MNS® iRPPInnovative power distributionto critical loads

April 2013

Page 2: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPIntroduction

What is MNS® iRPP (intelligent Remote Power Panel)

ABB’s MNS® iRPP offers complete power distribution and monitoring with up to 128 poles in a space-saving design.

MNS® iRPP key features:

Safe

Reliable

Scalable

Hot swappable branch circuits

Moves, add-ons and changes are accomplished without powering down the complete RPP

Continuous monitoring with user configurable alarms

Choice of top / bottom cable entry to suit non-raised / raised floor applications

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 2

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 3: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPValue proposition

Maximum uptime without outages

Safe, reliable operation with a complete vision of power distribution and monitoring.

Pre-outage alarms, triggered by user selectable parameters for main incomer and individual branch circuit breakers

Optimize energy usage

Assists with analysis of actual rack usage against the rack rated kW rating, helping data center operators manage power distribution more effectively.

Scalable for the future

Hot swappable branch circuits

User-friendly phase balancing capability

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 3

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 4: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPValue proposition

Safety in a compact footprint

The SMISSLINE TP plug-in socket system is fully protected against direct contact (IPXXB).

Simple, cost-effective operation and maintenance

Outputs can be replaced easily and quickly, reducing the component non-availability time (MTTR)

Business without barriers

No matter where you are in the world, ABB expertise is nearby.

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 4

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 5: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPOverview

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 5

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 6: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPOverview

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 6

Functional description

ABB MNS® iRPP I comprises of SMISSLINE TP socket system as distribution chassis to provide IPXXB protection for the branch MCBs and facilitate ‘hot swap’ of circuits. The current measurement system (CMS) continuously measures the current consumption in each branch circuit and the energy analyzer provides the reference voltage, cosphi and frequency from the incoming supply.

A single CMS control unit can monitor up to 64 branch circuits

The data from both the CMS control unit and the energy analyzer are fed into PLC AC500, which then calculates parameters like kW, kWh, etc., for each branch

The data from PLC can be displayed on the user friendly HMI type CP600 & can also be communicated serially to any BMS/ DCEM

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 7: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group 19. April 2023 | Slide 7

SMISSLINE-TP

Allows for load-free plugging in and unplugging of branch devices without additional personal safety equipment and without powering down the RPP

Five directly pluggable protection devices

Offers unrivalled flexibility, expandability and availability

Finger proof IP2XB

MNS® iRPPOverview

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 8: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group 19. April 2023 | Slide 8

MNS® iRPPOverview

Current measurement system (CMS)

Most compact, neat and hassle-free current measurement system

Current sensors get mounted directly on the SMISSLINE MCB, thus eliminating the need of cumbersome incoming cables

Quick start-up & reduced chances of errors

Easy & quick installation

High availability

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 9: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group 19. April 2023 | Slide 9

MNS® iRPPOverview

A44 EQ_Platinum

The energy analyzer has dual function. First, it provides the voltage and pf reference value to the PLC for calculating all the power/ energy values for the branch circuits.

Second, it provides the following data for the complete RPP:

Active power

Apparent power

Reactive power

Current

Voltage

Frequency

Power factor

Total harmonic distortion

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 10: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group 19. April 2023 | Slide 10

MNS® iRPPOverview

PLC AC500

ABB’s flagship PLC offers a wide range of performance levels and scalability within a single, simple concept

Designed to perform with ease varied communication tasks

Flexible

High data transmission speed

Multiple communication options

Easy configuration

Simple networking

Integrated web server

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 11: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group 19. April 2023 | Slide 11

MNS® iRPPOverview

• HMI CP660

Highly flexible

Specifically designed for advanced applications in complex systems or processes

Better information representation to ease human-machine interaction

Choice of screen size

Resolution: 800 x 600

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 12: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPMains monitoring

Voltage, L-L and average [V]

Voltage, L-N and average [V]

Current per phase [A]

Max. current [A] per phase

Current demand [kW] per phase

Max. current demand [kW] per phase

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 12

Energy [kWh] per phase

Real power [kW] per phase

Apparent power [kVA] per phase

Power factor per phase and total

Frequency [Hz]

Voltage, THD [%]

Current, THD [%]

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 13: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPBranch circuits monitoring

Current [A]

Max. current [A]

Current demand [A]

Max. current demand [kW]

Energy [kWh]

Real power [kW]

Real power [kW] demand

Real power [kW] demand max.

Branch CB On/Off

Branch CB rating

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 13

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 14: MNS ® iRPP Innovative power distribution to critical loads April 2013

MNS® iRPPAlarms indication

Over-/ under voltage

Over current

Phase loss

Over-/ under frequency

© BU 3101 Low Voltage Systems April 19, 2023 | Slide 14

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 15: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group April 19, 2023 | Slide 15

MNS® iRPPTypical iRPP application

- Low-voltage switchboards / switchgear- Circuit breakers- Active filters- Power factor correction

- Substation- Transformer- Medium-voltage switchboards / switches- Power quality assessments- MV UPS

- Intelligent power- Distribution units- Remote power panels- Branch circuit monitoring

- Smart grid connectivity- Microgrid solutions- Strategic partner to leading wind and photovoltaic OEMs

Data Center Infrastructure Management (DCIM)

Service and consulting offerings- Efficiency improvements- Power Quality Studies- Design- Remote monitoring- Service- Operation - Maintenance

- HVAC solutions- High-efficiency motors- Low-harmonic variable frequency drives / inverters- Circuit breakers- Cooling- Automation and control- Energy efficiency audits- Instrumentation

- Data center automation and power optimization- Remote monitoring and diagnostics - Wide range of gensets

- Rectifiers- UPS- Power transformer

Link to electrification capability slides

Page 16: MNS ® iRPP Innovative power distribution to critical loads April 2013

© ABB Group April 19, 2023 | Slide 16

MNS® iRPPTypical communication architecture

IntroductionValue propositionOverviewMains monitoringBranch circuits monitoringAlarms indicationTypical iRPP applicationTypical communication architecture

Page 17: MNS ® iRPP Innovative power distribution to critical loads April 2013
Page 18: MNS ® iRPP Innovative power distribution to critical loads April 2013

ABB in data centersScope of supply

Building electrical infrastructure (lighting, security, fire detection and suppression, etc.)Building electrical infrastructure (lighting, security, fire detection and suppression, etc.)

HV Substation

HV Substation

IT racksserversIT racksservers

Building mechanical infrastructure (doors, fences, security, barriers, etc.)Building mechanical infrastructure (doors, fences, security, barriers, etc.)

DCEM (data center enterprise management) including servicesDCEM (data center enterprise management) including services

Uti

lity-d

ata

cen

ter

dem

an

d-r

esp

on

se (

Pow

er

Ass

ure

, V

en

tyx)

Energy distribution network managementEnergy distribution network management

LV switchgear, PDUs, RPPsLV switchgear, PDUs, RPPsMV

switchgear

MV switchgear

Generator set

HVAC offering

Transformer

Transformer

& LV components

ABB offering (BU PACT)

ABB offering (BU PSSS)

Optional offering (as part of the energy supply package)

3rd party (outside of ABB’s scope and supply)

UPS or rectifier withbatteries

ABB offering (BU LPLS)ABB Ltd.April 19, 2023 | Slide 18CONFIDENTIAL – NO DISTRIBUTION WITHOUT WRITTEN PERMISSION

Page 19: MNS ® iRPP Innovative power distribution to critical loads April 2013

Energy supply for data centersAC or DC – we have the solution

MV ac 400Vac400Vac 400Vac 400Vac 12Vdc

Utility MV/LV transformers

UPS PDU ServersSwitchgear IT Power supply

AC Architecture

DC Architecture

Utility DC Rectifier

ServersDC Switchgear

IT Power supply

MV ac 380Vdc 12Vdc380Vdc

Batteries

Batteries

ABB Ltd.April 19, 2023 | Slide 19CONFIDENTIAL – NO DISTRIBUTION WITHOUT WRITTEN PERMISSION

Page 20: MNS ® iRPP Innovative power distribution to critical loads April 2013

Energy supply for data centersAC and DC

ABB Ltd.April 19, 2023 | Slide 20CONFIDENTIAL – NO DISTRIBUTION WITHOUT WRITTEN PERMISSION

AC

Medium voltage switchgear

Transformer

Low voltage AC bus duct

UPS (static/ rotary)

AC PDU/ RPP

Generator set

Power quality products

Low voltage AC switchgear

DC

MV/ LV rectifier

Low voltage DC bus duct

Battery

DC PDU/ RPP

Generator set

Low voltage DC switchgear

Page 21: MNS ® iRPP Innovative power distribution to critical loads April 2013

Summary: Key factors influencing data center success

Risk management / ease of doing business: ABB needs to become the easiest in doing business with, all around the globe. We take pride in directly providing 100% of our customer solutions, exclusively and anytime throughout the life cycle of our products.

Safety: With our proven ‘Safety Plus’ philosophy, we offer the safest systems on the market. Personal protection is our highest priority.

Availability / reliability: ABB’s portfolio offers the most reliable products on the market today by delivering real time predictive maintenance information, the most tested and industry proven components, high MTBF and shortest MTTR.

Scalability: ABB’s portfolio delivers the most flexible hardware and software options, allowing quick additions and / or configuration changes to match growing business needs.

Ease of operation / maintenance: As a world wide operating company, our service locations are close to any data center. We offer extensive SLA to suit individual facility requirements.

ABB as your partner