Upload
vuongkien
View
225
Download
1
Embed Size (px)
Citation preview
© ABB Oy Distribution AutomationJuly 1, 2009 | 1MRS756504 B |Slide 1
Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation
Relion® 615 series
© ABB OyJuly 1, 2009 | Slide 2
ContentsRED615 Technical Presentation
Introduction
Application examples
Hardware and options
Functionality highlights
Communication
Mechanical design
Front panel HMI
Tools
Conclusions
© ABB OyJuly 1, 2009 | Slide 3
Introduction
© ABB OyJuly 1, 2009 | Slide 4
Relion® 615 series RED615
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RED615 is a member of ABB’s Relion®
product family and part of its 615 protection and control product seriesThe 615 series IEDs are characterized by their compactness and withdrawable designOther members of the 615 product series:
REF615REM615RET615
© ABB OyJuly 1, 2009 | Slide 5
RED615 Description
RED615 is a phase-segregated two-end line differential protection and control IED (intelligent electronic device) designed for utility and industrial power systems, including looped and meshed distribution networks with or without decentralized power generation
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 6
RED615 Selective protection for a dedicated zone
Unit protection for applications calling for absolutely selective protection for a dedicated zoneMain application area: two-terminal protection for cable or overhead line feeders Phase segregated protection algorithmProtection communication using a dedicated optical linkDesigned for IEC 61850
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 7
RED615 A pre-configured IED
Three standard configurations availablePossibility to add, delete and change signal connections for binary inputs, binary outputs and between function blocks using PCM600The number and type of function blocks is fixed
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 8
RED615 Standard configurations
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Standard configuration ALine differential protection
Standard configuration BLine differential protection with directional earth-fault protection
Standard configuration CLine differential protection with non-directional earth-fault protection
© ABB OyJuly 1, 2009 | Slide 9
RED615 Standard configurations, page 1(3)
Standard configuration A B CProtection functionsLine differential protection and related measurements, stabilized and instantaneous stages
Three-phase non-directional overcurrent, low stage, instance 1
Three-phase non-directional overcurrent, high stage, instance 1
Three-phase non-directional overcurrent, high stage, instance 2
Three-phase non-directional overcurrent, instantaneous stage, instance 1
Non-directional earth-fault protection, low stage (SEF), instance 1 - -
Non-directional earth-fault protection, low stage, instance 2 - -
Non-directional earth-fault protection, high stage, instance 1 - -
Non-directional earth-fault protection, instantaneous stage, instance 1 - -
Directional earth-fault protection, low stage (SEF), instance 1 - -
Directional earth-fault protection, low stage, instance 2 - -
Directional earth-fault protection, high stage, instance 1 - -
Transient / intermittent earth-fault protection - -
= included, = optional at the time of order
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 10
RED615 Standard configurations, page 2(3)
Standard configuration A B CProtection functions, cont’dNon-directional (cross-country) earth-fault protection, using calculated Io
- -
Negative sequence overcurrent protection, instance 1
Negative sequence overcurrent protection, instance 2
Phase discontinuity protection -
Three-phase thermal protection for feeders, cables and distribution transformers
-
Binary signal transfer
Circuit-breaker failure protection
Three-phase inrush current detector
Master trip, instance 1
Master trip, instance 2
Control functionsCircuit-breaker control
Disconnector position indication, instance 1
Disconnector position indication, instance 2= included, = optional at the time of order
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 11
RED615 Standard configurations, page 3(3)
= included, = optional at the time of order
Standard configuration A B CControl functions, cont’dDisconnector position indication, instance 3
Earthing switch indication
Auto-reclosing - O O
Condition monitoringCircuit-breaker condition monitoring -
Trip circuit supervision, instance 1
Trip circuit supervision, instance 2
Current circuit supervision
Protection communication supervision
MeasurementDisturbance recorder
Three-phase current measurement
Sequence current measurement
Residual current measurement -
Residual voltage measurement - -
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 12
Application examples
© ABB OyJuly 1, 2009 | Slide 13
RED615 Why line differential protection?
Case Overcurrent protection challenges SolutionFault current contribution from more than one source (direction)
Selective protection scheme still required RED615
Protection co-ordination Protection co-ordination based on definite or inverse time delays might result in too high accumulated time delays within the chain of protection devices
RED615
Varying fault current levels Difficult to find protection setting parameters that would suit all cases RED615
Load currents magnitudes close to fault current levels
Difficult to separate fault conditions from normal loading RED615
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 14
RED615 Line differential protection application examples
Parallel feedersLooped feeder constructionDoubled feeders
Two interconnected feeders between a primary substation
Reserve connections or meshed type of network
Distributed generationPower generation at the remote end of the feeder
Weak grid supplying relatively long distribution lines
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 15
RED615 Unit protection with overcurrent back-up protection
The phase currents of CT core #2 are summated externally to the IED, and used as CT supervision (MCS3I) reference current
The two lowest overcurrent stages are used for remote back-up protection
The two highest overcurrent stages are blocked under normal conditions and released in case of protection communication failure
Binary signal transfer, 8 signals for user definable purpose (BST)
Protection communication supervision (PCS)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Standard configuration “A”
© ABB OyJuly 1, 2009 | Slide 16
RED615 Unit protection with directional earth-fault protection
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Standard configuration “B”
The cable CT I0 input is used for directional earth-fault protection and for CT supervision (MCS3I) reference current
Non-directional earth-fault protection stage, based on calculated I0,, for cross-country earth-fault protection
Auto-reclosing option for overheadlines
Thermal overload protection for feeders
The two lowest overcurrent stages are used for remote back-up protection
Two highest overcurrent stages are blocked under normal conditions and released in case of protection communication failure
Binary signal transfer, 8 signals for user definable purpose (BST)
Protection communication supervision (PCS)
© ABB OyJuly 1, 2009 | Slide 17
RED615 Unit protection with non-directional earth-fault protection
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Standard configuration “C”
The fourth CT (I0) input is used for non-directional earth-fault protection and for CT supervision (MCS3I) reference current
The same phase CT cores can be used for main protection and for earth-fault protection (external summation), but in that case the CT supervision shall not be used
Auto-reclosing option for overheadlines
Thermal overload protection for feeders
The two lowest overcurrent stages are used for remote back-up protection
Two highest overcurrent stages are blocked under normal conditions and released in case of protection communication failure
Binary signal transfer, 8 signals for user definable purpose (BST)
Protection communication supervision (PCS)
© ABB OyJuly 1, 2009 | Slide 18
615 series Supported ABB solutions, page 1(2)
The 615 series IEDs together with COM600 constitute a genuine IEC 61850 solution for reliable power distribution in utility and industrial power systemsThe native IEC 61850 support offer:
Fast software based communicationContinuous supervision of the integrity of the protection and communication systemInherent flexibility for reconfiguration and upgrades
ABB’s Connectivity Package concept enables:
Streamlining of the system engineering and IED configurationEasy integration with COM600 and MicroSCADA Pro
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Supported ABB solutions Version
Station Automation COM600 3.3 or later
MicroSCADA Pro 9.2 SP1 or later
© ABB OyJuly 1, 2009 | Slide 19
615 series Supported ABB solutions, page 2(2)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
The 615 series IEDs complemented with COM600 offer several benefits:
Enhanced substation level functionality using the data content of the bay level IEDsA web HMI providing single-line mimic diagrams for switchgear bay solutionsCOM600 can be used as a local data warehouse for technical documentation and for network dataExtensive reporting and analyzing of network fault situationsSeamless connectivity to MicroSCADAPro and System 800xA
Industrial example
Utility example
© ABB OyJuly 1, 2009 | Slide 20
Hardware and options
© ABB OyJuly 1, 2009 | Slide 21
RED615
[X000] Communication module with optional station bus ports
[X100] Power supply and binary output module
[X110] Binary I/O module [X120] Basic analog input module[X130] Additional binary I/O module
(option)
Hardware modules
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 22
RED615
Line differential protection link:
100BASE-FX with a fibre-optic LC connector, multi mode or single mode
Station bus options:
100BASE-TX with a RJ-45 connector
Serial (RS-485):Screw terminal connector
2-wire or 4-wire connection
Serial (ST connector)Glass fibre
Communication module variants [X000]
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 23
RED615
Power supply options:
48 V…250 V DC, 100 V…240 V AC
Four power output contacts capable of direct CB operation
Two contacts with integrated trip circuit supervision; also to be used with double-pole operation
Two signal output contacts (1 changeover, 1 normally open)
IRF output for self-supervision signalling
Power supply and binary output modules [X100]
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 24
RED615Binary I/O module [X110]
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
8 binary inputs6 inputs, grouped in pairs of two 2 inputs, separated (potential free)
4 binary outputs3 outputs, changeover contacts1 output, normally open
Selectable binary input thresholds(17 – 186 V DC)
© ABB OyJuly 1, 2009 | Slide 25
RED615
Four analog current inputs (I0 ,IL1, IL2, and IL3), user selectable 1 A or 5 AI0 used as current circuit supervision reference current
One voltage input U0 (std. conf B) alt. a fourth binary input with dedicated groundThree binary inputs (common ground), thresholds selectableBoth for ring and pin type wire terminals
Max. wire 1 x 6 mm2 or 2 x 2.5 mm2
Basic analog input modules [X120]
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 26
RED615Input / output overview
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Standard configuration
Analog inputs Binary inputs/outputs
CT VT BI BO
A 4 - 12 (18) 1) 10 (13) 1)
B 4 1 11 (17) 1) 10 (13) 1)
C 4 - 12 (18) 1) 10 (13) 1)
1) With optional binary I/O module ( )
© ABB OyJuly 1, 2009 | Slide 27
Functionality highlights
© ABB OyJuly 1, 2009 | Slide 28
RED615
Stabilized low stage and instantaneous high stageThe protection algorithm calculation is performed both in the local and the remote IEDDirect intertrip between line ends ensures simultaneous tripping of the local and the remote CB Detection (blocking) for inrush conditions based on the second harmonicPossibility to introduce either definite or inverse time delay for the stabilized low stage
Line differential protection
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 29
RED615
Small tapped loads can be included inside the LD protection zoneLD protection selectivity towards the protections on the LV-side of the power transformer can be achieved by introducing a time delay for the low set stageFaults on the feeder with low fault impedance (=> high fault current) cleared by the high set stage
Line differential protection, cont’d
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Reach of the instantaneous high stage
Reach of the stabilized low stage with inverse time delay
© ABB OyJuly 1, 2009 | Slide 30
RED615
Current transformer ratio correction factor Maximum ratio difference 1:5
Local and remote current transformers secondary side star-point selection
Both end on the busbar side or on the line side (by default)One end on the busbar side and the other end on the line side
Line differential protection, cont’d
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 31
RED615
Comparing calculated I0 to a measured I0(I_REF) from a different core or from a core balance current transformerWill block line differential and negative sequence overcurrent protection by default if the calculated and the measured I0 values do not matchOperation is indicated by an alarm LEDEnabled on load current levelsCan be switched “OFF” if required, or if there is no connected reference current measurement
Current circuit supervision
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 32
RED615
12 analog channels and 64 binary channelsTriggering by:
Analog or binary channelManual or periodic command
Recording modes:Wave form or trend
Selectable sampling rate, 32/16/8 samples per cycleMax 2 X 10 sec using the highest sampling rate and maximum number of recorded channels
Disturbance recorder
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 33
RED615
Non-volatile memory for:
Setting values
Configuration
Trip lock-out
Disturbance recorder data
Up to 50 event codes
Recorded data of the four latest events with time stamp
Operation indications and alarm LEDs show the status of the IED
Operation traceability
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 34
RED615
Continuous monitoring of: Memory circuits (RAM, ROM, EEPROM)CPU operation and program executionInternal supply voltagesInternal trip path continuityExternal trip circuit (TCS)Light sensor inputsHardware and software configuration
Self-supervision
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 35
RED615
Control of one circuit breaker
Dedicated push-buttons for opening and closing of the CB
Interlocking schemes
Control functions
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 36
RED615
Individual user accounts with role-based access controlFour access levels: viewer, operator, engineer and administrator levelApplies to:
Front-panel user interfaceWeb-browser based user interfacePCM600
Administrator programmable passwords
Access control
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 37
Communication
© ABB OyJuly 1, 2009 | Slide 38
615 series Designed for IEC 61850
Native support for IEC 61850 communication between devices in substationsIEC 61850 enables “GOOSE” (GenericObject Oriented Substation Event) horizontal communication between IEDsRED615 can simultaneously report events to five different clients on the station busRED615 also supports:
Modbus TCP/IP and RTU / ASCII DNP3 TCP/IP and serial IEC 60870-5-103
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 39
615 series IEC 61850 GOOSE communication
Standardized horizontal communication enables interoperability between any IEDs supporting GOOSE communicationUsed for transmitting binary process data to peer IEDs within a substationEthernet technology offers a fast and reliable station bus for the transfer of dataThe publisher-subscriber principle allows the IEDs to send and/or receive time critical data
Station Automation COM600
Station bus IEC 61850
Network control centreMicroSCADA Pro
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 40
615 series GOOSE communication benefits
Expandability and flexibility:Flexible modifications without changing the wiring between the IEDsNo IED I/Os are needed for the transer of data between the IEDsReduced wiring between the IEDsPossible to add functionality like interlocking schemes between the cubicles in existing switchgear (retrofit)
Supervised data transfer (connection and data quality)RED615 meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 41
RED615
On detecting a fault on the outgoing feeder IED B sends a trip command to CB “B” and initiates the CB failure protection function CB “B” fails to openThe CB failure protection function of IED B sends a trip command to IED A using GOOSEThe use of GOOSE communication eliminates the need for dedicated wiring CB failure protection can be added without renewing the wiring and with minimum disturbance to the process
GOOSE - Breaker failure protection
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
IED B
IED A
IED C
GOOSE message
© ABB OyJuly 1, 2009 | Slide 42
RED615
Physical communication link:A dedicated pair of optical single mode or multimode fibresOptical LCDistance: < 2 km (multi mode),2-20 km (single mode)
Protection communication supervision:Continuous supervision of sending and receiving of messagesIn the event of a communication failure an alarm is issued and the LD protection is blocked
Protection communication
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Fibre optic communication
link
IED 1
IED 2
© ABB OyJuly 1, 2009 | Slide 43
RED615
The communication link is used for both the LD protection communication and the binary signal transfer (BST)
The current phasor data, for each phase, is exchanged between the terminals 8 times per cycle (20 ms at 50 Hz)Simultaneous tripping of both the local and the remote circuit breaker8 user definable binary signals can be transferred between the terminals
Protection communication, cont’d
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Fibre optic communication
link
IED 1
IED 2
© ABB OyJuly 1, 2009 | Slide 44
RED615
No external time-synchronization devices(GPS) are neededCommunication propagation delay measuringof symmetrical communication linksSampling differential time calculationalgorithmSynchro-phasors in common time reference
Protection synchronisation
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 45
RED615
Binary information transfer between the line ends (the two IEDs located apart from each other) using the protection communication link
Typically used for interlocking and inter-tripping schemes
For user definable purposes, (8 signals) duplex communication
Fast communication between two RED615 IEDs (< 5 ms)
Fully user configurable using the signal matrix tool in PCM600
Binary signal transfer (BST)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 46
RED615Binary signal transfer, example 1
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Output 1
Output 8
Input 1
Input 8
BI
BO
BSTGGIO
Output 1
Output 8
Input 1
Input 8
BSTGGIO
Protection communication
© ABB OyJuly 1, 2009 | Slide 47
RED615Binary signal transfer, example 2
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Output 1
Output 8
Input 1
Input 8
BSTGGIO
Output 1
Output 8
Input 1
Input 8
BSTGGIO
Protection communication
BI
PHLPTOC
Block
I>
© ABB OyJuly 1, 2009 | Slide 48
RED615Binary signal transfer, example 3
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Output 1
Output 8
Input 1
Input 8
BSTGGIO
Output 1
Output 8
Input 1
Input 8
BSTGGIO
Protection communication
PHHPTOC 1
Block
3I>>
PHLPTOC
Start
3I>
© ABB OyJuly 1, 2009 | Slide 49
RED615Supported station communication protocols
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
= supported, - = not supported
Interfaces /Protocols
Ethernet(RJ-45)
Serial(RS-485 / RS-232)
+ IRIG-B
Serial(fibre ST)+IRIG-B
IEC 61850-8-1 - -
IEC 60870-5-103 -
DNP3 TCP/IP - -
DNP3 serial -
Modbus TCP/IP - -
Modbus RTU/ASCII -
© ABB OyJuly 1, 2009 | Slide 50
RED615
Ethernet-based time synchronization:SNTP (Simple Network Time Protocol)
With special time synchronization wiring:IRIG-B (Inter-Range Instrumentation Group - Time Code Format B)
Remote-end station time reference:Line-differential
Time stamp resolution: 1 ms
Station time synchronization
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 51
RED615
RJ45 Ethernet connectorIED configuration using PCM600IED access using the web-browser-based HMILED indication on the local HMI during data transferBoth crossover and regular cables can be used
Front port communication
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 52
Mechanical design
© ABB OyJuly 1, 2009 | Slide 53
615 series
Speeds up installation, maintenance and testing of the protectionContributes to a shortened MTTR (mean time to recover)Allows the cases to be installed and wired before the plug-in units are deliveredMechanical coding system for preventing insertion of a wrong plug-in unit in a caseSealable pull-out handle to prevent accidental (or unauthorized) withdrawal of the plug-in unit
Patented and compact plug-in design
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 54
615 series
Height: frame 177 mm, case 164 mmWidth: frame 177 mm (4U), case 160 mmDepth: case 155 mm
IED case and plug-in unit
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
IP classification
IP54 When panel- mounted
IP20 Rear side
© ABB OyJuly 1, 2009 | Slide 55
615 series
• Flush mountingThe same cut-out on the cubicle front as for the 610 series IEDs (height: 161.5 ±1, width: 165.5 ±1)
• Semi-flush mountingWith a 50 mm rising frame
Flush and semi-flush mounting
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 56
615 series
• Semi-flush mounting in a 25° angleWith special accessories
• Wall mountingThe IED can be tilted for easy access to the connectors
Semi-flush and wall mounting
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 57
615 series
• Mounting using a 19” mounting panelOne or two IEDs
• Mounting with an RTXP test switch in a 19” rackFor routine testing purposes
Panel and rack mounting
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 58
Front panel HMI
© ABB OyJuly 1, 2009 | Slide 59
615 series Front panel HMI
4 x 16 characterdisplay (LCD)
Front communication port
Three dedicated LEDs: Ready, Start,Trip
11 programmable LEDs
CB Control, OPEN and CLOSE buttons
ESC button
Navigation buttons
ENTER buttonCLEAR button
MENU button
LOCAL/REMOTE button, HELP
AUTHORIZATION
© ABB OyJuly 1, 2009 | Slide 60
615 series Display options
Large LCD, mono-spaced 10 x 20 characters, variable width 8 x 8 (or more) charactersSmall LCD, mono-spaced 4 x 20 characters, variable width 4 x 8 (or more) charactersBackground light with power-saving mode
Option: Small LCD
Large LCD
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 61
RED615 Display readouts
IEC 61850 naming, “classic”IEC symbols or ANSI codes: (LNPLDF, 3ΔI > , 87L)Fault indicationsFour fault recordings with time stampMeasurements:
Currents Historical data
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 62
RED615 Display readouts, cont’d
Name or code of protected objectsSettings in 4 setting groupsConfigurations such as protocol settings etc.Product information, serial number, software version, identification etc.
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 63
Tools
© ABB OyJuly 1, 2009 | Slide 64
RED615Tools
Tools VersionPCM600 2.0 SP2 or later
Web-browser-based user interface IE 7.0 or later
RED615 Connectivity Package, including the line differential characteristics tool
2.5 or later
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 65
PCM600 Protection and control IED Manager
A common tool for new and existing protection IEDs and terminalsIED-specific connectivity packages enable the use PCM600 for different ABB protection IEDs and terminalsSupports IEC 61850GOOSE messaging configuration (PCM600 Engineering Pro)IED interaction using:
Corporate LAN/WANThe IED’s communication port
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 66
PCM600 Tools
All tools needed to manage RED615 are included in PCM600:
Signal matrix Signal monitoring IED parameter settingDisturbance recorder handling and viewingIEC 61850 (GOOSE) communication configurationModbus communication configurationDNP3 communication configurationIEC 60870-5-103 communication configurationAccess control management
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 67
PCM600 Power system overview
PCM600 offers the possibility to create a tree-structure representing your individual power system, including:
Project nameSubstationsVoltage levels Bays IEDs/terminals
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 68
615 series Web-browser based user interface
Local or remote IED access using an IE 7.0 (or later) web browserDisabled by default, enabled by PCM600 or the local front-panel interfaceFunctions:
Viewing of alarm LEDs and event listsSaving of event dataParameter settingSignal monitoringMeasurement viewingPhasor diagram viewingReading of disturbance records
User access level authentication
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 69
RED615 Differential characteristics tool
Included in the connectivity packageVisual presentation of the differential protection characteristicsPossibility to read fault records from the IED and present them on the characteristicWriting of parameters to the IED using the local HMI, the web-browser based HMI or PCM600
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 70
Conclusions
© ABB OyJuly 1, 2009 | Slide 71
RED615
Phase segregated line differential protection with two stagesIEC 61850 station communication including GOOSE messagingBinary signal transfer between the IEDs in the substations (located apart from each other)Extensive supervision on protection communication and CT secondary connectionsAll I/Os are fully matrixed, thus enabling optimal use Rapid set-up and commissioning, pre-configured IEDsVersatile tools
Product summary
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 72
RED615Selection and ordering data, digit 1-3
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 73
RED615Selection and ordering data, digit 4-8
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 74
RED615Selection and ordering data, digit 9-11
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 75
RED615Selection and ordering data, digit 9-11 cont’d
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 76
RED615Selection and ordering data, digit 12-18
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 77
RED615Selection and ordering data, ordering code
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 78
RED615Product pages on the web
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB OyJuly 1, 2009 | Slide 79
Please visit our website for the latest product informationwww.abb.com/substationautomation