New Generation Power Factor Controller

M3 –

M3 –

PFC Controller

PowerFactorCorrectionSystem

Page 2: New Generation Power Factor Controller · Authorized Dealer Regional Sales Offices: Kolkata Mumbai Tel: +91-22-2575 0800 Fax: +91-22-2575 0810 Noida Tel: +91-120-450 5801. Fax: +91-120-450

Authorized Dealer

Regional Sales Offices:Kolkata Mumbai Tel: +91-22-2575 0800 Fax: +91-22-2575 0810Noida Tel: +91-120-450 5801. Fax: +91-120-450 5818Bengaluru Tel: +91-80-4039 0640. Fax: +91-80-4039 0603

Tel: +91-33-2419 8815. Fax: +91-33-2419 8815

EPCOS India Pvt. Ltd.A TDK Group CompanySales Head Office:14/2, Rajesh Chambers, Brunton Road, Bengaluru 560001. Tel: +91-80-4039 0640. Fax :+91-80-4039 0603.Email: [email protected].

EIPL- PFC Controller Crystal 022016 1

“Product development is a continuous process. Consequently the data indicated in this price list is subject to change without prior notice. For the latest information, contact your local partners.”

For more details on products and applications please contact our nearest sales office or write to us at [email protected]

BR4000ET BR4000ERPF display up to 3rd decimal Upgradable for steps

Intelligent Intelligent

Value for money Wide supply and measurement range

Compact Recall recorded values

l l

l l

l l

l l

Technical Data BR4000ET BR4000ER

Series Type B44066R4…A240 B44066R4…R240

Steps 4,6 and 8 relay output 4,6 and 8 relay output

Supply Voltage 144….288V ( L-N) 110….550V ( L-N/L-L)

Measurement Voltage 144….288V ( L-N) 110….550V ( L-N/L-L)

Frequency (Selectable) 50/60 Hz 40 to 70 Hz

Switching Contactor Contactor

Operating Temperature 0ºC to 55ºC -10ºC to 60ºC

Load CT input Current 1/5A 1/5A

Parameter displayedSystem voltage (V AC) Yes Yes

Reactive power (KVAr) Yes Yes

Active power (kW) Yes Yes

Apparent power (KVA) Yes Yes

Apparent current (A) Yes Yes

Temperature (°C) Yes Yes

Real-time cos Yes Yes

KVAr value to target cos No Yes

THD – V / THD - I in % Yes Yes

Individual Harmonics in % up to 31st for V and I No Yes

Energy kWh (Import/ Export) No Yes

Energy KVAh No Yes

Energy KVARh (Inductive / Capacitive) No Yes

Demand KVA /current No Yes

Run Hour – Number of hours load is connected No Yes

On Hour – hours for which power supply is On No Yes

No of interruption – Number of interruption for power supply No Yes

Alarm Relay No Yes

Out of Bank (Under Compensation) No Yes

Overcompensation No Yes

Under Voltage No Yes

Over Voltage No Yes

Undercurrent No Yes

Overcurrent No Yes

Over temperature No Yes

Under / Over Frequency No Yes

Excess Harmonics ( V-THD / I-THD) No Yes

Recall recorded valuesMaximum / Minimum Voltage No Yes

Maximum / Minimum current No Yes

Maximum / Minimum Apparent power No Yes

Maximum / Minimum Reactive power No Yes

Maximum / Minimum temperature No Yes

Maximum / Minimum THD (V/I) No Yes

Switching count of Capacitor No Yes

Operation time of Capacitor No Yes

Correction Time 10 sec ... 10 min 10 sec …30 min

Discharge Time 10 sec ... 10 min 60 sec …30 min

Dimension 96 × 96 × 51 mm 96 × 96 × 51 mm

Weight 0.5 Kg 0.35 Kg

ø

ø

Though alarm relay is not provided for fault conditions, built in factory set protection is available in BR4000-ET as per set-trip and resume limits