Installation calculation report
Dejan_Pejovski_final Full
Page 2/61
Project: dejan_pejovski_final 27/05/2015
Page 3/61
Project: dejan_pejovski_final 27/05/2015
Content
1 Project description ................................................................................................................. 4
1.1 Project general settings ................................................................................................................... 4
1.2 Settings for wiring device calculation............................................................................................. 4
1.3 List of loads ....................................................................................................................................... 4
2 Installation general design .................................................................................................... 5
2.1 List of devices ................................................................................................................................... 5
3 Calculation notes ................................................................................................................... 7
3.1 Source circuits ...................................................................................... Error! Bookmark not defined.
3.2 Generator circuits ................................................................................. Error! Bookmark not defined.
3.3 LV Source circuits ............................................................................................................................. 7
3.4 UPS circuits ........................................................................................... Error! Bookmark not defined.
3.5 Surge Arrester circuits ......................................................................... Error! Bookmark not defined.
3.6 Capacitor bank circuits ........................................................................ Error! Bookmark not defined.
3.7 Feeder circuits ....................................................................................... Error! Bookmark not defined.
3.8 LV Transformer circuits ........................................................................ Error! Bookmark not defined.
3.9 Couplers circuits ................................................................................... Error! Bookmark not defined.
3.10 Generic load circuits ....................................................................... Error! Bookmark not defined.
3.11 Lighting load circuits ................................................................................................................ 10
3.12 Power socket load circuits ....................................................................................................... 31
3.13 Motor starter combination .............................................................. Error! Bookmark not defined.
3.14 Busbar circuits ........................................................................................................................... 61
3.15 Busbar trunking system circuits .................................................... Error! Bookmark not defined.
3.16 Busbar trunking system circuits .................................................... Error! Bookmark not defined.
3.17 Lighting Busbar trunking system circuits .................................... Error! Bookmark not defined.
Page 4/61
Project: dejan_pejovski_final 27/05/2015
1 Project description
1.1 Project general settings Installation standard IEC60364
Calculation standard TR50480 Circuit breaker standard IEC 60947-2 Frequency 50 Hz
1.2 Settings for wiring device calculation Maximal CSA 300 mm
1.3 List of loads
1.3.1 Power sockets
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
AA 1 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 2 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 3 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 4 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 5 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 6 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 7 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 8 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 9 1.05 1 2.64 0.95 2 3Ph+N No 0 AA 10 1.05 1 2.64 0.95 2 3Ph+N No 0
1.3.2 Lighting distribution
Name Type of lamp P Lamp (W) P ballast (W) Nb of lamp/light Nb of light EA 11 Fluorescent
with electronic ballast
58 4.5 4 8
EA 14 Fluorescent with electronic ballast
58 4.5 4 8
EA 13 Fluorescent with electronic ballast
58 4.5 4 8
EA 12 Fluorescent with electronic ballast
58 4.5 4 8
EA 15 Fluorescent with electronic ballast
58 4.5 4 8
EA 16 Fluorescent with electronic ballast
58 4.5 4 8
EA 17 Fluorescent with electronic ballast
58 4.5 4 8
Page 5/61
Project: dejan_pejovski_final 27/05/2015
2 Installation general design
2.1 List of devices
2.1.1 LV switchboards and busbar
Switchboard name Range Rating (A) IP UC 2 No preference 0.00 Undefined
Busbar name Switchboard
name Ks Polarity SEA Equipotential bounding
WC 1 UC 2 1 3Ph+N TN-S With
2.1.2 Circuit breaker
Name Nbr Range - Designation
Rating (A) Poles Trip unit/Curve RCD RCD class
QA 0 1 Compact NSX - NSX250B
250 4P4d Micrologic 5.2 A
QA 1 2 Acti9 iC60 - iC60N
3 4P4d C
QA 2 2 Acti9 iC60 - iC60N
3 4P4d C
QA 3 2 Acti9 iC60 - iC60N
3 4P4d C
QA 4 2 Acti9 iC60 - iC60N
3 4P4d C
QA 5 2 Acti9 iC60 - iC60N
3 4P4d C
QA 6 2 Acti9 iC60 - iC60N
3 4P4d C
QA 7 2 Acti9 iC60 - iC60N
3 4P4d C
QA 8 2 Acti9 iC60 - iC60N
3 4P4d C
QA 9 2 Acti9 iC60 - iC60N
3 4P4d C
QA 10 2 Acti9 iC60 - iC60N
3 4P4d C
QA 11 8 Acti9 iC60 - iC60N
6 4P4d C
QA 14 8 Acti9 iC60 - iC60N
6 4P4d C
QA 13 8 Acti9 iC60 - iC60N
6 4P4d C
QA 12 8 Acti9 iC60 - iC60N
6 4P4d C
QA 15 8 Acti9 iC60 - iC60N
6 4P4d C
QA 16 8 Acti9 iC60 - iC60N
6 4P4d C
QA 17 1 Acti9 iC60 - iC60N
6 4P4d C
2.1.3 Cable schedule
Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN WD 10 2 QA 10 AA 10 Multi-core PVC 60 1x1.5
Copper 1x1.5 Copper
1x1.5 Copper
Page 6/61
Project: dejan_pejovski_final 27/05/2015
WD 9 2 QA 9 AA 9 Multi-core PVC 60 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 17 1 QA 17 EA 17 Multi-core PVC 50 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 16 8 QA 16 EA 16 Multi-core PVC 50 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 12 8 QA 12 EA 12 Multi-core PVC 50 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 11 8 QA 11 EA 11 Multi-core PVC 50 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 2 2 QA 2 AA 2 Multi-core PVC 50 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 1 2 QA 1 AA 1 Multi-core PVC 50 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 15 8 QA 15 EA 15 Multi-core PVC 45 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 13 8 QA 13 EA 13 Multi-core PVC 45 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 14 8 QA 14 EA 14 Multi-core PVC 40 1x2.5 Copper
1x2.5 Copper
1x2.5 Copper
WD 4 2 QA 4 AA 4 Multi-core PVC 40 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 3 2 QA 3 AA 3 Multi-core PVC 40 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 6 2 QA 6 AA 6 Multi-core PVC 30 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 5 2 QA 5 AA 5 Multi-core PVC 30 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 8 2 QA 8 AA 8 Multi-core PVC 20 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 7 2 QA 7 AA 7 Multi-core PVC 20 1x1.5 Copper
1x1.5 Copper
1x1.5 Copper
WD 0 1 W 0 QA 0 Multi-core PVC 5 1x95 Copper
1x95 Copper
1x50 Copper
Page 7/61
Project: dejan_pejovski_final 27/05/2015
3 Calculation notes
3.1 LV Source circuits
3.1.1 Circuit Source 0
LV power supply W 0 Connection description Type of connection Private substation Ur 230 V Connection capacity - Ir 206 A Polarity 3Ph+N System earthing arrangement TN-S Equipotential bounding No Rb (neutral grounding) NA Ra (mass grounding) NA Short circuit characteristics Ik3max 20 kA Ik1min 8 kA Ief 10 kA Ief2min 5 kA
Cos cc 0.3
Cable WD 0 Parameters Length 5 m Max length NA Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 206 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x95 mm Core Copper Iz under real conditions 238 A Selected neutral Cross section area 1x95 mm Core Copper
Page 8/61
Project: dejan_pejovski_final 27/05/2015
Iz under real conditions 238 A Selected PE Cross section area 1x50 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 20.00 17.32 9.26 13.37 7.21 8.43 0.00
Synthesis for all operating mode (kA) 20.00 17.32 9.26 13.37 7.21 8.43 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Circuit breaker QA 0 Ib 206 A
Distance from origin NA Sizing Information Sized by system Range Compact NSX Designation NSX250B Circuit breaker rating 250 A Breaking capacity 40 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation Micrologic 5.2 A Trip unit rating 250 A Long delay settings Ir 207 A Tr 16 s Short delay settings Isd current 2070 A Tsd 0 s Instantaneous tripping Ii current 3000 A
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
NA Discrimination can't be determinated : no upstream Lv Breaker
Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 206.499 206.499 148.235 58.3
Page 9/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 206.499 206.499 148.235 58.3 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 2.192 0.192
UL1L2 (%) 2.222 0.222
UL2L3 (%) 2.222 0.222
UL3L1 (%) 2.222 0.222
UL1N (%) 2.192 0.192
UL2N (%) 2.192 0.192
UL3N (%) 2.192 0.192
Page 10/61
Project: dejan_pejovski_final 27/05/2015
3.2 Lighting load circuits
3.2.1 Circuit Load 11
Circuit breaker QA 11 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 11 Parameters Length 50 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 11 has been
Page 11/61
Project: dejan_pejovski_final 27/05/2015
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 11 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Page 12/61
Project: dejan_pejovski_final 27/05/2015
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 4.087 1.895
UL1L2 (%) 4.410 2.188
UL2L3 (%) 4.045 1.824
UL3L1 (%) 4.045 1.824
UL1N (%) 4.719 2.527
UL2N (%) 4.719 2.527
UL3N (%) 4.087 1.895
Synthesis for all operating mode
U3L (%) 4.087
UL1L2 (%) 4.410
UL2L3 (%) 4.045
UL3L1 (%) 4.045
UL1N (%) 4.719
UL2N (%) 4.719
UL3N (%) 4.087
Page 13/61
Project: dejan_pejovski_final 27/05/2015
3.2.2 Circuit Load 14
Circuit breaker QA 14 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 14 Parameters Length 40 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 14 has been
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1
Page 14/61
Project: dejan_pejovski_final 27/05/2015
Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.30 0.18 0.18 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.30 0.18 0.18 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 14 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Page 15/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.708 1.516
UL1L2 (%) 3.972 1.751
UL2L3 (%) 3.681 1.459
UL3L1 (%) 3.681 1.459
UL1N (%) 4.214 2.021
UL2N (%) 4.214 2.021
UL3N (%) 3.708 1.516
Synthesis for all operating mode
U3L (%) 3.708
UL1L2 (%) 3.972
UL2L3 (%) 3.681
UL3L1 (%) 3.681
UL1N (%) 4.214
UL2N (%) 4.214
UL3N (%) 3.708
Page 16/61
Project: dejan_pejovski_final 27/05/2015
3.2.3 Circuit Load 13
Circuit breaker QA 13 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 13 Parameters Length 45 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 13 has been
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1
Page 17/61
Project: dejan_pejovski_final 27/05/2015
Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 13 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Page 18/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.898 1.706
UL1L2 (%) 4.191 1.969
UL2L3 (%) 3.863 1.641
UL3L1 (%) 3.863 1.641
UL1N (%) 4.466 2.274
UL2N (%) 4.466 2.274
UL3N (%) 3.898 1.706
Synthesis for all operating mode
U3L (%) 3.898
UL1L2 (%) 4.191
UL2L3 (%) 3.863
UL3L1 (%) 3.863
UL1N (%) 4.466
UL2N (%) 4.466
UL3N (%) 3.898
Page 19/61
Project: dejan_pejovski_final 27/05/2015
3.2.4 Circuit Load 12
Circuit breaker QA 12 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 12 Parameters Length 50 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 12 has been
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1
Page 20/61
Project: dejan_pejovski_final 27/05/2015
Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 12 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Page 21/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 4.087 1.895
UL1L2 (%) 4.410 2.188
UL2L3 (%) 4.045 1.824
UL3L1 (%) 4.045 1.824
UL1N (%) 4.719 2.527
UL2N (%) 4.719 2.527
UL3N (%) 4.087 1.895
Synthesis for all operating mode
U3L (%) 4.087
UL1L2 (%) 4.410
UL2L3 (%) 4.045
UL3L1 (%) 4.045
UL1N (%) 4.719
UL2N (%) 4.719
UL3N (%) 4.087
Page 22/61
Project: dejan_pejovski_final 27/05/2015
3.2.5 Circuit Load 15
Circuit breaker QA 15 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 15 Parameters Length 45 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 15 has been
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1
Page 23/61
Project: dejan_pejovski_final 27/05/2015
Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.27 0.16 0.16 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 15 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Page 24/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.898 1.706
UL1L2 (%) 4.191 1.969
UL2L3 (%) 3.863 1.641
UL3L1 (%) 3.863 1.641
UL1N (%) 4.466 2.274
UL2N (%) 4.466 2.274
UL3N (%) 3.898 1.706
Synthesis for all operating mode
U3L (%) 3.898
UL1L2 (%) 4.191
UL2L3 (%) 3.863
UL3L1 (%) 3.863
UL1N (%) 4.466
UL2N (%) 4.466
UL3N (%) 3.898
Page 25/61
Project: dejan_pejovski_final 27/05/2015
3.2.6 Circuit Load 16
Circuit breaker QA 16 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 16 Parameters Length 50 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 16 has been
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1
Page 26/61
Project: dejan_pejovski_final 27/05/2015
Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 16 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 8 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Page 27/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 4.087 1.895
UL1L2 (%) 4.410 2.188
UL2L3 (%) 4.045 1.824
UL3L1 (%) 4.045 1.824
UL1N (%) 4.719 2.527
UL2N (%) 4.719 2.527
UL3N (%) 4.087 1.895
Synthesis for all operating mode
U3L (%) 4.087
UL1L2 (%) 4.410
UL2L3 (%) 4.045
UL3L1 (%) 4.045
UL1N (%) 4.719
UL2N (%) 4.719
UL3N (%) 4.087
Page 28/61
Project: dejan_pejovski_final 27/05/2015
3.2.7 Circuit Load 17
Circuit breaker QA 17 Ib 5.95 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 6 A Breaking capacity 20 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 6 A Long delay settings Ir 6 A Tr NA Short delay settings Isd current 48 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 17 Parameters Length 50 m Max length 246 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 6 A Sizing constraint Voltage drop Sizing Information The CSA of cable WD 17 has been
increased from 1.5 to 2.5 to comply with the voltage drop in the circuit.Sized with Ir
Correction factors Temperature factor 1
Page 29/61
Project: dejan_pejovski_final 27/05/2015
Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected neutral Cross section area 1x2.5 mm Core Copper Iz under real conditions 25 A Selected PE Cross section area 1x2.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge EA 17 U 230 V S 2.37 kVA P 2 kW I 5.95 A
cos 0.95
Ku (Normal) 1 Number of circuit 1 Polarity 3Ph+N Phase connection Type of luminaries Fluorescent with electronic ballast Nb of luminaries 8 Nb of lights/luminaries 4 Lights power 58 W Ballast power 4.5 W Ia 5.95 A Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 5.945 5.945 3.964 1.98
Page 30/61
Project: dejan_pejovski_final 27/05/2015
Synthesis for all operating mode (A) 5.945 5.945 3.964 1.98 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 4.087 1.895
UL1L2 (%) 4.410 2.188
UL2L3 (%) 4.045 1.824
UL3L1 (%) 4.045 1.824
UL1N (%) 4.719 2.527
UL2N (%) 4.719 2.527
UL3N (%) 4.087 1.895
Synthesis for all operating mode
U3L (%) 4.087
UL1L2 (%) 4.410
UL2L3 (%) 4.045
UL3L1 (%) 4.045
UL1N (%) 4.719
UL2N (%) 4.719
UL3N (%) 4.087
Page 31/61
Project: dejan_pejovski_final 27/05/2015
3.3 Power socket load circuits
3.3.1 Circuit Load 1
Circuit breaker QA 1 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 1 Parameters Length 50 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors
Page 32/61
Project: dejan_pejovski_final 27/05/2015
Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16 Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 1 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Page 33/61
Project: dejan_pejovski_final 27/05/2015
Operating mode Normal
U3L (%) 3.594 1.402
UL1L2 (%) 3.841 1.619
UL2L3 (%) 3.841 1.619
UL3L1 (%) 3.841 1.619
UL1N (%) 3.594 1.402
UL2N (%) 3.594 1.402
UL3N (%) 3.594 1.402
Synthesis for all operating mode
U3L (%) 3.594
UL1L2 (%) 3.841
UL2L3 (%) 3.841
UL3L1 (%) 3.841
UL1N (%) 3.594
UL2N (%) 3.594
UL3N (%) 3.594
Page 34/61
Project: dejan_pejovski_final 27/05/2015
3.3.2 Circuit Load 2
Circuit breaker QA 2 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 2 Parameters Length 50 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 35/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.15 0.08 0.08 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 2 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.594 1.402
UL1L2 (%) 3.841 1.619
Page 36/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 3.841 1.619
UL3L1 (%) 3.841 1.619
UL1N (%) 3.594 1.402
UL2N (%) 3.594 1.402
UL3N (%) 3.594 1.402
Synthesis for all operating mode
U3L (%) 3.594
UL1L2 (%) 3.841
UL2L3 (%) 3.841
UL3L1 (%) 3.841
UL1N (%) 3.594
UL2N (%) 3.594
UL3N (%) 3.594
Page 37/61
Project: dejan_pejovski_final 27/05/2015
3.3.3 Circuit Load 3
Circuit breaker QA 3 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 3 Parameters Length 40 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 38/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 3 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.314 1.122
UL1L2 (%) 3.517 1.295
Page 39/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 3.517 1.295
UL3L1 (%) 3.517 1.295
UL1N (%) 3.314 1.122
UL2N (%) 3.314 1.122
UL3N (%) 3.314 1.122
Synthesis for all operating mode
U3L (%) 3.314
UL1L2 (%) 3.517
UL2L3 (%) 3.517
UL3L1 (%) 3.517
UL1N (%) 3.314
UL2N (%) 3.314
UL3N (%) 3.314
Page 40/61
Project: dejan_pejovski_final 27/05/2015
3.3.4 Circuit Load 4
Circuit breaker QA 4 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 4 Parameters Length 40 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 41/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.18 0.11 0.11 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 4 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.314 1.122
UL1L2 (%) 3.517 1.295
Page 42/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 3.517 1.295
UL3L1 (%) 3.517 1.295
UL1N (%) 3.314 1.122
UL2N (%) 3.314 1.122
UL3N (%) 3.314 1.122
Synthesis for all operating mode
U3L (%) 3.314
UL1L2 (%) 3.517
UL2L3 (%) 3.517
UL3L1 (%) 3.517
UL1N (%) 3.314
UL2N (%) 3.314
UL3N (%) 3.314
Page 43/61
Project: dejan_pejovski_final 27/05/2015
3.3.5 Circuit Load 5
Circuit breaker QA 5 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 5 Parameters Length 30 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 44/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 5 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.033 0.841
UL1L2 (%) 3.193 0.971
Page 45/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 3.193 0.971
UL3L1 (%) 3.193 0.971
UL1N (%) 3.033 0.841
UL2N (%) 3.033 0.841
UL3N (%) 3.033 0.841
Synthesis for all operating mode
U3L (%) 3.033
UL1L2 (%) 3.193
UL2L3 (%) 3.193
UL3L1 (%) 3.193
UL1N (%) 3.033
UL2N (%) 3.033
UL3N (%) 3.033
Page 46/61
Project: dejan_pejovski_final 27/05/2015
3.3.6 Circuit Load 6
Circuit breaker QA 6 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 6 Parameters Length 30 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 47/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.24 0.14 0.14 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 6 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.033 0.841
UL1L2 (%) 3.193 0.971
Page 48/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 3.193 0.971
UL3L1 (%) 3.193 0.971
UL1N (%) 3.033 0.841
UL2N (%) 3.033 0.841
UL3N (%) 3.033 0.841
Synthesis for all operating mode
U3L (%) 3.033
UL1L2 (%) 3.193
UL2L3 (%) 3.193
UL3L1 (%) 3.193
UL1N (%) 3.033
UL2N (%) 3.033
UL3N (%) 3.033
Page 49/61
Project: dejan_pejovski_final 27/05/2015
3.3.7 Circuit Load 7
Circuit breaker QA 7 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 7 Parameters Length 20 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 50/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 7 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 2.753 0.561
UL1L2 (%) 2.869 0.648
Page 51/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 2.869 0.648
UL3L1 (%) 2.869 0.648
UL1N (%) 2.753 0.561
UL2N (%) 2.753 0.561
UL3N (%) 2.753 0.561
Synthesis for all operating mode
U3L (%) 2.753
UL1L2 (%) 2.869
UL2L3 (%) 2.869
UL3L1 (%) 2.869
UL1N (%) 2.753
UL2N (%) 2.753
UL3N (%) 2.753
Page 52/61
Project: dejan_pejovski_final 27/05/2015
3.3.8 Circuit Load 8
Circuit breaker QA 8 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 8 Parameters Length 20 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 53/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.36 0.21 0.21 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 8 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 2.753 0.561
UL1L2 (%) 2.869 0.648
Page 54/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 2.869 0.648
UL3L1 (%) 2.869 0.648
UL1N (%) 2.753 0.561
UL2N (%) 2.753 0.561
UL3N (%) 2.753 0.561
Synthesis for all operating mode
U3L (%) 2.753
UL1L2 (%) 2.869
UL2L3 (%) 2.869
UL3L1 (%) 2.869
UL1N (%) 2.753
UL2N (%) 2.753
UL3N (%) 2.753
Page 55/61
Project: dejan_pejovski_final 27/05/2015
3.3.9 Circuit Load 9
Circuit breaker QA 9 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 9 Parameters Length 60 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 56/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 9 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.875 1.683
UL1L2 (%) 4.165 1.943
Page 57/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 4.165 1.943
UL3L1 (%) 4.165 1.943
UL1N (%) 3.875 1.683
UL2N (%) 3.875 1.683
UL3N (%) 3.875 1.683
Synthesis for all operating mode
U3L (%) 3.875
UL1L2 (%) 4.165
UL2L3 (%) 4.165
UL3L1 (%) 4.165
UL1N (%) 3.875
UL2N (%) 3.875
UL3N (%) 3.875
Page 58/61
Project: dejan_pejovski_final 27/05/2015
3.3.10 Circuit Load 10
Circuit breaker QA 10 Ib 2.64 A
Distance from origin NA Sizing Information Sized by system Range Acti9 iC60 Designation iC60N Circuit breaker rating 3 A Breaking capacity 50 kA TNS One pole breaking capacity NA IT One pole breaking capacity NA Reinforced breaking capacity NA Pole & protected pole 4P4d Trip unit designation C Trip unit rating 3 A Long delay settings Ir 3 A Tr NA Short delay settings Isd current 24 A Tsd NA Instantaneous tripping Ii current NA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0 NSX250B Micrologic 5.2 A 250 A / 4P4d
Full Discrimination
Cable WD 10 Parameters Length 60 m Max length 148 m Installation method 31
E Multi-core cables on horizontal perforated tray
Type of cable Multi-core Nb of additional touching circuits 0 Insulation PVC Ambient temperature 30 C Level of third harmonic THDI 0 % Ib 3 A Sizing constraint Iz Sizing Information Sized with Ir Correction factors Temperature factor 1 Standard table reference A-52-14 Soil thermal resistivity factor 1 Standard table reference A-52-16
Page 59/61
Project: dejan_pejovski_final 27/05/2015
Loaded neutral factor 1 Standard table reference D-52-1 Touching conductor factor 1 Standard table reference A-52-20 User correction factor 1 Overall factor 1
Selected phase Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected neutral Cross section area 1x1.5 mm Core Copper Iz under real conditions 18.5 A Selected PE Cross section area 1x1.5 mm Core Copper
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 0.12 0.07 0.07 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility. Charge AA 10 U 230 V S 1.05 kVA P 1 kW I 2.64 A
cos 0.95
Polarity 3Ph+N Phase connection Number of circuit 2 Ku (Normal) 1 Harmonic generator No THDI3 0 Sensitivity to over voltage NA Design current IL1 IL2 IL3 IN
Operating mode Normal (A) 2.642 2.642 2.642 0
Synthesis for all operating mode (A) 2.642 2.642 2.642 0 Voltage drop Cumulated from upstream Circuit
Operating mode Normal
U3L (%) 3.875 1.683
UL1L2 (%) 4.165 1.943
Page 60/61
Project: dejan_pejovski_final 27/05/2015
UL2L3 (%) 4.165 1.943
UL3L1 (%) 4.165 1.943
UL1N (%) 3.875 1.683
UL2N (%) 3.875 1.683
UL3N (%) 3.875 1.683
Synthesis for all operating mode
U3L (%) 3.875
UL1L2 (%) 4.165
UL2L3 (%) 4.165
UL3L1 (%) 4.165
UL1N (%) 3.875
UL2N (%) 3.875
UL3N (%) 3.875
Page 61/61
Project: dejan_pejovski_final 27/05/2015
3.4 Busbar circuits
3.4.1 Circuit WC 1
Busbar WC 1 Parameters Switchboard Name UC 2 Switchboard Range No preference Rating (A) 0 IP Undefined Feeder Circuit name Protection name Protection type
Load 1 QA 1 iC60N
Load 2 QA 2 iC60N
Load 3 QA 3 iC60N
Load 4 QA 4 iC60N
Load 5 QA 5 iC60N
Load 6 QA 6 iC60N
Load 7 QA 7 iC60N
Load 8 QA 8 iC60N
Load 9 QA 9 iC60N
Load 10 QA 10 iC60N
Load 11 QA 11 iC60N
Load 14 QA 14 iC60N
Load 13 QA 13 iC60N
Load 12 QA 12 iC60N
Load 15 QA 15 iC60N
Load 16 QA 16 iC60N
Load 17 QA 17 iC60N
Short circuit current Ik3max Ik2max Ik1max Ik2min Ik1min Ief Ief2min
Operating mode Normal (kA) 18.22 15.78 8.50 13.49 7.27 8.58 0.00
Synthesis for all operating mode (kA) 18.22 15.78 8.50 13.49 7.27 8.58 0.00
Calculation results in accordance with CENELEC technical report TR50480. All assumptions and device choices are the user's responsibility.