GRUNDFOS DATA BOOKLET

Fire CRFFGrundfos fire systems

VdS-approved CR pumps for fire systems50 Hz

Ta

ble

of c

on

ten

ts

2

Fire CRFF

1. Introduction to VdS 3

2. Product description 11Introduction 11Performance range 11Product range 12Type keys 12

3. Construction 13CR 5, 10, 15 and 20 13CRI 5, 10, 15 and 20 13CR 32, 45 and 64 14CRN 32, 45 and 64 14Test pressure 15Installation 15How to read the curve charts 23Curve conditions 23Performance tests 24Certificate 24

4. Performance curves 25CRFF 5- (1-29) 25CRFF 10- (1-20) 26CRFF 15- (1-14) 27CRFF 20- (1-14) 28CRFF 32- (1-11) 29CRFF 45- (1-7) 30CRFF 64- (1-8-1) 31

5. Further fire pumps 32End-suction pumps 32

6. Further product documentation 34WebCAPS 34WinCAPS 35

Intr

od

uc

tio

n t

o V

dS

Fire CRFF 1

1. Introduction to VdS

VdS Schadenverhütung GmbH is an independent, international, accredited and notified testing and certification institution for fire prevention and safety technology as well as for physical and electronic protection against intrusion. ("Schadenverhütung" is the German word for "loss prevention").

VdS Schadenverhütung is accredited according to the EN 45000 series of European standards and is a member of the European Fire and Security Group (EFSG). VdS experts are represented in all relevant German and international committees.

The concept behind VdS recognition is to ensure that only tested and certified products and services are offered to the safety and security markets. This is equally advantageous for user and supplier.

For further information on VdS, see www.vds.de.

VdS standardsThe products in this data booklet have been built to comply with VdS standards on water-based firefighting systems, described in the following documents:

• VdS CEA 4001-S:2003-11: Planning and installation.

• VdS 2100-07: Guidelines for water-based firefighting systems.

• VdS 2344: Procedures for testing and approval of equipment, components and systems used in fire protection and security control.

Standards approval processGrundfos is to test the pumps and fill in the application forms for each individual pump size. The following documentation should to submitted to the VdS:

• complete drawings with list of parts and materials of the major components

• a statement regarding quality and production (ISO 9001 + Annex A & D)

• data sheet with technical information

• installation and operating instructions.

If the application forms are accepted, VdS will attend the final test at the Grundfos premises. If the evaluation of the test results is positive, the VdS will issue a certificate on the approval of the pump.

3

Intro

du

ctio

n to

Vd

S

4

Fire CRFF1

VdS certificateThe following pages show the VdS certificate for the CRFF pumps.

TM

05

39

97

19

12

Intr

od

uc

tio

n t

o V

dS

Fire CRFF 1

TM

05

39

98

19

12

5

Intro

du

ctio

n to

Vd

S

6

Fire CRFF1

TM

05

39

99

19

12

Intr

od

uc

tio

n t

o V

dS

Fire CRFF 1

TM

05

40

00

19

12

7

Intro

du

ctio

n to

Vd

S

8

Fire CRFF1

TM

05

40

01

19

12

Intr

od

uc

tio

n t

o V

dS

Fire CRFF 1

Fire pumpsGrundfos centrifugal pumps approved by the VdS are designed for the distribution of water in stationary sprinkler systems using either foam or water spray. They are operated in case of fire and during tests.

Materials

VdS-approved pumps must comply with these requirements:

• impeller, wear rings and wet parts such as shaft, washers and nuts must be made of non-corrosive iron.

• castings must be made of EN-GJL-250 cast iron.

VdS requirements for EN-GJL-250 do not allow heads (H) above 110 m and flow rates (Q) above 600 m3/h. Above 110 m ductile iron is required.

Pump characteristic

The VdS focuses strongly on the instabilities which may be present in sprinkler systems consisting of long and different pipe circuits. Two instable pumps may cause vibrations or breakdown.

If the characteristic is instable, the instability must not exceed 5 %. See examples of instable (fig. 1) and stable (fig. 2) characteristics below.

Fig. 1 Instable characteristics

Fig. 2 Stable characteristics

Duty rangeThe VdS operates with a concept known as Qzul ("zul" is an abbreviation of "zulässig" which means permissible). See fig. 3. The duty point of the pump must not be to the right of this limit.

Qzul is defined on the basis of the pump NPSH curves. The following calculation must be made for the largest and smallest pump impeller diameter.

TM

03

27

95

49

05

0 20 40 60 80 100 120 140 160 180 Q [m³/h]

14

16

18

20

22

24

26

28

30

32

34

36

38

40

[m]H

NK 80-315

ISO 9906 Annex A

50 Hz, n = 1450 min-1

ø275

ø290

ø305

ø320

ø334

73.3 %

72.5 %

72.1 %

74.8 %

74.2 %74 %

72 %

70 %

68 %

68 %70 %

72 %

74 %

TM

05

21

64

05

12

Find the flow rate at 4.5 m and 5.5 m NPSH

Multiply the value Q4.5 m NPSH by 1.2

Does the result exceed the value of Q5.5 m NPSH?

YesQzul = Q5.5 m NPSH / 1.2

No

Qzul = Q4.5 m NPSH

0 200 400 600 800 1000 1200 1400 1600 1800 2000 Q [l/min]

0

5

10

15

20

25

30

35

40

45

50

55

60

65

[m]H

0 20 40 60 80 100 120 Q [m³/h]

NKF 50-200

ISO 9906 Annex A

EN12845/prEN12259-12

2950 rpm

ø170

ø194

ø207

ø219

15 kW

22 kW

18.5 kW

11 kW

9

Intro

du

ctio

n to

Vd

S

10

Fire CRFF1

Fig. 3 Exampel of Qzul and duty range

Motor power ratingTo ensure that the motor is capable of operating the pump at any time to supply water, the VdS stipulates an excess capacity of motor power.

Overloading power curves

Motor power is found at 16 m NPSH.

Non-overloading power curves

Motor power is found at the power peak +5 %.

TM

05

28

06

26

12

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

H[m]

0 1 2 3 4 5 6 7 8 Q [l/s]

0

400

800

1200

1600

2000

p[kPa]

CRFF 202-pole, 50 Hz

ISO 9906/2 Annex A

-1, ø104.8 (3 kW)

-12, ø104.8 (15 kW)

-14, ø104.8 (18.5 kW)

-2, ø104.8 (4 kW)

-4, ø104.8 (5.5 kW)

-5, ø104.8 (7.5 kW)

-8, ø104.8 (11 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]

0

4

8

12

P2[kW]

-1, ø104.8

-12, ø104.8

-14, ø104.8

-2, ø104.8-4, ø104.8-5, ø104.8

-8, ø104.8

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]

0

2

4

6

NPSH[m]

NPSH

Qzul

5.54.5

23.5

27.3 28.5

Pro

du

ct

de

sc

rip

tio

n

Fire CRFF 2

2. Product description

IntroductionGrundfos Fire CRFF pump units are typically used in firefighting applications for supplying water to fire hose reels, fire hydrants or sprinkler systems.

This data booklet covers the range of electrically powered CRFF centrifugal pumps, designed and approved by the VdS for use in fire systems.

Performance range

TM

05

40

32

19

123 4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 90

Q [m³/h]

20

40

60

80

100

120

140

160

180

200

220

240

H[m]

11 2 3 4 5 6 7 8 9 1010 Q [l/s]

0.4

0.8

1.2

1.6

2.0

2.4

[MPa]p

CRFF2-pole, 50 Hz

ISO 9906/2 Annex A

CR

FF

45

CR

FF

32

CR

FF

20

CR

FF

15

CR

FF

10

CR

FF

5

CR

FF

64

11

Pro

du

ct d

es

crip

tion

12

Fire CRFF2

Product range

Standard range

2-pole

Other stages are available on request.

Type keys

CR, CRI, CRN

Codes

Pump sizeNumber of

stages

VdS approval Number

Motor, P2 [kW]

Product number

CRFF 5

1

P412003

0.55 98156624

3 0.75 98156599

6 1.1 98156598

9 1.5 98156595

14 2.2 98156594

20 3 98156593

28 4 98156622

29 5.5 98156589

CRFF 10

1

P412003

1.1 98156655

3 1.5 98156653

4 2.2 98156651

7 3 98156649

10 4 98156645

15 5.5 98156647

20 7.5 98156641

CRFF 15

1

P412003

2.2 98156692

2 3 98156680

3 4 98156678

5 5.5 98156677

8 7.5 98156676

12 11 98156674

14 15 98156658

CRFF 20

1

P412003

3 98156748

2 4 98156730

4 5.5 98156729

5 7.5 98156728

9 11 98156727

13 15 98156722

14 18.5 98156721

CRFF 32

1

P412003

2.2 98158475

2 4 98158473

3 5.5 98158471

4 7.5 98158470

6 11 98158569

8 15 98158468

10 18.5 98158464

11 22 98158461

CRFF 45

1

P412003

5.5 98158498

2 11 98158497

3 15 98158496

4 18.5 98158595

5 22 98158480

7 30 98158479

CRFF 64

1

P412003

5.5 98158960

2 11 98158959

3 18.5 98158958

4 22 98158523

5 30 98158522

6 37 98158521

8-1 45 98158524

Example CR FF 32 (s) -4 -2 -A -F -G -E -HQQE

Type range:CR, CRI, CRN

Pump approved for firefighting

Flow rate [m3/h]

All impellers with reduced diameter

Number of impellers

Number of reduced-diameter impellers

Code for pump version

Code for pipe connection

Code for materials

Code for rubber parts

Code for shaft seal

Example A -F -A -E -H QQ E

Pump version

A Basic version

B Oversize motor

Pipe connection

F DIN flange

G ANSI flange

J JIS flange

Materials

I Wetted parts of EN 1.4301/AISI 304

Code for rubber parts

E EPDM

F FXM

K FFKM

V FKM

Shaft seal

H Balanced cartridge seal

Q Silicon carbide

U Tungsten carbide

B Carbon

E EPDM

F FXM

K FFKM

V FKM

Co

ns

tru

cti

on

Fire CRFF 3

3. Construction

CR 5, 10, 15 and 20

Sectional drawing

Materials, CR

1) CR 5.2) CR 10, 15, 20.

CRI 5, 10, 15 and 20

Sectional drawing

Materials, CRI

1) Stainless steel available on request.2) CRI 5.3) CRI 10, 15, 20.

TM

02

11

98

06

01

- G

R7

37

7 -

GR

73

79

TM

02

11

94

14

03

Pos. Designation Materials EN/DIN AISI/ASTM

1 Pump headCast ironEN-GJL-200

EN-JL1030 ASTM 25B

3 Shaft Stainless steel 1.4401 1)

1.4057 2)AISI 316AISI 431

4 Impeller Stainless steel 1.4301 AISI 304

5 Chamber Stainless steel 1.4301 AISI 304

6 Sleeve Stainless steel 1.4301 AISI 304

7O-ring for sleeve

EPDM or FKM

8 BaseCast ironEN-GJL-200

EN-JL1030 ASTM 25B

9 Neck ring PTFE

10 Shaft seal

Rubber parts EPDM or FKM

1

3

10

4

5

9

8

67

TM

02

18

08

20

01

- G

R7

37

3 -

GR

73

75

TM

02

11

95

14

03

Pos. Designation Materials EN/DIN AISI/ASTM

1 Pump headCast ironEN-GJL-200 1) EN-JL1030 ASTM 25B

2Pump head cover

Stainless steel 1.4408CF 8M equal to

AISI 316

3 Shaft Stainless steel 1.4401 2)

1.4460 3)AISI 316AISI 329

4 Impeller Stainless steel 1.4301 AISI 304

5 Chamber Stainless steel 1.4301 AISI 304

6 Sleeve Stainless steel 1.4301 AISI 304

7O-ring for sleeve

EPDM or FKM

8 Base Stainless steel 1.4408CF 8M equal to

AISI 316

9 Neck ring PTFE

10 Shaft seal Cartridge type

11 Base plateCast ironEN-GJL-200 1) EN-JL1030 ASTM 25B

Rubber parts EPDM or FKM

1

2 10

4

5

9

8

6

3

11

7

13

Co

ns

truc

tion

14

Fire CRFF3

CR 32, 45 and 64

Sectional drawing

Materials, CR

CRN 32, 45 and 64

Sectional drawing

Materials, CRN

1) Stainless steel available on request.

TM

01

21

50

12

98

TM

01

18

36

14

03

Pos. Designation Materials EN/DIN AISI/ASTM

1 Pump headCast ironEN-GJS-500-7

EN-JS1050ASTM

80-55-06

2 Motor stoolCast ironEN-GJL-200

EN-JL1030 ASTM 25B

3 Shaft Stainless steel 1.4057 AISI 431

4 Impeller Stainless steel 1.4301 AISI 304

5 Chamber Stainless steel 1.4301 AISI 304

6 Sleeve Stainless steel 1.4301 AISI 304

7O-ring for sleeve

EPDM or FKM

8 BaseCast ironEN-GJS-500-7

EN-JS1050ASTM

80-55-06

9 Neck ringCarbon-graphite filled PTFE

10 Shaft seal

11 Bearing ring Bronze

12Bottom bearing ring

Tungsten carbide/tungsten carbide

Rubber parts EPDM or FKM

2

3

1

5

9

4

6

11

8

12

10

7

TM

02

73

99

34

03

TM

01

18

37

14

03

Pos. Designation Materials EN/DIN AISI/ASTM

1 Pump head Stainless steel 1.4408CF 8M equal to

AISI 316

2 Motor stoolCast ironEN-GJL-200 1) EN-JL1030 ASTM 25B

3 Shaft Stainless steel 1.4462

4 Impeller Stainless steel 1.4401 AISI 316

5 Chamber Stainless steel 1.4401 AISI 316

6 Sleeve Stainless steel 1.4401 AISI 316

7O-ring for sleeve

EPDM or FKM

8 Base Stainless steel 1.4408CF 8M equal to

AISI 316

9 Neck ringCarbon-graphite filled PTFE

10 Shaft seal

11 Bearing ringCarbon-graphite filled PTFE

12Bottom bearing ring

Tungsten carbide/tungsten carbide

13 Base plateCast ironEN-GJS-500-7 1) EN-JS1050

ASTM 88-55-06

Rubber parts EPDM or FKM

2

1

5

9

4

6

11

8

12

7

13

3

10

2

1

5

9

4

6

11

8

12

7

13

3

10

Co

ns

tru

cti

on

Fire CRFF 3

Test pressurePressure testing has been made with +20 °C water containing corrosion inhibitor.

Installation

Pipe connectionWhen installing the pipes, make sure that the pump housing is not stressed by the pipework.

The suction and discharge pipes must be of an adequate size, taking the pump inlet pressure into account.

Install the pipes so that air locks are avoided, especially on the suction side of the pump. See fig. 4.

Fig. 4 Pipelines

Fit isolating valves on either side of the pump to avoid having to drain the system if the pump needs to be cleaned or repaired.

Make sure the pipes are adequately supported as close to the pump as possible, both on the suction and the discharge side. The counter flanges should lie true against the pump flanges without being stressed; otherwise, the pump will be damaged.

Pressure stage

Operating pressure Test pressure

bar MPa bar MPa

PN 10 10 1.0 15 1.5

PN 16 16 1.6 24 2.4

TM

00

22

63

33

93

15

Co

ns

truc

tion

16

Fire CRFF3

Dimensional sketch CR, CRI 5

Dimensions and weights

TM

03

17

23

28

05

ø35

ø14

0

75

20

B1

B2

141100

250

ø10

89

180220

4 x ø13.5

19 x 24.5G 1/2

D2

D1

G 1/2 G 1/2

FGJ (DIN-ANSI-JIS)PN 25 / DN 25/32

D3

Pump typeMotor

P2 [kW]

CR CRI

Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]

DIN flangeD1 D2 D3 DIN flange

DIN flangeD1 D2 D3 DIN flange

B1 B1+B2 B1 B1+B2

CR 5-1 0.55 279 470 141 109 - 24 - - - - - -

CR 5-3 0.75 306 497 141 109 - 26 - - - - - -

CR 5-6 1.1 393 644 141 109 - 30 - - - - - -

CR 5-9 1.5 490 771 178 110 - 38 - - - - - -

CR 5-14 2.2 625 946 178 110 - 42 - - - - - -

CRI 5-20 3 - - - - - - 795 1130 198 120 - 49

CRI 5-28 4 - - - - - - 1038 1410 220 134 - 64

CRI 5-29 5.5 - - - - - - 1038 1429 220 134 - 78.5

Co

ns

tru

cti

on

Fire CRFF 3

Dimensional sketch CR, CRI 10

Dimensions and weights

TM

03

17

25

28

03

B2

D2D1

4 x ø13.5130178

80

G 1/2

280

B1

G 1/2G 1/2

256

18 x 20.2

ø39

20

FJ (DIN-JIS)

ø11

150

215ø110

D3

PN 16-25 / DN 40

Pump typeMotor

P2 [kW]

CR CRI

Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]

DIN flange D1 D2 D3DIN flange

DIN flange D1 D2 D3DIN flange

B1 B1+B2 B1 B1+B2

CR 10-1 1.1 343 534 141 109 - 34 - - - - - -

CR 10-3 1.5 377 628 141 109 - 39 - - - - - -

CR 10-4 2.2 423 704 178 110 - 47 - - - - - -

CR 10-7 3 518 853 198 120 - 57 - - - - - -

CR 10-10 4 608 980 220 134 - 69 - - - - - -

CRI 10-15 5.5 - - - - - - 760 1151 220 134 300 94

CRI 10-20 7.5 - - - - - - 940 1319 260 159 300 112

17

Co

ns

truc

tion

18

Fire CRFF3

Dimensional sketch CR, CRI 15

Dimensions and weights

TM

03

17

27

28

05

B2

D2D1

G 1/2

G 1/2 D3

130176

90

G 1/2

300215256

ø6520

PN 16-25 / DN 50

ø12

165

B1

F (DIN)

4 x ø13.5 ø18.1

Pump typeMotor

P2 [kW]

CR CRI

Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]

DIN flange D1 D2 D3DIN flange

DIN flange D1 D2 D3DIN flange

B1 B1+B2 B1 B1+B2

CR 15-1 2.2 400 651 141 109 - 42 - - - - - -

CR 15-2 3 415 736 178 110 - 50 - - - - - -

CR 15-3 4 465 800 198 120 - 57 - - - - - -

CR 15-5 5.5 555 927 220 134 - 69 - - - - - -

CRI 15-8 7.5 - - - - - - 720 1099 260 159 300 104

CRI 15-12 11 - - - - - - 977 1448 314 204 350 151

CRI 15-14 15 - - - - - - 1067 1538 314 204 350 165

Co

ns

tru

cti

on

Fire CRFF 3

Dimensional sketch CR, CRI 20

Dimensions and weights

TM

03

17

27

28

05

B2

D2D1

G 1/2

G 1/2 D3

130176

90G 1/2

300215256

ø6520

PN 16-25 / DN 50

ø12

165

B1

F (DIN)

4 x ø13.5 ø18.1

Pump typeMotor

P2 [kW]

CR CRI

Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]

DIN flange D1 D2 D3DIN flange

DIN flange D1 D2 D3DIN flange

B1 B1+B2 B1 B1+B2

CR 20-1 3 400 651 141 109 - 42 - - - - - -

CR 20-2 4 415 736 178 110 - 50 - - - - - -

CR 20-4 5.5 542 933 220 134 300 88 - - - - - -

CR 20-5 7.5 587 978 220 134 300 90 - - - - - -

CRI 20-9 11 - - - - - - 797 1268 314 204 350 144

CRI 20-13 15 - - - - - - 977 1448 314 204 350 163

CRI 20-14 18.5 - - - - - - 1067 1538 314 204 350 178

19

Co

ns

truc

tion

20

Fire CRFF3

Dimensional sketch CR, CRN 32

Dimensions and weights

TM

01

17

49

32

98

Pump typeMotor

P2 [kW]

CR CRN

Dimensions [mm]Net weight [kg]

Dimensions [mm]Net weight [kg]

B1 B1+B2 D1 D2 D3 B1 B1+B2 D1 D2 D3

CR 32-1 2.2 505 826 178 110 270 64 - - - - - -

CR 32-2 4 575 947 220 134 270 82 - - - - - -

CR 32-3 5.5 645 1036 220 134 300 96 - - - - - -

CR 32-4 7.5 715 1094 260 159 300 111 - - - - - -

CRN 32-6 11 - - - - - - 965 1436 314 204 350 163

CRN 32-8 15 - - - - - - 1105 1576 314 204 350 185

CRN 32-10 18.5 - - - - - - 1245 1760 314 204 350 205

CRN 32-11 22 - - - - - - 1315 1856 314 204 350 222

Co

ns

tru

cti

on

Fire CRFF 3

Dimensional sketch CR, CRN 45

Dimensions and weights

TM

01

17

51

32

03

8 x ø18

G 1/2

ø80266331

ø120

ø160

ø200

D2D1

190248365

B1

B2

G 1/2

G 1/2

4 x ø14

140

D3

45

PN16-25-40/DN80

Pump typeMotor

P2 [kW]

CR CR

Dimensions [mm]Net weight [kg]

Dimensions [mm]Net weight [kg]

B1 B1+B2 D1 D2 D3 B1 B1+B2 D1 D2 D3

CR 45-1 5.5 559 950 220 134 270 100 - - - - - -

CR 45-2 11 639 1100 314 204 350 160 - - - - - -

CR 45-3 15 829 1300 314 204 350 176 - - - - - -

CR 45-4 18.5 909 1424 314 204 350 193 - - - - - -

CRN 45-5 22 - - - - - - 989 1530 314 204 350 211

CRN 45-7 30 - - - - - - 1149 1759 407 315 400 324

21

Co

ns

truc

tion

22

Fire CRFF3

Dimensional sketch CR, CRN 64

Dimensions and weights

TM

01

17

53

51

97

ø100266331

ø150

ø180

ø220

D2D1

190248365

B1

B2

G 1/2 8 x ø18

G 1/2

G 1/2

4 x ø14

140

D3

45

PN16/DN100

PN25-40/DN100

45

4 x ø14

G 1/2

8 x ø22

ø235

ø190

ø150

331266ø100

F (DIN)

F (DIN)

Pump typeMotor

P2 [kW]

CR CR

Dimensions [mm]Net weight [kg]

Dimensions [mm]Net weight [kg]

B1 B1+B2 D1 D2 D3 B1 B1+B2 D1 D2 D3

CR 64-1 5.5 561 952 220 134 300 102 - - - - - -

CR 64-2 11 754 1225 314 204 350 162 - - - - - -

CR 64-3 18.5 836 1351 314 204 350 193 - - - - - -

CR 64-4 22 919 1460 314 204 350 211 - - - - - -

CRN 64-5 30 - - - - - - 1001 1611 407 315 400 318

CRN 64-6 37 - - - - - - 1084 1751 407 315 400 355

CRN 64-8-1 45 - - - - - - 1249 1957 439 338 450 448

Co

ns

tru

cti

on

Fire CRFF 3

How to read the curve charts

Curve conditions

Selection of pumps

The guidelines below apply to the curves shown in the performance charts, pages 25 to 31.

• Tolerances according to ISO 9906 and VdS 2100-07.

• The curves show pump performance with different number of impellers at the nominal speed.

• The bold part of the curves shows the recommended operating range.

• The thin parts are not allowed according to the VdS.

• Do not use the pumps at minimum flow rates below 0.1 x Q at optimum efficiency because of the danger of overheating of the pump.

• The curves apply to of water at a temperature of +20 °C and a kinematic viscosity of 1 mm2/s (1 cSt).

• NPSH: The curves are according to the minimum and maximum number of impellers.

• In case of other densities than 1000 kg/m3 the discharge pressure is proportional to the density.

• When pumping water with a density higher than 1000 kg/m3, motors with correspondingly higher outputs must be used.

Calculation of total head

The total pump head consists of the height difference between the measuring points + the differential head + the dynamic head.

TM

05

28

07

26

12

0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

H[m]

0 2 4 6 8 10 12 Q [l/s]

0.0

0.4

0.8

1.2

1.6

2.0

[MPa]p

CRFF 322-pole, 50 Hz

ISO 9906/2 Annex A

-11, ø118.3 (22 kW)

-1, ø118.3 (2.2 kW)

-10, ø118.3 (18.5 kW)

-2, ø118.3 (4 kW)

-3, ø118.3 (5.5 kW)

-4, ø118.3 (7.5 kW)

-6, ø118.3 (11 kW)

-8, ø118.3 (15 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]

0

5

10

15

20

P2[kW]

-1, ø118.3

-10, ø118.3-11, ø118.3

-2, ø118.3-3, ø118.3-4, ø118.3

-6, ø118.3

-8, ø118.3

0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]

0

2

4

6

[m]NPSH

NPSH

Pump type and motor speed

Number of stages

Total pump headH = Htotal

The power curve indicates pump input power, P2.

The NPSH curve is according to the minimum and maximum impeller diameter.

Qzul indicates the limit of the individual pump performance range according to the VdS.

QH curve for the individual pump

Hgeo: Height difference between measuring points.Hstat: Differential head between the suction and the

discharge side of the pump.Hdyn: Calculated values based on the velocity of the

pumped water on the suction and the discharge side of the pump.

Htotal Hgeo Hstat Hdyn+ +=

23

Co

ns

truc

tion

24

Fire CRFF3

Performance testsThe requested duty point for every pump is tested according to ISO 9906 and VdS 2100-07.

If the customer requires a specific number of impellers (not a specific duty point), the pump will be tested at a duty point which is 2/3 of the maximum flow rate of the published performance curve related to the ordered number of impellers (according to ISO 9906).

If the customer requires either more points on the curve to be checked or certain minimum performances or certificates, individual measurements must be made.

CertificateThe pump order includes a test certificate confirming the required QH performance.

Pe

rfo

rma

nc

e c

urv

es

4

4. Performance curves

CRFF 5- (1-29)

TM

05

28

03

26

12

0 1 2 3 4 5 6 7 8 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

H[m]

0.0 0.5 1.0 1.5 2.0 2.5 Q [l/s]

0

400

800

1200

1600

p[kPa]

CRFF 52-pole, 50 Hz

ISO 9906/2 Annex A

-1, ø73.2 (0.55 kW)

-14, ø73.2 (2.2 kW)

-20, ø73.2 (3 kW)

-29, ø73.2 (5.5 kW)

-3, ø73.2 (0.75 kW)

-6, ø73.2 (1.1 kW)

-9, ø73.2 (1.5 kW)

-28, ø73.2 (4 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 1 2 3 4 5 6 7 8 Q [m³/h]

0

1

2

3

4

P2[kW]

-14, ø73.2

-20, ø73.2

-28, ø73.2-29, ø73.2

-3, ø73.2-6, ø73.2-9, ø73.2

-1, ø73.2

0 1 2 3 4 5 6 7 8 Q [m³/h]

0

1

2

3

NPSH[m]

NPSH

25

Pe

rform

an

ce

cu

rve

s

26

4

CRFF 10- (1-20)

TM

05

28

04

26

12

0 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

240

H[m]

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 Q [l/s]

0

400

800

1200

1600

2000

p[kPa]

CRFF 102-pole, 50 Hz

ISO 9906/2 Annex A

-1, ø92.9 (1.1 kW)

-10, ø92.9 (4 kW)

-14, ø92.9 (5.5 kW)

-20, ø92.9 (7.5 kW)

-3, ø92.9 (1.5 kW)

-4, ø92.9 (2.2 kW)

-7, ø92.9 (3 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [m³/h]

0

2

4

6

P2[kW]

-1, ø92.9

-10, ø92.9

-14, ø92.9

-20, ø92.9

-3, ø92.9-4, ø92.9-7, ø92.9

0 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [m³/h]

1

2

3

4

NPSH[m]

NPSH

Pe

rfo

rma

nc

e c

urv

es

4

CRFF 15- (1-14)

TM

05

28

05

26

12

0 2 4 6 8 10 12 14 16 18 20 22 24 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

H[m]

0 1 2 3 4 5 6 7 Q [l/s]

0

400

800

1200

1600

2000

p[kPa]

CRFF 152-pole, 50 Hz

ISO 9906/2 Annex A

-1, ø104.8 (2.2 kW)

-12, ø104.8 (11 kW)

-14, ø104.8 (15 kW)

-2, ø104.8 (3 kW)

-3, ø104.8 (4 kW)

-5, ø104.8 (5.5 kW)

-8, ø104.8 (7.5 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 2 4 6 8 10 12 14 16 18 20 22 24 Q [m³/h]

0

2

4

6

8

10

P2[kW]

-1, ø104.8

-12, ø104.8

-14, ø104.8

-2, ø104.8-3, ø104.8-5, ø104.8

-8, ø104.8

0 2 4 6 8 10 12 14 16 18 20 22 24 Q [m³/h]

0

1

2

3

4

NPSH[m]

NPSH

27

Pe

rform

an

ce

cu

rve

s

28

4

CRFF 20- (1-14)

TM

05

28

06

26

12

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

H[m]

0 1 2 3 4 5 6 7 8 Q [l/s]

0

400

800

1200

1600

2000

p[kPa]

CRFF 202-pole, 50 Hz

ISO 9906/2 Annex A

-1, ø104.8 (3 kW)

-12, ø104.8 (15 kW)

-14, ø104.8 (18.5 kW)

-2, ø104.8 (4 kW)

-4, ø104.8 (5.5 kW)

-5, ø104.8 (7.5 kW)

-8, ø104.8 (11 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]

0

4

8

12

P2[kW]

-1, ø104.8

-12, ø104.8

-14, ø104.8

-2, ø104.8-4, ø104.8-5, ø104.8

-8, ø104.8

0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]

0

2

4

6

NPSH[m]

NPSH

Pe

rfo

rma

nc

e c

urv

es

4

CRFF 32- (1-11)

TM

05

28

07

26

12

0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

H[m]

0 2 4 6 8 10 12 Q [l/s]

0.0

0.4

0.8

1.2

1.6

2.0

[MPa]p

CRFF 322-pole, 50 Hz

ISO 9906/2 Annex A

-11, ø118.3 (22 kW)

-1, ø118.3 (2.2 kW)

-10, ø118.3 (18.5 kW)

-2, ø118.3 (4 kW)

-3, ø118.3 (5.5 kW)

-4, ø118.3 (7.5 kW)

-6, ø118.3 (11 kW)

-8, ø118.3 (15 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]

0

5

10

15

20

P2[kW]

-1, ø118.3

-10, ø118.3-11, ø118.3

-2, ø118.3-3, ø118.3-4, ø118.3

-6, ø118.3

-8, ø118.3

0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]

0

2

4

6

[m]NPSH

NPSH

29

Pe

rform

an

ce

cu

rve

s

30

4

CRFF 45- (1-7)

TM

05

28

08

26

12

0 5 10 15 20 25 30 35 40 45 50 55 Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

H[m]

0 2 4 6 8 10 12 14 16 Q [l/s]

0.0

0.4

0.8

1.2

1.6

[MPa]p

CRFF 452-pole, 50 Hz

ISO 9906/2 Annex A

-7, ø136.3 (30 kW)

-2, ø136.3 (11 kW)

-3, ø136.3 (15 kW)

-4, ø136.3 (18.5 kW)

-5, ø136.3 (22 kW)

-1, ø136.3 (5.5 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 5 10 15 20 25 30 35 40 45 50 55 Q [m³/h]

0

5

10

15

20

25

P2[kW]

-7, ø136.3

-1, ø136.3

-2, ø136.3-3, ø136.3

-4, ø136.3

-5, ø136.3

0 5 10 15 20 25 30 35 40 45 50 55 Q [m³/h]

0

1

2

3

4

[m]NPSH

NPSH

Pe

rfo

rma

nc

e c

urv

es

4

CRFF 64- (1-8-1)

TM

05

28

09

26

12

0 10 20 30 40 50 60 70 80 90Q [m³/h]

0

20

40

60

80

100

120

140

160

180

200

220

240

H[m]

0 5 10 15 20 25 Q [l/s]

0.0

0.4

0.8

1.2

1.6

2.0

[MPa]p

CRFF 642-pole, 50 Hz

ISO 9906/2 Annex A

-8-1, ø142.9 (45 kW)

-1, ø142.9 (5.5 kW)

-2, ø142.9 (11 kW)

-3, ø142.9 (18.5 kW)

-4, ø142.9 (22 kW)

-5, ø142.9 (30 kW)

-6, ø142.9 (37 kW)

VdS Zulassungsgrenze / VdS Rated capacity

0 10 20 30 40 50 60 70 80 90Q [m³/h]

0

10

20

30

40

P2[kW]

-1, ø142.9-2, ø142.9

-3, ø142.9-4, ø142.9

-5, ø142.9-6, ø142.9

-8-1, ø142.9

0 10 20 30 40 50 60 70 80 90Q [m³/h]

0

2

4

6

[m]NPSH

NPSH

31

Fu

rthe

r fire p

um

ps

32

Fire CRFF5

5. Further fire pumps

Grundfos can also provide end-suction and split case pumps, controllers and drivers according to standards such as VdS, LPCB, EN, FM, OKF and NFPA.

Please contact your local Grundfos sales company for options of fire pump sets and other products with standards suitable for your requirements.

End-suction pumps

VdS diesel range

TM

03

84

73

26

11

20 30 40 50 60 80 100 150 200 300 400 500 600 800Q [m³/h]

20

30

40

50

60

70

80

90

100

120

[m]H

NKFDiesel

125-315

125-250.1

125-250

100-200

150-400

150-400

150-400

150-500

150-40080-250

65-200

80-20050-2002960 min-1

2960 min-1

2960 min-1

2960 min-1

1800 min-1

1800 min-1

1480 min-1

1700 min-1

1600 min-1

2960 min-1

2960 min-1

2990 min-1

2980 min-1

Fu

rth

er

fire

pu

mp

s

Fire CRFF 5

VdS electrical range

TM

02

93

54

26

11

20 30 40 50 60 80 100 150 200 300 400 500 600Q [m³/h]

20

30

40

50

60

70

80

90

100

120

150[m]H

NKF50 Hz

125-315/2

125-250.1/2

100-200/2

125-250/2

150-400/4

150-500/4

80-250/2

65-200/2 80-200/250-200/2

33

Fu

rthe

r pro

du

ct d

oc

um

en

tatio

n

34

Fire CRFF6

6. Further product documentation

WebCAPSWebCAPS is a Web-based Computer Aided Product Selection program available on www.grundfos.com.

WebCAPS contains detailed information on more than 220,000 Grundfos products in more than 30 languages.

Information in WebCAPS is divided into six sections:

• Catalogue

• Literature

• Service

• Sizing

• Replacement

• CAD drawings.

Catalogue

Based on fields of application and pump types, this section contains the following:• technical data• curves (QH, Eta, P1, P2, etc.) which can be adapted to the

density and viscosity of the pumped liquid and show the number of pumps in operation

• product photos• dimensional drawings• wiring diagrams• quotation texts, etc.

Literature

This section contains all the latest documents of a given pump, such as• data booklets• installation and operating instructions• service documentation, such as Service kit catalogue and

Service kit instructions• quick guides• product brochures.

Service

This section contains an easy-to-use interactive service catalogue. Here you can find and identify service parts of both existing and discontinued Grundfos pumps.Furthermore, the section contains service videos showing you how to replace service parts.

Fu

rth

er

pro

du

ct

do

cu

me

nta

tio

n

Fire CRFF 6

WinCAPS

Fig. 5 WinCAPS DVD

WinCAPS is a Windows-based Computer Aided Product Selection program containing detailed information on more than 220,000 Grundfos products in more than 30 languages.

The program contains the same features and functions as WebCAPS, but is an ideal solution if no internet connection is available.

WinCAPS is available on DVD and updated once a year.

Sizing

This section is based on different fields of application and installation examples and gives easy step-by-step instructions in how to size a product:• Select the most suitable and efficient pump for your

installation.• Carry out advanced calculations based on energy,

consumption, payback periods, load profiles, life cycle costs, etc.

• Analyse your selected pump via the built-in life cycle cost tool.• Determine the flow velocity in wastewater applications, etc.

Replacement

In this section you find a guide to selecting and comparing replacement data of an installed pump in order to replace the pump with a more efficient Grundfos pump. The section contains replacement data of a wide range of pumps produced by other manufacturers than Grundfos.

Based on an easy step-by-step guide, you can compare Grundfos pumps with the one you have installed on your site. When you have specified the installed pump, the guide will suggest a number of Grundfos pumps which can improve both comfort and efficiency.

CAD drawings

In this section, it is possible to download 2-dimensional (2D) and 3-dimensional (3D) CAD drawings of most Grundfos pumps.

These formats are available in WebCAPS:

2-dimensional drawings:• .dxf, wireframe drawings• .dwg, wireframe drawings.

3-dimensional drawings:• .dwg, wireframe drawings (without surfaces)• .stp, solid drawings (with surfaces)• .eprt, E-drawings.

0 1