Jornada Técnica
MATERIALES DE CONSTRUCCION
Los componentes que hacen un rociador son: Cuerpo Deflector Elemento Fusible o Ampolla (bulbo) Pip Cap (Gorra) Pintle Screw (Tornillo) Resorte Belleville Los Rociadores Viking utilizan latón de bajo contenido de zinc para suministrar un cuerpo mas “elástico”. Este contenido de zinc bajo protege al rociador de de-zincaficacion. El Resorte Bellville sella la salida del rociador. Este asiento metal-metal permite que el rociador opere aunque no halla presión en la tubería/rociador.
Aprobaciones
UL & c-UL (ULC) NFPA & Requerimientos UL
FM Requerimientos FM
(NFPA = mínimo)
LPC LPC Standard
VDS VDS Standard
NYC & LA Aprobaciones Especificas
Agencia Norma
Tipos de Rociadores
Tipo Control – Respuesta Standard y Respuesta Rápida
Cobertura Standard
Montante
Pendiente
Pared (Sidewall)
Cobertura Extendida
Montante
Pendiente
Pared (Sidewall)
Tipo Control Aplicación Especial
Rociador Gota Gorda (Large Drop)
Supresión
ESFR – Montante y Pendiente
Residencial
Rociadores Tipo Control
Rociadores Tipo Control están separados en las siguientes categorías:
Cobertura Standard - Respuesta Standard
Cobertura Standard - Respuesta Rápida
Cobertura Extendida – Respuesta Standard
Cobertura Extendida – Respuesta Rápida
Tubería Seco – Respuesta Standard/Respuesta Rápida
Almacenamiento – Respuesta Standard/Respuesta Rápida
Identificación de Rociadores
Índice de Temperatura de
Activación
155°F 175°F 200or212°F 286°F 360°F 500°F
(68°C) (79°C) (93or100°C) (141°C) (182°C) (260°C)
Ordinario Intermedio Alto Extra Ultra
Alto Alto
Máx Temp Máx Temp Máx Temp Máx Temp Máx Temp
Techo Techo Techo Techo Techo
100°F 150°F 225°F 300°F 465°F
(38°C) (65°C) (107°C) (149°C) (240°C)
Rojo Amarillo Verde Azul Malva Negro
Respuesta Standard – Ampolla de 5 mm
155°F 175°F 200or212°F 286°F
(68°C) (79°C) (93or100°C) (141°C)
Ordinario Intermedio Alto
Max Temp Max Temp Max Temp
Techo Techo Techo
100°F 150°F 225°F
(38°C) (65°C) (107°C)
Rojo Amarillo Verde Azul
Respuesta Rapida – Ampolla de 3 mm bulb
Instalado encima de la tuberia
Rociadores Montantes
Rociador Pendiente
Instalado en un techo
falso
Rociador Pendiente
Montado en tuberia
expuesta
Rociadores Pendientes son instalados de bajo de la tuberia o en un techo falso
Rociadores de Pared normalmente son instalados en la paredl
Horizontal Sidewall Sprinkler
Factor K del Rociador Los factores K son conocidos como los coeficiente de
descarga. Lo mas grande el factor K, la mayor descarga
de agua bajo una presion en particular. Hay (3)
tamanos de roscas actualmente utilizadas, ½”, ¾” y 1”.
No solamente utilice el diametro de la rosca cuando
Este reemplazando un rociador. Identifique la
orientacion, Factor K y Temperatura antes de
remplazar el rociador.
Factor Knominal(USA)
gpm/(psi)1/2
Intervalo devalores de K
(USA)gpm/(psi)1/2
Intervalo devalores de K
(Métrico)l/min/bar1/2
Porcentaje dedescarga con
relación al estándar K = 5.6
Tipo de
Rosca
1.41.92.84.25.68.0
11.214.016.819.622.425.228.0
1.3-1.51.8-2.02.6-2.94.0-4.45.3-5.87.4-8.2
11.0-11.513.5-14.516.0-17.618.6-20.621.3-23.523.9-26.526.6-29.4
19-2226-2938-4259-6476-84
107-118159-166195-209231-254272-301311-343349-387389-430
2533.35075
100140200250300350400450500
½” NPT½” NPT½” NPT½” NPT½” NPT
¾” o ½” NPT¾” o ½” NPT
¾” NPT¾” NPT1” NPT1” NPT1” NPT1” NPT
Factores K estándar (USA y métricos)
SENSIBILIDAD TÉRMICA
Índice de tiempo de respuesta
(RTI)
SENSIBILIDAD DE LOS
SPRINKLERS
• RESPUESTA ESTANDAR
– 3 Min. 51 Sec. Room Fire Test
– 100 Sec. Plunge Test
• RESPUESTA RÁPIDA
– 75 Sec. Room Fire Test
– 14 Sec. Plunge Test
• RESIDENCIALES
– Special Fire Test
– 14 Sec. Plunge
Plunge Oven
Índice de tiempo de
respuesta
(RTI)
• Respuesta rápida RTI < 50
• Respuesta especial 50 <RTI < 80
• Respuesta normal RTI > 80
Strut – 110 m-s½
Glass Bulb (5mm) - 105 m-s½ Fusible Link – 26 m-s½
Glass Bulb (3mm) - 36 m-s½ Glass Bulb (2.5mm) - 22 m-s½
Heat Fin - 26 m-s½
Rociadores de Cobertura Estandar
Pendiente y Montante
Rociadores de Cobertura Estandar
Pendiente o Montante
• Distribution 16 ft (4,9 m) dia @ 4 ft (1,2 m) debajo del deflector
15 gpm (0.95 L/s) for 1/2” (15 mm) “orificio estandar”
21 gpm (1,3 L/s) for 3/4” (20 mm) “orificio grande”
Rociadores Cobertura
Estandar
Rociadores de Cobertura Estandar
Pendiente o Montante
Espacio Rociadores Estandar (Area de Cobertura)
Riesgo Liviano (definido por NFPA 13) : 225 sq. ft. max
Riesgo Ordinario (definido por NFPA 13) : 130 sq. ft. max
Riesgo Extra (as defined by NFPA 13) : 100 sq. ft. max
(Nota: areas para sistemas calculados hidraulicamente)
15’-0”
(4,57m) 15’-0”
(4,57m)
15’-0”
(4,57m)
NFPA 13 limita la area de cobertura para Riesgos Livianos
a 225 sq. ft. por rociador
Rociadores de Cobertura Estandar
*Plan View
Classification of Occupancies
Upright and pendent spray sprinklers shall be permitted in all
occupancy hazard classifications and building construction types.
5.1* Classification of Occupancies.
5.1.1 Occupancy classifications for this standard shall relate to
sprinkler design, installation, and water supply requirements only.
5.1.2 Occupancy classifications shall not be intended to be a general
classification of occupancy hazards.
5.2* Light Hazard Occupancies.
Light hazard occupancies shall be defined as occupancies or portions
of other occupancies where the quantity and/or combustibility of
contents is low and fires with relatively low rates of heat release are
expected.
EXAMPLES: Churches, Clubs, Hospitals, Museums, Offices,
Restaurant Seating Areas
10’-0”
(3,04m)
10’-0”
(3,04m)
13’-0”
(3,97m)
NFPA 13 limita la area maxima de cobertura para riesgo
Ordinario a 130 sq. ft. por rociador
Rociadores Cobertura Estandar
*Plan View
Classification of Occupancies Upright and pendent spray sprinklers shall be permitted in all occupancy hazard
classifications and building construction types.
5.1* Classification of Occupancies.
5.1.1 Occupancy classifications for this standard shall relate to sprinkler design,
installation, and water supply requirements only.
5.1.2 Occupancy classifications shall not be intended to be a general classification of
occupancy hazards.
5.3.1* Ordinary Hazard (Group 1).
Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of
other occupancies where combustibility is low, quantity of combustibles is moderate,
stockpiles of combustibles do not exceed 8’-0”, and fires with moderate rates of heat
release are expected.
Examples:Restaurant Service Areas, Bakeries, Automobile Parking and
Showrooms, Laundries
5.3.2* Ordinary Hazard (Group 2). Ordinary hazard (Group 2) occupancies shall be defined
as occupancies or portions of other occupancies where the quantity and combustibility of
contents are moderate to high, stockpiles do not exceed 12’, and fires with moderate to
high rates of heat release are expected.
Examples: Dry Cleaners, Horse Stables, Machine Shops, Library
Stack Rooms, Mercantile, Confectionary Products
10’-0”
(3,04m) 10’-0”
(3,04m)
10’-0”
(3,04m)
NFPA 13 limita la area maxima de cobertura para riesgo
Extra a 100 sq. ft. por rociador
Standard Coverage Sprinklers
*Plan View
Classification of Occupancies Upright and pendent spray sprinklers shall be permitted in all occupancy hazard
classifications and building construction types.
5.1* Classification of Occupancies.
5.1.1 Occupancy classifications for this standard shall relate to sprinkler design,
installation, and water supply requirements only.
5.1.2 Occupancy classifications shall not be intended to be a general classification of
occupancy hazards.
5.4.1* Extra Hazard (Group 1). Extra hazard (Group 1) occupancies shall be defined as
occupancies or portions of other occupancies where the quantity and combustibility of
contents are very high and dust, lint, or other materials are present, introducing the
probability of rapidly developing fires with high rates of heat release but with little or no
combustible or flammable liquids.
Examples: Combustible Hydraulic Fluid Use Areas, Metal Extruding,
Saw Mills, Upholstering with Plastic Foams, Rubber Reclaiming
5.4.2* Extra Hazard (Group 2). Extra hazard (Group 2) occupancies shall be defined as
occupancies or portions of other occupancies with moderate to substantial amounts of
flammable or combustible liquids or occupancies where shielding of combustibles is
extensive.
Examples: Flammable Liquids Spraying, Open Oil Quenching,
Plastics Processing, Solvent Cleaning, Varnish and Paint Dipping
Rociadores Cobertura Estandar
Pendientes o Montantes
Presion Minima de operacion es 7 psi. Flujo por rociador
Es determinado por area x densidad o presion minima
Multiplicada por la raiz cuadrada de la presion minima
(cual sea la mayor)
Flujo Minimo Rociador
Q = Area x Densidad
Q = K x P
P = (Q/K)2
K = Q/ P
Q = Flujo Agua
K = Coefficiente de
Descarga
P = Presion
15’-0”
(4,57m) 15’-0”
(4,57m)
15’-0”
(4,57m)
Densidad requerida para Riesgo Ligero es .10 gpm per sq. ft.
Descarga Minima por rociador espacio 225 sq. ft. es
Determinado por area x densidad = Q
EJemplo: .10 gpm per sq. ft. x 225 sq. ft. = 22.5 gpm
*Plan View
10’-0”
(3,04m) 10’-0”
(3,04m)
13’-0”
(3,96m)
Densidad req. para Riesgo Ordinario 1 es .15 gpm per sq. ft.
Descarga Minima por rociador espacio 130 sq. ft. es
Determinado por area x densidad = Q
Ejemplo: .15 gpm per sq. ft. x 130 sq. ft. = 19.5 gpm
*Plan View
10’-0”
(3,04m)
10’-0”
(3,04m)
13’-0”
(3,96m)
Densidad req. para Riesgo Ordinario 2 es .20 gpm per sq. ft.
Descarga Minima por rociador espacio 130 sq. ft. es
Determinado por area x density = Q
Ejemplo: .20 gpm per sq. ft. x 130 sq. ft. = 26 gpm
*Plan View
10’-0”
(3,04m)
10’-0”
(3,04m)
10’-0”
(3,04m)
Densidad Req. para Riesgo Extra 1 is .30 gpm per sq. ft.
Descarga Minima por rociador espacio 100 sq. ft. is
Determinado por area x density = Q
Ejemplo: .30 gpm per sq. ft. x 100 sq. ft. = 30 gpm
*Plan View
10’-0”
(3,04m)
10’-0”
(3,04m)
10’-0”
(3,04m)
Densidad Req. para Riesgo Extra 2 is .40 gpm per sq. ft.
Descarga Minima por rociador espacio 100 sq. ft. es
Determinado por area x density = Q
Ejemplo: .40 gpm per sq. ft. x 100 sq. ft. = 40 gpm
*Plan View
Rociadores Cobertura Estandar
Pared
Debe cumplir con los requeriminetos medios de distribucion
sobre la area de 100 ft2 (9,3 m2) entre dos rociadores a un
espacio de 10 ft. (3,05 m) de separacion para rociadores
estandar de 1/2” (15 mm): 0.05 gpm/ft2 (0.034 L/s/m2) o
0.07gpm/ft2 (0.048 L/s/m2) para rociadores de grande orificios
17/32” (20 mm) : Y todavia proporcionar 3.5% contra la pared en
donde estan instalados los rociadores, para ambos 1/2” and L/O.
DISTRIBUCION ROCIADOR DE PARED
Rociadores Cobertura
Estandar de Pared
Rociadores Cobertura Estandar de
Pared
Espacio Rociador Estandar (Area de Cobertura)
Riesgo Ligero (acuerdo a la NFPA 13) : 196 sq. ft. max
(18,2 sq. m)
Riesgo Ordinario (acuerdo a la NFPA 13) : 100 sq. ft. max
(9,29 sq. m) (Nota: Debe ser listado para Riesgo Ordinario)
14’-0”
(4,27m)
14’-0”
(4,27m)
14’-0”
(4,27m)
Densidad Req. para Riesgo Ligero es .10 gpm
per sq. ft.
Descarga Minima por rociador espacio 196 sq. ft. es
Determinado por area x density = Q
Ejempl: .10 gpm per sq. ft. x 196 sq. ft. = 19.6 gpm
*Plan View
10’-0”
(3,04m) 10’-0”
(3,04m)
10’-0”
(3,04m)
Densidad Req. para Riesgo Ordinario Groupo 1
es .15 gpm per sq. ft.
Descarga Minima por rociador espacio 100 sq. ft. es
Determinado por area x density = Q
Ejemploe: .15 gpm per sq. ft. x 100 sq. ft. = 15 gpm
*Plan View
10’-0”
(3,04m)
10’-0”
(3,04m)
10’-0”
(3,04m)
Densidad Req. para Riesgo Ordinario Group 2
es .20 gpm per sq. ft.
Descarga Minima por rociador espacio 100 sq. ft. es
Determinado por area x density = Q
Ejemplo: .20 gpm per sq. ft. x 100 sq. ft. = 20 gpm
*Plan View
Rociadores Cobertura Extendida
Pendiente y Montante
Rociadores Cobertura Extendida Solo se permiten en areas de Riesgo Ligero
A menos que esten listados especificamente para
areas listadas para Riesgo Ordinario
Rociadores Cobertura Extendida Tienen areas de cobertura maxima de 400 sq. ft.
de acuerdo a NFPA 13. El Espacio esta en
incrementos de 2’-0”, ejemplo: 12’x12’, 14’x14’
16’x16’, 18’x18’, 20’x20’
DISTRIBUCION ROCIADORES • COVERTURA EXTENDIDA
– AREA DEL PISO MAS MOJAR LA PARED
30” (762 mm) ENCIMA DEL PISO ABADO
Model M ECOH-
ELO Pendent
VK534
Model M ECLH-
ELO Pendent
VK608
Model M ECOH-
ELO Upright
VK532
ECOH-K14
Cobertura Extendida- Pendiente
ECLH-ELO Pendiente
Espacio y Descarga Minima