Each column of Q is normalized such that the sum of the squares of the

real parts equals one and the sum of the squares of the imaginary parts is

minimum. In a next step the imaginary parts are neglected. leading to the

following current transformation matrix for the transmission line depicted

in Figure 3.3:

0.46 -0.30 0.53 0.25 0.58 0.16

0.24 -0.20 -0.38 0.54 -Q.35 0.47

Q 0.48 -0.61 -0.27 -0.38 -0.20 -o.51 (3.4)

0.48 0.61 -Q.27 0.38 0.20 -0.51

0.46 0.30 0.53 -0.25 -Q.58 0.16

0.24 0.20 -0.38 -Q.54 0.35 0.47

This matrix considerably differs from that for a balanced double-circuit

line (2.51). Obviously the transformation matrices for a balanced line

cannot be applied to nonbalanced lines. Nevertheless the transformation

matrix for a balanced 1 ine turns out to be sui table for the protection

algorithms to be discussed in forthcoming chapters.

3.2.3. The .!MARTI SETUP routine

A number of numerical transmission-line models are available within EMTP.

The model applied in this study is the ".}MARTI SETUP" proposed by Marti

[1982]. It is the most detailed model available. Whether its results are

close enough to reality is still a matter of debate [e.g. Empereur and

Somatilake, 1986; Lima, 1987; Marti, et al., 1987; Ametani, 1988]. This

question can only be answered by performing field tests (cf. Section 3.6).

The JMARTI SETUP incorporates the frequency dependence of modal wave

impedances and propagation coefficients. The transformation matrix Q is

considered to be frequency independent. (The debate concentrates on this

approximation that might not be valid for low frequencies.)

Page 39: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-31-

In Section 2.3 Bergeron's equations are given for a 1ossless frequency

independent line (2.22 and 2.23). The JMARTI SETUP uses a more general form

[Meyer and Dommel, 1974]. For the single-phase line of Figure 3.4. the

following equations hold:

B1 (w} = H(w).F2{w}

B2(w} = H{w).F1 (w}

where F1 (w} = V1 {w)

F2(w} = V2(w}

+ Z0 {w}

+ Zo(w}

B1 (w} = V1 (w} - Z0 (w}

B2(w) = V2(w} - Zo(w)

H(w} = exp (-'#}

11 {w)

12{w}

11 {w} ,

12(w}

;!! , -y(w) , Z0 (w}

"incoming waves"

"outgoing waves"

"weighting function".

(3.5}

(3.6}

Figure 3.~. SingLe-phase

line of Length ;!!; vot t­

age and current defini­

tions for EKTP' s JlfAKfi

SErUP.

As EMTP uses a time-domain description to calculate voltages and currents,

some simple 1 ink is required between the frequency-domain description of

(3.5) and (3.6} and its time-domain description. To this end the wave

impedance Z0 (w) is approximated by a rational function of jw with real

poles. K

+-n­jw+pn . {3.7)

Satisfactory approximations can be obtained with orders n between 5 and 15.

Figure 3.5. Repre­

sentation of uuve

impedance in JlfAKf I

SETUP. This impedance Z0 {<.J) can be realized by means of a series connection of

resistance-capacitance blocks. as shown in Figure 3.5, where

Ro = Ko .

Ri = K/pi

ci = 1/Kt

i

i

1. .n

1. .n

Page 40: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-32-

The time-domain equivalent of Z0 (w)I(w) is obtained by injecting a current

i(t} in the network of Figure 3.5.

The weighting function H{w} is approximated through

. [ H, H2 H ] H(w) = e-Jc.YT jw+q

1 + jw+q

2 + .. + j;~ .

where T is the travelling time of the highest frequency.

following weighting function in time domain {the "impulse

h(t} = [ H1exp{-q1 {t-r}) + .. + Hmexp(-~{t-r})] U(t-r) ,

(3.S)

This leads to the

response"):

(3.9}

where the step function U{t) is zero for t(O and unity for t>O. According to

Semlyen and Dabuleanu [1975] the time-domain equivalent of {3.5) can be

written, by using (3.9) as

b 1 (t) =a b 1 (t-At} +X f 2 (t-r) + ~ f 2 (t-r-At) , (3. 10)

where b 1 (t) and f 2 (t} are the transform of B1 (w) and F2 (w), respectively.

The parameters a, X and~ depend on the values of Hi' qi and the time step

At. This "recursive convolution technique" accounts for a considerable

reduction in computation time . The above procedure is used for every mode

to determine modal voltages and currents. The node (phase) voltages and

branch (phase) currents are found by using the transformation matrices Q and

S. In our example the value of the transformation matrix Q for a frequency

of 5000 Hz has been used.

The parameters describing a high-voltage line are, for each mode:

the wave impedance for very high frequencies (K0

in (3. 7}); a number of

residues (K1 .. Kn) and poles (p1 .. pn) for the wave impedance; the travelling

time for the highes frequency (T in (3.S)); a number of residues and poles

for the weighting function; and the current transformation matrix Q. Table

3.1 gives those parameters for the line of Figures 2.1 and 3.3. To describe

this line (100 km length) a total of 306 parameters is used.

3.3. The computer program TWONFIL

The simulation capabilities of EMTP are almost unlimited. On the one hand

this makes it very suitable to analyze transient phenomena in detail. On the

other hand it becomes less suitable for a quick overview of a large number

of situations. To overcome the latter limitation we developed the computer

program TWONFIL (Iravelling !aves Qn Honbalanced frequency Independent

transmission Lines). It consists of a number of PASCAL procedures for calcu­

lating travelling waves due to all kinds of faults and switching operations.

The reflection and transmission of waves at various discontinuities as well

as voltages and currents at the relay position can be analyzed.

Page 41: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-33-

-1 II 5'14.8 -. 75E3 . 11£5 '32£5 '70£6 . 53£7 . 15ES . 2JE6 .14£6 '23£6 '36£6 '69£6

.JOEl .29£2 .52E3 .18£5 .99£5 .61E6 .19E7 .47£7 .90£7 .12£8 .24£6 II .1901E-QJ

.28 .12E2 .20£2 .55£2 .55E3 -.13£4 .OOE4 .18£5 .27£7 .29£9 -.29E9

.5iE2 .18£4 .19£4 .28£4 .95£1 .21£5 .21£5 .41£5 .14£6 .13£6 .13£6 -2 12 379.2 .17£4 .20£3 .43E3 .20£3 .61E2 .19£3 .44£1 .12£6 .64£6 '17£7 .45£7 .26£6 .43EI .7JEI .11E2 .19£2 .32E2 .88E2 .18£4 .18£5 .28£6 .72£6 .19£7 .11£6

6 .1721E-()3 .JJ£5 .41£5 .35£6 .39E1 .63EI 10£2 '13£6 .21E6 . 48E6 . 11£7 .11E7 .11£7 -3 ll 259.3 . 19£4 . 26E3 . 83E3 .10E3 . 26E3 . 28£3 . 69£3 . 56E4 . 11£5 . 45£6 .JOEl .45£1 .95EI .17E2 .41£2 .5iE2 .60£3 .47£4 .12£5 .39E6

12 . 1701E-()3 .47E2 .78EI .15£3 .55£3 .17£4 .67£4-.53£6 .70£6 .21£6 .43£6 .liE! -.liE! .91£4 .16£4 .29£5 .11£6 .83£5 .17£6 .20£7 .17£7 .21E7 .33£9 .22£8 .22£8 -1 ll 264.1 .15E4 .72E2 .66E3 .JOE3 .19E3 .17£3 .ISE3 .83£2 .17£3 .35E1 .50£5 .33£1 .45£1 .SSE! .11E2 .20£2 .30£2 .50£2 .81E2 .16E3 .JOE4 .41£5

9 .1719E-oJ .23£2 .JOE3 .31E3 .17£4 .63£4 .13£7 -.10£7 -.51£7 .27£6 .37£4 .46£5 .52£6 .31£6 .28£6 .18£7 .18£7 .51£9 .33£6 -5 II 247.8 .11£4 .51E3 .72E3 .24£3 .10E3 .18£3 .16E3 .78£2 .14£3 .27£4 .42£5 .29EI .48£1 .OOEI .11E2 .18£2 .31£2 .48£2 .78£2 .14£3 .21£4 .37£5

10 .1681£-()3 .10£2 .91£2 .48E3 .76£3 .28£4 .41£5 .44£6 .53£6 .28£7 .ISES .22£4 19£5 .99£5 .18£6 .15E6 .10£7 .62£7 .33£7 .12£8 .39E8 -6 13 273.5 .12£4 .25E3 .77£3 .73E3 .41E3 .45E3 .14£3 .19£3 .26£4 .47£4 .11£5 .52£6 .79Z6 .31El .45El .95£1 .21£2 .32E2 .58£2 .78£2 .17£3 .21£4 .39E4 .ll£5 .43£5 .66E6

12 .1743£-()3 .78E1 .57E2 .61£2 .44£3 .19£4 .39£4 .99£5 .ll£6 .19£7 .20£7 .53-.53 .11£4 .11£5 .10£5 .61£5 .10£6.82£5 .13£7 .62£6 .35£7 .77£7 .31E8 .34£6

.460!5799 -.29982807 .52965392 .24901443 .58179180 .15831060

.21073739 19463382 -.39216777 .51208824 -.34661831 .46861377

.47999595 -.61009901 -.27095114 -.390J0143 -.20335198 -.50531068

.47999596 .61009901 -.27095114 .390J0143 .20335198 -.50531068

.46015799 .29982907 .52965392 -.24901443 -.58179190 .15831060

.21073739 .19463392 -.38216777 -.5420S824 .34661831 .46861377

Table 3.1. Parameters

used within E1ffP to

describe the high

voltage tine of Fig­

ure 2 .1. Given are

successively (for

each IIIOde): the IIIOde

number, the number of

poles to represent

the wave impedance,

the wave impedance

for very high fre-

quenctes, residues

and poles for the

wave impedance, the

number of poles for

the weighting func­

tion, the trave t t in.g

ttme for 'the highest

frequency, residues and poles for the weighting function. The last six tines

give the current transformation matrix.

3.3.1. A general description of TWONFIL

Within TWONFIL. a line is described in time domain by means of the modal

wave impedance matrix Z~ c) and the transformation matrices Q and S=Qt - 1 •

These matrices are evaluated by using EMTYs LINEOONSTANTS routine and are

approximated by omitting their imaginary parts. Further the propagation of

each modal waves is considered to be undamped and without dispersion. The

modes only differ with respect to their propagation velocities and their

wave impedances. This way the existing nonbalance of the multi-phase line is

incorporated. The propagation of each modal wave can now be described by

means of the simple form of Bergeron's equations (2.22 and 2.23).

The TWONFIL model is a modern version of Bewley's lattice diagram

[Bewley, 1963]. TWONFIL provides a number of PASCAL procedures to determine

waves generated during fault initiation and due to switching operations, as

well as reflected and transmitted waves at various discontinuities, and

superimposed voltages and currents {voltage and current jumps) at the relay

post tion. These voltages and currents can be used for the testing of

protection algorithms. After a certain reflection pattern has been chosen

Page 42: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-34-

some procedures can be taken from a 1 ibrary to write a PASCAL program to

calculate detection functions for all possible fault types and

fault-initiation-angles.

There are several arguments to use our new program for the study of

algorithms for travelling-wave-based protection:

The simplicity of the model makes the program fast and easy to implement

under different situations (line type, phase-initiation-angle, faulted

phase). so that the behaviour of protection algorithms in thousands of

fault and non-fault situations can be studied;

- Since travelling-wave-based protection detects a fault from information

obtained from the first travel! ing waves generated by the fault, the

(neglected) attenuation and dispersion do not yet play an important role;

-A comparison with EMTP (cf. Section 3.3.3) shows the approximations to be

acceptable;

-The results of the TWONFIL study can be a starting point for a more

complex study (e.g. EMTP): only the worst cases need to be studied which

leads to an enormous time saving.

3.3.2 An example of TWONFIL-calculations

i IF

j-,

I I I

I I r?r- 1

z~~ (C) I 0 F I

I z• I - - I! L/ ! I I

! I 1 i

Figure 3.6. FauLt initiation on a doubLe-circuit tine.

We demonstrate the TWONFIL program by calculating the superimposed voltages

and currents at the relay position, due to a fault somewhere on a line.

Consider the situation shown in Figure 3.6. A fault is initiated at the

fault position F. This will generate waves travelling from F to the relay

position R. At R the double-circuit line is terminated by a three-phase

busbar. The latter is connected to a network with homopolar mode impedance M M

Z0 and aerial mode impedance Z1 .The (superimposed} travelling waves that

Page 43: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-35-

originate from the fault position during a fault with earth connection11

satisfy the boundary conditions

= 0

= e m

for j non-faulted phase

form= faulted phase ,

and em = voltage jump caused by the fault.

(3.11)

{3.12}

During a fault without earth connection the waves satisfy the boundary

conditions

i~p) = 0 J

for j =non-faulted phase (3.13)

~ ik(p) = 0 fork= faulted phases , (3.14}

V(p}_v(p)_ e i j - ij for i,j = faulted phases , {3.15}

and eij =voltage jump caused by fault.

Because the fault initiation is supposed to be the only source of travelling

waves. there are, during a certain time, only waves travelling away from the

fault into the line section between F and R. At F this reads as

(3.16)

By using i(p}=Q i(c). v(p}=S v(c) and (3.16) together with (3.11} and (3.12)

or (3.13) through {3.15} voltages and currents at the fault position are

calculated. The incoming waves at F generated by the fault initiation are

given by

(3.17)

From Bergeron's equations it follows that these waves arrive at Rat a later

time and there play the role of outgoing waves G( c} with each individual

mode k having a characteristic delay:

~c)(t} = F~c)(t--rk) . (3.18)

The terminal impedance z(P) at R is a combination of the three-phase busbar

and a connected network (Z0 *, Z1 *>. At the relay position R (with inverted

reference direction of i} the following equations hold: v(c)- z(c)i(c) = G(c}, (3.19}

v(p} + z(P)i(p) = o . (3.20}

11 In case of a fault with earth connection one or more phase conductors come into (electrical) contact with ground. Therefore their voltage jumps to zero. In case of a fault without earth connection two or more conduc­tors come into contact with each other.

Page 44: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-36-

By using the above equations in combination with i(p}=Q i(c}and v(p}=S v(c}

a TWONFIL-procedure determines voltages and currents at the relay position.

3.3.3. TWONFIL versus EMTP

Figure 3.7: FauLt position

and reLay position used in a

certain TWONFIL-study.

No direct comparison has been made between TWONFIL and reality. Instead

TWONFIL has been compared with EMTP whose reliablity is discussed in Section

3.6.

Figure 3.8. shows the stylized "forward detection functions" 12 (i.e. a

linear combination of certain voltages and currents) during a fault on the

parallel circuit. The configuration under study is shown in Figure 3.7. The

spike (value 1) is caused by the difference in travelling time between the 13 different modal waves The height of the spike cannot be reproduced

exactly by TWONFIL due to the neglection of the damping. But a relay for

travelling-wave-based protection contains a low-pass filter. This smears out

the fine details of the measured signals so that the fi I tered versions of

EMTP and TWONFIL become almost identical. Value 2 is reached when all modal

waves have arrived at the relay position. This value can be reproduced

almost exactly by TWONFIL. After a number of reflections between the fault

and the busbar value 3 is reached. This value turns out to correspond to the

TWONFIL value for a "close fault", where it is assumed that the voltage at

the relay position equals that at the fault position.

Figure

TWONFIL resuLts.

3.8. ReLation

resuLts and

betllleen

EKfP

12 Forward detection functions are used for directional detection as discussed in detail in Chapter 5.

13 More about these spikes and the differences in travelling time can be found in Section 4.3, subsection ~pLke~ Ln the detectLon tanctLon~.

Page 45: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

3.3.4. Line types studied

17.4 24A

0 0 0

To

type A

17.4

0 0

0 0

0 ;J 0

type B

-37-

t~-00 w··

type C

Figure 3.9. Line types

used for TWONFIL-study.

The basic line type is that depicted in Figure 3.3. Because the phase

conductors are in a triangular configuration, the impedance and admittance

matrices will be fairly symmetrical. This line type will be denoted as line

type A. The two other (less symmetrical} line types used in our study are

also shown in Figure 3.9. Insulation distances and bundle conductors are the

same as for line type A. Differences are in the position of the phase

conductors. Line type B is a vertical configuration, line type C a

horizontal one.

3.4. Other network elements

So far only the modelling of high-voltage lines has been discussed. But a

high-voltage network contains other elements, too. These are situated in or

near a high-voltage substation, which makes the representation rather easy.

The spatial extent of such a substation is a few hundreds of meters. As the

validity of the line model used is only guaranteed for frequencies below a

few hundreds of kHz it is not needed to take this spatial extent into

account. Therefore the substation is described by a few lumped elements

representing the trafo between the high-voltage (380 kV} node and the

low-voltage {220 kV or 150 kV) node, as depicted in the inserts A and B of

Figure 3.10. {The inductance is mainly the short-circuit inductance of the

power transformer. which is different for the homopolar mode and the aerial

mode}. Measurements on large power transformers [Bollen and Vaessen, 1987]

confirm that a transformer can be represented by such a circuit with an

acceptable accuracy, up to at least 100 kHz. Measurements on 380/150 kV

transformers as used in the Dutch 380 kV-network yielded a capacitance of

about 10 nF, as seen from 380 kV-side. This value has been chosen as a

typical value per phase per transformer, for the 380/150 kV substations

{insert B). For the 380/220 kV substation Ens {insert A} values according to

Kersten and Jacobs [1988] have been used.

Within TWONFIL the substation is viewed as a single {three-phase} node,

with all other apparatus, except high-voltage lines, neglected.

Page 46: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

3.5. The basic network

Oude Haske

71.4 km

150 kV 81.2 km

150 kV

-38-

LK(mH) 22

- 1.4 33.9

!iK (ohm) 0. 1 0.62 0.5

!Bl

Voltage(I<Vll 360 ' 220

65

3~ ~ 10 nF R

:Lo•388 mH Ro•lOO ohm ILl-185 mH Rl•lOO ohm

G'berg Eindhoven

Maaebracht

62.4 l<m

150 kV 150 l<V

Ftgure 3.10.

Baste network

used for ElffP

study.

The program EMTP has been used to analyse the behaviour of protective

relays in the network depicted in Figure 3.10, where the squares denote the

relay positions. The simulated network is based on the Dutch 380 kV grid.

The lines Ens-Diemen, Diemen-Krimpen, Krimpen-Maasvlakte, Krimpen­

Geertruidenberg and Geertruidenberg-Eindhoven are represented in detail by

using JMARTI SETUP. The other network elements have been respresented

through lumped elements. More details on the simulations can be found in

[Bollen and Jacobs, 1988] and in [Kersten and Jacobs, 1988].

3.6. Model versus reality.

Representing the high-voltage 1 ine depicted in Figure 2.1 by our model and

the associated list of numbers in Table 3.1, implies various approximations.

Since voltages and currents resulting from this model are used for testing

protection algorithms by simulations, we have to check by field measurements

to what degree these quanti ties are in agreement with the actual physical

voltages and currents.

Page 47: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-39-

Figure 3.11. Comparison between mea.surements (left) and EMTP results

(right); adopted from [Von Heesch, et at.,1989].

some comparisons between field measurements and model results have been

made in our group by Kersten and Jacobs [1988] and by Van Heesch et al.

[1989]. Figure 3.11 is adopted from the latter publication. It shows

voltages and currents at the receiving end of a circuit being energized. The

circuit was part of a double-circuit line with the other circuit in

operation (cf. Figure 3.12). During the simulation most of the problems

occurred in obtaining information about the feeding networks. They affect

not only the new stationary situation but also the transient and even the

initial waves created by closing the breakers. This may largely account for

the deviation between model and reality.

Figure 3.12. Field mea.surements during tine energizing. At position 1 the

circuit breakers are being dosed, voltages are measured at position 2. A

and B are feeding networks affecting the transient phenomena.

To get a better insight into the limitations of the line model special

field experiments can be performed, e.g. as proposed in Figure 3.13. To

ensure that all deviations between model and reality are due to

Page 48: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-40-

imperfections of the line model, the feeding source has to be almost

perfectly modelled. Therefore a simple feeding source is recommended, e.g. a

low-impedance D.C. source or a large capacitor.

Figure 3.13. Proposal for field experiments to test transmission line model.

Nakanishi and Ametani [1986] have compared a number of modelling

techniques with field measurements. Figure 3.14 presents their results for

the energizing of a single phase of a three-phase line (voltages measured on

the receiving end are depicted). Two models are compared:

- EMTP' s .]MARTI SETUP with frequency dependent modal parameters but

frequency independent transformation matrix (dashed line):

-a model with both frequency dependences incorporated (dotted line):

The solid lines represent the measurements. It follows from the figure that

the results of the second model slightly differ from the EMTP results. But

the second model does not significantly reduce the deviation between model

and reality.

Figure 3.11f. Compl.ri-

--·(1) son between measure-

ments (solid lines)

and model results; (i)

refers to the phase

being energized, (iii)

to one of the other

phases; adopted from

[Nakanishi and

Ametani, 1986].

20 100 time(lls)

Page 49: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-41-

4. Testing of algorithms for travelling-wave-based protection

4.1. Potentially dangerous events

A protective relay must be able to take a correct decision in all cases. A

tripping signal must be generated for each fault in the zone-to-be­

protected. No tripping signal shall be generated in all other cases. In this

study special emphasis is laid on these "no-fault situations". An incorrect

decision can be due to technical failure of the relay or due to limitations

of the protection algorithm used. This study only concerns the latter case.

Many disturbances can take place in a high-voltage network. some are

listed in Section 2.4. Fach automobile crossing a high-voltage line will

cause some change in charge distribution and thus travel! ing waves. The

amplitude however will be very small, so not of any importance for this

study. The greatest possible disturbances in high-voltage networks are line

energizing, fault initiation and lightning. Therefore these have been

studied in detail.

~auLt~ L~ the ~one-to~e~tected

These are the situations where the relay should generate a tripping signal.

The following situations have been studied:

1. faults somewhere on the line;

2. faults close to one of the line terminals;

3. evolving faults;

4. faults due to lightning;

5. faults during line energizing.

Single-circuit faults: Single phase to ground Phase-to-phase Two-phase-to-ground Three-phase Three-phase-to-ground

Double-circuit faults: Phase-to-phase Two-phase-to-ground Three-phase Three-phase-to-ground Four-phase Four-phase-to-ground

Five-phase Five-phase-to-ground Six-phase Six-phase-to-ground

RNSNTN RSRTST RSN RTN STN RST RSTN

RV RW SW RUN RVN RWN SVN SWN Tt!N RSU RSV RSW RTU RTV RTW RVW STY STW RSUN RSVN RSWN RTUN RTVN RTWN RVWN STVN STWN RSTU RSTV RSTW RSUV RSUW RSVW RTUW RTVW STVW RSTUN RSTVN RSTWN RSUVN RSIJWN RSVWN RTUWN RTVWN STVWN RSTUV RSTVW RSUVW RSTUVN RSTVWN RSUVWN RSTUVW RSTUVWN

Table 4.1. Fault types studied by using TWONFIL. R S T denote }ilase

conductors of the first circuit, U V I of the second one. RS stands for a

faul.t between }ilase R and }ilase S, RJN for a faul.t between }ilase R and

}ilase I (T of the second circuit) with earth connection.

Page 50: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-42-

Ad. 1. Single-circuit as well as double-circuit faults have been studied. In

case of synunetry between both circuits (SU=RV. TII=RW. etc.) 64 different

combinations of faulted phases are possible. They are given in Table 4.1.

These faults have been studied by using TWONFIL for 12 fault-initiation­

angles, 15° apart.

Ad. 2. Only single-circuit faults have been studied (11 combinations of

faulted phases for 12 fault-initiation-angles each}.

Ad. 3. A fault can evolve to a more complex fault (more faulted phases) in

two ways: a rapidly changing elektromagnetic field may cause multiple

flashover (e.g. due to lightning): an arcing fault may spread to other

phases. In the first case the speed of expansion will be a substantial part

of the speed of light being 300 ml~s. As the distance between neighbouring

phases is around 10 meter. the evolution of the fault takes place on a

submicrosecond scale. So this multi-phase fault can be considered as

simultaneously. In the second case the speed of expansion will be at maximum

of the order of the speed of sound (360 m/s), leading to an evolution taking

place on a 10 to 100 millisecond scale. The situation studied is an evolving

fault after the new steady state has been reached. About 700 evolving faults

have been studied for 12 fault-initiation-angles each.

Ad. 4 and 5. To be duscussed further on.

~auLt~ out~Lde ot the ~ane-to-be-p~otected

For these situations the relay shall not generate a tripping signal. The

following faults have been studied (cf. Figure 4.1}:

6. faults somewhere on the parallel circuit;

7. faults close to one of the line terminals:

8. faults somewhere on another line;

9. evolving faults on the parallel circuit;

10. evolving faults somewhere on another line:

11. faults during energizing of the parallel circuit.

2

Figure 4.1. Fault postitions studied.

Page 51: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-43-

Ad. 6. Only single-circuit faults are of interest here: 11 combinations of

faulted phases for 12 fault-initiation-angles each.

Ad. 7. Compare Ad. 2.

Ad. 8. Compare Ad. 1.

Ad. 9. Only single-circuit faults evolving to other single-circuit faults

have been studied: 19 combinations of faulted phases for 12

fault-initiation-angles each.

Ad. 10. Compare Ad. 3.

Ad. 11. To be discussed further on.

Othe~ di~tu~bance~

These are situations where none of the relays shall generate a tripping

signal. The following situations have been studied:

12. energizing of a non-loaded line:

13. de-energizing of a short-circuited line;

14. lightning.

7 ')

Figure 4.2. Circuit breaker positions

studied for line energizing.

Ad. 12. The energizing situations studied are summarised in Figure 4.2. Each

switch in this figure denotes three circuit breakers studied for 19

combinations and 12 fault-initiation-angles each. The combinations of closed

phases and closing phases are given in Table 4.2.

Closed

none R s T SandT Rand T RandS

Closing

R. S, T. R and S, S. T. SandT R. T. R and T R, S. RandS R s T

Rand T. SandT. RandS and T

Table 4.2. Combinations

of dosed and cLosing

phases for energizing

as studied by using

TWONFIL.

Ad. 13. Like during line energizing, line de-energizing will cause

travelling waves. The most intense phenomena will occur between the circuit

breaker and the fault, i.e. on the line to be de-energized. This is not of

concern for protection anymore. Travelling waves will also appear on healthy

lines, where they may endanger the reliability of a relay. As de-energizing

Page 52: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-44-

will only take place at current zero, the number of situations is limited.

Line de-energizing has been studied by using EMTP.

Ad. 14. To be discussed further on.

4.2. General discription of a protection algorithm

An algorithm for travelling-wave-based protection uses travelling-wave

principles to detect a fault on a high-voltage line; it determines incoming

and outgoing waves from measured voltages and currents. As only the waves

caused by the fault initiation must be detected, "superimposed quanti ties"

must be used. Some algorithms derive them by subtracting the values one

power frequency cycle back in time. Other algorithms (e.g. differential

protection} take the difference between two values a small period in time

apart. In that case superimposed as well as momentary values can be used.

As shown in Section 2.2 for a single-phase line, the expressions v+Z0 i

and v-Z0 i denote incoming and outgoing waves, respectively, where Z0 is the

wave impedance. This also holds for the modal waves on a multi-phase line,

as shown in Section 2.3. A hypothetic algorithm to detect the outgoing waves

should use the following set of detection functions:

( 4.1}

where y(P} and I(p} are vectors of (superimposed} val tages and currents,

respectively; S, Q and zic} are val tage transformation matrix, current

transformation matrix and (diagonal} wave impedance matrix, respectively.

It is not practical trying to use the exact transformation matrices in

a protection algorithm, because:

the transformation matrices are not exactly known (i.e. the difference

between the exact values and the calculated values are very difficult

to determine};

problems occur for lines showing transposition points as well as for

double-circuit lines where parameters from both circuits are needed;

relatively complicated expressions show up.

To avoid all these problems the transformation matrices are considered to be

those for a balanced three-phase line. The errors introduced by this

approximation will be discussed further on. Using the transformation of

(2.45) leads to the following detection functions:

(vr+V8 +Vt} - Ro(ir+1 8 +1t)

(vt-V8 } - R1 (it-i 8 }

(4.2}

(4.3)

(4.4}

where R0 and R1 represent the homopolar and aerial mode wave impedance,

respectively. The homopolar detection function D0 will not be used because:

Page 53: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-45-

it shows large pulses of short duration ("spikes") during a fault on

the parallel circuit. They cannot be removed sufficiently by a low pass

filter. These spikes may cause false tripping of a circuit parallel to

the faulted circuit [Bollen and Jacobs 1988]:

homopolar mode quanti ties are strongly dependent on frequency as well

as on the composition of the ground. They are also dependent on the

state of the parallel circuit. It is therefore difficult to choose a

wave impedance setting for the relay;

a lightning stroke to a tower, to a shielding wire or somewhere in the

vicinity of the line will affect all conductors in about the same

extend, leading to a large homopolar wave, but almost none aerial

waves:

fault detection without the homopolar quantities does not introduce any

additional problems, but it will reduce the number of calculations to

perform with about 50%.

In this hypothetic case the following detection criteria are used to

distinguish between a "fault situation" and a "non-fault situation":

ID1 l<b and ID2I<b IDtl>b or ID2I>b

non fault

fault .

(4.5)

(4.6)

The setting of the threshold b as well as of the impedance value R1 will be

discussed in the next section.

4.3. Setting of,the different parameters.

~Lt~ and de~ee~

The protection algorithms to be discussed in this and forthcoming chapters

hold for every value of the nominal voltage. To get a reference, the

amplitude of the nominal phase voltage is considered to be equal to 1000

units. This makes it possible to express all detection functions (having the

dimension of a voltage) and all thresholds in these arbitrary units. The

second reference to be made conderns the fault-initiation-angle: zero

degrees corresponds to voltage maximum in phase R.

$hne~hold and Lapet:loll,ce ~etUng,

The detection functions (4.3 and 4.4) are equal to zero for a non-fault

situation on a balanced line. On a nonbalanced line the detection functions

possess a small but nonzero value during a non-fault situation. That is one

of the reasons to introduce a threshold value b. Criterion (4.5) must be

valid for all non-fault situations. Thus both detection functions must, in

absolute value, be below the threshold. Putting it the other way around: the

Page 54: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-46-

threshold b must be higher than the highest possible value of the detection

functions during a non-fault situation. This minimum threshold value is a

function of the impedance setting R1 • The shape of this function is shown in

Figure 4.3. The knee in the curve denotes optimum impedance setting.

R,-

Figure 4.3. Minimum threshoLd vatue b as a

function of impedance setting.

In reality it is not possible to set the impedance exactly to its

optimum value {e.g. due to uncertainties in the line parameters). As a

consequence of this the threshold must be higher than the optimum value.

Other settings can also deviate from their optimum values leading to even

higher thresholds, as will be seen further on.

The impedance uncertainty will greatly differ from situation to

situation. For this study an uncertainty of 5% has been choosen. In the

Dutch 380 kV network measurements give 50 Hz values for inductance and

capacitance of 0.882 mHIKm and 13.22 nF/Km respectively for the aerial

modes. This leads to a wave impedance value of 258.3 Q, being within 3% of

the optimum setting of 266 Q. So 5% seems to be an acceptable value.

:/!OU;-pa,o.o, tLLtc'I-

All kinds of disturbances cause high-frequency noise in the detection

functions. This can be due to characteristics of the lines {e.g. different

travelling times for the different modes) or due to external phenomena

(lightning strokes, radio transmissions). If such a high frequency

disturbance occurs during a non-fault situation it might lead to an

incorrect trip. To prevent this a low pass filter will be introduced.

For one of the algorithms14 a non-fault situation must be detected

within one travelling time of the line T. Therefore a block function with a

duration T shall not be distorted too much. From this a criterion as shown

in Figure 4.4 is introduced. Following an input step the output must be

within 10% of the final value after 1/2 T.

14 Directional detection {cf. Section 5.2).

Page 55: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

rnfiltered

«10%1-------,...,.---­, I

/ I ~ I

/ I I '

I I I

-47-

\ \ \--filtered

' ', ...... ..... _ ... _

-t

Figure. 4.4. Criterion to determine the cut-off frequency.

A first order filter will be used. with a transfer function of the form

H(f) 1 + jf/fc •

where fc is the cut-off frequency.

The step response a(t) or this filter is

a(t) = 1 exp (-2n£ct) • t > 0 .

From the criterion of Figure 4.4. follows

f > 0.73 . C T

(4.7)

(4.8)

(4.9)

An acceptable value for the cut-of£ frequency is rc = 1/-r, where T is the

travelling time of the line-to-be-protected. For a 100 km line this will be

3000Hz. This cut-of£ frequency will be used for other algorithms too. also

when theoretically no lower limit for the cut-of£ frequency is required. For

some combinations of algorithm and line type a lower cut-of£ frequency is

required and will thus be used.

The cut-off frequencies used (a few kHz) are of the same order of

magnitude as those used by other authors. Chamia and Liberman [1978] use the

low-pass behaviour of the voltage and current transformers. According to

them that cut-of£ frequency is a few kHz. The same is done by Mansour and

Swift [1986] using a sample frequency of 2kHz in accordance with a cut-of£

frequency of 1 kHz. Johns et al. [1986] use a cut-off frequency of 2kHz and

Ermolenko et al. [1988] one of 1 kHz.

Page 56: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-48-

'J''tal9-eULn,g. Use

Two of the algori thms15• determine the difference between a wave at a

certain moment and the same wave, some travelling time later. The algorithms

check whether Bergeron's equations (2.22 and 2.23) are valid or not. As

shown in Chapter 2, a multi-phase line can support more than one wave, each

having a different travelling time. The travelling time setting must be

somewhere in this interval. For line type A of Section 3.3.4 the travelling

time for a 100 km line is 364 JLS for the homopolar wave and 337 JLS for the

fastest wave. The slowest aerial wave possesses a travelling time of 349 JLS.

Consider the detection function to have the following form

D(t) = A(t) - B(t+T) : (4.10)

where A and B are expressions like (4.3) and (4.4) and T is the travelling

time setting. During a no-fault situation A(t) and B(t+T) are almost equal,

so ID(t)l is below the threshold b. The travelling time setting T must be

such that ID(t)l is as low as possible during a no-fault situation. Suppose

that A shows a sudden jump, e.g. due to a fault just outside of the

zone-to-be-protected. After a certain time. B will show a jump too. Due to

differences in travelling time the wave front will be less steep, as shown

in Figure 4.5.a and b.

Is A

® @ @ t s

I f s

B I D I I I I

0 t- l.j4t t- t-®

t t-D D D

t-

Figure. 4.5. InfLuence of traveLling ttme setting T on shape of detection

functions. a: initial wave; b: wave after travelling ttme; c: setting

according to fastest wave (T=t0 ); d: setting according to slowest wave

(T=t0 +At); e: optimum setting; f: extremely erronous setting.

15 Differential protection (cf. Section 6.2) and switch-on-to-fault detection (cf. Section 7.4).

Page 57: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-49-

In case the travelling time is set according to the fastest wave a

positive spike results in the detection function as shown in Figure 4.5.c. A

setting according to the slowest wave results in a negative spike of the

same dimensions (cf. Figure 4.5.d}. Figure 4.5.e shows the detection

function for a travelling time setting in the middle of these two extremes.

This is considered to be the optimum setting as it leads to the lowest

amplitude for the spikes. Because the detection functions do not use the

homopolar mode, only the aerial mode travelling times need to be considered.

It is assumed here that the properties of the different modes are such

that the front of B possesses a constant slope. This is certainly not true

for all situations. In case only the fastest waves are present or only the

slowest waves, the optimum setting will not decrease the amplitude of the

spike in the detection function. But it will decrease the duration by a

factor of two, leading to a reduction of the amplitude by a factor of two

after passing a low pass filter.

In case the travelling time setting deviates from its optimum value,

the duration and amplitude of the spikes in the detection function will

increase. Figure 4.5.f shows the detection function in case the travelling

time shows a setting error T, i.e. it is set to t 0 + At/2 + T. In the worst

case of only the fastest mode present a block with a heigth Sand a duration

T+At/2, results. After low pass filtering, the maximum value of ID(t) I

equals:

s[ 1 - exp {- 2x fc(At/2 + T)}] ~ 2x fc S(At/2 + T) ( 4.11)

The time above a threshold b is given by:

1 [ 2xf CS(At/2+T) ] T + At/2 + 2xf ln b .

c ( 4. 12}

As S can be high, it is clear that already a small error in travelling time

setting can introduce large spikes in the detection functions during

non-fault situations.

Othe~ ~PLke~ Ln the detectLon tunctLon~

The preceeding subsection discussed spikes due to differences in travelling

time for algorithms using a travelling time setting. But spikes also occur

for algorithms without such a setting16

16 The problem occurs with directional detection (cf. Section 5.2) for fau1 ts on a paralle 1 circuit and in a more intense way with a special double-circuit algorithm called DOOCP (cf. Section 7.2) for faults in the remote substation.

Page 58: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-50-

Consider the situation shown in Figure 4. 6, where the double-circuit

line consists of just two conductors. Two modes are possible: one with

currents having the same sign in both conductors. one with currents having

opposite sign. If the second one has the highest speed. the shape of the

detection functions for both relays during a fault in one of the circuits is

as shown in the right part of Figure 4.6. The detection function of Relay B

shows a spike. These spikes must be removed by the low pass filter

introduced above.

~etectLon •Lndoe

I Ftgure. 4 .6. Different modes on a

doubte-circuit tine (teft) and

resuLting detection functions

(right).

Due to multiple reflections two of the algorithms cannot be used anymore

from a certain (short) time after the occurrence of an external fault,

onward17 . As a consequence of this the relay must be blocked after the

detection of an external fault. This calls for additional detection

functions to detect the external disturbance within a "detection window".

After the relay has been blocked, it must remain blocked during a "blocking

time". Different authors propose different blocking times. Johns (1980]

proposes a blocking time of 60 milliseconds. Mansour and Swift [1986] one of

100 milliseconds, Ermolenko et al. [1988] use a blocking time between 500

and 2000 milliseconds. Such a fixed length will be too long for most

situations, as the relay cannot detect any fault when it is blocked. But the

blocking time may also be too short for some extreme situations. leading to

incorrect tripping. It is considered a better solution to deblock the relay

immediately after the end-of-transient, i.e. when all relevant detection

functions are below their threshold again.

~etectLon tL•e, 5e~LtLcatLon tL•e. t~LPPL~ tL•e

When a fault occurs somewhere in the zone-to-be-protected of a relay. waves

start to travel from the fault position to the relay position (actually the

position of the measurement transformers). After a certain travelling time

the fastest waves arrive at the relay position. At this moment the detection

function starts to deviate from zero. Due to the low pass filter introduced

it will take some time before the detection function exceeds the threshold

b. The "detection time" (DT in Figure 4. 7) will be defined as the time

17 Directional detection (cf. Section 5.2) and DOOCP (cf. Section 7.2).

Page 59: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-51-

between the arrival of the fastest waves at the relay position and the

moment the detection function exceeds the threshold.

D 8

0 0 t

Ftgure 4.7. Definition of detection time (DT).

uertftcat ton time (VT) and tripping time (TT).

oof = occurence of fault; gts = generation of

tripping signal.

To prevent false tripping, a tripping signal wi 11 not be generated

before the detection function has · been above the threshold during a

"verification time" (VI' in Figure 4.7). The "tripping time" is the sum of

detection time and verification time. A short verification time wil give a

short fault clearing time, but will also increase the chance of incorrect

tripping. In reality the choice of the length of the verification time will

be a compramise between speed and reliability. This trade-off is outside the

scope of this study.

'£tg.lr.tntng.

The most troublesome situation to occur during lightning is a direct stroke

to a phase conductor. not leading to a flashover. As this is a source of

travelling waves a travelling-wave-based algorithm may generate an incor­

rect trip. The risk of such an incorrect trip is reduced by introducing:

a threshold;

a low pass filter;

a verification time.

Consider the folowing shape for a (nonfiltered) detection function after a

lightning stroke:

D(t) = A exp(-t/T) U(t) , ( 4.13)

where the step function U(t) is zero for t < 0 and unity for t > 0; a

standard value for the time constant T is 70 ~s. The detection function has

the following shape (for 2xfcT ~1. where fc is the cut-off frequency):

2xf T [ ] D(t) =A 2xfcT-l exp(-t/T) - exp(-2xfct)

c ( 4. 14)

Figure 4.8 shows a few of these detection functions.

Page 60: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-52-

140 f'S-

Figure. 4.8. InfLuence of Low-puss filtering on Lightning-caused detection

functions ..

The highest possible value of A is determined by the flashover voltage

of the insulator chain. According to Kersten and van der Meijden [1984) the

flashover voltage for the Dutch 380 kV network is about 2.2 MV (for a

1.2/~s pulse). Reckoning the agreement at the start of this section the

flashover voltage will be 7000 units. This is considered to be the highest

possible voltage jump not leading to a flashover. For directional detection

and differential protection a voltage jump of 1000 units in one phase will

lead to a jump in the detection function of 1400 units. So the highest

possible direct stroke not leading to a fault causes a detection function of

the form (4.14) with A=10,000.

The time above threshold of such a lightning-caused detection function

must be shorter than the verification time. Figure 4.9 gives this time above

threshold (i.e. the minimum verification time) as a function of the cut-off

frequency for a few threshold values (notice the change in horizontal scale

at 1kHz). For low cut-off frequencies the verification time can be

considerably shortened when the threshold level is increased. This may

decrease the tripping time in a few cases. But for frequencies above 1 kHz

an higher threshold will not significantly shorten the verification time.

Page 61: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-53-

t

6

Figure. 4.9. Time above threshold for lightning-caused detection functions

as a function of cut ·off frequency, for different threshold values. The

maxtllltlllt value of the nonfHtered detection function is 10,000 units, its

time constant 70 ~s.

~e~L~tLon of the ~upe~L•PD~ed ~tLtLe~

Two of the algoritlnns18 use superimposed quantities (cf. Section 2.4.2).

They can be derived as the difference between the actual values and the

values one power frequency cycle back in time (the undisturbed values). As

the power frequency shows small changes on a minute scale, the delay time of

one power frequency cycle needs to be adjusted. A method for this is

proposed by Johns and El-din Mahmoud [1986]. Nevertheless the time delay

will not fit the power frequency exactly.

Consider a detection function D(t) being the difference of an actual

value M(t) and an undisturbed value Dcos (~0 t):

D(t) = M(t) - Dcos (~0 t-~oT) , (4.15)

where T is the time delay used, showing an error AT,

T = 2ltl~0 + AT (4.16)

If AT<<T the maximum error in the detection function is given by

18 Directional detection (cf. Section 5.2) and DOOCP (cf. Section 7.2).

Page 62: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-54-

( 4. 17)

Figure 4.10 shows the frequency drop measured during a 5500 MW power

shortage in the West European grid [Maas. 1987]. The maximum frequency

deviation was 0.4 Hz. This is the biggest frequency deviation ever observed

in the West European grid.

so.sl (~zll 504--------~------~~. ---------

49.51 ~. 50s t (sl-

Figure. 4 .10. Frequency deviation due to a. large power shortage, adopted

from [Raas, 1987].

From this it can be concluded that the frequency deviation in the relay

will almost certainly not exceed a value of 100 mHz. To cope with the worst

frequency deviation and to incorporate other errors too, 1% error will be

considered in this study (corresponding to 0.2 ms or 0.5 Hz on a 50 Hz

base).

4.4. Fault detection time

Each algorithm is based on superimposed voltages and currents, even though

not all of them actually derive these quantities. During a fault superimpos­

ed voltages and currents are caused by a virtual sinusoidal source switched

on at the instant of fault initiation. Before multiple reflections disturb

it the nonfiltered detection function will be of a sinusoidal shape too:

D(t) = Dcos(w0t~). t>O , ( 4.18)

where ~ is related to the fault-initiation angle. After passing a low-pass

filter with cut-off frequency fc (fc>>50 Hz) the detection function has the

following form:

D(t) = n[cos(w0 t~) ( 4. 19)

The detection time is the lowest positive t being a solution of

ID( t) I = 0 . (4.20)

The detection time is given in Figure 4.11 as a function of the

fault-initiation angle ~. for D/6 = 3.5 (a single-phase-to-ground fault in

combination with differential protection or directional detection) and

fc =5000Hz (60 km line).

Page 63: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-55-

Figure. 4.11. Detection time as a

function of fault-initiation-angle.

For Dcos(~)>b ( ~<73° in Figure 4.11 ) the curve can be approximated by

1 b t = 211:f ln (1 - Dcos~ ) (4.21)

c

This function has a very steep asymptote at~= arccos(b/D), the angle where

the jump in the nonfiltered detection function equals the threshold.

Slightly to the left of this asymptote the detection time is of the order of

tens of microseconds (10. 7 JlS for ~0 : 14.9 JlS for ~0°: 57.5 JlS for

~ = 70°). This is small as compared to the verification time (cf. Figure

4.9). So for a wide range of fault-initiation-angles (including those with

the highest chance of occurence) the length of the tripping time is

determined by the length of the verification time.

j) _] -----------

Figure 4.12. Detection function for a

fault somewhat before voltage zero. The

dot ted ltne denotes the threshold

level.

In case Dcos(~) < b (the jump in the nonftltered detection function is

less than the threshold value), the detection time will be much larger. The

worst case is shown in Figure 4. 12. The fault occurs before the zero

crossing of the detection function and the jump in the detection function is

just below the threshold. The chance of occurence of such a fault is not

known but it is clear that faults around voltage zero are seldom.

The basic assumption for (4.18) is the absence of multiple reflections.

This will hold for a detection time of 10.7 JlS but not for one of 1800 JlS.

It has been shown that multiple reflections speed up the fault detection

Page 64: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-56-

except for situations with a very weak infeed (low short-circuit power).

The above discussion holds for single-phase-to-ground and for phase-to­

phase faults. For these faults all detection functions show a zero crossing

at the same angle as the pre-fault voltage. For two-phase-to-ground and

three-phase faults the detection functions show their zero crossings at

different angles, so that always at least one of the detection functions

will exceed the threshold within a short time. For a three-phase fault on

line type A, and a cut-off frequency of 5000Hz, the detection time ranges

from 4 to 10 Jl.S.

4.5. Phase selection

After a fault had been detected the fault type can be selected. Depending on

the fault type a single-phase trip or a three-phase trip can be given. Phase

selection combined with travelling-wave-based protection is possible by

calculating six selection functions from the detection functions D1 and D2 •

8t=Dt

82=D2

83 =D1 +D2 ,

8 4 =Dt-D2 ,

8s=Dt+2D2 ,

86 =-2Dt-D2 •

(4.22) (4.23)

(4.24) (4.25)

(4.26)

(4.27)

Inserting (4.3) and (4.4) results in the following expressions (only the

voltage terms are given):

81=vt-Vs (4.28)

82=vr-Vt (4.29) 83 =vr-v., (4.30)

84=2vt-Vr-Vs (4.31)

8s=2vr-vs-vt (4.32)

86 =2v5 -vr-Vt (4.33)

During an R-N fault the superimposed voltage in phase S wi 11 be almost equal

to the one in phase T. The same applies to the current. Because of this the

selection function S 1 will be near to zero. The same is valid for 82 during

an 8-N fault and 83 during a T-N fault. This leads to the following

selection criteria for single-phase-to-ground faults.

IS1 I <cr l82l <cr IS:~I<cr

R-N

S-N T-N

(4.34)

(4.35)

(4.36)

Page 65: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-57-

During an R-S fault the superimposed current in phase R is about opposite to

the one in phase S. The current in phase T is almost equal to zero. The same

applies to the voltages. The selection function S4 is therefore near to

zero. In the same way S5 corresponds to an S-T fault and S6 to an R-T fault.

This leads to the following selection criteria for phase-to-phase faults:

ls .. l<a lssl<a ISsl<a

:R-S • :S-T , :R-T

(4.37)

(4.38)

{4.39)

When a single-phase-to-ground fault is detected the faulted phase will be

tripped. After a phase-to-phase fault only one of the faulted phases will be

tripped. More details on this can be found in [Bollen and Jacobs, 1988,

1989: Bollen. 1989]. The principal results are:

For most fault situations the additional time needed for phase

selection is just a few tens of microseconds. A few situations (e.g.

R-S-N around a zero crossing of the phase R voltage) show an initial

single-phase trip followed by the necessary three-phase trip after

about 1 ms):

Due to spikes in the selection functions additional filtering is needed

to prevent an incorrect three-phase trip during phase-to-phase faults:

During some double-circuit faults the algoritlun for phase selection

fails. Then two three-phase trips are generated in stead of two

single-phase trips.

Page 66: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-58-

5. Directional detection

The basic assumption for travelling-wave-based directional detection is: "a

source of travelling waves within the zone-to-be-protected is a fault" {cf.

figure 5.1). As the closing of the circuit breaker can also be a source of

travelling waves the circuit breakers must be located outside of the

zone-to-be-protected. So voltage and current must be measured on the line

side of the circuit breaker.

)(ll~--- --~------::_f8 )( Figure 5.1. Principle of travelling-wave-bused directional detection.

A directional detector at each line terminal determines the direction of

origin of the travelling waves (i.e. the direction to the fault). If both

detectors find a fault in their forward direction (the direction into the

line) tripping signals must be generated. To exchange this information a

communication link between both line terminals is necessary. Each detector

only needs to determine the direction of origin of the waves. The algorithms

proposed to determine this are discussed below.

Multiple reflections after a backward fault will lead to waves from the

forward direction; this might cause incorrect tripping of the line. To

prevent this, the relay will be blocked after the detection of a backward

fault. The blocking time has to continue ti 11 the amplitude of the waves

from the forward direction is low again. During this blocking time a fault

will not be detected. This is a fundamental disadvantage of travelling­

wave-based directional detection.

5.1. History

~La·~ at~Lthm

The algorithm proposed by Chamia and Liberman [1978] compares the polarity

of superimposed voltages and currents to yield the direction of origin of

the first travelling waves arriving at the relay position.

Figure 5.2. Travelling wuves due to a

forwurd and a backward fault

The different travelling waves after a fault initiation are shown in

Page 67: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-59-

Figure 5.2. Due to the fault a wave (1) travels from the fault position to

the substation, where a part is transmitted (2) and another part reflected

(3). Relay A measures a wave from the forward direction (an outgoing wave)

as well as one from the backward direction (an incoming wave). For the

superimposed voltages and currents measured by relay A, the two following

equations hold:

VA- Z.iA ¢ 0 •

vA + Z. tA = r(vA-z. tA)

(5.1)

(5.2)

where r is the reflection-coefficient, lr I<I. From this it follows that v A

and iA are of different polarity.

Relay B only measures an incoming wave leading to the following relations:

v8 - Z iB = 0 (5.3)

VB + z iB ~ 0 (5.4)

So vB and i 8 are of equal polarity.

This leads to the following detection criteria:

(v > 0 and i < 0) or (v < 0 and i > 0): forward fault

(v > 0 and i > 0) or (v < 0 and i < 0): backward fault .

(5.5) (5.6)

Olamia' s algorithm is used on a segregated phase basis in ASEA' s RALDA and

RALZA relays [Yee and Esztergalyos, 1978: Giulante et al., 1983].

I~ Zi !L{ 1 /

/ / 1

----------~---------v

Figure 5.3. The v, i-diagram., with pos­

itions obtained immediately after a for­

unrd fault (shaded area) and immediately

after a lxu:kunrd fault (dotted lines).

Vitins [1981] relates (5.1) through (5.4) to positions in a v,i-diagram, as

shown in Figure 5.3. He shows that {5.5) and {5.6) also hold during a few

milliseconds after the fault in case the new stationary situation should be

reached without any transient. This leads to the following detection

criteria:

Page 68: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

{v.i) reaches region 1 or 3 first

{v,i) reaches region 2 or 4 first

-60-

backward fault ;

forward fault .

{5.7)

{5.8)

The principle has been extended further by Engler et al. [1985]. They use a

"replica impedance" Zr to derive an auxiliary voltage v 1

from the

superimposed current at the relay position ir:

{5.9)

They show that the fault-trajectory of the post-fault stationary quantities

in the v-vi-plane is a straight line in case Zr=a.Zs' a>o. where Zs is the

{stationary) short-circuit impedance of the feeding network. From the

superimposed voltage at the relay post tion v and the replica voltage vi a

correlation function F{t) is determined:

t

F(t) I v(T).vi{T)dT {5.10)

0

A forward fault is concluded if F{t) exceeds a negative threshold, a

backward if F{t) exceeds a positive threshold. This principle is used in

BBC s LR-91 relay.

Figure 5.4. The first travelLing wave arriving

at the relay positian.

If a fault occurs with a small voltage jump, it will in general take some

time before the directional detectors detect the fault (cf. Section 4.4).

Dommel and Michels [1978] propose a method to detect each fault as soon as

the first travelling waves arrive. Figure 5.4 shows the single-phase

situation. The superimposed voltage at the fault position is: A

vF(t) = - V cos(w0

t + ~).U(t) , {5.11)

where V is the voltage amplitude and ~ the fault-initiation-angle, U(t) is

the unit step function (U{t)=O,t<O; U(t)=l,t>O). At the relay position a

wave from the forward direction (i.e. an outgoing wave) can be measured: A

v(t)-Z.i{t)=-2 V cos(w0t-w0T~).U(t) , (5.12)

The <1>-dependence is eliminated by using Pythagoras' law, leading to the

following detection function:

Page 69: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

2

DFw(t) = [ v(t)-Z.i(t)] 1 + ;;;­!.)

0

By using (5.12} it follows:

DFw(t) = 4(V)2 .t>O.

[ dv dt

-61-

z di] dt

2

The following detection criteria have been proposed

DFw( t)>O

DFw(t)=O

forward fault ,

backward fault .

(5.13}

(5. 14)

(5.15)

(5. 16}

Mansour and Swift [1986] use a second detection function beside (5.14) to

prevent false detection of a forward fault due to successive reflections: 2

ItJw(t) = [ v(t)+Z. i{t)]

2

+ 1 [ dv + z di] 7 dt dt 0

They propose the following detection criteria:

ItJw(t) > b and DFw(t) < b

DFW(t) > b

backward fault

forward fault .

(5.17)

(5.18)

{5.19)

The algorithm is very well capable of detecting a forward fault as shown by

Dommel and Michel [1978] as well as by Mansour and Swift [1986]. But non of

them mentions the problems during a backward fault. The time derivative

introduces large spikes in the forward detection functions, this necessi­

tates the use of low pass filters with a low cut-off frequency. It will be

shown in Section 5.2 that the gain in speed will be undone by these filters.

lolms' a.tg.ottttlu&

Johns [1980] proposes a relatively simple algorithm, based on (5.1} through

(5.4). From the superimposed voltages and currents six detection functions

are calculated:

DoFw Vr + V8 + vtl - Ro( ir + i 5 + it) , (5.20) D Fw _ 1 - (3/2 Vr - 3/2 Vt) - R1 (3/2 ir - 3/2 itl (5.21) D2Fw = ( 1/2 Vr - v,. + 1/2 vtJ - R1 C/2 ir - is + 1/2 itJ (5.22)

DoBw (vr + V5 + vt) +Ro (ir + i,. + it} (5.23) D1Bw (3/2 Vr - 3/2 vtJ + Rt (3/2 ir - 3/2 it) (5.24) D2Bw (1/2 Vr - Vs + 1/2 vtJ + R1 e/2 ir - is + 1/2 it} (5.25)

where Vr• v5 and Vt are phase voltages; ir• i 5 and it are phase currents,

the positive reference direction is from the substation into the line; Ro

and R1 are real approximations of the wave impedances for the ground wave Fw

and the aerial waves respectively. The forward detection functions Do •

D1 Fw and D2Fw are a measure for the outcoming waves i.e. from the forward

Page 70: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-62-

direction. The backward detection functions 00 Bw, D, Bw and D2 Bw are a

measure for the incoming waves, i.e. from the backward direction. A backward

fault is concluded if only incoming waves are present:

{ lo/wl < band IDo8wl > b }

or { ID,Fwl < band ID,Bwl ) b }

or { lo/wl < band ID2Bwl > b } (5.26)

If the relay is not in the blocking mode, a forward fault will be concluded

the soon an outgoing wave is present:

{ IDoFwl > b or IDo8wl < b }

and { ID,Fwl ) b or ID,Bwl < b }

and { io/wl ) o or ID2Bwl < 0 }

and { IDoFwl ) o or ID,Fwl ) o or lo/wl > o} . (5.27)

In a later version of the algorithm, the homopolar quantities have been

omitted and simpler combinations of voltages and currents are used [Johns et

al., 1986]. The homopolar quantities are also omitted in a recent proposal

by a Russian group [Ermelenko et al., 1988].

Johns and Walker [1988] give a very detailed description of the

development and testing of a prototype relay based on Johns' algorithm.

5.2. Results of the testing of Dommel' s algorithm

The following forward detection functions have been used in agreement with

the standard form of (4.3) and (4.4):

D, -['' + _1_ r:·fr - 1 (,)2

0

(5.28)

[ x' [ :2(

'/2

02 = 2 + _1_ (,)2

0

(5.29)

where x 1 (vt-vs) - R1 (it-is)'

x2 (vr-vt) - R1 (ir-it).

During a forward fault x 1 and x2 jump to a high value. During a backward

fault x 1 and x2 also show a jump (due to the unbalance of the line), but to

a lower value (cf. Figure 5.5). Due to the time derivative used in equations

(5.28) and (5.29) the detection functions 0 1 and 02 show very large values

the moment the waves arrive at the relay position. The spike due to a

backward fault might be much higher than the final value (i.e. after the

spike) during a forward fault. This will make a reliable detection very

Page 71: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-63-

difficult. A low-pass filter will be needed to reduce the amplitude of the

spikes. The filtering wi 11 be performed here on x 1 and x2 before the

determination of the derivative.

X

(j,---1-----

1--------2

t-

D

Figure 5.5. "Forunrd unues" during

backunrd fault (1) an.d during forunrd

• faul.t (2).

Figure 5.6. Detection. functions

durtn.g back.unrd fault (a) an.d durtn.g

forunrd fault (b). The dotted l.in.e

indicates the threshol.d needed to

distinguish between. the two

st tuation.s.

t-

The shape of D1 and D2 when using a low-pass filter is shown in Figure 5.6,

where the dotted line is a threshold value bused in the detection criterion

D1 >6 or D2 >6

D1 <6 and D2 <6

forward fault ,

backward fault .

(5.30)

(5.31)

For a reliable directional detection the threshold must be such that it is

above the highest value of D1 and D2 during a backward fault. But during

each possible forward fault at least one of the detection functions must be

above the threshold.

TWONFIL calculations have been performed to determine the values of the

nonfiltered detection functions after the initial spike. The detection

functions have been determined for all possible backward as well as forward

faults {cf. Section 4.1). It appeared for line type A that the threshold

should be below 1222 units ( 1000 units is the amplitude of the phase-to­

ground voltage). It has also been found that the highest value of x 1 and x2

during a backward fault is 215 units (an impedance value of 250 Q has been

used).

Page 72: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-64-

To suppress the spikes during a backward fault, x 1 and x2 are send

through a low-pass filter with a cut-off frequency fc. The worst backward

fault situation occurs when x{t) shows a jump: A

x{t) = x.U(t) .

After the low-pass filter this read as

x{t) = ~ { 1- exp(-2ttfct)}.U(t) •

leading to the following detection function: 4x2f 2 ~

D{t) = ~ [1-2 exp{-2ttf t) + (1 + __ c_)exp{-4xf t)] c 2 c

w 0

For fc~w0/2tt the highest value (reached for t=O) is equal to

A 2ttfc Dmax = x -w-- .

0

This value must be below the threshold 6, so

A

(5.32)

(5.33)

(5.34)

(5.35)

(5.36)

For 6=1222, x=215, this gives fc=284 Hz. For a forward fault during voltage

maximum this low cut-off frequency introduces no problems. The fault will be

detected illlllediately due to the high spike in the detection function.

Problems will arise however for faults around voltage zero, when x{t) is a

ramp function A

x{t)= w0

x t . (5.37)

After the low pass filter the shape is as follows:

A W X { } x(t) = w

0 x.t- ~f 1- exp{-2ttfct) ,

c (5.38)

leading to the following detection function:

D{t) = ~ wo [ [ t 1-e~~~fct) ]2

+ [ 1-exp::2ttfct) ]2

]~ . (5.39}

During an RN fault x=1400 units, together with fc=284 Hz. the threshold of

1222 units will be exceeded after 1030 JiS. This is not much faster than

obtained with the considerably more simple Johns' algorithm.

Multiple reflections will result in multiple spikes in the detection

functions leading to a constant noise level of considerable magnitude. This

calls for even lower cut-off frequencies and thus even longer detection

Page 73: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-65-

times. So despite of the more complicated calculations Dommel's algorithm is

not faster than others.

5.3. Results of the testing of Johns' algorithm

~he atg.<Ytt,tha

The algorithm by Johns [ 1980] has been used as a starting point for the

extensive testing. It has been chosen due to it's simplicity. During the

testing some modifications have been introduced leading to the algorithm

described in this section.

After the superimposed quantities have passed a low-pass filter with a

cut-off frequency 1/T ( T being the travelling time of the line ), four

detection functions are calculated:

D Fw _ 1 - ( Vt - Vs - R, ( it - is

D2Fw ( v,. - Vt - R, ( i,. it

01Bw

( Vt - Vs + R, ( it is D Bw _

2 - ( v,. - Vt + Rt ( i,. - it

(5.40)

(5.41)

(5.42)

(5.43)

As compared to the original algorithm other combinations of phases have been

used to reduce the number of calculations needed (compare (5.40) through

(5.43) with (5.20) through (5.25) ).

The following detection criterion will be applied:

[IDtFwl<o and ID2Fwl<o]and[IDtBwl>o or ID2Bwl>o]: Backward fault. (5.44)

IDtFwl>o or ID2Fwl>o : Forward fault , (5.45)

[IDtFwl<o and ID2Fwl<o]and[IDtBwl<o and ID2Bwl<o]: No fault . (5.46)

A backward fault is concluded if one of the backward detection functions

becomes high while both forward detection functions are still low {5.44). In

the original algorithm a backward fault was concluded if the above was valid

for at least one of the modes. During some forward double-circuit faults the

following situation arises : ID1 Fwl<o. ID/wi>o. ID1Bwl>o. ID2Bwl>o. This

leads to an incorrect blocking with the original algorithm. but to a correct

tripping with the new one.

After the detection of a backward fault the relay sends a blocking

signal to the other line terminal and waits for the end-of-transient to

continue its protection task:

ID1Fwl>o or ID2Fwl>o or IDtBw!>o or ID2Bwl>o :

end-of-transient not yet reached , (5.47)

Page 74: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-66-

ID2Fwl<b and ID2Fwl<b and IDtBwl<b and ID2Bwl<b

end-of-transient reached {5.48}

After the end-of-transient a clearing signal is send to the remote line

terminal. The end-of-transient will be reached after a few periods of the

power frequency.

If the relay is not in the blocking mode a forward fault is concluded

if one of the forward detection functions becomes non-zero. After a forward

fault has been detected the relay sends a clearing signal to the other line

terminal and waits for the reception of a clearing or blocking signal. After

receiving a clearing signal a tripping signal is generated by the relay if

the forward fault remains. If a blocking signal is received no tripping

signal will be generated and the relay waits for the end-of-transient.

WaGe-imPedance ~ettin~

The optimum setting of the wave impedance (the one leading to the lowest

threshold. cf. Section 4.3) is given in Table 5.1 together with the

corresponding threshold value for the three different line types.

line A line B line C Table 5.1. OptiiiiUlll impecUm.ce

(Q} 266 276 254 setting R1 and miniii!UlR threshold

b (units) 145 200 235 setting b for different line

b' {units) 239 270 304 types. The last row gives the

m.intii!UlR threshold when the

tmpecUm.ce setting shows an

uncertainty of 5%.

0 @ 1~ @ tg It)

jN Ill Ill

~ -1: ·c: :I :I :I

16 0 0 ... N

250 260 n2~ 240 .n-2-m._

Figure 5.7. Influence of im.pecUm.ce setting on m.ifUJliU.Uil threshold value for

three different tine types.

Figure 5.7 gives the influence of the impedance setting on the

threshold value. It gives an impression of the additional threshold needed

when the impedance setting deviates from the optimum value. Table 5.1 gives

Page 75: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-67-

the minimum threshold value in case the impedance setting deviates 5% from

its optimum value.

~h~e~hotd ~ettin~

The forward detection functions must remain below the threshold for some

time, after a disturbance in the backward direction. To put it the other way

around: the threshold value must be higher than the highest possible value

for the forward detection functions during backward disturbances. Four

mechanisms can be distinguished to create an undesirable non-zero value for

the forward detection functions:

1. the incorrect modal transformation used; the influence of this is given

in Table 5.1 row 2;

2. an incorrect frequency value during the derivation of the superimposed

quantities; this leads to a maximum error of about 100 units: (cf.

(4.15) with 0=1800 units);

3. an incorrect value of the wave-impedance setting (cf. Figure 5.7);

4. all kinds of noise picked up from the outside world, or created inside

of the protection system (e.g extragalactic noise. radio stations,

measurement errors and quantisation errors): a substantial part of the

external noise will be suppressed by the low pass filter and false

trips due to short duration spikes like lightning are. in general. not

possible because of the verification time introduced.

Settings for the three line types discussed here are given in Table 5.2. The

last column gives a setting that can be used for all three line types. The

threshold value is higher for this setting {making fault detection slower)

and it is not clear whether this setting holds for all possible line types.

line A Line B line C Universal R, (Q) 266 276 254 260

b (units) 400 430 470 550

Table 5.2. Relay settings for the three different line types

and universal settings usefuU for "all" U.ne types.

The following error sources have been incorporated in the thresholds of

table 5.2.:

the nonbalance of the line;

5% error in wave impedance setting;

0.5 Hz error in stationary frequency;

50 units additional noise.

Page 76: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-68-

figure 5.8. fault on a paraLLeL circuit; T 1

1; T 2 =traveLLing time fault to relay 2.

travelling time fault to relay

After the detection of a backward fault the relay must be blocked to prevent

false detection of a forward fault due to reflected waves. The shortest time

window between the arrival of the backward waves and the arrival of the for­

ward waves occurs during faults on the parallel circuit (c£. Figure 5.12).

As soon as the waves following path A arrive at relay 1 (T1 after raul t

initiation) the backward detection functions will become non-zero. The

forward detection functions become non-zero as soon as the waves following

path B arrive (T1 +2T2 after fault initiation). I£ the fault is close to

relay 2 the time difference (2T2 ) is very short and relay 1 will probably

{incorrectly) detect the fault as a forward fault. Fortunately relay 2 will

have almost twice the travelling time of the line (2T1 ) to detect the fault

as a backward fault. The communication between the relays will prevent the

disconnection of the non-faulted circuit.

The worst situation is a fault midway on the parallel circuit. In that

case both relays have only one travelling time (T1 +T2 ) available. So after a

backward fault the relay must go into the blocking mode within one

travelling time of the line-to-be-protected.

~ication and ~e~ification time

With directional detection there are two ways of communication between the

line terminals: a "directional blocking scheme" and a "directional clearing

scheme". In the t:LL~e.cUonai ~ioekLng. !!.eke-me a tripping signal will be

generated in case of a" forward raul t not followed by the receipt of a

blocking signal within a certain time. This verification time must at least

be equal to the difference in travelling time between the communication link

and the high-voltage line. It must also be longer than the minimum

verification time as introduced in Section 4.3.

In the t:LL~ectLonai cie~L~~ !!.eke-me. a tripping signal will be generated

in case of a forward fault followed by the receipt of a clearing signal. The

time between detection and tripping depends on the fault position. For a

fault close to the relay it is equal to the sum of the travelling times of

Page 77: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-69-

the communication link and the high-voltage line. For a fault close to the

remote line terminal it is equal to the difference in travelling time.

In both schemes a tripping signal must only be generated if the forward

detection function remains above the threshold during the verification time.

Figure 5.9 gives the verification and communication time as a function of

the line length. The travelling time of the communication link is considered

to be 530 J.ts/100 km (a fiber optic link) versus 330 J.ts/100 km for the

high-voltage line. The upper dotted line denotes the sum of the travelling

times, the lower one the difference between them. The solid curve gives the

minimum verification time needed to cope with lightning. for a threshold

setting of 400 units.

In case of a blocking scheme the communication time (equal to the

difference in travelling time) is too short to cope with lightning. An

additional verification time will be needed. Only for lines longer than 200

km this is not necessary. In case of a clearing scheme the verification time

due to communication is in between the two dotted lines. To cope with the

worst case (a stroke close to the remote line terminal) the same additional

verification time as with the blocking scheme is needed.

It can also be concluded from figure 5.9 that a blocking scheme is not

faster than a clearing scheme for short lines (i.e. shorter than 35 km).

t t s

I / I 1 / / 1 I I I

o I / g I 1

I / I I I I I I I I I

50 100

I I

I

I I

I I

I

/ I

I

I I

/

200 d(km)--

Figure 5.9. Duration of "light­

ning stroke" in foriiXlrd detection

function for different line

lengths. The dotted Lines give

communi cat ion time.

Page 78: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

I

-7o-

~aatt detection time

As shown in Section 4.4 the detection time is very small for most faults,

typically 10-100 ~s. Only for faults around voltage zero the detection time

can be much longer. The maximum detection time depends on the feeding

network as well as on the distance to the fault. Table 5.3 gives this

maximum for the network of Section 3.5. The fault was situated at a distance

of 12 km from Diemen and 45.7 km from Krimpen. All detection times appeared

to be below 1.5 milliseconds. The tripping time will be about 500 ~s for

most faults but increase to somewhat below 2000 ~s for faults around voltage

zero. It follows from Section 4.4 that only a small region around voltage

zero possesses long detection times. For a single-phase-to-ground fault the

width of this region is about 30°. In case of a verification time of 500 ~s.

24% of the power frequency cycle will show a tripping time above 1

millisecond. But this will be much less than 24% of the number of faults.

Fault

Diernen

R-N 1120 ~s

S-N 1050

detection

Krimpen

1460,.Js

1400

Table 5.3. Detection time for single­

I~tase-to-grOlllld and I~tase-to-phase

fa.u:tts.

lT-N 1010 1440

R-S Sr,O 1220

R-T 500 660

S-T 520 730

Nondetect~Le ~~~ fauLt~

After the detection of a backward disturbance the relay is blocked. This

blocking will last for a few cycles of the power frequency. If a fault

occurs on the line-to-be-protected during the blocking time the relay will

not react. Examples of these nondetectable faults are:

faults during line energizing;

faults evolving from the parallel circuit;

a fault in the zone-to-be-protected within a few cycles after a fault

on the parallel cicruit or on an adjacent line: this might occur due to

two lightning stokes shortly after each other or due to some strange

coincidence.

Figure 5.10. Waves during a non­

detectable double-circuit fault.

Page 79: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-71-

Also some rare double-circuit faults showed to be nondetectable. With

these faults the zero crossings of the forward detection functions (i.e. of

the waves generated at fault initiation) do not coincide for both circuits.

Figure 5.10 shows the travelling waves for a double-circuit fault that

occurred close to a zero crossing in circuit 1. Trave ll i ng waves are

initiated in circuit 2. but not in circuit 1. At the busbar behind the relay

position both circuits are connected. A forward wave in one circuit will

cause a backward wave in both circuits. In circuit 2 forward and backward

detection functions exceed the thresholds leading to the detection of a

forward fault. In circuit 1 only the backward detection functions exceed the

threshold. This will cause the relay to make a wrong decision (backward

fault instead of forward fault).

8 I()

8 I()

I

········ ........... .

\.----'\ 0 sw

I, 1 ...... :~······· .......... .

• ...... '\ ..... .! \ i :

0Fw 2

-t (~S)

Figure 5.11. RVN-fault, .P=%0

, at 12 km.

frOIIl Diemen and 45.7

km. fr011t Krimpen (cf.

Figure 3.10). De tee-

tion functions are

given for the relay in

Dtemen in circuit 1.

Dotted Lines denote

the threshold.

Figure 5.11 shows an example of such a nondetectable situation. An RVN fault

at a fault-initiation-angle of 96° causes travelling waves in circuit 2 but

not in circuit 1. The figure shows the situation for the relay in Diemen.

The forward detection functions remain below the threshold for some hundreds

of microseconds, while D1 Bw exceeds the threshold soon after the waves ar­

rive at the relay position. Therefore a backward fault is detected instead

of a forward fault. Even if the relay in Krimpen detects a forward fault,

both relays will be blocked and the (faulted) circuit will not be disconnect

ed. The other circuit shows no problems during this fault situation.

Although this is an extremely rare situation a back-up relay will be

necessary for this. According to Light [1979] about 130 faults occur each

year in the British CEGB network. Three percent of them are double-circuit

faults. There are 53 types of double-circuit faults, 15 of them show the

behaviour discussed above. Suppose all double-circuit faults and all

Page 80: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-72-

fault-initiation angles are of equal probability. Further suppose that those

15 fault-situations are nondetectable during 10 X of the power-frequency

cycle. In that case 1 nondetectable double-circuit fault is expected each 10

years on the CEGB network.

~ ~umaa~ of tke ~e~att~

It is shown in this section that the somewhat modified version of Johns'

algorithm is capable of generating a tripping signal within about 500 J.Ls.

This time holds for faults with a considerable voltage jump. Faults around

voltage zero show a longer detection time. The longest tripping time is

about 2000 J.LS.

A few situations showed to be nondetectable:

-a fault during (due to) line energizing;

-a single-circuit fault evolving to a double-circuit fault:

- a fault within a few cycles after a "backward disturbance";

a few rarely occuring double-circuit faults.

A false trip will only be generated in case of a direct lightning

stroke with an extreme shape (high maximum current, slow decay) but not

leading to a flashover.

Page 81: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-73-

6. Differential protection

The basic assumption for travelling-wave-based differential protection is

the same as for directional detection: " a source of travelling waves in the

zone-to-be-protected is a fault". The detection functions, determined from

incoming and outgoing waves at both line terminals, are proportional to the

fault current. This leads to a highly reliable algorithm but at the same

time it calls for a highly reliable communication link. Like with

directional detection, voltages and currents have to be measured at the line

side of the circuit breakers.

6.1. History

The algorithm for travelling-wave-based differential protection is proposed

by Takagi et al. [1977]. When a line is healthy, the incoming waves at one

terminal will be outgoing waves at the other terminal after one travelling

time.

i .L I Flgure 6.1. Line-to-be-protected and -0+ + definitions used for differential

v T z v' protection.

For a loss less single-phase line (cf. Figure 6.1} Bergeron's equations

(2.22) and (2.23) read as

v(t) + Z.i(t) = v' (t+T) - Zi' (t+T)

v(t} - Z. i(t) = v' (t-T) + Zi' (t-T)

(6.1}

(6.2)

where Z and T are wave impedance and travelling time, respectively. For a

multi-phase line these equations hold for each modal component. The soon a

fault occurs on the line Bergeron's equations do not hold anymore. This has

led to the following detection function for mode k:

fk(t)=ik(t)+ik' (t-Tk) ~{vk(t)-v.; (t-Tk)} . (6.3)

It can be proved that this detection fucntion is equal to the (modal}

current at the fault position. This led to the following detection

criterion, for a three-phase line:

ft::O and f2::0 and E3::0 Et~ or f2~ or E3~

, no internal fault ,

, internal fault .

(6.4)

(6.5)

Takagi at al. [197Sa, 1978b] use equation (6.3) for their "simply d' Alembert

relay". Instead of modal quanti ties they use phase quanti ties. They have

Page 82: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-74-

studied the influence of variations in the impedance setting Z and the

travelling time setting T. An incorrect travelling time setting appears

shown to introduce spikes in f(t) during an external fault. This may cause

misoperation of the relay. A low-pass filter is proposed to reduce this

risk. An error in impedance setting does not seem to have much influence on

the detection functions.

6.2. Results of the testing

Takagi's algorithm has been modified slightly to make it correspond to the

standard algorithm of Section 4.2.

~he aigc'tt.tha

From the actual values of filtered voltages and currents measured at both

line terminals, two detection functions are calculated:

£1 (t) = [ {vt(t)-vs(t)} - R1{tt(t)-is(t)} ]

- [ {vt' (t-T)-vs' (t-T)} + R1{it' (t-T)-is'(t-T)}] • (6.6)

[ {vr(t)-vt(t)}- R1{ir(t)-it(t)} ]

- [ {vr' (t-T)-vt' (t--r)} + R1{ir' (t--r)-it' {t--r)} ] (6.7)

where R1 and T are wave impedance setting and travelling time setting,

respectively. The following criteria are used for fault detection:

l£t{t)l > b or l£2{t)l > o internal fault •

l£t(t)l < o and l£ 2{t)l < o no internal fault

{6.8)

{6.9)

After the detection of an internal fault, the verification time is started

as introduced in Section 4.3.

~he OOARUnicatLon iink

A differential relay uses voltages and currents from both line-terminals. To

transmit these signals communication links are needed (cf. Figure 6.2).

Three voltages and three currents are transmitted from terminal 8 to termi­

nal A. Three tripping signals are transmitted back to terminal B. Shorter

communication links are present between the relay and the circuit breaker

and between the relay and the measurement transformers at terminal A.

Page 83: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-75-

3x trip y 3V 3i

A l B

'-" '-"

Figure 6.2. Communication links used for differential protection.

The relay takes the difference between local quantities and remote

quantities one travelling time of the high-voltage line back in time. The

remote quantities are transmitted to the relay via a communication link. As

the travelling time of this communication link is always larger than that of

the high-voltage line. the remote quantities are delayed too much when they

arrive at the relay. To compensate this excess delay the local quantities

must be delayed too. This local delay must be equal to the difference in

travelling time between the communication link and the high voltage line. It

is interesting to note that this is equal to the minimum time needed for

communication when using directional detection. But with directional

detection this time could be used as a verification time to prevent false

tripping. This is not possible with differential protection as the detection

functions are calculated after the delay. So this difference in travelling

time will lead to a fundamental delay in fault clearing.

For a glass fiber link the tr~velling time will be about 500 ~-ts/100 km.

for the high-voltage line this is about 330 ~-ts/100 km. The additional delay

will be about 200 ~-ts/100 km plus the delay in transmitter and receiver. In

case a cable is used as a communication link, the delay will be longer. The

transmitter/receiver delay is not included in these figures.

1ettt~g of tapedaace ~a t~etttng ttae

As already stated in Section 4.1, all kinds of external disturbances have

been studied by using TWONFIL as well as EMTP. From this study it appeared

that "backward external faults" (c£. Figure 4.3) give rise to higher values

of the detection functions than "forward external faults". The highest

values are reached when the first waves arrive at substation A. The

detection functions remain at this value for twice the travelling time of

the line. As the (superimposed) remote quantities are zero during twice the

travelling time of the line, the detection functions of differential

protection (6.6-6.7) transfer to the forward detection functions of

directional detection (5.40-5.41). Because of this the impedance setting for

directional detection can also be applied to differential protection. So can

the corresponding value of the threshold. Both can be found in Table 6.1.

Page 84: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-76-

AI~ 61" I Figure 6.3. Backux:trd (1} and

72 ·fonoo.rd (2} external faults.

~ The travelling time setting will be midway between the travelling time

of the fastest mode and that of the slowest aerial mode (cf. Section 4.3).

~Pike~ i~ the detection tunction~

It was shown in Section 4.3 that the different modal velocities cause spikes

in the detection functions. The highest spikes occur for a forward external

fault, just outside of the zone-to-be-protected (i.e. a fault in the remote

substation}.

One of the most beautiful examples of spikes in detection functions is

shown in Figure 6.4. The simulated network was the basic network of Figure

3.10 with the line between Diemen and Krimpen replaced by a 50 km line of

type B. An RSTN-fault at a fault-initiation-angle of 60 degrees occurred in

the substation Diemen. The differential relay was situated in the substation

Krimpen and protecting circuit 1 of the line to Diemen. Wave impedance and

travelling time have been set according to their optimum values.

500

t{JJS) --500

-1000

Ftgure 6.4 Spike in detection function.

Page 85: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-77-

In case the travelling time is not set according to its optimum value

the spikes in the detection functions are of longer duration. Expressions

for the height of the spike, as well as the time-above-threshold are given

in Section 4.3. Of interest here is the time-above-threshold; it must be

shorter than the verification time. With f =1/T, (4.12) transfers into c

t = ~ ln { ~ S . O.~At+T} + T + 0.5At {6.10)

where At is the difference in travelling time between the fastest and

slowest aerial waves and T the error in travelling time setting. To prevent

accumulation of spikes due to multiple reflections the time-above-threshold

may only be a fraction of the travelling time of the line.

The height of the block S is at maximum about 4000 units. a threshold of 450

units and a maximum allowed time-above-threshold of 20% of the travelling

time of the line allows for 3% error in travelling time setting for line

type A and C; for line type B the allowable error is only 1%. This calls for

a highly accurate synchronisation between both line terminals. More details

on this will be given in Section 8.3.

~h~e~hota ~etttn~. ~e~Lttcatton tL•e

Multiple reflections will cause multiple spikes in the detection functions.

They are of much lower amplitude than the first spike, especially after

filtering. These filtered multiple spikes cause a kind of background noise

on the detection functions. This calls for an increase in threshold value.

An increase of about 150 units appeared to be more than sufficient to

prevent false tripping. This leads to the following threshold settings for

the three line types :

450 units for line type A;

475 units for line type B:

500 units for line type C.

The following error sources have been incorporated in this setting:

5X error in impedance setting:

3% error in travelling time setting (1% for line type B):

150 units noise due to multiple reflections:

50 units additional noise.

The minimum verification time needed to cope with lightning strokes is only

a 11 ttle shorter than the one for directional detection. All settings for

the differential relay are given in Table 6.1.

Page 86: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-78-

line A line B line C

Impedance 266 Q 276 Q 254Q

Threshold 450 units 475 units 500 units

Travelling time 346 J.I.S 364 j.I.S 342 j.I.S

Verification time 260 j.I.S 260 j.I.S 260 j.I.S

Cut-off frequency 3kHz 3kHz 3kHz

Table 6.1. Settings for differential protection of a 100 km line.

~i.,ne ene'l.g-L:fLttg

The algorithm for differential protection shows a "perfect" discrimination

between internal and external faults. However during line energizing (or

during fast reclosure) a nondetectable situation occurs. The relevant part

of the high-voltage network is shown in Figure 6.5. The circuit breaker on

the right remains open whereas the left one closes. The differential relay

will detect any fault on the line in between the measurement transformers.

Problems might occur for a fault in one of the two small regions A and B in

between the circuit breaker and the measurement transformer. A fault in

region A can be detected by the busbar protection or by a special zero

voltage detector (the voltage drops to a very small value almost immediately

due to such a close fault). A fault in region B will not be detected. As

this is the place where the highest overvoltages occur during line

energizing, it is the place with the highest chance of insulation failure.

Switch-on-to-fault situations in regions A and B also occur when the ground

connectors are not removed after a line has been out of operation. This is a

situation that seems to occur quite often. A special algorithm will be

needed for switch-on-to-fault detection. Some possible solutions are

proposed in Section 7.4.

Figure 6.5. Line energizing and differential protection.

Page 87: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-79-

~Peed ot taait detectLon

The time between fault initiation and the generation of a tripping signal

consists of the following contributions:

a. travelling time between the fault position and the relay position; this

contribution will not be considered here;

b. additional .delay to compensate the longer travelling time of the

communication link; it is about 200 ~s per 100 km, as discussed before;

c. the detection time as discussed in Section 4.4; the detection time for

faults around voltage zero is given in Table 6.2 for line type A for

the same situations as shown in Table 4.4; it is about equal to the one

for directional detection:

d. the verification time (to exclude false tripping); this is between 200

and 400 ~s depending on the line length.

For a 100 km line the tripping time (b+c+d} will be between 500 and 1600 ~s.

when using a glass fiber communication link.

Fault time (!-is) TabLe 6.2. Detection time for single-phase-to-ground

and phase-to-phase fauLts on Line type A. RN 1100

SN 1000

1N 1100

RS 900

Rf 550

ST 600

6.3. Differential or directional ?

In the preceeding chapters similarities as well as differences between

directional detection and differential protection have been found:

both are able to generate a tripping signal within a few milliseconds;

the hardware requirements will be about equal for both principles.

except for the derivation of the superimposed quantities with

directional detection and the synchronising between both terminals for

differential protection;

both might generate a false tripping signal due to extremely shaped

direct lightning strokes:

directional detection shows a few nondetectable situations but

differential protection shows none.

Although differential protection might show hardware problems due to the

synchronization needed, the author gives prefers this one because of its

high reliability. But others may have a different opinion in this.

Page 88: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-so-

7. Other algorithms for travelling-wave-based protection

7.1 History of distance protection

~he c~~eLatLon aethod

The time delay between incoming and outgoing waves at the relay position,

can be a measure for the travelling time between the relay and the fault and

hence of the distance to the fault. This method for distance protection has

been proposed by Vitins [1978] and was further developed at the University

of Manchester [Crossley and McLaren, 1983; McLaren et al., 1985].

__!_.

:· ~· 1_ : Figure 7.1. Incoming (F) and

outgoing (B) waves as used for • /\JV\f"'- F

correlation method.

Consider the single-phase situation shown in figure 7.1. From the actual or

superimposed voltages and currents two quantities are formed:

F(t) = R i{t) + v{t)

B{t) = R i{t) - v{t)

(7.1)

{7.2)

where R is the wave impedance setting. In case of a solid fault and a travel

ling timeT between the relay and the fault, the following expression holds:

B{t) = F{t-2T) . {7.3)

From B{t) and F{t) a correlation function can be formed: T

~(x) = T~x I B{t)F{t-x}dt , (7.4}

X

where T is the measurement window. The correlation function ~{x) will show a

maximum for x=2T.

Crossley and McLaren [1983] use superimposed modal quantities to

calculate correlation functions according to {7.4}. But {7.3) only holds for

modal quantities during a three-phase fault. In case of a single-phase fault

the maximum in the correlation function is not as pronounced as during a

three-phase fault. This causes difficulties in fault detection, especially

for faults close to one of the line terminals. Problems also appear for

faults around voltage zero. In most situations the algorithm cannot

discriminate between a fault at a distance x behind the remote terminal and

a fault at a distance x from the relay. Some problems can be solved by

combining the correlation method with Donmel' s method [Koglin and Biao

Zhang, 1987], by using two different measurement windows [Shebab-Eldin and

Page 89: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-Bl-

McLaren, 19BB] or by using the difference in travelling time between the

ground mode and the aerial modes [Christopoulos et al., l9B9]. But still no

satisfying solution has been found.

::ltoh.i..a(l.' aLgcnithm

Kohlas [1973] proposes a method to calculate the voltages and currents along

a single-phase line from the voltages and currents measured at one of the

line terminals. The line is considered to have frequency independent R, L

and C values and G = 0. He gives complicated expressions for voltages and

currents along the 1 ine and rewrites these to somewhat less complicated

discrete expressions.

When the voltages along the line are known, a fault will show up as a

place where the voltage remains zero. Ibe and Cory [19B6, l9B7] use the

discrete expressions of Kohlas to calculate voltages along the line and from

those the following detection function:

T-z/c

d2

[ 1 I 2 ] G(z) = d? T-2z/c v (z, t)dt ,

zlc

(7.5)

where c is the propagation velocity of the waves and T the measurement

window. The fault position will show up as a very sharp maximum in G(z).

....!.!i: tl

vlz,tJ AZ At

i(l!~)

V (Z+IIZ,t)

Figure 7.2. Part of a stngte-phase

tosstess tine.

Our experiments have shown that it is not necessary to use the

complicated expressions of Kohlas. Leaving out the terms caused by the

resistance R, will give expressions that can be derived from Bergeron's

equations, (2.22) and (2.23). These expressions read as (cf. Figure 7.2):

2v(z+Az,t) = v(z,t+At) + v(z.t-At)

- Zi(z,t+At) + Zi(z.t-At) ,

2Zi(z+Az,t) = v(z,t+At) - v(z,t-At)

+ Zi(z,t+At)+ Zi(z.t-At)

(7.6)

(7.7)

Bergeron's equations as weel as (7.6) and (7.7) hold for a single-phase line

and for the modal quantities on a multi-phase line. But only phase

quanti ties can be measured and in general, only the phase voltage at the

fault position is equal to zero. From (7.6) and (7.7) the following

expression can be derived for the phase currents:

Page 90: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-82-

I(p)(z+!z,t) = Q y(c) S-1

[ y(P)(z,t+!t)- y(P)(z,t-!t)

+ I(p)(z,t+!t) + I(p)(z,t-!t) • (7.8)

where y(c) is the inverse of the wave impedance matrix z(c). A similar

expression can be derived for the phase voltages. For the balanced

three-phase line of Section 2.3.1 these equations transfer to:

2vr(z+!z,t) = Vr(z,t+!t) + Vr(z,t-!t)

- Ztir(z,t+!t) + Z1 1r(z,t-!t)

- t (Zo-Z1 ) {to(z,t+!t)- i 0 (z,t-!t)}

2Z1 ir(z+!z,t) = Vr(z,t+!t) - Vr(z,t-!t)

+ Z1 ir(z,t+!t) + Z1 1r(z,t-!t)

-(Z0 -Z 1 )/3Zo {v0 (z,t+!t)- v0 (z.t-!t)}

where i 0 =ir+i 8 +it

and v0 =vr+v5 +Vt

(7.9)

(7 .10)

Similar equations are valid for the other phases. From the voltage profiles

six detection functions are determined:

T-z/c

F(z) = T-2!/c J v2(z,t)dt

z/c

(7 .11)

Three detection functions are calculated from the phase voltages Vr.v •• vt,

to detect single-phase-to-ground faults; three detection functions are

calculated from the line voltages vr-v8 , v,.-vt• vt-Vr to detect

phase-to-phase faults. If a fault is detected by only one detection function

a single-phase trip will be generated. A three-phase trip will be given as

soon as two or more detection functions detect a fault.

A fault is detected if all three conditions below are true:

the detection function F(z) shows a minimum not coinciding with one of

the line terminals;

if Fmax and Fmin are maximum and minimum value of F(z) respectively,

than Fmax/Fmin > !;

at the suspected fault position 50% of the voltage values must be, in

absolute value, below 100 units.

EMTP simulations have shown that a fairly good discrimination can be made

between internal faults and external faults [Van Dongen. 1988]. Still some

problems remain:

faults close to one of the line terminals are not detected;

most of the double-circuit faults are not detected;

Page 91: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-83-

the calculations to perform need a lot of computation time, making a

relay based on this principle slow.

Nimmersjo and Saba [1989] use equations somewhat more complicated than

(7.6) for the detection of a close fault. They include losses by introducing

an exponential factor in Bergeron's equations. A low-pass filter with a low

cut-off frequency is used. Their experiments yield a tripping time of about

10 mi 11 !seconds.

~ke atgo~LthM ot ~L~topouto~

Christopoulos et al. [1988, 1989] propose an algorithm that derives

information from successive reflections of travelling waves. From the

measured time delay between incoming and outgoing waves a fault distance is

estimated. This leads to a certain redundancy. In case of a contradiction a

new distance is estimated.

The principle shall be reproduced in a modified form. From the first

waves arriving at the relay position the direction to the fault is

determined by using the following detection functions:

DFw = v - Zi ,

r/'W = v + Zi

(7.12)

(7. 13)

In case of a forward fault more computations are performed. The reflected

wave travelling from the relay position back to the fault (with amplitude

r/'W) is reflected at the fault and travels back to the relay position again.

Upon arriving there it causes a jump in DFw and r/'W. From the jump ADFw in

DFw and the pre-jump value of r/'w. the fault impedance RF can be determined:

(7 .14)

From the elapsed time between the first and the second jump in DFw an

estimate for the fault distance is found. The pre-fault voltages and

currents at the relay position are used to calculate the pre-fault voltage

at this estimated fault position. If the pre-fault voltage is equal to VF

and the post-fault resistance equal to RF' the amplitude of the initiated

wave is equal to: Fw 2Zo

D = - Zo+~ VF (7 .15)

This wave is detected at the relay position as the first jump in ufw. From

this jump a second estimate for the fault resistance is found:

0Fw _ 2Zo (7. 16)

Page 92: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-84-

If this value agrees with the value of (7.14) the fault is considered to be

at the estimated distance. If the values do not agree the procedure is

repeated for another jump in DFw. This is continued untill the fault

position is found or untill the fault is shown to be outside of the

zone-to-be-protected.

The algorithm has been tested for a few situations. It has been shown

by Christopoulos et al. [1988, 1989] that it is possible, in those

situations, to distinguish between an internal and an external fault.

7.2. Double circuit current comparison protection (DOOCP}

The algorithm discussed in this chapter deviates from the algorithms

discussed before on two counts:

quantities from both circuits of a double-circuit line are used:

The algorithm makes use of a specific network configuration.

Special measures have to be taken to prevent the above differences from

becoming disadvantages of DOOCP.

~he P'Li-nci-pie

Figure 7.3. Double-

circuit tine with

ZJ3 I® ZJ, ~2 internal fCllllt (1)

and external fCllllts

(2,3). R denotes a

ZXXJ.:;P- relay .

Consider the double-circuit situation shown in Figure 7 .3. In case of an

internal single-circuit fault (position 1), the currents in the faulted

circuit will be different from the currents in the non-faulted circuit. In

case of an external fault (position 2 or 3), the currents in both circuits

are equal. This leads to a very simple relaying algorithm:

(ir=iu) and (i 5 =iv) and (it=iw)

(ir#iu) or (i 5 #iv) or (it#iw)

no fault

fault .

(7 .17)

(7 .18)

It holds for stationary quantities, as well as for travelling waves. The

travelling-wave-based algorithms is be named double-circuit current

comparison protection or in short DOOCP. The principle has been used in the

past, based on the balance of stationary currents [Clemens and Rothe, 1980].

It has never been in general use, because [Blackburn 1987]:

it is not applicable to single-circuit lines;

it must be disabled for single-circuit operation:

Page 93: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-85-

it requires interconnections between the controls for the two lines,

which is not desirable for reasons of reliability:

it can experience difficulties for a fault involving both circuits.

The first disadvantage is fundamental and applies also to the travelling

wave version. The second disadvantage is strongly related to the first one.

It calls for some kind of external blocking when only one cicrui t is in

operation. This used to be a problem in the past but integration of

protection and control will facilitate it to a large extend. Chapter Swill

provide an example of such an integrated scheme.

In case usually only one circuit is in operation, it is of course not

very practical using ~- But in the majority of cases usually both

circuits are in operation.

The third disadvantage is overruled by tripping at most one circuit (to

prevent incorrect double-circuit tripping) and by combining I:lCXl:P with a

backup working on a single-circuit basis. The fourth disadvantage is also

overruled by this backup.

DOOCP shows a few important advantages when compared to other

travelling-wave-based algorithms:

it does not use quantities from the remote line-terminal, therefore no

additional delay nor any unreliability due to the communication link,

is introduced:

the calculations to perform are much less complicated than for other

algorithms not needing a communication link.

This section will discuss the algorithm for ~ as if it operates

independently. Chapter S will discuss it as part of a protective scheme.

Also some hardware requirements will be given there.

~he aLg.o'tLtha

AI though the basic principle is the same, the detection functions are

somewhat different from (7.17) and (7.18). The new detection functions only

use aerial mode quantities (cf. Section 4.2).

From the superimposed currents at one line terminal the following

"disturbance-detection functions" are determined:

X1 = R (it-is) • (7 .19)

X2 = R (ir-it) (7.20}

x3 =R (iw-iv) • (7.21)

x .. = R (iu-iw} (7 .22)

The value of R is not of any importance for the performance of the

algorithm. It is only used to get values comparable to the values of the

detection functions for directional detection and differential protection.

Page 94: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-86-

This is done by making R equal to an approximation of the aerial mode wave

impedance. In this study the round value of 250 Q has been used. Two

"fault-detection functions" are determined:

Dt = X1-X3

D2 = X2 -x .. (7.23)

(7.24)

For circuit selection two "circuit-selection functions" are determined after

the detection of an internal fault:

c1 1x1 1-1x31 C2 = 1x21-1x .. 1 .

N

Figure 7.4. Decision process of DCOCP.

(7.25)

(7.26)

A flow chart of the detection criteria is shown in Figure 7 .4. After the

detection of a disturbance (at least one of the disturbance-detection

functions exceeds the threshold f) an internal fault is detected if a

Page 95: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-87-

raul t-detection function exceeds the threshold b. If the raul t-detection

functions all remain below the threshold ban external fault is detected and

the relay will be blocked till the end-of-transient. This is to prevent a

false trip due to the unbalance of the stationary short-circuit currents

during an external disturbance.

After detection of an internal fault the faulted circuit is selected.

Only one circuit is tripped, also during double-circuit faults. This is to

rule out incorrect double-circuit trips as much as possible. After detection

of an internal fault and selection of the faulted circuit a verification

time is started.

~ett~ng ot the cut-ott t~e~enc~

For a quantitive study. the three line types of Section 3.3. have been used

in combination with TWONFIL, as well as the EMTP networks shown in Figures

7.5 and 3. 10.

ENS MAAS­~--~~~-----r------~~~--+-------~~--~VLAKT

66.2km 59.7km ~"""-- 52km

DIEM EN KRIMPEN

2R85km

G' BERG -"---

Figure 7.5. Network configuration used for EKTP testtng of rx::a:;p, The

presentations of the terminations at Ens, Diemen and .Haasulakte are the same

as discussed in Sectton 3.5. The line Geertruidenberg-Eindhouen has been

represented by its wave impedance. The stationary short-circuit current at

Kr!mpen due to a three-phase subs tat !on faut t has been increased to 50 kA on

a 380 kV basis, to get a high short-circuit current.

The external faults studied by using TWONFIL are shown in Figure 7.6.

The worst cases {highest values of the fault-detection functions) appeared

to occur for fault position 3, due to the differences in travelling time for

the different modes as discussed in Section 4.3.

Page 96: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-88-

Figure 7.6. External faults studied for DDOCP.

3

Figure 7. 7 Shape of the

filtered detectton func­

tton for DDOCP during a.

faul.t a.t the remote line

term.inal.

Figure 7. 7 shows such a spike after having passed through a low-pass

filter. The shape can be approximated as:

(7.27)

where fc is the cut-off frequency of the low-pass filter used. The values of

x0 and x 1 have been calculated for faults at the remote line-terminal. The

travelling times of the different modes have been derived from EMTP

("travelling time for the highest frequency" as used by JMARTI SETUP;

Section 3.2.3). A comparison between filtered EMTP values and filtered

TWONFIL values showed the difference to be less than 6%.

The highest values of x0 and x1 found from TWONFIL have been used to

determine minimum threshold values for the three line types. If a cut-off

frequency equal to 1/T is used, the condition that the detection function

shall not be above the threshold for longer than 0.2T during an external

fault, leads to the following minimum threshold value:

b = xo + (x1 -x0 ) exp(-Q.4n) . (7.28)

Page 97: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-89-

The minimum threshold values found under this assumption are:

line type A 305 units;

line type B 815 units;

line type C 407 units.

Using a lower cut-off frequency decreases the value of x1 , but it also makes

the tail of the spike longer. Therefore the minimum threshold is only

slightly lower. A cut-off frequency equal to 0.5/~ gives values of 251, 778

and 382 units for line type A, Band C, respectively. For fc=0.3/T they are

207, 623 and 382 units.

On line type B the initial jump in the disturbance-detection functions

after a single-phase-to-ground fault is about 900 units. In case of a

threshold above this value none of the single-phase-to-ground faults could

be detected by its initial travelling wave (cf. Section 4.4). Therefore a

cut-off frequency of 0.3/T is used. For line types A and C a cut-off

frequency equal to 1/T appears to be sui table.

q2T

100 200 d(km)-

Figure 7. 8. Minimum verification

time for the three line types as

a fWlCtion of the ttne length.

Circles are for line type A

(fc=l/T;0=300), triangles are for

line type B (0.3/T;800}, squares

are for line type C (1/T;I!OO).

Tite dotted line corresponds to 20

% of the trave n tng time of the

Une : the "maximum t tme above

threshold" for the fault detec-

tion fW1Ctions during an external

fault.

Like with directional detection and differential protection a lightning

stroke direct to a phase conductor might lead to an incorrect trip. This can

Page 98: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-90-

be prevented by introducing a verification time. As shown in Section 4.3.

the length of this verification time depends on the threshold setting and on

the cut-off frequency used. For each line type the threshold setting is

constant and the cut-off frequency is inversely proportional to the line

length. It is therefore possible to give the minimum verification time

needed as a function of the line length, as shown in Figure 7.8.

On a double-circuit line. the loss of one circuit during a short time

(e.g. 1 second) will not disturb the electricity supply. In most cases the

loss of one circuit even for a long time will not disturb the supply. It may

therefore be more practical to use a shorter verification time. in

combination with fast reclosure. Then faults will be detected faster and the

relay will detect faults closer to the remote line-terminal, as shown in the

subsection "faults near the remote 1 ine terminal". The verification time

should never be less than 20% of the travelling time of the line as this

will lead to incorrect trips due to faults in or behind the remote station.

~upe~L•Po~ed quantLtLe~

During large power flow over a high-voltage line, the unbalance between the

circuits might cause ])(XX]l to give an incorrect trip ( in case actual

current values are used). An effective current of 2500 A (corresponding to

three times the natural power flow on the Dutch 380 kV line) would cause a

maximum value for the fault-detection functions of 750 units on line type A.

This would lead to a final threshold of 1100 units which is considered far

too high. This problem can be overruled by using superimposed quanti ties.

Only a small additional threshold is needed then due to variations in the

power frequency as shown in Section 4.3. Row four of Table 7.1 gives the

additional threshold needed for the three 1 ine types in case of 0.5 Hz

frequency deviation.

~k~e~hotd ~ettLng

The fifth row of Table 7.1 gives the final threshold for the three line

types. This threshold is made up of the following contributions:

the threshold needed to keep the "time-above-threshold" for external

faults below 20% of the travelling time of the line (row two of table

7.1);

the maximum error in the fault-detection functions due to 0.5 Hz

frequency deviation (row four);

50 units additional noise.

Contrary to differential protection and directional detection, the threshold

setting shows a large variety among the three line types. This implies that

Page 99: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-91-

the relay setting must be determined for each line type before installation.

All discussion on thresholds hitherto concerned the threshold for the

fault-detection functions (o in Figure 7.4). An internal fault is detected

if, immediately after the threshold crossing of one of the disturbance­

detection functions. the raul t-detection function is above its threshold.

This implies that, during an internal fault, the fault-detection function

must exceed its threshold f before the disturbance-detection function ex­

ceeds its threshold o. According to TWONFIL calculations the fault-detection

functions show a higher absolute value than the disturbance-detection func­

tions for each internal fault. This means that taking f equal to o will pre­

vent incorrect blocking. EMTP simulations support this conclusion. It is

assumed here that the fault is not too close to the remote line-terminal.

line A line B line C

cut-off frequency 1/-r 0.3/T 1/-r

minimal threshold 305 units 623 units 407 units

verification time ( lOOkm) 300 J-I.S 350 J-I.S 325 J-I.S

superimposed threshold 47 units 138 units 21 units

final threshold 400 units 800 units 500 units

speed ~n 288 J-I.S 807 j.I.S 2fi1 IJ.S

speed ~ 2S3 J-I.S 471 J-I.S 267 j.I.S

speed~ 281 J-I.S 465 J-I.S 262 !lS

relay reach 92% 71% 89%

Table 7.1. Optillllllli setttngs and performance for OCI::CP on three different

Hnes of 100 km.

1aaLt~ ne~ the ~e•ote LLne-te~LnaL

An internal fault close to the remote line-terminal cannot be distinghuised

from an external fault close to the remote line-terminal. The relay reach

will therefore be less than 100 %. If the distance between the fault and the

remote 1 ine-terminal corresponds to a travel! ing time liT. the non£ i l tered

fault-detection function wi 11 possess a high value during a time 2\T and

then decrease to a lower value. Consider the fault-detection function to be

a rectangular pulse with a height D and a duration 2/iT, and the disturbance­

detection function to show a step X (X<D). The "time-above-threshold" is the

time between the threshold crossing of the disturbance-detection function

and the downward threshold-crossing of the fault-detection-function. For a

Page 100: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-92-

threshold o and a cut-off frequency fc it is given by:

td = 2~T - ~fc ln(XIX-6} + 2:fc ln[ ~ { 1-exp(-4:n:fc~T) } ] {7.29)

This "time-above-threshold" must be longer than the verification time.

Considering the verification time to be equal to 20% of the travelling time,

the relay reach for each of the three lines for a single-phase-to-ground

fault at voltage maximum is:

line A 92%;

line B 71%;

line C 89%.

For a three-phase fault the relay reach is a little more.

~Peed ot the GLgo~Lthm

The last three rows of Table 7.1 give the tripping time of the algorithm for

specific situations. The row "speed <1>-n" gives the tripping time for a

single-phase-to-ground fault at voltage maximum. The next row applies to

phase-to-phase faults. The last row gives the tripping time for a

three-phase fault. All values have been determined for a 100 km line. As a

comparison the tripping time of a phase-to-ground fault for differential

protection on a 100 km line (line type A) is about 600 ~s. The difference is

predominantly determined by the delay due to the communication link.

Fault type detection time TabLe 7.2. Detection

1 RN 0° Diemen 12 lon 16 j.J.S

2 Krimpen 46 lon 16 j.J.S ttm.e for zx::x::;cp • as

3 RN 90° Diemen 12 lon 797 j.J.S determined by using

4 Krimpen 46 lon relay blocked ElffP. Situations 1 5 RS 30° Diemen 12 lon 14 j.J.S through 10 heme been 6 Krimpen 46 lon '12 j.J.S studted tn the basic 7 RS 120° Die men 12 lon 612 j.J.S

network of Section 8 Krimpen 46 lon relay blocked

9 RSN 120° Diemen 12 lon 68 j.J.S 3.5; situations 11

10 Krimpen 46 lon 46 j.J.S through 11, f.n the

11 RSf 60° Diemen 58lon 16 IJ.S* network of Figure 12 Krimpen 2lon 8 IJ.S 7.5. 13 Diemen 29 lon 12 IJ.S

14 Krimpen 31 lon 12 j.J.S

"Blocked if verification time is longer than 120 IJ.S.

Page 101: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-93-

Table 7.2 summarizes a few results of EMTP-testing. The detection time

is given for a cut-off frequency of 5000Hz and a thresholds of 400 units.

Most fault situations are detected very fast, an exception are faults around

voltage zero. Faults too close to the remote line-terminal are not detected

at all. especially those around voltage zero. The latter can be overruled by

means of a transfer-trip mechanism or by using some backup algorithm.

~Le ct~cuit taaLt~

The algorithm is, fundamentally. not suitable for double-circuit faults. Two

kinds of wrong decisions occur:

during a symmetrical double-circuit fault (e.g. R-U-N) none of the

fault-detection functions will exceed the threshold and the relay will

be. blocked;

during a non-symmetrical double-circuit fault only one circuit will be

tripped.

This again calls for a backup protection.

~tage~ and di~ad~tage~

The algorithm shows the following advantages. as compared to differential

protection:

no communication link is needed;

the tripping time is smaller;

no precise setting of impedance or travelling time is needed.

DOOCP shows a few disadvantages, too:

the relay must be blocked as soon as the double-circuit line is no

longer operated as a double-circuit line;

double-circuit faults wil not be detected;

faults close to the remote line-terminal, especially those around

voltage zero, are not detected at all;

one relay is used for the protection of both circuits;

the relay setting must be determined for each line type to get optimal

results.

The next chapter will discuss a protective scheme in which DOOCP and

differential protection are used. In that case advantages of the two

algorithms are combined.

7.3. Distance protection. yes or no?

All algorithms discussed in this section have one great advantage in common:

the reliability of the protection does not depend on the availability of a

long communication link. A common disadvantage of all distance-protection

algorithms is the inability to distinguish between a short-circuit somewhat

Page 102: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-94-

before the remote line-terminal and a short-circuit in or somewhat behind

the remote substation. This problem might be overruled by using a transfer

trip scheme or by introducing a delayed tripping for faults close to the

remote line-terminal. The first solution introduces a communication link as

yet, whereas the second solution slows down the protection and is not

possible for all algorithms.

Almost all algorithms for travelling-wave-based distance protection

show a fairly high degree of complexity. This makes the implementation on a

microprocessor difficult and the relay relatively slow. It will also make a

prediction of the correct operation very difficult. These kinds of

algorithms are not very suitable for fast protection. Some of the proposed

algorithms may however be used as a "slow" remote back-up. A simple

principle for distance protection is DOOCP. Its disadvantages. can be

overruled by combining it with other algorithms, as will be shown in the

next chapter.

It can be concluded that none of the proposed algorithms for

travelling-wave-based distance protection is generally suitable for the

protection of high-voltage lines.

7.4. Switch-on-to-fault detection

7 .4.1. History

One fundamental disadvantage of travelling-wave-based directional detection

is the inability to detect a switch-on-to-fault situation. Also differential

protection shows a few non-detectable fault situations during line

energizing. To overrule this Yee and Esztergalyos [1978] use a switch-on-to­

fault detector in combination with Chamia's algorithm (cf. section 5.1). If

the initial current is zero and the current change is of sufficient

magnitude, but the voltage does not rise within a preset time limit, a

switch-on-to-fault condition is recognized. The time limit is set to 5-12

milliseconds. A similar principle is used by Johns and Walker [1988] in a

prototype relay based on Johns' algorithm. Ermolenko et al. [1988] use an

additional distance relay, disabled during normal practice.

Page 103: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-95-

7.4.2. Travelling-wave-based switch-on-to-fault detection

_/\.....!- i' Figure 7.9. Ltne energi-- zing; single-phase sttua---o 0 + +

z T tion.

v V'

Consider the (single-phase) situation shown in Figure 7.9. At the instant of

breaker closure a wave is initiated travelling from left to right. After a

travelling time T, the wave arrives at the remote line-terminal where a

reflected wave is initiated travelling back to the circuit breaker. For a

non-fault situation both waves are of equal sign and magnitude. This is no

longer true if a fault occurs somewhere on the line-to-be-protected. So the

difference between incoming and outgoing waves can be used as a fault

detection criterium.

For the line of Figure 7.9 Bergeron's equations read as:

v(t-2T) + Z i(t-2T} : v' (t-T} + Z i' (t-T}

v(t) - Z i(t) v' (t-T) Z i' (t-T}

During line energizing the other line terminal is open, so

i' (t-T) = 0 .

(7.30}

(7. 31)

(7.32}

From the above three equations an expression for the quantities on the line

side of the circuit-breaker can be derived:

v(t-2r) + Z i(t-2r) = v(t) z i(t) . (7.33)

This holds in case the line is healthy (i.e. no internal reflection point)

and if the current at the remote line-terminal is zero. This leads to the

detection algorithm below:

D(t) = {v(t-2T) + Z i(t-2r)} {v(t) - Z i(t)} . (7.34)

ID(t)l < o no fault (7.35)

ID(t)l > o fault . (7.36)

'he muttL-pha~e P~LncLPte

In case all phases of a multi-phase line are open at the remote line

terminal, equation (7.33) holds for all modes. But in general not all phases

are open. During energizing of a parallel circuit only three phases are open

(three are closed). During single-phase reclosure only one phase is open.

Both situations will be discussed further on.

Page 104: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-96-

Equation (7.33) refers to the phase currents, but (7.30} and (7.31} to modal

waves. From the two latter equations it follows:

[ y(c)(t-2T) + z(c) I(c)(t-2T)] - [ y(c)(t)- z{c) I(c)(t)]

= 2Z(c) I' (c){t-T) ' (7.37}

where V(c) and I(c} are vectors of component voltages and currents.

respectively; z(c} is the diagonal wave impedance matrix. Using

transformation matrices Sand Q (cf. Section 2.3} and the admittance matrix -1

y(c) = [z(c)] (7.38)

gives the following expression for the phase currents at the remote

1 ine-terminal:

2 I' (p)(t-T) [Q y(c) S-1

y(P) (t-2T} + I(p)(t-2T)]

- [Q y(c) S-1

y(P} (t)- I(p) (t)] . (7.39}

It is considered here that all modal waves travel at the same velocity.

Using the transformation matrices for the balanced double-circuit line, {cf.

Section 2.3.2). gives (the elements of the wave-admittance matrix are

denoted Y0 , Yd. Y1 , Y1• Y1 • Y1 ):

21r' (t-T) = [Yi Vr{t-2T) + ir{t-2T)]- [Y1 Vr{t}- ir{t)]

+ (Y0 +Yd-2Y1)/6 [vr(t-2T)+vs(t-2T)+vt(t-2T)-vr{t)-vs(t)-vt{t)]

+ {Yo-Yd)/6 [vu(t-2T)+vv(t-2T)+vw(t-2T)-vu(t}-vv(t)-vw(t)] . (7.40)

Similar expressions can be derived for the current in the other phases.

Figure 7 . 10. Three-phase re­

ctosure on a double-circuit

tine.

Page 105: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-fJl-

During the energizing of one circuit of a double-circuit line (cf. Figure

7.10) three currents at the remote line-terminal equal zero:

t .. • (t) 0

is' (t) 0

it'(t)=O

(7.41)

(7.42)

(7 .43)

So are the current differences it'-1 8 ' and ir'-it', leading to the detection

functions below:

D1 (t) = [ {vt(t-2T)-v5 (t-2T)} + R1 {it(t-2T)-i8 (t-2T)}

- [ {vt(t)-v5 (t)} R1 {it(t)-i 8 (t)} ] • (7 .44)

D2 (t) [ {v .. (t-2T)-vt(t-2T)} + R1 {i .. (t-2T)-it(t-2T)}

- [ {v .. (t}-vt(t)} - R, {i .. (t)-it(t)} ] , (7 .45)

where R1 is the wave-impedance setting.

Before energizing all voltages and currents are zero. Therefore it does

not make any difference whether the relay uses momentary values or

superimposed values. Also during the new stationary situation after line

energizing both can be used because Bergeron's equations hold for momentary

as well as for superimposed quantities. For the testing of the algorithm as

discussed in the next subsection, momentary values have been used.

To detect a switch-on-to-fault situation or a fault during line

energizing the following algorithm will be used:

ID1(t)l <band ID2 (t)l < b no fault (7.46)

ID1(t)l > b or ID2 (t)l > b fault. (7.47)

~he Pe~to~ance of th~ee-Pha~e ~~-detection

The setting of the threshold value b (7.46-47) is largely determined by the

differences in travelling time between the different modes, as discussed in

Section 4.3. The optimum travelling time setting is half-way between the

fastest and the slowest aerial waves. The threshold value and cut-off

frequency needed have been determined by using TWONFIL in the following way.

On a double-circuit line. six waves are initiated by the closing of a

circuit breaker. Each wave reflects at the open line-terminal creating six

reflected waves, leading to a total of 36 travelling times. These 36 "waves"

have been split in two: those arriving before the travelling time set and

those arriving after it. The first group leads to a negative spike, the

second one to a positive spike. The waves from the first group have been

considered to arrive all together at the arriving instant of the fastest

Page 106: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-98-

wave. The travelling time of the second group has been set equal to that of

the slowest aerial wave. After filtering this will lead to higher values for

the detection functions than in reality. The highest possible value of the

filtered detection functions has been determined for the three line types by

simulating all energizing situations.

The results of the study are reproduced in Table 7.3. The impedance setting

has been determined by neglecting the differences in travelling time. The

cut-off frequency has been chosen such that the maximum detection time is of

an acceptable value. Another value for the cut-off frequency will lead to

other values for the threshold and for the fault-detection time.

The maximum detection time is twice the time between the arrival of the

fasted reflected waves and the threshold crossing for the closing of the

R-phase at voltage zero. when there exists a short-circuit in the R-phase at

the remote line-terminal (cf. Figure 4.12).

line A line B line C

cut-off frequency 1/2T 1/5T 1/2T

trav. time (50 km} 343 I-tS 364 I-tS 342 I-tS

I impedance setting 260 Q 270 Q 250 Q 1

threshold setting 400 units 600 units 550 units

max. detection time 1120 I-tS 1620 J"S 1280 I!S

Table 7.3. setting and performance of three-phase SOTF.

~he atgo~~tha to~ ~~ngte-pka~e ~ecto~a~e

Single-phase reclosure is used after single-phase tripping. In that case

only one phase at the remote line-terminal is open. Figure 7.11 shows the

situation when phase R is rec1osed at one line terminal and remains open at

the other. In that case the detection function should. apart from a constant

factor. be equal to the right-hand member of equation (7.40), but this leads

to a complicated expression. Therefore some simplification will be made.

' R ! >.~SOTF f!LY I y s )...1

'-"I

T ,t_

u v w

·"---Figure 7.11. single­

phase rectosure.

Page 107: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-99-

After the closing of the circuit breaker the voltages in both circuits are

equal. thus also

{7 .48)

This leads to the following detection algorithm during reclosure of phase R:

Dr = [vr(t-2-r) + R1ir(t-2T)] - [vr{t) R1ir{t)]

+a [v0 (t-2T)- v0 (t)] ,

R0 is an approximation of the homopolar-mode wave-impedance.

In I < 6: fault has extinguished . r

In I > 6: fault has not extinguished r

(7.49)

(7.50)

(7.51)

Similar detection functions are used during reclosure of the other phases.

~he pe~fo~ance of ~Ln~le-pha~e ~~~-detectLon

The values of the wave impedance R0 and R1, the time delay 2T and the

threshold o, as introduced in the preceeding subsection. have been

determined by using the network models discussed before. The optimal

impedance settings have been determined by using TWONFIL. To find the

optimum travelling time setting, EMTP has been used. Due to the limited

number of possible non-fault situations (only three) it was easy to study

them all in detail. The results are reproduced in Table 7.4. The travelling

time setting is valid for a 50 km line; the optimum time delay and the

threshold value have been determined for a cut-off frequency equal to 6 kHz.

The following error sources have been incorporated in the threshold setting:

- 1.5% deviation in travelling time setting;

- 5 % deviation in wave-impedance setting;

-50 units additional noise.

The last two rows give the detection time for single-phase-to-ground faults.

The fault is considered to be a solid connection between one phase and

ground close to the remote 1 ine-terminal. The last row but one gives the

fault detection time for the closing instant at voltage maximum. The last

row gives the longest possible detection time, i.e. for a closing instant

somewhat before voltage zero.

Page 108: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-100-

line A line B line C

homopolar impedance 650Q 670 Q 790 Q

aerial impedance 265Q 2S5Q 267 Q

trav. time (2T) 354 j.I.S 355 J.tS 347.5 J.tS

threshold 450 units 725 units 525 units

detect time fast 45 J.'S 70 J.tS 50 J.tS

detect time slow 1100 J.'S }90() J.'S 1300 J.tS

Table 7.4. setting and performace for single-phase SOTF.

'£i-glttn.i-ng.

Because the SOTF-detector is only in use during short periods. the chance of

an incorrect trip due to a lightning stroke is in general very small. There

are however situations when the chance is much higher. Single-phase

reclosure is used after single-phase tripping. A large number of these

single-phase trips are caused by lightning. Therefore the chance of a

lightning stroke during single-phase reclosure may be not so small. This

subsection wi 11 discuss some measures to prevent false tripping due to a

lightning stroke.

With three-phase SOTF, the only situation of concern is a 1 ightning

stroke to a phase conductor not leading to a fault. Considering the same

shape of the lightning stroke as in Section 4.3 gives the minimum

verification time for the three line types: 260 ~s for line type A; 225 ~s

for line type B and 250 ~s for line type C. all for a 50 km line length.

With single-phase SOTF the situation is somewhat more complicated

because the homopolar mode is used. Therefore also lightning strokes to a

tower or shielding wire will cause high values of the detection functions.

This will increase the chance of an incorrect trip and therefore the need

for a verification time. The verification time needed will be about 300 ~s

for the three line-types, for a line length of 50 km.

~ ~umma~ ot the ~e~uit~,

It has been shown that fast switch-on-to-fault protection is possible. By

using simple detection functions a fault during line energizing can be

detected within some hundreds of microseconds. Only situations around

voltage zero will take more time, up till two milliseconds. The proposed

algorithm will minimize the risk of transient instability during line

energizing and single-phase reclosure.

Page 109: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-101-

7.5. Which algorithm is the best one?

An algorithm for travel! ing-wave-based protection should be capable of

detecting a fault from the travelling waves caused by the voltage jump at

fault initiation. From quantities measured during a short period of time the

algorithm must decide whether the waves originated from a fault in the zone­

to-be-protected or not. The ideal algorithm is able to do this without com­

plicated ( =expensive, vulnerable and unreliable ? ) technical facilities.

From the chapters 4 through 7 is has become clear that such an ideal

algorithm does not (yet?) exist. Therefore a compromise has to be found. The

preference of differential protection over directional detection became

already evident in Section 6.3. Differential protection is capable to

distinguish between internal and external disturbances very fast (i.e.

within a few microseconds for most disturbances but up to one or two

milliseconds for faults arounds voltage zero}. But discrimination between an

internal fault and a direct lightning stroke is only possible through the

short duration of the latter. As a consequence of this a verification time

has to be introduced. An additional delay is introduced by the necessary

communication link. As a consequence of this the decision takes place some

hundreds of microseconds after the arrival of the travelling wave.

Algorithms for distance protection have much more difficulty in

distinguishing between an internal and an external fault. Besides, the

calculations needed are, in general, much more complicated. An exception to

the latter disadvantage is the IXXX:P-algorithm being, fundamentally. only

suitable for double-circuit lines. The DOOCP-algorithm is very fast for the

majority of short circuit situations. But a number of short circuit

situations will not be detected at all. A large advantage of DOOCP is the

simplicity. No long communication links are needed nor any precise setting

of impedance or travelling time.

Summarizing: differential protection is the most reliable algorithm and

already quite fast, DOOCP is even faster and more simple but less reliable.

Page 110: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-102-

8. A Protective scheme for a double-circuit line

Three of the algorithm discussed in the preceeding chapters will be used

here in a fast protective scheme for a double-circuit line. First the

protective scheme will be described roughly, then the different protective

relays and finally the local protection control forming the center of the

protective scheme. Some thoughts shall be given concerning the

implementation of the algorithms in a protective relay.

uoccp: Double-circuit Current Comparison Protection

SOTF

LPF

CB

LPC

MMI

Switch-On-To-fault

Low Pass Filter

Circuit Breaker

Local Protection Control

Man Machine Interface.

Travelling time of the line-to-be-protected

Table 8.1. Abbreviations used in chapter 8.

8.1. The protective scheme

I I

1 I

8------------- -----ffi

Figure 8.1 . A double­

circuit line together

with protect ion aPJXlr­

atus as discussed in

the text.

Figure 8.1. shows a double circuit line together with the position of

measurement transformers, communication links and protective relays. The

following protective devices are present:

1. a J:JCXXP-relay acting as primary protection; it generates a tripping

signal for single-circuit faults with a considerable voltage jump not

too close to the remote line-terminal; it has to be blocked as soon as

one circuit is out of operation;

2. differential protection acting as a local backup; it serves as a

primary protection for the non-detectable situations of DCOCP and when

the J:JCXXP-relay is blocked:

Page 111: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-103-

3. a switch-on-to-fault detector taking over the primary protection during

line energizing and during fast reclosure;

4. a "local protection control" for adaptive relay setting, for breaker

failure detection and to serve as a communication buffer;

5. a remote backup to disconnect the fault in case all other devices

should fai 1.

The DOOCP algorithm is discussed in Section 7.2, the algorithm for

differential protection in Section 6.2 and the SOTF algorithm in Section

7.4.2.

Fault type relay line A line B line C

cp-n max DOOCP I 110 IJ.S 700 IJ.S 120 IJ.S

Differential 530!J.s 510 IJ.S 530 IJ.S

SOTF 130 IJ.S 240 IJ.S 130 IJ.S

cp-n zero IXXCP 1090 IJ.S 2110 IJ.S 1340 IJ.S

Differential 1230 IJ.S 1320 IJ.S 1340 IJ.S

SOTF 740 IJ.S 1170 !-IS 910 IJ.S

cp-cp-cp IXXCP 100 IJ.S 270 IJ.S 90 !-IS

Differential 530 IJ.S 510 IJ.S 530 !-IS

Table 8.2. Performance of the algorithms for three different lines of length

100 km. Tripping time !s given for single-phase-to-ground faults at voltage

maxii!UlJ!t (cp-n max), at voltage zero (cp-n zero) and for three-phase faults

(cp-cp-cp).

Table 8.2 shows the tripping time of the relays for some fault situations.

The settings for DOOCP are according to Table 7.7, except for the verifica­

tion time, which was set equal to 0.2 T; the settings for differential pro­

tection are as in Table 6.5 and for SOTF as in Table 7.9; for the latter a

verification time of 0.2 T has been used. The travelling time of the commu­

nication channel needed for differential protection is considered to be

600 IJ.S. For DOOCP and differential protection tripping times have been de­

termined for a fault midway on a 100 km line. For SOTF tripping times have

been determined for the closing of the R-phase in case of a solid R-N fault

at the remote line-terminal. The network simulation has been performed on

the EMTP model of Section 3.5 where the line between Diemen and Krimpen is

replaced by a 100 km line. All relays are situated in Diemen. For the

interpretation of the table it must be kept in mind that faults close to the

remote line-terminal will not be detected by DOOCP. This holds especially

for faults around voltage zero.

Page 112: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-104-

For different fault situations different relays will generate the first

tripping signal. The discussion further on applies to line type A and C. For

line type B differential protection is not slower than DOX:P for single­

phase-to-ground faults, making the protective scheme too complicated. Faults

with a considerable voltage jump not too close to the remote line-terminal

are detected by DOX:P with a tripping time of about 100 ~s. Faults close to

the remote 1 ine-terminal and double-circuit faults are detected by the

differential relay with a tripping time of about 600 ~s. Faults around

voltage zero are detected by the differential relay or by the DOX:P relay

with a tripping time of one or two milliseconds. Faults during line energi­

zing are detected by the SOTF-relay with a tripping time between 100 ~s and

1.5 milliseconds. In case one circuit is out-of-operation (the DOX:P relay

is blocked) faults on the other circuit are detected by the differential

relay.

8.2. Implementation of the DOX:P-algorithm

input unit

status word

decision unit from

LPC

Figure 8.2. Hardware requirements for

DOCCP. CB = circuit breakers, LPC = local protection control, LPF = Low

pass fitter.

Figure 8.2 shows a possible global structure for a DOX:P-relay. The six

input currents pass through a filter and reach the input unit, where eight

logical signals are formed Clx,l>f •..• lx4 l>f.ID,I>o. ID2 I>o. C1 >0. C2> 0).

They form the status word that serves as an input for the decision unit,

consisting of a microprocessor that generates tripping signals when needed.

External blocking can take place by using a logical "and" in the link to the

circuit breaker or by means of an interrupt to the microprocessor.

Figure 8.3 provides more details on the input unit. From the six input

currents four differential signals are formed. From these the four

disturbance-detection functions (X 1 through X4 ) are formed by subtracting

the value one power frequency period ago. Its length is provided from some

external device. From the disturbance-detection functions two fault­

detection functions and two circuit-selection functions are determined.

Page 113: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-105-

From the detection and selection functions an eight bit status word is

formed by comparing them with preset thresholds b and f. The status word

will be transfered to the decision unit at predefined points in time

(provided by an external clock).

Figure 8.3. The input unit.

···-~··-~·-~--····~~~~-~~----~~---'

Figure 8.4. shows the flow chart of the algorithm to be implemented on the

decision unit's microprocessor. On an MC6BOOO-processor [Harman and Lawson,

1985] the longest loop between two input-instructions takes 170 clock

cycles. In case of a 12 MHz processor clock a sampling frequency up to

94 kHz is possible (taking two inputs during the verification time of 0.2 T

this corresponds to line longer than 30 km). Synchronisation between A.D.

convertors and microprocessor is provided by means of a low-level interrupt.

External blocking is provided by means of a high-level interrupt. The

processor will turn into a wait state. External unblocking is provided by

means of a reset. After the generation of a tripping signal the processor

will turn into a wait state by itself.

8.3. Implementation of differential protection

To reduce the amount of data to be transmitted and to decrease the tripping

time. the relay is split in two identical parts, one at each line

terminal.The structure of one half-relay is shown in Figure 8.5. The input

unit forms four combinations of voltages and currents:

(vt-vs) + R(it-is)

(vr-vd + R(ir-id

(vt-vs) - R{it-is)

(vr-vd R(ir-id.

The first two signals are sent to the remote line-terminal, the other two

are provided to the local decision unit. The delay for the last two signals

Page 114: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-106-

I __ J

Figure 8.4. Flow chart for the decision processor of DCOCP. x1 stands for

IXt l)f, d1 for IDt 1)6, c 1 for C1 )0.

is equal to the difference in travelling time between the communication link

and the high-voltage line.

!l!fltclv!.OO.iA),at/-oo.

As shown in Section 6.2, only minor changes in travelling time setting are

allowed. This calls for a highly stable communication link and for some kind

of synchronisation between both units. Figure 8.5 shows a possible solution.

The clock pulses are generated at the remote terminal and recovered from the

transmitted signal. The recovered clock will trigger the local A.D.

convertor as well as the decision unit's microprocessor. As the delay

compensates the difference in travelling time between the communication link

and the line, both signals are synchronised at the input of the decision

unit. Even if the clock recovery misses a clock pulse. no error is

introduced. It is supposed here that changes in travelling time can be

neglected. In case the recovered sample frequency is stable on a timescale

Page 115: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-107-

corresponding to the travelling time of the line, delay and A.D. conversion

may be interchanged in Figure 8.5 ..

R

T

8

remote line­terminal

1------ce

.,_---•LPC

remote line­terminal

Figure 8.5. Hardware requirements for differentiaL protection.

~ampie e~eqae~cy

Differential protection works on every time scale. This is one of the main

advantages of this principle, for there is no need for a very high sample

frequency. A very low sample frequency wi 11 of course make the fault

detection too slow. To justify the term "travelling-wave-based" the sample

time must at least be of the order of the travelling time of the line. A

sample frequency of 10kHz will suite in most cases.

Hum.l..e~ ot t..i.t().

An A.D. convertor can be characterised by its dynamic range and the number

of bits used. If the analog input is higher than some upper limit, the

digital representation is equal to that of the upper limit. The same holds

for the lower limit. In case one of the A.D. convertor outputs of the

differential relay shows such an overflow the decision unit will calculate

an incorrect value for the detection function. But as long as no incorrect

decisions are taken this is not of any concern for the protection of the

line.

During an external fault the two corresponding input signals (v-Ri and

v+Ri) are of the same sign and of almost equal magnitude. In case one of

them shows an over£ low the detection function (the difference between the

input signals) will become less in absolute value. As it remains below the

threshold no incorrect decision will occur. In fact the detection function

will become zero soon after the overflow because the second function will

show an overflow, too.

During an internal fault an overflow will also cause the detection

functions to become less in absolute value. Therefore this overflow must not

Page 116: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-108-

occur before a tripping signal is generated. As the two corresponding inputs

are of opposite sign, the upper limit must be higher than the upper

threshold and the lower 1 imi t lower than the lower threshold. Values of +

2500 units and - 2500 units are more than sufficient. An 8-bit A.D.

convertor will then give a quantisation step of about 20 units (thus at

maximum 20 units quantisation noise).

~he eommantcatton channet

The communication channel must be able to transmit two 8-bi t signals at a

frequency of 10 kHz. This calls for a bit rate of at least 160.000 baud. In

case four extra bits are included for synchronisation and error detection a

bit rate of 240,000 baud is needed.

Two of these channels are needed for each circuit, i.e. four for a

double-circuit line. It is recommended to use one fiber for each circuit.

For a glass fibre the product of bandwidth and length is constant. Depending

on the type of cable this figure ranges from 10 MHz.km up to 50 GHz.km

[Lohage et al .• 1987]. In case of a bandwidth of 1 MHz (four channels in one

fibre) the maximum possible line length is between 10 km and 50,000 km. Thus

for a line length in the order of 100 km it is certainly possible to find an

appropriate glass fibre.

Figure 8.6. Flow chart of the decision unit's microprocessor.

Figure 8.6 gives a flow_chart for the decision proces as performed by the

decision unit's microprocessor. The synchronisation with the remote

line-terminal is created by means of a low level interrupt. The interrupt

can only interfere when the processor is in the "wait for interrupt" state.

On a MC68000 processor the longest loop will take about 200 clock cycles. So

even the lowest clock frequeney of the MC68000 (4 MHz) can support sample

frequencies up to 20 kHz.

Page 117: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-109-

8.4. Implementation of SOTF detection

fc

Figure 8.7. Hardware requirements for SOTF-detection.

to CB

Figure 8.7 shows a possible structure for the SOTF-detector. After filtering

of voltages and currents the two detection functions are formed by analog

circuitry. The decision process is performed by means of four comparators

(two for each detection function). a number of logical or-gates (+) and a

counter. If the counter's input is high during a number of consecutive clock

pulses, the output becomes high. A tripping signal is generated if the L~s

output is also high (i.e. if the relay is not blocked).

The settings are controled by the local protection control (LPC) or through

a man-machine interface (MMI).

The structure shown in figure 8. 7 does not make use of a

microprocessor. Microprocessor based implementations are possible.e.g. by

using the microprocessor of the differential relay.

8.5. Breaker-failure detection.

In case a tripping signal is generated by one of the local relays (DOOCP,

differential or SOTF) a number of circuit breakers need to open. If one of

the circuit breakers fails to open. the fault will not be disconnected. If

no other measures are taken, the remote backup will disconnect the fault.

Unfortunately also a number of healthy lines will be deenergized.

A less severe method is to detect the breaker failure and give tripping

signals to those circuit breakers disconnecting the fault plus a minimum

part of the high-voltage network. As most high-voltage stations are of the

double-bus type, only one busbar needs to be deenergized to disconnect the

fault.

In the proposed scheme each generated tripping signal is not only sent

to the circuit breaker but also to the local protection control. By

measuring voltage across and/or current through the breaker its opening can

easily be detected. If the breaker fails to open within a certain time,

tripping signals will be sent to the backup circuit breakers.

Page 118: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-llo-

To determine which circuit breakers should open in case of breaker

failure the substation configuration must be known. This information is

obtained from the system center computer.

8.6. The remote backup

In case all protections should fail to operate, the remote backup will

disconnect the fault. Together with the fault a number of healthy lines will

be disconnected. Therefore the remote backup must be extremely reliable.

As the most reliable relay available today is a simple time-curr.ent relay

[Heising and Patterson, 1989], it is the first candidates to serve as a

remote backup.

Despite of this the proposed scheme containes distance relays as a

remote backup. It will be considered that each relay's setting is adapted to

the momentary load flow situation [e.g. Phadke et al., 1987]. The

information needed for this adaptive protection will be obtained through the

local protection control and the system center computer.

After a fault in one of the zones a certain verification time starts.

This verificaton time is of a much longer duration than the verification

times introduced before (tens of milliseconds in stead of hundreds of

microseconds). The verification time can be set in two ways:

1. constant verification time, each zone has a fixed verification time,

increasing for more distant zones;

2. adaptive verification time: the duration of the verification time is

controlled by the LPC' s.

~~tant ~e~tttcatton ttae

For zone 1 (0-80%) no verification time will be needed. The relay will act

as an additional local backup. For zone 2 (SD-160%) the verification time

must be equal to the sum of the following contributions:

maximum clearing time of the circuit breakers;

maximum time needed for breaker-failure detection;

maximum clearing time of the backup breakers;

safety margin.

For zone 3 ( 160-240%) the verification time must be equal to the zone 2

verification time plus the last two contributions. Especially for zone 3 the

verification time may become very long. For complicated network configura­

tions it will be difficult to define the borders of the different zones.

Both problems can be solved by using an adaptive verification time.

Page 119: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-111-

ddapti~e ~e~itication time

In the normal state the remote backups have no verification time in their

zones one and two. The verification time in zone 3 is equal to the maximum

clearing time for a fault on the adjacent line. If a fault occurs somewhere

in the network this will be detected by the travelling-wave-based relays

long before the remote backup reacts. Upon detecting a fault the local

protection control sends a signal to the remote backups to increase the

verification time of zone 2 and 3. The verification time will depend on the

location of the relay. An example will be discussed from Figure 8.8.

)(

A

Ftgure 8.8. Position of remote backup reLays.

Circuit breaker "A" should open in case of a f au 1 t at the posit ton

shown. When the tripping signal is generated by one of the relays. the local

protection control will inform this to the relays through 4. The

verification time of zone 2 and 3 of relay 2 will be increased with the

maximum clearing time of breaker "A". It will generate a tripping signal in

case breaker "A" should fail to open. The verification time of zone 2 and 3

of relay 1 and 3 will be increased with the maximum clearing time of breaker

"A" plus that of breaker "C". They will generate tripping signals in case

breakers "A" and "C" both fail to open (or breaker "A" and the

breaker-failure-detection both fail). The verification time of zone 3 of

relay 4 will be set equal to the sum of the maximum clearing times of the

breakers "A", "C" and "D". Zone 1 of all relays as well as zone 2 of relay 4

are not affected. As soon as the fault is cleared all remote backup relays

reset themselves to the normal state.

The main advantage of the adaptive verification time shows up in case

none of the local relays generates a tripping signal. The local protection

control will not send a message to the remote backups and relays 1,2 and 3

will generate a tripping signal without a long verification time.

Page 120: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-112-

8.7. The local protection control

The local protection control serves as a link between the protective relays

among themselves and between the relays and the system center computer. It

is part of the hierarchical system as described by Phadke [1988] (his

"substation host computer" corresponds to our "local protection control").

The structure of the hierarchical system is shown in Figure 8.9.

system center computer

---------------.

Figure 8.9. Hternrchicnl structure for protection and control (R=protectiue

relay)

Most of the communication is between different levels but some is on the

same level. Communication between LPC' s in neighbouring substations is e.g.

needed for adaptive verification time setting of remote backups (cf. Section

5.6). between relays in different substations for differential protection.

The local protection control will perform the following functions:

adaptive blocking and unblocking;

adaptive setting of the remote backup relays;

breaker-failure detection;

generation of sequence of events records:

monitoring and checking of the relays.

As an example Figure 8.10 sUI'IUIIarizes some of the LPC' s actions during a

reclosure session. In the double-circuit state all four sets of circuit

breakers are closed. In the double-circuit state the IXXCP relay is in

operation and the SOTF detector is blocked.

If one of the local relays generates a tripping signal the IXXCP relay

will be blocked and the breaker-failure detection starts. The LPC will also

generate messages for the neighbouring LPC' s and the system center. Also in

case of a manual trip the IXXCP relay will be blocked.

Page 121: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-113-

If the local breakers have opened within the available time and the

circuit breakers at the remote line-terminal are also open the SOTF-relay

will be declocked. After a certain time (needed for the fault to

extinghuish) the local breakers will be closed again. If no tripping signal

is generated the SOTF-detector will be blocked, the circuit breakers at the

remote line-terminal will be closed and the DOOCP-relay will be deblocked.

N

Figure 8.10. Actions of tocat protection control during a reclosure session.

Page 122: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-114-

9. Summary and conclusions

This thesis consists of three parts:

i) the development of network models for the study of travelling-wave­

based protection;

ii) the testing of the proposed algorithms for travelling-wave-based

protection;

iii) a few proposals for the design and use of future relays.

This work tries to answer the question: "Is fast protection based on

travelling-wave principles possible?".

Travel! ing-wave-based protection detects a fault on a high-voltage 1 ine

through measuring incoming and outgoing waves at one or more line terminals.

Therefore the modelling effort is focussed on travelling waves along

high-voltage lines.

The high-voltage line is viewed as a number of parallel conductors

above a lossy ground. Up to a few hundreds of kHz such a system can be

mathematically described through a set of coupled differential equations

which the voltages and currents have to satisfy. Their solutions are weakly

damped travelling waves. A system of n metallic conductors plus ground can

support n different modal waves. For existing high-voltage lines the

expressions for the L and R-parameters found by Carson in 1926 can be used

to calculate the pertinent wave constants.

The line model is used in two computer programs for network

calculations: an existing one, called EMTP and a newly developed one, called

TWONFIL. Within EMTP the frequency dependence of the wave parameters is

reckoned with for each mode. Although the frequency dependence of the modal

transformation matrix is neglected, EMTP is considered to be very closes to

reality.

The detailed modelling as used in EMTP makes it very suitable for an

accurate simulation of voltages and currents. On the other hand the

associated complexity prevents its use for the study of a large number of

situations. To overcome this, TWONFIL has been developed. Within TWONFIL the

wave parameters are considered frequency independent. TWONFIL has been used

to calculate voltages and currents in thousands of fault and non-fault

situations. A limited number of typical situations and worst cases has been

studied in more detail by using EMTP.

Page 123: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-115-

9.2. The testing of algorithms

An algorithm for travelling-wave-based protection uses filtered values of

voltage and current to determine a set of detection functions and detect a

fault from them. A low pass filter with a cut-off frequency equal to one

divided by the travelling time of the line, showed to give good results. The

algorithms are based on expressions for the aerial waves on a balanced

three-phase line. The nonbalance of the line is not incorporated in the

protection algorithm (i) because the exact transformation matrices are not

known. (ii) to prevent problems when transposition points are used and (iii)

to keep the algorithm as simple as possible. Homopolar quanti ties are not

used (i) because of their strong frequency dependence, (ii) to prevent

problems on double-circuit lines and during lightning and (iii) because they

are not really needed.

The algorithms use the difference between voltages and currents at

different points of time (one power frequency cycle apart or one travelling

time apart) or at different positions in the network. General expressions

for the detection functions used are:

(vt-vs) + R, (it-is)

(vr-Vt) + R1 (ir-it)

(9.1)

(9.2)

where R1 is a wave-impedance setting, Vr,Vs,Vt and ir,is,it are voltage

{differences) and current (differences), respectively. General detection

criteria used are:

ID, I< 6 and ID2I < o: no fault

ID, I > o or ID2I > o : fault ,

where o is a threshold needed to prevent incorrect tripping.

(9.3)

(9.4)

After one or two detection functions exceed the threshold, a

verification time is started.

Methods have been developed to find the optimum settings for wave impedance

and travelling time, i.e. those leading to the lowest threshold value. The

threshold value must be higher than the highest value of the detection

functions during a non-fault situation. Therefore special emphasis is laid

on the study of these non-fault situations. The length of the verification

time is evaluated by considering the worst case, i.e. a lightning stroke to

a phase conductor not leading to a fault.

After the study of those non-fault situations needed for setting of

cut-off frequency, threshold, travelling time, wave impedance and

verification time, the speed of the algorithm can be evaluated from the

study of fault situations.

Page 124: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-116-

This way about a dozen algorithms have been considered, four of them

have been investigated in detai 1. From this vast study no other algorithm

has been found that can compete with the reliability of ditte~entiai

p~otection. This algorithm is able to detect any internal fault within one

or two milliseconds without the risk of an incorrect trip due to external

disturbances. The majority of internal faults can even be detected within

half a millisecond. A disadvantage of differential protection is the need

for a long high-speed communication link.

Many investigators have searched for a travelling-wave-based algorithm

for di~tance P~otectLon (i.e. one not needing a communication link). But

none of the existing algorithms is able to determine the distance to the

fault without complicated (time consuming) calculations.

Two new algorithms that do not need a communication link have been

developed in this study. The first one, DCCCP,

double-circuit lines. The second one (SOTF)

is especially sui ted for

is especially suited for

switch-on-to-fault detection. DCCCP is a very simple algorithm not needing a

long communication link, neither any precise setting of wave impedance or

travelling time. It gives a considerable reduction of tripping time as

compared to differential protection. It does, however, show a few

nondetectable situations.

Concluding: differential protection is the most reliable algorithm and DCCCP

is the fastest and most simple one.

9.3. A future relay

Three of the algorithms are used in a proposal for a protective scheme:

DCCCP, differential protection and SOTF. The blocking and unblocking of

DCCCP and SOTF is governed by a "local protection control". The

travelling-wave-based algorithms provide primary protection and local

backup. The remote backup is formed by (conventional) distance relays with

an adaptive verification-time setting. This setting is again governed by the

local protection control.

Suggestions for implementation in a relay are given for the three

travelling-wave-based algorithms used in the protective scheme. No great

technical problems are to be expected. But the communication link needed for

differential protection may become an economical problem.

Page 125: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-117-

9.4. Suggestions for future work

From the study presented in this thesis an answer in the affirmative is

concluded for the question whether fast protection. based on travelling-wave

principles is possible. Therefore future work can concentrate on building

travelling-wave relays. As very short tripping times are not yet wanted,

such a relay can be made extremely reliable by introducing a verification

time of one or two milliseconds.

In case very fast fault-clearing times are really needed much emphasis

must be laid on the setting of verification time, wave impedance, travelling

time and threshold. As the length of the verification time is determined by

the shape of lightning-caused waves, more research must be performed after

this shape.

The introduction of these very fast relays is only meaningful in

combination with fast circuit breakers. The use of active current-limiting

devices will justify the introduction of fast relays even more.

On the field of network modelling work must be performed to get a

better justification of the model. Nowadays ever more complicated structures

can be simulated by using numerical techniques like EMTP. But the foundation

of this must be provided from measurements.

Page 126: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-118-

lO.References.

Product guide. LINE PROTECfiON RELAYS: FAULT LOCATION. Modern Power Systems, Vol.8, no.l. (Jan. 1988), p.57-61.

Ametani, A USAGE OF EMPT IN JAPAN. 15th European EMTP Meeting, Leuven, Belgium, Oct. 17, 1988

Anders, G.J. and P.L. Dandeno, E.E. Neudorf COMPUTATION OF FREQUENCY OF SEVERE POWER SYSTEM FAULTS. IEEE Transactions on Power Apparatus and Systems,Vol.103(1984),p.2369-2374.

Anderson, R.B. LIGIITNING PERFORMANCE CRITERIA FOR ELECrRIC POWER SYSTEMS. lEE Proceedings. Vol.132 (1985), Pt.C, p.298-306.

Bergeron. L. WATER HAMMER IN HYDRAULICS AND WAVE SURGES IN ELECTRICITY New York: Wiley, 1961. French original published by Dunod in 1950.

Bewley, L. V. TRAVELING WAVES ON TRANSMISSION SYSTEMS. 2nd ed. New York: Wiley/ London: Chapman and Hall, 1951, General Electric series.

Blackburn, J. L. PROTECTIVE RELAYING, principles and applications. New York: Marcel Dekker, 1987. Electrical Engineering and Electronics, Vol.37.

Bollen. M.H.J. EXTENSIVE TESTING OF ALGORITHMS FOR TRAVELLING-WAVE-BASED PROTECTION. In: Proc. 4th Int. Conf. on Developments in Power System Protection, Edinburgh, U.K .• April 11-13, 1989. London: Institution of Electrical Engineers. 1989. lEE Conference Publication No. 302. P.l35-139.

Bollen, M.H.J. and G.A.P . .lacobs EXTENSIVE TESTING OF AN ALGORITHM FOR TRAVELLING-WAVE-BASED DIRECfiONAL DETECTION AND PHASE SELECTION BY USING TWONFIL AND EMTP. Eindhoven, The Netherlands: Eindhoven University of Technology, Faculty of Electrical Engineering, October 1988. EUT Report SS-E-206.

Bollen. M.H.J. and G.A.P . .Iacobs IMPLEMENTATION OF AN ALGORITHM FOR TRAVELLING-WAVE-BASED DIRECfiONAL DETECTION. Eindhoven, The Netherlands: Eindhoven University of Technology, Faculty of Electrical Engineering, January 1989. EUT Report 89-E-214.

Bollen. M.H.J. and P.T.M. Vaessen FREQUENCY SPECTRA FOR ADMITTANCES AND VOLTAGE TRANSFERS MEASURED ON A THREE-PHASE POWER TRANSFORMER. Eindhoven, The Netherlands: Eindhoven University of Technology. Faculty of Electrical Engineering, October 1987. EUT Report 87-E-181.

Barnard, P. and J.M. Tesseron, J.C. Bastide, M. Nourris FIELD EXPERIENCE OF DIGITAL FAULT RECORDERS AND DISTANCE RELAY IN EHV SUBSTATIONS. IEEE Transactions on Power Apparatus and Systems, Vol.PAS-103 (1984), p.133-139.

Page 127: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-119-

Brandao Faria, J.A. OVERHEAD THREE-PHASE TRANSMISSION LINES - NON-DIAGONALIZABLE SOLliTIONS. IEEE Transactions on Power Delivery, Vol. PWRD-3 (1988), p.134S-1355.

Brandao Faria, J.A. and J.F. Borges da Silva WAVE PROPAGATION IN POLYPHASE TRANSMISSION LINES, A general solution to include cases where ordinary modal theory fails. IEEE Transactions on Power Delivery, Vol. PWRD-1 (1986), No. 2, p.lS2-189.

Carson, J.R. WAVE PROPAGATION IN OVERHEAD WIRES Willi GROUND RETURN. Bell System Technical Journal, Vol. 5 (1926}, p. 539-554.

CCIR WORLD ATLAS OF GROUND roNDUCTIVITIES. Geneva: International Telecommunication Union, 1988. CCIR Report 717-2.

Chamia, M. EDITORIAL. Electra (CIGRE), no.116 (Jan.1988), p.3-5.

Chamia, M. and S. Liberman ULTRA HIGH SPEED RELAY FOR EHV/UHV TRANSMISSION LINES - development, design and application. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-97 (1978), p.2104-2116.

Olang D.C. and R.G. Olsen EXCITATION OF AN INFINITE ANTENNA ABOVE A DISSIPATIVE EARTII. Radio Science, Vol. 10 (1975), p.S23-831.

CIGRE Protective relaying in Japan. CIGRE SC 34 Colloquim, Nov. 7, 1983, Tokyo, Japan.

Clemens, H. and K. Rothe Relaisschutztechnik in Elektroenergiesystemen. Berlin, German Democratic Republic: VEB Verlag Technik, 1980.

Cornick, K.J. and Y.M. Ko, B. Pek POWER SYSTEM TRANSIENTS CAUSED BY ARCING FAULTS. lEE Proceedings, Vol. 128 (1981), Pt. C., p. 18-27.

Christopoulos, C. and D.W.P. Thomas, A. Wright SCHEME, BASED 00 TRAVELLING-WAVES, FOR THE PROTECTION OF MAJOR TRANSMISSION LINES. lEE Proceedings, Vol. 135 (1988), Pt.C., p. 63-73.

Christopoulos, C. and D.W.P. Thomas, A. Wright THE PERFORMANCE OF A PROTECTIVE SCHEME BASED ON TRAVELLING WAVES. In: Proc. 4th Int. Conf. on Developments in Power System Protection, Edinburgh, U.K., April 11-13, 1989. London: Institution of Electrical Engineers. 1989. lEE Conference Publication No. 302. P.146-150.

Cooray, V. and F. de la Rosa SHAPES AND AMPLITUDES OF THE INITIAL PEAKS OF LIGHTNING-INDUCED VOLTAGE IN POWER LINES OVER FINITELY CONDUCTING EARTII: theory and comparison with experiment. IEEE Transactions on Antennas and Propagation. Vol. AP-34 (1986). p.SS-92.

Page 128: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-120-

Cornfield, G. and M.F. Stringfellow CALaJLATION AND MEASUREMENT OF LIGliTNING-INDUCED VOLTAGES ON OVERHEAD DISTRIBUTION LINES. In: Proc. Conf. on Lightning and the Distribution System, Jan. 17-18, 1974, London. London: Institution of Electrical Engineers, 1974. lEE Conference Publication No. 108. P.41-50.

Crossley, P.A. and P.G. McLaren DISTANCE PROTECfiON BASED ON TRAVElLING WAVES. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-102 (1983), p.2971-2983.

De la Rosa, F. and R. Valdivia, M. Perez, J. Loza DISCUSSION ABOUT TIIE INDOCING EFFECTS OF LIGHTNING IN AN EXPERIMENTAL POWER DISTRUBITION LINE IN MEXICO. IEEE Transactions on Power Delivery, Vo1.PWRD-3 (1988}. p.lOS0-1089.

Diordievic, A.R., T.K. Sarkar, R.F. Harrington TIME-DOMAIN RESPONSE OF MULTICONDUCfOR TRANSMISSION LINES. Proceedings of the IEEE, Vol. 75 {1987}, p.743-764.

Dommel, H. W. ELECTROMAGNETIC TRANSIENTS PROGRAM REFERENCE MANUAL (EMPT theory book}. Portland, Oregon 97208 (P.O.Box 3621): Bonneville Power Administration. August 1986.

Dommel, H.W. and J.M. Michels HIGH SPEED RELAYING USING TRAVELING WAVE TRANSIENT ANALYSIS. In: Proc. IEEEIPES Winter Meeting, New York, Jan. 29 - Feb. 3, 1978. New York: IEEE. 1978. Paper A 78 214-9.

Efthymiadis, A.E. and L.M. Wedepohl PROPAGATION CHARACfERISTICS OF INFINITELY-LONG SINGLE-ODNDUcrOR LINES BY TIIE COMPLETE FIELD SOLUTION METHOD. Proceedings lEE, Vol. 125 (1978), p.511-517.

Empereur, G. and K. D. Soma t ilake MODAL ANALYSIS IN POWER SYSTEMS. EMTP Newsletter, Vol. 6., No. 4 (December 1986}, p.15-24. Available at LEC, Kard. Mercierlaan 94, B-3030 Heverlee, Belgium.

~. F. and O.E. Lanz, M. lllinggli, G. Bacchini TRANSIENT SIGNALS AND TIIEIR PROCESSING IN AN ULTRA HIGH-SPEED DIRECfiONAL RELAY FOR EIN/UHV TRANSMISSION LINE PRarECI'ION. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-104 (1985), p.1463-1473.

EPRI TRANSIENTS ON TRANSMISSION SYSTEMS. DATA PRESENTATION AND ANALYSIS. Palo Alto, California (P.O. box 10412) : Eletric Power Research Institute, 1986. Report EPRI-EL-4403.

Eriksson, A.J. LIGHTNING OVERVOLTAGES ON HIGH VOLTAGE TRANSMISSION LINES INVESTIGATION OF WAVE-SHAPE CHARACfERISTICS. Electra {CIGRE), No. 47 (July 1976), p.87-110.

Ermolenko, V.M. and V.F. Lachugin, D.R. Lyubarsky. I.N. Popov, G.V. Sokolova HIGH SPEED WAVE DIREcriONAL RELAY PROTECfiON OF UHV LINES. In: Proc. of the 32th Int. Conf. on Large High Voltage Electric Systems, Paris, Aug. 28 Sept. 3. 1988. Paris: CIGRE, 1988. Paper 34-11.

Page 129: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-121-

Esztergalyos, J. and M.T. Yee, M. Charnia, S. Liberman TilE DEVELOPMENT AND OPERATION OF AN ULTRA HIGH SPEED RELAYING SYSTEM FOR EHV TRANSMISSION LINES. In: Proc. of the 27th Int. Conf. on Large High Voltage Electric Systems, Paris, France, Aug. 30 - Sept. 7, 1978. Paris: CIGRE, 1978. Paper 34-04.

Giuliante, A.T. and G. Stranne, R.R. Slatem, C. Ohlen A DIRECTIONAL WAVE DETECTOR RELAY WITH ENHANCED APPLICATION CAPABILITIES FOR EHV AND UHV LINES. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-102 (1983), p 2881-2892.

Glavitsch, H. and A. Btirki, H. Ungrad DISTANCE RELAY TECHNOLOGY; NEEDS AND EXPECTATIONS. In: Proc~ Blacksburg Conf. on Computer Relaying, Oct. 6-7, 1987, Blacksburg, Virginia. Blacksburg: Virginia Polytechnical Institute, 1987. Paper I-4.

Harman, T. L. and B. Lawson TilE MOTOROLA MC68000 MICROPROCESSOR FAMILY: ASSEMBLY LANGUAGE, INTERFACE DESIGN AND SYSTEM DESIGN. Englewood Cliffs, New Jersey: Prentice-Hall, 1985.

Heaviside, 0. ELECTROMAGNETIC THEORY VOL. 1 . New York: Chelsea, 1971. Original publication: London, 1893.

Hedmann, D.E. PROPAGATION ON OVERHEAD TRANSMISSION LINES II: Earth-conduction effects and practical results. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-84 (1965), p.205-211.

Heising, C.R. and R.C. Patterson RELIABILITY EXPECTATIONS FOR PROTECTIVE RELAYS. In: Proc. 4th Int. Conf. on Developments in Power System Protection, Edinburgh, U.K., April 11-13, 1989. London: Institution of Electrical Engineers, 1989. lEE Conference Publication No. 302. P.23-36.

Hicks, K.L. and W.H. Butt FEASABILITY AND ECONOMICS OF ULTRA-HIGH-SPEED FAULT CLEARING. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-99 (1980), p.213S-2145.

Ibe, A.O. and B.j. Cory A TRAVELLING WAVE-BASED FAULT LOCATOR FOR TWQ- AND THREE-TERMINAL NETWORKS. IEEE Transactions on Power Delivery, Vol. PWRD-1. no. 2 (April 1986), p.283-2S8.

Ibe, A.O. and B.J. Cory FAULT-LOCATION ALGORITHM FOR MULTIPHASE POWER LINES. lEE Proceedings, Vol. 134 (1987), Pt.C., p.43-50 .

.Johns, A. T. NEW ULTRA-HIGH-SPEED DIRECTIONAL OOMPARISON TECHNIQUE FOR TilE PROTECTION OF E.H.V. TRANSMISSION LINES. lEE Proceedings, Vol. 127 (1980), Pt. C. p.228-239 .

.Johns, A.T. and M.M. El-din Mahmoud NEW APPROACH TO ULTRA-HIGH-SPEED PHASE SELECTION IN SINGLE-POLE AtrrOREa..oouRE SCHEMES. lEE Proceedings, Vol. 133 (1986). Pt. C .• p.1SS-200.

Page 130: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-122-

Johns, A.T. and M.A. Martin, A. Barker, E.P. Walker. P.A. Crossley A NEW APPROACH TO E.H. V. DIRECTIONAL a>MPARISON PROTECTION USING DIGITAL SIGNAL PROCESSING TECHNIQUES. IEEE Transactions on Power Delivery, Vol. PWRD-1, no. 2 (April 1986). p.24-34.

Johns, A.T. and E.P. Walker co-oPERATIVE RESEARCH INTO THE ENGINEERING AND DESIGN OF A NEW DIGITAL DIRECTIONAL a>MPARISON SCHEME. lEE Proceedings, Vol. 135 (1988), Pt. C., p.334-368.

Kersten, W.F.J. and G.A.P . .Jacobs ANALOG AND DIGITAL SIMULTATION OF LINE-ENERGIZING OVERVOLTAGES AND <X>MPARISON WITH MEASUREMENTS IN A 400 kV NETWORK. Eindhoven, The Netherlands: Eindhoven University of Technology, Faculty of Electrical Engineering, 1988. EUT Report 88-E-193.

Kersten, W.F.J. and M.A.M.M. van der Meiiden LINE PARAMETERS SENSITIVITY OF BACKFLASHOVER RATES OF H. V. LINES. In: Proc. Int. Conf. on Lightning and Power Systems, London, UK, June 5-7, 1984. London: Institution of Electrical Engineers, 1984. lEE Conference Publication no. 236. p.&-10.

!ili!g, R.W.P. TRANSMISSION-LINE THEORY, 2nd ed. New York: Dover, 1965. Originally Published by McGraw-Hill in 1955.

Kinoshita, H. and T. Higuchi, K. Yamamoto, I. Arima SIMULTANEOUS AND DIFFERENT POLARITY VOLTAGES DUE TO LIGHTNING APPEARING ON TRANSMISSION LINES. In: Proc. 5th Int. Symp. on High Voltage Engineering, Braunschweig, Federal Republic of Germany, Aug. 24-28, 1987. Paper 81.3.

Koglin. H.J. and Biao Zhang A NEW AL<X>RITHM FOR DIGITAL DISfANCE PRarECfiON BASED ON THE TRAVELLING WAVE PRINCIPLE. In: Proc. of the 9th Power Systems Computation Conf., Cascais, Portugal, Aug. 30- Sept. 4, 1987. London: Butterworth, 1987. P.746-750.

Kohlas, J. ESfiMATION OF FAULT LOCATIONS ON POWER LINES. In: Identification and System Parameter Estimation, Proc. 3rd IFAC Symposium, The Hague/Delft, the Netherlands, June 12-15, 1973. (Ed. by P. Eykhoff) Amsterdam: North-Holland, 1973. P.393-402.

Koreman, C.G.A. RESULTATEN VAN DE METING VAN DE BLIKSEMOVERSPANNINGEN IN HET 220 kV SfATION IN HOOGEVEEN. Arnhem, The Netherlands: KEMA, 1988. Report 31751-EO 87-3072.

Landoll, L.E. et al. REVIEW OF RECENT PRACTICES AND TRENDS IN PROTECTIVE RELAYING, IEEE <X>MMITTEE REPORT. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100 (1981), p.4054-4064.

Leppers. P.H. ANALYSE ENQUETE VAN LIJNUITSCHAKELINGEN OCOR GALOPPEREN Elektrotechniek. Vol.63 (1985), p.1123-1127.

Page 131: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-123-

Liew, A.C. and M. Darveniza CALaJLATION OF THE LIGHrNING PERFORMANCE OF UNSHIELDED TRANSMISSION LINES. IEEE Transactions on Power Apparatus and Systems, Vol.PAS-101 (1982), p.1471-1477.

Light, B.R. TRANSIENT STABILI1Y ASPECTS OF POWER SYSTEM RELIABILI1Y (CEGB SYSTEM). In: Proc. Int. Conf. on Reliability of Power Supply Systems, London, Feb 21 - 23, 1977. London: Institution of Electrical Engineers, 1977. lEE Conference Publication, No. 148. P.101-104.

Lima, J.A. EMTP LINE MODELLING ACUJRACY. In: Proc. of the 9th Power System Computation Con£., Oascais, Portugal, Aug. 30- Sept. 4. 1987. London: Butterworth, 1987. P.391-395.

~. L. and j. Ferre, H. Hupfauer, C. ~. V. Narayan, C. Starace. PROTECTION SYSTEMS USING TELECOMMUNICATIONS. Paris: CIGRE. October 1987.

~.R.W. UBER I..ErnER-WELLEN, LEITUNGS-WELLEN UND TEM-WELLEN AUF VERLUSTBEHAFTETEN MEHRLEITERSYSTEMEN UND DIE BEDEUTUNG DER DIFFUSIONSGLEIOIDNG ZUR ERMITTLUNG DER LEITUNGSBELAGE. Frequenz. Vol. 25 (1971}. p.208-214.

Luis Naredo, j. DISCUSSION. IEEE Transaction on Power Delivery. Vol. PWRD-1 (April 1986). no.2. p.188.

Maas. J.H. RIPES - VINGER AAN DE POLS BIJ DE DIAGNOSE VAN DE GEZONDHEIIBTOESTAND VAN HET KOPPELNET. Elektrotechniek, Vol. 65 (1987), p.699-704.

Mackay, K.M.E. and A.R. Barber, M.D. Rowbottom OPERATIONAL PERFORMANCE OF THE CEGB TRANSMISSION LINE NETWORK. In: Proc. 26th Int. Conf on Large High-Voltage Electric Systems (CIGRE), Paris, Aug. 25 Sept. 2. 1976. Paris: CIGRE, 1976. Paper 22-9.

Malewski, R. and J. Douville, L. Lavallee MEASUREMENT OF SWITQUNG TRANSIENTS IN 735-kV SUBSTATIONS AND ASSESSMENT OF THEIR SEVERI1Y FOR TRANSFORMER INSULATION. IEEE Transactions on Power Delivery, Vol. PWRD-3 (1988). p.1380-1390.

Mansour, M.M. and G.W. Swift A MULTI-MICROPROCESSOR BASED TRAVELLING WAVE RELAY: theory and realization. IEEE Transactions on Power Delivery, Vol. PWRD-1, no. 1 (Jan. 1986}, p.272-279.

Marti, j.R. ACUJRATE MODELLING OF FREQUENCY-DEPENDENT TRANSMISSION LINES IN El.ECfROMAGNETIC TRANSIENT SIMULATIONS. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-101 (1982}. p.l47-157.

Marti, j.R. and H.W. Dommel, L. Marti, V. Brandwajn APPROXIMATE TRANSFORMATION MATRICES FOR UNBALANCED TRANSMISSION LINES. In: Proc. 9th Power System Computation con£., Oascais, Portugal, Aug. 30-Sept. 4, 1987. London: Butterworth, 1987. P.416-422.

Page 132: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-124-

Man, 0. DIE ERDE AlS WEa:ISELSTROMLEITER. Elektrotechnische Zeitschrift, Jg 36 (1925), S.1352-1355, 1436-1440.

McLaren, P.J. and S. Raiendra. E. Shehab-Eldin, P.A. Crossley ULTRA HIGH SPEED DISI'ANCE PRUI'ECTON BASED ON TRAVELLING WAVES. In: Proc. 3rd Int. Con£. on Developments in Power System protection, April 17-19. 1985. London: Institute of Electrical Engineers, 1985. lEE Conference Publication No.249. P.106-110.

Menemenlis, C. and Zhu Tong Chun WAVE PROPAGATION IN NONUNIFORM LINES. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-101 (1982), p.833-839.

Meyer, W .S. and H. W. Dommel NUMERICAL MODELLING OF FREQUENCY-DEPENDENT TRANSMISSION-LINE PARAMETERS IN AN ELECTROMAGNETIC TRANSIENTS PROGRAM. IEEE Transaction on Power Apparatus and Systems, Vol. PAS-93 (1974}. p.1401-1409

Nakagawa, M. and A. Ametani, K. Iwamato FURTHER srtJDIES ON WAVE PROPAGATION IN OVERHEAD LINES WITH EARTH RETURN: impedance of stratified earth. Proceedings lEE, Vol. 120 (1973), p.1521-1528.

Nakanishi, H. and A. Ametami TRANSIENT CALCULATION OF A TRANSMISSION LINE USING SUPERPOSITION LAW. lEE Proceedings, Vol.133 (1986), Pt. C, p.263-269. .

Nimmersio. G. and M.M. Saha A NEW APPROACH TO HIGH SPEED RELAYING BASED ON TRANSIENT PHENOMENA. In: Proc 4th Int. Con£. on Developments in Power System Protection, Edinburgh, U.K., April 11-13, 1989. London: Institution of Electrical Engineers, 1989. lEE Conference Publication No. 302. P.140-145.

Okumura, K. and A. Kiiima A METHOD FOR OJMPUTING THE SURGE IMPEDANCE OF TRANSMISSION LINE TOWER BY ELECTROMAGNETIC FIELD THEORY. Electrical Engineering in japan, Vol. 105, no. 6 (1985), p.56-64. Transl. from: Denki Gakkai Ronbonski, Vol.105-B, no.9 (sept. 1985}. p.733-740.

Olsen, R.G. ELECTROMAGNETIC CHARACTERISI'ICS OF HORIZONTAL AND VERTICAL WIRES OVER A DISSIPATIVE EARTH. Ph.D. Thesis, University of Colorado, Boulder, Colorado, 1974. Ann Arbor, Michigan: University Microfilms. Order No. 74-22,379.

Olsen, R.G. DISCUSSION IEEE Transactions on Power Delivery, Vol. PWRD-2 (April 1986), no. 2. p.188.

Olsen, R.G. and D.C. ~ NEW MODAL REPRESENTATION OF ELECTROMAGNETIC WAVES SUPPORTED BY HORIZONTAL WIRE ABOVE DISSIPATIVE EARTH. Electronics Letters, Vol. 10, (1974), p.92-94.

Olsen, R.G. and T .A. Pankaskie ON THE EXACT. CARSON AND IMAGE THEORIES FOR WIRES AT OR ABOVE THE EARTH' S INTERFACE. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-102 (1983), p.769-77S.

Page 133: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-125-

Phadke, A.G. OOMPliTER RELAYING IN AN IN1EGRATED HIERARCHICAL STRUCIURE. In: Microprocessor Relays and Protection Systems, IEEE tutorial course. New York: IEEE, 1988. P.48-55.

Phadke, A.G. and J.S. Thorp, S.H. Horowitz IMPACf OF ADAPTIVE PROTECfiON ON POWER SYSTEM roNTROL. In: Proc. 9th Power Systems Computation Con£., Cascais, Portugal, Aug. 30 Sept. 4. 1987. London: Butterworth, 1987. P.283-290.

Pirjola, R. and A. Vilianen ON GEOMAGNETICALLY-INDUCED aJRRENTS IN TilE FINNISH 400 kV POWER SYSTEM BY AN AURORAL Fl..EcrROJET aJRRENT. IEEE Transactions on Power Delivery, Vol. PWRD-4 (1989), p.1239-1245.

Po llaczek. F. tlBER DAS FELD EINER UNENDLIOI LANGEN WEXllSEl.SfROMDUROIFLOSSENEN EINFAOILEITIJNG. Elektrische Nachrichten-Technik, Jg. 3 (1926), S.339-359.

Recker, M. and H. Reisner, W. Waste DAS STORUNGS- UND SOIADENGESCHEHEN IN DEN HOCHSPANNUNGSNETZEN IN DER BUNDESREPUBLIK DEUTSCHLAND IN DEN JAHREN 1963 BIS 1983: Jahreswerte, Mittelwerte, Trends (Eine Auswertung der VDEW-Storungs und Schadenstatistik). Essen: RWE, 1996.

Rtidenberg, R. . • DIE AUSBREITIJNG DER ERmTROME IN DER UMGEBUNG VON WECHSELSTROMLEITIJNGEN. Zeitschrift flir angewandte Mathematik und Mechanik, Jg. 5 (1925), S.361-389.

Sargent, M.A. and M. Darveniza LIGHfNING PERFORMANCE OF OOUBlE-ciRCUIT TRANSMISSION LINFS. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-89 (1970), p.913-925.

Semlyen, A. and A. Dabuleanu FAST AND Aa:'URATE SWITOIING TRANSIENT CALCULATIONS ON TRANSMISSION LINFS WITH GROUND RETURN USING RECURSIVE roNVOLUTIONS. IEEE Transactions on Power apparatus and Systems. Vol. PAS-94 (1975). p.561-571.

Shehab-Eldin, E.H. and P.G. McLaren TRAVELLING WAVE DISTANCE PROTEcriON - PROBlEM AREAS AND SOLUTIONS. IEEE Transactions on Power Delivery, Vol. PWRD-3 (1988), p.S94-902.

~. T. and J. Baba, K. Uemura, T. Sakaguchi FAULT PROTEcriON BASED ON TRAVELLING WAVE THEORY. Part I: Theory. In: Proc. IEEE/PES Summer Meeting, Mexico City, July 17-22, 1977. New York: IEEE, 1977. Paper 750-3.

~. T. and J. Baba. K. Uemuro, T. Sakaguchi FAULT PROTEcriON BASED ON TRAVELLING WAVE THEORY. Part II: Sensitivity analysis and laboratory test. In: Proc. IEEE/PES Winter Meeting, New York, Jan. 29 - Feb. 3, 1978. New York: IEEE, 1978. Paper 220-6.

~. T. andY. Miki, J. Makino. I. Matori FEASIBILITY STUDY FOR A aJRRENT DIFFERENTIAL CARRIER RELAY SYSTEM BASED ON TRAVELLING WAVE THEORY. In: Proc. IEEEIPES Winter meeting, New York, Jan. 29 - Feb. 3, 1978. New York: IEEE, 1978. paper 132-3.

Page 134: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-126-

Thuries, E. and Phrun Van Doan INlERRELATION BETWEEN THE 1-CYa..E BREAKER AND THE a.JRRENT-LIMITING DEVICE. In: Proc. Joint Power Generation Conf., Charlotte, North Carolina,Oct. 7-11, 1979. New York: IEEE. 1979. Paper 827-7.

Van Dongen, A.W.A. EEN DISTANTIEBEVEILIGINGSALGORITHME VOOR HOCX;SPANNINGSLIJNEN. Group of Electrical Energy Systems. Faculty of Electrical Engineering. Eindhoven University of Technology. 1988. Master Thesis, EO.SS.A.49.

Van Heesch. E.J.M. and A.P.J. van Deursen, M.A. van Houten. G.A.P . .Jacobs, W.F.J. Kersten. P.C.T. van der Laan. FIELD TF.STS AND RESPONSE OF THE D/1 H. V. MEASURING SYSTEM. Sixth Int. Symp. on High Voltage Engineering, New Orleans, USA, Aug. 28-Sep. 1' 1989.

Vi tins, M. A CURRELATION METilOD FOR TRANSMISSION LINE PROTECI'ION. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-97 (1978), p. 1607-1617.

Vitins, M. A FUNDAMENTAL CUNCEPT FOR HIGH SPEED RELAYING. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100 (1981}, p. 163-173.

Wait, J.R. THEORY OF WAVE PROPAGATION ALONG A THIN WIRE PARALLEL TO AN INlERFACE. Radio Science, Vol. 7 (1972), p.675-679.

Walter, M. DIE ENTWICKLUNG DES SELEKTIVEN KURZSOD...UJjSCHUTZES. Elektrizitatswirtschaft, Jg.66 (1967), S.317-323.

Wedepohl, L.M. APPLICATION OF MATRIX METilODS TO THE SOLUTION OF TRAVELLING-WAVE PHENOMENA IN POLYPHASE SYSTEMS. Proceedings lEE, Vol. 110 (1963). p.2200-2212.

Wedepohl, L.M. and A.E. Efthymiadis WAVE PROPAGATION IN TRANSMISSION LINES OVER LOSSY GROUND: a new complete field solution. Proceedings lEE, Vol. 125 (1978), p.505-510

Wedepohl, L.M. and R.G. Wasley WAVE PROPAGATION IN MULTICUNDUCI'OR OVERHEAD LINES: Calculation of series impedance for multilayer earth. Proceedings lEE, Vol. 113 (1966), p.627-632

Wise, W.H. POTENTIAL CUEFFICIENTS FOR GROUND RE1lJRN CIRaJITS. Bell System Technical Journal, Vol. 27 (1948), p.365-371.

Yee, M.T. and J, Esztergalyos ULTRA HIGH SPEED RELAY FOR EHV/UHV TRANSMISSION LINES - installation, staged fault tests and operational experience. IEEE Transaction on Power Apparatus and Systems, Vol. PAS-97, (1978), p.1814-1825.

Page 135: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-127-

SAMENVATIING Het optreden van een kortsluiting in een elektriciteitsnet kan zeer grote

stromen tot gevolg hebben. Deze stromen zijn ongewenst aangezien ze de on­

derdelen van het net zwaar kunnen beschadigen en tevens de elektriciteits­

voorziening op andere wijze kunnen ontregelen. Om de gevolgen van zo'n kort­

sluiting zoveel mogelijk te beperken wordt getracht zo snel mogelijk na het

optreden ervan een aantal schakelaars te openen, waardoor de kortsluitstroom

verdwijnt zonder dat de elektriciteitsvoorziening ontregeld wordt (men

spreekt in deze context van "kortsluitbeveiliging" of kortweg

"beveiliging").

Wanneer ergens op een hoogspanningslijn een kortsluiting optreedt

veranderen daar ter plaatse ogenblikkelijk de voorheen aanwezige spanningen

en stromen. Deze veranderingen planten zich vervolgens vanaf de kortsluiting

voort met een zeer hoge snelheid (nagenoeg de lichtsnelheid). Een derge­

lijke, zich snel voortplantende spannings- en stroomverandering wordt een

lopende golf genoemd. Na een zekere, geringe, looptijd arriveren deze golven

in een hoogspanningsstation. waar ze de eerste melding vormen van een kort­

sluiting verderop. Men zou deze golven daarom, in principe. kunnen gebruiken

als detektiesignaal voor een zeer snelle beveiliging. Een moeilijkheid daar­

bij is, dat vele andere gebeurtenissen (schakelhandelingen, bliksemontla­

dingen, fouten elders) ook lopende golven veroorzaken maar niet tot een

afschakeling mogen leiden.

Het onderzoek beschreven in dit proefschrift tracht een antwoord te geven op

de vraag of het mogelijk is een betrouwbare lopende-golfbeveiliging te

ontwerpen. Het onderzoek bestaat uit drie delen:

1 het ontwikkelen van modellen geschikt voor het bestuderen van lopende

golven in elektriciteitsnetten;

2 het testen van voorgestelde methoden voor lopende-golfbeveiliging;

3 het inpassen van deze methoden in toekomstige beveiligingsrelais.

1. De modelvorming is vooral gericht op lopende golven op hoogspannings­

lijnen. De hoogspanningslijn wordt gezien als een aantal paralelle geleiders

hoven een geleidende aarde. Tot enkele honderden kHz blijkt het mogelijk bet

gedrag van een dergelijk systeem te beschrijven door middel van een stelsel

gekoppelde differentiaalvergelijkingen voor spanning en stroom. De oplos­

singen hiervan zijn zwak-gedempte lopende golven waarvan de eigenschappen

kunnen worden bepaald met behulp van in 1926 door Carson gevonden uitdruk­

kingen.

Page 136: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-128-

Het op deze manter ontstane lijnmodel is gebruikt in twee computerpro­

gr~s voor netwerkberekeningen: een bestaand, genaamd EMTP en een nieuw

ontwikkeld, genaamd TWONFIL. EMTP neemt het grootste deel van de frequentie­

afhankelijkheden van de golfeigenschappen mee. EMTP' s rijkdom aan mogelijk­

heden maakt het zeer geschikt voor het nauwkeurig berekenen van spanningen

en stromen. De hiermee samenhangende complexiteit maakt het echter minder

geschikt voor het in detail bestuderen van een groot aantal gevallen. Voor

dat laatste is TWONFIL ontwikkeld. Binnen TWONFIL worden de golfeigenschap­

pen frequentie-onafhakelijk beschouwd. TWONFIL is gebruikt voor het bereke­

nen van spanningen en stromen in duizenden gevallen. Een beperkt aantal

karakteristieke gevalen is in detail bestudeerd met behulp van EMTP.

2. Lopende-golfbeveil iging gebruikt gefil terde waarden van spanning en

stroom en berekent hieruit een aantal detectiefuncties waarmee een kort­

sluiting op het te beveiligen traject kan worden gedetecteerd. Uitgaande van

spanningen en stromen gemeten op verschillende plaatsen en/of tijdstippen.

in combinatie met golfimpedantie- en looptijdinstellingen, worden twee

detectiefuncties berekend. Wanneer een of beide detectiefuncties een zekere

drempel overschrijden start een zogenaamde verificatietijd. Blijven de

detectiefuncties boven de drempel gedurende deze tijd. dan wordt er een af­

schakelcommando naar de schakelaars gestuurd.

Er zijn technieken ontwikkeld ter bepaling van optimale golfimpedantie­

en looptijdinstelling, d.w.z. die instelwaarde welke leidt tot de laagste

drempelwaarde, en dus tot de snelste afschakeling. De drempelwaarde moet

boger zijn dan de hoogstmogelijke waarde welke optreedt tijdens si tuaties

die niet tot een afschakel tng mogen leiden. Daarom is er extra aandacht

besteed aan dit soort situaties. Na het bestuderen hiervan en het instellen

van afsnijfrequentie, drempelwaarde, loopttjd, golfimpedantie en verifica­

tietijd, is de snelheid van de beveiliging bepaald uit het bestuderen van

alle mogelijke kortsluitingen op de te beveiligen lijn._De minimale duur van

de verificatietijd is bepaald door de maximale duur van de drempelover­

schrijding als gevolg van een blikseminslag. welke niet leidt tot een kort­

sluiting.

Op deze wijze is een tiental methoden beschouwd, waarvan vier in

detail. Uit deze grondige studie blijkt dat geen van de andere bestudeerde

methoden de betrouwbaarheid van lopende-golfdifferentiaalbeveil iging kan

evenaren. Deze methode is in staat elke kortsluiting op de te beveiligen

lijn binnen een a twee milliseconden te detecteren zonder het risico van een

onterechte afschakeling als gevolg van een gebeurtenis buiten die lijn. De

meeste kortslui tingen kunnen zelfs binnen een halve milliseconde worden

Page 137: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-129-

gedetecteerd. De andere methoden zijn veelal wel in staat kortslui tingen

snel te detecteren doch niet in alle gevallen of geven in somrnige gevallen

onterechte afschakelcomrnando' s. Het nadeel van lopende-golfdi fferentiaal­

beveiliging is de vereiste aanwezigheid van lange, hoogwaardige comrnunica­

tieverbindingen. Er zijn twee nieuwe methoden ontwikkeld, welke geen gebruik

maken van dit soort verbindingen. De eerste (DOOCP} is speciaal ontwikkeld

voor dubbelcircuitlijnen, de tweede (S<YfF} voor het inschakelen van onbe­

laste lijnen. DOOCP is een eenvoudige methode die geen nauwkeurige instel­

ling van looptijd of golfimpedantie vereist. Deze methode geeft een aan­

zienlijke versnelling ten opzichte van lopende-golfdifferentiaalbeveiliging,

doch vertoont een aantal niet-detecteerbare gevallen.

Concluste: lopende-golfdifferentiaalbeveiliging is de meest betrouwbare

methode; DOOCP is daarentegen sneller en eenvoudiger.

3. Er is een volledig beveiligingsconcept voor een dubbelcircuitlijn voor­

gesteld. Hierin zijn drie van de bestudeerde methoden gebruikt, nl. DOOCP.

lopende-golfdifferentiaalbeveiliging en sarF, die tezamen de primaire

beveiliging en de reserve ter plaatse vormen. De reserve op afstand wordt

gevormd door (conventionele) distantiebeveiliging.

Er zijn voorstellen gedaan voor de technische uitvoering van de lopende

golfbeveil igingen in het voorgestelde beveil igingsconcept. Er zijn geen

grote technische problemen te verwachten. De comrnunicatieverbinding vereist

voor lopende-golfdifferentiaalbeveiliging zou echter een economisch probleem

kunnen zijn.

Uit het onderzoek, beschreven in dit proefschrift, blijkt dat de vraag

of lopende-golfbeveiliging mogelijk is, met "ja" kan worden beantwoord.

Page 138: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-130-

Aan dit proefschrift werd medewerking verleend door:

Ir. W.F.J. Kersten, Prof.dr.ir. W.M.C. van den Heuvel en Prof.Dr.-Ing. H.J.

Butterweck (technische en tactische tips);

Marijke van de Wijdeven (typewerk en ondersteuning);

Gerard jacobs (figuren en diverse metingen);

vele anderen.

Page 139: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-131-

Levens loop:

Math Bollen werd op 21 juli 1960 geboren te Stein (L). Na enkele maanden

verhuisde hij naar bet nabijgelegen Ceulle, alwaar hij zowel de kleuter­

school als de lagere school bezocht. Na bet eindexamen Atheneum B aan de

Scholengerneenschap St. Michie} te Celeen ging hij Elektrotechniek studeren

aan de Technische Hogeschool Eindhoven (tegenwoordig Technische Universiteit

geheten). Daar studeerde hij in februari 1985 (met lof) af in de groep

"Theoretische Elektrotechniek", onder leiding van Prof .dr. M.P.H. Ween ink.

Het afstudeerwerk betrof elektrornagnetische verschijnselen in de hogere

delen van de aardatmosfeer.

In september 1985 trad hij in dienst bij de groep "Elektrische Energie­

systernen" van de Technische Hogeschool Eindhoven. Onder Ieiding van

Prof.dr.ir. W.M.C. van de Heuvel en Ir. W.F.j. Kersten verrichtte hij onder­

zoek naar snelle beveiliging van hoogspanningsnetten en modelvorrning van

hoogspanningsl ijnen en verrnogenstransforrnatoren. Een deel van dat werk

resulteerde in dit proefschrift.

Page 140: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

Stellingen beborende bij het proefschrift van Math Bollen.

-1-

Samenwerking en bet geven van onderlinge steun zijn veel belangrijker voor

bet voortbesta.an van de soort dan onderlinge "strijd om bet bestaan".

M.. de Geus, "Het onbegrepen a.narchisme", Intermediair, 3 feb. 1989.

-2-

Zowel de vergelijkingen van Carson als de telegraafvergelijkingen verliezen,

voor boogspanningslijnen, hun betekenis voor frequenties van 1 MHz en boger.

Di t maakt bet gebruik van hierop gebaseerde lijnmodellen zinloos voor

verschijnselen welke zich afspelen op een submicroseconde-tijdschaal.

].R. Carson, Belt System Technical ]ournat. §. 539, 1926;

dit proefschrift, hoofdstuk 2.

-3-

Een wijziging van de winkelslui tingswet zou voor een groot deel overbodig

worden door de wekelijkse koopavond naar dinsdag of woensdag te verplaatsen.

-4-

Bij bet bestuderen van foutdetectie-algoritmen gebaseerd op lopende golven

dient de nadruk te liggen op bet gedrag van het algoritme in die gevallen

waarbij er geen fout gedetecteerd dient te worden.

Dit proefschrift, hoofdstuk 4.

-5-

Het door Dommel en Michels voorgestelde beveiligingsalgoritme zal, voor een

betrouwbare werking, moeten worden gecombineerd met een laagdoorlaatfilter

met een lage afsnijfrequentie. Hierdoor zal de foutdetectie ui teindelijk

niet of nauwelijks sneller zijn dan bij bet gebruik van andere, aanzienlijk

eenvoudigere, algoritmen.

H.W Dommel en ].H. Hichets, IEEE/PES Winter Meeting 1978, paper 214-9;

dit proefschrift, hoofdstuk 5.

-6-

Lopende-golfdifferentiaalbeveiliging in combinatie met een verificatietijd

van een a twee milliseconden maakt een zeer betrouwbaar beveiligingsrelais

mogelijk dat in staat is een afschakelcommando te genereren twee tot vijf

milliseconden na bet optreden van een kortsluiting op bet te beveiligen

traject.

Dit proefschrift, hoofdstuk 6.

Page 141: On travelling-wave-based protection of high-voltage networks · ON TRAVELLING-WAVE-BASED PROTECTION OF HIGH-VOLTAGE NETWORKS PROEFSCHRIFf ter verkrijging van de graad van doctor aan

-7-

Hoewel de basisgedachte achter de kritische theorie van Horkheimer en

Adorno, "elk individu stelt zijn eigenbelang hoven het algemeen belang", bij

haar aanhangers steeds tot een pessimistische visie heeft geleid met

betrekking tot de grootschalige problemen welke zich in onze maatschappij

voordoen, volgt uit dezelfde basisgedachte dat een naderende catastrofe kan

worden afgewend wanneer elk individu ervan doordrongen raakt dat onsociaal

gedrag uiteindelijk tot zijn of haar eigen ondergang leidt; elk individu zal

dan uit eigenbelang het algemeen belang nastreven.

H.Hoefnagets, "Kritische sociotogie', in: Auta 588, 1971, p.2~5-271.

-8-

In tegenstelling tot recente berichten1 bestaat er geen discrepantie tussen

de waa.rgenomen relatieve heliumconcentratie en de massadichtheid van het

heelal 2• Di t maakt het postuleren van exotische elementaire deel tjes ter

oplossing van het probleem van de "missing mass", overbodig.

1: Sky and Telescope, feb.'89, p.131; Zenit, mrt.'89, p.lOl.

2: Steuen Weinberg, "The first three mtTU.Ites", p.112.

-9-

De frequentie-afhankelijke wervelstroomeffecten zowel als de niet-lineaire

magnetisatie-effecten in de ijzerkern van een transformator kunnen samen

worden gerepresenteerd door middel van de parallelschakeling van een

frequentie-onafhankelijke niet-1ineaire zelfinductie en een frequentie­

onafhankelijke lineaire weerstand.

M.H.]. Botten, 16th European EMTP Meeting, Dubrounik, 1989.

-10-

Het wantrouwen als gevolg van de criminaliteit is een veel grater

maatschappelijk probleem dan de economische gevolgen van de criminaliteit.

-11-

Zolang niet aangetoond is dat er andere bewoonde J>Janeten bestaan heeft de

mensheid een extra reden om zuinig te zijn op de enige bewoonde planeet in

het heelal.

-12-

Wanneer de vereiste sterke daling van het elektriciteitsverbruik inderdaad

wordt gerealiseerd is onderzoek naar snelle beveiliginsalgori tmen. zoals

uitgevoerd door Bollen, overbodig.

M.H.]. Botten, proefschrift Eindhoven, 1989.