56
Form 7 microprocessor-based pole-mount recloser control installation and operation instructions COOPER POWER SERIES Reclosers MN280095EN Effective February 2022 Supersedes November 2020

Form 7 microprocessor-based pole-mount recloser control

  • Upload
    others

  • View
    15

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Form 7 microprocessor-based pole-mount recloser control

Form 7 microprocessor-based pole-mount recloser control installation and operation instructions

COOPER POWERSERIES

Reclosers MN280095EN

Effective February 2022Supersedes November 2020

Page 2: Form 7 microprocessor-based pole-mount recloser control

ii INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.

THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice.

Page 3: Form 7 microprocessor-based pole-mount recloser control

iiiINSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Contents

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY ........................................................................II

SAFETY INFORMATION ......................................................................................................................................... VHazard statement definitions ............................................................................................................................................ v

Safety instructions ............................................................................................................................................................. v

INTRODUCTION .......................................................................................................................................................1About this document .........................................................................................................................................................1

Product information ...........................................................................................................................................................1

ANSI standards ..................................................................................................................................................................1

Quality standards...............................................................................................................................................................1

Acceptance and initial inspection ......................................................................................................................................1

Handling and storage .........................................................................................................................................................1

FORM 7 CONTROL DESCRIPTION .........................................................................................................................2Description ........................................................................................................................................................................2

Theory of operation ...........................................................................................................................................................2

Front panel .........................................................................................................................................................................4

Features .............................................................................................................................................................................7

Communications .............................................................................................................................................................. 11

Control information label ................................................................................................................................................. 13

Module access ................................................................................................................................................................ 13

INSTALLATION .......................................................................................................................................................13Prerequisites .................................................................................................................................................................... 13

Procedure ........................................................................................................................................................................ 14

Mount the control ............................................................................................................................................................ 14

Ground the control .......................................................................................................................................................... 16

Install the battery............................................................................................................................................................. 19

Make customer connections for AC power .....................................................................................................................20

Change removable inserts ...............................................................................................................................................28

Install the control cable ...................................................................................................................................................28

Lock the control ...............................................................................................................................................................29

Before placing the control and the recloser into service ................................................................................................29

Control battery .................................................................................................................................................................30

Fuse specifications ..........................................................................................................................................................30

TESTING .................................................................................................................................................................30Testing an installed control ..............................................................................................................................................30

Remove the control from service ....................................................................................................................................31

Preliminary testing with no AC available .........................................................................................................................31

Electrical testing of NOVA NX-T ......................................................................................................................................32

Control testing with a KMET tester .................................................................................................................................32

Battery test and charging procedures .............................................................................................................................32

Return the control to service ...........................................................................................................................................34

Page 4: Form 7 microprocessor-based pole-mount recloser control

iv INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

OPERATION ............................................................................................................................................................34Modes of operation .........................................................................................................................................................34

Operation upon loss of AC power ...................................................................................................................................35

ACCESSORIES .......................................................................................................................................................35Additional communication cards .....................................................................................................................................35

Auxiliary contact I/O ........................................................................................................................................................36

Loop scheme accessory ..................................................................................................................................................36

Incoming power receptacles ...........................................................................................................................................37

Cable locking sleeves ......................................................................................................................................................37

Stainless steel cabinet.....................................................................................................................................................37

120 Vac GFI duplex outlet ................................................................................................................................................37

Internal voltage sensing and load side sensing ...............................................................................................................37

Radio mounting accessory ..............................................................................................................................................38

Mechanical pushbutton with Hot Line Tag toggle switch ................................................................................................38

Door alarm accessory ......................................................................................................................................................38

Replacement kits .............................................................................................................................................................38

Form 7 triple single adapter.............................................................................................................................................38

SUPPORT ................................................................................................................................................................38Factory-authorized service centers..................................................................................................................................38

Switchgear Support Group ..............................................................................................................................................38

Page 5: Form 7 microprocessor-based pole-mount recloser control

vINSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

SAFETY FOR LIFE

Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power™ series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service.

We strongly urge that you always follow all locally-approved safety procedures and safety instructions when working around high-voltage lines and equipment, and support our “Safety For Life” mission.

SAFETY INFORMATION

The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it.

A competent technician has these qualifications:

Is thoroughly familiar with these instructions.

Is trained in industry-accepted high- and low-voltage safe operating practices and procedures.

Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment.

Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc.

Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings.

Hazard statement definitionsThis manual may contain four types of hazard statements:

DANGERINDICATES AN IMMINENTLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.

WARNINGINDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY.

CAUTIONINDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, MAY RESULT IN MINOR OR MODERATE INJURY.

NOTICEINDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, MAY RESULT IN EQUIPMENT DAMAGE ONLY.

Safety instructionsFollowing are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual.

DANGERHAZARDOUS VOLTAGE. CONTACT WITH HAZARDOUS VOLTAGE WILL CAUSE DEATH OR SEVERE PERSONAL INJURY. FOLLOW ALL LOCALLY-APPROVED SAFETY PROCEDURES WHEN WORKING AROUND HIGH- AND LOW-VOLTAGE LINES AND EQUIPMENT.

WARNINGBEFORE INSTALLING, OPERATING, MAINTAINING, OR TESTING THIS EQUIPMENT, CAREFULLY READ AND UNDERSTAND THE CONTENTS OF THIS MANUAL. IMPROPER OPERATION, HANDLING, OR MAINTENANCE CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND EQUIPMENT DAMAGE.

WARNINGTHIS EQUIPMENT IS NOT INTENDED TO PROTECT HUMAN LIFE. FOLLOW ALL LOCALLY-APPROVED PROCEDURES AND SAFETY PRACTICES WHEN INSTALLING OR OPERATING THIS EQUIPMENT. FAILURE TO COMPLY CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND EQUIPMENT DAMAGE.

WARNINGPOWER DISTRIBUTION AND TRANSMISSION EQUIPMENT MUST BE PROPERLY SELECTED FOR THE INTENDED APPLICATION. IT MUST BE INSTALLED AND SERVICED BY COMPETENT PERSONNEL WHO HAVE BEEN TRAINED AND UNDERSTAND PROPER SAFETY PROCEDURES. THESE INSTRUCTIONS ARE WRITTEN FOR SUCH PERSONNEL AND ARE NOT A SUBSTITUTE FOR ADEQUATE TRAINING AND EXPERIENCE IN SAFETY PROCEDURES. FAILURE TO PROPERLY SELECT, INSTALL, OR MAINTAIN POWER DISTRIBUTION AND TRANSMISSION EQUIPMENT CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND EQUIPMENT DAMAGE.

WARNINGOVERLAPPING ZONES OF PROTECTION ARE REQUIRED. UPSTREAM PROTECTION DEVICE SETTINGS MUST PROVIDE ADEQUATE OVERCURRENT PROTECTION IN THE EVENT OF A SYSTEM OR PRODUCT FAILURE. FAILURE TO PROPERLY SELECT APPROPRIATE UPSTREAM COORDINATION PROTECTION CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND EQUIPMENT DAMAGE.

!SAFETYFOR LIFE

!SAFETYFOR LIFE

Page 6: Form 7 microprocessor-based pole-mount recloser control

vi INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

his page is intentionally left blank.T

Page 7: Form 7 microprocessor-based pole-mount recloser control

1INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

INTRODUCTION

About this documentThis manual provides installation and operation instructions for the Form 7 pole-mount recloser control.

For ProView NXG software information, refer to Form 7 Recloser Control Programming Guide: ProView NXG software MN280096EN.

The Form 7 control is designed for use with NOVA NX-T reclosers, only. Refer to NOVA NX-T Recloser Installation and Operation Instructions MN280087EN.

Read this manual first

Read and understand the contents of this manual and follow all locally approved procedures and safety practices when installing or operating this equipment.

Additional information

These instructions cannot cover all details or vari ations in the equipment, procedures, or process described, nor provide directions for meeting every possible contin gency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not cov ered sufficiently for the user’s purpose, contact your Eaton representative.

Product informationThe Form 7 recloser control includes hardware features including modular, flexible and scalable hardware operated with an 800 MHz quad-core processor, 1GB RAM, and 4GB flash storage. The control’s modular layout affords the ability to easily insert hardware as new applications arise and requirements change.

The Form 7 control’s powerful Workbench NXG is a highly intuitive graphical user interface that simplifies training and operator familiarity. Workbench NXG logic is fully transparent with powerful logic tools available to customize control functions or create powerful, unique applications.

The control includes an array of integrated security tools for the user to prevent local intrusion or unauthorized operation. These security tools include Role-Based Access Control (RBAC), signed firmware, a user audit log, and an optional door alarm accessory that provides feedback when the door is closed, opened, or if the switch is disconnected. Transport Layer Security (TLS) encryption tools can be utilized to establish a secure, private communications channel or SCADA traffic and remote connection to ProView NXG.

As ordered, the control is powered from either 120 or 240 Vac.

ANSI standardsEaton Cooper Power Series reclosers are designed and tested in accordance with the following ANSI standards: C37.60 and C37.85 and ANSI Guide C37.61.

Quality standardsAll Form 7 controls are manufactured in ISO 9001 certified production facilities.

Acceptance and initial inspectionEach Form 7 recloser control is completely assembled, tested, and inspected at the factory. It is carefully calibrated, adjusted and in good condition when accepted by the carrier for shipment.

Upon receipt, inspect the carton for signs of damage. Unpack the control and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately.

Handling and storageBe careful during handling and storage of the control to minimize the possibility of damage. If the control is to be stored for any length of time prior to installation, provide a clean, dry storage area. If storage is in a humid atmosphere, make provisions to keep the control circuitry energized.

ote: N To energize the control, supply AC power to input terminal block TB7. This terminal block is mounted on the lower left of the back panel.

Control battery

The 24 Vdc Form 7 recloser control battery is fully charged prior to shipment and is ready for use.

The control is shipped with the battery not installed.

Remove the battery from the Control before transporting the Control. Do not transport a Form 7 control with the battery inside the control enclosure.

The battery shall be installed only after the control has been mounted.

IMPORTANT: To maintain sufficient charge to operate the control and prevent battery cell damage, the sealed lead-acid batteries should be charged after no more than three months of storage.

Temperature affects battery life. Store sealed lead acid batteries fully charged and at room temperature. Never store lead acid batteries at temperatures exceeding 117 °F (47 °C). Storing the battery for any time above 117 °F (47 °C) can result in approximately one month of shortened life.

After three months of storage (from the previous test date), test and then charge the batteries for 24 hours. Catalog Number KA43ME7001 is a 120-Volt battery charger used to provide an external source of charge for the control’s 24 Vdc battery (two 12 Vdc batteries).

Page 8: Form 7 microprocessor-based pole-mount recloser control

2 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

IMPORTANT: Connect the control battery before AC power is connected to the control’s AC supply Input Terminal Block. The battery must be disconnected and removed prior to shipping. The battery must be disconnected prior to storing the control. See Figure 13.

ote: N When shipped from the factory, the battery will be in the same carton as the control. The battery leads will be taped to the battery casing. Connect the battery plugs into the mating connectors to complete the battery circuit.

Dispose expired batteries in an environmentally responsible manner. Consult local regulations for proper battery disposal.

FORM 7 CONTROL DESCRIPTION

DescriptionThe Form 7 control is designed for use with NOVA NX-T reclosers to provide protection, metering, and automation of distribution feeders in substation and line applications. The control operates the individual reclosers representing phases A, B, and C.

ote: N The phase sequence positions (phase A, B, and C) are independent of each other.

The Form 7 recloser control includes extensive system protection functionality including:

Phase, ground, and negative sequence overcurrent protection

Over/under frequency and voltage protection

Directionality

Sync check

Analysis tools are provided to empower the user’s ability to respond to events occurring on their system. These tools include fault locating, event recording, Workbench NXG, and oscillography.

Metering functions include demand and instantaneous current on a per-phase basis, instantaneous voltage and power factor on a per-phase basis, and power (real, reactive, apparent) on a per phase or total basis. Symmetrical components for both voltage and current are displayed along with kilowatt-hours for energy metering. Harmonics from the 2nd to the 15th harmonic are also included.

Use the front panel LCD display to:

Configure the operating settings for the control

Display metering, counter information, control parameters, and alarms

Provide diagnostic information

With Form 7 NXG interface software, you can perform control programming, interrogation, and operations. Install the software on a personal computer and connect it to the control’s front panel through the USB or Ethernet port.

The NXG interface program software includes additional functions used to create and graphically display Time Current Curves, and provides the Workbench NXG for configuring user-selected inputs and outputs, configurable event and alarm data, and selectable communication points for serial and Ethernet communication.

The control operates on 50 and 60 Hz systems.

The control can be configured, by the factory or by the user, for a wide variety of applications. If user requirements change, the control functions can be modified to meet the new requirements.

Theory of operationA functional block diagram of the Form 7 control is shown in Figure 1. Current sensing is provided by three current transformers located in the recloser and interfaced to the Form 7 control through the control cable. The control cable also supplies the Form 7 with the trip and close signals, the recloser status, and provides a connection to the Recloser Interface (RIF) module that provides isolation and reliable operation. Voltages for metering are connected to the voltage data acquisition (DAQ) module through connectors P251 and P252. If PT (potential transformer) sensing is being used, the signals are first routed through the PT sensing board and connected at TB8.

Line current flowing through the recloser is measured by the integrated current transformers and then converted by the DAQ module to a digital signal suitable for metering and fault current calculations. Data sampling occurs at a rate of 128 samples/cycle. The CPU contains a data acquisition section that uses the acquired samples to compute the fundamental currents and voltage for use in overcurrent, under/overvoltage, and under/overfrequency protection, as well as currents and voltages for metering functions. The current for overcurrent protection is calculated on a sub-cycle basis; it includes only the fundamental and DC component.

When the phase or ground current exceeds its programmed minimum-trip value and associated time-current-curve (TCC) timing, the control initiates the programmed sequence of recloser tripping and reclosing operations via the CPU and RIF modules. If the fault is temporary, the control ceases to command recloser operations after a successful reclose, and the control resets to the start of its operating sequence after a preset time delay. If the fault is permanent, the control performs its complete programmed sequence of reclose commands and locks out with the recloser open. Once locked out, the control must be closed via the operator panel or SCADA communications. This resets the control to the start of the operating sequence.

Page 9: Form 7 microprocessor-based pole-mount recloser control

3INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 1. Form 7 recloser control operational flow diagram

Phase operation

The Form 7 control uses three modes of operation that are configured through the ProView NXG user interface software or LCD Front Panel.

In Three-Phase Trip, Three-Phase Lockout (ganged) mode, all three phases will simultaneously trip and close due to a protection event or user command.

In Single-Phase Trip, Three-Phase Lockout mode, all three phases will trip and lockout when one of the phases sequences to lockout. While the phases will operate independently within their sequence the protection parameter programming is shared between all three.

In Single-Phase Trip, Single-Phase Lockout mode, each phase independently sequences to lockout. The protection parameters are still shared between the phases in Single-Phase Trip, Single-Phase Lockout mode.

The yellow handles on the triple single recloser can be manually operated to open and lockout a phase. If the device is in the following modes and any handle is pulled, all three phases will open and lockout:

Three-Phase Trip, Three-Phase Lockout mode

Single-Phase Trip, Three-Phase Lockout mode

If the device is in Single-Phase Trip, Single-Phase Lockout mode, only the phase whose handle is pulled will trip and lockout.

The NOVA NX-T recloser’s mechanical blocking feature prohibits the phase to be closed with its handle pulled down. The open signal to trip and lockout the device is sent from the Form 7 control.

WARNINGHAZARDOUS VOLTAGE. DO NOT RELY ON THE OPEN POSITION OF THE YELLOW OPERATING HANDLE; IT DOES NOT ENSURE THAT THE LINE HAS BEEN DE-ENERGIZED. ALWAYS ESTABLISH A VISIBLE DISCONNECT. FAILURE TO FOLLOW PROPER SAFETY PRACTICES CAN RESULT IN CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY.

IMPORTANT: Pushing the yellow operating handle to the CLOSE position will not close the recloser. All close operations are initiated by the Form 7 control.

24 VDCBATTERY

POWERSUPPLY

TB7TB8

PT SENSINGBOARD

CTDAQ

RIF

VOLTAGEDAQ

PCIE bus52a/b

CT

SWITCHES

NOVANX-T

RECLOSER

OPTIONALMECHANICAL

OPEN/CLOSE/HLT

RS-232RJ-45IRIG-BUSB

NOVA NX-TINTEGRATEDJUNCTION

BOX

52a/b

CT

SWITCHES

52a/b

CT

SWITCHES

37-PINCONNECTOR

2 PIN/3 PIN POWERSOURCE 1

2 PIN/3 PIN POWERSOURCE 2

FORM 7 CONTROL

FRONT PANEL

CPU

LEA SENSING

PT SENSING

Page 10: Form 7 microprocessor-based pole-mount recloser control

4 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Ground operation

Ground overcurrent operation will mirror phase overcurrent operation when the device is in Three-Phase Trip, Three-Phase Lockout mode.

In Single-Phase Trip, Three-Phase Lockout and Single-Phase Trip, Single-Phase Lockout modes, ground tripping is only active when all three phases are closed. Ground tripping is disabled during the reclose interval of any one phase.

For faults above the ground minimum trip value, and below the phase minimum trip value, all three phases trip on ground and advance to the next sequence position.

For faults above the phase and ground minimum trip value, the control trips on the phase(s) above phase minimum trip, operating on the phase or ground TCC, whichever is faster.Only tripped phases advance in sequence and are counted as phase operations.

Phase/ground sequencing

Phase and ground share the same sequence position. As the position sequence advances, the phase and ground TCCs advance together to maintain proper coordination with upline and downline devices. This is applicable for temporary and permanent faults including faults on multiple phases.

Front panelThe Form 7 control front panel is illustrated in Figure 2. Use the LCD screen and keypad for programming the control and viewing its status. The right portion of the panel is used for operating the control and recloser.

If no key is pressed within fifteen minutes, the Power Save feature turns off the backlit LCD display and most LEDs (except Hot Line Tag).

ote: N Enable or disable the Power Save feature through the ProView NXG interface software. The default setting is “enabled.”

Figure 2. Form 7 control front panel

The control includes a Front Panel Inactivity Time Delay that causes the LCD display to revert to the Recloser Status menu after fifteen minutes of inactivity.

ote: N The fifteen-minute time delay and Recloser Status menu are ProView NXG interface software default settings. The menu selection and timer can be changed via the ProView NXG interface software.

The front panel (Figure 2) contains:

Status LEDs

LCD

Numeric keypad

Hot Line Tag On/Off pushbutton

TRIP (Lockout) pushbutton

CLOSE pushbutton

Status LEDs

The status LEDs (Figure 2) reflect the control and recloser status. You can reconfigure most LEDs with the exceptions of the CONTROL OK, Alarm, and the indicator for Hot Line Tag. Reconfigure the LEDs using the Workbench NXG. Refer to the Form 7 Programming Guide for additional information.

The label inserts can be user customized. Refer to the Change removable inserts section of this manual for additional information.

FREQUENCY TRIP: Indicates the recloser tripped due to an under or over frequency condition.

VOLTAGE TRIP: Indicates the recloser tripped due to an under or over voltage condition.

ABOVE MIN TRIP: The red LED indicates the line current is presently exceeding the level set for minimum trip.

PHASE FAULT: The red LEDs indicate A, B, and/or C phase current was either the maximum phase current or within 20% of the maximum when a trip signal was issued in response to an overcurrent event.

GROUND FAULT: The red LED indicates that a Ground tripping function was asserted at the time the trip signal was asserted.

LOCKOUT: A lit LED indicates the phase (A, B, or C) is in a locked-out state.

OPEN: The steady green LED indicates that the specified phase (A, B, or C) is open.

CLOSED: The steady green LED indicates that the specified phase (A, B, or C) is closed.

ALARM: The red LED indicates an alarm has been issued. View the alarm status and log on the LCD display for the specific alarm.

CONTROL OK: A lit green LED indicates the control is operating normally. This LED status is off (unlit) for system error states.

AC POWER: The green LED indicates there is adequate AC voltage to power the control.

HOT LINE TAG, Trip, and Close buttons

LCD and numerickeypad

StatusLEDs

Function keys and LEDs

Page 11: Form 7 microprocessor-based pole-mount recloser control

5INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

BATTERY: The green LED indicates there is adequate battery voltage to power the control.

PHASE VOLTAGE: A, B, C, X, Y, Z: Indicates a presence of voltage on the respective phases. The setting “V Present” in the System Configuration menu of ProView NXG sets the threshold for the LEDs to light.

INDICATOR 1–5: Customizable LED functions programmed through the Workbench NXG. The indicators lack active default values and light when the status configured through the Workbench is present.

COMM:

TX: Lights when data is being transmitted from the device.

RX: Lights when data is being received by the device over the active data port.

DATA PORTS:

PC: Green LED lights when a personal computer is connected.

USB: Green LED lights when a USB drive is connected.

LCD and keypad

The LCD and keypad provide a menu-driven interface and a numeric interface with function hotkeys. The backlit 7-line, 21-character per line LCD display provides distribution system, recloser, and control status information (Figure 3).

ote: N You can adjust the LCD display panel contrast to allow for various mounting heights and applications. To change the contrast, press and hold the FUNC key while pressing the Up or Down key.

The LCD navigation buttons are as follows:

ENTER: Select a menu option

ESCAPE: Return to the previous screen

EDIT: Modify a setting

Up: Move the cursor up

Down: Move the cursor down

Left: Move the cursor left

Right: Moves the cursor right

The number pad keys can be used alongside the FUNC key to access specific menu commands. For example, pressing the FUNC key and then entering “0082” will bring the user to the battery test screen.

The default text message displays the mode of the triple-single configuration and the status of each phase.

Figure 3. Form 7 LCD and keypad

Feature access using the FUNC key

To access certain features, press the number associated with the menu (Table 1).

Table 1. Hot key menu access

Menu Number

SETTINGS 1

SEQUENCE OF EVENTS 2

METERING 3

ALARM LOG & STATUS 4

COUNTER 5

COMMUNICATIONS 6

CALENDAR/CLOCK 7

DIAGNOSTICS 8

MENU SYSTEM 9

USB MEMORY DRIVE 0

SYM keyThe SYM key is used to enter special characters.

HMI function codesTo open an HMI menu, enter the four-digit HMI code and then press ENTER. Procedures in this manual include the required HMI function code. For a complete listing of the available codes, refer to the appendix in the Form 7 Programming Guide.

Page 12: Form 7 microprocessor-based pole-mount recloser control

6 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

HOT LINE TAG ON/OFF

The Form 7 control default configuration is with a membrane pushbutton for TRIP, CLOSE, and Hot Line Tag. Optional mechanical pushbuttons for TRIP and CLOSE and a toggle switch for Hot Line Tag are available. See Figure 4 and Figure 5.

WARNINGHAZARDOUS VOLTAGE. DO NOT USE HOT LINE TAG AS A SUBSTITUTE FOR A VISIBLE DISCONNECT. ALWAYS ESTABLISH A VISIBLE DISCONNECT PRIOR TO PERFORMING ANY WORK REQUIRING A DE-ENERGIZED LINE. FAILURE TO COMPLY MAY CAUSE DEATH, SEVERE PERSONAL INJURY, OR EQUIPMENT DAMAGE.

Hot Line Tag is provided for live-line work applications. All closing operations are disabled when the Hot Line Tag feature is activated.

IMPORTANT: Hot Line Tag activation does not cause the recloser to trip open. It only prevents the recloser from closing.

IMPORTANT: Hot Line Tag is intended solely for live-line work applications, such as maintenance, repairs or improvements to the distribution system, that occur while the line remains energized.

Figure 4. Membrane TRIP (Lockout) and CLOSE buttons, and Hot Line Tag button and indicator LEDs

Figure 5. Mechanical TRIP (Lockout) pushbutton; CLOSE pushbutton; Hot Line Tag switch and Hot Line Tag red indicator LEDs

IMPORTANT: If the Front Panel Inactivity Time Delay is enabled (default) and Hot Line Tag is active, the Hot Line Tag LED will not turn off when the inactivity timer is reached.

Hot Line Tag prevents all closing attempts from the control and shifts protection to one trip-to-lockout on the composite curve of the Hot Line Tag definite time and the TCC1 curve (whichever is faster).

Hot Line Tag takes precedence over Cold Load Pickup, Non-Reclosing, and Fast Trips Disabled.

Hot Line Tag is activated from either the operator panel toggle switch, serial communications, or a discrete SCADA function. All sources must be off to de-activate Hot Line Tag.

To activate the Hot Line Tag function from the operator panel, either press the membrane button or flip the optional toggle switch up to the ON position. The LED indicator illuminates when the function is active.

Default configuration for the Hot Line Tag function permits it to only be reset by the source that initiates it. For example, if Hot Line Tag is activated at the operator panel, the reset function is only possible at the operator panel, and not via SCADA command. If Hot Line Tag is set remotely the HLT LEDs will continually flash and will not be able to be reset from the operator panel. The flashing indicates to the user that HLT was set by a remote source, and this source can be seen through the Front Panel HLT menu. This functionality can be configured further in Proview NXG. Refer to the Form 7 Programming Guide for additional information.

TRIP (Lockout) pushbutton

The TRIP button provides front-panel access to trip (lockout) the recloser. When pressed, the TRIP pushbutton opens the recloser and locks out the control. Options for the button include a membrane button or a mechanical pushbutton. See Figure 4 and Figure 5.

CLOSE pushbutton

When pressed, the CLOSE button returns the control to the initial or home sequence position, closing the recloser. The control is then ready for the start of a new trip/close sequence. The close operation can be delayed by a user configurable time (see Manual close delay on page 10). Options for the button include a mechanical pushbutton or a membrane button (see Figure 4 and Figure 5).

ote: N A Close Malfunction alarm must be reset before Closing will be allowed.

ote: N Pressing the CLOSE button from the Lockout position initiates Cold Load Pickup (CLPU) protection, if the feature is enabled.

The user does have the ability to block COLD LOAD PICKUP through the LCD menu or by configuring one of the Option one-touch function keys via the Workbench NXG feature in ProView NXG.

If the recloser is closed, pushing and holding the CLOSE button does not activate the Cold Load Pickup feature. See Cold load pickup on page 8 in the Features section of this manual.

ON

OFF

TRIP CLOSE

(LOCKOUT)

HOT LINE TAG

Page 13: Form 7 microprocessor-based pole-mount recloser control

7INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Function keys and LEDs

Function keys provide quick access to frequently operated Form 7 control features (Figure 6). Each key has a red LED that indicates the status of the function, regardless of local or remote activation. For example, if Ground Trip Blocked is activated from a SCADA signal, the red indicator will illuminate even though it was not activated from the operator panel.

Figure 6. Form 7 control operator panel one-touch function keys

GND TRIP BLOCKED: The Ground Trip Blocked function blocks all ground protection in the control for the active profile. This red LED lights when Ground Trip Block is activated from the serial port, Ethernet communications, I/O, the interface software, or locally from the front panel.

NON RECLOSE: The control is operating in a non-reclosing mode when the NON RECLOSE red indicator is illuminated. Non-reclosing mode disables any automatic reclosing operations.

Non-reclosing does not alter the active TCC. Activation is possible from the serial port, Ethernet communications, I/O, the interface software, or locally from the front panel.

SUPERVISORY OFF: When the SUPERVISORY OFF red indicator is illuminated, supervisory commands are blocked. Supervisory functions through the serial and Ethernet communications ports and the discrete I/O are blocked. Proview NXG communications through the Ethernet port remain active independent of the status of the SUPERVISORY OFF switch. Activation of this function key is restricted to locally from the front panel. Operational data and metering information are available while the control is in the SUPERVISORY OFF position. The TRIP and CLOSE pushbuttons and Hot Line Tag are active independent of the SUPERVISORY OFF function.

A PHASE SELECT, B PHASE SELECT, C PHASE SELECT: The Form 7 control, when in Single-Phase Trip/Single-Phase Lockout mode, has phase selection keys available for the user to indicate which phase(s) of the triple-single recloser will operate when the manual TRIP (LOCKOUT) and CLOSE pushbuttons on the Form 7 operator panel are pressed. When the TRIP or CLOSE buttons are pressed, only the phase(s) that are selected (LED on) will trip or close.

OPTION 1–9: The OPTION function keys must be programmed using the ProView NXG software. These options do not have active default values. OPTION LEDs are illuminated when the options configured via the Workbench NXG are selected. Refer to the Form 7 Programming Guide for additional information.

These OPTION keys provide a momentary signal. For instance, these keys can be programmed to toggle control status, protective functions, or a momentary input pulse.

ALT PROFILE SELECT: Displays the ALT PROFILE SELECT menu.

PUSH BUTTONS LOCKED: To lock all pushbuttons except TRIP, CLOSE, and HOT LINE TAG, press and hold PUSH BUTTONS LOCKED for 4 seconds. To unlock, press and hold PUSH BUTTONS LOCKED for 4 seconds.

FeaturesThe following control features and accessories are standard on the Form 7 recloser control.

Control security

To limit the programming and viewing to authorized personnel, the control provides more than 10 user-configurable password and username combinations. Configure these usernames and passwords using the Proview NXG software. When configured, the usernames and passwords are used for Proview NXG access and for logging into the Human Machine Interface (HMI).

Refer to the Form 7 Programming Guide for additional information.

Page 14: Form 7 microprocessor-based pole-mount recloser control

8 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Protection profiles

Eight protection profiles capable of fully specifying control operation are standard in the control. Each protection profile includes the following settings:

Overcurrent Protection

Operation Sequence

Reclose Intervals

Cold-Load Pickup

Hot Line Tag Functionality

High Current Lockout

Reclose/Retry

Directional Protection

Sync Check

Sequence Coordination

Over/Under Frequency

Over/Under Voltage

Switch on to Fault

Target Reset

Time current curves (TCC)

Time-current curves are available for numerous functions, including fast and delayed operations for phase, ground, and negative sequence protection. Each time-current curve is selected from 51 curves (includes IEC, IEEE, and SEL curves) which can be further customized by the user.

The time-current curves include the following modifications for phase, ground, and negative sequence protection:

Time Multiplier with a range of 0.1 to 25 in 0.001 increments.

Time Adder with a range of 0 to 30 seconds in 0.001 second increments.

Minimum Response Time with a range of 0.01 to 1 seconds in 0.001 second increments.

High Current Trip multiplier with a range of 1 to 32 multipliers in increments of 0.001.

High Current Trip Time Delay with a range of 0.01 to 0.150 second in 0.001 second increments.

Time Dial Reset coefficient with a range of 0.000001 to 30 seconds in 0.000001 second increments.

Sequence coordination

Sequence Coordination eliminates nuisance tripping due to miscoordination with downstream devices. It allows the control to step through selected operations in the operating sequence without tripping. The control will step forward in the operating sequence when it detects a down-line device has operated. The number of Sequence Coordination advances is programmable from one to three operations and is independently selectable for each protection profile.

Cold load pickup

The control includes a Cold Load Pickup feature to prevent the control from tripping while energizing non-fault system loads. This feature has independently programmable minimum trip value time-current curve, reclose interval, and number of independent operations to lockout for each protection profile. Cold Load Pickup also includes TCC Multipliers, TCC Adders, Minimum Response Time, Time Dial Reset, and High Current Lockout. Also, direct values, not multiples of minimum trip, are provided for high current lockout.

High current lockout

The high current lockout (HCL) feature automatically places the control in lockout when the current exceeds a programmed threshold on phase, ground, or negative sequence. On each of the protection profiles, the value for High Current Lockout can be set for operation one, two, or three. The control is placed in lockout if the current exceeds the programmed value during the present operation.

Thermostatically controlled heater

The control has a standard 100 Watt thermostatically controlled heater (ON 70 °F, OFF 85 °F) for humidity control and is voltage input independent. The heater is powered by 120/240 Vac from the power supply board.

Metering

The control provides instantaneous and/or demand metering with programmable integration intervals for the following functions:

Real and reactive power for each phase and total on an individual phase basis.

Demand currents on a per phase basis.

Instantaneous currents, including ground current.

Instantaneous voltage on a per phase basis.

Instantaneous frequency.

Positive, negative, and zero sequence voltages.

Instantaneous power factor on a per phase basis.

Metering settings to include demand interval, and alarm thresholds for current, single-phase kW, three-phase kW, single-phase kvar, and three-phase kvar.

Page 15: Form 7 microprocessor-based pole-mount recloser control

9INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Event recorder

The Form 7 control can perform Sequence of Events timestamping. This includes both factory and user defined Sequence of Events. Program user-defined user defined Sequence of Events (inputs) through the Workbench NXG.

There are currently over 160 factory defined event types including:

Overcurrent Protection Trip

External Trip

Non-Reclose Trip

External Close

Lockout

Sequence Reset

The Event Recorder saves the last 1500 events and the last 50 events are viewable from the Form 7 LCD. Refer to the Form 7 Programming Guide for additional information.

Discrete SCADA communications

The control provides two output status contacts and two input control contacts as standard.

By default, the output and input contacts are not configured. Use the Proview NXG Workbench to program these contacts to perform specific operations.

Each control contact input is explicitly configurable (no default configuration) using the Proview NXG Workbench. Contacts accept a whetting voltage range of 12 – 250 Vdc, 120/240 Vac. Each digital input can be configured as a momentary, maintained, or maintained with precedence contact within ProView NXG Workbench.

Removable inserts

Removable inserts are included with the control to allow customization for specific protection requirements. Inserts are available for the status LEDs, and the operator panel function keys. The removable inserts are designed for use without adhesives, label makers, or temporary labels. Refer to the Change removable inserts section in this manual for more information.

Workbench NXG

The Workbench NXG provides access to various inputs, intermediate variables, and internal Form 7 alarms, status, and targets to allow user customization of the Form 7 recloser control to meet specific and unique applications. The Workbench NXG also gives the user the ability to perform logical functions with these variables by using a simple graphical user interface. Use of the Workbench NXG is not a requirement for operation.

Refer to the Form 7 Programming Guide for additional Workbench NXG information.

Over/under frequency protection

Six levels of frequency protection are included with the control. Each level is configurable as either overfrequency or underfrequency. Overfrequency and underfrequency are included as part of each protection profile.

A frequency protection restoration function can be enabled by the user. This function allows the recloser to automatically close if the frequency returns to within the user-configured frequency band during the user-specified time.

Over/under voltage protection

The Form 7 control provides the following voltage protection features:

Under-voltage (27) for single-phase and three-phase with capability of single-phase operation

Over-voltage (59) for single-phase and three-phase

Negative Sequence Over-voltage (59Q)

Zero Sequence Over-voltage (59N)

A voltage protection restoration function can be enabled by the user. This function allows the recloser to automatically close if the voltage returns to within the user-configured voltage band during the user-specified time.

Directional

Directional functionality is included to maintain system coordination from multiple sources, as well as circuit re-configuration for each profile. Directional applies to phase, ground, and negative sequence protection, selected independently. The maximum torque angle has a range of –90 to +90 degrees.

Fault location

The Form 7 control includes a fault location feature that estimates the distance to a fault. This feature uses the reactance method of fault location. This method considers the ratio of the difference between the measured reactance and the source impedance relative to the reactance of the entire line and estimates the distance to the fault.

Sync check

The Form 7 control includes sync check functionality. Sync check enables permissive close supervision based on the user configured settings. Sync check allows for closing for any combination of dead/live bus/line and to perform anticipatory closing for a live bus/live line condition by calculating slip and anticipating the mechanism closing delay. In addition to the anticipatory close calculation, the sync check system:

Performs verification of line and bus voltage magnitudes and frequencies to determine that they are within predetermined ranges

Checks that the angular differences between the two systems is also within the predetermined range

Page 16: Form 7 microprocessor-based pole-mount recloser control

10 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Sync check parameters include the following configurable settings:

Voltage angle

Mechanism operating delay

Static angle delay

Dead threshold

Live threshold

Upper voltage limit

Lower voltage limit

Upper frequency limit

Lower frequency limit

Fail-to-close timer

Data profiler

A fully configurable data profiler is available which allows the user to collect information by sampling data at selectable intervals. These time-stamped values can then be viewed to determine weekly load profiles, daily harmonic disturbances or hourly voltage fluctuations. The number of days of information the data profiler can provide depends upon configuration parameters. The data recorded is placed in a data table that can be exported to an external CSV file for further review (outside of ProView NXG).

Refer to the Form 7 Control Programming Guide for additional information.

Manual close delay

Manual Close Delay provides a delay from the time that the manual CLOSE button is pushed to the time the manual close operation is performed.

The delay is programmable from 0 to 60 seconds in 1 second increments. A programmed delay value can be overridden for immediate closing by pressing the CLOSE button a second time.

An active Manual Close Delay can be canceled by pressing the TRIP/LOCKOUT button.

The default setting has the feature disabled (0 seconds). A countdown on the front panel LCD screen indicates Manual Close Delay is active.

Abbreviated sequence (79AS)

Abbreviated Sequence (79AS) is a function that can be enabled by the user to advance the start of the reclosing sequence to a later position, as selected by the user. Abbreviated Sequence (79AS) must be enabled and unblocked for the sequence position to be advanced.

Abbreviated Sequence applies to any overcurrent protection function that relies on the reclosing (79) sequence position to determine operation settings such as TCC curves, number of shots to lockout, etc.

Switch-onto-Fault (SOTF)

The “Switch-onto-Fault” (SOTF) feature is a setting that allows the control to differentiate between close protection between re-energizing large loads (CLPU) and re-energizing when a fault is still present on the line.

Switch mode

Switch Mode is an additional targeting element within the Form 7 control, which allows the configuration of a separate pickup value (for Phase and Ground) that will set the control’s fault targets when pickup is exceeded.

An inrush blocking feature is available which allows a temporarily increased pickup level for phase current and blocking of ground targeting entirely for a specified time after recloser closure.

The Switch Mode element shall run in parallel with all other protection functionality programmed into the Form 7 control.

Sectionalizer mode

Sectionalizer Mode allows the recloser to operate as a sectionalizer. The Form 7 control can be programmed to count faults interrupted by an upstream recloser, and then isolate a fault section downstream from the Form 7 control’s location when the number of programmed fault interruption counts to lockout is reached.

The Form 7 control provides two independent sectionalizer elements (element 1, element 2) that count the non-directional/directional/dual directional faults, in coordination with other recloser elements, in the Form 7 control and the distribution system.

Page 17: Form 7 microprocessor-based pole-mount recloser control

11INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Breaker failure

Breaker failure protection is provided as a failsafe means of detecting if the connected recloser was not able to clear the fault it was intended to trip on. A breaker failure signal is generated by the Form 7 control if it sends a trip command, but sees the recloser remain closed.

The breaker failure signal can be mapped to an output contact I/O for a local backup breaker or recloser to clear the fault in the event the connected recloser is unable to clear the fault.

Non-volatile mode controls

The Form 7 control provides Non-Volatile Mode Controls (NVMC) to block and unblock various protection elements and control functions at run-time. Configuration options are provided to tailor NVMC operation to specific applications, including configurable profile dependence. The default NVMC logic allows only those elements and functions that have been enabled and configured in the active protection profile to be unblocked or blocked by user commands, SCADA commands, or Workbench logic. The NVMC logic stores block/unblock status for each protection profile by default, but can be configured to use a single block/unblock status across all profiles for specific control modes, if desired.

Communications

Communication ports

On the CPU board, the standard Form 7 control has the following standard ports (see Figure 7):

9-pin RS-232 port

USB 2.0 ports (3): Two ports are type A and serve as USB host ports. The other port is type B and serves as a USB device port. One host port and one device port are brought out to the inner swing panel for easier access. USB 2.0 host and device ports

Ethernet RJ45

IRIG-B port: User time-syncing

Communication protocols

The DNP3 communication protocol is available for use with the Form 7 control. The user can configure this protocol with the ProView NXG software in the communications section.

Ethernet communications ProView over TCP/IP

DNP3 over TCP/IP

DNP3 UDP/IP

DNP3 with SAv5

Ethernet connection allows for network application of the Form 7 control for both DNP3 and ProView NXG protocols.

Ethernet configuration is accomplished via ProView NXG interface software. Refer to the Form 7 Control Cybersecurity and Communications Guide for Ethernet Configuration information.

The user can simultaneously communicate to the Form 7 control using any of the data ports provided on the module.

Page 18: Form 7 microprocessor-based pole-mount recloser control

12 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 7. Form 7 recloser module access panel terminal block and communication ports

Battery

Optional PT sensingterminals (TB8)

CPU

Aux. bays1, 2, 3

Exp. bays4, 5

Exp. bays6, 7

Optional door switch

USB ports(host and device)

Control Front Panel(Swing Panel)

Voltagesensing DAQ

Recloser interface (RIF)

High voltagepresent LED

Powersupply

Options/accessorytray

Options/accessoryback plate

Convenience outlet(heater behind)

Fuse

AC inputterminal blocks(TB7)

Door

Heater/thermostat

Page 19: Form 7 microprocessor-based pole-mount recloser control

13INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Control information labelRefer to the Control ID label on the inside of the cabinet door for the specific control information including serial number and configuration. Refer to Figure 8 for an example of the Control ID Label.

Figure 8. Control information label

Module accessAccess the module by opening the front swing panel. The CPU board contains serial ports and other connections (Figure 7).

INSTALLATION

PrerequisitesPerform all prerequisites and have all items needed on hand before beginning installation

Perform initial programming (prior to installation)

CAUTIONEQUIPMENT MISOPERATION. DO NOT CONNECT THIS CONTROL TO AN ENERGIZED RECLOSER UNTIL ALL CONTROL SETTINGS HAVE BEEN PROPERLY PROGRAMMED AND VERIFIED. REFER TO THE PROGRAMMING INFORMATION FOR THIS CONTROL. FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION, EQUIPMENT DAMAGE, AND PERSONAL INJURY.

NOTICEEQUIPMENT MISOPERATION. CHECK MINIMUM TRIP VALUES PRIOR TO CHANGING AN ALTERNATE PROFILE. FAILURE TO DO SO MAY CAUSE MISOPERATION OF THE RECLOSER UNDER LOAD CONDITIONS.

IMPORTANT: Program all protection profiles. Unused alternate profiles should be programmed with the same settings as one of the applicable profiles. Default settings on unused alternate profiles can cause unnecessary outages if they are below normal system requirements.

ote: N Initial programming of the control is the responsibility of a qualified technician or engineer familiar with control functions and programming parameters required for the specific recloser installation.

Before operating the control with an energized recloser, program the control with all necessary operating settings, all alternate profiles, and parameters.

Use the Form 7 ProView NXG interface software to program the control. Refer to the Form 7 Programming Guide for additional information.

Control/recloser compatibility

The Form 7 pole-mount recloser control is compatible with the NOVA NX-T recloser. Refer to Service Information MN280087EN NOVA NX-T Recloser Installation and Operation Instructions. Only use the Form 7 control with compatible reclosers.

Page 20: Form 7 microprocessor-based pole-mount recloser control

14 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Items needed for installation

In addition to the Form 7 Control, make sure you have the following items available before you start installation:

Personal Protective Equipment (PPE) as required by local safety standards. Safety glasses with side shields and insulating gloves are recommended at a minimum.

Lock (if needed to prevent unauthorized access)

Screwdriver with 3.5 mm x 0.5 mm head (needed to insert and remove wires from touch safe terminal blocks)

37-Pin Breech-Lok™ Control Cable (refer to catalog for part number)

Power Cable(s) and PT for control power (refer to catalog for part numbers). PTs can be configured to be site ready installed on the NOVA NX-T frame, if required. The transformer used for control power should be a minimum of 1 kVA.

Battery (Packed Separately)

Optional Cable Locking Sleeves (refer to catalog for part number)

Prepared site and required hardware (see Figure 9 for recommended mounting dimensions)

Optional radio and communications provisions (see Radio mounting accessory on page 38)

ProcedureThe following steps outline how to install the Form 7 control. Additional information on each step is provided in the related sections:

1. Complete prerequisites (page 13):

a. Perform initial programming (page 13).

b. Verify control/recloser compatibility (page 13).

c. Obtain all items needed for installation (page 14).

2. Install bypass switches. Refer to bypass switch manufacturer for information.

3. Mount the control (page 14).

4. Ground the control (page 16).

5. Install the battery (page 19).

6. Test the battery. Refer to the procedure provided in Installed battery test on page 32.

7. Make customer connections for AC Power. Refer to Spring loaded contacts on page 21 and Power connections on page 22.

8. Verify front panel labels. Modify if needed using the procedure in Change removable inserts on page 28).

9. Verify initial control programming. Refer to Perform initial programming (prior to installation) on page 13.

10. Make customer connections to terminal blocks. Refer to Spring loaded contacts on page 21.

11. Wire and verify standard IO programming and ratings. Refer to the Form 7 Programming Guide, for information.

12. Install the control cable (page 28).

13. Lock the control (page 29).

Mount the control

WARNINGTHIS EQUIPMENT IS NOT INTENDED TO PROTECT HUMAN LIFE. FOLLOW ALL LOCALLY APPROVED PROCEDURES AND SAFETY PRACTICES WHEN INSTALLING OR OPERATING THIS EQUIPMENT. FAILURE TO COMPLY MAY RESULT IN DEATH, SEVERE PERSONAL INJURY AND EQUIPMENT DAMAGE.

WARNINGFALLING EQUIPMENT. USE THE LIFTING LUGS PROVIDED AND FOLLOW ALL LOCALLY APPROVED SAFETY PRACTICES WHEN LIFTING AND MOUNTING THE EQUIPMENT. LIFT THE UNIT SMOOTHLY AND DO NOT ALLOW THE UNIT TO SHIFT. IMPROPER LIFTING CAN RESULT IN SEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE.

Mount the Form 7 recloser control in a convenient, accessible location. Mounting dimensions are provided in Figure 9.

ote: N Unless otherwise specified, dimensions shown in inches (mm).

A hole and keyway in the control mounting bracket accommodates a 5/8-inch (15.9 mm) bolt.

Page 21: Form 7 microprocessor-based pole-mount recloser control

15INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 9. Form 7 pole-mount recloser control weight, dimensions, and pad-lock shackle diameters— dimensions in inches (mm)

15.90(405.0)

Ø1.13 (29.0)Lifting holes

17.40(442.0)

Provisions for0.625 (16.0) mounting

Center of gravityCenter

of gravity

3-pointlatch handle

34.90(885.0)

Ø0.75 (19.0)hole provided for

customer lock

37.00(940.0)

40.00(1016.0)

17.90(455.0)

8.60(218.0)

Front viewdoor closed

Side view

6.70(170.0)

Six available Ø1.5 (38.0)receptacle holes for options

and accessories

3.50(89.0)

2.60(67.0)

Vent opening

2.60(67.0)

Ground lug for#4–#14 solid orstandard wire

Bottom view

Controlinterface

Options/accyreceptacle plate

Top view

29.00(737.0)

24.70(627.0)

113°

CONTROL WEIGHT: 150 lbs. (68 kg) [without battery]13 AH BATTERY WEIGHT: 24 lbs. (10 kg)(All weights are approximate.)

Page 22: Form 7 microprocessor-based pole-mount recloser control

16 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Ground the control

WARNINGHAZARDOUS VOLTAGE. RECLOSER AND CONTROL MUST BE SOLIDLY GROUNDED. FOLLOW ALL LOCALLY APPROVED PROCEDURES AND SAFETY PRACTICES WHEN GROUNDING THIS EQUIPMENT. IMPROPER GROUNDING CAN RESULT IN CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY

Solidly ground the recloser and control. Ground the control by grounding the control cabinet. A grounding connector on the underside of the cabinet accommodates No. 14 solid through No. 4 stranded conductors. Refer to Figure 9, Bottom View, for ground lug location.

Suggested methods for grounding the control and recloser are shown in Figure 10, Figure 11, and Figure 12.

Figure 10 illustrates grounding methods for 3-wire ungrounded and 4-wire multi-grounded systems with local supply voltage transformer.

Figure 11 illustrates grounding methods for 3-wire ungrounded and 4-wire multi-grounded systems with remote supply voltage transformer.

Figure 12 illustrates grounding on a 3-wire uni-grounded system.

For effective surge protection, route all Form 7 control and power conductors parallel to a corresponding ground path. For example, the AC power supply for the control should be parallel to and equal in length to the transformer ground path. The control cable should be parallel to and routed close to the recloser ground path.

Grounding with a local supply voltage transformer; 4-wire multi-grounded, 3-wire ungrounded, or impedance-grounded

Installation of a Form 7 control and NOVA NX-T system must include the following:

Protection of the recloser bushings and the supplying transformer with lightning arresters

Grounding of all recloser head(s) and tank(s)

Grounding of the transformer tank

Grounding of the control cabinet

Grounding of the SCADA equipment

IMPORTANT: All external inputs to the Form 7 control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5 kV per foot can develop in the conductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.

4-Wire multi-grounded systems

IMPORTANT:In pole-mounted applications, a ground connection must be made between the recloser, transformer, recloser control, and SCADA equipment for proper protection of the equipment. The pole ground must be sized per local utility practices to minimize the impedance between the recloser and the control.

3-Wire ungrounded and impedance grounded systems

The use of a grounding mat may be required depending upon the local safety regulations defining the permissible step and touch potential levels. Consult local regulations for proper grounding procedures

Grounding with a remote supply voltage transformer; 4-wire multi-grounded, 3-wire ungrounded, or impedance-grounded

Installation of a Form 7 control and NOVA NX-T system with a remote supply voltage transformer must include the following:

Protection of the recloser bushings and the supplying transformer with lightning arresters

Grounding of all recloser head(s) and tank(s)

Grounding of the transformer tank

Grounding of the control cabinet

Grounding of the SCADA equipment

Page 23: Form 7 microprocessor-based pole-mount recloser control

17INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 10. Recommended grounding for control installed on 4-wire multi-grounded, 3-wire ungrounded, or impedance-grounded systems with local supply voltage

IMPORTANT: In pole-mounted applications, a ground connection must be made between the recloser, transformer, recloser control, and SCADA equipment for proper protection of the equipment. The pole ground must be sized per local utility practices to minimize the impedance between the recloser and the control.

IMPORTANT: All external inputs to the Form 7 control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5 kV per foot can develop in the conductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.

Customer ground connectionat external lug

Pole ground

TransformerSurge

arrester

GNDNEUAC

Typical transformer mountingis 180 to the recloser

Supplyvoltage

Input terminalblock

Form 7 control

NE

UA

C

Pole mounting frame

Recloserhead ground

Surgearrester

Surgearrester

PoleSurgearrester

Controlcable

AC

NEUTRAL

Form 7 control

Supply voltage

Transformer

Electrical connections line to neutral connected transformer

Inputterminalblock

External ground lug

Form 7 control

ACNEUTRAL

Supply voltage

Transformer

Electrical connectionsline to line connected transformer

Linetolinevoltage

Input terminalblock External

Ground Lug

Page 24: Form 7 microprocessor-based pole-mount recloser control

18 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 11. Recommended grounding for control installed on 4-wire multi-grounded, 3-wire ungrounded, or impedance-grounded systems with remote supply voltage transformer

Grounding on a 3-wire uni-grounded system

Installation of a Form 7 control and NOVA NX-T system on a 3-wire uni-ground system must include the following:

Protection of the recloser bushings and the supplying transformer with lightning arresters

Grounding of all recloser head(s) and tank(s)

Grounding of the transformer tank

Grounding of the control cabinet

Grounding of the SCADA equipment

WARNINGHAZARDOUS VOLTAGE. USE LOCALLY APPROVED OPERATOR SAFETY PROCEDURES FOR PROPER INSULATION WHEN MAINTAINING THIS EQUIPMENT. HIGH VOLTAGE STEP AND TOUCH POTENTIAL IS CHARACTERISTIC IN UNI-GROUND SYSTEMS. FAILURE TO COMPLY CAN CAUSE DEATH OR SEVERE PERSONAL INJURY.

CAUTIONEXPORTED POTENTIAL. DO NOT MAKE DIRECT ELECTRICAL CONNECTIONS TO REMOTE DEVICES. ALL SCADA EQUIPMENT MUST BE MOUNTED LOCALLY OR CONNECTED USING THE FIBER-OPTIC OR RADIO COMMUNICATION ACCESSORY. DIRECT CONNECTIONS TO REMOTE DEVICES CAN PRODUCE EXPORTED POTENTIAL CAUSING EQUIPMENT DAMAGE OR PERSONAL INJURY.

CAUTIONHAZARDOUS VOLTAGE. DO NOT USE A SHARED LOW VOLTAGE NETWORK TO POWER THE RECLOSER CONTROL UNLESS THE NETWORK IS SPECIFICALLY DESIGNED TO WITHSTAND MAXIMUM GROUND POTENTIAL RISE. GROUND FAULTS ON A HIGH VOLTAGE NETWORK CAN CREATE A RISE IN GROUND POTENTIAL.

IMPORTANT: In pole-mounted applications, a ground connection must be made between the recloser, transformer, recloser control, and SCADA equipment for proper protection of the equipment. The pole ground must be sized per local utility practices to minimize the impedance between the recloser and the control.

Pole

Control cable

Customer ground connectionat external lug

Pole ground

Surgearrester

Surgearrester

Surgearrester

Pole mounting frame

NE

UA

CInput terminal block

Form 7 control

Pole

Transformer

ACNEUGND

Note: Distance between transformer and recloser should be one pole span or less.

Supplyvoltage

Surgearrester

Pole ground

SystemNeutral

AC

NEUTRAL

Form 7 controlSupply voltage

Transformer

Electrical connections—remote dedicated supply transformer

Inputterminalblock

Externalground lug

Form 7 control

ACNEUTRAL

115 Vacsupply voltage

Local isolationtransformer

Electrical connections—using isolation transformer

Customersuppliedlow voltage

Low voltagearresterExternal

ground lug

Inputterminal

block

Low voltage distribution network

Recloser head ground

Page 25: Form 7 microprocessor-based pole-mount recloser control

19INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

IMPORTANT: All external inputs to the Form 7 control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5 kV per foot can develop in the conductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.

Figure 12. Recommended grounding for control installed on a 3-wire uni-grounded system

Install the battery

The 24 Vdc control battery in the Form 7 recloser control is fully charged prior to shipment and is ready for use.

The control is shipped with the battery not installed

Do not transport any Form 7 control with the battery inside the control enclosure

The battery shall be installed only after the control has been mounted

IMPORTANT: If battery power is connected to the control without AC power supplied, the control can be activated by pressing the “Manual Battery Reconnect” button located on the Form 7 power supply (see Figure 30). Note: While in this mode, the battery will discharge until AC power is connected.

IMPORTANT: Disconnect the separable connector prior to removing battery. Do not reconnect the separable connector until after the battery is installed. Do not disconnect the “+” and “–” leads from the battery posts if the separable harness is connected; battery wiring harness “+” and “–” post terminals are energized and can short-circuit if they come in contact with the cabinet or each other, consequently damaging the internal power supply.

To install the battery:

1. Open and hold up Velcro strap.

2. Place the battery against the back of the holding tray in the bottom of the control with the battery terminals facing toward the front of the control enclosure.

3. Feed strap through strap slot in battery tray and tighten the strap.

4. Fold the strap up and over, attaching the end of the strap to the middle of the strap. See Figure 13.

5. Connect the red and black connector from the battery to the mating red and black connector from the control to complete the battery installation process.

Controlcable

Customer groundconnection

at external lug

Poleground

Typical transformer mountingis 180° to the recloser

NE

UA

C

Supplyvoltage

Input terminalblock

Form 7 control

AC

NEUTRAL

Form 7 controlSupply voltage

Transformer

Electrical connections line to neutral connected transformer

Input terminalblock

External ground lug

Surgearrester

GNDNEUAC

Transformer

Control height must be3 meters (10 feet)

minimum above earth

Pole

Surgearrester

Surgearrester

Polemounting frame

Recloserhead ground

Surgearrester

Page 26: Form 7 microprocessor-based pole-mount recloser control

20 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 13. 24-Volt DC 13 Ahr battery

Make customer connections for AC power

DANGERHAZARDOUS VOLTAGE. DO NOT CONNECT POTENTIAL TRANSFORMER LOW-VOLTAGE SECONDARIES TO THE CONTROL THROUGH CABLES OR OTHER WIRING UNTIL THE UNIT IS INSTALLED IN THE FIELD. TRANSFORMER HIGH-VOLTAGE PRIMARY WINDINGS WILL BECOME LIVE WHEN 120/240 VAC IS APPLIED TO THE CONTROL FROM AN ALTERNATE SOURCE IF THE TRANSFORMER SECONDARY IS CONNECTED. FAILURE TO COMPLY MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

WARNINGHAZARDOUS VOLTAGE. BEFORE APPLYING POWER TO THE CONTROL, CONFIRM THAT MALE PINS OF THE INPUT POWER RECEPTACLE ARE ELECTRICALLY INSULATED TO PREVENT UNINTENTIONAL CONTACT WITH 120/240 VAC VOLTAGE. FAILURE TO DO SO MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

CAUTIONEQUIPMENT DAMAGE. DO NOT DRILL CONNECTION HOLES INTO THE TOP OF THE CABINET. CONNECTION HOLES IN THE TOP OF THE CABINET WILL ALLOW MOISTURE TO SEEP INTO THE CONTROL AND DAMAGE THE COMPONENTS OR CAUSE CONTROL MISOPERATION. FAILURE TO COMPLY WILL VOID THE CONTROL’S FACTORY WARRANTY.

Input power to the Form 7 recloser control can be connected to an optional fuse at the terminal block. Incoming power connects to terminal block TB7. Transformer voltages used for metering will connect to terminal block TB8 (and are fused at the terminal block).

For single-phase 120 Vac or 240 Vac voltage supply, connect to TB7 as shown in Figure 16. For three-phase voltage supply, connect to TB8 as show in Figure 17. For 240-Volt, 3-wire transformer connection refer to Figure 20.

Input power provides:

Power to the Form 7 recloser control

Voltage and power metering

Power to the thermostatically controlled heater

Power to the convenience accessory outlet

Power supply (battery charger)

Incoming AC power is routed to the power supply. The power supply is configured at the factory based on the customer order and accepts either 120 Vac or 240 Vac (see Figure 14). The power supply’s battery charger is temperature-compensated to optimally charge the control battery. The power supply also includes an auxiliary power supply for connection to communication equipment (radios, modems, and so on). This auxiliary power supply is rated at 40 W continuous, 75 W peak. The 13.5 Vdc output between TB9 pin 4 (+) and pin 5 (–) on the power supply is rated for maximum continuous output of 17.25 W at 13.5 Vdc. Use shielded wire whenever making connections to the auxiliary power supply. Additional features include:

Positive LED indicator for power supply presence

Use of factory configured 120 Vac or 240 Vac for multiple transformer connections

Self-protective fuses (5 A, 250 Vac): FU1 and FU2

Whetting voltage (28 Vdc) for I/O contact inputs. Refer to Figure 23, TB9, Pin 1 (+) and Pin 2 (–)

13.5 Vdc for automation power supply (radio accessories)Refer to Figure 23, TB9, Pin 4 (+) and Pin 5 (–)

WARNINGHAZARDOUS VOLTAGE. DO NOT DISASSEMBLE THIS MODULE WITH THE CONTROL ENERGIZED OR WHILE THE “HIGH VOLTAGE PRESENT LED” IS LIT. IF LED DID NOT LIGHT WHEN CONTROL WAS DE-ENERGIZED, DO NOT DISASSEMBLE THE MODULE AND CONSULT MANUAL. FAILURE TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH.

The Form 7 power supply provides 225 Vdc to the actuator during a close or open operation.

When the module is disconnected from AC power and DC battery, the HIGH VOLTAGE PRESENT LED is lit (steady red). After about 7 minutes, the LED dims and is unlit indicating the module is fully de-energized. Before removing the power supply board, make two “Live-Dead-Live” checks of voltage on the power supply.

Velcrostrap Battery

Page 27: Form 7 microprocessor-based pole-mount recloser control

21INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Remove the power supply board To remove the power supply board:

1. Wear insulating gloves.

2. De-energize the control.

3. Check and verify that the voltage between P155 (CAP) pin 1 (+), and P155 pin 2(–) is near 0 Vdc. Refer to Figure 14.

4. Check and verify that the voltage between P153 (Heater) pin 1 (+) and pin 3 (–) is near 0 Vdc. Refer to Figure 14.

5. After verifying that both of the above voltages are not present, remove the power supply from the Form 7 control. Then the Form 7 power supply module can be disassembled.

WARNINGHAZARDOUS VOLTAGE. DO NOT TOUCH THE PINS INSIDE THE CONTROL CABLE CONNECTOR. PINS COULD BE ENERGIZED IF A TRIP OR CLOSE SIGNAL IS ISSUED. FAILURE TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH.

ote: N Control is interlocked such that during normal operation, voltage cannot appear unless correct 52a/b status is reported by the recloser.

Figure 14. Power supply (battery charger)

Spring loaded contacts

Two terminal blocks, TB7 and TB8, provide connections to the Form 7 recloser control. These touch safe terminal blocks are spring loaded for #12 AWG wire (see Figure 15 for examples of these terminal blocks).

TB7 Power Supply Terminal BlockThis contact provides power to the Form 7 control and is directly connected to the power supply circuit board.

To insert a wire into a TB7 terminal:

1. Insert a screwdriver into the associated square access point.

2. Press in this access point to open the contact and allow the wire to be inserted.

3. Insert the wire.

4. Remove the screwdriver to return pressure to the contact and secure the wire.

TB8 Metering Terminal BlockThis contact senses transformer voltage. The wiring of the transformers should follow the application illustrations per Figure 17, Figure 18, Figure 19, and Figure 20. Only Form 7 controls configured for PT voltage sensing have this terminal block and associated board.

To insert a new wire into a TB8 terminal:

1. Insert a screwdriver into the central terminal associated with the wire point.

2. Press in this access point to open the contact and allow the wire to be inserted.

3. Insert the wire.

4. Remove the screwdriver to reassert pressure on the wire and hold it in place.

WiringIf PT sensing is configured for the unit, default factory wiring connects two wires from TB7 to the Metering Terminal Block TB8. See Figure 15.

Figure 19 shows customer connections for TB8, 120 Vac Delta Connection.

The wiring from S1H to TB8-3 and from S1N to TB8-4 connects control power inputs to the B phase metering (Figure 16). If the incoming power supply voltage is from a different phase the TB8 landing location will be different. See Figure 17.

For A phase incoming power, connect to TB8-1.

For C phase incoming power, connect to TB8-5.

150

POW

ER S

UPP

LY

P153

HEATERAC INPUT POWER FU1FU1

HIGH VOLTAGEPRESENT

MA

NU

AL

BAT

TERY

REC

ON

NEC

T

P152P151

P154

1 1

1 4

2

1

1

12

TB9 P156

CAPP155

28 VDCWHETTINGVOLTAGE

13.5 VDCAUX

POWER

P153(heater)

FU1FU1 P152(AC input power)

P151

P154 P156

TB9

P155(CAP)

28 Vdcwhettingvoltage

13.5 VdcAUXpower

Manual battery reconnect button

Page 28: Form 7 microprocessor-based pole-mount recloser control

22 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Power connections

TB8 is a PT accessory board that is used for up to 6 voltage inputs. TB8 will only be present in Form 7 controls configured for PT voltage sensing. Use a 3.5 mm flathead screwdriver to open contact jaws on TB8 before making connections.

Figure 15. Default factory wiring connected to B-Phase voltage metering with B-Phase incoming supply

DANGERHAZARDOUS VOLTAGE. DO NOT CONNECT POTENTIAL TRANSFORMER LOW-VOLTAGE SECONDARIES TO THE CONTROL THROUGH CABLES OR OTHER WIRING UNTIL THE UNIT IS INSTALLED IN THE FIELD. TRANSFORMER HIGH-VOLTAGE PRIMARY WINDINGS WILL BECOME LIVE WHEN 120/240 VAC IS APPLIED TO THE CONTROL FROM AN ALTERNATE SOURCE IF THE TRANSFORMER SECONDARY IS CONNECTED. FAILURE TO COMPLY MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

WARNINGHAZARDOUS VOLTAGE. BEFORE APPLYING POWER TO THE CONTROL, CONFIRM THAT MALE PINS OF THE INPUT POWER RECEPTACLE ARE ELECTRICALLY INSULATED TO PREVENT UNINTENTIONAL CONTACT WITH 120/240 VAC VOLTAGE. FAILURE TO DO SO MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

Figure 16. Single-phase transformer connection, B-phase input for power and sensing

S1 H

S1 N

S2 H

S2 N

1

2

3

4

1 2 3 4 5 6 7 8 9 10 11 12

TB7

TB8

S1 H

S1 N

S2 H

S2 N

1

2

3

4

NEU

User-supplieddisconnect

switch

TB7

Page 29: Form 7 microprocessor-based pole-mount recloser control

23INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

DANGERHAZARDOUS VOLTAGE. DO NOT CONNECT POTENTIAL TRANSFORMER LOW-VOLTAGE SECONDARIES TO THE CONTROL THROUGH CABLES OR OTHER WIRING UNTIL THE UNIT IS INSTALLED IN THE FIELD. TRANSFORMER HIGH-VOLTAGE PRIMARY WINDINGS WILL BECOME LIVE WHEN 120/240 VAC IS APPLIED TO THE CONTROL FROM AN ALTERNATE SOURCE IF THE TRANSFORMER SECONDARY IS CONNECTED. FAILURE TO COMPLY MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

WARNINGHAZARDOUS VOLTAGE. BEFORE APPLYING POWER TO THE CONTROL, CONFIRM THAT MALE PINS OF THE INPUT POWER RECEPTACLE ARE ELECTRICALLY INSULATED TO PREVENT UNINTENTIONAL CONTACT WITH 120/240 VAC VOLTAGE. FAILURE TO DO SO MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

Figure 17. Modified wiring connected to A-Phase voltage metering with A-Phase incoming supply

S1 H

S1 N

S2 H

S2 N

1

2

3

4

1 2 3 4 5 6 7 8 9 10 11 12

TB7

TB8

User-supplieddisconnect

switch

Page 30: Form 7 microprocessor-based pole-mount recloser control

24 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

DANGERHAZARDOUS VOLTAGE. DO NOT CONNECT POTENTIAL TRANSFORMER LOW-VOLTAGE SECONDARIES TO THE CONTROL THROUGH CABLES OR OTHER WIRING UNTIL THE UNIT IS INSTALLED IN THE FIELD. TRANSFORMER HIGH-VOLTAGE PRIMARY WINDINGS WILL BECOME LIVE WHEN 120/240 VAC IS APPLIED TO THE CONTROL FROM AN ALTERNATE SOURCE IF THE TRANSFORMER SECONDARY IS CONNECTED. FAILURE TO COMPLY MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

WARNINGHAZARDOUS VOLTAGE. BEFORE APPLYING POWER TO THE CONTROL, CONFIRM THAT MALE PINS OF THE INPUT POWER RECEPTACLE ARE ELECTRICALLY INSULATED TO PREVENT UNINTENTIONAL CONTACT WITH 120/240 VAC VOLTAGE. FAILURE TO DO SO MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

Figure 18. Three-phase transformer connection, wye configuration only (TB8 terminal block connection)

Figure 19. Customer connections to TB8, 120 Vac delta connection

NEU

User-supplieddisconnectswitches

TB8

1 2 3 4 5 6 7 8 9 10 11 12

User-supplieddisconnectswitches

1 2 3 4 5 6 7 8 9 10 11 12

TB8

Page 31: Form 7 microprocessor-based pole-mount recloser control

25INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

DANGERHAZARDOUS VOLTAGE. DO NOT CONNECT POTENTIAL TRANSFORMER LOW-VOLTAGE SECONDARIES TO THE CONTROL THROUGH CABLES OR OTHER WIRING UNTIL THE UNIT IS INSTALLED IN THE FIELD. TRANSFORMER HIGH-VOLTAGE PRIMARY WINDINGS WILL BECOME LIVE WHEN 120/240 VAC IS APPLIED TO THE CONTROL FROM AN ALTERNATE SOURCE IF THE TRANSFORMER SECONDARY IS CONNECTED. FAILURE TO COMPLY MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

WARNINGHAZARDOUS VOLTAGE. BEFORE APPLYING POWER TO THE CONTROL, CONFIRM THAT MALE PINS OF THE INPUT POWER RECEPTACLE ARE ELECTRICALLY INSULATED TO PREVENT UNINTENTIONAL CONTACT WITH 120/240 VAC VOLTAGE. FAILURE TO DO SO MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.

Figure 20. 240 V, 3-wire transformer connection: B phase input for power and sensing, *YØ for sync check voltage

Standard default supervisory input control and output status contacts

Make standard customer connections to TB1. Refer to Figure 22, Table 2, and Table 3. The Workbench NXG allows customization of all the control and status points. Refer to the Form 7 Programming Guide for additional information.

NOTICEEXTERNAL LEADS MUST BE SHIELDED AND THE SHIELD MUST BE GROUNDED AT BOTH ENDS. TERMINATE EACH LEAD WITH A 320 VAC, 150 JOULES METAL OXIDE VARISTOR (MOV), OR EQUIVALENT, AT THE REMOTE END. ATTACH MOV’S BETWEEN THE LEADS AND GROUND. FAILURE TO PROPERLY SHIELD AND PROTECT LEADS CAN RESULT IN EQUIPMENT DAMAGE AND/OR UNINTENTIONAL OPERATION.

IMPORTANT: Shielding and surge protection of supervisory cables—all supervisory operation and control monitor leads must be protected within shielded cables. Refer to Figure 23.

240

120

120

120

Load side

Source side

NEU

User-supplieddisconnect

switch

User-supplieddisconnectswitches

1 2 3 4 5 6 7 8 9 10 11 12

TB7

TB8

S1 H

S1 N

S2 H

S2 N

1

2

3

4

S1 L2

Page 32: Form 7 microprocessor-based pole-mount recloser control

26 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Table 2. Contact input ratings (native and auxiliary)

Rating Specification

Native contact input rating (voltage)

12–250 Vdc: 2 mA

12–240 Vac (250 Vac maximum): 2 mA

Auxiliary contact input rating (voltage)

12–250 Vdc: 2 mA

85–240 Vac (250 Vac maximum): 2 mA

Contact input maximum pickup time (native and auxiliary)

12 ms (for DC or AC inputs)

Contact input maximum release time (native and auxiliary)

17 ms (for DC), 40.34 ms (for AC)

Table 3. Contact output ratings (native and auxiliary)

Rating Specification

Maximum Switching Voltage 250 Vac, RMS or 125 Vdc

Maximum Switching Loading Refer to Figure 21

Maximum Pickup Time (native) 8 ms (not including control response time)

Maximum Pickup Time (auxiliary) ≤ 2 ms for solid-state (SS) output (not including control response time)

≤ 10 ms for electro-mechanical relay output (not including control response time)

Maximum Release Time (native) 15 ms (not including control response time)

Maximum Release Time (auxiliary) < 15 ms for solid-state (SS) and electro-mechanical relay output (not including control reponse time)

Make and Carry rating 30 A for 0.2 ms (with external interruption) at 125 Vdc, 250 Vdc, 120 Vac, and 240 Vac

Output Protection Shunting type using MOVs and capacitors. 1500 Vac, RMS isolation between coil and contacts

Hi-Pot Capability 2.850 kV DC for 1 second from one output to the next or from one pin to chassis, but not across two terminals of a single output (due to output protection).

Fusing Outputs are not internally fuse-protected. Customer-supplied fusing is recommended.

NOTICEEXTERNAL LEADS MUST BE SHIELDED AND THE SHIELD MUST BE GROUNDED AT BOTH ENDS. TERMINATE EACH LEAD WITH A 320 VAC, 150 JOULES METAL OXIDE VARISTOR (MOV), OR EQUIVALENT, AT THE REMOTE END. ATTACH MOV’S BETWEEN THE LEADS AND GROUND. FAILURE TO PROPERLY SHIELD AND PROTECT LEADS CAN RESULT IN EQUIPMENT DAMAGE AND/OR UNINTENTIONAL OPERATION.

Figure 21. Maximum output switching graph

Important: Shielding and surge protection of supervisory cables—all supervisory operation and control monitor leads must be protected within shielded cables. Refer to Figure 23.

Figure 22. Maximum output switching graph

NOTICEEXTERNAL LEADS MUST BE SHIELDED AND THE SHIELD MUST BE GROUNDED AT BOTH ENDS. TERMINATE EACH LEAD WITH A 320 VAC, 150 JOULES METAL OXIDE VARISTOR (MOV), OR EQUIVALENT, AT THE REMOTE END. ATTACH MOV’S BETWEEN THE LEADS AND GROUND. FAILURE TO PROPERLY SHIELD AND PROTECT LEADS CAN RESULT IN EQUIPMENT DAMAGE AND/OR UNINTENTIONAL OPERATION.

IMPORTANT: Shielding and surge protection of supervisory cables—all supervisory operation and control monitor leads must be protected within shielded cables. Refer to Figure 23.

10

5

2

1

0.5

0.2

0.110 20 50 100 200 500

Cu

rren

t (A

)

Voltage (V)

Maximum switching power

AC resistive load

DC resistive load

AC resistive load: DC resistive load:

Legend

TB1 TB1 reference1 3 5 7 9

2 4 6 8

CI1 CI2 CO1 CO2

CI1 CI2 CO1 CO2

Page 33: Form 7 microprocessor-based pole-mount recloser control

27INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 23. Shielding and surge protection for supervisory and remote cables

REMOTEBOX

Not all remoteconnections

shown

SHIELD

1

3

2

4

CI1

CI2

CI1

CI2

+

Whetting voltage terminalsCustomer wiring

Customer wiring

28 Vdc

6 7CO1 CO1

8 9CO2 CO2

Factory-supplied28 Vdc whetting

voltage

TB9power supply

TB1CPU

TB11 3 5 7 9

2 4 6 8

Page 34: Form 7 microprocessor-based pole-mount recloser control

28 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

RS-232 communication port pin assignments

Table 4 indicates the pin assignments for the RS-232 communication port (see Figure 24 for location and Figure 25 for pin identification). Refer to Communication protocols for additional information.

Table 4. RS-232 communication port pin assignments

Pin number Signal name

1 DCD Carrier detect

2 RXD Receive data

3 TXD Transmit data

4 DTR Data terminal ready (Not Connected)

5 GND Signal Ground

6 DSR Data Set Ready (Not Connected)

7 RTS Request to Send

8 CTS Clear to Send

9 N.C. Not Used

10 (Shroud) Chassis Ground

Figure 24. Form 7 recloser control RS-232 communication ports (standard configuration)

Figure 25. RS-232 communication port pin identification

Change removable insertsTo change the front panel inserts:

ote: N It is not necessary to disconnect any wires.

1. Pull gently from the top to change remove the insert.

ote: N The insert will slide out of the top of the programming panel indicator section (Figure 26).

2. Change the existing label or slide in a new label with the name of the programmed option.

IMPORTANTLAMINATE THE REMOVABLE INSERTS PRIOR TO INSTALLING. THIS WILL SEAL THE INK/TONER AND AVOID DAMAGE TO THE FRONT PANEL.

3. Gently push the insert into the top of the operating panel (Figure 26).

4. Make sure the insert matches the actual configuration of the Form 7 control.

Figure 26. Open front panel and then remove and replace Status LEDs labels from the top

Install the control cable

WARNINGHAZARDOUS VOLTAGE. RECLOSER AND CONTROL MUST BE SOLIDLY GROUNDED. FOLLOW ALL APPROVED PROCEDURES AND SAFETY PRACTICES WHEN GROUNDING THIS EQUIPMENT. IMPROPER GROUNDING CAN RESULT IN CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY.

WARNINGHAZARDOUS VOLTAGE. DO NOT TOUCH THE PINS INSIDE THE CONTROL CABLE CONNECTOR. PINS COULD BE ENERGIZED IF A TRIP OR CLOSE SIGNAL IS ISSUED. FAILURE TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH.

ote: N Control is interlocked such that during normal operation, voltage cannot appear unless correct 52a/b status is reported by the recloser.

The maximum control cable length between the Form 7 control and the frame-integrated junction box is 95 feet.

ote: N The control cable must be supported along its length to prevent repeated movement due to wind or other outside forces which can damage the cable.

Contact input/output designation label

Ethernet RJ45 IRIG-B

2 contact input and 2 contact output terminals

RS-232

RS-232 DTE

J1-RS-232

1 2 3 4 5

6 7 8 9

Page 35: Form 7 microprocessor-based pole-mount recloser control

29INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

IMPORTANTALL EXTERNAL INPUTS TO THE FORM 7 RECLOSER CONTROL MUST BE ROUTED WITHIN 8 INCHES OF THEIR CORRESPONDING GROUND. DURING A SURGE, A POTENTIAL OF APPROXIMATELY 1.5 KV PER FOOT CAN DEVELOP IN THE CONDUCTORS. DIFFERENCES BETWEEN CONDUCTOR AND GROUND PATH LENGTHS CAN ADD ADDITIONAL STRESS TO THE CONTROL COMPONENTS IN THE EVENT OF A POWER SURGE

To install the control cable:

1. Connect the control cable to the bottom of the Form 7 cabinet with the provided 37-Pin Breech-Lok™ Control Cable using the MIL-DTL-38999 receptacle.

2. Route the control cable between the control and recloser.

3. Connect the control cable to the bottom of the NOVA NX-T integrated junction box.

NX-T junction box

The NOVA NX-T pole-mount frame incorporates a junction box as part of the frame construction. The junction box is fully vented around the perimeter of its bottom panel, allowing moisture to easily drain out without pooling within the enclosure. Each NOVA NX-T recloser junction box cable and the single control cable utilizes Eaton’s MIL-DTL-38999 Series IV connector and is completely sealed against moisture. There are no terminal blocks, heaters, or exposed bare wires required within the junction box enclosure. The unique design of Eaton’s MIL-DTL-38999 Series IV connector interface will prevent moisture from entering the connector system.

Figure 27. NOVA NX-T reclosers are connected to the Form 7 control through the junction box

Lock the controlTo prevent unauthorized access, install a padlock on the handle of the Form 7 control cabinet. Refer to Figure 9 for the 3-POINT LATCH HANDLE location.

Before placing the control and the recloser into service

CAUTIONEQUIPMENT MISOPERATION. DO NOT CONNECT THIS CONTROL TO AN ENERGIZED RECLOSER UNTIL ALL CONTROL SETTINGS HAVE BEEN PROPERLY PROGRAMMED AND VERIFIED. REFER TO THE PROGRAMMING INFORMATION FOR THIS CONTROL. FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION, EQUIPMENT DAMAGE, AND PERSONAL INJURY.

Before placing the control and recloser into service, complete and verify the following:

1. Verify the front panel label inserts are correct (if applicable).

ote: N Refer to Change removable inserts in this manual.

2. Verify the control is properly mounted for the installation.

3. Verify AC disconnect switches are properly installed.

4. Verify the Recloser is properly installed. Make sure the installation is in accordance with all locally approved standards and standard practices.

5. Verify the control and reclosers are properly grounded, in accordance with guidelines in this manual and the appropriate recloser manual (see Service Information MN280087EN NOVA NX-T Recloser Installation and Operation Instructions).

6. Verify control cables are supported and connected.

7. Check that the control battery is connected and has been tested for proper operation.

ote: N The battery test is blocked for 30 seconds upon power-up of the control.

8. Verify AC power is connected to the control. (AC Power LED indicator is illuminated.)

ote: N The control Front Panel Inactivity Time Delay turns off the backlit LCD display and most LEDs if no front panel keypad is pressed within fifteen minutes.

9. Verify control programming has been completed and was verified by appropriate personnel.

ote: N Refer to the Form 7 Programming Guide for additional information.

10. Verify the control clock set to the correct time.

ote: N Refer to the Form 7 Programming Guide for additional information.

Page 36: Form 7 microprocessor-based pole-mount recloser control

30 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

11. Check customer connections for remote and supervisory operation were completed in accordance with proper shielding and surge protection (Figure 23).

NOTICEEXTERNAL LEADS MUST BE SHIELDED AND THE SHIELD MUST BE GROUNDED AT BOTH ENDS. TERMINATE EACH LEAD WITH A 320 VAC, 150 JOULES METAL OXIDE VARISTOR (MOV), OR EQUIVALENT, AT THE REMOTE END. ATTACH MOV’S BETWEEN THE LEADS AND GROUND. FAILURE TO PROPERLY SHIELD AND PROTECT LEADS CAN RESULT IN EQUIPMENT DAMAGE AND/OR UNINTENTIONAL OPERATION.

12. Verify the health and status of the control (see Testing on page 30).

Control batteryIMPORTANT: Disconnect the separable connector prior to removing battery. Do not reconnect the separable connector until after the battery is installed. Do not disconnect the “+” and “–” leads from the battery posts if the separable harness is connected; battery wiring harness “+” and “–” post terminals are energized and can short-circuit if they come in contact with the cabinet or each other, consequently damaging the internal power supply.

Battery removal

To remove the battery:

1. Disconnect the red and black connectors from the control‘s wire harness.

2. Disconnect the separable connector.

3. Disconnect Velcro strapping. Do not remove strap from mounting tray slots.

4. Carefully remove battery.

5. Replace according to battery installation procedure (see Install the battery on page 19).

Figure 28. 24-Volt DC 13 Ahr battery

Battery replacement and disposal

The 24 Vdc control battery has a life expectancy of four years. It is recommended that the battery be replaced after four years or if the battery fails a battery test—whichever occurs first.

An unlit BATTERY Status LED on the control front panel could indicate a weak or failed battery.

ote: N Battery life is decreased at higher temperatures.

Dispose expired batteries in an environmentally responsible manner. Consult local regulations for proper battery disposal.

Fuse specificationsThe following table contains fuse specifications. Only use fuses with the same specifications.

Description Fuse Specification Reference

Power supply: 150 Power Supply

FU-1/FU-2 5A 250 Vac, Time delay fuse, 50 A interrupting

Figure 14

Optional input power: Fuse holders provided on Back Panel Terminal Blocks

FU-3 through FU-6

System dependent (10 kA interrupting 120 Vac, or 750 A interrupting 250 Vac)

Figure 7

GFCI Convenience Outlet Fuse

Mounted on GFCI

System dependent (10 kA interrupting 120 Vac, or 750 A interrupting 250 Vac)

Figure 7

TESTING

CAUTIONEQUIPMENT MISOPERATION. DO NOT CONNECT THIS CONTROL TO AN ENERGIZED RECLOSER UNTIL ALL CONTROL SETTINGS HAVE BEEN PROPERLY PROGRAMMED AND VERIFIED. REFER TO THE PROGRAMMING INFORMATION FOR THIS CONTROL. FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION, EQUIPMENT DAMAGE, AND PERSONAL INJURY.

IMPORTANT: The Form 7 control can be taken out of service for testing and placed back into service without de-energizing its recloser and interrupting the system. However, during the time the control is out of service, the recloser is inoperative.

Testing an installed controlTo determine the initial operations that the Form 7 recloser control can be perform while connected to an operating recloser:

ote: N These are the only tests that should be performed on an installed, operating control.

1. Check the operational values for currents, voltages, and other metering information.

ote: N Scroll through the LCD display messages by pressing the and arrows on the keypad

Velcrostrap Battery

Page 37: Form 7 microprocessor-based pole-mount recloser control

31INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

2. Test the battery (see Installed battery test on page 32).

3. Verify the Control OK LED is illuminated on the control operator panel (Figure 29). This indicates that the control is ready to operate the device.

ote: N The control includes a Front Panel Inactivity Time Delay that turns off the backlit LCD display and most LEDs if no front panel keypad is pressed within fifteen minutes. Pressing any pushbutton to reactivate the display and active LEDs.

4. Verify that the AC Power LED and the Battery Power LED are lit on the operator panel. These indicate the presence of the necessary power supplies.

All other tests described in this Testing section require the Form 7 recloser control to be removed from service, connected to a bypassed recloser, or tested at a location where the proper testing equipment is available.

Figure 29. Control OK LED

Remove the control from service

IMPORTANT: Disconnect switches for AC sensing and power connections are necessary to isolate the Form 7 control for testing and servicing.

IMPORTANT: The control must be removed from service in the exact order specified in this section.

To remove the control from service:

1. Enable GND TRIP BLOCKED to allow for ground trip to be disabled when re-energized.

2. Disconnect and remove the battery (see Figure 13 for battery location).

3. Remove control AC sensing and power connections from the control using a separate disconnect switch.

DANGERHAZARDOUS VOLTAGE. OPEN CT SECONDARIES CAN GENERATE HIGH VOLTAGES. CONTACT WITH CT PINS OF THE DISCONNECTED CABLE CAN CAUSE ELECTRIC SHOCK AND MAY RESULT IN PERSONAL INJURY. OPEN RECLOSER CONTACTS AND OPEN DISCONNECT SWITCHES BEFORE DISCONNECTING CONTROL CABLE.

CAUTIONEQUIPMENT MISOPERATION. DISCONNECT ALL CONTROL POWER SOURCES PRIOR TO DISCONNECTING OR RECONNECTION THE CONTROL CABLE FROM THE CONTROL. FAILURE TO COMPLY CAN RESULT IN RECLOSER MISOPERATION AT THE TIME OF DISCONNECTION OR RECONNECTION OF THE CONTROL CABLE TO THE CONTROL.

4. Disconnect control cable from control.

ote: N Do not disconnect any of the recloser cables from the recloser(s) or integrated junction box unless all of the above steps have been completed. Refer to the appropriate recloser instructions:

ote: N Service Information MN280087EN NOVA NX-T contains Recloser Installation and Operation Instructions.

5. Remove any control input and status output wiring from TB1 (Figure 24).

6. Disconnect any communications ports and IRIG-B timing connections (Figure 24).

7. Disconnect the ground from the control.

8. Carefully transport the control to a suitable service facility.

Preliminary testing with no AC availableIf the Form 7 control is not in service and preliminary testing needs to be performed, the control can be powered through its connected battery.

To perform preliminary testing with no AC available:

1. Open the swing panel of the Form 7 pole-mount control cabinet and locate the MANUAL BATTERY RECONNECT button (Figure 30).

Figure 30. Location of MANUAL BATTERY RECONNECT button

2. Momentarily press the MANUAL BATTERY RECONNECT button. The control will power up.

3. Power down the Form 7 control by unplugging the battery (disconnect the black/red battery connector).

MANUALBATTERY

RECONNECT

12

P151

P15

1

Page 38: Form 7 microprocessor-based pole-mount recloser control

32 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

4. Perform a battery charging cycle. Refer to in the Battery test and charging procedures section of these instructions.

IMPORTANT: While the Form 7 control is powered in this manner, the control battery is being continuously discharged. When the battery voltage drops to 22 Vdc, the control will automatically power down.

If the battery is left in a discharged condition, the battery will sustain irreversible damage. Therefore, initiate a battery charging cycle always after performing this procedure to bring the battery back up to full charge.

Electrical testing of NOVA NX-T

WARNINGHAZARDOUS VOLTAGE. SOLIDLY GROUND ALL EQUIPMENT. FAILURE TO COMPLY CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND EQUIPMENT DAMAGE.

Figure 31 shows a test circuit for NOVA NX-T reclosers with the Form 7 control.

IMPORTANT: To ensure proper operation for the NOVA NX-T recloser, always verify that the three cables between the integrated junction box and the NX-T reclosers are connected when the control is in single-phase trip, three-phase lockout mode or three-phase trip, three-phase lockout (ganged) mode.

Use this circuit to simulate load current and for testing minimum trip operation and sequencing the mechanism with the Form 7 control for each phase.

Figure 31. Suggested test circuit for NOVA NX-T reclosers with Form 7 control

Control testing with a KMET testerA KMET Tester (KMET1 TESTER) and KMET NX-T adapter (KMET45812) can be used to simulate over current situations and monitor control timing. Review the KMET manual (MN280067EN) for more information.

Battery test and charging proceduresThere are different battery test and charging procedures for an installed battery versus an uninstalled battery (one that has been removed from the control).

Installed battery test

Follow the procedure below to perform a battery test in the Form 7 control. The values in the test procedures are based on testing at 77 ºF (25 ºC).

This procedure checks the condition of the Form 7 control battery using the Battery Test function on the BATTERY MENU (no external current/voltage meter is necessary for testing):

Alarm Conditionsote: N During a manual battery test a 5 Ω, 55-watt resistor is

placed across the battery terminals for approximately 5 seconds. The Form 7 control measures the battery voltage, if the voltage drops below 22.8 Vdc for one full second, the ALARM LED (battery alarm) is illuminated.

ote: N When the Form 7 control is disconnected from AC power and the control battery drops below 23.5 Vdc for 60 seconds, the ALARM LED will illuminate. If the battery voltage continues to decay and drops below 22 Vdc, the Form 7 control will shut down.

ote: N The battery test is blocked for 30 seconds upon power up of the control.

ote: N AC power can be either connected or disconnected for battery test.

ote: N If the battery voltage drops below 19 V, the battery must be charged by the external battery charger KA43ME7001.

600:5RecloserBCT ON 600:5 Tap

2

115 VACVariableAutotransformer (10 A)

Clamp-OnAmmeter

IntegratedJunction Box

Use 2/0 cable or larger

Form 7Control

Source

Load

1

2

35

46

Page 39: Form 7 microprocessor-based pole-mount recloser control

33INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

To test and initiate a charging cycle (if needed) on an installed battery:

1. Login to the control.

2. Using the LCD and numeric keypad, press FUNC and then enter “82”.

3. Using the up/down arrow keys, highlight TEST BATTERY and then press ENTER. The battery test results will display in the battery metering menu. If needed after the test, the Form 7 control automatically begins charging the battery.

ote: N Voltage should be between 25–31 Vdc with the higher voltage at colder temperatures.

Under normal conditions, with AC connected and a fully charged battery, the charging current should be less than 20 mA.

With AC connected and a discharged battery, the current range should be between 20 and less than 450 mA. Current of 450 mA or greater indicates a problem with the charging circuit on the pole-mount power supply.

With AC disconnected and the battery supplying the load, current will read –400 to –600 mA depending on connected accessories.

Uninstalled battery test

This entire process should be conducted in a clean environment, such as a repair shop, and requires an external current/voltage meter. Refer to Table 5 for specifications and follow this procedure to perform a bench test on a control battery in a service shop.

To uninstall the battery, and then test and charge it:

1. Remove the control from service (see Remove the control from service on page 31 procedure).

2. Uninstall the battery from the control and carefully transport it to a suitable service facility (see Battery removal on page 30).

3. Measure battery voltage.

4. Apply test load and measure battery voltage after 5 seconds of load to determine voltage drop. Refer to Table 5 for Bench Test Load Condition.

5. Remove test load.

If the battery fails the test or is at least four years old, it should be replaced. Refer to Table 5 for battery catalog part number.

Battery charging

If it is not possible to charge the battery with the control’s built-in charger, a KME5-60-1 (120 Vac) portable bench type battery charger kit is available, which includes the KA43ME7001 Battery Charger (Figure 32) and the KME5-325-1 Adapter Cable. Refer to S280-79-14 KA43ME7001 Portable Lead Acid Battery Charger Instructions for additional information.

IMPORTANT: Do not attempt to charge a lead acid battery below 2 Vdc with the KA43ME7001 charger (the charger will not operate).

If while charging the lead acid battery, the battery’s voltage remains below 19 Vdc for 2 days, replace the battery. Dispose of the expired battery in an environmentally responsible manner. Consult local regulations for proper battery disposal.

Table 5. Control battery specifications

Specification Value

Control type Form 7 (high capacity)

Battery catalog part # KME5-134-1

Voltage 24 Vdc (two 12 C batteries)

Type Lead-Acid battery

Amp/Hour 13

Bench test load condition for 5 seconds 5 Ω 55 watt

Acceptable voltage drop at end of test load 2 V or less

Items required:

KA43ME7001 charger

KME5-325-1 adapter

To charge the Form 7 Pole-mount Recloser Control high capacity battery:

1. Connect the two 12-Volt batteries to the KA43ME7001 charger using adapter KME5-325-1.

2. Apply power to the charger to start the charging.

3. Allow battery to complete charging cycle.

IMPORTANT: Never connect a single 12-Volt battery to the KA43ME7001 charger. Use adapter KME5-325-1 with the battery assembly when connecting the charger to the two 12-volt batteries.

ote: N A yellow LED indicator on the body of the charger illuminates when charging. A green LED indicator illuminates when the charge is complete.

The charger senses when the battery voltage reaches 2.27 volts per cell, then the charge rate reduces to maintain a trickle charge.

The yellow LED flickers to indicate the battery has reached a full charge. This process can take up to 24 hours.

Page 40: Form 7 microprocessor-based pole-mount recloser control

34 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 32. KA43ME7001 battery charger. Included in KME5-60-1 portable bench type battery charger kit.

Return the control to service

CAUTIONEQUIPMENT MISOPERATION. DO NOT CONNECT THIS CONTROL TO AN ENERGIZED RECLOSER UNTIL ALL CONTROL SETTINGS HAVE BEEN PROPERLY PROGRAMMED AND VERIFIED. REFER TO THE PROGRAMMING INFORMATION FOR THIS CONTROL. FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION, EQUIPMENT DAMAGE, AND PERSONAL INJURY.

After the required work is completed, disconnect the control from the test set and follow this procedure to return the control to service:

1. While still in the service shop, appropriate personnel must verify that all control settings are correct.

2. Reconnect the ground cable to the control.

IMPORTANT: Equipment misoperation. Disconnect all control power sources prior to disconnecting or reconnecting the control cable from the control. Failure to comply can result in recloser misoperation at the time of disconnection or reconnection of the control cable to the control.

IMPORTANT: Prior to reconnecting the control cable, verify the control was removed from service in the exact order specified in the Remove the control from service section of this manual.

3. Control cable properly connected and supported.

4. Plug in the control battery.

ote: N The Form 7 recloser control will not power up until AC power is applied.

5. Apply AC power to the control.

6. Disable GND TRIP BLOCKED.

7. Verify the control clock is set to the current time after AC power has been reapplied.

ote: N The control clock may require resetting if the operating power has been disconnected for more than thirty days. Refer to the Form 7 Programming Guide for information on setting the control clock.

OPERATION

Modes of operationThe control has three modes of operation:

Three-phase trip and three-phase lockout (ganged)

Single-phase trip and three-phase lockout

Single-phase trip and single-phase lockout

Configure the mode of operation through the ProView user interface software. With the exception of the trip, operation is similar for the Three-Phase Trip and Three-Phase Lockout (ganged) and the Single-Phase Trip and Three-Phase Lockout.

Three-Phase Lockout

If the control is in Three-Phase Trip and Three-Phase Lockout (ganged) mode or Single-Phase Trip and Three-Phase Lockout mode, all three phases are permanently selected and the A PHASE SELECT, B PHASE SELECT, and C PHASE SELECT LEDs light. When one phase is opened with the yellow operating handle, all three phases open and lockout. The OPEN and LOCKOUT indicator LEDs light (on the control panel). With the yellow operating handle of the appropriate phase in the CLOSE position, press the CLOSE pushbutton on the control operator panel. All three phases close and the CLOSED LED lights.

Single-Phase Lockout

When in Single-Phase Trip and Single-Phase Lockout mode, any combination of phases can be selected and the respective PHASE SELECT LED lights. Each selected phase must be closed individually. When the selected phase is opened with the yellow operating handle, only that phase opens and locks out. The LOCKOUT, OPEN, and CLOSED indicator LEDs blink (on the control panel). The default text message on the LCD displays the mode of the triple-single configuration and the status of each phase. With the yellow operating handle of the selected phase in the CLOSE position, press the CLOSE pushbutton on the control panel. The phase closes and the CLOSED LED lights.

Page 41: Form 7 microprocessor-based pole-mount recloser control

35INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

IMPORTANT: If the Front Panel Inactivity Time Delay is enabled (default), and more than fifteen minutes has elapsed since the last panel operation, all the LEDs except HOT LINE TAG (if active), Alarm, Control OK, AC power, Battery, and recloser status will turn off. Verify the phase or phases you want activated are selected prior to pressing the TRIP or CLOSE button.

Operation upon loss of AC powerThe control is equipped with a 13 Amp-Hour 24 Vdc lead acid battery for operation upon loss of AC power. The control maintains full operation from the battery for a period of time—24-hour maximum at 68 °F (20 °C). If AC power has not returned during this period, the control disconnects the battery from the circuit.

ote: N The control continuously monitors the battery voltage. To prevent battery damage, the control shuts down automatically upon detection of low battery voltage (below 22 Vdc) for 60 seconds.

Control programming settings and parameters—including event recorder—are stored in non-volatile memory and retained upon loss of control power. The time/date clock will continue to operate for approximately 30 days after loss of control power.

IMPORTANT: A control that has shut down due to low battery voltage before AC power is restored will have a blank LCD display (no text message shown) and none of the LEDs will be illuminated.

The control clock may require resetting if the operating power has been disconnected for more than thirty days. Refer to the Form 7 Programming Guide for information on setting the control clock.

Maintaining battery charge (loss of AC power)

IMPORTANT: To maintain sufficient charge to operate the control and prevent battery cell damage, the sealed lead-acid batteries should be charged after no more than three months of storage.

The batteries must be tested and charged for 24 hours following every three months of storage from the last test date. A separate portable charger accessory is available. Catalog Number KA43ME7001 is a 120-Volt battery charger used to provide an external source of charge for the control’s 24 Vdc battery (two 12 Vdc batteries).

IMPORTANT: Connect the control battery before AC power is connected to the control’s AC supply Input Terminal Block. The battery must be disconnected and removed prior to shipping. The battery must be disconnected prior to storing the control. See Figure 13.

ACCESSORIES

These accessories are available. Contact your Eaton representative for additional information.

Additional communication cardsAdditional communication cards are available and can be installed either at the factory or in the field via a service kit.

Below is a list of additional communication cards available:

RS-232

RS-485

Serial fiber optic (ST)

Ethernet fiber optic multi-mode (LC, MTRJ, SC, or ST)

Ethernet fiber optic single-mode (LC)

Ethernet copper (RJ45)

These communication cards can be installed in expansion bay 4, 5, 6 or 7. However, Ethernet fiber communication cards (single-mode or multi-mode) can only be installed in expansion bay 4 or expansion bay 5 only. There are no install bay limitations for the other available communication cards.

To install a communication card, the Form 7 control must be powered down. Remove the bay cover (secured with two screws) for the desired expansion bay (4, 5, 6 or 7) and insert the communication card into the bay using the internal guide rails. Afterward, power on the Form 7 control, and either enable the desired expansion bay through the HMI, or via ProView NXG. Refer to the Form 7 Cybersecurity and Communications Guide for further details on how to configure specific communication settings.

See Figure 33 for additional communication card options available.

Page 42: Form 7 microprocessor-based pole-mount recloser control

36 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 33. Additional Form 7 serial and Ethernet communication options

Auxiliary contact I/OAvailable as an accessory, an optional auxiliary contact I/O card can be installed in auxiliary bay 1, 2, or 3. These auxiliary bays are vertical full bay slots, designated from left to right, and are located to the right of the voltage sensing bay. Up to three auxiliary contact I/O cards can be installed in the Form 7 module (either at factory or via a field service kit).

Each auxiliary contact I/O card has four contact inputs, four contact outputs, and one solid-state output contact.

An overlay is displayed on the faceplate of each auxiliary contact I/O card for easier contact I/O identification. By default, each contact input and output is unassigned, and can be configured using ProView NXG software. When in an enabled bay, each auxiliary contact I/O status is shown via the Form 7’s human-machine interface (HMI), ProView NXG software, or via SCADA.

To install an auxiliary contact I/O card, the Form 7 must be powered down. Remove the bay cover (secured with two screws) for the desired auxiliary bay (1, 2, or 3) and insert the auxiliary contact I/O card into the bay using the internal guide rails. Afterward, power on the Form 7 control, and enable the desired auxiliary bay through the HMI, or via ProView NXG.

Refer to the Form 7 Programming Guide for further details bay enablement and how to configure native and auxiliary contact I/Os using ProView NXG Workbench. See Figure 38 for shielding and surge protection wiring for supervisory and remote cables for auxiliary contact I/O.

See Figure 34 for example of two auxiliary contact I/O cards (with terminal block removed from top card), and Figure 35 for auxiliary contact I/O faceplate labeling.

Figure 34. Two auxiliary contact I/O cards (top card shown with terminal block removed)

Figure 35. Auxiliary contact I/O faceplate labeling

Loop scheme accessoryThe Form 7 control includes a Loop Scheme (LS) feature for use in distribution feeder loop sectionalizing schemes in feeder applications to improve distribution system continuity through load-transfer and loop-sectionalizing schemes.

When the Form 7 control senses a loss of voltage, the control shall perform the programmed LS action to restore service to the affected feeder. The loss of voltage sensing can be accomplished via customer-supplied potential transformers or via recloser’s voltage sensors (internal and integral).

The control will perform its programmed LS functions after a programmable time delay when loss of voltage occurs. The control can be programmed for either sectionalizing or tie mode of operation.

The Form 7 control can change the protection scheme upon an LS action. Each protection profile (up to eight profiles) can be configured differently, and LS programming can be easily accomplished for sectionalizing or tie applications via

Ethernet MM100 Base-FX (LC)

Ethernet MM100 Base-FX (SC)

Ethernet MM100 Base-FX (ST)

Ethernet SM100 Base-LX10 (LC)

Ethernet Copper1000 Base-T (8P8C)

Ethernet MM100 Base-FX (MT-RJ)

Serial Fiber (ST)Serial RS-232 Serial RS-485

Page 43: Form 7 microprocessor-based pole-mount recloser control

37INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

the Form 7 front panel HMI or through the Loop Scheme settings dialog window within ProView NXG.

When ordered from the factory, the control shall have LS inserts and LS test switches installed at the factory, in addition to default Loop Scheme settings file applied to the control.

See Figure 36 for Form 7 control’s front panel with LS inserts installed.

Figure 36. Form 7 front panel with LS inserts

See Figure 39 through Figure 44 for reference Loop Scheme wiring diagrams.

Incoming power receptaclesThe Incoming Power Receptacle allows the user to plug the power cable into the control thereby eliminating the need for hardwiring. Various options are available based upon the input power voltage and phase sensing requirements. Table 6 includes the available input receptacles for the control.

Table 6. Input and heater receptacles

Description Catalog number

120 Vac or 240 Vac input receptacle, 2-pin KME7-5577-A

120 Vac input receptacle, 3-pin KME7-5577-B

240 Vac input receptacle, 3-pin KME7-5577-C

Figure 37. Form 7 recloser control input receptacle locations

Cable locking sleevesTo prevent detachment of the control cable from the control cabinet by unauthorized personnel, a cable-locking sleeve is available to enclose the cable plug. The plug is passed through the sleeve and the sleeve is then fastened from inside the control cabinet. There is no access to the cable receptacle without opening the locked cabinet door and detaching the sleeve.

Stainless steel cabinetA cabinet constructed from AISI 304 stainless steel is available as an accessory.

120 Vac GFI duplex outletThe GFI Duplex Outlet is provided in controls powered by 120 Vac. This convenience outlet is rated for 15 A and is accessible through the front door in the control cabinet. The 120 Vac GFI Duplex Outlet is used for many applications such as power for the MET Tester, auxiliary measurement equipment, and supplemental lighting. This accessory is standard for the Form 7 control when configured for 120 Vac input applications.

Internal voltage sensing and load side sensingInternal voltage sensors, located on the source side of the recloser, and load side voltage sensors (located on the load side of the recloser), indicate voltage magnitude within an accuracy 2% or better and a phase degree accuracy within 1.5 degrees (includes sensor, cable, and control).

Refer to Service Information MN280087EN NOVA NX-T Recloser Installation and Operation Instructions.

Page 44: Form 7 microprocessor-based pole-mount recloser control

38 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Radio mounting accessoryThe radio mounting accessory is powered from a voltage regulated power supply factory-calibrated with an output of 13.5 Vdc.

The output is 13.5 Vdc between TB9 pin 4 (+) and pin 5 (–) on the power supply. The output is rated for maximum continuous output of 17.25 W at 13.5 Vdc.

ote: N This output cannot be field-calibrated.

The radio will continue to operate during the loss of AC power if power is supplied from the battery. The power supply is designed to provide up to 75 Watts (peak). Refer to Table 7 for list of communications hardware accessories that can be ordered with the Form 7 control.

Contact your Eaton representative for any additional voltage requirements.

The control CPU board provides one standard 9-pin RS-232 port, one RJ45 port, two USB host ports, one USB device port, and a standard IRIG B port for user time syncing. See Figure 7.

Table 7. Communications hardware accessories

Description Catalog number

Radio shelf option

Radio shelf KME7-5576-A

Polyphaser accessory

700 MHz–2 GHz polyphaser and mounting hardware with N(f)-type external termination

KME7-5583-A

100 MHz–300 MHz polyphaser and mounting hardware with N(f)-type external termination

KME7-5583-B

300 MHz–700 MHz polyphaser and mounting hardware with N(f)-type external termination

KME7-5583-C

2.7 GHz–6 GHz polyphaser and mounting hardware with N(f)-type external termination

KME7-5583-D

Antenna coax a

Cable, N (male)—BNC (male), 24 in (0.6 m) length KME7-2375-A

Cable, N (male)—N (male), 24 in (0.6 m) length KME7-2375-B

Cable, N (male)—RP-SMA (male), 24 in (0.6 m) length KME7-2375-C

Cable, N (male)—SMA (male), 24 in (0.6 m) length KME7-2375-D

Cable, N (male)—RP-TNC (male), 24 in (0.6 m) length KME7-2375-E

Cable, N (male)—TNC (male), 24 in (0.6 m) length KME7-2375-F

Other communication hardware

Provisions for two-way automatic communication system (TWACS)

KME7-5565-A

aAccessory is packed with the control

Mechanical pushbutton with Hot Line Tag toggle switchThe Form 7 Control comes with an option for mechanical pushbuttons, Green and Red, and Hot Line Tag toggle switch. These items replace the standard membrane switch.

Door alarm accessoryThe door alarm accessory provides the feedback to the user when the door is closed, open, or if the switch is disconnected.

Replacement kitsReplacement kits for the Form 7 pole-mount control are available through the factory Service Department. Contact your Eaton representative for additional information and order procedures.

Form 7 triple single adapterA Triple Single adapter, specific for the Form 6 NX-T and Form 7 is needed to interface the Form 7 control with the KMET tester. This adapter can be purchased from Eaton. Contact your Eaton representative for additional information

SUPPORT

Factory-authorized service centersFactory-authorized service centers are located throughout the continental United States to provide maintenance, repair and testing services for Eaton Cooper Power Series controls and reclosers. Contact your Eaton representative for additional information.

Switchgear Support GroupFor additional product assistance, contact Eaton’s Cooper Power series Support Group at: (800) 497-5953 or [email protected].

Page 45: Form 7 microprocessor-based pole-mount recloser control

39INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 38. Shielding and surge protection for supervisory and remote cables for auxiliary contact I/O

NOTICEEXTERNAL LEADS MUST BE SHIELDED AND THE SHIELD MUST BE GROUNDED AT BOTH ENDS. TERMINATE EACH LEAD WITH A 320 VAC, 150 JOULES METAL OXIDE VARISTOR (MOV), OR EQUIVALENT, AT THE REMOTE END. ATTACH MOV’S BETWEEN THE LEADS AND GROUND. FAILURE TO PROPERLY SHIELD AND PROTECT LEADS CAN RESULT IN EQUIPMENT DAMAGE AND/OR UNINTENTIONAL OPERATION.

IMPORTANT: Shielding and surge protection of supervisory cables—all supervisory operation and control monitor leads must be protected within shielded cables.

REMOTEBOX

Not all remoteconnections

shown

SHIELD

9

1

SS1

CI1

10 SS1

2 CI1

+

Whetting voltage terminalsCustomer wiring

Customer wiring

28 Vdc

20CO4 COM

11 CO1 NO

13 CO1 NC

Factory-supplied28 Vdc whetting

voltage

TB9power supply

AUX TB I/O

CI1 wiring shown. CI2 through CI4 can be wired the same.

SS1 wiring shown. Normally Open output contact.

CO1 (Form C) wiring shown. CO2 and CO3 can be wired the same. Shown in de-energized state.

Aux TB reference drawing

21 CO4 NC

12 CO1 COM

CI1

CI2

CI3

CI4

SS1

CO1 NC

CO1 NO

CO2 COM

CO3 NC

CO3 NO

CO4 NC

CI1

CI2

CI3

CI4

SS1

CO1 COM

CO2 NC

CO2 NO

CO3 COM

CO4 COM

Page 46: Form 7 microprocessor-based pole-mount recloser control

40 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 39. Generic Form 7 wiring diagram with six sensors

CU

STO

ME

R'S

SO

UR

CE

2V

OLT

AG

E IN

PU

T12

0VA

C 2

WIR

E

120V

AC

2 W

IRE

SO

UR

CE

1V

OLT

AG

E IN

PU

T

CU

STO

ME

R'S

120

VA

C

NE

UTR

AL

CO

NT

RO

L C

AB

INE

T

"FO

RM

7"

MO

DU

LE

KM

E7

SH

IELD

CT

CO

MC

T C

Ø

D E F G H J K L M NCBA

H

"R1"

KN

XT-

XX

-XX

-XX

XN

OV

A N

XT

TYP

ER

EC

LOS

ER

S (3

)

CO

NTR

OL

CA

BLE

KA

155M

E-X

XX

X F

T LG

KN

XT

CA

BLE

INTE

RC

ON

NE

CTI

ON

JUN

CTI

ON

BO

X

P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T B

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T A

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

F L J P M V b Y a X Z W A B C Dc d e R S T h k m n p q r f E

CLO

SE

+ C

CLO

SE

- C

CLO

SE

+ B

CLO

SE

- B

CLO

SE

+ A

CLO

SE

- A

VTC

CO

M (+

12V

)

52b

C

52a

C

52b

B

52a

B

52b

A

52a

A

CT

A

CT

B

CT

C

CT

CO

M

69 A

69 B

69 C

IVS

-V1

IVS

-V3

IVS

-V5

IVS

-V2

IVS

-V4

IVS

-V6

SH

IELD

SH

IELD

IVS

PO

WE

R S

UP

PLY

BO

AR

D15

0

H F L J P M V b Y a X Z A B C Dc d e R S T h k m n p q r f EW

P25

1

P25

2

VO

LTA

GE

SE

NS

ING

BO

AR

D25

0

P10

9P

104

52

68

37

41

12

34

56

78

9

CI1

CI2

CO

1C

O2

TB1

I/O

RS

-232

DTE

P10

5P

108

(RJ4

5/R

J45)

P10

1

US

B

P10

6P

107

CP

U B

OA

RD

, 100

FRO

NT

PA

NE

L H

MI

TRIP

CLO

SE

HLT

IRIG

-B

P10

21

23

4

US

BU

SB

P10

3

10 9 8 2

RIF

BO

AR

D20

0

98 2010 1819

UU

K

G K

NN

G

CLO

SE

+ C

SE

L

CLO

SE

+ B

SE

L

CLO

SE

+ A

SE

L

69 S

EL

4 1 15113 5212 1314 16

6 5 4

3 2 1 3 2 14

6 58 7

5 4 3 7 61

P20

2

P20

1

85°

TO 7

0° F

THE

RM

OS

TAT

100W

HE

ATE

R

P15

3

TB9

28VD

C W

HET

TIN

G +

VOLT

AGE

-

13.5

VD

C A

UX

+P

OW

ER

-

1 2

P15

5C

AP

AC

ITO

R

P15

2

AU

X B

AY

1

AU

X B

AY

2

+

24V

-13A

H- +-

2 3 411 2 3 4 5

1 2 3 4

7 8 9 10 126

115

P15

4

BLK RE

D

BA

TTE

RY

TES

T LO

AD

BA

TTE

RY

AS

Y

AC INPUT POWER

2 3 41 5 6 7 8 9

AU

X B

AY

3

gg

IVS

-N (1

,3,5

)

IVS

-N (2

,4,6

)

8 2

3 7 61

P20

3

1 2

3 4

P15

1

FAU

LT IN

DIC

ATO

RR

EC

EP

TAC

LE W

/GR

OU

ND

PO

LAR

IZE

D

WH

T

BLK

TR

RE

CLO

SE

R

RE

CLO

SE

R

RE

CLO

SE

R

EX

P B

AY

5E

XP

BA

Y 4

EX

P B

AY

6E

XP

BA

Y 7

FRO

NT

PA

NE

L P

OR

TS

ETH

ER

NE

T

P15

6

1 2

4 5 63 1 2

3 4

P20

4

S2 N

S2 H

S1 N

S1 H

"TB

7"

AUX

H

AUX

N

120

VA

C

NE

UTR

AL

NE

UTR

AL

120

VA

C

NE

UTR

AL

120

VA

C

SU

PP

LIE

D

(-)

CU

STO

ME

R

RA

DIO

(+)

PW

RA

NT

RE

CO

MM

EN

DE

D C

OM

M D

EV

ICE

WIR

ING

Page 47: Form 7 microprocessor-based pole-mount recloser control

41INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 40. Generic Form 7 wiring diagram with three sensors / three PTs

CU

STO

ME

R'S

SO

UR

CE

2V

OLT

AG

E IN

PU

T12

0VA

C 2

WIR

E

120V

AC

2 W

IRE

SO

UR

CE

1V

OLT

AG

E IN

PU

T

CU

STO

ME

R'S

120

VA

C

NE

UTR

AL

CO

NT

RO

L C

AB

INE

T

"FO

RM

7"

MO

DU

LE

KM

E7

SH

IELD

CT

CO

MC

T C

Ø

D E F G H J K L M NCBA

H

"R1"

KN

XT-

XX

-XX

-XX

XN

OV

A N

XT

TYP

ER

EC

LOS

ER

S (3

)

CO

NTR

OL

CA

BLE

KA

155M

E-X

XX

X F

T LG

KN

XT

CA

BLE

INTE

RC

ON

NE

CTI

ON

JUN

CTI

ON

BO

X

P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T B

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T A

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

F L J P M V b Y a X Z W A B C Dc d e R S T h k m n p q r f E

CLO

SE

+ C

CLO

SE

- C

CLO

SE

+ B

CLO

SE

- B

CLO

SE

+ A

CLO

SE

- A

VTC

CO

M (+

12V

)

52b

C

52a

C

52b

B

52a

B

52b

A

52a

A

CT

A

CT

B

CT

C

CT

CO

M

69 A

69 B

69 C

SH

IELD

SH

IELD

IVS

PO

WE

R S

UP

PLY

BO

AR

D15

0

H F L J P M V b Y a X Z A B C Dc d e R S T h k m n p q r f EW

P25

1

P25

2

VO

LTA

GE

SE

NS

ING

BO

AR

D25

0

P10

9P

104

52

68

37

41

12

34

56

78

9

CI1

CI2

CO

1C

O2

TB1

I/O

RS

-232

DTE

P10

5P

108

(RJ4

5/R

J45)

P10

1

US

B

P10

6P

107

CP

U B

OA

RD

, 100

FRO

NT

PA

NE

L H

MI

TRIP

CLO

SE

HLT

IRIG

-B

P10

21

23

4

US

BU

SB

P10

3

10 9 8 2

RIF

BO

AR

D20

0

98 2010 1819

UU

K

G K

NN

G

CLO

SE

+ C

SE

L

CLO

SE

+ B

SE

L

CLO

SE

+ A

SE

L

69 S

EL

4 1 15113 5212 1314 16

6 5 4

3 2 1 3 2 14

6 58 7

5 4 3 7 61

P20

2

P20

1

85°

TO 7

0° F

THE

RM

OS

TAT

100W

HE

ATE

R

P15

3

TB9

28VD

C W

HET

TIN

G +

VOLT

AGE

-

13.5

VD

C A

UX

+P

OW

ER

-

1 2

P15

5C

AP

AC

ITO

R

P15

2

AU

X B

AY

1

AU

X B

AY

2

+

24V

-13A

H- +-

2 3 411 2 3 4 5

1 2 3 4

7 8 9 10 126

115

P15

4

BLK RE

D

BA

TTE

RY

TES

T LO

AD

BA

TTE

RY

AS

Y

AC INPUT POWER

2 3 41 5 6 7 8 9

AU

X B

AY

3

gg

8 2

3 7 61

P20

3

1 2

3 4

P15

1

FAU

LT IN

DIC

ATO

RR

EC

EP

TAC

LE W

/GR

OU

ND

PO

LAR

IZE

D

WH

T

BLK

TR

RE

CLO

SE

R

RE

CLO

SE

R

RE

CLO

SE

R

EX

P B

AY

5E

XP

BA

Y 4

EX

P B

AY

6E

XP

BA

Y 7

FRO

NT

PA

NE

L P

OR

TS

ETH

ER

NE

T

P15

6

1 2

4 5 63 1 2

3 4

P20

4

NEU

J354

32

16

78

54

32

16

J2

PT

Inpu

tsW

ye C

onne

ctio

ns

PT

to L

EA

Atte

nuat

orC

ircui

t Boa

rd

1 2 3 4 5 6 7 8 9 10 11 12

J1

V1+

IVS

-V1

IVS

-V3

IVS

-V5

IVS

-N (1

,3,5

)

S2 N

S2 H

S1 N

S1 H

"TB

7"

AUX

H

AUX

N

120

VA

C

NE

UTR

AL

NE

UTR

AL

120

VA

C

NE

UTR

AL

120

VA

C

SU

PP

LIE

D

(-)

CU

STO

ME

R

RA

DIO

(+)

PW

RA

NT

RE

CO

MM

EN

DE

D C

OM

M D

EV

ICE

WIR

ING

V1-

V3+

V3-

V5+

V5-

V2+

V2-

V4+

V4-

V6+

V6-"TB

8"TB

8 C

ON

NE

CTI

ON

SS

HO

WN

IN B

US

HIN

G 3

/4P

OS

ITIO

N, W

YE

CO

NFI

GU

RA

TIO

N

Page 48: Form 7 microprocessor-based pole-mount recloser control

42 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 41. Generic Form 7 wiring diagram with six PTs

CU

STO

ME

R'S

SO

UR

CE

2V

OLT

AG

E IN

PU

T12

0VA

C 2

WIR

E

120V

AC

2 W

IRE

SO

UR

CE

1V

OLT

AG

E IN

PU

T

CU

STO

ME

R'S

120

VA

C

NE

UTR

AL

CO

NT

RO

L C

AB

INE

T

"FO

RM

7"

MO

DU

LE

KM

E7

SH

IELD

CT

CO

MC

T C

Ø

D E F G H J K L M NCBA

H

"R1"

KN

XT-

XX

-XX

-XX

XN

OV

A N

XT

TYP

ER

EC

LOS

ER

S (3

)

CO

NTR

OL

CA

BLE

KA

155M

E-X

XX

X F

T LG

KN

XT

CA

BLE

INTE

RC

ON

NE

CTI

ON

JUN

CTI

ON

BO

X

P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T B

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T A

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

F L J P M V b Y a X Z W A B C Dc d e R S T h k m n p q r f E

CLO

SE

+ C

CLO

SE

- C

CLO

SE

+ B

CLO

SE

- B

CLO

SE

+ A

CLO

SE

- A

VTC

CO

M (+

12V

)

52b

C

52a

C

52b

B

52a

B

52b

A

52a

A

CT

A

CT

B

CT

C

CT

CO

M

69 A

69 B

69 C

SH

IELD

SH

IELD

IVS

PO

WE

R S

UP

PLY

BO

AR

D15

0

H F L J P M V b Y a X Z A B C Dc d e R S T h k m n p q r f EW

P25

1

P25

2

VO

LTA

GE

SE

NS

ING

BO

AR

D25

0

P10

9P

104

52

68

37

41

12

34

56

78

9

CI1

CI2

CO

1C

O2

TB1

I/O

RS

-232

DTE

P10

5P

108

(RJ4

5/R

J45)

P10

1

US

B

P10

6P

107

CP

U B

OA

RD

, 100

FRO

NT

PA

NE

L H

MI

TRIP

CLO

SE

HLT

IRIG

-B

P10

21

23

4

US

BU

SB

P10

3

10 9 8 2

RIF

BO

AR

D20

0

98 2010 1819

UU

K

G K

NN

G

CLO

SE

+ C

SE

L

CLO

SE

+ B

SE

L

CLO

SE

+ A

SE

L

69 S

EL

4 1 15113 5212 1314 16

6 5 4

3 2 1 3 2 14

6 58 7

5 4 3 7 61

P20

2

P20

1

85°

TO 7

0° F

THE

RM

OS

TAT

100W

HE

ATE

R

P15

3

TB9

28VD

C W

HET

TIN

G +

VOLT

AGE

-

13.5

VD

C A

UX

+P

OW

ER

-

1 2

P15

5C

AP

AC

ITO

R

P15

2

AU

X B

AY

1

AU

X B

AY

2

+

24V

-13A

H- +-

2 3 411 2 3 4 5

1 2 3 4

7 8 9 10 126

115

P15

4

BLK RE

D

BA

TTE

RY

TES

T LO

AD

BA

TTE

RY

AS

Y

AC INPUT POWER

2 3 41 5 6 7 8 9

AU

X B

AY

3

gg

8 2

3 7 61

P20

3

1 2

3 4

P15

1

FAU

LT IN

DIC

ATO

RR

EC

EP

TAC

LE W

/GR

OU

ND

PO

LAR

IZE

D

WH

T

BLK

TR

RE

CLO

SE

R

RE

CLO

SE

R

RE

CLO

SE

R

EX

P B

AY

5E

XP

BA

Y 4

EX

P B

AY

6E

XP

BA

Y 7

FRO

NT

PA

NE

L P

OR

TS

ETH

ER

NE

T

P15

6

1 2

4 5 63 1 2

3 4

P20

4

NEU

J354

32

16

78

54

32

16

J2

1 2 3 4 5 6 7 8 9 10 11 12

J1

V1+

V1-

V3+

V3-

V5+

V5-

V2+

V2-

V4+

V4-

V6+

V6-

PT

to L

EA

Atte

nuat

orC

ircui

t Boa

rd

NEU

PT

Inpu

tsW

ye C

onne

ctio

ns

S2 N

S2 H

S1 N

S1 H

"TB

7"

AUX

H

AUX

N

120

VA

C

NE

UTR

AL

NE

UTR

AL

120

VA

C

NE

UTR

AL

120

VA

C

SU

PP

LIE

D

(-)

CU

STO

ME

R

RA

DIO

(+)

PW

RA

NT

RE

CO

MM

EN

DE

D C

OM

M D

EV

ICE

WIR

ING

"TB

8"TB

8 C

ON

NE

CTI

ON

SS

HO

WN

IN B

US

HIN

G 3

/4P

OS

ITIO

N, W

YE

CO

NFI

GU

RA

TIO

N

Page 49: Form 7 microprocessor-based pole-mount recloser control

43INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 42. Generic Form 7 wiring diagram with six sensors and LS test switches

CU

STO

ME

R'S

SO

UR

CE

2V

OLT

AG

E IN

PU

T12

0VA

C 2

WIR

E

120V

AC

2 W

IRE

SO

UR

CE

1V

OLT

AG

E IN

PU

T

CU

STO

ME

R'S

120

VA

C

NE

UTR

AL

CO

NT

RO

L C

AB

INE

T

"FO

RM

7"

MO

DU

LE

KM

E7

SH

IELD

CT

CO

MC

T C

Ø

D E F G H J K L M NCBA

H

"R1"

KN

XT-

XX

-XX

-XX

XN

OV

A N

XT

TYP

ER

EC

LOS

ER

S (3

)

CO

NTR

OL

CA

BLE

KA

155M

E-X

XX

X F

T LG

KN

XT

CA

BLE

INTE

RC

ON

NE

CTI

ON

JUN

CTI

ON

BO

X

P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T B

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T A

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

F L J P M V b Y a X Z W A B C Dc d e R S T h k m n p q r f E

CLO

SE

+ C

CLO

SE

- C

CLO

SE

+ B

CLO

SE

- B

CLO

SE

+ A

CLO

SE

- A

VTC

CO

M (+

12V

)

52b

C

52a

C

52b

B

52a

B

52b

A

52a

A

CT

A

CT

B

CT

C

CT

CO

M

69 A

69 B

69 C

IVS

-V1

IVS

-V3

IVS

-V5

IVS

-V2

IVS

-V4

IVS

-V6

SH

IELD

SH

IELD

IVS

PO

WE

R S

UP

PLY

BO

AR

D15

0

H F L J P M V b Y a X Z A B C Dc d e R S T h k m n p q r f EW

P25

1

P25

2

VO

LTA

GE

SE

NS

ING

BO

AR

D25

0

P10

9P

104

52

68

37

41

12

34

56

78

9

CI1

CI2

CO

1C

O2

TB1

I/O

RS

-232

DTE

P10

5P

108

(RJ4

5/R

J45)

P10

1

US

B

P10

6P

107

CP

U B

OA

RD

, 100

FRO

NT

PA

NE

L H

MI

TRIP

CLO

SE

HLT

IRIG

-B

P10

21

23

4

US

BU

SB

P10

3

10 9 8 2

RIF

BO

AR

D20

0

98 2010 1819

UU

K

G K

NN

G

CLO

SE

+ C

SE

L

CLO

SE

+ B

SE

L

CLO

SE

+ A

SE

L

69 S

EL

4 1 15113 5212 1314 16

6 5 4

3 2 1 3 2 14

6 58 7

5 4 3 7 61

P20

2

P20

1

85°

TO 7

0° F

THE

RM

OS

TAT

100W

HE

ATE

R

P15

3

TB9

28VD

C W

HET

TIN

G +

VOLT

AGE

-

13.5

VD

C A

UX

+P

OW

ER

-

1 2

P15

5C

AP

AC

ITO

R

P15

2

AU

X B

AY

1

AU

X B

AY

2

+

24V

-13A

H- +-

2 3 411 2 3 4 5

1 2 3 4

7 8 9 10 126

115

P15

4

BLK RE

D

BA

TTE

RY

TES

T LO

AD

BA

TTE

RY

AS

Y

AC INPUT POWER

2 3 41 5 6 7 8 9

AU

X B

AY

3

gg

IVS

-N (1

,3,5

)

IVS

-N (2

,4,6

)

8 2

3 7 61

P20

3

1 2

3 4

P15

1

FAU

LT IN

DIC

ATO

RR

EC

EP

TAC

LE W

/GR

OU

ND

PO

LAR

IZE

D

WH

T

BLK

TR

RE

CLO

SE

R

RE

CLO

SE

R

RE

CLO

SE

R

EX

P B

AY

5E

XP

BA

Y 4

EX

P B

AY

6E

XP

BA

Y 7

FRO

NT

PA

NE

L P

OR

TS

ETH

ER

NE

T

P15

6

1 2

4 5 63 1 2

3 4

P20

4

S2 N

S2 H

S1 N

S1 H

"TB

7"

AUX

H

AUX

N

120

VA

C

NE

UTR

AL

NE

UTR

AL

120

VA

C

NE

UTR

AL

120

VA

C

SU

PP

LIE

D

(-)

CU

STO

ME

R

RA

DIO

(+)

PW

RA

NT

RE

CO

MM

EN

DE

D C

OM

M D

EV

ICE

WIR

ING

LS T

ES

TS

WIT

CH

ES

Page 50: Form 7 microprocessor-based pole-mount recloser control

44 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 43. Generic Form 7 wiring diagram with three sensors / three PTs and LS test switches

CU

STO

ME

R'S

SO

UR

CE

2V

OLT

AG

E IN

PU

T12

0VA

C 2

WIR

E

120V

AC

2 W

IRE

SO

UR

CE

1V

OLT

AG

E IN

PU

T

CU

STO

ME

R'S

120

VA

C

NE

UTR

AL

CO

NT

RO

L C

AB

INE

T

"FO

RM

7"

MO

DU

LE

KM

E7

SH

IELD

CT

CO

MC

T C

Ø

D E F G H J K L M NCBA

H

"R1"

KN

XT-

XX

-XX

-XX

XN

OV

A N

XT

TYP

ER

EC

LOS

ER

S (3

)

CO

NTR

OL

CA

BLE

KA

155M

E-X

XX

X F

T LG

KN

XT

CA

BLE

INTE

RC

ON

NE

CTI

ON

JUN

CTI

ON

BO

X

P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T B

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T A

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

F L J P M V b Y a X Z W A B C Dc d e R S T h k m n p q r f E

CLO

SE

+ C

CLO

SE

- C

CLO

SE

+ B

CLO

SE

- B

CLO

SE

+ A

CLO

SE

- A

VTC

CO

M (+

12V

)

52b

C

52a

C

52b

B

52a

B

52b

A

52a

A

CT

A

CT

B

CT

C

CT

CO

M

69 A

69 B

69 C

SH

IELD

SH

IELD

IVS

PO

WE

R S

UP

PLY

BO

AR

D15

0

H F L J P M V b Y a X Z A B C Dc d e R S T h k m n p q r f EW

P25

1

P25

2

VO

LTA

GE

SE

NS

ING

BO

AR

D25

0

P10

9P

104

52

68

37

41

12

34

56

78

9

CI1

CI2

CO

1C

O2

TB1

I/O

RS

-232

DTE

P10

5P

108

(RJ4

5/R

J45)

P10

1

US

B

P10

6P

107

CP

U B

OA

RD

, 100

FRO

NT

PA

NE

L H

MI

TRIP

CLO

SE

HLT

IRIG

-B

P10

21

23

4

US

BU

SB

P10

3

10 9 8 2

RIF

BO

AR

D20

0

98 2010 1819

UU

K

G K

NN

G

CLO

SE

+ C

SE

L

CLO

SE

+ B

SE

L

CLO

SE

+ A

SE

L

69 S

EL

4 1 15113 5212 1314 16

6 5 4

3 2 1 3 2 14

6 58 7

5 4 3 7 61

P20

2

P20

1

85°

TO 7

0° F

THE

RM

OS

TAT

100W

HE

ATE

R

P15

3

TB9

28VD

C W

HET

TIN

G +

VOLT

AGE

-

13.5

VD

C A

UX

+P

OW

ER

-

1 2

P15

5C

AP

AC

ITO

R

P15

2

AU

X B

AY

1

AU

X B

AY

2

+

24V

-13A

H- +-

2 3 411 2 3 4 5

1 2 3 4

7 8 9 10 126

115

P15

4

BLK RE

D

BA

TTE

RY

TES

T LO

AD

BA

TTE

RY

AS

Y

AC INPUT POWER

2 3 41 5 6 7 8 9

AU

X B

AY

3

gg

8 2

3 7 61

P20

3

1 2

3 4

P15

1

FAU

LT IN

DIC

ATO

RR

EC

EP

TAC

LE W

/GR

OU

ND

PO

LAR

IZE

D

WH

T

BLK

TR

RE

CLO

SE

R

RE

CLO

SE

R

RE

CLO

SE

R

EX

P B

AY

5E

XP

BA

Y 4

EX

P B

AY

6E

XP

BA

Y 7

FRO

NT

PA

NE

L P

OR

TS

ETH

ER

NE

T

P15

6

1 2

4 5 63 1 2

3 4

P20

4

NEU

J354

32

16

78

54

32

16

J2

PT

Inpu

tsW

ye C

onne

ctio

ns

PT

to L

EA

Atte

nuat

orC

ircui

t Boa

rd

1 2 3 4 5 6 7 8 9 10 11 12

J1

V1+

IVS

-V1

IVS

-V3

IVS

-V5

IVS

-N (1

,3,5

)

S2 N

S2 H

S1 N

S1 H

"TB

7"

AUX

H

AUX

N

120

VA

C

NE

UTR

AL

NE

UTR

AL

120

VA

C

NE

UTR

AL

120

VA

C

SU

PP

LIE

D

(-)

CU

STO

ME

R

RA

DIO

(+)

PW

RA

NT

RE

CO

MM

EN

DE

D C

OM

M D

EV

ICE

WIR

ING

V1-

V3+

V3-

V5+

V5-

V2+

V2-

V4+

V4-

V6+

V6-

LS T

ES

TS

WIT

CH

ES

"TB

8"TB

8 C

ON

NE

CTI

ON

SS

HO

WN

IN B

US

HIN

G 3

/4P

OS

ITIO

N, W

YE

CO

NFI

GU

RA

TIO

N

Page 51: Form 7 microprocessor-based pole-mount recloser control

45INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 44. Generic Form 7 wiring diagram with six PTs and LS test switches

CU

STO

ME

R'S

SO

UR

CE

2V

OLT

AG

E IN

PU

T12

0VA

C 2

WIR

E

120V

AC

2 W

IRE

SO

UR

CE

1V

OLT

AG

E IN

PU

T

CU

STO

ME

R'S

120

VA

C

NE

UTR

AL

CO

NT

RO

L C

AB

INE

T

"FO

RM

7"

MO

DU

LE

KM

E7

SH

IELD

CT

CO

MC

T C

Ø

D E F G H J K L M NCBA

H

"R1"

KN

XT-

XX

-XX

-XX

XN

OV

A N

XT

TYP

ER

EC

LOS

ER

S (3

)

CO

NTR

OL

CA

BLE

KA

155M

E-X

XX

X F

T LG

KN

XT

CA

BLE

INTE

RC

ON

NE

CTI

ON

JUN

CTI

ON

BO

X

P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T B

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

SH

IELD

CT

CO

MC

T A

Ø

D E F G H J K L M NCBA P R S T U

D E F G H J K L M NCBA P R S T U

CLO

SE

+C

LOS

E +

SE

LC

LOS

E -

AU

X 5

2aA

UX

52b

AU

X S

W C

OM

VTC

CO

M52

a52

b69

SH

IELD

IVS

IVS

SO

UR

CE

IVS

LO

AD

IVS

NE

U

69 S

EL

F L J P M V b Y a X Z W A B C Dc d e R S T h k m n p q r f E

CLO

SE

+ C

CLO

SE

- C

CLO

SE

+ B

CLO

SE

- B

CLO

SE

+ A

CLO

SE

- A

VTC

CO

M (+

12V

)

52b

C

52a

C

52b

B

52a

B

52b

A

52a

A

CT

A

CT

B

CT

C

CT

CO

M

69 A

69 B

69 C

SH

IELD

SH

IELD

IVS

PO

WE

R S

UP

PLY

BO

AR

D15

0

H F L J P M V b Y a X Z A B C Dc d e R S T h k m n p q r f EW

P25

1

P25

2

VO

LTA

GE

SE

NS

ING

BO

AR

D25

0

P10

9P

104

52

68

37

41

12

34

56

78

9

CI1

CI2

CO

1C

O2

TB1

I/O

RS

-232

DTE

P10

5P

108

(RJ4

5/R

J45)

P10

1

US

B

P10

6P

107

CP

U B

OA

RD

, 100

FRO

NT

PA

NE

L H

MI

TRIP

CLO

SE

HLT

IRIG

-B

P10

21

23

4

US

BU

SB

P10

3

10 9 8 2

RIF

BO

AR

D20

0

98 2010 1819

UU

K

G K

NN

G

CLO

SE

+ C

SE

L

CLO

SE

+ B

SE

L

CLO

SE

+ A

SE

L

69 S

EL

4 1 15113 5212 1314 16

6 5 4

3 2 1 3 2 14

6 58 7

5 4 3 7 61

P20

2

P20

1

85°

TO 7

0° F

THE

RM

OS

TAT

100W

HE

ATE

R

P15

3

TB9

28VD

C W

HET

TIN

G +

VOLT

AGE

-

13.5

VD

C A

UX

+P

OW

ER

-

1 2

P15

5C

AP

AC

ITO

R

P15

2

AU

X B

AY

1

AU

X B

AY

2

+

24V

-13A

H- +-

2 3 411 2 3 4 5

1 2 3 4

7 8 9 10 126

115

P15

4

BLK RE

D

BA

TTE

RY

TES

T LO

AD

BA

TTE

RY

AS

Y

AC INPUT POWER

2 3 41 5 6 7 8 9

AU

X B

AY

3

gg

8 2

3 7 61

P20

3

1 2

3 4

P15

1

FAU

LT IN

DIC

ATO

RR

EC

EP

TAC

LE W

/GR

OU

ND

PO

LAR

IZE

D

WH

T

BLK

TR

RE

CLO

SE

R

RE

CLO

SE

R

RE

CLO

SE

R

EX

P B

AY

5E

XP

BA

Y 4

EX

P B

AY

6E

XP

BA

Y 7

FRO

NT

PA

NE

L P

OR

TS

ETH

ER

NE

T

P15

6

1 2

4 5 63 1 2

3 4

P20

4

NEU

J354

32

16

78

54

32

16

J2

1 2 3 4 5 6 7 8 9 10 11 12

J1

V1+

V1-

V3+

V3-

V5+

V5-

V2+

V2-

V4+

V4-

V6+

V6-

PT

to L

EA

Atte

nuat

orC

ircui

t Boa

rd

NEU

PT

Inpu

tsW

ye C

onne

ctio

ns

S2 N

S2 H

S1 N

S1 H

"TB

7"

AUX

H

AUX

N

120

VA

C

NE

UTR

AL

NE

UTR

AL

120

VA

C

NE

UTR

AL

120

VA

C

SU

PP

LIE

D

(-)

CU

STO

ME

R

RA

DIO

(+)

PW

RA

NT

RE

CO

MM

EN

DE

D C

OM

M D

EV

ICE

WIR

ING

LS T

ES

TS

WIT

CH

ES

"TB

8"TB

8 C

ON

NE

CTI

ON

SS

HO

WN

IN B

US

HIN

G 3

/4P

OS

ITIO

N, W

YE

CO

NFI

GU

RA

TIO

N

Page 52: Form 7 microprocessor-based pole-mount recloser control

46 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 45. Voltage sensing option A (IVS and LSVS) with Loop Scheme (LS)

Figure 46. Voltage sensing option B (IVS and PT) with Loop Scheme (LS)

YØOFF

AØ BØ CØ XØOFF

ON

OFF

ON

OFF

ON

OFF

ON

ZØOFF

ONON

Form 7 voltagesensing board

(board 250)

37 pincontrol

receptacle

LS testswitches

BUSHING1 3 5 2 4 6

P252P251

+ +--

Voltage sensingharness plugs

YØOFF

AØ BØ CØ XØOFF

ON

OFF

ON

OFF

ON

OFF

ON

ZØOFF

ONON

Form 7 voltagesensing board

(board 250)

37 pincontrol

receptacle

LS testswitches

BUSHING1 3 5 2 4 6

P252P251

+ +--

Voltage sensingharness plug

WARNING

Hazardous Voltage

Can Cause SevereInjury or Death

Turn off power beforeremoving cover.

SI01038002

V1 V3 V5 V2 V4 V6+ - + - + - + - + - + -

S2 H

S2 N

TB7terminal

block

PTattenuator

board

Jumpers shownin default

V5 position

Page 53: Form 7 microprocessor-based pole-mount recloser control

47INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 47. Voltage sensing option C (PT only) with Loop Scheme (LS)

Figure 48. Voltage sensing option A (IVS and LSVS) without Loop Scheme (LS)

YØOFF

AØ BØ CØ XØOFF

ON

OFF

ON

OFF

ON

OFF

ON

ZØOFF

ONON

WARNING

Hazardous Voltage

Can Cause SevereInjury or Death

Turn off power beforeremoving cover.

SI01038002

V1 V3 V5 V2 V4 V6+ - + - + - + - + - + -

Form 7 voltagesensing board

(board 250)

S1 H

S1N

S2 H

S2 N

TB7terminal

block

PTattenuator

board

LS testswitches

Jumpers shownin default

V3 and V5 positions

BUSHING1 3 5 2 4 6

P252P251

+ +--

Form 7 voltagesensing board

(board 250)

37 pincontrol

receptacle

BUSHING1 3 5 2 4 6

P252P251

+ +--

Voltage sensingharness plugs

Page 54: Form 7 microprocessor-based pole-mount recloser control

48 INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

Figure 49. Voltage sensing option B (IVS and PT) without Loop Scheme (LS)

Figure 50. Voltage sensing option C (PT only) without Loop Scheme (LS)

Form 7 voltagesensing board

(board 250)

37 pincontrol

receptacle

BUSHING1 3 5 2 4 6

P252P251

+ +--

Voltage sensingharness plug

WARNING

Hazardous Voltage

Can Cause SevereInjury or Death

Turn off power beforeremoving cover.

SI01038002

V1 V3 V5 V2 V4 V6+ - + - + - + - + - + -

S2 H

S2 N

TB7terminal

block

PTattenuator

board

Jumpers shownin default

V5 position

WARNING

Hazardous Voltage

Can Cause SevereInjury or Death

Turn off power beforeremoving cover.

SI01038002

V1 V3 V5 V2 V4 V6+ - + - + - + - + - + -

Form 7 voltagesensing board

(board 250)

S1 H

S1N

S2 H

S2 N

TB7terminal

block

PTattenuator

board

Jumpers shownin default

V3 and V5 positions

BUSHING1 3 5 2 4 6

P252P251

+ +--

Page 55: Form 7 microprocessor-based pole-mount recloser control

49INSTALLATION AND OPERATION INSTRUCTIONS MN280095EN February 2022

Form 7 microprocessor-based pole-mount recloser control

his page is intentionally left blank.T

Page 56: Form 7 microprocessor-based pole-mount recloser control

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

Eaton’s Power Systems Division2300 Badger DriveWaukesha, WI 53188United StatesEaton.com/cooperpowerseries

© 2022 EatonAll Rights ReservedPrinted in USAPublication No. MN280095EN / Z25907KA2048-761 REV 01February 2022

Eaton is a registered trademark.

All trademarks are property of their respective owners.

For Eaton’s Cooper Power series product information, call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.

!SAFETYFOR LIFE