MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH)

BUDGETARY OFFER FOR

PROVIDING POWER SUPPLY AND LIGHTING ARRANGEMENTS FOR COAST GUARD AT MADHUSUDAN JETTY

SUBMISSION ON OR BEFORE 18.04.2016

THE CHIEF MECHANICAL ENGINEER 7TH Floor, Centenary Building Rajaji Salai, Chennai – 600 001.

Page 2: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

2

BUDGETARY OFFER FOR PROVIDING POWER SUPPLY AND LIGHTING ARRANGEMENTS FOR COAST GUARD AT MADHUSUDAN JETTY

TECHNICAL SPECIFICATION

SCHEDULE - ‘A’

1.0 GENERAL:

Chennai Port Trust is proposed to install 11 KV / 433V Compact substation at Madhusudhan jetty in Chennai Port Trust for providing of power supply to Coast Guard. The said substation will receives H.T. power supply from 33 KV substation and cater to the power supply for Coast guard.

2.0 SCOPE OF WORKS: The Scope of Work includes:

i) Design, Supply, Installation, testing and commissioning of 11 KV / 433 V, 2000 KVA outdoor type package substation with Resin cast dry type transformer, SF6 insulated circuit breaker ACB, APFC, Trivector meter, numerical relay Providing Charger unit with maintenance free batteries and other safety equipments with standard accessories etc.,

ii) Design, Supply, Installation, testing and commissioning of LT panel with

ACBs and MCCBs with multifunction meter and all other accessories.

iii) Design, Supply, installation, testing and commissioning of outdoor LT panels at wharf.

iv) Design, Supply, Installation, testing and commissioning of 11 kV, 630 A,

indoor, VCB Panel with Trivector meter, numerical relay MFM and all other accessories at 33 KV substation.

v) Supply and laying of H.T. and L.T. cables, end terminations and Straight

through joints. Provision of copper Plate Earthing and Earthing Flats, etc. All the materials and accessories shall be supplied and executed as per relevant IS Standard and IER by the contractor.

vi) Supply and installation of safety equipments.

vii) Supply and installation of outside light fittings with LED lamps

viii) Obtaining CEA’s approval.

Page 3: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

3

3.0 STANDARDS The design, manufacturer supply and testing of the various equipments and

accessories covered in this specification shall comply as per relevant IS standards with latest amendments.

4.0. TECHNICAL SPECIFICATIONS:- 2000 KVA OUTDOOR TYPE PACKAGE SUBSTATION

Scope of work includes design, manufacture, supply, installation, testing and commissioning of package substation suitable for marine atmosphere.

The prefabricated package substation shall be designed for compactness, fast

installation, maintenance free operation and maximum safety for operator / workers.

The package substation with all accessories, fittings and auxiliary equipment

in an enclosure shall consist of:

a) HT Compartment b) 11 KV / 433 V Dry type Resin Cast OFF load tap changer

Transformer compartment with copper Windings. c) LT Compartment d) APFC (Microprocessor Based) Capacitor Panel

The panels shall be manufactured as per relevant latest IEC/IS standard and

the design and operational features will comply with the provision of latest version of Indian Electricity Act, Indian Electricity Rules, Factory Act and Fire Insurance Regulation.

The specification covers technical and constructional details of outdoor type

Package Substation Unit which shall be capable of performing satisfactorily in open atmosphere/heavy dust atmosphere with high relative humidity. The Package Substation Unit shall be compact in size, transportable, light weight rugged and of robust construction and capable to withstand rough use in highly humid areas and suitable for use in outdoor location. It shall be installed and overall dimension shall be kept to minimum as far as practicable.

The Package Substation Unit shall be manufactured as per Manufacturers

standard. Access to the operating bay and to the transformer shall be avoided with

double doors. Compartments of HT /LT Doors shall be provided with pad

Page 4: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

4

locking arrangement. Internal lighting with door operated switch shall be provided for each compartment separately and safety notices shall be provided. The main components of a prefabricated-unitized substation are Transformer, High-voltage switchgear-control gear, Low-voltage switchgear-control gear, corresponding interconnections (cable, busbars) & auxiliary equipment. The components shall be enclosed, by either common enclosure. All the components shall comply with their relevant IS/IEC standards. It is mandatory to use Manufacturer’s own make switchgear inside the CSS. Ratings of CSS:

Description Unit Value Rated Voltage / Operating Voltage

kV rms 11

Rated frequency & Number of phases

Hz & nos.

50 & 3

Rated maximum power of substation

kVA Upto 2000 KVA(Cast Resin Type)

Rated Ingress protection class of Enclosure

IP: IP:54 for LT Switchgear & HT Switchgear compartments and IP-34 for Transformer compartment. Enclosure shall be IP 23.

HV Insulation Level

Rated withstand voltage at power frequency of 50 Hz

kV rms 28

Rated Impulse withstand Voltage

kV peak

75

Rated current Amp 630A Rated short time withstand current

kA rms / 3sec

21

Making capacity for switch-disconnector & earthing switches

kA peak

52kA

LV Network

LV Incomer: 1No. 4 pole 3200A electrically / manually operated fixed type ACB with thermal magnetic release.

Page 5: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

5

Enclosure GTP:

1)

Ambient Temperature 40° C

2) Type of Ventilation for a) Normal Condition b) Hot Condition

- Natural - Natural

3)

Compartmentalized Yes

4)

Rated temperature enclosure class K10

5)

Applicable Standard IEC62271-202

6) Enclosure material Galvanized sheet Steel

7) Thickness of sheet (GI only) 2mm for enclosure. 4mm for PSS Base.

Painting and Fabrication process :

a) The paints shall be carefully selected to withstand tropical heat rain. The paint shall not scale off or crinkle or be removed by abrasion due to normal handling. For this purpose powder coating shall be used.

b) Special care shall be taken by the manufacturer to ensure against rusting of nuts, bolts and fittings during operation. All bushings and current carrying parts shall be cleaned properly after final painting.

c) The fabrication process shall ensure that there are no sharp edges on the GI sheets used.

All enclosures metal frames of package substation, HV switchgear, transformer, LT switchgear and capacitor panel are to be connected to the earth system. Continuity of the earth system shall be ensured taking into account the thermal and mechanical stress caused by the current it may have to carry. Highest degree of protection to equipment and persons shall be provided. Labels for warning and operating instructions etc. shall be provided.

All equipments and material shall be designed, manufactured and tested in

accordance with latest IEC Standards. The high / low voltage prefabricated package substation shall comply with and tested as per IEC 61330/62271-202

The switchgear components shall be capable of withstanding mechanical and

thermal stress of short circuit without any damages or deterioration of materials.

Page 6: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

6

For continuous operation of specified ratings temperature rise of various switchgear components shall be limited to permissible values stipulated in the relevant standards/codes and this specification.

Earthing arrangement shall be provided for earthing of each cable, glands,

star point of Transformer, chassis & framework of the Compact SS with separate earthing terminals at two ends. Earthing Strip shall be of hot dip GI of size 50mmx6mm for Body & Neutral protected against corrosion and readily accessible. The strip shall be connected to earthing terminals with Stainless Steel nut – bolts. Separate Earthing for Body and Neutral shall be provided (Two each)

The Package Substation Unit will comprise of the following:

Incoming cable entry provision

SF6 insulated circuit breaker for primary control of Cast resin Dry type copper winding Transformer with over current short circuit and earth leakage protection. The SF6 insulated circuit breaker compartment contain numerical relay, Trivector meter, MFM and all other accessories.

Double wound outdoor type copper wound dry type Resin Cast transformer

The transformer and HT switchgear and LT switch gear shall be connected with copper bus bar with suitable size to withstand short circuit current.

LT side of the Transformer to provide MFM and all other accessories.

Weather proof sheet steel enclosure with skid base, provision for lifting arrangement.

Measuring instruments with CTs & PTs for HT and LT side.

To avoid entry of rodent in the transformer compartment stainless steel mesh shall be provided from inner side of louvers.

Adequate ventilation shall be provided.

Potential transformer and Current transformers shall be of dry type. HT – PT 11000/√3, 110/√3, CT incomer 300/1/1. LT – CT shall be provide suitable range Internal Arc tested of 21KA / 0.2 sec as per latest IEC 62271-202

2 Nos. 230V AC space heater with suitable rating, ON/OFF switch and thermostat control. Current density 1.5 A / Sq.mm

Page 7: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

7

4.2. Off Load Tap changer Transformer

2000KVA, double wound dry type Resin Cast transformer complete with all fittings and accessories. The input /output to the Transformer for specified KV. The output of the Transformer for specified KV. The output of the Transformer to the LT panel shall be by means of bus bar arrangement. A common under base on which the above HT cubicle, Transformer and LT panel are assembled and inter connection made as mentioned above. The under base shall be provided with steel base and fitted with lifting and haulage lugs.

The equipment covered by this specification shall, unless otherwise stated to be designed, constructed and tested in accordance with latest revisions of relevant Indian standards / IEC publications.

IS 1271 - Classification of Insulating Materials. IS 2026 - Power transformers (part I - V) IS 2099 - Bushing for alternating voltages above 1000 V IS 2705 - Current transformers IS 3202 - Code of practice for climate proofing IS 3639 - Power transformer fittings and accessories IS 4257 - Porcelain bushings for transformers IS 11171 - Dry type Transformer IS 8478 - Application guide for tap-changers

IS 10028 - Code of practice for selection, installation and maintenance of transformers.

The transformer shall be dry type Resin Cast only and of latest design with off load Tap changer. The transformer shall be suitable for operation at full rated power on all tapings without exceeding the applicable temperature rise.

It shall be possible to operate the transformer satisfactorily, with the loading guide specified in IS-6600. There shall be no limitations imposed by bushings, tap changers, auxiliary equipment to meet this requirement.

The transformer shall be designed to be capable of with-standing, without injury, the thermal and mechanical effects of short-circuits between phases or between phase and earth at the terminals of any winding with full voltage applied across the other winding for periods given in relevant standards. There shall be no limitations imposed by any part/component of the transformer off load tap links to meet the short circuit level Specified.

The transformer shall be designed for minimum no-load and load losses within the economic limit and shall be able to have minimum loss at the rated load condition.

Page 8: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

8

All electrical connections and contacts shall be of ample cross sections for carrying the rated current without excessive heating. The transformer shall be capable of continuous operation at full load rating. The core-clamping frame shall be provided with lifting eyes having ample strength to lift the complete core and winding assembly. Off circuit tapings shall be provided on the HV windings. Tap changing is done by means of off-circuit links accessible through openings provided. The lifting lugs and rollers shall be provided. A winding temperature scanner shall be provided and shall be actuated by means of resistance temperature detectors embedded in LV windings of all three phases. It shall have alarm and trip contacts at a specified temperature. Windings shall be of electrolytic copper conductors (circular in shape) of high conductivity and 99.9% purity. Windings shall be designed to withstand the specified thermal and dynamic short circuit stresses. The windings shall be duly sectionalized. Accessible joints brazed or welded and finished smooth shall connect similar sections. No corona discharge shall result on the winding upon testing the transformer for induced voltage test as specified in IS.

The end turns of the high voltage windings shall have reinforced insulation to take care of the voltage surges likely to occur during switching or any other abnormal condition. The high voltage and low voltage winding are shall be made of copper Conductors. Output in KVA : 2000 KVA double copper wound. Rated No load voltage ratio : 11KV/433 Volts No. of phase : 03 Rated frequency : 50 Hz Connections : Primary – Delta

Secondary – Star with Neutral Vector Group : DYn11 Tapings on HV Side : ±5% in steps of 2.5% Type of Tap changer : Off circuit tap links on HV side. Cooling : Naturally cooled (AN) Termination : HT Side - Suitable for bus bar.

LT Side - Suitable for Bus bar

Page 9: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

9

Fittings : 2 Nos. earthing terminals, rating & diagram plate, bidirectional rollers, lifting lugs, winding temperature scanner.

Temp. Rise winding over ambient temp : 90˚C Insulation Class : F Percentage Impedance : 5% Paint : Enamel (Siemens Grey) Transformer losses : The transformer shall be so designed it should have minimum losses and it shall be submitted by the Bidder along with the Bid with calculation. 4.3. LT SIDE

LT switchgear panel shall complete in all respects with all equipment fittings and accessories including internal wiring for efficient and trouble free operation as required. Air Circuit Breakers (ACB) shall be with fault level of 50 KA for 1 Sec., copper bus bar, spring charging operating mechanism, microprocessor based overload, short circuit and earth fault protection releases with wide setting range, LED displays, alarm display for microprocessor fault, interlocking, etc. complete as required.

The LT Panel shall be the integral part of the Package substation Unit and suitable for outdoor use. This shall be suitable to receive power at 433 V, 50 c/s, 3 phase AC and restricted earth neutral system and comprising of the followings: Incomer Capacity: 1 No. 3200A, 4P, 50 KA ACB with microprocessor based over

current, short circuit and earth fault release, MFM, indicating lamps and ON/OFF push buttons.

NOTE: Type Test Certificate of Similar type (ACB) & Rating shall be submitted by

the successful tenderer.

OUT GOING: Outgoing cable 4 x 1000sq.mm single core LT cable shall be connected to

indoor type 9 way LT panel. All outgoing feeders shall have phase indicating led lamps and Multifunction

Meter.

Page 10: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

10

4.4. 750 KVAR APFC Capacitor Panel:

The capacitor panel shall be an integral part of package substation. The Capacitors control panel shall be of automatic switching type with facilities for manual control. The panel shall be a cubical type metal clad board equipped with Microprocessor based intelligence version APFC relay with 3 phase CT sensing, Switch Fuse Units with HRC fuses (feeder Control), Heavy duty contactors and metering equipment and controlling banks of capacitor mounted in ventilated compartments with IP:54 protection with bottom lowers. The switch units, contactors, etc. shall be selected to suit Capacitor ratings. The panel shall be capable of switching ON/ switching OFF capacitor bank in stages with on delay timer. The APFC relay provided in the panel shall be three phase sensing power factor on 433V bus and there upon switch ON/switch OFF.

The panel shall be inbuilt in Compact SS with separate compartments for incoming outgoing control switches or the capacitor banks. A continuous earth bar shall be provided to which the individual capacitor banks shall be connected. All main bus bar connection shall be of Copper. Panel shall be painted with Epoxy primer and Epoxy paint after an accepted metal treatment process.

The switching of capacitor bank by a re-strike free breaker shall not cause first peak of transient over voltage not to exceed 2√2 times the applied voltage (rms) for maximum duration of 1/2 cycle and shall be suitable for performing 5000 switching operation/year under these conditions.

LT capacitor banks shall be provided on the LT buses in proposed sub-station to improve the power factor from 0.8 to 0.98 and above lagging.

LT Capacitor banks of suitable rating shall be provided directly at incoming side of incomer breakers of LT panel to compensate the reactive load of transformers and to maintain power factor above 0.98 even when no motor is in operation. Contractor shall furnish the calculation for suitability of capacitor bank range.

The rated voltage of 3 phase capacitor bank shall be 433 V (Phase to Phase) and 230 V (Phase to Ground). The capacitor offered shall be non self-heating type, super heavy duty long life MPP type conforming to IS 2834 and IS 13585.

Capacitors banks are to be built up from individual single phase units suitably interconnected and housed in a metal enclosure to form a single 3 phase bank Capacitor. Capacitors having low Loss/KVAR shall be preferred.

Page 11: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

11

Capacitors shall be suitable for operation at power frequency voltage level and for power frequency plus harmonics such that current does not exceed the values specified in clause 6.2 Annex C & E of IS 13585.

Capacitor modules shall be provided with in-built MCCB to isolate individual faulty units from the total bank. Capacitors are also to be provided 0.2% series Reactor to limit the fault current or inrush current during switching operations along with ON delay timer on individual feeder.

Capacitors shall be provided with directly connected discharge device suitable to reduce the residual voltage from crest value of the rated voltage to 50 volts or less within 1 min after the same is disconnected from the supply.

For enabling the metal container to carry fault current in the event of breakdown of container, this container shall be provided with a connection capable of carrying the fault current.

Relay shall be suitable for operation at low load and current sensitivity shall be equivalent to 1%.

The capacitor should be of rating as indicated in the Bill of Quantities, to provide for a gradual increase in KVAR ratings in steps.

Type tests certificate for similar type & rating of capacitors in accordance with IS 13585 shall be submitted by the successful Bidder.

The routine and acceptance test shall also be performed as per the relevant standards

4.5. Tests (i) Type test certificate for similar type & Rating of Compact Package Substation manufactured as per IEC 61330/62271-202 be submitted by the successful tenderer.

(ii) The Routine and Field test shall be arranged by the Contractor and carried out on

Compact Package Substation as per latest relevant IEC / IS Standards in presence of Third Party Inspection Agency. The Certified copies of test certificates shall be submitted before despatch.

(iii) The package sub-station shall be designed to meet the similar rating of type test.

(iv) All the tests shall be carried out as per relevant IS specifications and IER 1956 before charging the Transformer

Page 12: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

12

(v) After installation of CSS / HT VCB panels / LT panels testing and commissioning shall be done as directed by TPI / Engineer in charge.

5.0. HT VCB PANEL AT SUBSTAIONS:

HT panel shall be modular design, panel type suitable for 1 No. 11 KV, VCB for as Incomer mounting on a common under base with suitable cable entry box arrangement for 185 sq.mm XLPE cables. Necessary control Protection and metering circuits are completely assembled, wired and enclosed in a weather and dust proof cubicle. The equipment shall be suitable for outdoor installation in highly humid area. The input to HT side of Transformer shall be through 11 KV VCB panel.

The HT Panel shall be sheet steel enclosed, dust and vermin proof, suitable for indoor use. This shall be suitable to receive power at 11 KV, 50 Hz, 3 phase AC with all equipment fittings and accessories for efficient and trouble free operation.

a) 11KV, 630A VCB The self-tripping mechanism with numerical

relay with IDMT, over current, earth fault and Instantaneous protection including TVM, MFM and all others panel’s indications lamps.

b) 11KV / 110 V PT of 100VA along with HRC Fuses.

c) 11KV CTs of 300/1/1 ratio with suitable VA burden and accuracy class 1.0 for metering, 10P10 for protection conforming to IEC 60185.

d) Incoming cable entry box shall be provided for the required cable entry.

e) System rated voltage 11 kV

f) System maximum voltage 12 kV

g) Frequency 50Hz

h) Insulation level

i) 1.2/50 microsecond Impulse withstand voltage

75 kV peak

Page 13: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

13

ii) One minute power frequency withstand voltage

28 kV rms

j) Rated current

i) Continuous

- Bus bar 630 A

- Incoming/outgoing circuit breaker

630 A

ii)Short time current for seconds

25 kA rms

k) Circuit breaker

i) Quantity One incomer

ii) Rated breaking capacity Symmetrical.

21 KA / 1 Sec.

iii) Rated making capacity 52.5 KA

iv) Total breaking time 7 cycles maximum

v) Operating sequence As per IS/IEC

l) Potential transformers

i) Quantity One set for HT outgoing

ii) Voltage ratio 11000/√3 : 110/√3 : 110/√3

iii) Reference Standard As per IS-3156

iv) Over voltage factor As per IS-3156

v) Accuracy class 1.0

vi) Insulation Level 75 kV Peak / 28 KV rms

Page 14: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

14

vii) Voltage Factor 1:2

viii) Rated Burden 100 VA

m) Current Transformer

i) For Relay 10P10/15 VA (Min)

ii) For Metering 1 / 15VA

iii) Insulation Level 75 kV Peak / 28 KV rms

iv) Insulation Class F

v) Reference Standards IS:2705

vi) Ratio 300 /1 /1

The panel shall be provided with two earthing terminal , necessary inter-

connection, control wiring and shall be complete with finishing paint etc. & conform to relevant IS.

Vacuum Circuit Breaker variable setting ranges from 50–100 %. The neutral system comprising of housing of breaker, safety shutters, isolating plugs and socket and VCB trolley with 3 Nos. vacuum interrupters with safe aligning finger type, isolating contacts suitable for vertical isolation and horizontal draw out. VCB included 3 phase, 3 limb, draw out feeder connected PT. (i) Type of charging : Manual as well as motorized Mechanism with 230V AC Operated motor. (ii) One No. Shunt trip coil : 24V DC (iv) One No.closing coil : 24V DC (v) One No. busbar chamber with 630 A copper busbar, heat shrinkable PVC

sleeved / powder coated with colour code. The current density 1.5 Amps/sq mm. The busbar shall be high conductive electrolyte copper.

(vi) 2 Nos. 230 V AC space heater with ON-OFF switch and thermostat. (vii) 3 Nos. epoxy cast resin CTs with 15VA burden STR of 25 KA for 1 sec.

metering accuracy class 1 and protection accuracy 10 P10 and having of CTR 300 /1-1 for Incomer.

Page 15: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

15

(ix) The Trivector meters shall be consist of Amps, Volts, KVA, KW, KWHr, KVAR, PF, Frequency and etc.

(x) One set of breaker ON-OFF LED indicating lamp. (xi) One No. trip circuit healthy indicating LED indicating lamp with push button. (xii) One No. Spring charged LED lamp indication. (xiii) One No. TNC (trip neutral close) switch.

(xiv) Numerical relays consist of IDMTL + Inst 3 O/C + Inst E/F relay – 1No. Master trip - 1 No. (xv) 2 sets of operating handle, spring charging handle and other required

accessories shall be supplied. (Xvi) One No. Cable Box suitable from receiving of 3CX185 Sq.mm H.T. XLPE

Cables. (xvii) One No. panel illumination lamp. (xviii) Hooter for tripping.

All necessary protection fuses /MCCB for the instruments and relays shall be provided separately inside the enclosures suitable capacity

The incomer VCB with necessary interconnection with fine wiring, feruled properly, Earthing, etc. The layout drawing dimensional drawings and electrical wiring diagram and operation maintenance manuals in duplicate shall be supplied with VCB. The VCB shall be supplied in conformity with relevant IS & IEC with up to date amendments along with manufacturer’s / authorized system house test certificate shall be produced. The VCB panel shall be delivered after third party agency acceptance certificate.

HT copper busbar shall have electrolytic grade of 630 Amps rating for three phases including color code and PVC sleeving. All the HT busbar shall be supported on hylem / epoxy insulators. The Bakelite sheet of 12 mm thickness (minimum) shall be provided in side enclosures of panel and wherever it is found necessary under relevant IS specification & IER-1956 rules. 6.0. INDOOR TYPE L.T.PANEL:

The L.T. panel shall be of metal enclosed, indoor floor mounted free standing weather proof compartmentalized. The L.T. panel switch board frame load bearing members shall be fabricated using suitable mild steel structural section or pressed and shaped CRCA sheet of thickness not less than 2 mm. Frame shall be

Page 16: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

16

enclosed in CRCA of thickness not less than 2 mm. Suitable size of brick pedestal shall be provided.

9 way L.T. panel shall comprising of the following: Incomer 3200A, 4P, ACB, 50 KA : 1 No. Outgoing 1600A, 4P, ACB, 50 KA : 1 No. 800A, 4P, ACB, 50 KA : 1 No. 400A, 4P, MCCB, 50 KA : 3 Nos. 100A,4P,MCCB, 50 KA : 3 Nos.

The ACB variable setting ranges from 50–100%. The MCCB shall be micro processor based over load release and short circuit protection. All the MCCB shall be as per IS 13947 the variable setting ranges from 80–100 % All the breakers shall have current limiting and isolation features.

7.0. OUTDOOR L.T. DISTRIBUTION PANEL AT WHARF:

It shall be Design, Supply, Installation, testing and commissioning of out door type, SS304 LT panel IP 65 shall comprising of the following:

PANEL – I (5 way) Incomer 1600A, 4P, 50 KA, ACB : 1 No. Outgoing 800A, 4P, 50 KA, ACB : 4 Nos.

PANEL – II (7 way)

Incomer 800A, 4P, 50 KA, ACB : 1 No. Outgoing 250 A, 4P, 50KA, MCCB : 6 No.

Note: 1. The LT panels shall be supplied with CPRI / other skateboard laboratories test certificate

2. The LT panels shall be delivered after third party agency acceptance certificate.

7.1. INSTALLATION OF CSS AND ALL PANELS:

The contractor shall maintain the floor level to erect the compact substation / HT VCB panel / LT panels. If involve any fabrication work and civil work the required materials and labour charges shall be borne by the contractor.

Page 17: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

17

8.0 SUPPLY AND LAYING OF 11 KV 3 X185 sq. mm XLPE H.T. CABLES

The cable measurements are tentative and may vary as per site condition. This includes supply and laying of H.T. 11KV, XLPE (E) 3C x 185 sq. mm. aluminium conductor armoured cable. The cables are to be laid as per IS: 1255 and as detailed under:

(i) The cable shall be laid in the existing trench by opening the slab covers and re closing the same with out damaging the slab after laying of the cable.

(ii) The cable shall be laid Earth / concrete road cutting / concrete cutting / Tar road cutting. Rail way line of size 60 cm width x 90 cm depth to lay each run of the above cable covered with RCC trough and re-closing with excavated soil and make it original level. Required RCC Troughs shall be supplied by the Contractor. For road crossing / Rail way line crossing G.I pipe shall be provided and shall be supplied by the Contractor. The size of pipe shall not be less than 10 cm in diameter for each cable. The pipe shall be laid at an angle to avoid sharp cable bends at the point of entry and exit. A spare pipe of the same size shall simultaneously be laid for future augmentation / requirement.

9.0. H.T Cable Straight through joint:

H.T. straight jointing of cable shall be done with heat shrink jointing kits of

approved make. All jointing accessories and other material shall confirm to IS Specifications wherever available. On both sides of joints a loop of sufficient length of 3 to 5 Mtrs shall be kept for future requirement.

This also includes housing of straight through joint in a R.C.C. chamber of adequate size and strength duly fitted with the pipe of suitable size at an entry and exit point of chamber to facilitate easy movement of cable. The chamber shall be covered with RCC slab of suitable thickness and strength.

The cable shall be provided with suitable identification indicator mark. The work includes all labour and l required material and shall be done as required by E.I.C. 9.1 End termination of H.T. cables:

This includes providing and fixing end termination to HT 11 KV 3 C x 185 sq. mm. XLPE(E) aluminium conductor armored cable with heat shrink type indoor end termination kit with all accessories and other material shall be supplied by the contractor and confirming to relevant IS specification the additional length of cable shall be provided for loop of sufficient length (3 to 5 mtrs.) for future requirement before commencing and termination work. The work includes all labour and required material and shall be done as directed by E.I.C.

The work includes end termination of cables of HV & LV cable and termination with epoxy cable jointing kits & materials, lugs of all other accessories including labour etc.

Page 18: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

18

The work includes all labour and material of approved make & shall be done as directed by E.I.C. The complete work shall be carried out as per standards of CEA. 10.0 LT CABLES 10.1. SUPPLY AND LAYING OF L.T. SINGLE CORE 1000 SQ MM AND 3.5

CORE 185 SQ.MM UNDER GROUND CABLE:

The cable measurements are tentative and may vary as per site condition. Supply and laying of Aluminium XLPE L.T. under ground cable of 1.1KV voltage grade having stranded compacted aluminium conductor with, XLPE insulation, R,Y & B colour for phases and Black colour for Neutral core, extruded PVC inner sheathed, single layer of galvanized steel wire / strip armoured, over all PVC sheathed conforming to IS 7098 Part I 1985 with latest amendments with ISI mark. Note: i) Test certificates from the manufacturers for HT /LT cables shall be submitted along with the supply of cables and TPI acceptance report before dispatch of the cables. ii) 1 X 1000 sq.mm LT cable shall be laid from the Compact substation LT panel to LT panel. iii) 3.5 core 185 sq.mm LT cable from LT panel to wharf panel. It shall be laid on the wharf using suitable clamps with equal interval and covered with cement mortar. The end termination for 1100Vgrade under ground cables shall be of crimping type lugs shall be supplied by the contractor. The crimping type lugs shall be installed by highly skilled personnel.

10.2 LT CABLES FOR STREET LIGHT

SUPPLY: Supply of 4 core 10 Sq. mm Aluminium PVC L.T. under ground cable of 1100V voltage grade having stranded compacted aluminium conductor conforming to IS 7098 Part I 1985 with latest amendments with ISI mark.

LAYING:

Laying of one run of above cable shall be laid on the wharf using suitable clamps with equal interval and covered with cement mortar.

Page 19: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

19

11.0 SUPPLY AND INSTALLATION OF LIGHT FITTINGS:

a) TWIN STREET LIGHT FITTINGS: Supply and installation of 3mm thickness of G.I.Street light pole of 10 metres, Height with base plate of 16 mm thickness minimum It shall conforming to BSEn 10025. The bottom section diameter shall not be less than 200 mm, gradually reduced at the top section diameter shall not be less then that 100 mm. Necessary junction box shall be fitted at bottom of post with suitable cable connector (i.e. 2x4 core x 10 sq.mm L.T, XLPE, .U.G.Cable) and one number 6 A, SP, MCB inside the pole with hinged front door. 3 core 1.5 sq.mm copper cable shall be laid from junction box to top of the 2 Nos. LED Flood light fittings equivalent to 2 x400 W HPSV fittings.

FOUNDATION: Earth work excavation, designing and casting suitable foundation with M 20 concrete foundation for fixing the base plate with bolts and nuts for erecting the street light posts with suitable provision of cable entry for incoming and outgoing and for earthing wire.

b) LIGHT FITTINGS ON WALL:

Supply and installation of wall mounted light fittings with necessary GI bracket at a height of 7 – 10 Mtrs. 230V, 1 Ph, 50 Hz, LED light fitting is equivalent to 400 W HPSV light fittings. c) RED LIGHT FITTINGS ON WALL: Supply and installation of wall mounted water tight explosion proof RED colour light fittings at a height of 7 – 10 Mtrs. 230V, 1 Ph, 50 Hz, 100 W at various locations.

12.0 INTERNAL ELECTRIFICATION: Internal electrification of compact substation shall be carried out with suitable light fittings, switch boards and necessary wiring to maintain required illumination level of the compact substation. 13.0 BATTERY CHARGER: Supply, Installation, Testing and commissioning of the battery charger unit with 2 Nos. 12 V with 2 Hrs back up with suitable rating Maintenance free battery. The battery charger shall be of floor mounting and air cooled type. The input supply of the

Page 20: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

20

unit shall be 230V / 250V. Single-phase AC 50HZ and the output supply of the unit shall be 24V DC. Suitable for tripping / closing / Indication. 14.0 SPECIFICATION OF SAFETY EQUIPMENTS: The following safety equipments shall be supplied in the substation as per the IER. FIRE EXTINGUISHERS: Adequate number of portable chemical fire extinguishers of carbon tetra chloride conforming to IS 935 latest version shall be supplied and installed at the proposed 11KV substation. FIRE BUCKETS: Adequate number of fire buckets with M.S. angle stands each consists of 4 Nos. of round bottom fire buckets painted with red and marked fire and filled with clear dry river sand shall be supplied and installed at convenient locations at proposed 11KV substation. The fire extinguishers and fire buckets shall be provided conspicuously marked to comply with Indian Electricity Rules 4.3 of 1956. FIRST AID CHART AND BOX: The first aid boxes and charts equipped fully with such contents as stipulated by the CEA conspicuously marked shall be supplied and installed in the switch gear room at 11KV proposed substations. INSTRUCTION FOR RESTORATION OF PERSONS SUFFERING FROM ELECTRIC SHOCK: Instruction in English and Tamil for providing artificial respiration as per CEA regulations shall be supplied and affixed in a frame board at convenient location in the proposed 11KV substations. Safety posters for vigilance against electrical accidents as per CEA regulations shall also be provided by the contractor. RUBBER MAT: Suitable size of tested flexible rubber mat conforming to IS 5424 of 1994 shall be provided around the compact substation and L.T. panel. RUBBER GLOVES: Required number of rubber gloves conforming to IS 4770 of 1991 and tested to 15KV shall be supplied and provided in the proposed 11KV substations.

Page 21: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

21

CAUTION BOARD:

Required number of Danger board / sticker of H.T. Voltage in three languages English / Tamil / Hindi are to be provided on the panel. The firm shall obtain necessary approval of the drawing of HT panel from Ch.P.T. before fabrication. 15.0. LETTER PAINTING:-

All incomer cables / all outgoing cables / P.T. & C.T. VCBs details shall be painted at the front and rear sides of the compact s s / LT panel specifying the full details and furnishing the amperage, voltage, size of the cable in the red letters on white back ground. Should be written in both L.T. & H.T. panels. 16.0. TESTS:- The 11 KV / 433Volt Compact substation, HT and LT panels shall be tested for routine tests as per relevant IS. Type test certificates shall also furnished along with routine test certificates. Manufacturer’s test certificates shall be furnished for major components.

17.0 EARTH PITS AND EARTHING:

The earth system shall be designed and installed so as to meet the

requirement of CEA. The value of resistance of earth system should not exceed value acceptable to the Central Electricity Authority.

The earth value shall be obtained accordance with relevant standards and the earth values shall be measured after installation in the presence of Trust Engineer. All non current carrying parts with conducting surface such as power transformer, frame works of circuit breakers and medium / low voltage switch gears, instrument transformer cases, cable glands, cable supports, any steel works of the substation buildings should be efficiently grounded for the protection of equipments and operating personnel by connecting to the earth ring bus with two distinct and separate earth leads. The earth connection shall be made of copper of adequate size and section of the conductor conforming to IS 3043 to safety carry the maximum fault current for a short period without burning the conductor and pass on the fault current is in excess of this, additional earth connections under fault condition and at no time the potential shall exceed 10 volts between the equipment and earth. The earth system shall be mechanically robust and joints shall be capable of retaining low resistance even after many passages of fault current. The G.I. flats of size 50x 6mm shall be interconnected of earth pits.

Page 22: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

22

Interconnections and joints for earth conductors shall be riveted and soldered for retaining low resistance. Each earth bar should be connected to the main earth through a bolted removable link. All ground connections shall be compounded and braided. The earth electrodes shall be driven to a depth of not less than 2.7 meters below the ground level and at least 3 meters away from the building and any other earth electrodes treating the soil surrounding the electrodes with the salt, coke and charcoal in accordance with IS 3043. 4Nos. 600x600x6mm copper Plate earthing for HT panel and Transformer and 2 Nos. Maintenance free earthing for L.T.panel.

A suitable brick cemented enclosure for neutral and body earth will be

as per IE Rule (i.e) 450mm x 450mm with 125mm wall thickness. The depth of the masonry work will be not less than 600mm below the ground level and with suitable cover provided by the contractor enclosing the earth electrodes and shall be able to take up the load of lorries, etc., operating in that area. The top surface of the earth pit shall be in level with the finished surface level of the surrounding area. 6 Nos. earth pits for Compact substation and HT/LT panels and Transformer. 18.0. SUPPLY AND LAYING OF GI FLAT:

Supply and laying of 1 run of 50 x 6 mm GI flats from the LT panel to LT distribution board along with 3 ½ core 185 Sq.mm LT Cable.

19.0.DRAWING LIST:-

Necessary drawings shall be prepared and submitted to Trust’s Engineer for approval before fabrication of panel and commencement of work All catalogues, technical drawings, details etc., for all the proposed Compact substation, H,T. & L.T. panels with operation and maintenance manuals with spares list shall be furnished to the Trust’s Engineer by the contractor.

20.0 CEA APPROVAL AND TESTING AND COMMISSIONING:-

The contractor shall arrange for obtaining CEA approval and the Trust will not pay for the inspection charges. It is the responsibility of the contractor to carry out the

Page 23: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

23

works in accordance with the requirements of CEA. Any modification and corrections suggested by CEA on inspection shall also be complied by the contractor. 21.0.

22.0 LIST OF APPROVED MAKES S.No. ITEM Name of Manufacturers

1 Volt meter and Ammeter AE / MECO / YOKINS / NIPPEN

2 Selector switches, Push buttons, Emergency Switches

KAYCEE / L & T / GE / BCH / LEGRAND

3 HRC Fuses L & T / GE / SIEMENS / ABB / INDO KOPP

4 Indicating light AE / KAYCEE / VAISHNAV / L & T /SIEMENS

5 MCB L & T / LEGRAND / SIEMENS / ABB / SCHNEIDER

6 Sub Distribution Board L & T / LEGRAND / SIEMENS / SCHNEIDER / HENSEL

7 EL MCB L & T / SCHNEIDER / LEGRAND / SIEMENS / ABB

8

FRLS PVC insulated copper conductor single/multi core stranded wires of 650/1100 volt grade

HAVELLS / FINOLEX / RPG /UNIFLEX /NICCO /RR Kables

9 Steel Conduit/PVC Conduit BEC / AKG / NIC

10 Switches, TV & Telephone Socket outlets, Boxes

MK / CLIPSAL / LEGRAND / NORTH WEST /ANCHOR

11 Light Fixtures PHILIPS / BAJAJ / WIPRO / CROMPTON

12 Lamps and Tubes PHILIPS / WIPRO / BAJAJ / CROMPTON

13 Ceiling fans/Wall bracket fans / Exhaust Fans

HAVELLS / CROMPTON GREAVES / USHA / ORIENT

Page 24: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

24

S.No. ITEM Name of Manufacturers

14 Cable lug & Cable Gland DOWELLS / JHONSON / RAYCHEM

15 Terminal Blocks WAGO & CONTROLS / PHOENIX CONTACTS / OBO BETTERMANN

16 Multi-function Meter ABB / SIEMENS / L&T / HPL SOCOMEC/CONZERVE (ENERCON)

17 DWC HDPE Pipe DURA LINE / CARLON / EMTELLE

18 Contactors L&T / SCHNEIDER / SIEMENS/ABB / BCH

19 MCCB L&T / SIEMENS / SCHENEIDER / ABB

20 VCB / SF6/ Isolator SIEMENS / AREVA / ABB / SCHNEIDER

21 Push Buttons SIEMENS / ABB / TELEMECANIQUE / L&T / SCHNEIDER

22 Relays L&T / ABB / SIEMENS / SCHNEIDER/AREVA

23 Timers L&T / SIEMENS / TELEMECANIQUE/ABB

24 Indicating Light L&T / SIEMENS / TELEMECANIQUE / ABB / GE

25 Indicating Instruments AE / MECO / CONZERVE / L&T

26 HT Cable FINOLEX / RPG / UNIFLEX / TORRENT / HAVELLS / UNISTAR /NICCO

27 LT Cable (XLPE and FRLS )

UNISTAR / FINOLEX/ NICCO / HAVELLS / RPG / UNIFLEX

28 Termination Kit BIRLA 3M / RAYCHEM /DENSON

29 CTs L&T / AREVA / JYOTI / KAPPA / PRAGATHI

30 PTs AREVA / KAPPA / PRAGATHI

31 HT Panels SIEMENS / SCHNEIDER / ABB / AREVA

32 LT Panels SIEMENS / L&T / SCHNEIDER / ABB

33 Cable Trays (FRP) LEGRAND / ERCON / NEEDO / SUMMIP

Page 25: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

25

S.No. ITEM Name of Manufacturers

34 ACB SCHNEIDER / SIEMENS / ABB / L&T

35 Selector Switch KAYCEE / L&T / SIEMENS / BCH / GE / SALZAR

36 Capacitor Banks EPCOS / L&T / SCHNEIDER

37 Trivector Meter (Digital) L&T / SCHNEIDER / SIEMENS / HPL SOCOMEC

38 Capacitor Panels ABB / L&T / EPCOS / SCHNEIDER

39 Power Factor Correction Relay EPCOS / L & T / ABB

40 Elastomeric Mat

PREMIER POLYFILM LTD / POLYELECTROSAFE / CHALLENGER

41 MS & GI Conduits Accessories STEEL MARK / NIC

42 Transformer ABB / SCHNEIDER / SIEMENS

43 Compact SS ABB / SCHNEIDER / SIEMENS

44 Items not covered above As per samples approved 23.0. THIRD PARTY INSPECTION REPORT: The executed work along with materials is certified by third party inspection report. The TPI charges will be borne by Chennai Port Trust. Note :

i) For any clarifications, the firm may contact Executive Engineer (PS) at IInd floor, Old Administrative office, Chennai Port Trust, Telephone Nos.25362201 – Ext:2542 (or) SE(ES&CH) at IInd floor, Old Administrative office, Chennai Port Trust.

SUPERINTENDING ENGINEER(ES&CH) CHENNAI PORT TRUST

Page 26: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

26

SCHEDULE OF QUANTITIES & PRICES

SCHEDULE – ‘A1’ PART – 1

Sl. No.

Description of the work

Unit

Qty

Rate in Rupees

Amount in Rupees

1. Design, Supply, Installation, testing and commissioning of 11 KV / 433V, 2000 KVA, Package Outdoor Sub-Station comprising of: HV Compartment comprising of 1 No. of 11 KV, 630A, 25 KA, 3 Phase 50 HZ SF6 insulated circuit breaker with standard accessories as per Technical specification schedule ‘A’., a) with P.T. -1No. Transformer compartment: 11 KV/433V, 2000 KVA, DYn II, Dry type Resin cast Transformer with standard accessories. LV compartment comprising of 1 No. of . 415V, 3200A, 4 pole, 50KA, ACB and 1 No. APFC unit with standard accessories as per Technical specification of Schedule ‘A’. Compact substation shall be positioned with necessary M.S channel fabrication work and flooring work. a) Supply b) Installation

Set Set

1 1

2. Design, Supply, Installation, testing and commissioning of 11 KV, 630A, 25KA, 3 Phase 50 HZ Vacuum circuit breaker with P.T and all other accessories (out going Feeder) at 33 KV substation as per Technical specification schedule ‘A’.. a) Supply b) Installation

No. No.

1 1

3. Design, Supply and Installation of 9 way, L.T. distribution panel with ACBs and MCCBs as per Technical specification schedule ‘A’. It shall be positioned with necessary RCC pedestal M.S channel fabrication work and flooring work a) Supply b) Installation

Set Set

1 1

Page 27: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

27

4.

Design, Supply, Installation, testing and commissioning of out door type, SS304 L.T. distribution panel as per CPRI and IP 65 shall comprising of the following: Both locations shall be positioned with necessary M.S channel fabrication work and flooring work (i) PANEL – I Incomer:1000A, 4P, 50 KA, ACB- 1 No. Outgoing: 800A, 4P, 50 KA, ACB:4 Nos. a) Supply b) Installation.

Set Set

1 1

(ii) PANEL – II: Incomer:800A, 4P, 50 KA, ACB : 1 No. Outgoing 250 A, 4P, 50 KA, MCCB: 6 No. a) Supply b) Installation.

set set

1 1

5. Supply of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable as per Technical specification of schedule ‘A’.

Mtr.

1,400

6. Laying of H.T. 11KV, 3 C X185 Sq.mm. XLPE U.G. Alu. cable as per Technical specification of schedule ‘A’ a) Through cable Trench b) Through Earth with RCC Troughs c)Through Concrete road / Tar road cutting through G.I. pipes

Mtr. Mtr. Mtr.

820 455 125

7. Supply and installation of Heat shrinkable Straight through joint kit for H.T. 11KV, 3X185 sq mm XLPE UG Aluminum Cables a) Supply b) Installation, testing and commissioning

No. No.

3 3

8. Supply and installation of Indoor type heat shrinkable End termination kit for H.T. 11KV, 3X185 Sq mm XLPE UG Aluminum Cables. a) Supply b) Installation, testing and commissioning

No. No.

2 2

9. Supply and laying of Single core 1000 Sq.mm. LT Aluminum XLPE cable from LT Panel ACB to LT panel including end terminations as per Technical specification of schedule ‘A’ a) Supply b) Laying

Mtr. Mtr.

50 50

Page 28: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

28

10 Supply of 3.5 core 185 Sq.mm. LT Aluminum XLPE cable including end terminations accessories as per Technical specification of schedule ‘A’.

Mtrs.

1500

11. Laying of 3.5 core 185 Sq.mm. LT Aluminum XLPE cable by clamping on wharf with equal intervals from Indoor LT panel to Panel - I and Panel – II including end terminations

Mtrs. 1500

12. Supply of 4 core 10 Sq.mm. LT Aluminum PVC cable from Indoor LT panel to outside light fittings as per Technical specification of schedule ‘A’

Mtrs. 500

13. Laying of 4 core 10 Sq.mm. LT Aluminum PVC cable by clamping on wharf with equal intervals from Indoor LT panel to outside light fittings including end terminations materials and accessories.

Mtrs. 500

14. Supply and installation of Battery charger unit including 2 Nos.12V, 2 Hrs. back up with suitable rating of Maintenance free Battery as per Technical specification of schedule ‘A’ a) Supply b) Installation, testing and commissioning

Set Set

1 1

15. Supply of following electrical materials and accessories as per IER (i) 11 KV grade rubber hand gloves (ii) First aid box (iii) Shock treatment chart and safety rules mounted on acrylic sheet with suspension clamp and front clear plastic sheet lamination (iv) Fire extinguisher- 1 No. and Fire bucket 4 Nos. with pedestal stand

Pair No. No. Set.

1 1 1 1

16 Supply and installation 10 Mtrs. street light post of 230V, 1 Ph 50 Hz, rating of suitable 2 Nos. LED Flood light fittings are equivalent to 2 x 400 W HPSV light fitting as per Technical specification of schedule ‘A’ a) Supply b) Installation, testing and commissioning

No. No.

4 4

Page 29: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

29

17 Supply and installation wall mounted light fittings at a height of 7 - 10 Mtrs. 230V, 1 Ph 50 Hz, rating of suitable LED Flood light fittings are equivalent to 400 W HPSV light fitting as per Technical specification of schedule ‘A’ a) Supply b) Installation, testing and commissioning

Nos. Nos.

6 6

18 Supply and installation of wall mounted water tight explosion proof RED colour light fittings at a height of 7 – 10 Mtrs. 230V, 1 Ph, 50 Hz, 100 W at various locations. a) Supply b) Installation, testing and commissioning

No. No.

3 3

19. Providing of Cast iron pipe earthing with Copper plate in accordance with BIS 3043 / BS 7430 or latest as per Technical specification of schedule ‘A’ a) Supply b) Installation, testing and commissioning

No. No.

4 4

20. Providing of maintenance free earthing with Copper plate in accordance with BIS 3043 / BS 7430 or latest as per Technical specification of schedule ‘A’ a) Supply b) Installation, testing and commissioning

No. No.

2 2

21. Supply and laying of 50mm x 6 mm G.I. flat for 2000 KVA, Package indoor Sub-Station and feeder pillar earths as per Technical specification of schedule ‘A’ a) Supply b) Installation, testing and commissioning

Mtr. Mtr.

300 300

22. Providing electrification work at compact substation room with suitable light fitting including all other accessories.

L.S. L.S

23 Charges for CEA approval L.S. L.S Total

Service Tax % Total Amount in Rs.

Firm’s Sign and Seal

Page 30: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

30

SPECIAL CONDITIONS OF CONTRACT SCHEDULE - `B'

1. The Tenderer shall examine carefully the General Rules and Directions, General

and Special Conditions of Contract, Technical Specifications and Drawing and Shall inspect the site to acquaint himself with the nature of work local working conditions etc., for the purpose of making his offer on his own responsibility.

2. It shall be open to the Chief Mechanical Engineer to nominate one or more of his representatives to supervise the work and to satisfy about the quality of materials and workmanship as required by the relevant regulation and as mentioned in technical specifications. The decision of the Chief Mechanical Engineer shall be final as regards the quality of materials and workmanship shall be binding on the contractor.

3. The prices shall be firm and not subject to fluctuation at any stage till the completion of the contract. The prices quoted must be filled in ink both in figures and words in the Schedule of prices attached with the Tender Document the prices quoted shall be inclusive off taxes, duties, freight, insurance, unloading etc. and any correction shall be supported by the Tenderer's signature there against.

4. The offers with specifications very near to those stated in the Technical Specifications may also be given consideration as alternate besides the main offer with full specification. The Tenderer shall give clear indication in his tender of the items he does not propose to include in the tender. Where such clear mention is not given it will be construed that the tender covers all parts required for completion of work.

5. The Tenderer shall quote separately for any items which have not been specifically mentioned in the specification but which are found necessary for completion, efficient installation and operation of electrification system other than those items which are not covered under 'works not included'.

6. The tender shall be accompanied by sufficient details of materials included in the offer with catalogue and sketches wherever if necessary for comprehensive assessment of its merits and performance

7. It will be entirely the Tenderer's responsibility to take required steps to adequately safeguard the personnel carrying out the work and to ensure that the work is carried out in such a manner that maximum safety to the personnel is assured.

8. All materials and components included in the contract shall conform to the relevant Indian Standard Specification wherever they exist.

Page 31: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

31

9. The decision of the Chief Mechanical Engineer or his representative regarding the quality of any materials used on the work will be final and binding on the Tenderer. The Tenderer shall remove from the site of work any material rejected as unfit for use on the work at his own cost as soon as he is ordered to do so, failing which the Chief Mechanical Engineer or his representative shall remove such material from the site of work and shall deduct the cost incurred by such removal by the Board from any money due to the Tenderer.

10. The Tenderer shall co-ordinate his work with that of other Tenderers executing other works in the site and plan his work as to minimise inconvenience to others in the work site.

11. The watch and ward and storage of materials will be Tenderer's responsibility and the Board shall not be held responsible for any loss of the material.

12. The Tenderer shall be deemed to have satisfied himself before submitting the tender as to the correctness and sufficiency of his tender for the work and of his price stated in the schedule as to cover his entire obligation under the contract for completion of the work.

13. For Harbour entry pass and direction to site of work for inspection for the purpose of making the offer, the Tenderer shall contact the “Dy.CME (ES&CH), 7th floor of the Centenary Building, Chennai Port Trust. Telephone Nos. 25362201 – Extn: 2707

CHIEF MECHANICAL ENGINEER

CHENNAI PORT TRUST

Page 32: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

32

GENERAL CONDITIONS OF CONTRACT SCHEDULE - `C'

1. DEFINITIONS AND INTERPRETATIONS In the contract (as hereinafter defined) the following words and expressions shall

have the meanings hereby assigned to them except where the context otherwise requires:

(a) "BOARD" means the Board of Trustees of the Port of Chennai as

constituted under the Major Port Trusts' Act, 1963 as amended from time to time.

(b) "CHIEF MECHANICAL ENGINEER' means the Chief Mechanical Engineer

of the Chennai Port Trust. (c) "CHIEF MECHANICAL ENGINEER'S REPRESENTATIVE" means any

Resident Engineer or Assistant of the Chief Mechanical Engineer or any clerk of works detailed from time to time by the Chief Mechanical Engineer to perform the duties as may be specified in the contract.

(d) "CONSTRUCTIONAL WORKS" means all appliances or things or

whatsoever nature required in or about the execution, completion or maintenance of the `Works' or `Temporary Works' (as hereinafter defined) but does not include materials or other things intended to form or forming part of the permanent work.

(e) "CONTRACT" means the General Conditions, Specifications, Drawings,

Priced Bill or Quantities. Schedule of Rates, Prices if any) tender and contract agreement.

(f) "CONTRACTOR" means the person or persons, firm or company whose

tender has been accepted by the Board and Tenderer's permitted assigns.

(g) "CONTRACT PRICE" means the sum named in the tender subject to such conditions thereto or deductions there from as may be made under provisions hereinafter contained.

(h) "DRAWINGS” means the drawings referred to in the contract agreement

and any modifications of such drawings approved in writing by the Chief Mechanical Engineer and such other drawings as may from to time be furnished or approved in writing by the Chief Mechanical Engineer.

Page 33: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

33

(i) "SITE" means the lands and other places on/under/in/of, through which the 'work ' are to be executed or carried out and any other lands or places provided by the Board for the purposes of the contract.

(j) "TEMPORARY WORKS" means temporary works of every kind required in

the execution, completion or maintenance of the works and which do not form an item of the `work' or `works'.

(k) "WORKS" means the works to be executed in accordance with the contract

under the relevant schedules. (l) "TRUST'S STORES" means the storage yards for materials of the Trust

anywhere in the Harbour premises. 2. EXTENT OF CONTRACT The contract comprises, the construction, completion and maintenance of the

'works' and the provision of all labour, materials constructional Generator, temporary works and every thing whether of a temporary or permanent nature required in and for such construction, completion and maintenance so for as the necessity for providing the same is specified in or reasonably to be inferred from the contract.

3. COMPLETION PERIOD

The entire work shall be completed with in 6 months from the 7th day of issue order.

a) In case of delay in the progress of work, the Chief Mechanical Engineer

shall issue to the Tenderer a memo in writing pointing out the delay in the progress and calling upon the Tenderer to explain the causes for the delay within three days of the receipt of the memo. If the Chief Mechanical Engineer is not satisfied with the explanation offered, he may forfeit the security deposit and/or withhold payment of pending bills in whole or in part. The Tenderer may appeal to the Chairman against the order of the Chief Mechanical Engineer forfeiting the Security Deposit and withholding of bills within a week of the said order and the decision of the Chairman shall be final and binding on the Tenderer.

b) If the security deposit or any part thereof is forfeited by an order of the

Chief Mechanical Engineer and such order become final, the Tenderer shall make good the security deposit or part of such deposit so forfeited within a fortnight thereafter or such further time as the Chief Mechanical Engineer may grant failing which the Chief Mechanical Engineer may determine the Contract.

Page 34: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

34

4. GUARANTEE PERIOD (a) The contractor shall ensure no damage to the any Trust Properties

during contract period. If any, the same shall be rectified and / or replaced at free of cost by the Tenderer.

(b) If during this twelve months guarantee period any defects are noticed,

which in the opinion of the Chief Mechanical Engineer are due to bad materials used and/or defective workmanship the Tenderer shall be required to carryout at the Tenderer's cost, such repairs, as the Chief Mechanical Engineer considers necessary or in the event of the Tenderer failing to do this within a notified time the Chief Mechanical Engineer may arrange for such repairs to be carried out and deduct the cost of such rectification of the defects from the amount retained, without prejudice to the recovery of any amount that may have been spent in excess of the deposit. For purposes, the period of 12 months shall count from the date of handing over of the completed part or whole of works by the Tenderer to the Chief Mechanical Engineer.

5. (a) The Chief Mechanical Engineer reserves to himself the right to cancel the

contract for unsatisfactory progress in the work at any stage. (b) CONTRACTOR'S SUPERINTENDENCE The Tenderer shall give or provide all necessary superintendence to the

complete satisfaction of the Chief Mechanical Engineer during the execution of the works and as long thereafter as the Chief Mechanical Engineer may consider necessary. The Tenderer or a competent and authorised agent or representative approved in writing by the Chief Mechanical Engineer which approval may at any time be withdrawn is to be constantly on the work and shall give his whole time to the superintendence of the same. Such authorised agent or representative shall receive on behalf of the Tenderer directions and instructions from the Chief Mechanical Engineer or (subject to the limitations of Clause 9 hereof) the Chief Mechanical Engineer's representative.

6. PROGRAMME TO BE FURNISHED As soon as practicable, after the acceptance of his tender, the Contractor shall, if

required, submit to the Chief Mechanical Engineer for his approval a detailed programme showing the order of procedure and method in which he proposes to carry out the works and shall whenever required by the Chief Mechanical Engineer furnish for his information particulars in writing of the Contractor's arrangements for carrying out the works and of the constructional plant and temporary works which the Contractor intends to supply, use or construct, as the

Page 35: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

35

case may be. Submission to and approval by the Chief Mechanical Engineer of such programme or furnishing of such particulars shall not relieve the Contractor of any of his duties or responsibilities under the contract.

7. If the progress of work is held up owing to circumstances which, in the opinion of

the Chief Mechanical Engineer are beyond the control of the Tenderer, such as war, stormy weather etc., the Chief Mechanical Engineer may at his discretion, grant to the Tenderer such extension of time as he considers reasonable for the completion of the works. The grant of such extension of time shall not bestow on them for any claim or compensation/extra payment at a future date whatsoever.

8. The materials used on the work must be of first class variety corresponding to

relevant ISS and other specifications laid in the contract. The work must be carried out in a workmanlike and expeditious manner and quality of work at each stage shall be subject to approval of the Chief Mechanical Engineer. The Chief Mechanical Engineer's decision as to the quality of such materials and work shall be final and binding on the Tenderer.

9. The Tenderer shall maintain at the site or work an Inspection Register, which

must be produced by the Tenderer or his agent whenever called upon to do so by the Chief Mechanical Engineer or his representative during their inspection of the work. If the rectifications ordered to be done are not carried out within the time specified by the Chief Mechanical Engineer, the Chief Mechanical Engineer shall have the right to get such work done by any other agency and to recover the cost thereof from the Tenderer. This inspection register shall be the duplicate copying type so that one copy of the entries get recorded in the Chief Mechanical Engineer's Office. The Tenderer shall not make any entry of any kind in this register.

10. CHIEF MECHANICAL ENGINEER’S REPRESENTATIVE The duties of the Chief Mechanical Engineer’s Representative are to watch and

supervise the works and to test and examine any materials to be used or workmanship employed in connection with the works. He shall have no authority to relieve the Contractor of any of his duties or obligations under the contract or except as expressively provided hereunder to order any work involving delay or any extra payment by the Board or to make any variation or of in the works.

11. WORK TO BE TO THE SATISFACTION OF THE CHIEF MECHANICAL

ENGINEER: The Tenderer shall execute, complete and maintain the works strictly in

accordance with the contract to the satisfaction of the Chief Mechanical Engineer and shall comply with and adhere strictly to the Chief Mechanical Engineer's instructions and directions on any matter (whether mentioned in the contract

Page 36: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

36

or not). The Tenderer shall take instructions and directions only from the Chief Mechanical Engineer or his representatives.

12. LIQUIDATED DAMAGES/LATE DELIVEY CHARGES: The Liquidated Damages/Late Delivery Charges shall be deducted from any

amount payable to or to be payable to the contractor/supplier including encashment of Bank Guarantee or any securities/guarantees, if any available with the Port Trust.

The maximum amount of Liquidated Damages/Late Delivery Charges shall be worked out based on the total contract/supply order value inclusive of all taxes and duties.

In case of part/portions of the contract work/supply order completed and taken possession by the Trust and the Trust operates/can be made for operation of the part portion/supply order, the calculation of Liquidated Damages will be restricted to the uncompleted/undelivered value of the work/supply order subject to the amount of the maximum percentage prescribed for the Liquidated Damages/Late Delivery Charges of the total value of the contract/supply.

The Liquidated Damages/Late Delivery Charges shall be ½% of the contract value per week or part thereof (a week is defined as 7 days inclusive of holidays) subject to a maximum of 10% of the contract value.

If the contract/supply order is delayed after giving due notice, the contract/supply order may be cancelled by the competent authority with the condition that any additional expenditure incurred by the Port Trust in completing the work/supply order will be recovered from the contractor/supplier of the cancelled contract/supply order for non-performance/delay in the execution of the contract/supply.

13. SUPPLY OF MATERIALS AND LABOUR

Except where otherwise specified in the contract the Tenderer shall at his own expense supply and provide all the temporary works, materials both for temporary and for works under the contract, labour (including the supervision thereof) transport to or from the site and in and about the works and other things of every kind required for the construction, completion and maintenance of the works. The Tenderer shall not hire out any item or equipment brought by him in connection with the execution of the work under the contract to any other party in connection with any work of the latter in the Port, without the written permission of the Chairman. Such permission may or may not be granted by the Chairman.

14. The Tenderer shall at his own cost make due arrangements for the proper watch

and safety of all materials and supplied to him by the Board for the use on this work. He shall not remove such constructional or materials from the site without

Page 37: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

37

the permission of the Chief Mechanical Engineer. If any of these materials are lost or damaged in any way due to negligence or carelessness on the part of the Tenderers or any of his employees, the cost for the materials lost or damaged and penalty for such negligence or carelessness of the Tenderer as determined by the Chief Mechanical Engineer shall be recovered from the Tenderer from any moneys due to him or to become due to him.

15. ASSIGNMENT AND SUB-LETTING The Tenderer shall not assign the contract or any part thereof or any benefit or

interest therein or there under without the written consent of the Board. The Tenderer shall not sublet the whole of the works. The Tenderer shall not sublet any part of the works without the written consent of the Board and such consent if given shall not relieve the Tenderer of any liability or obligation under the contract and he shall be responsible for the acts, defaults and neglects of any Sub-Tenderer and his agents, servants or workmen as if they were the acts, defaults, or neglects of the Tenderer, his agents, servants or workmen provided always that the provision of labour on a piece work basis shall not be deemed to be a subletting of assignment of benefit or interest under this clause.

16. The Tenderer shall be solely responsible for any accident, damage or injury

caused to any of his employees or the Board's employees in the execution of the works and shall hold the Board blameless in respect thereof and also in respect of any claims made by any person in the employment of the Tenderer for any reason whatsoever.

17. (a) The Tenderer shall be responsible for all structural or decorative damage

to Board's or his own property and injury caused by the works or workmen in his employment to persons, animals or things and shall indemnify the Board against any claims or actions arising there from. He shall also be responsible for any injuries or damage caused to the works by inclemency of weather outbreak of fire and shall rectify at his own cost all such damage and thoroughly complete the works.

(b) The Tenderer shall be solely responsible for reporting the Board and Police

Department immediately any serious or fatal accidents at any place belonging to the Board including premises leased to the Board to any of his employees/ workmen engaged by him.

18. The Tenderer shall not house any of his workmen at or near the site. He shall not

construct any structure even of a temporary nature for any other purpose on Board's premises except with the written permission of the Chief Mechanical Engineer and any such construction so put up shall be removed by the Tenderer whenever the Chief Mechanical Engineer calls upon the Tenderer to remove.

Page 38: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

38

19. The Tenderer shall not operate the workshop at the site for the purpose of this contract beyond what is absolutely necessary for the execution of this contract, the necessity for and extent of which the Chief Mechanical Engineer's decision shall be final. Such necessary structures shall be non-inflammable materials as approved by the Chief Mechanical Engineer.

Only vehicles licensed by the Board will be allowed inside the Harbour premises. 20. Measurements taken by the person authorised by the Chief Mechanical Engineer

to take them will be binding on the Tenderer who will always be given the opportunity of witnessing the measurements. The contractor should submit a bill in the Trust’s prescribed billing format.

21. PAYMENT TERMS:

(a) 70% payment will be made for the supply items on delivery at site in

good condition and acceptance of the same. (b) 20% payment will be made for the supply items against testing and

commissioning.

(c) Balance 10% payment for the supply items and 100% payment for all other Items will be paid after taken over.

Income tax @ 2% shall be levied U/S 194 (c) of Income Tax Act 1961. Similarly Tamil Nadu Value Added Tax as per Section 13 of T.N.VAT Act 2006 shall also be deducted. In case of exemption from the above levy necessary non-deduction certificate shall be produced by the tenderer from Income Tax / Commercial Tax office respectively.

The tenderer shall quote the Bank Account details for the payment through ECS along with PAN. A copies of the Pan Card, ESI regn No. and Service Tax Regn No. shall be furnished.

22. TAXES AND DUTIES All prices shall be firm inclusive of all taxes and duties. Any new and variation in Taxes & Duties shall be applicable only during the

scheduled completion period and new/variation in Taxes & Duties will not be allowed during the extended delivery/ completion period.

Any penal interest, penalty or fine payable / paid by the contractor to the Tax

Authorities on the Taxes & duties shall not be paid / reimbursed by the Trust under any circumstances.

Page 39: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

39

In the event, the Contractor not indicating the rate of Taxes and Duties included in the price separately in the Bid, the port shall not pay any change in the rate of Taxes and Duties including any newly levied Taxes and Duties during the entire currency of the contract under any circumstances.

23. In the event of the death, insanity or insolvency of the Tenderer or in the case of

the Tenderer being a partnership on a dissolution of the firm of Tenderer or in the case of the Tenderer being a company governed by Companies' Act 1956, the winding up of the company the contract shall be terminated on the happening of the event above said and all accepted and acceptable work shall be measured up and paid for, to the person or persons legally entitled to receive payment for work done and on his or their executing a bond indemnifying the Board against all claims that may be made in respect of payments made by the Board by persons claiming from the Tenderer or others, in respect of work done by the Tenderer prior to the termination of the contract.

24. In the event of the contract being terminated at any stage due to unsatisfactory

progress of work as per Tender Specification, the Chief Mechanical Engineer shall have the right to execute the portions of works left incomplete using the Board's labour or any other agency and the Tenderer shall be liable to make good any loss incurred by the Board on this account. Such amounts shall be recovered from any moneys due to or to become due to the Tenderer.

25. (i) If the Tenderer claims that the decisions or the instructions of the Chief

Mechanical Engineer are unjustified and that accordingly he is entitled to extra payments on account thereof, he shall forthwith notify this to the Chief Mechanical Engineer to record his decisions and the reasons therefore in writing and shall within two weeks state his claims in writing to the Chief Mechanical Engineer thereafter. The Chief Mechanical Engineer shall thereafter within four weeks of the receipt of the claim reply negotiations or discussions immediately thereafter within a further four weeks, the question of liability for such payments will be treated as one of disputes.

(ii) In the Contract whenever there is a discretion or exercise or will by the Chief Mechanical Engineer during the progress of work, the mode or manner of the exercise or discretion shall not be a matter of legal adjudication.

(iii) Wherever the Board is given discretion to do any act under the contract,

the exercise of the discretion by the Board shall be final, conclusive and binding on all parties and the manner of exercise of such discretion shall not be called in question and the matter cannot be referred to court of law.

(iv) The decision of the Chief Mechanical Engineer shall be final, conclusive

and binding on all parties to the contract upon all questions relating to the

Page 40: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

40

meaning of the specifications, designs, drawings and instructions and as to the quality of workmanship or material used on the work or any matter arising out of or relating to the specifications, designs and drawings and instructions concerning the works or the execution of or failure to execute the same arising during the course of works. The above shall not be the subject or Legal adjudication and in no case shall the work be stopped consequent on such a dispute arising and the work shall also be carried out by the Tenderer strictly in accordance with the instructions of the Chief Mechanical Engineer.

(v) Any litigation arising out of this agreement, shall only be adjudicated before

the competent court of law within the jurisdiction of the Hon’ble High Court of Madras.

26. REMOVAL OF WORKMEN The Tenderer shall employ in and about the execution of the works only such

persons as are careful, skilled and experience, in their several trades and callings to the approval of the Chief Mechanical Engineer. The Chief Mechanical Engineer shall be at liberty to object to and require the Tenderer to remove from the works any persons employed by the Tenderer in or about the execution of the works who in the opinion of the Chief Mechanical Engineer, misconducts himself or incompetent or negligent in the proper performance of his duties and such persons shall not be again employed upon the works without the written permission of the Chief Mechanical Engineer.

27. (i) The Tenderer shall confirm to and comply with the regulations and byelaws

of the State or Central Government or of the Board and of all other local authorities such as Corporation of Madras, the Tamil Nadu Electricity System, the Chief Electrical Inspector to the Government of Tamil Nadu, the Government Customs and Police Departments, Fire Services, the provisions contained in the various Labour Acts enacted by the State Legislature and Central Parliament in force and the rules made thereunder including those under Minimum Wages Act, Factories Act, the Indian Electricity Act and rules framed under it, Workmen Compensation Act, Provident Fund Regulations Act, Employees Provident Fund Act, 1961 and scheme made under the said Act, Health and Sanitary arrangements for workers etc. and Contract Labour (Regulation and Abolition) Act, 1970 and the Contract (Regulation and Abolition) Central Rules, 1971 etc. for welfare and protection of works, workers or for the safety of the public and other insurance provisions.

(ii) The Board shall not be liable for the failure of the contractor in confirming

to the provision of the Acts, Rules and regulations etc., referred to in the above para and in case of any contravention of the provisions of the

Page 41: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

41

Acts, Rules regulations etc. the contractor shall keep the Board indemnified against any loss, cost and damage in the event of any action being taken for contravention.

(iii) If any enhancement in the rates of wages becomes payable as a result of

the implementation of the Chief Labour Commissioner's interpretation of the Contract Labour (Regulation and Abolition) Central Rules, 1971 upto and including an increase of 10% of the wages shall be borne by the Tenderer and enhancement in excess of 10% would be borne by the Port Trust.

(iv) ESI CLAUSE:

The details of employees proposed to be engaged shall be furnished to this office before the commencement of the work.

(a) As per the Govt. Notification dated 20.07.2009, Chennai Port Trust has registered under the ESI Act on 26.09.2012 with ESI Corporation and provision of ESI Act, 1948 are applicable to Chennai Port Trust, a Social Security Act, is applicable to Factories using power and employing 10 or more personnel and establishment employing 20 or more persons and drawing wages/salary upto Rs.15,000/- per month. Workers covered under ESI Act, are entitled for full medical care for self and family. Besides, cash benefit in the event of sickness, maternity and employment injury. Accordingly, the contractual/casual employees drawing wages upto Rs.15,000/- per month employed either directly by Port Trust or through contractor are covered under ESI Act, 1948. It is obligatory on the part of the employer to calculate and remit ESI contribution comprising of employers’ share of 4.75% plus employees’ share of 1.75% which is payable on or before 21st of the following month, to which the salary relates.

(b) In case of Contractor employs more than 20 employees, they should register their name with ESI as per ESI Act, 1948 and obtain ESI Code. Both Employers share of 4.75% and Employees contribution of 1.75% (recovered from employees), totally 6.5% to be paid as contribution to ESI in their Code on or before 21st of following month to which the salary relates and acknowledgement for the same shall be submitted to the Port while claiming the bill. The bill without the acknowledgment of ESI contribution will not be entertained. In case the contractor has not paid the ESI contribution same will be recovered in the running bill and paid to the ESI Corporation in contractor’s code. The delay in payment of contribution payable under the Act may be recovered as an arrear of Land Revenue.

(c) In case the contractor employs less than 20 employees, the list of employees’ names, their father’s name, identification proof, one passport photo shall be submitted to the Port Trust. The contribution of ESI amount, both Employers

Page 42: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

42

share of 4.75% and Employees contribution of 1.75% (recovered from Employees salary), totally 6.5% shall be paid by the Contractor in the Chennai Port Trust Code on or before 21st of the following month to which the salary relates or otherwise payment to the contractor will be withheld. If the contractor fails to comply with the above instruction, then the Principal Employer (Chennai Port Trust) will make payment to the ESI Corporation. Such amount will be deducted from any amount due to the contractor. The delay in payment of contribution payable under the Act may be recovered as an arrear of Land Revenue.

(d) As per the above government Notification i) All intending tenderer at the time of Tender shall disclose all necessary documents as to whether they are covered under ESI Act or not.

ii) In case they are covered under ESI Act, they have to furnish the details of registration.

iii) In case the tenderer does not possess ESI Registration at the time of participation in the Tender, then they should obtain registration under ESI Regulations before award of the work by Chennai Port Trust and submit the same within 30 days from the date of issue of work order. Any payment towards the work order will be made only after the ESI registration.

iv) The Tenderer shall submit his first bill together with evidence of having obtained registration under ESI regulations and only then the bill will be processed for payment. Subsequently, the Tenderer should periodically submit to Chennai Port the Form 6 prescribed under ESI Regulations along with the proof for having remitted his dues under ESI Regulations in respect of the workers / labours employed for the work awarded by Chennai Port to facilitate making payment for the bills of the Contractor. v) In case, the Tenderer is not covered under ESI Act or exempted, they would furnish necessary documents along with an affidavit in original affirming before a first class Judicial Magistrate in a Non Judicial Stamp Paper worth Rs.20.00 to that effect. vi) In case they are not covered under ESI Act, they must additionally indemnify ChPT against all damages & accident occurring to his labour in a Non – Judicial Stamp paper worth Rs.100/-.

(v) Insurance

The Tenderer advised to take necessary insurance at his cost for his employees, materials and machineries etc.

28. Foreclosure of Contract: I. Not withstanding anything in the contract agreement the contractor agrees that

the Trust (on its won or acting on behalf of the Government of India) or the

Page 43: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

43

Government of India shall be entitles to foreclose the contract on occurrence of the following events:

i. In the event of breach of contract by the Contractor ii. An emergency or

iii. for national security and /or national interest and /or public reasons.

II. Upon the occurrence of the events specified in the above I (i),(ii) and (iii) above the Trust or Government of India reserve the right to fore close the contract at any point of time during the contract period on the issue of the termination notice under provision of the termination clause , the Trust shall not be liable to compensate the contractor or any other person for any losses or estimated loss of profits during such period.

29. The Chief Mechanical Engineer reserves to himself the right to alter the

specification or design of the works at any stage of the work and also to make additions or omissions or alterations.

30. Further Instructions The Chief Mechanical Engineer shall have full power and authority to supply to

the Contractor from time to time during the progress of the works such instructions as necessary for the purpose of the proper and adequate execution and maintenance of the works and the Contractor shall carry out and be bound by the same.

31. Any notice to the Tenderer shall be deemed to be sufficiently served if given or

left in writing at his usual or last known place of abode or business or at site. 32. All payments made by the Board to the Tenderer under this contract shall be

rounded off to the nearest paise. 33. (i) The contract is liable for cancellation if either the Tenderer himself or any

of his employee is found to be a person who has held a Class I post under the Board immediately before retirement and has, within two years of such retirements, accepted without obtaining the previous permission of the Board of the Chairman as the case may be an employment as Tenderer for, or in connection with the execution of public works, as an employee of such Tenderer.

(ii) If any contract is terminated on account of the failure of the Tenderer to comply with the above clause the Board shall be entitled to recover from him such damages as may be determined by the Chief Mechanical Engineer with due regard to the inconvenience caused to the Trust on account of such termination without prejudice to the Trust's right to proceed against such officer.

Page 44: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

44

34. It must be clearly understood that the rates mentioned in Schedule `A1' are

inclusive of everything required to be done by the conditions of the contract and specifications or by the drawings therein referred to and also all such work as is necessary for the proper completion of the Tenderer although special mention thereof may have been omitted in the specification or drawings.

35. In these conditions unless there is something in this subject or context

inconsistent therewith words importing the singular shall include the plural and vice versa words importing the masculine gender shall include feminine and words importing persons shall include bodies corporate.

36. The technical specification – “Schedule-A” and Price Schedule – A1” to be read in

conjunction to make sure of the supply and works involved. 37. The contractor is required to offer rates as per Trust’s format “Schedule- A1”

without fail and mention taxes and duties.

38. Necessary paid entry passes to be obtained by the contractor at their own cost. 39. The contractor is advised to visit the site if required. 40. The Trust will not be responsible for any loss or damage of Men/materials/plants engaged during the work. 41. The Contractor shall arrange their own tools and plants and other materials and

components required for the above work. 42. All transport required for the work shall be arranged by the contractor at their own

cost. 43. TERMINATION: a) The employer, without prejudice to any other remedy for breach of contract,

by written notice of default sent to the contractor, may terminate the contract.

i) If the contractor fails to deliver any or all of the Goods with in the period specified in the contract, or with in any extension thereof granted by the Employer.

ii) If the contractor fails to perform any other obligation under the contract (or)

iii) If the contractor, in the judgement of the Employer has engaged in fraud and corruption.

Page 45: MEE/ GC2 / 963 / 2008 / Dy.CME(ES&CH) BUDGETARY … And... · Chennai Port Trust is proposed to install 11KV / 433V Compact substation at ... VCB Panel with Trivector meter, ... Enclosure

45

b) In the event the Employer terminates the Contract in whole or in part, the Employer may procure, upon such terms and in such manner as it deems appropriate, goods or related services similar to those undelivered or not performed, and the contractor shall be liable to the Employer for any additional cost for such similar goods or related services. However, the contractor shall continue performance of the contract to the extent not terminate. In such terminations Security deposit will be forfeited.

44. VARIATION:

Variation means variation in quantities of items ie. Where there is increase of quantities of items of work in the agreement. On other words, the nomenclature of work remains the same, but the quantity of variation is maximum 30 % against the Tender cost shown in the agreement. The said variation shall be executed after approval of the competent authority.

CHIEF MECHANICAL ENGINEER CHENNAI PORT TRUST