© ABB GroupMay 13, 2010 | Slide 1 | 1MRS756700 B

Relion® 615 series Ver 2.0General Presentation

ABB Oy Distribution Automation

© ABB Group May 13, 2010 | Slide 2

Relion® 615 series Contents

The 615 series of IEDs

Common features of the 615 series

Feeder Protection and Control REF615

Line Differential Protection and Control RED615

Transformer Protection and Control RET615

Motor Protection and Control REM615

Conclusions

© ABB Group May 13, 2010 | Slide 3

Introduction Relion® 615 series

© ABB Group May 13, 2010 | Slide 4

Relion® 615 seriesProducts

The 615 series IEDs (intelligent electronic devices) members of ABB’s Relion® product family

The 615 series IEDs are characterized by their compactness and withdrawable design

615 series products:

Feeder Protection and Control REF615

Line Differential Protection and Control RED615

Transformer Protection and Control RET615

Motor Protection and Control REM615

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 5

Common featuresRelion® 615 series

© ABB Group May 13, 2010 | Slide 6

Relion® 615 series IEC 61850 based connectivity and interoperability

Native support for IEC 61850 communication between devices in substations (including GOOSE messaging)

Meets the GOOSE requirements for tripping applications in distribution substations as defined by the IEC 61850 standard

The 615 series also supports:

Modbus TCP/IP and RTU / ASCII

DNP3 TCP/IP and serial

IEC 60870-5-103

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 7

Relion® 615 seriesPatented plug-in design

Speeds up installation, maintenance and testing of the protection

Contributes to a shortened MTTR (mean time to recover)

Allows the cases to be installed and wired before the plug-in units are delivered

Mechanical coding system for preventing insertion of a wrong plug-in unit in a case

Sealable pull-out handle to prevent accidental (or unauthorized) withdrawal of the plug-in unit

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 8

Relion® 615 seriesPre-configured functions

Ready-made adaptations (standard configurations)

The IEDs can be rapidly set up and commissioned once they have been given the application-specific settings

The standard signal configuration setting can be adjusted using the PCM600 setting and configuration tool

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 9

Relion® 615 seriesControl functions

Control of one circuit-breaker via the IED’s HMI or a remote control system

Dedicated push-buttons for opening and closing of the CB

Interlocking schemes

Optional multi-shot auto-reclosing of one CB (REF615 and RED615)

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 10

Relion® 615 series Enhanced disturbance recorder functionality

Records up to 12 analog channels and 64 binary channels

Flexible triggering

Selectable sampling rate offers increased flexibility

The disturbance records can be uploaded to PCM600 for in-depth disturbance and fault analysis

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 11

Relion® 615 seriesOperation traceability

For pre and post fault analysis

Data is stored in non-volatile memory Event log Recorded data Settings and configuration,

trip lock-out, disturbance recorder data

Thermal loading Number of auto-reclosing

shots and starts/trips of the protection stages

CB conditioning monitoring values

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 12

Relion® 615 seriesSelf-supervision functionality

Provides information about the operational availability of the protection

Used for continuous monitoring of the IED itself

Monitors both the state of the hardware and the operation of the software

External trip-circuit supervision (TCS)

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 13

Relion® 615 seriesCircuit-breaker condition monitoring

Provides information for scheduling CB maintenance

Monitors the wear and tear of the circuit-breaker

Circuit-breaker gas pressure

Circuit-breaker spring charging

Circuit-breaker travel time

Circuit-breaker operation counter

Scheduled maintenance

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 14

Relion® 615 seriesRole-based access control

Individual user accounts with role-based access control protects the IED from unauthorized access

Four access levels: viewer, operator, engineer and administrator

Applies to: Front-panel user interface Web browser based user

interface PCM600

Passwords programmable by the administrator

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 15

Relion® 615 series Tools and substation automation products

PCM600 One single tool for managing settings,

signal configuration and disturbance handling

Web browser based user interface Local or remote IED access using an IE

7.0 (or later) web browser

IED specific connectivity packages For automatic configuration via

MicroSCADA Pro, Station Automation Series COM600 or PCM600

Station Automation COM600 ver 3.3

MicroSCADA Pro

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 16

Feeder Protection and Control REF615

© ABB Group May 13, 2010 | Slide 17

REF615 Description

REF615 is a dedicated feeder protection IED designed for the protection, measurement and supervision of utility substations and industrial power systems

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 18

REF615Area of application

Designed for general applications requiring over-current and earth-fault protection

Main application area: cable or overhead line feeders in solidly earthed, resistance earthed, isolated neutral or compensated networks

Optional three-channel arcprotection system

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 19

REF615 Six standard configurations

Std configuration ANon-directional overcurrent and directional E/F protection without CB condition monitoring

Standard configuration BNon-directional overcurrent and directional E/F protection with CB condition monitoring and interlocking schemes

Standard configuration CNon-directional overcurrent and non-directional E/F protection without CB condition monitoring

Standard configuration DNon-directional overcurrent and non-directional E/F protection with CB condition monitoring and interlocking schemes

Standard configuration ENon-directional overcurrent and directional E/F protection with phase-voltage based measurements

Standard configuration FDirectional overcurrent and directional earth-fault protection with phase-voltage based measurements, under- / overvoltage and residual overvoltage protection

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 20

REF615Optional arc protection

Increases safety during maintenance work

Reduces material damage

Minimizes system downtime

Continuously supervises the CB, cable and busbarcompartment of metal-enclosed switchgear

Same lens and optic fibre as for REA 107

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 21

Line Differential Protection and Control RED615

© ABB Group May 13, 2010 | Slide 22

RED615Description

RED615 is a phase-segregated two-end line differential protection and control IED designed for utility and industrial power systems, including looped and meshed distribution networks with or without decentralized power generation

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 23

RED615Grounds for using line differential protection

RED615Difficult to separate fault conditions from normal load conditions

Load current magnitudes close to fault current levels

RED615Difficult to find protection settings that would suit all cases

Varying fault current levels

RED615Protection co-ordination based on definite or inverse time delay might result in too long accumulated time delays within the chain of protection devices

Protection co-ordination

RED615Selective protection scheme still required

Fault current contribution from more than one direction

SolutionOvercurrent protection challengesCaseIntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 24

RED615Selective protection for a defined zone

Unit protection for applications requiring absolutely selective protection for a defined zone

Main application area: two-terminal protection for cable or overhead line feeders

Phase-segregated protection algorithm

Protection communication over a fibre-optic link

GOOSE messaging in combination with binary signal transfer enable smart protection schemes for dynamic power systems

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 25

RED615 Three standard configurations

Standard configuration ALine differential protection

Standard configuration BLine differential protection with directional earth-fault protection

Standard configuration CLine differential protection with non-directional earth-fault protection

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 26

RED615Line differential protection application examples

Parallel feeders

Looped feeder configuration Doubled feeders

Two interconnected feeders Reserve connections or meshed type

of network Distributed generation

Power generation at the remote end of the feeder

Weak grid supplying relatively long distribution lines

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 27

RED615Supervised protection communication

Fibre optic communicationlink

IED 2

IED 1

A pair of optical single mode or multimode fibres form the protection communication link

Distance recommendations < 2 km (multi mode) 2-20 km (single mode)

Continuous supervision of sending and receiving of messages ensures reliable protection communication

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 28

RED615Binary signal transfer

Binary signal transfer (BST) between the two line ends using the protection communication link

Typically used for interlocking and inter-tripping schemes

Eight signals for user definable purposes

Fast communication between two RED615s (<5 ms)

Fully user configurable using the signal matrix tool in PCM600

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 29

Transformer Protection and Control RET615

© ABB Group May 13, 2010 | Slide 30

RET615Description

RET615 is a dedicated transformer protection and control IED for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 31

RET615Area of application

Designed for unit protection applications calling for stabilized differential protection

Main application area: two winding transformers in power distribution networks

Optional three-channel arc protection system

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 32

RET615 Four standard configurations

Standard configuration AThree-phase transformer differential protection for two-winding transformers, with numerical restricted earth-fault protection for the high-voltage (HV) side

Standard configuration BThree-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side

Standard configuration CThree-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the high-voltage (HV) side

Standard configuration DThree-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the low-voltage (LV) side

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 33

Motor Protection and Control REM615

© ABB Group May 13, 2010 | Slide 34

REM615Description

REM615 is a dedicated motor protection and control IED designed for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process industry

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 35

REM615Area of application

Circuit-breaker or contactor controlled high-voltage (HV) motors

Contactor controlled medium sized and large low-voltage (LV) motors

Protection for a variety of drives such as:

Pumps and conveyors

Crushers and choppers

Mixers and agitators

Fans and aerators

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 36

REM615 One standard configuration

Standard configuration CMotor protection with current and voltage based protection and measurements functions

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 37

REM615Motor protection functionality

REM615 includes the needed functionality to manage motor starts, normal drive operations and fault clearance Thermal overload protection

Startup supervision

Emergency start

Runtime jam protection

Negative sequence overcurrent protection

Loss-of-load supervision

Phase reversal protection

Optional arc protection with three sensors

Motor start and stop buttons on the local HMI

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 38

ABB solutionsRelion® 615 series

© ABB Group May 13, 2010 | Slide 39

Relion® 615 series Supported ABB solutions, page 1(2)

The 615 series IEDs together with COM600 constitute a genuine IEC 61850 solution for reliable power distribution in utility and industrial power systems

The native IEC 61850 support offer: Fast software based communication

Continuous supervision of the integrity of the protection and communication system

Inherent flexibility for reconfiguration and upgrades

ABB’s Connectivity Package concept enables:

Streamlining of the system engineering and IED configuration

Easy integration with COM600 and MicroSCADA Pro

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 40

Relion® 615 series Supported ABB solutions, page 2(2)

The 615 series IEDs complemented with COM600 offer several benefits:

Enhanced substation level functionality using the data content of the bay level IEDs

A web HMI providing single-line mimic diagrams for switchgear bay solutions

COM600 can be used as a local data warehouse for technical documentation and for network data

Extensive reporting and analyzing of network fault situations

Seamless connectivity to MicroSCADAPro and System 800xA

Industrial example

Utility example

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions

© ABB Group May 13, 2010 | Slide 41

ConclusionsRelion® 615 series

© ABB Group May 13, 2010 | Slide 42

Relion® 615 seriesConclusions

Native support for IEC 61850 and GOOSE messaging

Patented plug-in design for flexible mounting, fast installation and commissioning

Pre-configured IEDs

The 615 series IEDs include a comprehensive range of monitoring and watchdog functions

Versatile tools including IED specific connectivity packages

IntroductionCommon featuresREF615RED615RET615REM615SolutionsConclusions