550720 Revision F
Liquid-Level TransmitterModel M-SeriesAnalog Output
Operation and Installation
l
L e v e l P l u s ®
TABLE OF CONTENTSSection Page
Notices used in this book iiiRelated publications iiiHow this book is organized iiiGetting information, help, and service iv
1.0 INTRODUCTION 12.0 PRODUCT DESCRIPTION 2
2.1 Level Plus M-Series transmitter specifications 32.2 Accuracy 42.3 Theory of operation 42.4 Enclosure options for a Level Plus M-Series transmitter 5
3.0 INSTALLATION AND MOUNTING 63.1 Rigid and flexible transmitter mounting options 6
3.1a Threaded-flange mounting 63.1b Welded-flange mounting 7
3.2 Sanitary transmitter mounting 83.3 Installing a flexible sensor pipe with a bottom-fixing weight or magnet 83.4 Installing a flexible sensor element 9
4.0 ELECTRICAL CONNECTIONS AND WIRING PROCEDURES 124.1 Agency controlled drawing references, M-Series Analog 13
4.1a Installation drawing, M-Series transmitter with explosionproof enclosure, part no. 650805 (revision D) sheet 1 of 2. 13
4.1b Installation drawing, M-Series transmitter with explosionproof enclosure, part no. 650805 (revision D) sheet 2 of 2. 14
4.2 Electrical conduit installation 154.3 Cable specifications 164.4 Safety guidelines for the M-Series transmitter 174.5 Safety barriers for IS installation 17
5.0 SYSTEM CHECK 185.1 Performing a loop #1 test 185.2 Performing a loop #2 test (if applicable) 18
6.0 FLOATS 187.0 MAINTENANCE 19
7.1 Replacing an M-Series electronic module (puck) or interconnect board 197.1a Replacing an M-Series electronics module (puck) 197.1b Replacing the interconnect board 20
8.0 USING THE KEYPAD DISPLAY TO CALIBRATE THE LEVEL PLUS M-SERIES 20TRANSMITTER8.1 Modes of operation 208.2 LCD display and keypad (optional) 228.3 Alarm settings 238.4 Manual calibration 23
9.0 USING THE HART COMMUNICATION PROTOCOL TO CALIBRATE THE M-SERIES TRANSMITTER 249.1 Preparing the transmitter for re-calibration 249.2 Setting the low value 259.3 Setting the high value 25
10.0 INSTALLING AND USING THE M-SERIES FIELD SETUP SOFTWARE V1.01 (CD-ROM) T0 SETUP PARAMETERS AND ADJUST CALIBRATION 2610.1 Installing the M-series Field Setup software v1.0 2610.2 Calibration and setup parameters 2710.3 Instrument parameters 27
ii
Notices used in this book
This book contains notices to highlight specific information as follows:
Notes
These notices provide important tips, guidance, or advice.
Important
These notices provide information that might help you avoid inconvenient or problem situations.
Attention
These notices indicate possible damage to programs, devices, or data. An attention notice is placed justbefore the instruction or situation in which damage could occur.
Caution
These notices indicate situations that can be potentially hazardous to you. A Caution notice is placed justbefore a description of a potentially hazardous procedure, step, or situation.
Related publications
The following publications are available in Adobe Acrobat Portable Document Format (PDF) athttp://www.mtssensors.com.
550731 Installation sheet, M-Series Electronics Module550677 Product Specification, Level Plus M-Series Analog550537 Product Specification, Level Plus M-Series Floats and Accessories
For information about safe work procedures, refer to the following documentation:National Electric Code ANSI/NFPA 70
How this book is organized
1.0 “Introduction”, on page 1 provides an overview of the Level Plus M-Series transmitter and its features.
2.0 “Product Description”, on page 2 gives an overall product description for the Level Plus liquid level sensor, its specifications, use output, and electronics.
3.0 “Installation and Mounting” on page 6 provides detailed installation and mounting information.
4.0 “Electrical Connections and Wiring Procedures” on page 12 provides Engineering specifications and wiring diagrams to assist in the installation process.
5.0 “System Check” on page 18 provides information about testing Loop 1 and Loop 2.
6.0 “Floats” on page 18 provides guidelines for selecting the appropriate float for your application.
7.0 “Maintenance” on page 19 provides the procedures required for replacing the M-Series electronic module or electronic transmitter?
8.0 “Using the Keypad Display to Calibrate the Level Plus M-Series Transmitter” on page 21 describes modes of operation, LCD display functionality, alarm settings and how to calibrate the unit manually.
9.0 “Using the HART Communication Protocol to Calibrate the M-Series Transmitter” on page 24 provides procedures for recalibration and setting low and high values.
10.0“Installing and Using the M-Series Field Setup Software v1.01 (CD-ROM) to Setup Parameters and Adjust Calibration“ on page 26 provides software installation, parameter setup, and calibration procedures.
iii
iv
Getting information, help, and service
Ordering information and software updates
You can get the latest ordering information and software updates by using the World Wide Web. Go towww.mtssensors.com.
For information relating to HART® Communication Foundation , go to www.hartcomm.org.
HART Communication Foundation (USA)9390 Research Blvd., Suite I-350Austin TX 78759
Fax: 512.794.3904Phone: 512.794.0369
Contact information
Fax: 800.943.1145919.677.2545
Phone: 800.457.6620919.678.2769
Email: [email protected]
Shipping address
MTS Systems CorporationSensors Division3001 Sheldon DriveCary, North Carolina 27513
Office hoursMonday - Friday: 8:00 a.m. to 5:00 p.m. EST
1.0 INTRODUCTION
MTS is recognized as the pioneer, innovator and leader in magnetostrictive sensing. The Level Plus® M-Seriestransmitter design represents a continuation of our on-going effort to provide effective, innovative and reliableproducts to the liquid-level marketplace.
Throughout this document, the following “short names” are used:
• Level Plus M-Series Transmitter is referred to as M-Series transmitter or transmitter• Transmitter electronics interconnect board is referred to as interconnect board.• HART hand-held converter is referred to as HART converter• Electronics module is referred to as puck• Housing is referred to as enclosure• Bottom-fixing weight, magnet or hook is referred to as retaining hardware
Go to www.mtssensors.com for:
• Current Level Plus M-Series model numbers.
• Detailed ordering information.
• Ordering online using our interactive application worksheets.
• Downloading Software updates.
1
2.0 PRODUCT DESCRIPTION
The Level Plus M-Series transmitter is multi-functional with two 4-20 mA loops that utilize HighwayAddressable Remote Transducer (HART) communications. It provides up to two analog outputs of level, inter-face, or temperature. An optional electronics module displays simultaneous readouts of level, interface, or tem-perature. The optional electronics module is designed with three push buttons for local setup of all parameters.Outputs can be monitored using 4-20 mA signal output, when you use a RS-232 to HART Hand-Held Converterwith an optional integral display or MTS PC-compatible M-Series Field Setup software.
Level Plus M-Series transmitters can be housed in three types of enclosure configurations: • NEMA 4X electropolished• Stainless steel with I.S. approval• Single cavity or dual-cavity explosionproof enclosure with epoxy-powder coating.
The outer pipe is constructed of a variety of configurations (Contact factory for other materials):• 5/8 in. diameter rigid outer pipe of 316L stainless steel • 5/8 in. diameter rigid outer pipe of polished 316L stainless steel with sanitary process connection
and end-plug.• 7/8 in. diameter flexible pipe of 316L stainless steel
M-Series transmitters utilize a special sensor element which allows easy removal or replacement while the tank orvessel is in service, leaving the tank connection or seal intact. This design allows the sensor element to beinstalled or removed in situations where there is a low overhead clearance.
A temperature sensing function is optional with the M-Series transmitter. The temperature sensing device is aResistive Temperature Device (RTD) mounted inside the transmitter’s outer tube assembly. The RTD is a 1000ohm platinum film device.
2
3
2.1 Level Plus M-Series transmitter specifications
P A R A M E T E R S P E C I F I C A T I O N
LEVEL OUTPUTMeasured variable: Product level and interface levelOutput: 4-20 mA, 2 loops with HART interfaceFull range: Flexible gauges: 120 to 480 in. (3050 to 11890 mm)
Rigid gauges: 20 in. to 300 in (508 mm to 7620 mm)vt
Notes: Rigid sensor pipes have a rigid sensor element. Flexible sensor pipes have a flexible sensor element. Flexible sensor elements are available for rigid pipe configuration as an option.
Non-linearity: Flexible gauges: 0.035% F.S. (independent BSL) or 1/32 in. (0.794 mm)HRigid gauges: 0.020% F.S. (independent BSL) or 1/32 in. (0.794 mm)H
Repeatability: Flexible gauges: Up to 0.01% F.S. or 0.015 in. (0.381 mm)HRigid gauges: Up to 0.005% F.S. or 0.005 in. or (0.127 mm)H
Sensor operating temperature: -40 to 257 oF (-40 to 125 oC) (Consult factory for higher temperature applications.)GAUGE LOOPInput voltage range: 10.5 to 36.1 VdcReverse polarity protection: Series diodeTransient protection: Stage 1: Line-to-ground surge suppressors; 2500 Amps peak (8/20 µsec)
Stage 2: Line-to-line and line-to-ground transient suppressors; 1500 Watts peak (10/1000 µsec)CALIBRATIONZero adjust range: Anywhere within the active lengthSpan adjust range: Full scale ≥ 0.5 ft. (152 mm) from zeroTEMPERATURE OUTPUTType: 4-20 mA from 1,000 ohm platinum RTD at 0 oCRepeatability: ±0.18 oF (0.1 oC)Accuracy: ±2.7 oF (±1.5 oC)Drift: ±0.9 oF (0.5 oC) per yearZero adjust: -40 to 255 oF (-40.to 124 oC)Span adjust: 45 oF (7.2 oC) minimum, full scale (maximum) = 300 oF (149 oC)ENVIRONMENTALHumidity: 0 to 100% R.H., non-condensingElectronics operating temperature: -30 to 160 oF (-34 to 71 oC)Vessel pressure: Dependent on float pressure rating, refer to MTS document part number 550537 for more information.s
Materials (wetted parts): 316L stainless steel lFIELD INSTALLATION:Length (including housing): 20 in to 40 ft. (508 to 12,192 mm)vt
Mounting: 3/4 in. NPT adjustable fitting (rigid pipe) 1 in. NPT adjustable fitting (flex pipe)
Wiring: 2-wire connection, shielded cable or twisted pair to screw terminals through a 3/4 in. NPT conduit opening. NEMA 4X:15 ft. (457 cm) pigtail integral cable or Daniel Woodhead (part number 70807SS) 6-pole Male 1/4 in.-18
MNPT key-way receptacle.DISPLAY (Optional)Measured variables: Level 1, Level 2 and temperature.Update rate: 3 secondSize: 0.5 in. (12.7 mm)Number of digits: 16HART communicationsMethod of communication: Frequency Shift Keying (FSK) conforms with Bell 202 Modem Standard with respect to baud rate and digital “1” and “0”
frequencies.Baud rate: 1200 bps.Digital “0” frequency: 2200 Hz.Digital “1” frequency: 1200 Hz.Data-byte structure: 1 Start bit, 8 data bits, 1 odd parity bit, and 1 stop bitDigital process variable rate: Poll/Response Midel 2.0 per second
4
2.2 Accuracy
The absolute accuracy of the transmitter is a function of the manufacture of the waveguide. That is, any imper-fections in the waveguide are reflected in the linearity of its output. MTS tolerances reflect a maximum non-lin-earity of 0.035% of full scale. Due to its high degree of repeatability, the differential accuracy is extremely high.
2.3 Theory of operation
The magnetostrictive Level Plus M-Series transmitter will pre-cisely sense the position of an external float by applying an inter-rogation pulse to a waveguide medium. This current pulse causesa magnetic field to instantly surround the waveguide. The mag-net installed within the float also creates a magnetic field. Wherethe magnetic fields from the waveguide and float intersect, arotational force is created (waveguide twist). This, in turn, cre-ates a torsional-sonic pulse that travels along the waveguide asshown in Figure 2-1 “Principal of magnetostriction”.
The head of the sensing element houses the sensing circuit,which detects the torsional-sonic pulse and converts it to an elec-trical pulse. The distance from a reference point to the float isdetermined by measuring the time interval between the initiatingcurrent pulse and the return pulse and precisely knowing thespeed of these pulses. The time interval is converted into a 4-20mA loop signal.
The Level Plus M-Series transmitter offers level, interface, ortemperature outputs. There are two current loops available; anyoutput may be assigned to either of the two loops.
Float(moves as level changes)
Waveguide
Outer pipe
Float magnets
Magnetic fieldfrom float magnets
Waveguide twist(at intersection ofmagnetic field)
Magnetic field frominterrogation pulse
Figure 2-1Principle of magnetostriction
P A R A M E T E R S P E C I F I C A T I O N
AGENCY/SAFETY Approval: FM/CSA: Explosion-proof FM/CSA: Intrinsically Safe Class I, Groups B,C,D Class I, Groups A,B,C,DClass II, Groups E,F,G Class II, Groups E,F,GDivision 1, NEMA 4X Division I, NEMA 4XModels: Explosion-proof housing req. Models: All
H Whichever is greaterHHMust specify at time of order, not on all unitstContact factory for longer lengths. l Contact factory for other materialss Contact factory for higher pressure ratings.v Flexible sensor elements are available for rigid pipe configurations as an option.All Specifications are subject to change. Please contact MTS for specifications critical to your needs.
5
2.4 Enclosure options fora Level Plus M-Series transmitter
There are three M-Series transmitter enclosure options: NEMA 4X, single-cavity and dual-cavity enclosure. TheNEMA 4X enclosure is constructed of 316L stainless steel. The single and dual-cavity enclosures are ratedNEMA 7 explosionproof. Enclosure dimensions are shown in Figure 2-2a, 2b and 2c below.
Figure 2-2 M-Series transmitter enclosure dimensions
Figure 2-2bSingle-cavity explosionproof enclosure
Figure 2-2cDual-cavity explosionproof enclosure
4.84 in. (123 mm)5 in. (127 mm)
8.25 in.(210 mm)
5 in. (127 mm)
8.25 in.(210 mm)
Optionaldisplay
3/4 in. NPT conduit access
5 in. (127 mm)
8.25 in.(210 mm)
5 in. (127 mm)
8.25 in.(210 mm)
6.95 in. (176 mm)
3.48 in.(88 mm)
Optionaldisplay
3/4 in. NPT conduit access
Figure 2-2aNEMA 4X enclosure
4.85 in. (123 mm)
3.19 in.(81 mm)
6.0 in.(152 mm)
4.85 in. (123 mm)
Factory supplied pigtailcable (15 ft.)
3.0 INSTALLATION AND MOUNTING
The method you use to mount the M-Series transmitter is dependent on the vessel or tank in which it is beingused, and what type of sensor is being mounted. Most applications will require one of two methods; threaded orflange mounting, as shown in Figure 3-1a “Threaded-flange mounting for rigid and flexible pipe” and Figure 3-1b“Welded-flange mounting for rigid and flexible pipe”. (For detailed information about Sanitary application mount-ing, go to 3.2 “Sanitary Sensor Mounting” on page 8.)
3.1 Rigid and flexible transmitter mounting options
3.1a Threaded-flange mountingIn applications with smaller vessels and tanks, the transmitter can be mounted directly to the tank or flange byusing a threaded NPT fitting, assuming there is a proper threaded connection available. If the float will not fitthrough the tank flange, there must also be some means to mount the float on the transmitter from inside the ves-sel; this may require a float access port nearby the entry point of the transmitter (as shown in Figure 3-1a“Threaded-flange mounting for rigid and flexible pipe” on page 6).
Complete the following steps to mount the transmitter using the threaded-flange method:
1. Remove the float(s) retaining hardware, then remove the transmitter.
2. Insert the transmitter tip through the threaded vessel opening or flange.
3. The transmitter tip can now be lowered to the vessel bottom and the connection can be made from the thread-ed NPT fitting to the vessel. In general, there should not be more than 12 inches of the transmitter’s pipeassembly extending above the vessel.
Important:Before you completely insert the transmitter to the bottom of the vessel, you must remount the float(s) through anaccess port and also reattach the float retaining hardware.
Figure 3-1aThreaded-flange mountingfor rigid and flexible pipe
Riser
NPT Fitting
Tip of transmitter
Tank flange(provided by customeror ordered separately)
Float access port
Retaining hardware
Pipe assembly
6
7
3.1b Welded-flange mounting
The M-Series transmitter can also be mounted to a tank flange as shown in Figure 3-1b “Welded-flange mountingfor rigid and flexible pipe”. Complete the following steps to mount the transmitter onto a tank flange:
1. Install the product and interface floats onto the flexible-sensor pipe.
2. Install the bottom-fixing weight, magnet or hook (also referred to as retaining hardware) on to the tip of the trans-mitter.
3. To complete the installation, mount the transmitter, tank flange, flexible-sensor pipe and product/interface floats asan assembled unit in to the tank.
Note:In general, there should not be more than 12 inches of the transmitter’s sensor pipe length extending above the vessel.
Figure 3-1bWelded-flange mountingfor rigid and flexible pipe
Stainless steelflexible sensor pipe
Interfacefloat
Riser
Productfloat
Welding sleeve1.125 in.(28.6 mm) dia.
Flange (welded)
Tank flange
Bottom-fixing weight,magnet, or hook
3.2 Sanitary transmitter mounting
In sanitary applications, the M-Series transmitter is mounted to the tank using a standard sanitary process connec-tion and sanitary clamp* as shown in Figure 3-2 “M-Series transmitter, tank-mounted sanitary connection”. In mostcases, it is not necessary to remove the sanitary float as the sanitary end-plug fitting is sized to allow installationwith the float in place. Please note that some sanitary end-plug styles have the float(s) permanently mounted.
3.3 Installing a flexible sensor pipe with a bottom-fixing weight or magnet
Complete the following steps to install a flexible sensor pipe with a bottom-fixing weight or magnet:
1. With assistance, feed the flexible sensor pipe through the NPT opening of the tank flange until the flange ispositioned at the rigid section of flexible sensor pipe near the top of the transmitter. Insert the threaded por-tion of the adjustable fitting into the customer flange (apply pipe thread sealant if required). See Figure 3-1a“Threaded-flange mounting for rigid and flexible pipe” on page 6.
2. Slide the product float onto the flexible sensor pipe. See Figure 3-1b “Welded-flange mounting for rigid and flexi-ble pipe” on page 7.
3. Slide the interface float (optional) onto the flexible sensor pipe. Figure 3-1b “Welded-flange mounting for rigidand flexible pipe” on page 7.
4. If you are using a weight or magnet, mount the weight or the magnet to the welded end-plug section of the flexi-ble sensor pipe (this is the bottom rigid section of the flexible sensor pipe) using the supplied nut, spacer andwasher as shown in Figure 3-3 “Retaining hardware” on page 9. Securely tighten mounting nut using 1/2-inchwrench.
Attention:Be careful not to drop the flange on flexible sensor pipe as damage may result.
Important:When assembling and installing the M-Series transmitter, be careful not to allow the flexible hose to kink or becoiled in less than an 16-inch diameter.
To ensure proper and safe assembly and mounting of the transmitter, a minimum of two (2) individuals are required.Gloves are also required.
Sanitary process connnection*(welded to sensor pipe)
Sanitary clamp(customer supplied)
Mating process connection(customer supplied)
Factory supplied pigtailcable (15 ft.)
Sanitary float(permanently mounted withT-bar and drain-in-place endplug styles)
Tip of transmitter
Top viewRiser
*�When using the adjustable tri-clamp(version 401537-1 through -14), thetri-clamp must be removed andmanually cleaned per 3A guidelines.
*�When using the adjustable tri-clamp(version 401537-1 through -14), thetri-clamp must be removed andmanually cleaned per 3A guidelines.
Figure 3-2M-Series transmitter, tank-mounted sanitary connection
Attention:Do not drop the float(s) or allow them to free fall along the flexible sensor pipe as damage may result.
8
9
5. Slide the float(s) back down to the weight or magnet to prevent them from free falling during installation intothe tank. Insert the flexible sensor pipe (with floats) through the tank riser pipe and lower the transmitterassembly into the tank until it rests on the bottom. DO NOT DROP OR DAMAGE THE PIPE.
6. If you are using a flexible sensor pipe with a bottom-fixing hook, fasten the bottom-fixing hook to the appropri-ate customer-supplied mating hardware at the tank bottom.
7. Secure the flange onto the tank riser pipe.
8. Pull the flexible sensor pipe upward to straighten the pipe until the resistance of the weight or magnet is feltwithout raising the weight or magnet off the floor of the tank. Tighten the adjustable fitting to hold the sensorin place.
9. Terminate the field-wire cables noting proper wire orientation.
3.4 Installing a flexible sensor element
Complete the following steps to replace an transmitter electronics housing and flexible sensor element into an exist-ing pipe assembly:
Attention:• Do not bend flexible sensor element to less than a 16-inch bending diameter or damage may result.• Always use safe handling procedures when handling electronics equipment.• Be sure that the inside of the existing outer pipe is clean and dry, and free of debris before installing the M-Series
transmitter.
Attention:Do not kink or bend the flexible sensor pipe in less that a 16-inch diameter as damage may result.
Weight
Flexible sensor pipe Flexible sensor pipe
Magnet
Gauge retention using weight
Weldedend-plug
Flexible sensor pipe
Weldedend-plug
Bottom-fixing hook (mates with customer-supplied
hardware mounted on tank bottom)
Nut Nut
Weldedend-plug
Washer Washer
Spacer Spacer
Gauge retention using hookGauge retention using magnet
Figure 3-3Retaining hardware
1. Sensor pipe and floats should already be installed (see 3.2 “Sanitary Sensor Mounting” on page 8). The electron-ics housing and sensor element portion of the gauge should be separate from the sensor pipe, as shown inFigure-3-4 “Flexible sensor element installation”.
The M-Series transmitter is shipped with the following mounting hardware (as shown in Figure 3-5 “Installing themounting hardware”):
1 hex nut1 ferrule1 rubber sleeve
2. Install the hex nut onto the existing sensor pipe to ensure the threads on the inside of the hex nut are facing up.
3. Install the ferrule onto the sensor pipe, ensuring that the tapered end is down.
4. Install the rubber sleeve onto the sensor pipe and push the rubber sleeve down into the hex nut.
Important:The mounting hardware must be installed in a specific order, and when installed, the ferrule and rubber sleeve collapseinside of the hex nut.
NPT Fitting
Tip of transmitter
Tank
Existing pipeassembly
installation
Sensorcartridge
Flexible sensorelement
M-Series transmitterelectronics housing withsensor element
Enclosure
Figure 3-4 Flexible sensor element installation
Tank flangeNPT Fitting
Mountinghardware
Hex nut
Ferrule
Rubber sleeve
Installed sensor pipe
Figure 3-5 Installing the mounting hardware
10
5. Mount the sensor element into the existing sensor pipe. Do not damage or kink the flexible sensor element inless than a 16-inch bend diameter while installing the element. Guide the sensor downward until the matingsurface of the enclosure installs over the existing sensor pipe, as shown in Figure 3-6a.
6. Make sure that the sensor pipe seats firm against the sensor cartridge nut and then pull up the mounting hard-ware to engage it with the threads of the sensor cartridge, as shown in Figure 3-6b. Ensure that you are notcross-threading as you begin to screw the hex nut onto the threads.
7. Hand tighten the mounting hardware and tighten another two full turns with a wrench. Hold the sensor car-tridge nut while tightening the mounting hardware to ensure that the electronics housing does not swivel withthe turning of the wrench.
8. Ensure that the enclosure and existing pipe assembly are properly tightened; pull up on the enclosure, theenclosure and pipe assembly should not move.
NPT Fitting
Tank
Existing pipeassembly installation
Sensor element
Mountinghardware
Enclosure
Figure 3-6a Figure 3-6b
Tank
Mountinghardware
Sensor cartridge nut
Enclosure
11
4.0 ELECTRICAL CONNECTIONS AND WIRING PROCEDURES
A typical intrinsically-safe connection for the Level Plus transmitter includes protective safety barriers, a powersupply, and a reading or monitoring device. Refer to MTS drawing number 650805 (Revision D) in section 4-1aand 4-1b on pages 13 and 14 for detailed installation and wiring information.
If you are using an integral connector with a NEMA 4X Intrinsically safe enclosure, see section 4-1b “Installationdrawing, M-Series transmitter with NEMA 4X enclosure” on page 14 MTS drawing part number 650805 forwiring information.
A typical explosionproof connection for the Level Plus transmitter includes a power supply and a reading or monitoring device connected using an explosionproof conduit (see section 4.1 “Agency controlled drawing refer-ences, M-Series Analog” on page 13 for a typical conduit installation). Refer to MTS engineering drawing number650805 (Revision D) for detailed installation and wiring information. See also section 4.2 “Electrical Conduitinstallation”.
Notes:1. Loop #1 must be powered on for the M-Series transmitter to operate properly.2. For explosionproof installation, safety barriers are not required and wiring must be installed in accordance with the
National Electric Code ANSI/NFPA 70.
12
4.1 Agency controlled drawing references, M-Series analog
4.1a. Installation drawing, M-Series transmitter with explosionproof enclosure, 650805 (Revision D) sheet 1 of 2
M-S
erie
s Tr
ansm
itte
rLe
vel P
lus
LO
OP
1 T
ES
T
RR
HA
RT
LO
OP
2 T
ES
T
Æ
+-
+-
J4 LOO
P 2
+
+
J2
TB1
J3
J1
J6
J7
J5
J6J6J2J2
J3J3
J5J5TB1
TB1
J7J7
J4J4
J1J1
LOO
P 1
-
1
1
++
-
-
-
NO
REV
ISIO
NS
SHA
LL B
E M
AD
E W
ITH
OU
T N
OTI
FIC
ATI
ON
TO
APP
ROV
AL
AG
ENC
Y(S
).
A
ND
CLA
SS
HA
ZA
RDO
US
LOC
ATI
ON
S.
15. U
SE O
NLY
NRT
L LI
STED
AN
D C
SA C
ERTI
FIED
DU
ST-T
IGH
T SE
AL
FOR
CLA
SS
O
NLY
BE
CO
NN
ECTE
D IN
AC
CO
RDA
NC
E W
/MFG
IS IN
STA
LLA
TIO
N IN
STRU
CTI
ON
S.
14. H
ART
CO
MM
UN
ICA
TOR
WH
ICH
FM
& C
SA A
PPRO
VED
(AS
APP
LIC
AB
LE) M
UST
* RU
NN
ING
LO
OPS
IN S
EPA
RATE
GRO
UN
DED
SH
IELD
S.
* RU
NN
ING
LO
OPS
IN S
EPA
RATE
CA
BLE
S.
13. A
PPRO
VED
MET
HO
DS
FOR
SEPA
RATI
ON
OF
EAC
H L
OO
P A
RE:
CLA
SS II
IC
LASS
, D
IVIS
ION
1, G
ROU
PS E
, F A
ND
G,
11. E
AC
H L
OO
P EN
TITY
PA
RAM
ETER
S
WIT
H N
EMA
/TY
PE 4
X, F
OR
OU
TDO
OR
USE
.
Vm
ax=
36V
Imax
= 1
18m
AC
= 0
L =
200
uH
W
ITH
TH
E C
OU
NTR
Y IN
USE
(eg
CA
NA
DIA
N E
LEC
TRIC
AL
CO
DE,
PA
RT 1
, NA
TIO
NA
L
N
OT
EXC
EED
BA
RRIE
R La
. (SE
E N
OTE
14)
B
ARR
IER
Ca.
TRA
NSM
ITTE
R Li
PLU
S TO
TAL
CA
BLE
IND
UC
TAN
CE
FOR
EAC
H L
OO
P M
UST
7. T
RAN
SMIT
TER
Ci P
LUS
TOTA
L C
AB
LE C
APA
CIT
AN
CE
FOR
EAC
H L
OO
P M
UST
NO
T EX
CEE
D
A
ND
TRA
NSM
ITTE
R Im
ax IS
GRE
ATE
R TH
AN
BA
RRIE
R Is
c.
APP
ROV
ED C
ON
FIG
URA
TIO
N W
HER
E TR
AN
SMIT
TER
Vm
ax IS
GRE
ATE
R TH
AN
BA
RRIE
R V
oc
6. S
AFE
TY B
ARR
IERS
ARE
FM
RC A
ND
CSA
EN
TITY
APP
ROV
ED S
AFE
TY B
ARR
IERS
USE
D IN
AN
4. F
OR
FMRC
& C
SA A
PPRO
VED
GA
UG
ES, B
ARR
IERS
MU
ST B
E FM
RC &
CSA
APP
ROV
ED.
8. G
AU
GE
ENC
LOSU
RE S
HA
LL B
E G
ROU
ND
ED T
O E
ART
H G
ROU
ND
TH
ROU
GH
TH
E PR
OV
IDED
A
PPRO
VED
SA
FETY
BA
RRIE
RS A
ND
SY
STEM
EA
RTH
GRO
UN
D M
UST
BE
LESS
TH
AN
1 o
hm
.
5. T
HE
CO
NN
ECTI
ON
BET
WEE
N T
HE
EART
H G
ROU
ND
TER
MIN
AL
3. C
ON
TRO
L RO
OM
EQ
UIP
MEN
T SH
OU
LD N
OT
USE
OR
GEN
ERA
TE M
ORE
TH
AN
250
V R
MS.
1. F
OR
I.S. F
IELD
INST
ALL
ATI
ON
WIR
ING
SH
ALL
BE
INST
ALL
ED IN
AC
CO
RDA
NC
E
I=4
TO 2
0 m
A
10
CLA
SS I,
DIV
ISIO
N 1
, GRO
UPS
A, B
, C A
ND
D
INTR
INSI
CIA
LLY
SA
FE F
OR:
9. N
O R
EVIS
ION
S SH
ALL
BE
MA
DE
WIT
HO
UT
GRO
UN
D L
UG
IN T
HE
ENC
LOSU
RE.
CA
BLE
CA
PAC
ITA
NC
E SH
ALL
BE
LESS
TH
AN
30
PF P
ER F
OO
T.
.2. S
HIE
LDED
TW
ISTE
D C
AB
LE O
F 24
AW
G O
R H
EAV
IER
SHO
ULD
BE
USE
D.
NO
TES:
1 TO
5 V
OLT
S
CO
MPU
TER
OR
OTH
ER D
EVIC
E
(SEE
NO
TE 3
)
250
oh
ms
24 V
DC
NO
N H
AZ
ARD
OU
S LO
CA
TIO
N
(SEE
NO
TE 3
)
(MA
X 3
6 V
DC
)
POW
ER S
UPP
LY 1
TO 5
VO
LTS
-
(SEE
NO
TE 3
)
OTH
ER D
EVIC
EC
OM
PUTE
R O
R
I=4
TO 2
0 m
A 250
oh
ms
NO
N H
AZ
ARD
OU
S LO
CA
TIO
N
OF
FMRC
OR
CSA
EN
TITY
NO
TIFI
CA
TIO
N O
F A
PPRO
VA
L A
GEN
CY
(S).
FMRC
OR
CSA
EN
TITY
APP
ROV
ED S
AFE
TYB
ARR
IER
EART
H G
ROU
ND
(SEE
NO
TE 5
)
12. T
EMPE
RATU
RE C
OD
E IS
T4.
HA
ZA
RDO
US
LOC
ATI
ON
APP
ROV
ED S
AFE
TYFM
RC O
R C
SA E
NTI
TY
BA
RRIE
R
EART
H G
ROU
ND
(SEE
NO
TE 5
)
BU
SS B
AR
(SEE
NO
TE 5
)EA
RTH
GRO
UN
D
BU
SS B
AR
SEE
NO
TE 1
6IN
TERC
ON
NEC
T B
OA
RD
LEV
EL T
RAN
SMIT
TER
INST
ALL
ATI
ON
DRA
WIN
G--
----
-
----
---
1 2
4/27
/99
---
BB
6508
05
M-S
ERIE
S G
AU
GE
D
HA
RT C
OM
MU
NIC
ATO
RSU
CH
AS
ROSE
MO
UN
T
(SEE
NO
TE 1
4)M
OD
EL 2
75
SEE
NO
TE 8
CO
NN
ECTI
ON
S W
ILL
BE
MA
DE
AT
TERM
INA
L B
LOC
K O
N P
OW
ER
16. F
OR
TRA
NSM
ITTE
RS W
ITH
DU
AL-
CA
VIT
Y E
NC
LOSU
RES,
CU
STO
MER
SID
E O
F H
OU
SIN
G (N
OT
TO T
ERM
INA
L B
LOC
K O
N IN
TERC
ON
NEC
T B
OA
RD)
LEV
EL T
RAN
SMIT
TER
SEE
NO
TE 1
6
EX H
OU
SIN
G
VIE
W S
HO
WN
AB
OV
E
SIN
GLE
CA
VIT
Y H
OU
SIN
G
DU
AL
CA
VIT
Y H
OU
SIN
GLE
VEL
TRA
NSM
ITTE
R (S
EE N
OTE
16)
SHIE
LD
SHIE
LDSH
IELD
SHIE
LD
EL
ECTR
IC C
OD
E A
NSI
/NFP
A 7
0 A
RTIC
LE 5
04-3
0.)
17.
CA
UTI
ON
: FL
EXIB
LE P
ROB
ES H
AV
E A
MIN
IMU
M B
END
RA
DIU
S O
F 15
INC
HES
(380
mm
).
D
5/
19/0
0
KLP
407
7
AD
DED
NO
TES
FOR
MC
B
11
/23/
99
KLP
39
06
CH
AN
GED
NO
TES
1, 6
, 10,
11,
13,
14
& 1
5 O
N P
G 1
AN
D 2
.
C
3/
16/0
0
LJH
40
21
AD
DED
NO
TE 1
7 M
IN B
END
RA
DIU
S.
CO
NN
ECTI
ON
SO
PTIO
NA
L SE
CO
ND
LO
OP
ECO
NO
.B
YD
ATE
REV
.D
ESC
RIPT
ION
UN
LESS
OTH
ERW
ISE
SPEC
IFIE
D:
REM
OV
E B
URR
S A
ND
SH
ARP
EDG
ES .0
15 M
AX
DIM
. LIM
ITS
HEL
D A
FTER
PLA
TIN
G O
R C
ON
VER
SIO
N
.XX
X =
.0
05A
NG
ULA
R =
1
.XX
=
.01
DRI
LL D
EPTH
S A
RE T
OFU
LL D
IAM
ETER
TAP
DEP
THS
ARE
MIN
IMU
MFU
LL T
HRE
AD
S
CO
ATI
NG
++
+
+
DRA
WIN
GSC
ALE
DO
NO
T
FIN
ISH
MA
TERI
AL
DA
TE
DA
TE
DA
TE
DA
TE
DA
TE
SHEE
T
SCA
LE
QC
MFG
OF
ENG
R
DRA
WN
CH
K
DW
G N
O.
TITL
E
REV
LOOP 2
LOOP 1
+-
SEE
NO
TE17
RESE
ARC
H T
RIA
NG
LE P
ARK
, NO
RTH
CA
ROLI
NA
277
09
SEN
SORS
DIV
ISIO
N
13
LO
OP
2 T
ES
TLO
OP
2 T
ES
TLO
OP
1 T
ES
TLO
OP
1 T
ES
TH
AR
TH
AR
T+ +
--+ +
--
1 TO
5 V
OLT
S
250
oh
ms
CO
MPU
TER
OR
OTH
ER D
EVIC
E
24 V
DC
POW
ER S
UPP
LY
-
BA
RRIE
R
I=4
TO 2
0 m
A
----
---
BB
4/27
/99
---
2 2
6508
05
INST
ALL
ATI
ON
DRA
WIN
G, I
.S.
MC
& M
-SER
IES
GA
UG
E--
----
-
(MA
X 3
6 V
DC
)
EART
H G
ROU
ND
(SEE
NO
TES
5 &
8)
BU
SS B
AR
NO
N H
AZ
ARD
OU
S LO
CA
TIO
N
FMRC
OR
CSA
EN
TITY
HA
ZA
RDO
US
LOC
ATI
ON
(SEE
NO
TE 3
)
(SEE
NO
TE 3
)
APP
ROV
ED S
AFE
TY
NO
TES:
1. F
OR
I.S. F
IELD
INST
ALL
ATI
ON
WIR
ING
SH
ALL
BE
INST
ALL
ED IN
AC
CO
RDA
NC
E
CA
BLE
CA
PAC
ITA
NC
E SH
ALL
BE
LESS
TH
AN
30
PF P
ER F
OO
T.
3. C
ON
TRO
L RO
OM
EQ
UIP
MEN
T SH
OU
LD N
OT
USE
OR
GEN
ERA
TE M
ORE
TH
AN
250
V R
MS.
2. S
HIE
LDED
TW
ISTE
D C
AB
LE O
F 24
AW
G O
R H
EAV
IER
SHO
ULD
BE
USE
D.
INST
RUM
ENT
GRO
UN
D.
9. N
O R
EVIS
ION
S SH
ALL
BE
MA
DE
WIT
HO
UT
NO
TIFI
CA
TIO
N O
F A
PPRO
VA
L A
GEN
CY
(S).
5. T
HE
CO
NN
ECTI
ON
BET
WEE
N T
HE
EART
H G
ROU
ND
TER
MIN
AL
OF
FMRC
OR
CSA
EN
TITY
A
PPRO
VED
SA
FETY
BA
RRIE
RS A
ND
SY
STEM
EA
RTH
GRO
UN
D M
UST
BE
LESS
TH
AN
1 o
hm
.
8. G
AU
GE
SHA
LL B
E G
ROU
ND
ED T
O E
ART
H G
ROU
ND
TH
ROU
GH
TH
E PR
OV
IDED
GRO
UN
D L
UG
CLA
SS ,
DIV
ISIO
N 1
, GRO
UPS
E, F
AN
D G
, CLA
SS II
IW
ITH
NEM
A/T
YPE
4X
, FO
R O
UTD
OO
R U
SE.
10.
INTR
INSI
CIA
LLY
SA
FE F
OR:
CLA
SS I,
DIV
ISIO
N 1
, GRO
UPS
A, B
, C A
ND
D
4. F
OR
FMRC
& C
SA A
PPRO
VED
GA
UG
ES,
BA
RRIE
RS M
UST
BE
FMRC
& C
SA A
PPRO
VED
.12
. TEM
PERA
TURE
CO
DE
IS T
4.
13. A
PPRO
VED
MET
HO
DS
FOR
SEPA
RATI
ON
OF
EAC
H L
OO
P A
RE:
* RU
NN
ING
LO
OPS
IN S
EPA
RATE
CA
BLE
S.
* RU
NN
ING
LO
OPS
IN S
EPA
RATE
GRO
UN
DED
SH
IELD
S. 6
. SA
FETY
BA
RRIE
RS A
RE F
MRC
AN
D C
SA E
NTI
TY A
PPRO
VED
SA
FETY
BA
RRIE
RS U
SED
IN A
N
APP
ROV
ED C
ON
FIG
URA
TIO
N W
HER
E TR
AN
SMIT
TER
Vm
ax IS
GRE
ATE
R TH
AN
BA
RRIE
R V
oc
A
ND
TRA
NSM
ITTE
R Im
ax IS
GRE
ATE
R TH
AN
BA
RRIE
R Is
c.
7. T
RAN
SMIT
TER
Ci P
LUS
TOTA
L C
AB
LE C
APA
CIT
AN
CE
FOR
EAC
H L
OO
P M
UST
NO
T EX
CEE
D
B
ARR
IER
Ca.
TRA
NSM
ITTE
R Li
PLU
S TO
TAL
CA
BLE
IND
UC
TAN
CE
FOR
EAC
H L
OO
P M
UST
NO
T EX
CEE
D B
ARR
IER
La. (
SEE
NO
TE 1
4)
NO
N H
AZ
ARD
OU
S LO
CA
TIO
N
1 TO
5 V
OLT
S
BU
SS B
AR
I=4
TO 2
0 m
A
250
oh
ms
(SEE
NO
TE 3
)
OTH
ER D
EVIC
EC
OM
PUTE
R O
R
APP
ROV
ED S
AFE
TYFM
RC O
R C
SA E
NTI
TY
BA
RRIE
R
(SEE
NO
TES
5 &
8)
EART
H G
ROU
ND
W
ITH
TH
E C
OU
NTR
Y IN
USE
(eg
CA
NA
DIA
N E
LEC
TRIC
AL
CO
DE,
PA
RT 1
, NA
TIO
NA
L
11. E
AC
H L
OO
P EN
TITY
PA
RAM
ETER
S (P
RIN
TED
ON
LA
BEL
)
L =
200
uH
C =
0
ii
Imax
= 1
18m
AV
max
= 3
6V
14. H
ART
CO
MM
UN
ICA
TOR
WH
ICH
FM
& C
SA A
PPRO
VED
(AS
APP
LIC
AB
LE) M
UST
O
NLY
BE
CO
NN
ECTE
D IN
AC
CO
RDA
NC
E W
ITH
MFG
IS IN
STA
LLA
TIO
N IN
STRU
CTI
ON
S.
15. U
SE O
NLY
NRT
L LI
STED
AN
D C
SA C
ERTI
FIED
DU
ST-T
IGH
T SE
AL
FOR
CLA
SS
A
ND
CLA
SS
HA
ZA
RDO
US
LOC
ATI
ON
S.
(SEE
NO
TE 5
)EA
RTH
GRO
UN
D
MO
DEL
275
(SEE
NO
TE 1
4)
SUC
H A
S RO
SEM
OU
NT
HA
RT C
OM
MU
NIC
ATO
R
NO
REV
ISIO
NS
SHA
LL B
E M
AD
E W
ITH
OU
T N
OTI
FIC
ATI
ON
TO
APP
ROV
AL
AG
ENC
Y(S
).
LEV
EL T
RAN
SMIT
TER
NEM
A 4
X H
OU
SIN
G
SHIE
LD
SHIE
LD
SHIE
LD
SHIE
LD
D
EL
ECTR
IC C
OD
E A
NSI
/NFP
A 7
0 A
RTIC
LE 5
04-3
0.)
IN T
HE
ENC
LOSU
RE.
WH
ERE
INTE
GRA
L C
AB
LE IS
PRO
VID
ED, L
OO
P 2
SHIE
LD IS
NO
T A
VA
ILA
BLE
ON
MC
OPT
ION
AL
SEC
ON
D L
OO
PC
ON
NEC
TIO
NS
(NO
T A
VA
ILA
BLE
ON
MC
)
SIG
NA
LW
IRE
CO
LOR
LOO
P 1
+RE
D
BLA
CK
LOO
P 1
-
WH
ITE
LOO
P 2
+
BLU
ELO
OP
2 -
WIR
E TE
RMIN
ATI
ON
CH
ART
6 PI
N C
ON
N C
AB
LE W
IRE
CO
LOR
RED
RED
W/W
HIT
E TR
AC
E
RED
W/Y
ELLO
W T
RAC
E
GRE
EN
GRO
UN
D
(SEE
NO
TE 8
)
RED
W/B
LUE
TRA
CE
BA
RE
MR
(M-S
ERIE
S)
MC
MO
DEL
REV
.D
ATE
BY
DC
R N
O.
DES
CRI
PTIO
N
+
FULL
TH
REA
DS
TAP
DEP
THS
ARE
MIN
IMU
M
FULL
DIA
MET
ERD
RILL
DEP
THS
ARE
TO
MFG
QC
ENG
R
CH
K+
.XX
=
.01
DO
NO
T SC
ALE
DRA
WIN
G
++
AN
GU
LAR
=
1.X
XX
=
.005
CO
ATI
NG
PLA
TIN
G O
R C
ON
VER
SIO
N
DIM
. LIM
ITS
HEL
D A
FTER
EDG
ES .0
15 M
AX
REM
OV
E B
URR
S A
ND
SH
ARP
UN
LESS
OTH
ERW
ISE
SPEC
IFIE
D:
DRA
WN
DA
TE
DA
TE
DA
TE
DA
TE
DA
TE
SCA
LE
SHEE
TO
FRE
VD
WG
NO
.
TITL
E
MA
TERI
AL
FIN
ISH
RESE
ARC
H T
RIA
NG
LE P
ARK
, NO
RTH
CA
ROLI
NA
277
09
SEN
SORS
DIV
ISIO
N
4.1b Installation drawing M-Series transmitter with NEMA 4X enclosure, 650805 (Revision D) sheet 2 of 2
14
4.2 Electrical conduit installation
Attention:• Use an explosionproof type conduit sealing fitting. • Tighten housing cover (both front and back covers if dual cavity) to full stop against “O” ring.• Do not over-tighten compression fittings.• Use side conduit entry only.• Do not use plugged housing entry for termination of conduit.• In high humidity areas, use a breather drain type conduit sealing fitting to minimize moisture intrusion.
Figure 4-2Typical transmitter installation
NPT FittingDo not over-tightencompression fitting!
Interface float(ordered
separately)
Product float(ordered
separately)
View shown withcover removed
Plugged entryDo not use(see notes)
Do not remove cover with circuit livein hazardous locations!
Follow safe work procedures.
3/4 NPT conduit accessUse NPT conduit fitting only!
Conduit (flexible or rigid)
Explosionproof-typeconduit sealing fitting
Conduit fromcontrol room
l
Loop 1 Test + —
Loop 2 Test + —
HART
Level Plus®M-Series Transmitter
TOREM
OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW
IST
ORTU
RN
l
Loop 1 Test + —
Loop 2 Test + —
HART
Level Plus®M-Series Transmitter
TOREM
OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW
IST
ORTU
RN
15
4.3 Cable specifications
The following section lists cable parameters and specifications for the M-Series transmitter. The list is not inclu-sive of all cable types and cable manufacturers and should serve only as a guideline when choosing cables. Othercable types can be selected that meet the requirements.
Parameter SpecificationMinimum cable size: 24 AWG or heavier (0.51 mm diameter)
Contact MTS for additional assistance in selecting proper cableCable type: Single pair shielded or multiple pair with overall shieldMaximum cable length: Twisted pair: 10,000 ft. (3,048 m)
Multiple twisted-pair: 5,000 ft. (1,524 m)Maximum cable length formula: Use the following formula to determine the maximum cable length for a
specific application:
L = [(65 x 106) ÷ (R x C)] - [(Cf + 10,000) ÷ C]
Where: L = Length in feet or metersR = Resistance in ohm, current sense resistance plus barrier resistanceC = Cable capacitance in pF/ft, or pF/mCf = Maximum shunt capacitance of smart field devices in pF
Example:Assume a high performing smart transmitter, a control system,and a single pair of shielded wires.R = 250 ohmC = 50 pF/ftCf = 5,000 pF
L = [(65 x 106) ÷ 250 x 50)] - [(5,000 + 10,000) ÷ 50]
L = 4,900 ft (1,494 m)
16
4.4 Safety guidelines for the M-Series transmitter
Be sure you:
* Follow any applicable local and national electrical codes and observe polarity when making electrical connec-tions.
* Never make electrical connections to the M-Series transmitter when it is powered on.
* Check that no wire strands are loose or sticking out of the terminal block connection on the interconnect boardwhich could short and cause a problem. see Figure 7-2a “Transmitter electronics interconnect board” on page 20/.
* Check that no wire strands, including shield, are in contact with the electronics module or interconnect board.
* Ensure that the electronics module is grounded through interconnect board and electrically isolated from theexplosionproof enclosure.
* Refer to the safe operating power chart in Figure 4-4 “Loop resistance vs power supply” which shows the relation-ship between loop resistance and operating voltage.
4.5 Safety Barriers for IS Installation
Figure 4-5, “Safety barrier types for the M-Series transmitter” illustrates passive/active safety barriers. See page 13 and14 for wiring and entity parameters.
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
INSUFFICIENTOPERATING POWER
EXCESS POWER
Resistance(Ohms)
Supply Voltage (Volts DC)
Figure 4-4Loop resistance vs power supply
Transmitter
+Passive
+ 24 Vdc Input
+ 1 to 5 V Output
Power & signal common
250 ohm0.1%, 2.5 W
HAZARDOUS AREA NON-HAZARDOUS AREA
SHUNT BARRIERS (I.S. Ground Connection REQUIRED)
Transmitter
ISOLATED BARRIERS (I.S. ground connection NOT REQUIRED)
I.S. ground connection
+24 Vdc
-
+ 1 to 5 V Output
1 to 5 V Return
250 ohm0.1%, 2.5 W
-
+
-
ActiveLoad
Load
Figure 4-5Safety barrier types for the M-Series
transmitter
Notes:• When selecting barrier types, the electrical
specifications for the M-Series transmitterare: Vmax = 36.1 Vdc, Imax = 118 mA (totalcurrent), Ci = 0.0 µF, Li = 0.0 µHy
• MTS stocks Stahl barriers 9001/01-280-100-10 (MTS part number 560669).
17
5.0 SYSTEM CHECK
After you complete the M-Series wiring, complete the following steps to perform the system check:1. Apply power to the transmitter.
2. Using a DC volt meter, measure the voltage at loop #1 connections. The voltage must be ≥ 10.5V. If loop #2is being used, measure the voltage at the loop #2 connections, it also must be at ≥ 10.5V. If the voltage levelsare too low, turn off power to the transmitter..
3. Check for shorts, power supply voltage, and excessive loop resistance. Refer to Figure 4-4,”Loop resistance vspower supply” on page 17) which shows the relationship between loop resistance and operating voltage.
5.1 Performing a loop #1 test
To test loop #1, lay the transmitter on a flat surface and move the float along the operational range of the M-Series transmitter. If the transmitter is functioning properly, the output current will change as the float moves.
If the output current is less than 4 mA or greater than 20 mA, this could indicate a problem with the M-Seriestransmitter.
5.2 Performing a loop #2 test (if applicable)
If you are using loop #2, complete the following steps to test the loop (the following test varies depending on theconfiguration):
1. To access loop #2, power on loop #1.
2. If loop #2 is set for level measurement, test the transmitter in the same manner as defined in section 5.1,“Performing a loop #1 test” on page 18.
3. If loop #2 is assigned to measure temperature, first read the output current. Then, if the setpoint values areknown, calculate the temperature using the following formula:
T = [(T20mA - T4mA) ÷ 16] (I - 4) + T4mAWhere: T = TemperatureT20mA = Temperature @ 20 mA setpoint (Factory Setting: 300 °F)
T4mA = Temperature @ 4 mA setpoint (Factory Setting: -30 °F)
I = Output current (in mA)
The M-Series transmitter’s sensing Resistance Temperature Device (RTD) is located at approximately three inchesfrom the transmitter’s tip. Measure the temperature near the tip to see if it is an approximation of the calculatedvalue. If the output current is less than 4 mA or greater than 20 mA, there may be a problem with the sensingRTD (i.e., it may be shorted or open).
6.0 FLOATS
For information about floats, go to www.mtssensors.com and refer to the float specification, MTS part number550537. For float application information, please contact the MTS Level Plus Applications Engineering.
When contacting MTS for assistance on floats, please have the following information available:
• Specific gravity of liquid(s) being measured• Process temperature• Vessel pressure
18
7.0 MAINTENANCE
M-Series transmitter assemblies use magnetostrictive technology and only have one moving part, the float. Thistechnology ensures no scheduled maintenance or recalibration is required. However, it is necessary that you checkthe sensor pipe annually for build up of process material. Floats should move freely along the sensor pipe. If theydo not, routine cleaning should be performed.
7.1 Replacing an M-Series electronics module (puck) or interconnect board
The M-Series electronics module, also referred to as a puck, is modular in design. The puck or interconnect boardcan be replaced in the field without onsite MTS Applications Engineering Support.
7.1a Replacing an M-Series electronics module (puck)
Complete the following steps to install the puck:
1. Remove any dirt, debris, or liquid from the top of the instrument enclosure (see Figure 7-1a, “Instrument enclo-sure”).
2. Remove the instrument housing cover (see Figure 7-1a, “Instrument enclosure”).
3. Remove the existing puck by grasping the perimeter of the puck and lifting upward. the puck will slide freefrom the two female interconnects that are mounted on the transmitter electronics interconnect board (see Figure 7-1b, “Electronics Module (puck)”)
4. Remove the replacement puck from its package. To ensure that the new puck installs correctly, align the inter-connects on the back of the puck with the male interconnects on the interconnect board as shown in Figure 7-1c, Transmitter electronics interconnect board”. Secure the puck into the instrument housing by pressing downaround the parameter of the puck face. The puck should feel secure and not “rock”.
5. install the instrument housing cover.6. Continue with section 8.0, “Using the keypad to calibrate M-Series transmitters”, on page 21 for calibration and
setup instructions.
19
Attention:Ensure that all power is disconnected and that all lockout procedures are followed prior to opening the M-Series instru-ment housing.
Figure 7-1bElectronics module (puck)
Figure 7-1aInstrument enclosure
Figure 7-1cTransmitter electronics (baseboard)
Instrumentenclosure
Housingcover
Transmitter electronicsinterconnect board
puck(front view)
Puck(rear view)
Female interconnects
Male interconnects
20
7.1b Replacing the interconnect board
Complete the following steps to replace the transmitter electronics interconnect board:
1. Remove any dirt, debris, or liquid from the top of the instrument enclosure.
2. Remove the instrument housing cover (see Figure 7-1a “Instrument enclosure” on page 19.
3. Remove the existing puck by grasping the perimeter of the puck and lifting upward (see Figure 7-1b,“Electronics Module (puck)” on page 19. The puck will slide free from the two female interconnects that aremounted on the interconnect board (see Figure 7-2a “Transmitter electronics interconnect board components”. Placethe puck in a safe area.
4. Disconnect the terminal block connector (replacement included if needed) and wired connector see Figure 7-2a.
5. Disconnect the sensing element connector and RTD cable connector if present (see Figure 7-2a).
6. Unscrew the four standoffs and remove the interconnect board from the instrument enclosure (see Figure 7-2a). 7. Remove the replacement interconnect board from its package. line the board up with the four mounting screws
(see Figure 7-2a). Secure the interconnect board to the instrument enclosure with four standoffs (includedwith kit).
8. Connect the wired connector and the terminal block connector (see Figure 7-2a).
9. Connect the sensing element connector and RTD cable connector.
11. To install the new puck, Using even pressure, press down firmly on the face of the puck until the male andfemale interconnects engage fully. Ensure that the new puck is installed correctly in the instrument housing bypressing down around the parameter of the puck face. The puck should feel secure and not “rock”.
12. Replace the instrument housing cover.
AttentionBefore you begin, ensure that all power is disconnected and that all lockout procedures are followed prior to opening theM-Series instrument housing.
Figure 7-2aTransmitter electronics
interconnect board components
Terminal Block
Sensing elementconnector
Transmitter electronicsinterconnect board
Female interconnects
RTD connector
Wired connector
Female interconnects
Mounting screws
8.0 USING THE KEYPAD DISPLAY TO CALIBRATE THE LEVEL PLUS M-SERIES TRANSMITTERThe M-Series transmitter can be calibrated by using the HART communications protocol or it may be manuallycalibrated using the optional keypad display. This section explains modes of operation and the steps you need toperform to calibrate your transmitter manually using the keypad display.
8.1 Modes of operation
The M-Series transmitter runs in one of the following modes of operation. You can use these modes to calibrateand set up various operating parameters.
Run modeRun mode is the primary mode of operation. This mode will perform measurements, display data, and respondto HART commands. The run mode can be configured for various output options. The minimum configurationwill only perform a single-level measurement. More complex configurations will perform a second float measure-ment (interface), or temperature measurements.
Program modeThe program mode is only applicable to M-Series transmitter with the keypad display option. Enter this mode bypressing any of the three keys, Up keypad, Down keypad, and Enter keypad as shown in Figure 8-2, “M-Series key-pad display”. Menus guide the user through various programming options. When in the program mode, HARTcommunications are not functional. An automatic timeout feature is provided so that the transmitter does notremain inadvertently in program mode.
Display test modeThis mode is invoked through the keypad.
Keypad display usage in program modeThe M-Series transmitter can be configured by pressing three keys, the Up keypad, Down keypad, and Enter key-pad as shown in Figure 8-2, “M-Series keypad display”. This gives the user a means to calibrate and set up variousoperating parameters.
l
Loop 1 Test + —
Loop 2 Test + —
HART
Level Plus®M-Series Transmitter
TOREM
OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW
IST
ORTU
RN
Loop 1 test port Loop 2 test port
HART test port
Up key Enter key
Down key
Custom LCD display
8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8.% mA in ft mm cm m % mA in ft mm cm m °C °F
LEVEL 1 LEVEL 2 TEMP
Level 1 Data Field Temperature Data Field
Level 2 Data Field
Level 1 iconis always enabled
in Run Mode
Level 2 icon is enabled onlywhen in Run Mode and Level 2measurement is enabled
Temp icon is enabled onlywhen in Run Mode andtemperature is enabled
Level 1 Unit icons Level 2 Unit icons Temperature Unit icons
Figure 8-2M-Series keypad display
21
The three keypads are identified with “t” “”, and “<—”. The “s” keypad may be used to indicate Up responses,the “t” symbol indicates Down responses, and “<—” indicates an Enter response. Normally, the M-Series trans-mitter will remain in run mode. When you press any three keys, the transmitter will enter program mode. In pro-gram mode, the electronics module menu displays options that you can scroll through using the Up and Downkeypads. To select an option, press Enter.
Program mode TimerAfter you enter the programming mode, a one-minute timer is started. Each time you press a button, the timer isreset. If you do not press a menu button within one minute, the timer will expire and the transmitter will returnto the run mode (See “run” mode on page 21).
Loop #1 and loop #2 test portsUsing a standard multi-meter set the meter to DC current and attach across the terminals, loop current can beread directly from ports #1 and #2 see Figure 8-2, “M-Series keypad display”. The current read on the meter shouldcorrespond with the data being displayed. These ports allow the loop current to be read directly without havingto interrupt power.
HART portThis port allows for direct connection of the Rosemount-275 or 375 field calibrator or other HART host deviceas long as there is a load on loop 1.
8.2 LCD display and keypad (optional)
A sixteen character, seven-segment LCD display and three button keypad option is available. Level and tempera-ture measurements are displayed when the transmitter is in run mode. When power is applied to the transmitter,a Start message displays. When the transmitter is in run mode, the display is refreshed every three seconds. Thereare three data fields on the display; Level 1, Level 2 and Temperature see Figure 8.2 “M-Series keypad display”. If ameasurement is not available, dashes (- - - - -) will display in the corresponding field.
Note:In program mode, the transmitter will not respond to incoming HART commands. This function will prevent a user ata remote terminal from overwriting a parameter that is being entered at the same time from a local site.
l
Loop 1 Test + —
Loop 2 Test + —
HART
Level Plus®M-Series Transmitter
TOREM
OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW
IST
ORTU
RN
Loop 1 test port Loop 2 test port
HART test port
Up key Enter key
Down key
Custom LCD display
8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8.% mA in ft mm cm m % mA in ft mm cm m °C °F
LEVEL 1 LEVEL 2 TEMP
Level 1 Data Field Temperature Data Field
Level 2 Data Field
Level 1 iconis always enabled
in Run Mode
Level 2 icon is enabled onlywhen in Run Mode and Level 2measurement is enabled
Temp icon is enabled onlywhen in Run Mode andtemperature is enabled
Level 1 Unit icons Level 2 Unit icons Temperature Unit icons
Figure 8-2M-Series keypad display LCD display
22
8.3 Alarm settings
When a fault condition is detected by the internal microprocessor, the 4 to 20 mA current will go to the currentselected. If in the 4 mA alarm mode when a fault is detected, the output will be continuous at 3.8 ± 0.1 mA. Ifin the 20 mA alarm mode when a fault is detected, the output will be continuous at 21.5 ±0.2 mA.
8.4 Manual calibration
Figure 8-4, “Manual calibration matrix” illustrates the procedure to enter calibration mode and modify levels 1 and2, adjust LCD contrast and perform a LCD test.
23
Figure 8-4Manual calibration matrix
Calibrate Level 1?
Calibrate Level 2?
AdjustLCD Contrast?
PerformLCD Test?
Press any button to Enter Menu
+
‘Enter’ or ‘Carriage Return’Down arrow button
Up arrow button
Accept new value?If No: +If Yes:
Reads current floatposition, Move floatto desired position
= Calibrate Span
= Calibrate Zero
= Calibrate Span
= Calibrate Zero
Reads current floatposition, Move floatto desired position
Increases Value
Decreases Value
Shows currentLCD contrast value
Accept new value?If No: +If Yes:
Tests all segmentsof LCD
(lasts 10 seconds)
To exit Calibration Modeat any time, press all threebuttons simultaneously:
+ +
+ hold for 1 second
+ hold for 1 second
+ hold for 1 second
24
9.0 USING THE HART COMMUNICATION PROTOCOL TO CALIBRATE THE LEVEL PLUS M-SERIES TRANSMITTER
Refer to the documentation that comes with the HART Model 275 and 375 Hand-Held Terminal for specificsensor calibration information. This section describes how the HART protocol is applied to the Level Plus M-Series transmitter only.
Using the HART interface allows for calibration without having to remove the transmitter from the process andposition of the floats. You can perform this function by using HART commands 35 and 65.
Any measured output may be assigned to any variable. Loop #1 is always the primary variable (PV); level one isusually assigned to loop #1. Loop #2 is always the Second Variable (SV); usually represents temperature or level32. The Third Variable (TV) and Fourth Variable (FV) may be assigned to any remaining output such as, level 2,temperature. Analog output codes are 0, 1, and 2 respectively.
Calibration set points for level are given as the absolute displacement (in the appropriate units) from the tip ofthe sensor pipe. For example, if the Zero (LRV) position for level 1 is given as 5 inches, the transmitter will pro-duce 4 mA when the float is 5 inches from the tip of the sensor pipe. If the Span (URV) position for level 1 isgiven as 30 inches, the transmitter will produce 20 mA when the float is 35 inches from the top of the sensorpipe. To calibrate the temperature set points, the Zero (LRV) and Span (URV) points are given in degrees. Fortemperature, the Zero (LRV) value (in degrees) must always be less than the Span (URV) value (in degrees).
9.1 Preparing the transmitter for re-calibration
The M-Series transmitter can be re-calibrated by using the HART model 275 and 375 hand-held terminal.Complete the following procedure to reset the low and high values for loop #1 (only loop #1 can be calibratedwith the HART hand-held terminal using the generic XMTR type driver. To access both loops as well as otherparameters, the MTS device driver must be purchased and installed in to the 275/375 hand-held device. Formore information about the HART device driver, go to HARTcomm.org.
Before you begin, do the following:
1. Connect the transmitter to a clean 24 Vdc power supply. Use a linear supply, switching types does not provideripple-free power. HART cannot tolerate more than a 25 mV voltage ripple.
2. If the unit is installed in a live application, place your automatic controllers in manual mode and be advisedthat the output current will change during calibration.
3. Follow safe working procedures for working on live equipment in a hazardous location before you remove thehousing cover.
4. Connect the HART hand-held terminal to the terminals that are labeled HART located on the front panel dis-play of the Level Plus transmitter.
5. Press the black and white I/O button on the HART terminal. The HART terminal will perform an automaticself test. The Main window displays. If the device is not connected properly, the message “No device found”displays.
6. In the Main window, press the key #1, the Device Setup window displays.
7. In the Device setup window, press Key #3. The Basic Setup window displays.
Attention:Be sure you have loop #1 connected to a load of 250 to 500 ohm. A transmitter installed in a control loop is a goodexample of the loop load. You might also use a load resistor in the range of the above value.
25
8. In the Basic Setup window, press Key #3. The Range Values window displays.
9.2 Setting the low value
Complete the following steps to set the low value:
1. To set the low value, Process Variable, Low Range Value (PV LRV) to 4 mA, select Key #1. The PV LRV win-dow displays the current low value. Below the highlighted value located under the current value, key in thelow value you want (example 3.00 in. is shown; if 4 inches is the value you want, key in 4.) and press Enter(F4) located below the LCD display.
2. To write the changed lower value to memory, press the Send key.
3. Two Warning messages will display before the new values take affect; if your new low values are correct, respondto the Warning messages by pressing OK when prompted. This action resets the Low Range Value, or 4 mAposition into the transmitter's memory.
4. Go back to the Range Values window to verify that the new parameters have been accepted into the transmit-ter’s memory.
5. Do one of the following:5.a Exit program mode.
5.b To reset the upper value, continue to 9.3 “Setting the Upper Range Value”.
9.3 Setting the Upper Range Value
Complete the following steps to set the Upper Range Value:
1. Open the Range Values window. To set the 20 mA Upper Range Value, press Key #2. The Process Variable,Upper Range Value (PV URV) window displays.
2. As shown the Lower Value window, the current value displays with a highlighted number below the value dis-played. To change the upper value, key in the new value. You can use whole numbers or whole numbers anddecimals (example, 40 = 40 inches, or 40.5 = 40.50 inches.) Whole numbers will be converted as decimalequivalents automatically by the HART terminal.
3. Key in the new Upper Range Value and press Enter or (F4). The Range Values window displays.
4. Verify that the upper and lower values are correct. If the values are correct, press Send.
5. You will be prompted with two Warning messages, press OK in response to both warnings.
Caution:DO NOT enter a high value that exceeds the active length of the sensor.
10.0 INSTALLING AND USING THE M-SERIES FIELD SETUP SOFTWARE V1.01 (CD-ROM) TO SETUP PARAMETERS AND ADJUST CALIBRATION
Adjustments to the calibration and setup parameters of the transmitter may be done using the M-Series FieldSetup software v1.0 and a RS-232 to HART converter (SMAR HI-311, MTS Part # 380068). Be sure you areinstalling the latest software package, go to www.mtssensors.com for more information. The following parameterscan be viewed or modified when using the M-Series Field Setup software:
Basic: Manufacturing informationAdvanced: Gauge length, Gradient, Head Adder, Enable Display, Enable Loop 2,
and Set Alarm Output to Low or HighCalibration: Level 1 Span and Offset. Level 2 Span and Offset, Temperature Span and OffsetOutput: Level 1 Units of Measure, Level 2 Units of Measure, Temperature Units of Measure,
Output Units of Measure, Output Designations and View Output Data
10.1 Installing the M-Series Field Setup software
Before you begin, do the following:
1. Obtain a Linear Power Supply, Multi-meter, PC and a HART RS-232 Converter.
2. Complete the following steps to install the M-Series Field Setup Software package and/or modify calibration andsetup parameters:
a. Insert the CD into the proper drive.
b. Browse to to CD-ROM drive and run setup.exe.
c. Follow the instructions on screen to install the program.
3. Connect the amp meter, power supply and transmitter. Set the proper scale on the meter. Ensure a 250 ohmresistor is installed in the line to enable uninterrupted communication.
4. Connect the HART adapter/converter to the RS-232 COM port on the back of the PC.
5. Attach the HART converter to the HART connection pins located on top of the M-Series Electronic module(puck) or across the resistor.
4. Connect HART adapter/converter clip leads to HART port on M-Series Electronic module (puck).
5. Apply power to the M-Series Transmitter and PC.
26
10.2 Calibration and setup parameters
1. From your desktop double-click the MSeries Field Setup icon to start the software.
2. Setup will automatically search and receive configuration data from the transmitter. The M-Series Field Setupwindow displays as shown in Figure 10-1 “M-Series Field Setup software - Basic Setup window”, click the BasicSetup tab to review the data. If there is no data, assign a different serial communications port and click theFind button in the top left corner to rerun the search program.
27
Figure 10-1M-Series Field Setup software - Basic Setup window
3. In the M-Series Field Setup window as shown in Figure 10-2 “M-Series Field Setup software-Advanced setupwindow, click the Advanced Setup tab. Confirm that the Gradient, Length, and Head Adder have beenreceived from the level transmitter. If the information does not display, click the Read button at the bottomof the window and manually enter the missing data. The sensor information fields are defined as follows:
Sensor information:Gradient: Is slightly different for each transmitter. It can be found on sensor element head.
Units: Determines the units of measure for Length and Head Adder. This is used when writing new val-ues of Order Length and Head Adder to the transmitter. Click the Output Tab to change units of meas-ure for all data.
Length: Is equal to the order length of the transmitter being used.
Head Adder: Is the distance between the sensing element and the order length. Each model has a slightlydifferent adder as follows:Gauge Style: Length in Inches:NEMA 4X housing, standard rigid pipe 4.3 to 4.5Explosionproof housing with/without display with rigid pipe 5.6 to 5.7NEMA 4X housing with flex pipe < 10 feet 14.0 to 14.5Explosionproof housing with or without display with flex pipe < 10 feet 14.0 to 14.5.
10.3 Instrument parameters:
Display Units: Type of level data displayed on the optional LCD display; Units, mA and Percent.Float #2: optional float #2; Enable/Disable .Temperature: optional temperature data; Enable and Disable.Display: optional LCD display; Enable and Disable.Alarm: Output current value defined as Low (3.8 mA) or High (21.5 mA), if the float(s) or temperaturesensor should fail.
28
Figure 10-2M-Series Field Setup software - Advanced Setup window
4. In the M-Series Field Setup window as shown in Figure 10-3 “M-Series Field Setup software - Calibration Setupwindow”, click the Calibration tab. Adjust the Zero (LRV) value and Press the Write button. Adjust the Span(URV) value and Units value from the appropriate channel and press the Write button.
The Calibration window fields are defined as follows:
The Calibration window contains the Zero (LRV) and Span (URV) set points for all three variables. Tochange a value, type in the new value and press the Write button to save your change. To confirm thevalue change, press the Read button.
The Units field shows the units of measure for the Zero (LRV) and Span URV). To change the units ofmeasure for the Zero(LRV) and Span (URV) press the arrow and select from the pull down menu. Pressthe Write button to confirm any changes to the settings. Press the Read button to confirm that thetransmitter has accepted the new value.
The Offset field is used for making adjustments to the optional LCD display, not the current output.
Example: If the float is at the 4-mA point, but the display reads +.25 inches. Enter in -.25 inches in theblock and press the W key to save, Now the display will read 0.00 inches even though the current hasremained at 4 mA.
29
Figure 10-3M-Series Field Setup software - Calibration Setup window
UNITED STATESMTS Systems CorporationSensors Division3001 Sheldon DriveCary, NC 27513Tel: 800-457-6620Fax: 919-677-2545
GERMANYMTS Sensor TechnologieGmbH & Co. KGAuf dem Schüffel 9D - 58513 LüdenscheidTel: +49 / 23 51 / 95 87-0Fax: +49 / 23 51 / 56 [email protected]
JAPANMTS Sensors TechnologyCorporationUshikubo Bldg.737 Aihara-cho, Machida-shiTokyo 194-0211, JapanTel: + 81 (42) 775-3838Fax:+ 81 (42) [email protected]
Part Number: 10-04 550720 Revision FMTS is a registered trademerk of MTS Systems Corporation.
Level Plus is a registered trademark of MTS Systems Corporation.All other trademarks are the property of their respective owners.
All Temposonics sensors are covered by US patent number 5,545,984. Additional patents are pending.Printed in USA. Copyright © 2004 MTS Systems Corporation. All Rights Reserved.FM
APPROVED