  • ANADVANTAGE THESIZEOFTHEWORLD

    81YEARS OFINNOVATION

    Nationalandinternationalconsolidation1stgenerationofsemihermeticreciprocatingcompressors

    Firstscrewcompressorsinstallations2ndgenerationofsemihermeticreciprocatingcompressors

    NewproductrangesCompactscrewcompressors,CO2,integratedVFD

    InaugurationofFrascoldINDIAinAhmedabadAndAustralianOfficeinSidney

    Frascoldisfounded

    81yearsofhistory

    Andmoreyettocome…

    1970s1936 Today1990s 20122000s 2014

    InaugurationofFrascoldUSAinSeattleAndFrascoldChinainShanghai

    Blueis better

  • FRASCOLD SpAItaly (1936)

    Frascold India(2012)

    Frascold Shanghai(2014)

    Frascold USA(2014)

    Sales office(2012)

    Frascold SpARescaldina (MI)Headquarters and production

    Frascold IndiaAhmedabadCond. unit assembly and warehouse

    Frascold ShanghaiShanghaiSales office and warehouse

    Frascold USASeattleSales office and warehouse

    Blueis better

  • Main Customers and References

    Stationary Refrigeration

    TEKO (Germany) 

    Racks and condensing units

    Zanotti (Italy, Spain, UK) 

    Racks and condensing units

    Rivacold (Italy) 

    Racks and condensing units

    Tecumseh (FR, Indonesia, Brasil, USA)

    Condensing Units

    Carpigiani (Italy)

    Ice Cream Machine

    Comfort

    Euroklimat (Italy) Chillers 

    Jonhson Controls (DK) Chillers

    Kirloskar (India) Chillers

    Thermocold (Italy) Chillers

    Rhoss (Italy) Chillers

    RC Group (Italy) Chillers

    Geoclima (Italy) Chillers

    Blueis better

  • 6

    Main Customers and References

    Mobile Cooling

    Thermo King (Spain, USA, Brazil) 

    Refrigerated trucks

    Carrier Transicold (France)

    Refrigerated trucks

    Zanotti (Italy) 

    Refrigerated trucks

    Cold Car (Italy) 

    Refrigerated trucks

    Transfrig (South Africa)

    Refrigerated trucks

    Siemens (Belgium) 

    Train A/C

    Carrier (Korea) 

    Train A/C  

    Blueis better

  • 7

    Branded Compressors

    Thermo King (Semi‐hermetic and open reciprocating compressors)

    Tecumseh (Semi‐hermetic reciprocating compressors)

    Carrier (Semi‐hermetic reciprocating compressors)

    Carrier Transicold (Semi‐hermetic reciprocating compressors)

    Kirloskar Chillers (Semi‐hermetic compact screw compressors)

    Lebrun (Semi‐hermetic compact screw compressors)

    Blueis better

  • Reciprocating Compressors

    Standard Reciprocating Compressors Optimized for R134a

    SK Models Sub‐CriticalCO2 Application

    TK Models Trans‐Critical CO2 Application

    Two Stage Compressors For Low Temp Application

    Tandem Compressor Models

    VS Compressor Models with Built‐In VFD

    Transport Compressors

    Blueis better

  • SEMI HERMETIC COMPRESSORS

    RECIPROCATING

    Single stage

    CO2 subcritical – 80 bar

    CO2 transcritical – 155 bar

    ECOinside (optimized R134a) 

    VS (built‐in VSD)

    AXH and AXY (ATEX)

    Double stage

    Tandem

    TS (transport)

    Blueis better

    New Capacity control

    New Capacyti control

    New Capacity control

    New Capacity control

    New Capacity control

    New Capacity control

    Reciprocating Compressors

  • 10

    GENERAL CONCEPTS

    Systems are designed to satisfy the maximum cooling capacity that could occur, so for most 

    of the operating time systems are over dimensioned 

    The capacity could be reduced switching OFF periodically the compressor but there are 

    limitations: max switch rate: 8‐10/hour – minimum running time 2 – 5 min.

    These limitation brings to large temperature deviation in the room

    The system has to cool down the room enough to guarantee that during compressor 

    standstill  (6 min – cycle time) the temperature can’t rise over the maximum acceptable 

    temperature, to do this lower Tevap. is required

    Lower evapora ng temperature → lower COP of the compressor

    The possibility to regulate capacity permit to keep the compressor in operation for longer 

    time and to operate at a higher Tevap. .

    Blueis better

    Exclusive and innovative Capacity Control

  • Blueis better

    How standard capacity control  works?

    Exclusive and innovative Capacity Control

  • 0% Displacement

    100% Displacement

    ‐ Vacuum effect‐ Unbalancing

    STANDARD CC HEAD

    Blueis better

    Exclusive and innovative Capacity Control

  • 13

    compressor ON‐OFF

    12 start/hour TOO MANY !!! Out of Compressor limits!

    Very short running time

    Temperature variation can’t be increased

    compressor1 with Capacity Control

    10 start/hour OK Less compressor starts

    Longer running time

    Case 1: Reducing n° of start / hour

    Blueis better

    Exclusive and innovative Capacity Control

  • 14

    Given Tmax and Tmin, with Capacity regulation is 

    possible to:

    increase continuous running time

    reduce starts/hour

    → Reduced electrical stress at start‐up

    → Reduced mechanical stress at start‐up

    → Better oil return to the compressor

    Secondary effect: at partial load the load on condenser is less

    → With Capacity regulation (and floating condensing temp) is possible to reduce Tcond

    Case 1: Reducing n° of start / hour

    Blueis better

    Exclusive and innovative Capacity Control

  • 15

    compressor ON‐OFF

    6 start/hour OK Very short running time

    Large Temperature variation 

    Low Tmin → Low Tevap (Tmin ‐14°F)

    compressor1 with Capacity Control

    6 start/hour OK Longer running time

    Smaller temperature variation 

    Higher Tmin → Higher Tevap

    Case 2: improving efficiency

    Blueis better

    Exclusive and innovative Capacity Control

  • 16

    With Capacity regulation is possible to reduce 

    variation of room temperature.

    Given Tmax is possible to increase Tmin Tevap = Tmin – evaporator’s ∆T

    → Regulating capacity is possible to increase Tevap

    @‐35°C/45°C:   Tevap ↑1.8°C  ↔  COP ↑ 4%Tevap ↑3.6°C ↔   COP ↑ 6% Tevap ↑5.4°C ↔  COP ↑ 10%

    Secondary effect: at partial load the load on condenser is less

    → With Capacity regulation (and floating condensing temp) is possible to reduce Tcond

    Blueis better

    Exclusive and innovative Capacity Control

  • LESS compressor On‐Off cycles

    FEATURES & PRO’s

    Blueis better

    Exclusive and innovative Capacity Control

  • 18

    Capacity Control Problems

    Traditional Capacity Controls operates closing completely the suction flow 

    to the cylinders under the CC head.

    This can cause several problems that can cause serious consequences:

    Overheating

    • The refrigerant trapped into the cylinders is continuously expanded and compressed increasing gradually its temperature

    • No temperature monitoring because these cylinder has no discharge flow

    • Over 150‐160 °C POE oil vaporize and parts start wearing; over 170°C POE oil carbonize and create contaminants increasing wearing of parts

    • Worn piston and piston rings permit high pressure bypass to the crankcase closing oil check valve and interrupting oil flow back from 

    the system

    High pressure in crankcase

    Oil check valve closedNO oil return Blueis better

    Exclusive and innovative Capacity Control

  • 19

    Capacity Control Problems

    Vacuum operation

    • Every cycle the piston movement create  vacuum into the cylinder 

    but suction reed don’t open (no suction flow)

    • Vacuum suck oil from cylinder liners and accumulate it into the 

    cylinder.

    • Oil accumulation can lead to liquid slug and damage or broke the  

    discharge reed or the valve plate gasket

    • Broken parts will end up in compressor malfunctioning

    Brokendischargereed 

    Brokengasket

    Blueis better

    Exclusive and innovative Capacity Control

  • RSH HEAD

    50% Displacement

    100% Displacement

    ‐ Operating Pressure‐ More balanced

    Blueis better

    Exclusive and innovative Capacity Control

  • LESS compressor On‐Off cycles and  BETTER system efficiency

    FEATURES & PRO’s

    Blueis better

    Very constant evaporatingtemperature (green line)

    Exclusive and innovative Capacity Control