The Minimax fire detection control panelFMZ 4100 is a compact function centrewith high availability, combining all the ad-vantages of modern micro-electronics.
The reliable and reasonably priced linetechnology is ideal for the monitoring oflarge areas. In addition, digital informationcan be transferred from each detectorthus enabling, amongst other things, indi-vidual single alarm identification. As a re-sult of this, it is possible to combine manysmall areas or rooms in only one detectorgroup. The activated detector can then beclearly identified on the LC display of thefire detection control panel.
The heart of the control panel is a microprocessor controlled analysis unit. Thisunit is responsible for all monitoring andcontrol functions and because of its in-built automatic interrupt control functionit can react to alarm signals without delay.The panel itself is monitored by a watch-dog timer which is reactivated each timedata passes through the cyclic runningprogramme. If the trigger impulse fails to
appear, the programme controlled alarmanalysis is interrupted in order to avoidany faulty functioning. In this case, thealarm evaluation continues to function bymeans of an emergency operational cir-cuit. In the case of interference, maximumonly one plug-in unit will fail to functiondue to the parallel operation of the diffe-rent analysis units. It is also possible toexchange defective components withoutany operational interruptions occuring.
The fire detection control panel FMZ 4100contains all of the essential performancefeatures of the earlier Minimax devices.Additionally, it fulfills all requirements of amodern comprehensive safety-informa-tion system with an integrated detectoridentification system and a large LC dis-play as well as having a report printer, sta-tus and intervention system and an inter-face to building adminstration systems.These features enable an exact evaluationof the incoming alarms so that prevent-ative measures may be carried out quickly.
Minimax's experience collected over manyyears in the field of evaluation and assess-ment of fire characteristics is to be foundin an extensive, error-tolerant analysissoftware. The software enables the sys-tem to differentiate between alarm signalsand spurious (parasitic) signals. By meansof a dialogue between the fire detectioncontrol panel and himself, the user is ledthrough the necessary operational phasesthereby ruling out, to the greatest possibleextent, all possibility of problems arisingfrom incorrect operating or stress influ-enced abnormal behaviour in the case ofalarms or disturbances.
The fire detection control panel FMZ 4100fulfills the highest safety requirementswhich are, of course, indispensable in thefield of fire protection. The control panelincluding the system's components are inaccordance with the valid guidelines,norms and regulations especially VDEand EN 54 and is approved by theVerband der Schadenversicherer (VdS,Association of German Property Insurers).
Fire Detection Control Panel FMZ 4100
Design variants
The fire detection control panel is a modu-lar extendable 19" unit assembly system.Even in its smallest basic design (GAB 32),it is capable of accomodating 2 x 32 firealarm groups and 32 primary controlgroups, besides the central equipmentsuch as the power supply unit, battery andmain alarm tripping.
In the larger model (GAB 128), the systemcan be extended to 3 x 128 groups bymeans of additional plug-in zone modules.
In this case, a common central plug-in unit(master system) takes over the overridingcontrol procedure for the otherwise au-tarkic plug-in zone modules (master-slaveprocess).
A total combination of 3072 groups can beobtained by joining together up to 8 stand-ing cabinets of the above type.
FMZ 4100 - GAB 32
is extendable, with each device having 32automatic and contact giving fire alarmgroups as well as primary control groupsfor the electrical monitoring and for theoperating of the important function alarmdevices such as alarm horns, release sol-enoids, etc.
FMZ 4100 - GAB 128
is extendable, with each device having 128automatic and contact giving fire alarmzones as well as primary control groups.
Each group is connected to the line cardvia line termination cards. Using one linecard, it is possible to supply, evaluate andmonitor 4 alarm groups for automatic firealarms, 4 alarm groups for contact giving firealarms and 4 primary control groups. A re-duced version can be supplied when only4 automatic fire alarm groups are required.
The alarm signals recorded in the fire con-trol panel are digitalized and are then, incomparison between normal condition andactual condition, compared with the pro-grammed values in the non-volatile mem-ory. In the case of negative results, eitheran alarm signal or an interference signal(e.g. wire breakage, short circuit, de-tector removed) is produced. A redundant,independent alarm circuit continues to con-duct the alarm even in the case of inter-ference or breakdown of the control sys-tem.Important alarm devices are connected tothe quiescent current monitoring of the pri-mary control groups.
Detector identification system(ZID-V)
This is a system component which func-tions independently from the analysis unit.It displays selectively the position and typeof the activated, defective or removed de-tectors.
The main component of this device is amicrocontroller which additionally and uni-directionally requests data from the detec-tor via a secondary network. A speciallydeveloped analysis software checks thedetectors signal for accuracy and thenevaluates it. The obtained results are trans-mitted asynchronously to the analysis unitvia FIFO-circuits where they are then dis-played on a comprehensive 8 x 40 figurealpha-numerical LC display.
The detector identification system, the al-pha-numerical clear text display and thereport printer complement each other andtogether form an important informationsystem thus enabling the quick introduc-tion of decisive and appropriate measures.
Extinguishing controlfor the fire extinguishing system
The system component extinguishingcontrol is used to control single and multi-
zone fire extinguishing systems. It func-tions independently from the other sys-tems of the fire detection control paneland therefore has its own display andoperating panel.
Each extinguishing zone is controlled andmonitored by an autarkical functioning ex-tinguishing control card. All the importantcomponents which are necessary for thetrouble-free functioning of an extinguishingsystem (e.g. detectors, release and alarm)devices are connected to the extinguishingcontrol system. In the case of alarm, theextinguishing control system registers andanalyses the detector signal, soundsthe fire alarm and activates the pre-pro-grammed control function as well as the fireextinguishing system.
Programming
The fire detection control panel FMZ 4100can be programmed for different applica-tions. For this purpose a special configur-ation programme has been developedwhich transforms the physical values ofentered characteristics (e.g. alarm thres-hold, short circuit threshold, etc.) into alanguage understandable for the micro-controller. In this way, the user has themaximum amount of flexibility which, forinstance, is required when extendingalready existing systems. Programming is greatly simplified by theuse of modern pull-down-menu-techni-ques and easy-to-understand input in-structions.
Secondary groups
The fire detection control panel FMZ 4100can be equipped with free programmablerelays in order to enable further alarm or-ganization, for example: the disconnectionof the air conditioning, the interruption ofthe manufacturing process, the opening ofsmoke vent flaps, etc. 2 break contacts(b-contacts) and 2 make contacts (a-con-tacts) with a maximum contact load of 2amperes are available for each relay. Theoperating and logical combination of therelays is determined for each specific sys-tem by means of the Minimax configu-ration programme. The standard functionsare as follows: operating tripped by alarm,pre-alarm and interferences as well as thedisconnection of fire detector groups.
Wall mounted cabinet 15U
Upright cabinet 31U
Alarm and graphics reporting system ZID-V detector
Serial interfaces
The fire detection control panel FMZ 4100has standard serial interfaces for connec-tion to external equipment, e.g. alarm andgraphics reporting system or printer, aswell as enabling communication with asuperordinate administration system. Anadditional microcontroller circuit which hasbeen especially developed for the oper-ating of repeater panels as well as exter-nally situated control devices can exchangeinformation with the fire detection controlpanel via a serial interface. There are 768programmable outputs available for theoperating of the LEDs in a repeater panel.Additionally, the microcontroller has a seri-al interface for data transmission, e.g. for adesk-top printer. The fire detection controlpanel FMZ 4100 offers further interfacesfor fire brigade control panels as well as forthe so-called public main alarm. An alarmsignal can be automatically transmitted fur-ther to an external service, e.g. fire brigade,by means of the main alarm function. Addi-tional VdS standard interfaces are avail-able for the connection of fire detectionequipment from other manufacturers to theFMZ 4100 extinguishing control system.
Special applications
Spark extinguishing systemsThe possibility of realizing special applica-tions of fire detection and extinguishingtechnology were taken into considerationduring the development of the fire detec-tion control panel FMZ 4100. These spe-cial applications are, for example, sparkextinguishing systems for the wood indus-try, fire suppression systems for paintspraying plants as well as for the protec-tion of equipment in computing centres. Ifone takes the spark extinguishing systemas an example, it can be seen that this sys-tem can be connected to the control panelwithout any special or additional analyzingelectronics. All the requirements neces-sary for operating a spark extinguishingsystem such as adjustable extinguishingtimes for each extinguishing area, moni-toring of the extinguishing agent supply,electrical monitoring of heat tapes and leak detectors are to be found in the stan-dard programme of the control panel. It is,therefore, guaranteed that the evaluationof spark alarms as well as the operating ofthe automatic extinguishing system will becarried out with virtually no delay.
Gas detectorsA gas detector is an autonomous subsys-tem that can be easily integrated in theFMZ 4100 fire detection control panel. Owing to the increasingly complex chemi-cal processes used in industry, gas detec-tion at an early stage is often the main element of a safety scheme and is accor-dingly very suitable for combination withfire detection and fire systems. A displaycontinuously indicates the gas concentra-tions in the gas detectors. If the gas con-centration measured exceeds a preset li-mit, external equipment can be activatedvia secondary control lines. All measureddata is passed on to the FMZ 4100 whereit is recorded. This assures the traceabilityof events even after a lengthy period.
Reportprinter
Buildingmanagementsystem
Alarm andgraphics re-porting system
Repeaterpanel
Slave control panels
Manualrelease
Secondrelease
Extinguishingdelay
Systemmonitoring
Automaticrelease
Serialinterface
Networkinterface
Field termi-nation cardextinguish-ing system control EMIprotection
Operator panelextinguishing
control
Multi-zoneextinguishing control system
Field termination card for primary control zones EMI protection
CO2 low pressure system CO2 / Argon high pressure system
O
Fire brigadeoperating panel
FMZ 4100 multi zone CO2 extinguishing control panel
Fire protection for paint spraying plants
Scheme of control panel FMZ 4100
Concentrationdisplay and
operating panel
Other extinguishing systems Deluge- Foam- /Powder- Spark- Pre-action Sprinkler- Argon extinguishing system
System Gas detectionGas line card
Slave CPU 1evaluation and control
Master CPUperipheral evaluation
and control
Operator panel
Mimic panelFire brigadekey box
Fire brigademain alarm
Group LEDs
Linecard
Termi-nationandcontrolcard
Field termi-nation card for detector groupsEMI protec- tion
Field termi-nation card for primary control groupsEMI protec- tion
Relaycontrolcard
Relaycard
Detectoridentification
system
Field termination carddetectoridentificationEMI protec- tion
Evaluation and control system
Detector identification system
Extinguishing control system
Quiescent current monitoring
Digital system monitoring
Non monitored lines
Automaticdetectors
Contact givingdetectors
Optical / acousticalarm
Trigger solenoidvalve
Air conditionoff
Machineryoff
Smoke ventunlock
Detector identificationfor automatic andcontact giving detectors
Gas detector
Optical / acousticalarm
Machineryoff
Gas detection system
Minimax detector collection Fire protection for EDP installations Repeater panel
Fire detection and extinguishing control panel for 384 groups
Master plug-in card
Interface to master module
Interface to slave module
Detector identification card
Processor card
Field terminationcard detectoridentification
Relay control card
Field termination card for detector groups
Field terminationcard for primarycontrol groups
Field terminationcard for detectorgroups
Relay card
Line card for 4 automatic, contactgiving and primary control groups
Line card for4 automaticgroups
Extinguishing control card
Technical DataFire Detection Control Panel FMZ 4100 GAB 32, GAB 96, GAB 128
Specific System DataPower supply 230 V/110 V, 50/60 Hz, (+10 %, -15 %) switchable by jumper at power supplyOperating voltages 15 V, 12 V, 5 VControl voltage of external devices 24 V DCEmergency power supply 24 V DC (2 x12 V maintenance free and sealed batteries, independent of
position, deep-discharge resitant, capacity range application specific)Control relay rating 30 W/60 VA/1.5 A /250 VControl signal of main alarm 24 V DC, constant or pulses, adjustable from 1 to 10 secondsPermissible ambient temperature -5 - +40 CPermissible ambient air humidity 12 g/m3
Place of installation dry operating areas with restricted accessVdS approval G 29013FM approval OY4AO.AY
Specific Data FMZ 4100 GAB32 FMZ 4100 GAB96 FMZ 4100 GAB128Max. number of groups 32/32/321 96/96/961 128/128/1281
Serial interfaces RS 232C 2 3 2Number of control relays with full complement 80 224 296Housing type wall-mounted 15U upright cabinet 31U upright cabinet 40U
swivel frame swivel frame swivel frameColour RAL 7032, grey, structured RAL 7032, grey, structured RAL 7032, grey, structuredWeight of complete unit (without batteries) approx. 48 kg approx. 135 kg approx. 160 kgIP rating IP 42 IP 54 IP 54Dimensions in mm (W x H x D) 2 525 x 709 x 275 800 x 1600 x 500 800 x 2060 x 600
Line cards3
Automatic detector groups
Detection Group voltage 9 VDetection Group quiescent current approx. 5 mADetection Group alarm current 9 mA (spark extinguishing system: 15 mA)4Detection Group terminating resistance 1800 Alarm resistance (detector) 470 - 1000 Permissible max. line resistance 50 Permissible max. number of detectors per group 10 manual call points or 60 sprinkler monitoring modules 5
Contact giving detector groups
Detection Group current approx. 2.2 mADetection Group quiescent voltage 3.9 - 4.1 VDetection Group alarm voltage 2.7 V4
Detection Group terminating zener diode ZPD 4V3 (spark extinguishing system BZX 4V3)Detection Group alarm zener diode ZPD 2V7 (spark extinguishing system BZX 2V4)6
Permissible max. line resistance 50 Permissible max. amount of detectors per groups 105
Primary control groups
Detection Group current approx. 2.6 mAControl voltage 24 V DCDetection Group quiescent voltage approx. 2.6 VMax. load 2 A ( limited by fuse)Detection Group terminating resistance 1000 /1 Watt
Fire extinguishing control system
4 groups for automatic detectors7
4 groups for contact giving detectors7
4 primary control groups7
8 free programmable relays for non monitored groups
1 For 32, 96 or 128 automatic and contact giving groups and primary control groups2 Other cabinet sizes available3 A reduced version can be supplied when only automatic fire alarm groups are required4 Other current/voltage threshold values programmable5 VdS standard value6 For evaluation of different interferences in sparc extinguishing systems, e.g. continuous extinguishing, water supply fault, 3 additional thershold voltage values are monitored7 Technical data for groups of the extinguishing control system are similar to the line card
The right is reserved to modify any specification without prior notice.