NOx emissions <15 ppm4LN version gas burners (with Flue Gas Recirculation)
infoInformation on Ultra Low NOx gas burners
NOx emissions below 15 ppm:4LN-version Weishaupt monarch® burners
10
20
0
70
80
30
60
40
50
0 25 50 10075
Burner rating [%]
NO
x[p
pm]
The values are based on burner versions on three-pass combustion chambers with medium tem-peratures ≤ 230F (110 °C).
NOx emissions achievable when firing natural gas
For many decades, the Weishauptmonarch® brand has been known fortheir low emissions, robustness andreliable operation.
The 4LN-version of the current WM 20to WM 50 range of Weishaupt monarch®
burners can comply with the most strin-gent environmental standards in forceworldwide. A 4LN-version burner isequipped with a flue gas recirculationsystem (FGR) whose control componentsintegrated with the burner.
Specially designed mixing head assem-bly and digital combustion managementensure that the key characteristics ofWeishaupt burners – reliable ignition, ahigh degree of flame stability and safeoperation – remain very much to thefore.
Version:multiflam® 3LN
Version:1LN
Version:NR
Version:4LN
Air inlet housing with factory-preassembled flue gas recirculation components
Flue gas temperature sensor
FGR butterfly valvewith actuator
Flue gas connection
Burner versions
Version FuelsGas Oil Dual-fuel
ZM-NR ● ● ●
ZM-LN ● – –
ZM-3LN ● ● ●
ZM-4LN ● – –
Version Flue gas recirculation (FGR)Gas Oil
ZM-NR –
ZM-LN –
ZM-3LN –
ZM-4LN ● –
● Standard Optional – Not available
General arrangement of a flue gas recirculation system with a WM-series burner
Capacity graph showing maximum burner capacity at a recirculation rate of 0 % – refer to page 4 for examples of capacity reductions with x% recirculation
FGR butterfly valve and actuator
FGR temperature sensor
Shutoff valve(recommended)
Drain
InsulationFGR pipe
Break point for blanking plate
-2
0
3
5
8
0 2,500 5,000 7,500 10,000 17,500 20,000 30,00015,000 22,500
12
25,00012,500 27,500
-1
1
2
4
6
7
9
10
11
Burner model CapacityWM-G20/2-A ZM-4LN 683–5,120 MBHWM-G20/3-A ZM-4LN 1,195–6,820 MBH
Burner model CapacityWM-G30/1-A ZM-4LN 1,365–12,970 MBHWM-G30/2-A ZM-4LN 1,700–17,000 MBHWM-G30/3-A ZM-4LN 1,700–17,000 MBH
Burner type Capacity WM-G50/1-A ZM-4LN 3,410–25,600 MBH
Com
bust
ion
cham
ber r
esis
tanc
e (“
W.C
.)
Burner capacity [MBH]
Capacity reduction with flue gas recirculation
Stated ratings are based on an airtemperature of 68 F (20 °C) and an installation at sea level. For installations at higher altitudes, a reduction in capacity of 1 % per 328ft (100 m) above sea level should betaken into account.
Why does burner capacity reduce?Equipping a burner with flue gas recirculation reduces its capacity. The ex-tent of the reduction has to be calculatedindividually for each individual installation.
The burner fan was designed to supplycombustion air. If a burner is equippedwith flue gas recirculation, however,then the fan has to draw both air andflue gas and mix the two together. As aconsequence, while the overall volumesupplied by the fan remains the same,the addition of the flue gas reduces thetotal oxygen concentration. With lessoxygen in the combustion air, the burner’scapacity is reduced.
What does flue gas recirculation do?• Reduce oxygen concentration per
unit volume (cu-ft, m3) of air• Increase the air flow speed• Shorten dwell times for combustion
gases in the hot reaction zone• Lower flame temperatures
• Reduce NOx emissions
-2
-1
0
1
2
3
7
12
0 2,000 4,000 6,000 8,000 14,000 16,00010,000 12,000 18,000
8
20,000
4
5
6
9
10
11
7.6
5.2
Burner type WM-G30/3-A ZM-4LNCaspacity range Natural gas 1,700–17,000 MBH
Propane 1,700–17,000MBH
Com
bust
ion
cham
ber r
esis
tanc
e
Burner capacity [MBH]
[“W.C.] Example:
NOx emission 15 ppmBurner rating 10,580 MBHResistance (furnace pressure) 5.2 “w.c. (13 mbar)Installation altitude 1,640 ft (500 m) aslFuel – natural gas 1,000 BTU/ cu-ftFGR take-off point• Flue gas pressure 0 “w.c.• Flue gas temperature 320 F (160 °C)
Weishaupt’s standard conditions for calculatingthe burner’s capacity reduction:
• Combustion chamber 3-pass• FGR pipe length 2.5 x combustion
chamber length• Number of FGR pipe elbows 5• Flue gas pressure 0”w.c. (0 mbar)• Additional fittings none
1 Capacity reduction with FGR referenced to 15 ppm of NOx
1
Order numbers/ availability
Burner Version Order No.model
WM-G20/2-A ZM-4LN 217 218 11
WM-G20/3-A ZM-4LN 217 219 11
WM-G30/1-A ZM-4LN 217 322 12
WM-G30/2-A ZM-4LN 217 323 12
WM-G30/3-A ZM-4LN 217 324 12
WM-G50/1-A ZM-4LN 217 523 13
Gas burners
Burner Version Availabilitytype
WM-G20/2-A ZM-4LN Now
WM-G20/3-A ZM-4LN Now
WM-G30/1-A ZM-4LN Now
WM-G30/2-A ZM-4LN Now
WM-G30/3-A ZM-4LN Now
WM-G50/1-A ZM-4LN Now
WM-G50/2-A ZM-4LN 2018
Availability
6
Low NOx emissions for large burner capacity:The WKmono 80 in 4LN version
WKmono-G80 with flue gas recirculation
FGR connecting elbow with actuator and tempera-ture sensor
multiflam® mixing assembly
Flexibility with flue gas recirculationWhere the most stringent emission limitsfor nitrogen oxides are in force, Weishaupt’s multiflam® technology forgas-fired burners can be combined withflue gas recirculation. Weishaupt takes advantage of the special properties ofthe flame geometry, and with it theadaption to the combustion chamber, toreduce NOx levels.
7
General arrangement of a flue gas recirculation system with a WKmono-series burner
The multiflam® technology develo-ped and patented by Weishaupt is away to reduce nitrogen oxide emis-sions to a minimum.
At the heart of Weishaupt’s multiflam®
technology is a special mixing assemblydesign, which distributes the fuel amongprimary and secondary nozzles. This results in extremely efficient combustionthanks to recirculation of the flue gasesdirectly at the mixing assembly.
If a specific market demands ultra-lowNOx emissions, Weishaupt combinesmultiflam® technology with external fluegas recirculation. This system, which isdesigned for gaseous fuels, reducesNOxemissions to levels that will meetthe most stringent requirements of NOxemissions worldwide.
The compact FGR dosing unit is worthhighlighting. The connecting elbow incorporates the FGR butterfly valveand the associated temperature sensor.This packaged assembly allows the
system to be fully tested at the factoryand avoids additional installation workon site.
The FGR system is controlled by the W-FM 200 combustion manager. An additional software module ensures proper dosing of temperature-compen-sated volume of flue gas at all operatingstages, reliable cold start behaviour andthe highest degree of operational availa-bility.
QRA 73 flame sensor
FGR butterfly valve
Connection hose
W-FM 200 combustion manager(FGR version)
Flue gas temperature sensor
X8-03 X8-02 X8-01 X9-03 X9-02 X9-01 X10-03 X10-02 X10-01
F3/T
4IE
C 1
27-2
/VF1
/T6,
3IE
C 1
27-2
/VF2
/T4
IEC
127
-2/V
X3-01 X3-02 X3-03 X3-04X4-01 X4-02 X4-03X5-01 X5-02 X5-03
V1
PE N L
V1
PE N L LO
IL
LG
AS
min.
max
.LT
(CP
I) L
PE N
V1L
V2L
PVL
SVL
ION
FSV/
QR
I
PE N L
Pow
er Q
RI
QR
B
FLAME
L N G0 G
LIN
E
12VA
C
X7-
03X
7-02
X7-
01
PE
V2
PE
V3
PE
X6-
03X
6-02
X6-
01
Start
Start
H0-Start
PE
SV
PE
PE min
L PE max
L ON
/OFF
3
L
2
INT
GAS
OIL
L
RES
ET
PE N L PE N L(S
TART
)
IGN
ITIO
N
L L
MO
TOR
ALAR
M
L L
FLAN
GE
LSA
FETY
LOO
P
PE LNLI
NE
VOLT
AGE
OIL
OIL
GAS
SIEMENS
Burner ControlFuel Air Ratio ControlLoad ControlOXYGEN CONTROL
FeuerungautomatBrennst.-Luftverbundst.
LeistungsreglerSauerstoffregler
LMV52.200B2 230 VAC -15% /+10%50 or 60 Hz - 6% / + 6%-20°C to + 60°C- 4°F to +140°FFCC: part 15, Class BUse wires accaptablefor at least 90°C / 194°FRefer to data sheet 7550Made in Germany
Rg.5F193CE-0085BL0373
Siemens AG
S 1312120025
1P
DIN
Drain
Insulation Manual shutoffFGR pipe
Break point for blanking plate
Low NOx emissions for large burner capacity:WK-series burners with flue gas recirculation
8
General arrangement of a flue gas recirculation system with WK-series burner and mixing box
Flue gas recirculation is also availa-ble for Weishaupt’s WK-series indus-trial burners. The special modulardesign of the WK-series burners separates burner body from com-bustion air fan, thus facilitating inno-vative and customer-oriented solu-tions.
The mixing boxThe mixing box is developed in a colla-boration with our combustion air fan manufacturer. It is fitted directly to thecombustion air fan and forms a compactassembly with fixed dimensions. The mixing box consists of a housing with anintegrated air damper register for suction control, a flanged connection foreasy installation of the FGR butterflyvalve and a sleeve with inbuilt tempera-ture sensor.
AdvantagesTo the customer, the mixing box presentsmany advantages. Precise site planscan be drawn up, if required, fully encap-sulating sound absorbers can be fabri-cated without the need for on-site mea-surements, installation times arereduced and – the crucial factor forfunctionality – everything is in the rightplace.
All in all, a convincing, complete packa-ged solution.
M
MMMM
M
Mixing boxW-FM 200 combustion manager(FGR version)
X8-03 X8-02 X8-01 X9-03 X9-02 X9-01 X10-03 X10-02 X10-01
F3/T
4IE
C 1
27-2
/VF1
/T6,
3IE
C 1
27-2
/VF2
/T4
IEC
127
-2/V
X3-01 X3-02 X3-03 X3-04X4-01 X4-02 X4-03X5-01 X5-02 X5-03
V1
PE N L
V1
PE N L LO
IL
LG
AS
min.
max
.LT
(CP
I) L
PE N
V1L
V2L
PVL
SVL
ION
FSV/
QR
I
PE N L
Pow
er Q
RI
QR
B
FLAME
L N G0 G
LIN
E
12VA
C
X7-
03X
7-02
X7-
01
PE
V2
PE
V3
PE
X6-
03X
6-02
X6-
01
Start
Start
H0-Start
PE
SV
PE
PE min
L PE max
L ON
/OFF
3
L
2
INT
GAS
OIL
L
RES
ET
PE N L PE N L(S
TART
)
IGN
ITIO
N
L L
MO
TOR
ALAR
M
L L
FLAN
GE
LSA
FETY
LOO
P
PE LNLI
NE
VOLT
AGE
OIL
OIL
GAS
SIEMENS
Burner ControlFuel Air Ratio ControlLoad ControlOXYGEN CONTROL
FeuerungautomatBrennst.-Luftverbundst.
LeistungsreglerSauerstoffregler
LMV52.200B2 230 VAC -15% /+10%50 or 60 Hz - 6% / + 6%-20°C to + 60°C- 4°F to +140°FFCC: part 15, Class BUse wires accaptablefor at least 90°C / 194°FRefer to data sheet 7550Made in Germany
Rg.5F193CE-0085BL0373
Siemens AG
S 1312120025
1P
DIN
Drain
Insulation Manual shutoffFGR pipe
FGR butterfly valve
FGR temperature sensor
Fabric compensator
9
Air damper register for flue gas suction control
FGR butterfly valve
Flexible compensator
Mixing box
Junction box for theelectrical components
Temperature sensor
Mixing box for flue gas recirculation at the combustion air fan
10
Functional and safe:Temperature-compensated flue gas dosing
0
10
0
20
30
40
50
60
70
80
90
160F (70C)
195F (90C)
230F (110C)
265F (130C)
300F (150C)
100%
P1P2
P3
P4P5
P6
Burner rating [%]
FGR butterfly valve positions
Maximum opening
Load-dependent opening (setting points)
Opening at 32F (0 °C)(calculated automatically)
Minimum position (adjustable)
Opening range de-pendent on fluegas temperature
Act
uato
r 3 [
°<)]
FGR te
mperature
Flue gas recirculation Burner’s air intake is connected to theboiler’ s stack and with help of burner’sfan the flue gas is drawn off and fedback into the flame mixed with the combustion air. The result: extremely lowNOx emissions.
However, the critical factor is the precisedosing of the recirculated flue gas. TheW-FM 200 combustion manager is bestequipped to control this process. Withjust two additional components – a fluegas temperature sensor and a butterflyvalve – and some additional software,the W-FM 200 can control the flow offlue gas so that the correct amount willbe fed into the combustion air under alloperating conditions, providing reliablestartup and operational behaviour – justas you would expect.
Simple commissioningThe W-FM 200’s fuel - air ratio control-ler provides up to 15 setting pointswhich can be positioned as requiredthroughout the burner’s operating range.This allows the volume of recirculatedflue gas to be matched precisely to thecombustion conditions.
Flue gas temperature is also crucial indetermining the volume of flue gas to berecirculated. The temperature of theflue gas affects its density and thus themass flow rate.
The flue gas temperature is measuredcontinuously to ensure stable burneroperating behaviour and consistentlylow NOx levels. Variations in temperatureare compensated automatically by adjustments to the FGR butterfly valve.
System-specific adaptionsBeside controlling the FGR butterflyvalve, the W-FM 200 combustion mana-ger’s software has parameters at handthat allow additional adjustments to suitsite conditions, such as defining mini-mum and maximum FGR butterfly valvepositions and make adjustments via correction factors.
11Burners with FGR on long-term test at Weishaupt factory’s boiler room
12
Weishaupt Corporation6280 Danville RoadMississauga, ON L5T 2H7, CanadaPh: (905) 564 0946 Fax: (905) 564 0949www.weishaupt-corp.com
Weishaupt America Inc.2587 Millenium Drive, Unit AElgin, IL 60124, USAPh: (847) 531 5800Fax: (847) 531 5855www.weishaupt-america.com
Print No. 83217416, October 2017Printed in Germany. All rights reserved.
Regular maintenance reduces heatingcosts and environmental pollution. Only aproperly adjusted burner can save energyand be environmentally friendly. Behindeach Weishaupt burner stands the wholeWeishaupt customer service organization.The outstanding efforts made inmaintenance and service justify theenormous trust placed in Weishaupt’sburners, for at Weishaupt, product andcustomer service belong together.
Weishaupt customer service is there foryou all year round. Whenever you needhelp, be it the supply of spare parts,technical advice or a site visit. We arethere when you need us.