  • 1External Roof-mounted Power Vent System EuropeanHome.com

    -- Installation and service must be performed by a qualified installer, service agency or the gas supplier.

    WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

    INSTALLER: Leave this manual with the appliance.CONSUMER: Retain this manual for future reference.

    Installation, Operation

    andOwners Manual

    August 16, 2017

    External Roof-mounted Power Vent System

    Please read this manual thoroughly before beginning the installation. It has information which is important for safe

    installation and operation.

    Control Number 4006611

  • 2External Roof-mounted Power Vent System EuropeanHome.com

    TABLE OF CONTENTS

    Important Safety Information 3

    Product Information 4

    Venting Requirements 8

    Installation 11

    Operating the System 19

    Troubleshooting 20

    Warranty Appendix A

  • 3

    IMPORTANT SAFETY INFORMATIONRead these instructions carefully before installing or operating this system.

    External Roof-mounted Power Vent System EuropeanHome.com

    Symbol Legend:The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product.

    Danger: Indicates an imminent hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.X

    Caution: Indicates an imminent hazardous situation which, if not avoided, may result in personal injury or property damage.

    TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

    1. This system is intended for use with European Home products ONLY.

    2. Before servicing or cleaning the unit, switch the electric service off at the load center and lock the load center to prevent the power from being switched on accidentally.

    3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with applicable codes and standards.

    4. Follow the appliance manufacturers guidelines and safety standards such as those published by the National Fire Protection Associations (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.

    5. This unit must be grounded.

  • PRODUCT INFORMATION

    4External Roof-mounted Power Vent System EuropeanHome.com

    Thank you for purchasing an External Roof-mounted Power Vent System (ERPVS) by European Home. This system combines two great hearth product names; European Home and Enervex. Where necessary, excerpts (in italics) of the Enervex installation instruc-tions are inserted into this manual and labeled with: ENERVEX

    OVERVIEW

    The ERPVS is approved for use with the entire line of Element4 fireplaces. It accepts 5 x 8 venting and is intended for external, roof-mounted use ONLY. The ERPVS consists of six main components:

    1. a PV-GS-SGV-02 solenoid valve2. a PV-VM-FMA-01 fan mount assembly3. a PV-GS-CM-ADC 100 system control with PDS 1 proven draft switch, included4. a PV-VM-PV-RS009 fan5. a PV-ES-PLS-WHT system switch6. an E4-SA-WS-80 flame wall switch7. an installation manual

    The PV-VM-PV-RS009 fan, which creates negative pressure within the venting, is bolted to the PV-VM-FMA-01 fan mount which, in turn, is fastened to the customer-provided venting chase. Inside of the building, the PDS 1 proven draft switch senses the draft pressure and signals the system control. Once the draft has been established the solenoid valve is opened, the ready light is lit and the fireplace can be operated as usual.

    The above components are all connected by customer-supplied wiring which must be in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, NFPA70.

    The installation of your ERPVS will follow the steps below and this manual is laid out accordingly.

    Installing the Fan and Fan Controls

    Installing the Solenoid Gas Valve

    Testing the System

    As sold, the Enervex components may be installed to accommodate a number of different fireplace models and types. However, when installed with an Element4 fireplace from European Home the Enervex instructions excerpted in this manual are to be followed exclusively.

  • PRODUCT INFORMATION

    External Roof-mounted Power Vent System EuropeanHome.com5

    Fan (PV-VM-PV-RS009)

    Voltage 1 x 120V AC

    Amperage 0.5

    RPM 1600

    Horsepower 1/30

    Weight 29 lbs.

    Dimension (A) 10.2

    Dimension (B) 11.7

    Dimension (C) 10.8

    Dimension (D) 3.0

    Dimension (E) 9.4

    SPECIFICATIONS

    System Control (PV-GS-CM-ADC 100)

    Voltage 1 x 120V AC

    Amperage 6.3

    Draft Pressure -0.05 w.c.

    Weight 2.6 lbs.

    Dimension (B) 6.3

    Dimension (A) 9.6

    Dimension (C) 3.5

    Proven Draft Switch (PDS 1)

    Temp. Limits -40F to +190F

    Draft Pressure -0.05 w.c.

    Weight 9.6 oz.

    Max. Height 3.7

    Max. Width 5.1

    Max. Depth 3.2

    4

    3916067 01.13

    2.Specifications

    2.1 Dimensions & Capacities

    ADC100 ControlPower supply V 1x120VACAmperage A 6.3Operating temperature F/C -4 to 122 / -20 to 50Control signal mA max. 10Control relay Max. 120 VAC / 8A Output VAC 10-120

    VDC 0-10Post Purge Time 0-3 MinutesAlarm Delay Time 15 SecondsDimensions A in/mm 9.6 / 244

    B in/mm 6.3 / 160C in/mm 3.5 / 90

    Weight lbs/kg 2.6 / 1.2Chimney ProbeDimensions D in/mm 4.25 / 108

    E in/mm 3.50 / 89

    B

    A

    C

    ADC100

    E

    D

    ADC100

    2

    3903001 05.12

    1. Product Information .............................................................................................................2

    2. Specifications .............................................................................................................2

    3. MechanicalInstallation .............................................................................................................3

    4. ElectricalInstallation .............................................................................................................4 5. StartupandConfiguration .............................................................................................................4

    1. Product Information

    1.1 FunctionUse The PDS 1, Proven Draft Switch, is a fixed position differential pressure switch that is used in conjunction with ENERVEXs Mechanical Draft Systems for insufficient draft protection. If an unsafe draft condition occurs, whether this is caused by mechanical or electrical failure, the switch will shut down the heating appliance. It is typically used with gas or oil fired appliances where it can be interlocked with the gas supply valve or the safety or control circuit of the appliance.

    Construction The enclosure, the switch housing and the internal switch are made of polycarbonate. The diaphragm is madeofNBR(silicone),whiletheswitchingcontactismadeinfinesilver.

    Listings The switch is UL recognized product

    1.2ComponentsStandard packinglist The PDS shipment contains: - 1 PDS 1 Differential Pressure Switch - Duct Kit consisting of stack probe with mounting flange and 6 ft silicone tubing If other components are shipped, they will appear as separate items on the shipping packing list.

    1.3 Warranty CompletewarrantyconditionsareavailablefromENERVEX,Inc.

    2.Specifications

    2.1Dimensions&Capacities

    PDS 1Maximum Load V 1x120 VAC

    Amperage A 3

    Range of Operation inWC/Pa .05 to .50/13 to 135

    Temperature Limits oF/oC -40 to +190/ -40 to +88

    Max. Pressure PSI/mbar 3 / 207

    Wiring Connections 1/4 Solderless Quick Con-nect Terminals

    Pressure Connections Two plastic tubes, outside diameter of 1/4 (6.0mm)

    Weight oz. / kg 9.6 / 0.275

    ENERVEX

    PDS 1

    5.12 (130 mm)

    3.70

    (9

    4 m

    m)

    3.19 (81 mm)

    ENERVEX

    ENERVEX

    4

    3000270 03.14

    2. Specifications 2.1 Dimensions & Capacities

    Capacity

    Sound Data

    1 Junction Box 2 Conduit/cord3 Motor4 Motor Housing5 Cooling Plates6 Bird Screen7 Base Plate8 Locking Nut9 Inlet10 Axial Vane11 Hinges12 Capacitor (inside junction box)

    Model Lw dB (measured in accordance with ISO 3744) Lp dB(A)

    125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz

    RS 009 54 50 47 43 38 31 25 21

    RS 012 64 60 55 52 48 42 34 30

    RS 014 75 69 65 62 57 51 44 41

    RS 016 81 76 72 69 64 58 52 47

    Model RS 009 RS 012 RS 014 RS 016Discharge Horizontal

    Fan Type Axial Vane

    Motor Type Totally enclosed, Variable speed, Class H

Search related