  • Installation calculation report

    Dejan_Pejovski_final Full

  • Page 2/61

    Project: dejan_pejovski_final 27/05/2015

  • Page 3/61

    Project: dejan_pejovski_final 27/05/2015

    Content

    1 Project description ................................................................................................................. 4

    1.1 Project general settings ................................................................................................................... 4

    1.2 Settings for wiring device calculation............................................................................................. 4

    1.3 List of loads ....................................................................................................................................... 4

    2 Installation general design .................................................................................................... 5

    2.1 List of devices ................................................................................................................................... 5

    3 Calculation notes ................................................................................................................... 7

    3.1 Source circuits ...................................................................................... Error! Bookmark not defined.

    3.2 Generator circuits ................................................................................. Error! Bookmark not defined.

    3.3 LV Source circuits ............................................................................................................................. 7

    3.4 UPS circuits ........................................................................................... Error! Bookmark not defined.

    3.5 Surge Arrester circuits ......................................................................... Error! Bookmark not defined.

    3.6 Capacitor bank circuits ........................................................................ Error! Bookmark not defined.

    3.7 Feeder circuits ....................................................................................... Error! Bookmark not defined.

    3.8 LV Transformer circuits ........................................................................ Error! Bookmark not defined.

    3.9 Couplers circuits ................................................................................... Error! Bookmark not defined.

    3.10 Generic load circuits ....................................................................... Error! Bookmark not defined.

    3.11 Lighting load circuits ................................................................................................................ 10

    3.12 Power socket load circuits ....................................................................................................... 31

    3.13 Motor starter combination .............................................................. Error! Bookmark not defined.

    3.14 Busbar circuits ........................................................................................................................... 61

    3.15 Busbar trunking system circuits .................................................... Error! Bookmark not defined.

    3.16 Busbar trunking system circuits .................................................... Error! Bookmark not defined.

    3.17 Lighting Busbar trunking system circuits .................................... Error! Bookmark not defined.

  • Page 4/61

    Project: dejan_pejovski_final 27/05/2015

    1 Project description

    1.1 Project general settings Installation standard IEC60364

    Calculation standard TR50480 Circuit breaker standard IEC 60947-2 Frequency 50 Hz

    1.2 Settings for wiring device calculation Maximal CSA 300 mm

    1.3 List of loads

    1.3.1 Power sockets

    Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)

    AA 1 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 2 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 3 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 4 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 5 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 6 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 7 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 8 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 9 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 10 1.05 1 2.64 0.95 2 3Ph+N No 0

    1.3.2 Lighting distribution

    Name Type of lamp P Lamp (W) P ballast (W) Nb of lamp/light Nb of light EA 11 Fluorescent

    with electronic ballast

    58 4.5 4 8

    EA 14 Fluorescent with electronic ballast

    58 4.5 4 8

    EA 13 Fluorescent with electronic ballast

    58 4.5 4 8

    EA 12 Fluorescent with electronic ballast

    58 4.5 4 8

    EA 15 Fluorescent with electronic ballast

    58 4.5 4 8

    EA 16 Fluorescent with electronic ballast

    58 4.5 4 8

    EA 17 Fluorescent with electronic ballast

    58 4.5 4 8

  • Page 5/61

    Project: dejan_pejovski_final 27/05/2015

    2 Installation general design

    2.1 List of devices

    2.1.1 LV switchboards and busbar

    Switchboard name Range Rating (A) IP UC 2 No preference 0.00 Undefined

    Busbar name Switchboard

    name Ks Polarity SEA Equipotential bounding

    WC 1 UC 2 1 3Ph+N TN-S With

    2.1.2 Circuit breaker

    Name Nbr Range - Designation

    Rating (A) Poles Trip unit/Curve RCD RCD class

    QA 0 1 Compact NSX - NSX250B

    250 4P4d Micrologic 5.2 A

    QA 1 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 2 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 3 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 4 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 5 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 6 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 7 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 8 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 9 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 10 2 Acti9 iC60 - iC60N

    3 4P4d C

    QA 11 8 Acti9 iC60 - iC60N

    6 4P4d C

    QA 14 8 Acti9 iC60 - iC60N

    6 4P4d C

    QA 13 8 Acti9 iC60 - iC60N

    6 4P4d C

    QA 12 8 Acti9 iC60 - iC60N

    6 4P4d C

    QA 15 8 Acti9 iC60 - iC60N

    6 4P4d C

    QA 16 8 Acti9 iC60 - iC60N

    6 4P4d C

    QA 17 1 Acti9 iC60 - iC60N

    6 4P4d C

    2.1.3 Cable schedule

    Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN WD 10 2 QA 10 AA 10 Multi-core PVC 60 1x1.5

    Copper 1x1.5 Copper

    1x1.5 Copper

  • Page 6/61

    Project: dejan_pejovski_final 27/05/2015

    WD 9 2 QA 9 AA 9 Multi-core PVC 60 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 17 1 QA 17 EA 17 Multi-core PVC 50 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 16 8 QA 16 EA 16 Multi-core PVC 50 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 12 8 QA 12 EA 12 Multi-core PVC 50 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 11 8 QA 11 EA 11 Multi-core PVC 50 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 2 2 QA 2 AA 2 Multi-core PVC 50 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 1 2 QA 1 AA 1 Multi-core PVC 50 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 15 8 QA 15 EA 15 Multi-core PVC 45 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 13 8 QA 13 EA 13 Multi-core PVC 45 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 14 8 QA 14 EA 14 Multi-core PVC 40 1x2.5 Copper

    1x2.5 Copper

    1x2.5 Copper

    WD 4 2 QA 4 AA 4 Multi-core PVC 40 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 3 2 QA 3 AA 3 Multi-core PVC 40 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 6 2 QA 6 AA 6 Multi-core PVC 30 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 5 2 QA 5 AA 5 Multi-core PVC 30 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 8 2 QA 8 AA 8 Multi-core PVC 20 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 7 2 QA 7 AA 7 Multi-core PVC 20 1x1.5 Copper

    1x1.5 Copper

    1x1.5 Copper

    WD 0 1 W 0 QA 0 Multi-core PVC 5 1x95 Copper

    1x95 Copper

    1x50 Copper

  • Page 7/61

    Project: dejan_pejovski_final 27/05/2015

    3 Calculation notes

    3.1 LV Source circuits

    3.1.1 Circuit Source 0

    LV power supply W 0 Connection description Type of connection Private substation Ur 230 V Connection capacity - Ir 206 A Polarity 3Ph+N System earthing arrangement TN-S Equipotential bounding No Rb (neutral grounding) NA Ra (mass grounding) NA Short circuit characteristics Ik3max 20 kA Ik1min 8 kA Ief 10 kA Ief2min 5 kA

    Cos cc 0.3

    Cable WD 0 Parameters Length 5 m Max length NA Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 206 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x95 mm Core Copper Iz under real conditions 238 A Selected neutral Cross section area 1x95 mm Core Copper

  • Page 8/61

    Project: dejan_pejovski_final 27/05/2015

    Iz under real conditions 238 A Selected PE Cross section area 1x50 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 20.00 17.32 9.26 13.37 7.21 8.43 0.00

    Synthesis for all operating mode (kA) 20.00 17.32 9.26 13.37 7.21 8.43 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Circuit breaker QA 0 Ib 206 A

    Distance from origin NA Sizing Information Sized by system Range Compact NSX Designation NSX250B Circuit breaker rating 250 A Breaking capacity 40 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation Micrologic 5.2 A Trip unit rating 250 A Long delay settings Ir 207 A Tr 16 s Short delay settings Isd current 2070 A Tsd 0 s Instantaneous tripping Ii current 3000 A

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    NA Discrimination can't be determinated : no upstream Lv Breaker

    Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 206.499 206.499 148.235 58.3

  • Page 9/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 206.499 206.499 148.235 58.3 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 2.192 0.192

    UL1L2 (%) 2.222 0.222

    UL2L3 (%) 2.222 0.222

    UL3L1 (%) 2.222 0.222

    UL1N (%) 2.192 0.192

    UL2N (%) 2.192 0.192

    UL3N (%) 2.192 0.192

  • Page 10/61

    Project: dejan_pejovski_final 27/05/2015

    3.2 Lighting load circuits

    3.2.1 Circuit Load 11

    Circuit breaker QA 11 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 11 Parameters Length 50 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 11 has been

  • Page 11/61

    Project: dejan_pejovski_final 27/05/2015

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 11 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

  • Page 12/61

    Project: dejan_pejovski_final 27/05/2015

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 4.087 1.895

    UL1L2 (%) 4.410 2.188

    UL2L3 (%) 4.045 1.824

    UL3L1 (%) 4.045 1.824

    UL1N (%) 4.719 2.527

    UL2N (%) 4.719 2.527

    UL3N (%) 4.087 1.895

    Synthesis for all operating mode

    U3L (%) 4.087

    UL1L2 (%) 4.410

    UL2L3 (%) 4.045

    UL3L1 (%) 4.045

    UL1N (%) 4.719

    UL2N (%) 4.719

    UL3N (%) 4.087

  • Page 13/61

    Project: dejan_pejovski_final 27/05/2015

    3.2.2 Circuit Load 14

    Circuit breaker QA 14 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 14 Parameters Length 40 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 14 has been

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1

  • Page 14/61

    Project: dejan_pejovski_final 27/05/2015

    Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.30 0.18 0.18 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.30 0.18 0.18 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 14 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

  • Page 15/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.708 1.516

    UL1L2 (%) 3.972 1.751

    UL2L3 (%) 3.681 1.459

    UL3L1 (%) 3.681 1.459

    UL1N (%) 4.214 2.021

    UL2N (%) 4.214 2.021

    UL3N (%) 3.708 1.516

    Synthesis for all operating mode

    U3L (%) 3.708

    UL1L2 (%) 3.972

    UL2L3 (%) 3.681

    UL3L1 (%) 3.681

    UL1N (%) 4.214

    UL2N (%) 4.214

    UL3N (%) 3.708

  • Page 16/61

    Project: dejan_pejovski_final 27/05/2015

    3.2.3 Circuit Load 13

    Circuit breaker QA 13 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 13 Parameters Length 45 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 13 has been

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1

  • Page 17/61

    Project: dejan_pejovski_final 27/05/2015

    Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 13 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

  • Page 18/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.898 1.706

    UL1L2 (%) 4.191 1.969

    UL2L3 (%) 3.863 1.641

    UL3L1 (%) 3.863 1.641

    UL1N (%) 4.466 2.274

    UL2N (%) 4.466 2.274

    UL3N (%) 3.898 1.706

    Synthesis for all operating mode

    U3L (%) 3.898

    UL1L2 (%) 4.191

    UL2L3 (%) 3.863

    UL3L1 (%) 3.863

    UL1N (%) 4.466

    UL2N (%) 4.466

    UL3N (%) 3.898

  • Page 19/61

    Project: dejan_pejovski_final 27/05/2015

    3.2.4 Circuit Load 12

    Circuit breaker QA 12 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 12 Parameters Length 50 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 12 has been

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1

  • Page 20/61

    Project: dejan_pejovski_final 27/05/2015

    Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 12 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

  • Page 21/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 4.087 1.895

    UL1L2 (%) 4.410 2.188

    UL2L3 (%) 4.045 1.824

    UL3L1 (%) 4.045 1.824

    UL1N (%) 4.719 2.527

    UL2N (%) 4.719 2.527

    UL3N (%) 4.087 1.895

    Synthesis for all operating mode

    U3L (%) 4.087

    UL1L2 (%) 4.410

    UL2L3 (%) 4.045

    UL3L1 (%) 4.045

    UL1N (%) 4.719

    UL2N (%) 4.719

    UL3N (%) 4.087

  • Page 22/61

    Project: dejan_pejovski_final 27/05/2015

    3.2.5 Circuit Load 15

    Circuit breaker QA 15 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 15 Parameters Length 45 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 15 has been

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1

  • Page 23/61

    Project: dejan_pejovski_final 27/05/2015

    Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 15 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

  • Page 24/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.898 1.706

    UL1L2 (%) 4.191 1.969

    UL2L3 (%) 3.863 1.641

    UL3L1 (%) 3.863 1.641

    UL1N (%) 4.466 2.274

    UL2N (%) 4.466 2.274

    UL3N (%) 3.898 1.706

    Synthesis for all operating mode

    U3L (%) 3.898

    UL1L2 (%) 4.191

    UL2L3 (%) 3.863

    UL3L1 (%) 3.863

    UL1N (%) 4.466

    UL2N (%) 4.466

    UL3N (%) 3.898

  • Page 25/61

    Project: dejan_pejovski_final 27/05/2015

    3.2.6 Circuit Load 16

    Circuit breaker QA 16 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 16 Parameters Length 50 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 16 has been

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1

  • Page 26/61

    Project: dejan_pejovski_final 27/05/2015

    Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 16 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

  • Page 27/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 4.087 1.895

    UL1L2 (%) 4.410 2.188

    UL2L3 (%) 4.045 1.824

    UL3L1 (%) 4.045 1.824

    UL1N (%) 4.719 2.527

    UL2N (%) 4.719 2.527

    UL3N (%) 4.087 1.895

    Synthesis for all operating mode

    U3L (%) 4.087

    UL1L2 (%) 4.410

    UL2L3 (%) 4.045

    UL3L1 (%) 4.045

    UL1N (%) 4.719

    UL2N (%) 4.719

    UL3N (%) 4.087

  • Page 28/61

    Project: dejan_pejovski_final 27/05/2015

    3.2.7 Circuit Load 17

    Circuit breaker QA 17 Ib 5.95 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 17 Parameters Length 50 m Max length 246 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 17 has been

    increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir

    Correction factors Temperature factor 1

  • Page 29/61

    Project: dejan_pejovski_final 27/05/2015

    Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 17 U 230 V S 2.37 kVA P 2 kW I 5.95 A

    cos 0.95

    Ku (Normal) 1 Number of circuit 1 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 5.945 5.945 3.964 1.98

  • Page 30/61

    Project: dejan_pejovski_final 27/05/2015

    Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 4.087 1.895

    UL1L2 (%) 4.410 2.188

    UL2L3 (%) 4.045 1.824

    UL3L1 (%) 4.045 1.824

    UL1N (%) 4.719 2.527

    UL2N (%) 4.719 2.527

    UL3N (%) 4.087 1.895

    Synthesis for all operating mode

    U3L (%) 4.087

    UL1L2 (%) 4.410

    UL2L3 (%) 4.045

    UL3L1 (%) 4.045

    UL1N (%) 4.719

    UL2N (%) 4.719

    UL3N (%) 4.087

  • Page 31/61

    Project: dejan_pejovski_final 27/05/2015

    3.3 Power socket load circuits

    3.3.1 Circuit Load 1

    Circuit breaker QA 1 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 1 Parameters Length 50 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors

  • Page 32/61

    Project: dejan_pejovski_final 27/05/2015

    Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 1 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

  • Page 33/61

    Project: dejan_pejovski_final 27/05/2015

    Operating mode Normal

    U3L (%) 3.594 1.402

    UL1L2 (%) 3.841 1.619

    UL2L3 (%) 3.841 1.619

    UL3L1 (%) 3.841 1.619

    UL1N (%) 3.594 1.402

    UL2N (%) 3.594 1.402

    UL3N (%) 3.594 1.402

    Synthesis for all operating mode

    U3L (%) 3.594

    UL1L2 (%) 3.841

    UL2L3 (%) 3.841

    UL3L1 (%) 3.841

    UL1N (%) 3.594

    UL2N (%) 3.594

    UL3N (%) 3.594

  • Page 34/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.2 Circuit Load 2

    Circuit breaker QA 2 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 2 Parameters Length 50 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 35/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 2 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.594 1.402

    UL1L2 (%) 3.841 1.619

  • Page 36/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 3.841 1.619

    UL3L1 (%) 3.841 1.619

    UL1N (%) 3.594 1.402

    UL2N (%) 3.594 1.402

    UL3N (%) 3.594 1.402

    Synthesis for all operating mode

    U3L (%) 3.594

    UL1L2 (%) 3.841

    UL2L3 (%) 3.841

    UL3L1 (%) 3.841

    UL1N (%) 3.594

    UL2N (%) 3.594

    UL3N (%) 3.594

  • Page 37/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.3 Circuit Load 3

    Circuit breaker QA 3 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 3 Parameters Length 40 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 38/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 3 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.314 1.122

    UL1L2 (%) 3.517 1.295

  • Page 39/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 3.517 1.295

    UL3L1 (%) 3.517 1.295

    UL1N (%) 3.314 1.122

    UL2N (%) 3.314 1.122

    UL3N (%) 3.314 1.122

    Synthesis for all operating mode

    U3L (%) 3.314

    UL1L2 (%) 3.517

    UL2L3 (%) 3.517

    UL3L1 (%) 3.517

    UL1N (%) 3.314

    UL2N (%) 3.314

    UL3N (%) 3.314

  • Page 40/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.4 Circuit Load 4

    Circuit breaker QA 4 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 4 Parameters Length 40 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 41/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 4 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.314 1.122

    UL1L2 (%) 3.517 1.295

  • Page 42/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 3.517 1.295

    UL3L1 (%) 3.517 1.295

    UL1N (%) 3.314 1.122

    UL2N (%) 3.314 1.122

    UL3N (%) 3.314 1.122

    Synthesis for all operating mode

    U3L (%) 3.314

    UL1L2 (%) 3.517

    UL2L3 (%) 3.517

    UL3L1 (%) 3.517

    UL1N (%) 3.314

    UL2N (%) 3.314

    UL3N (%) 3.314

  • Page 43/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.5 Circuit Load 5

    Circuit breaker QA 5 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 5 Parameters Length 30 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 44/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 5 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.033 0.841

    UL1L2 (%) 3.193 0.971

  • Page 45/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 3.193 0.971

    UL3L1 (%) 3.193 0.971

    UL1N (%) 3.033 0.841

    UL2N (%) 3.033 0.841

    UL3N (%) 3.033 0.841

    Synthesis for all operating mode

    U3L (%) 3.033

    UL1L2 (%) 3.193

    UL2L3 (%) 3.193

    UL3L1 (%) 3.193

    UL1N (%) 3.033

    UL2N (%) 3.033

    UL3N (%) 3.033

  • Page 46/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.6 Circuit Load 6

    Circuit breaker QA 6 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 6 Parameters Length 30 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 47/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 6 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.033 0.841

    UL1L2 (%) 3.193 0.971

  • Page 48/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 3.193 0.971

    UL3L1 (%) 3.193 0.971

    UL1N (%) 3.033 0.841

    UL2N (%) 3.033 0.841

    UL3N (%) 3.033 0.841

    Synthesis for all operating mode

    U3L (%) 3.033

    UL1L2 (%) 3.193

    UL2L3 (%) 3.193

    UL3L1 (%) 3.193

    UL1N (%) 3.033

    UL2N (%) 3.033

    UL3N (%) 3.033

  • Page 49/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.7 Circuit Load 7

    Circuit breaker QA 7 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 7 Parameters Length 20 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 50/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 7 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 2.753 0.561

    UL1L2 (%) 2.869 0.648

  • Page 51/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 2.869 0.648

    UL3L1 (%) 2.869 0.648

    UL1N (%) 2.753 0.561

    UL2N (%) 2.753 0.561

    UL3N (%) 2.753 0.561

    Synthesis for all operating mode

    U3L (%) 2.753

    UL1L2 (%) 2.869

    UL2L3 (%) 2.869

    UL3L1 (%) 2.869

    UL1N (%) 2.753

    UL2N (%) 2.753

    UL3N (%) 2.753

  • Page 52/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.8 Circuit Load 8

    Circuit breaker QA 8 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 8 Parameters Length 20 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 53/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 8 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 2.753 0.561

    UL1L2 (%) 2.869 0.648

  • Page 54/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 2.869 0.648

    UL3L1 (%) 2.869 0.648

    UL1N (%) 2.753 0.561

    UL2N (%) 2.753 0.561

    UL3N (%) 2.753 0.561

    Synthesis for all operating mode

    U3L (%) 2.753

    UL1L2 (%) 2.869

    UL2L3 (%) 2.869

    UL3L1 (%) 2.869

    UL1N (%) 2.753

    UL2N (%) 2.753

    UL3N (%) 2.753

  • Page 55/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.9 Circuit Load 9

    Circuit breaker QA 9 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 9 Parameters Length 60 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 56/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 9 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.875 1.683

    UL1L2 (%) 4.165 1.943

  • Page 57/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 4.165 1.943

    UL3L1 (%) 4.165 1.943

    UL1N (%) 3.875 1.683

    UL2N (%) 3.875 1.683

    UL3N (%) 3.875 1.683

    Synthesis for all operating mode

    U3L (%) 3.875

    UL1L2 (%) 4.165

    UL2L3 (%) 4.165

    UL3L1 (%) 4.165

    UL1N (%) 3.875

    UL2N (%) 3.875

    UL3N (%) 3.875

  • Page 58/61

    Project: dejan_pejovski_final 27/05/2015

    3.3.10 Circuit Load 10

    Circuit breaker QA 10 Ib 2.64 A

    Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA

    Discrimination Results

    UpStream Discrimination Limit

    Operating mode Normal

    QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d

    Full Discrimination

    Cable WD 10 Parameters Length 60 m Max length 148 m Installation method 31

    E Multi-core cables on horizontal perforated tray

    Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16

  • Page 59/61

    Project: dejan_pejovski_final 27/05/2015

    Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1

    Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 10 U 230 V S 1.05 kVA P 1 kW I 2.64 A

    cos 0.95

    Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN

    Operating mode Normal (A) 2.642 2.642 2.642 0

    Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit

    Operating mode Normal

    U3L (%) 3.875 1.683

    UL1L2 (%) 4.165 1.943

  • Page 60/61

    Project: dejan_pejovski_final 27/05/2015

    UL2L3 (%) 4.165 1.943

    UL3L1 (%) 4.165 1.943

    UL1N (%) 3.875 1.683

    UL2N (%) 3.875 1.683

    UL3N (%) 3.875 1.683

    Synthesis for all operating mode

    U3L (%) 3.875

    UL1L2 (%) 4.165

    UL2L3 (%) 4.165

    UL3L1 (%) 4.165

    UL1N (%) 3.875

    UL2N (%) 3.875

    UL3N (%) 3.875

  • Page 61/61

    Project: dejan_pejovski_final 27/05/2015

    3.4 Busbar circuits

    3.4.1 Circuit WC 1

    Busbar WC 1 Parameters Switchboard Name UC 2 Switchboard Range No preference Rating (A) 0 IP Undefined Feeder Circuit name Protection name Protection type

    Load 1 QA 1 iC60N

    Load 2 QA 2 iC60N

    Load 3 QA 3 iC60N

    Load 4 QA 4 iC60N

    Load 5 QA 5 iC60N

    Load 6 QA 6 iC60N

    Load 7 QA 7 iC60N

    Load 8 QA 8 iC60N

    Load 9 QA 9 iC60N

    Load 10 QA 10 iC60N

    Load 11 QA 11 iC60N

    Load 14 QA 14 iC60N

    Load 13 QA 13 iC60N

    Load 12 QA 12 iC60N

    Load 15 QA 15 iC60N

    Load 16 QA 16 iC60N

    Load 17 QA 17 iC60N

    Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min

    Operating mode Normal (kA) 18.22 15.78 8.50 13.49 7.27 8.58 0.00

    Synthesis for all operating mode (kA) 18.22 15.78 8.50 13.49 7.27 8.58 0.00

    Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility.