13
Medical Purificatory Modular Air Handling Unit T: 1800 953 260 W: www.altituderefrigeration.com.au Postal Address: PO Box 384, Kellyville, NSW, 2155, Sydney, Australia PO Box 678, Oxenford, QLD, 4210, Gold Coast, Australia

Medical Purifactory Modular Air Handling Unit

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Medical Purifactory Modular Air Handling Unit

Medical Purificatory Modular Air Handling Unit

T: 1800 953 260W: www.altituderefrigeration.com.auPostal Address:PO Box 384, Kellyville, NSW, 2155, Sydney, AustraliaPO Box 678, Oxenford, QLD, 4210, Gold Coast, Australia

Page 2: Medical Purifactory Modular Air Handling Unit

02

1

2

1067 A R -2 X B AA

250 B R -2 X B AA

02

02

04

07

08

09

12

13

15

16

18

19

20

21

23

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

Product Summary

Product Feature

Model Instruction

Air Volume Table

Cooling Performance Parameters

Hot Water Coil Performance

Direct Expansion Specification

Isothermal & Isohumidity Unit

Direct Expansion External Unit

Function Section

Compound Mode

Length and Weight

Installation

Wiring Diagram

The new type medical purificatory modular air handling units is for the special requirements of the operation room, related medical treatment, medicament and foodstuff. It has many advantage such aslow air leakage rate, high mechanical strength; the sterilization effect is good and also can inhibit bacteria propagation and breeding and so on. The medical purificatory air handling unit can be divided into 2 series: water coiler combined air handling unit and direct expansion combine air handling unit.

Direct Expansion Type Outdoor Unit

Detailed specification

Power type

Different model code

Refrigerant (2-R407C; Omitted is R22)

Function code (R-heat pump; omitted is chiller)Design version

Model code

Detailed specification

Power type

Different model code

Refrigerant (2-R407C; Omitted is R22)

Function code (R-heat pump; omitted is chiller)

Design version

Model code

Note: The unit Under 25KW has no R407c type.

QWCA

QWSA

Air cooled scroll outdoor unit

Air cooled screw outdoor unit

Use and maitenance

CONTENTPRODUCT OVERVIEW

MODEL SPECIFICATION

Page 3: Medical Purifactory Modular Air Handling Unit

0403

ENERGY EFFICIENT1

PURIFICATION APPLICATION2

3

21 18 D H -- -Y 05 L 2

21 18 D R - -H YX 080 L D

Heating type: D-electric Z-steam

Connected direction: L-left R-rightUnit No.Medical purificatory (direct expansion)type

Structure :H-horizontal type; V-vertical type; C-ceiling typeFunction :H-Isothermal& Isohumidity; R-heat pump; omitted is chillerDesign No.

Height modular

Width modular

Heating coil rows

Connected direction: L-left R-right

Cooling coil rows

Medical purificatory (water coil) type

Structure :H-horizontal type; V-vertical type; C-ceiling type

Design No.

Height modular

Width modular

According to the special requirements of medical clean room, the medical purificatory air handlingunit applies the special configuration for its air regulating system and the equipment.

Patent tenon double column cabinet design

Super strengthThe panel and profile come into column after forming, the panels apply tenon structure +bolt connection, it can bear large pulling force and shear force, the intern of the panels are PU forming, the forming density is above 50kg/m3, it ensure the panel have enough strength.

Low air leakageThe panel apply 45°section connection, through multi-tenon and seals and O rings with bolts connecting, making sure the unit has the lower air leakage. In the national air leakage test report, the air leakage rate is 0.16%

No cold bridge designThe panels design is tenon double column structure + insulating rubber, making the internal wallboard is totally isolated from the external metals. The panel apply high density PU forming, eliminating cold bridge. In the national cold bridge factors, heat transfer coefficient text report, the cold bridge meet TB2, heat transfer coefficient meet T2.

Antimicrobial Type Heat ExchangerThe heat exchanger fins apply hydrophilic aluminum foil or copper fins, it has no spray on the fins, avoiding splash, preventing bacterial growth. Kingair can supply you fan coil for different kinds(different pitches of fins, varies fins structure, copper diameters, and etc.) we will try our best to meet your requirements.

The Bare Pipe HeaterThe heater pipes apply stainless steel, smooth surface, no fins, preventing dust and bacteria.

QWZS

Combined air handling unitQWZE-25mm thicknessQWZS-35mm thicknessQWZW-50mm thickness

Combined air handling unitQWZE-25mm thicknessQWZS-35mm thicknessQWZW-50mm thickness

QWZS

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

PRODUCTFEATURES

Page 4: Medical Purifactory Modular Air Handling Unit

0605

INTELLIGENT DESIGN

3

STABLE AND RELIABLE

4

3

Direct drive frequency conversion voluteless fanThe fan applies frequency conversion voluteless fan, high transmission efficiency, no belt wear pollution, stable operation, this kinds of fan is easy to maintenance, especially for the clean room. The fan can meet the big air volume,high static pressure requirements.

Steam HumidifierThe unit applies electrode or dry steam clean humidify, avoid the water humidify bringing the humid environment, preventing bacterium.

High Quality Filter1, the unit can choose different filters for clients’ requirements, making performance optimization.2, filter’s structure design, high collection efficiency. High dust holding capacity, it is easy to clean and change.3, plate type and bag type filter can be put in the same frame, reducing the case length. 4, The filter frame can install different factories, zinc plated and coating making the frame has high corrosion

resistance; sheet metal parts are perfect, no burrs; filters are fixed by bolts, goods air tightness.

Sterilization And Disinfection1, Inner wallboard, condenser pan, coiler apply stainless steel material, heat exchanger applies aluminum foil

and copper fins, preventing bacterial.2, Tilting stainless steel water pan ensure that there is no water in the unit, no bacteria growth.3, The unit can have UV sterilizer, photocatalyst, ozonizer, achieving sterilization and disinfection,

improving the air quality.4, The unit can have the electronic air cleaner, apply electrostatic dust removal technology, thoroughly to

eliminate the breeding spread of bacteria and zymad, also eliminate the cross infection.

UV Sterilizer Photocatalyst Ozonizer

Reasonable DesignFront fan ensure the inner of the unit case is positive pressure; preventing air leaking affect the cleanliness, the condensing water is discharged by the unit positive pressure, front filter protects heat exchanger having no dust, preventing bacteria.

Intelligent Design

Reliability

Professional Selection Software

1,Professional selection software2,Simply operation interface3,Supply multiple choices according to the clients' requirements;4,Automatically output the performance parameters according to requirements5,Ensure the parts list, calculating the unit price6,Output the outline drawing, design chart and technology instruction

Double-stage vibration isolation design1, Spring shock absorber, littler vibration, low noise.2, Flexible soft connection, no vibration transfer

Production passed the performance test.

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

PRODUCTFEATURES

Spring shock absorber

Flexible soft connection

Harmful Compound

Organic Compound

Page 5: Medical Purifactory Modular Air Handling Unit

0807

5

0606

0906

0908

0909

1209

1409

1511

1512

1812

1914

1515

2114

2018

2415

1919

2121

2419

2719

2521

2624

2722

3022

2525

2824

3027

3325

3427

3628

4230

4530

4830

4533

4833

4536

4836

5136

5436

5736

6036

6636

(m3/h)

1563

2720

3920

4275

6161

8047

8961

11704

14448

17191

15362

18962

24000

26163

24963

27935

32393

36850

35079

38622

43937

49252

45606

49606

55607

67768

74369

87118

94851

113006

120927

126459

135323

142603

152599

162594

172590

182585

192581

208000

5.3

13

21

21

32

43

47

62

77

93

75

94

115

136

133

153

178

195

192

212

234

262

239

262

297

332

367

430

468

563

605

630

645

689

731

793

857

917

980

1058

11.7

22

33

34

51

70

76

100

127

150

133

167

200

234

220

247

290

332

310

345

395

428

408

429

482

539

594

698

767

915

986

1030

1107

1163

1254

1317

1398

1490

1601

1729

14.9

30

45

48

70

95

104

138

171

204

182

226

270

310

297

334

384

440

411

457

518

573

538

590

665

730

794

928

1005

1213

1306

1360

1462

1535

1665

1783

1922

2059

2188

2363

18.6

36

53

56

83

111

122

160

198

233

210

261

308

359

344

383

444

509

481

530

612

676

626

684

764

849

921

1079

1181

1412

1510

1574

1685

1774

1926

2079

2207

2357

2518

2720

4

11

16

18

26

35

38

50

64

76

60

77

94

111

112

125

146

168

157

175

200

215

205

216

242

268

299

350

382

460

499

523

559

593

632

682

696

748

800

864

9.4

17

27

27

43

57

62

82

104

123

109

136

163

193

181

203

237

273

257

286

322

367

337

369

415

444

487

570

623

750

807

848

908

959

1035

1120

1206

1291

1316

1422

11.9

25

38

39

59

79

86

115

143

168

150

186

221

261

246

279

324

364

350

381

435

487

450

492

551

616

673

792

854

1029

1082

1148

1234

1296

1404

1494

1599

1709

1828

1975

15.1

29

43

47

69

92

102

133

166

197

176

218

257

300

288

319

372

424

401

442

508

567

528

572

639

709

781

909

992

1175

1259

1321

1416

1491

1603

1731

1860

1987

2116

2285

kW kW kW kW kW kW kW kW

4

(m3/h)

0606

0906

0908

0909

1209

1409

1511

1512

1812

1914

1515

2114

2018

2415

2121

2119

2419

2719

2521

2624

2722

3022

2525

2824

3027

3325

3427

3628

4230

4530

4830

4533

4833

4536

4836

5136

5436

5736

6036

6636

1563

2720

3920

4275

6161

8047

8961

11704

14448

17191

15362

18962

22563

26163

24963

27935

32393

36850

35079

38622

43937

49252

45606

49606

55607

67768

74369

87118

94851

113006

120927

126459

135323

142603

152599

162594

172590

182585

192581

208000

7.8

14

22

23

36

49

47

64

81

96

83

107

125

143

140

163

177

207

200

216

241

264

264

280

308

368

407

473

518

587

634

549

593

615

664

712

761

810

859

943

17.8

30

49

49

81

114

105

147

189

224

192

248

290

331

324

381

409

481

466

502

558

608

613

649

710

851

944

1095

1204

1336

1448

1196

1297

1338

1449

1562

1674

1787

1899

2100

kW kW kW kW kW kW kW kW kW kW kW kW

10.2

18

27

30

45

60

58

84

95

110

96

133

146

173

161

198

206

243

239

262

282

338

313

332

364

448

496

577

633

767

825

859

923

964

1036

1108

1181

1253

1326

1447

25

41

64

69

106

142

138

192

224

259

222

309

339

400

373

463

475

564

556

607

653

778

727

769

840

1078

1195

1389

1525

1855

1995

2075

2232

2327

2504

2680

2857

3033

3211

3508

11.5

20

29

33

48

63

62

93

101

121

107

142

157

186

177

213

222

265

257

283

307

371

340

363

399

503

556

648

710

859

922

961

1032

1079

1160

1240

1321

1401

1482

1614

28.7

46

68

77

112

150

147

213

239

285

247

330

364

430

410

498

513

615

599

657

710

853

792

840

921

1225

1355

1578

1730

2094

2250

2343

2518

2632

2828

3025

3222

3418

3615

3939

5.7

11

16

17

25

33

36

47

59

71

63

77

93

102

100

115

130

150

142

157

170

195

186

201

210

272

385

443

384

466

502

522

562

585

630

674

719

764

808

859

7.3

14

22

23

35

47

48

65

83

101

90

108

132

150

144

164

184

210

199

222

244

282

264

285

305

376

420

487

538

658

711

737

796

825

891

958

1025

1092

1159

1213

7.3

13

20

22

31

39

44

55

72

85

73

94

105

120

124

145

166

165

170

195

217

236

225

246

280

346

381

444

486

576

603

645

675

705

758

812

865

919

972

1061

10.7

19

29

32

47

58

61

82

107

123

107

141

160

182

187

220

239

261

260

296

327

362

337

371

410

525

581

676

741

876

907

980

1015

1054

1138

1221

1305

1388

1472

1615

8.3

15

21

24

33

44

44

61

79

90

80

104

120

135

133

154

175

196

192

209

236

257

246

260

290

381

420

490

535

620

666

693

746

780

838

897

956

1014

1074

1169

13

21

33

37

52

70

71

95

122

140

120

158

184

215

210

240

272

304

300

330

376

426

389

426

466

600

663

772

845

965

1041

1080

1165

1212

1307

1402

1497

1591

1686

1843

Model Rated Air flow

Fresh air working condition Return air working condition

4 Rows 6 Rows 8 Rows 4 Rows 6 Rows 8 RowsSensible Total Sensible Total SensibleTotalSensibleTotalSensible TotalSensibleTotal

Note: 1, Chilled water inlet/ outlet temperature: 7°C/12°C2, Return air inlet DB temperature 27°C, WB temperature 19°C; Fresh air inlet DB temperature 35°C, WB temperature 28°C.3, All the above is for your reference, if the working condition has changed, the capacity will change too, please contact with Kingair for details.4, No further inform if there are some products change.5, Sensible means sensible cooling capacity; Total means total cooling capacity.

Model Rated Air flow

Fresh air working condition Return air working condition1 Row 2 Rows 3 Rows 4 Rows 1 Row 2 Rows 3 Rows 4 Rows

Total TotalTotal Total TotalTotal Total Total

Note:1, Hot water inlet /outlet temperature 60/50°C;2,Return air working condition DB temperature 15°C; fresh air working condition DB temperature 7°C.3, All the above is for your reference, if the working condition is changed, the heating capacity will change, please contact with Kingair for details.4, No further inform if there are some products change.

QWZE/QWZS/QWZWQWZE/QWZS/QWZW

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

VARIABLE COEFFICIENT

PERFORMANCE PARAMETER T

Page 6: Medical Purifactory Modular Air Handling Unit

09 10

YX-050 YX-050

1

50

-

17.6

-

480

kW

kW

m3/h

mm

mm

mm

kW

kW

kg

mm

mm

mm

mm(in)

mm(in)

10000

1550

1230

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

15000

1850

1330

1558

882

1170

2*12.7(1/2)

2*22.22(7/8)

380V/3N~/50Hz

R22

12000

1550

1330

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

1

50

56

17.6

16.5

492

YX-062

1

62

-

19.8

-

532

YX-076

2

74

-

11.6

-

305

YX-076

2

74

82

11.6

11.2

315

YX-062

1

62

68

19.8

18.6

544

YX-102 YX-102

2

102

-

17.6

-

480

kW

kW

m3/h

mm

mm

mm

kW

kW

kg

mm

mm

mm

mm(in)

mm(in)

20000

2150

1530

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

30000

2170

2270

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

380V/3N~/50Hz

R22

24000

2050

1930

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

2

102

110

17.6

16.5

492

YX-125

2

125

-

19.8

-

532

YX-152

3

152

-

17.6

-

480

YX-152

3

152

160

17.6

16.5

492

YX-125

2

125

128

19.8

18.6

544

6YX-012 YX-012

1

12

-

4.25

-

120

kW

kW

m3/h

mm

mm

mm

kW

kW

kg

mm

mm

mm

mm(in)

mm(in)

2500

950

730

940

400

1243

9.52(3/8)

19.05(3/4)

4200

950

930

1403

821

980

2*12.7(1/2)

2*19.05(3/4)

380V/3N~/50Hz

R22

3000

950

730

940

400

1243

9.52(3/8)

19.05(3/4)

1

12

13

4.25

3.85

120

YX-014

1

14

-

4.9

-

120

YX-019

1

19

-

6.96

-

215

YX-019

1

19

21

6.96

6.4

223

YX-014

1

14

16

4.9

4.55

120

YX-026 YX-026

1

26.5

-

8.5

-

232

kW

kW

m3/h

mm

mm

mm

kW

kW

kg

mm

mm

mm

mm(in)

mm(in)

5000

950

1030

1403

821

980

2*12.7(1/2)

2*19.05(3/4)

7500

1450

1030

1558

882

1170

2*12.7(1/2)

2*22.22(7/8)

380V/3N~/50Hz

R22

6500

1250

1030

1558

882

1170

2*12.7(1/2)

2*19.05(3/4)

1

26.5

28

8.5

7.8

240

YX-030

1

30

-

10.2

-

252

YX-039

1

37

-

11.6

-

305

YX-039

1

37

41

11.6

11.2

315

YX-030

1

30

34

10.2

10

260

Model

Indoor unit

Outdoor unitName

Quantity

Model

Indoor unit

Outdoor unitName

Quantity

Model

Indoor unit

Outdoor unitName

Quantity

Model

Indoor unit

Outdoor unitName

Quantity

Rated cooling capacity

Rated heating capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow

WidthHeight

Length

Compressor

Cooling power inputHeating power input

Weight

Size

Width

DeepHeight

PipeLiquid

Steam

Rated cooling capacity

Rated heating capacity

Power

Refrigerant

Indoor unitO

utdoor unit

Size

Airflow

Width

HeightLength

Compressor

Cooling power input

Heating power inputWeight

SizeWidthDeep

Height

Pipe Liquid

Steam

Rated cooling capacity

Rated heating capacity

Power

Refrigerant

Indoor unitO

utdoor unit

Size

Airflow Width

HeightLength

Compressor Cooling power inputHeating power input

Weight

SizeWidth

DeepHeight

PipeLiquid

Steam

Rated cooling capacity

Rated heating capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow Width

Height

Length

Compressor Cooling power input

Heating power input

Weight

SizeWidthDeep

Height

Pipe LiquidSteam

Based on the functional sections

scroll*1 scroll*2

Based on the functional sections

scroll*1 scroll*2

Based on the functional sections scroll*2

Based on the functional sections

scroll*3scroll*2

QWZE0906D- QWZE0906DR- QWZE0906D- QWZE0906DR- QWZE0908D- QWZE0908DR-

QWSA050BX QWSA050BRX QWSA060BX QWSA060BRX QWSA075BX QWSA075BRX

QWZE0909D- QWZE0909DR- QWZE1209D- QWZE1209DR- QWZE1409D- QWZE1409DR-

QWSA100BX QWSA100BRX QWSA125BX QWSA125BRX QWSA150BX QWSA150BRX

QWZE1511D- QWZE1511DR- QWZE1512D- QWZE1512DR- QWZE1812D- QWZE1812DR-

QWSA200BX QWSA200BRX QWSA250BX QWSA250BRX QWSA150BM QWSA150BRM

QWZE2114D- QWZE2114DR- QWZE2018D- QWZE2018DR- QWZE2121D- QWZE2121DR-

QWSA200BM QWSA200BRM QWSA250BM QWSA250BRXM QWSA200BM QWSA200BRM

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

DIRECT EXPANSION SPECIFICATIONS

Page 7: Medical Purifactory Modular Air Handling Unit

11 12

6 7YX-029

1

25.2

16

8

5000

950

1030

8.5

232

1403

821

980

2*12.7(1/2)

2*19.05(3/4)

YX-029

1

29

20

10

6500

1250

1030

10.2

252

1558

882

1170

2*12.7(1/2)

2*19.05(3/4)

YX-048

1

48

28

18

10000

1550

1230

17.6

480

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

YX-059

1

59

32

22

12000

1550

1330

19.8

532

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

YX-037

1

35.5

24

13

380V/3N~/50Hz

R22

7500

1450

1030

11.6

305

1558

882

1170

2*12.7(1/2)

2*22.22(7/8)

kW

kW

kg/h

m3/h

mm

mm

mm

kW

kg

mm

mm

mm

mm(in)

mm(in)

YX-073

2

71

38

25

15000

1850

1330

11.6

305

1558

882

1170

2*12.7(1/2)

2*22.22(7/8)

YX-097

2

97

50

35

20000

2150

1530

17.6

480

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

YX-146

3

146

75

54

30000

2170

2270

17.6

480

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

YX-176

1

176

100

60

37500

2570

2270

62.1

2050

2340

2232

2270

28.6(1-1/8)

53.97(2-1/8)

YX-120

2

120

65

43

380V/3N~/50Hz

R22

24000

2050

1930

19.8

532

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

kW

kW

kg/h

m3/h

mm

mm

mm

kW

kg

mm

mm

mm

mm(in)

mm(in)

YX-186 YX-186

3

186

-

19.8

-

532

kW

kW

m3/h

mm

mm

mm

kW

kW

kg

mm

mm

mm

mm(in)

mm(in)

37500

2570

2270

1808

1090

1190

2*15.88(5/8)

2*28.6(1-1/8)

50000

2870

2570

3100

2232

2370

34.9(1-3/8)

79.4(3-1/8)

380V/3N~/50Hz

R22

40000

2770

2270

2940

2232

2370

28.6(1-1/8)

66.68(2-5/8)

3

186

192

19.8

18.6

544

YX-235

1

235

-

75.3

-

2580

YX-076

1

272

-

82.8

-

2780

YX-076

1

272

315

82.8

75.2

2850

YX-235

1

235

273

75.3

68.5

2650

YX-325 YX-325

1

325

-

105.7

-

3570

kW

kW

m3/h

mm

mm

mm

kW

kW

kg

mm

mm

mm

mm(in)

mm(in)

60000

3100

2900

4040

2232

2500

34.9(1-3/8)

79.4(3-1/8)

80000

3600

3200

4040

2232

2880

41.3(1-5/8)

92(3-5/8)

380V/3N~/50Hz

R22

70000

3500

2900

4040

2232

2500

34.9(1-3/8)

79.4(3-1/8)

1

325

375

105.7

97

3650

YX-372

1

372

-

118

-

3660

YX-451

1

451

-

139.9

-

4100

YX-451

1

451

520

139.9

127.5

4200

YX-372

1

372

430

118

108.2

3740

Model

Indoor unit

Outdoor unitName

Quantity

Model

Indoor unit

Outdoor unitName

Quantity

Model

Indoor unit

Outdoor unitName

Quantity

Model

Indoor unit

Outdoor unitName

QuantityRated cooling capacityRated heating capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow WidthHeightLength

Compressor Cooling power input

Heating power inputWeight

SizeWidthDeep

Height

Pipe LiquidSteam

Rated cooling capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow

WidthHeightLength

Compressor Cooling power input

Weight

Size

WidthDeep

Height

Pipe Liquid

Steam

Rated cooling capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow

Width

Height

LengthCompressor

Cooling power inputWeight

SizeWidthDeep

Height

PipeLiquid

Steam

Rated cooling capacityRated heating capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow

WidthHeightLength

Compressor Cooling power inputHeating power input

Weight

SizeWidthDeepHeight

PipeLiquidSteam

Electrical heater

Electrical heater

Humidify

Humidify

Based on the functional sections

scroll*2

Based on the functional sections

Based on the functional sections

scroll*2

Based on the functional sections

scroll*2scroll*2scroll*2

scroll*2scroll*2

Semi-hermetical screw *1

Semi-hermetical screw *1

Semi-hermetical screw *1

Note:1, Rated cooling capacity is based on room DB/WB temp. 27/19°C; and environment temp DB 35°C.2 , Rated heating capacity is based on room DB temp. 20°C and environment DB/WB temperature 7/6°C.3, Rated cooling capacity doesn’t consider the fan motor heating lose, the ESP can make based on the custom requirements.4, There is no further information if there is some improvements.

QWSA250BM QWSA250BRM QWCA1067AX QWCA1067ARX QWCA1078AX QWCA1078ARX

QWZS2521D- QWZS2521DR- QWZS2721D- QWZS2721DR- QWZS2824D- QWZS2824DR-

QWCA1093AX QWCA1093ARX QWCA1108AX QWCA1108ARX QWCA1130AX QWCA1130ARX

QWZW3027D- QWZW3027DR- QWZW3427D- QWZW3427DR- QWZW3530D- QWZW3530DR-

QWZE0909D- QWZE1209D- QWZE1409D- QWZE1511D- QWZE1512D-

QWSA100BX QWSA125BX QWSA150BX QWSA200BX QWSA250BX

QWZE1812D- QWZE2114D- QWZE2018D- QWZE2121D- QWZE2521D-

QWSA150BX QWSA200BX QWSA250BX QWSA200BX QWCA1050AX

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

DIRECT EXPANSION SPECIFICATIONS

STANDARD SPECIFICATION FOR DIRECT EXPANSION TYPE CONSTANT TEMPERATURE AND HUMIDITY UNIT

Page 8: Medical Purifactory Modular Air Handling Unit

1413

A

1403

1403

1558

1558

1808

1808

B

746

746

808

808

1018

1018

C

980

980

1170

1170

1190

1190

D

781

781

842

842

1050

1050

E

821

821

882

882

1090

1090

F

770

810

880

880

750p*2=1500

750p*2=1500

N

4

4

4

4

6

6

1050A(R)X

1067A(R)X

1078A(R)X

1093A(R)X

1108A(R)X

1130A(R)X

A

2235

2235

2235

2235

2235

2235

B

2100

2100

2100

2100

2100

2100

B

2430

2430

2430

3435

3435

4400

D

900p×2=1800

900p×2=1800

900p×3=2700

900p×3=2700

900p×3=2700

1100p×3=3300

H

2400

2400

2400

2400

2400

2400

M

280

210

260

520

520

520

N

6

6

8

8

8

8

N-φ18

H

A

B M

C

D

WIND TURBINE SAFETY CONDITIONS

18~32℃

18~45℃

10~30℃

-10~25℃

8

YX-225

1

225

120

65

40000

2770

2270

75.3

2580

2940

2232

2370

28.6(1-1/8)

66.68(2-5/8)

YX-258

1

258

140

80

50000

2870

2570

82.8

2780

3100

2232

2370

34.9(1-3/8)

79.4(3-1/8)

YX-355

1

355

180

100

70000

3500

2900

118

3660

4040

2232

2500

34.9(1-3/8)

79.4(3-1/8)

YX-430

1

430

220

120

80000

3600

3200

139.9

4100

4040

2232

2880

41.3(1-5/8)

92(3-5/8)

YX-310

1

310

160

90

380V/3N~/50Hz

R22

60000

3100

2900

105.7

3570

4040

2232

2500

34.9(1-3/8)

79.4(3-1/8)

kW

kW

kg/h

m3/h

mm

mm

mm

kW

kg

mm

mm

mm

mm(in)

mm(in)

A

B

C

D

E

QWSA050B(R)X/QWSA060B(R)X

940

350

1243

590

380

7

Model

Indoor unit

Outdoor unitName

Quantity

Rated cooling capacity

PowerRefrigerant

Indoor unitO

utdoor unit

Size

Airflow Width

Height

Length

Compressor

Cooling power inputWeight

SizeWidthDeep

Height

Pipe Liquid

Steam

Electrical heater

Humidify

Based on the functional sections

Semi-hermetical screw *1

Note:1, Rated cooling capacity is based on room DB/WB temp. 23/17°C; and environment temp DB 35°C.2, Rated cooling capacity doesn't consider the fan motor heating lose, the ESP can make based on the custom requirements.3, There is no further information if there is some improvements.

Cooling Heating

Return air temperature

Environment temperature

Note: 1, If the working condition is out of the above working condition, the protection device will be started.2, The unit not included in the above, it will be non-standard design unit.

QWZS2721D- QWZS2824D- QWZW3027D- QWZW3427D- QWZW3530D-

QWCA1067AX QWCA1078AX QWCA1093AX QWCA1108AX QWCA1130AX

QWSA050B(R)X/QWSA060B(R)X

SizeQWCA

QWCA1050/1067/1078/1093/1108/1130A(R)X

QWSA075/100/125/150/200/250B(R)X/150/200/250B(R)M

Model

QWSA075B(R)X

QWSA100B(R)X

QWSA125B(R)X

QWSA150B(R)X/B(R)M

QWSA200B(R)X/B(R)M

QWSA250B(R)X/B(R)M

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

OUTDOOR MACHINE APPEARANCE

STANDARD SPECIFICATION FOR DIRECT EXPANSION TYPE CONSTANT TEMPERATURE AND HUMIDITY UNIT

DIRECT EXPANSION

Page 9: Medical Purifactory Modular Air Handling Unit

1615

9

10●

检 检 检 3

3

3

检 检 检 检 检 检

检 检 检 检 检

The medical purificatory modular air handling unit can supply you different air handling functional sections, such as mixed section, draught distribution section, filter section, primary cold /heating section, spray section, muffler section, humidifier section, fan section, electric heating section, rotary heat recovery section, UV germicidal section, current sharing section, ozone generating section, maintenance section and so on, the user choose the suitable ones according to their needs, we will do that for every customers, supply the best unit for controlling the temperature, humidity and cleanness.

Mixed section Draught distribution section Filter section Primary cold /heating section Spray section

Muffler section Humidifier section Fan section Electric heating sectionRotary heat recovery section

UV germicidal section Ozone generating section Maintenance sectionCurrent sharing section

The combination for hospital operation room

(mixed + primary + fan + cooling coil + inspection + heating + humidifier + medium/ UV germicidal + air outlet/Ozone )The unit has not only the primary and medium filter, also has the UV germicidal lamps which can kill the bacteria, set the Ozone generator at the air outlet section, it can improve the air quality.

Mixed Primary filter Fan Cooling coil Inspection Heating

Humidifier Inspection Medium filter Air outlet

(air inlet + return fan +exhaust air + fresh air + primary filer + supply fan +pre-cooling + heating +humidifier +inspection + medium filter/ UV germicidal + air outlet)The return fan and supply fan are working together, through distribution to exhaust air, the air handling volume is big, and purification and filter level are higher.

Pharmaceutical industry clean room 1

Pharmaceutical industry clean room 2(air inlet + return fan +exhaust air + fresh air + primary filer + supply fan +pre-cooling + heating +inspection + medium filter/ UV germicidal + air outlet)The unit has cooling, heating, no need humidifier, suitable for the place where doesn’t need humidifier.

Air inlet Return fanExhaust air Fresh air

Primary filter Supply fan Pre-coolingHeating

Humidifier InspectionMedium filter Supply air

Air inlet Return fanExhaust air Fresh air

Primary filter Supply fan Pre-coolingHeating

InspectionMedium filter Supply air

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

SCHEMATIC DIAGRAM OF FUNCTIONAL SECTION

COMMON FUNCTIONCOMBINATION

Page 10: Medical Purifactory Modular Air Handling Unit

1817

10●

检 检 检 检 检

检 检 检

11

0606

0906

1206

0909

1209

1509

1212

1512

1812

2112

1515

1815

2115

2415

1919

2119

2419

2719

2222

2422

2722

3022

2525

2725

3025

3325

3625

3628

3928

4530

4830

4533

4833

4536

4836

5136

5436

5736

6036

6636

4

6

8

9

12

14

15

18

21

25

23

27

31

35

35

38

43

50

47

51

57

63

59

65

72

79

86

95

104

122

135

133

147

144

159

171

181

191

200

220

300

25

31

33

38

40

43

48

50

52

55

57

60

62

64

70

72

74

76

80

81

84

86

89

91

93

95

98

105

107

117

119

124

126

131

134

136

138

141

143

158

600

38

49

53

58

62

66

71

75

78

82

84

88

91

95

101

103

107

111

114

116

120

124

127

129

133

137

141

150

154

168

172

177

181

186

190

194

198

202

206

227

900

52

66

72

77

83

88

93

99

1050

110

110

115

121

127

132

135

141

147

148

152

157

163

164

168

174

179

185

196

201

220

225

230

236

241

247

252

258

264

269

296

1200

72

84

91

96

104

111

116

123

131

138

136

143

151

158

162

167

174

182

182

187

194

201

202

206

214

221

228

241

248

271

278

283

291

296

303

310

318

325

332

365

5

7

9

10

13

15

16

19

23

26

23

27

32

36

36

39

44

49

46

50

56

62

59

63

69

76

82

91

99

120

128

132

140

143

152

161

170

179

188

207

6

8

10

10

13

16

17

20

24

27

24

29

33

37

37

40

45

51

48

52

58

63

60

65

71

78

84

94

101

123

131

134

143

146

155

164

173

182

191

210

300

32

34

37

42

45

48

53

56

59

61

64

67

69

72

78

80

83

86

89

91

94

97

100

102

105

108

110

118

121

132

135

140

143

148

151

154

157

160

163

180

600

47

55

60

65

70

75

81

86

91

96

96

101

106

112

117

120

125

131

132

136

141

146

148

151

156

161

167

177

182

199

205

210

215

220

225

230

236

241

246

271

900

62

76

83

88

96

103

108

116

123

131

128

136

143

151

155

160

168

175

175

180

188

195

195

200

208

215

223

235

243

266

274

279

286

292

299

307

314

322

329

362

1200

86

97

106

111

121

131

136

146

156

166

161

171

180

190

194

200

210

220

218

225

235

245

243

250

259

269

279

294

304

333

343

348

358

363

373

383

393

402

412

453

300

27

31

34

39

41

44

49

51

53

56

58

61

63

66

72

73

76

78

81

83

85

88

91

93

95

98

100

107

110

120

122

127

129

134

137

139

142

144

146

161

600

40

50

54

59

63

67

72

76

81

85

86

90

94

98

104

106

111

115

117

120

124

128

130

133

137

142

146

155

159

174

178

183

187

192

196

200

205

209

213

234

900

55

68

74

79

85

91

96

102

108

114

113

119

125

131

136

140

146

152

153

157

163

168

170

174

180

185

191

202

208

228

234

239

245

250

256

262

268

274

280

308

1200

76

87

94

99

107

115

120

128

136

144

141

149

156

164

168

174

181

189

189

194

202

210

210

215

223

231

239

251

259

283

291

296

304

309

317

325

333

340

348

383

ModelCase thickness 25mm Case thickness 35mm Case thickness 55mm

Empty section weight(kgs)

End panel End panel End panel

Pharmaceutical industry clean room 3

(fresh air + primary filer + pre-cooling + inspection + rotary dehumidifier + air return + supply fan + cooling coil + heating + inspection +medium filter + air outlet)The unit has cooling, heating, and dehumidifier, suitable for the place where need dehumidifier.

The combination with heat recovery(Upper: Return air + primary filter + rotary + exhaust air)(Bottom: fresh air +primary filter +rotary + inspection +supply fan + cooling +heating + humidifier +supply air)The unit has heat recovery device, exchange the exhaust air heat with the fresh air, use the exhaust energy to achieve energy saving.

Return airPrimary filter

Rotary Exhaust fan

Supply airHumidifier

HeatingCooling

Supply fan Inspection

RotaryPrimary filter

Fresh air

Return air Supply airHeatingCooling Supply fan

InspectionPrimary filterFresh air Pre-cooling

Rotary dehumidifier

Regeneration fan

Inspection

Regeneration air filtering and heating

Medium filter

QWZE/QWZS/QWZW

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

COMMON FUNCTIONCOMBINATION

EACH FUNCTIONAL SECTIONLENGTH OF WEIGHT

Page 11: Medical Purifactory Modular Air Handling Unit

2019

12

0606

0906

0908

0909

1209

1409

1511

1512

1812

1914

1515

2114

2018

2415

1919

2121

2419

2719

2521

2624

2722

3022

2525

2824

3027

3325

3427

3628

4230

4530

4830

4533

4833

4536

4836

5136

5436

5736

6036

6636

1.60

1000

1741

2509

2736

3943

5150

5735

7490

9246

11002

9832

12136

14440

16745

15976

17878

20731

23584

22450

24718

28120

31521

29188

31748

35589

39429

43270

50687

55186

65749

70358

73576

78734

82969

88785

94600

100416

106231

112047

121020

2.00

1250

2176

3136

3420

4929

6437

7169

9363

11558

13753

12290

15170

18050

20931

19970

22348

25914

29480

28063

30898

35150

39401

36485

39685

44486

49286

54087

63359

68982

82186

87947

91970

98417

103711

110981

118250

125520

132789

140059

151300

2.25

1406

2448

3528

3847

5545

7242

8065

10534

13003

15472

13826

17066

20307

23547

22467

25141

29153

33165

31571

34760

39543

44327

41045

44646

50046

55447

60848

71279

77605

92460

98940

103467

110719

116675

124853

133031

141210

149388

157566

170200

2.50

1563

2720

3920

4275

6161

8047

8961

11704

14448

17191

15362

18962

22563

26163

24963

27935

32393

36850

35079

38622

43937

49252

45606

49606

55607

61608

67608

79198

86228

102733

109934

114963

123021

129639

138726

147813

156900

165986

175073

189090

2.75

1719

2992

4313

4702

6777

8851

9857

12875

15892

18910

16898

20859

24819

28780

27459

30728

35632

40535

38587

42484

48331

54177

50166

54567

61168

67768

74369

87118

94851

113006

120927

126459

135323

142603

152599

162594

172590

182585

192581

208000

2.85

1781

3101

4469

4873

7023

9173

10216

13343

16470

19597

17513

21617

25722

29826

28458

31846

36928

42009

39990

44029

50088

56147

51990

56551

63392

70233

77074

90286

98300

117115

125324

131058

140244

147789

158148

168507

178866

189225

199548

215560

3.00

1875

3264

4705

5130

7393

9656

10753

14045

17337

20629

18434

22755

27075

31396

29956

33522

38871

44220

42094

46346

52754

59102

54727

59527

66728

73929

81130

95038

103474

123279

131920

137956

147625

155567

166471

177375

188280

199184

210088

227000

3.50

2188

3808

5489

5985

8625

11265

12546

16386

20227

24067

21507

26547

31588

36629

34948

39109

45350

54590

49110

54071

61512

68953

63848

69449

77850

86251

94652

110878

120719

143826

153907

160948

172230

181495

194216

206938

219659

232381

245103

265000

4.00

2500

4353

6273

6840

9857

12875

14338

18727

23116

27505

24579

30340

36101

41861

39941

44696

51828

58961

56126

61795

70299

78803

72969

79370

88971

98572

108174

126718

137965

164373

175894

183941

196834

207422

221961

236500

251039

265578

280117

300000

(m/s)

13●●

●●

●●

W+1

00

L+100

Hmm

:H ≥150mm

≥15

0mm 80

~10

0mm

Ensuing the air handling unit is installed on the horizontal position.There should be keeping enough space (suggestion not less than 1m)around the unit, especially for the piping and the maintenance.Condensed water outlet should be set water seal(like the picture), then connected to the external piping.Please make the pipes correctly according to the indication, even effort on the pipes when connection,do not make effort to large, ensuing the internal structure of the unit is not damaged.The standard power of the unit is 3 phase 4 wires, 380V, 50Hz, AC, before power on, please check whether the voltage is meet the requirements or not, whether it has the phase lacking, and etc, after power on, start motor first, check the fan has the right direction of rotation.The motor of the unit should be connected to the power which has the overload protector.The connection between the unit and air ducts and water pipes should use soften connection, in order to avoid vibration.

ModelAir speed Air flow (m3/h)

Unit foundation diagram

L—unit length W—unit width

Waterway

Foundation

Flow drain

A-A Enlargement

Water seal diagram

Unit

Basement

Foundation

Drainage pipe

Suggestion:

Waterway

Flow drain

QWZE/QWZS/QWZW

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

UNITAIR FLOW

UNITINSTALLATION

Page 12: Medical Purifactory Modular Air Handling Unit

21 22

VARIABLE FREQUENCY STARTING CABINET FOR ELECTRIC HEATER2

KM

L3

L3

FH

TB L1 L2

L1 L2

E

QF1

N

QF

FH

KA1

FU SB1SB2 KA1

N

SA1

Y1 Y2

1 5 6

QF2

HL1

N

9

WVU

15

13

12

11

3~

321

WVU

TSR

TSR

VFD-F

+10V

ACM

KA1

DCM

FWD

FAN

14AVI

RC1

RA1

5Kohm

17

2

KA2 KA2

KA2

KA2RC2

RA218

2

X1 X2

F1 F2

KA4

F3 F4

KA5

Y1 Y2X1 X2

2 4

KA2

KA3

KA317 HL2RA1 RC1

KA4

18 HL3RA2 RC2

KA5

KA4

SA2

KT1

KT2

KT1

KT2

KM

SA2

110℃70℃TH

20

22 23

19

KA4 26KA5 25

21

3 -380V-50Hz

14

FREQUENCY CONVERSION STARTING CABINET1

L3

L3

FH

TB L1 L2

L1 L2

EN

QF

KA1

FU SB1 SB2KA1

HL1

N

WVU

15

13

12

11

3~

321

WVU

TSR

TSR

VFD-F

+10V

ACM

KA1

DCM

FWD

FAN

14 AVI

RC1

RA1

5Kohm

17

1

1

5 6 9

KA2 KA2

KA2

KA2RC2

RA218

1

Y1 Y2

F1 F2

KA4

F3 F4

KA5

X1 X2

17

Y1 Y2

HL2

X1 X2

RA1 RC1

KA4

18

HL3RA2 RC2

KA5

KA2

KA3

KA3

SA1

3 -380V-50HZ

Instruction : dotted line------client connection

DF—low pressure breaker SB1—stop button SB2—start button FU—fuse protector VFD—F Delta fan pump special frequency converter KA—intermediate relay HL1—power indicator HL2—operation indicator HL3—fault indicator SA—switch FAN- fan motor

User

Remote frequency signal

LocalStop Remote

0-10V signalRemote start signal

Fan operation signalFan fault signal

Distribution box earth connection

Instruction: Dotted line------client connection

DF—low pressure breaker VFD—F Delta fan pump special frequency converter SB1—stop button SB2—start button FU—fuse protector FH—fire damper KM—electrical heater connector KT2—power off time delay relay KT2—power on time delay relay KA—intermediate relay HL1—power indicator HL2—operation indicator HL3—fault indicator SA—switch FAN- fan motor

Generally power on time delay set 30 seconds, power off time delay set at least 180 seconds.

Electric heater is finished into unit frame before delivery, the internal line has been connected,and keeping the power connector, please connect to the power according to the signal, please refer to the wiring drawing as below:

User

Remote frequency signal

Local Stop Remote

0-10V signalRemote start signal

Fan operation signalFan fault signal

Distribution box earth connection

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

ELECTRICALWIRING

Page 13: Medical Purifactory Modular Air Handling Unit

14

23 24

15●●●●●

Before each operation, please check all the valves of the water pipes and air ducts, making sure that they are in the operation state;

Please make the regular checking for the fan, motor and any other moving parts, making the adjustment in time;

The clean of the primary filter according to the degree of the dirty, the clean frequency is according to the environment;

Medium efficiency filter should be cleaned and changed when the resistance it two times as primary resistance;

The cold water and hot water is softened water, please clean the scale in the coiler and the fins every two year.

If the unit is not in use in winter, please let the water in the coiler out; if the unit is in use in winter, please keep the coiler water flowing,

shut down the fresh air valve when stop the unit preventing the coiler is frost damage. Let the water out when stop the unit for long time.

For the details please refer to the USERS' OPERATION MANUAL

Warning:Electric heater protector should connected into the return part of the fan and electric heater control circle, can not be short circuit.After the fan is in regular operation, then start the electric heater. If stop the unit, before stop the fan, shut down the electric heater for 3 minutes. When design the control part, the dehumidifier and any other wiring, please in accords with the wiring drawing with the unit.Please note: the dehumidifier should be linked with the fan, after the fan start, then it can be start, shut down it first then stop the fan.If there are motor damper in regular state when the fan is in operation.

Warning:

All the electrical equipment should be safety earthing connected according to the signal, can not be used zero as the eathing connection. If there are some mistakes, it will cause bomb, fire and other accident.

MEDICAL PURIFICATORY MODULAR AIR HANDLING UNIT

ELECTRICAL WIRING

USE AND MAINTENANCE