32
 21, rue d’Artois, F-75008 PARIS A1-107 CIGRE 2008 http : //www.cigre.org EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES. A. Tabernero * , B. Batlle, LM. López, A. Villarubia, S.Rodriguez, O. Martínez IBERDROLA & unitronics electric SPAIN SUMMARY The aim of this technical work is to introduce a reliable technique for predictive maintenance of rotating machines stator insulation, the EDA test. This test, ruled through different IEEE and CEI standards, has been successfully used by Iberdrola since the middle of the 80’s, proving its reliability thanks to more than 5,000 test performed in about 400 machines (120 hydrogenerators, 30 turbogenerators and about 280 MV motors). The EDA test consists in a set of different measurements performed in just one test (%H, ºC, AC & DC Capacitance, two step voltage charge & discharge). It offers several reliable parameters with a correlation between them, and an easy information management to follow up their evolution. This test allows detecting preliminary degradation in dielectric that can be solved on time, saving the machine * [email protected] 1

EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

Embed Size (px)

Citation preview

Page 1: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 1/32

 21, rue d’Artois, F-75008 PARIS A1-107  CIGRE 2008

http : //www.cigre.org

EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT

ROTATING MACHINES.

A. Tabernero*, B. Batlle, LM. López, A. Villarubia, S.Rodriguez, O. Martínez

IBERDROLA & unitronics electric

SPAIN

SUMMARY 

The aim of this technical work is to introduce a reliable technique for predictive maintenance of rotating machines stator insulation, the EDA test. This test, ruled through different IEEE and CEIstandards, has been successfully used by Iberdrola since the middle of the 80’s, proving its reliabilitythanks to more than 5,000 test performed in about 400 machines (120 hydrogenerators, 30turbogenerators and about 280 MV motors).

The EDA test consists in a set of different measurements performed in just one test (%H, ºC, AC &DC Capacitance, two step voltage charge & discharge). It offers several reliable parameters with acorrelation between them, and an easy information management to follow up their evolution. This testallows detecting preliminary degradation in dielectric that can be solved on time, saving the machine

* [email protected]

1

Page 2: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 2/32

from premature faults and regaining it to service, some times with low cost maintenance.

The EDA test is an easy to perform process that allowed Iberdrola defining it as the first level of theelectrical maintenance policy.

 Nowadays Iberdrola owns 41.001 MW  of power installed in Spain, Latin-America and UnitedKingdom (Scottish Power), corresponding to different generation technologies. In Spain, the 26.509MW of power installed are distributed as:

  Hydraulic: 8.842 MW  Thermal Coal: 1.253 MW  Thermal Gas-Fuel: 2.889 MW   Nuclear: 3.344 MW  Wind & Mini-Hydraulic: 4.977 MW  Combined Cycle: 4.800 MW  Co-generation: 404 MW

In terms of production centers it means:

  One nuclear power plant owned 100% and different percentages in another 5 plants  3 coal fired power plants  4 fuel-oil & gas fired power plants  9 combined-cycle power plants  80 large and 93 small hydro-power plants  The first company in the world about wind-generation power installed with more than

3.800 MW

In terms of relevant machines it means:

  29 turbo generators from 148 to 514 MW, cooled by H2 and air   1 turbo of about 1.000MW water cooled  156 large hydrogenerators, 33 of them with more than 100MW

In order to manage the predictive maintenance of these number of machines, the EDA test has beenestablished as the first level of electrical maintenance policy. That means it can be performed once ayear or every two years by the plant technicians, without need of a specialized test engineer. This testgives information about the general state of the insulation and indicates the risk of more critical

 problems that will be confirmed with a second instance test or visual inspections.

The easy test process and its traceability, where the results of the test are not affected by the operator,make EDA an excellent tool for trending.

Iberdrola defines the following types of predictive inspections of rotating machines. They depend of its aim and situation. There, EDA is considered as the main routine test for all rotating machines:Hydrogenerators, Turbogenerators and MV Motors.

2

Page 3: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 3/32

 

A Basic or first level inspection inside of Maintenance program. Routine tests.EDA On-Line Partial Discharge

B Specific or second level inspection inside of Maintenance program. Special or type tests.Internal Visual Inspection Stator Windings

Power Factor Off-Line Partial Discharge

Winding ResistanceSurge Test (If multiturn coils)

Generators Rotor Windings

Insulation Resistance andPolarization Index

Winding ResistanceImpedanceSurge Test

RSO

C

After repair (cleaning or rewinding) or first test on new machines / intensive inspection whenthe rotor is disassembled. Intensive Tests. These inspections on regular bases are only performedin Generators. In motors, these kinds of tests are only carried out during repair or faultinvestigation.

Stator Windings

TVA Test.Core tests

EL CIDWedge Tap Test.

The periodic bases of these inspections will depend of machine characteristics, running hours,operation characteristics, machine importance for operation, machine status, if there is redundancy,etc. Anyway, as a general basis, following periodicity is established for Turbo generators, Large hydroand MV motors, in years:

YEARSTURBO HYDRO MOTOR 

MACHINE

INSPECTION A B C A B C A B<20 2 2 6 2 4 12 2 10

20…40 1 1 5 1 3 9 1 5Age

(years)>40 1 1 5 1 2 6

As you can appreciate, in order to reduce assembling and disassembling works and time consumption,as well as have bigger information as possible in each inspection, type A is always performed at thesame time that B and A+B when inspection type C is carried out.

In this paper we present the results of a technical work performed only in a wide group of motors. Thissample is chosen because of the large amount of motors available in any thermal production center. Insuch locations there are a lot of machines with similar characteristics and similar working conditions(load, contamination, running hours… ) making the study more uniform.

KEYWORDS

EDA - Predictive Maintenance - Insulation testing - Stator insulation – Electrical insulation

3

Page 4: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 4/32

 1.-  TEST DESCRIPTION

It is an off-line, DC test that obtains information concerning overall status of the insulation. It consistsfirst in the measure and comparison of the capacitance of the insulation submitted at low AC and DCvoltage, and second in the analysis of the current through the insulation during two charge anddischarge cycles performed at two different test voltages. In this case, the behavior should be linear when the machine status is good. If this is not the case, we have an indication of degradation.

EDA test is a non destructive DC voltage Test. The test consists in the following sequence of dataacquiring:

•  Environmental Data acquisition: Ambient temperature and moisture is obtained. Thiswill be part of the report. If the machine was switched off long enough, this temperaturecould be used to compensate the parameters read. Moisture is used to have a usefulindication of ambient conditions when the test was performed, both for air cooledmachines and to know if measurement instrumentation performance is exceeded.

•  Capacitances measurement: The system performs insulation capacitance measurementat low voltage and at two frequencies: DC and 1KHz AC.  

•  First Test Voltage: System switches DC test voltage to the insulation while 30 minutes.Currents are plotted and recorded meanwhile to determine several parameters. At the end

of the 30 minutes, the system performs a 2 minutes discharge period.

4

Page 5: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 5/32

 

•  Second Test Voltage: After complete discharge of the insulation from 1st test voltage, asecond test voltage with a value above the 1 st is applied to the machine. The procedure isthe same. This step is made to check for possible problems in insulation at a high voltageand second to check about linearity of insulation with voltage.

•  Diagnosis: The diagnosis management works in two steps: First and as reference of initial values, an electrical engineer performs and EDA test during machinecommissioning or after any refurbishment, stating so that the reference values are thoseof health insulation. After that and during routine maintenance, once finished the test, theinspector can immediately check the numeric values of all the parameters and their comparison with previous test done and the initial reference values and have so that a

 punctual view of the status of the machine insulation. 

5

Page 6: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 6/32

 

•  Trending: Predictive maintenance techniques need of trending data that can help usdecide about last parameter’s evolution and indicate the future tendency. With this data,inspectors can decide about future maintenance actions on the machine…

From the test, we obtain and we study several parameters (based on IEEE and CEI standards) thatallow us determining the condition of the insulation. One of the aims of this method is the diagnostichas to be based in more than just one parameter, because of the importance of the decision of takingout of service a machine.

6

Page 7: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 7/32

 

2.-  TEST PARAMETERS AND INTERPRETATION

EDA system offers a group of parameters that when analyzed together give a very good approach of 

insulation status. Now we indicate each parameter, what does the parameter indicate and how itchanges because of different problems with a simple explanation.

The main parameters we analyze are:

•  Capacitance Ratio (CR). This is the ratio between DC and AC (1KHz) capacitances.This ratio allows detect contamination and moisture problems.

  Contamination: Contamination extends all over the windings in the end-windingarea. This contamination extends the plates of the equivalent geometric capacitor formed between the phases and the magnetic core. This extension is measured inDC, but in AC part of the capacitance is neglected due to the effect of the inductanceof the coils, so the bigger the difference, or the greater CR, the greater thecontamination degree.

  Moisture: When moisture is in the surface of the insulation, the effect is similar tocontamination. If moisture is inside the insulation, then it is the dielectric constant of the insulation that changes from the value in dry insulation increasing capacitances.

  Aging: The insulation may degrade simply by the pass of time or by another accelerated process usually due to thermal aging. In both situations, componentsinside the insulation volatilize and the space is filled by air or another gases. In thiscondition, the effective distance between layers of the capacitor decrease, and alsothe effective dielectric constant of the equivalent capacitor decrease. Both situationslead to a low but noticeable annual decrease of the machine capacitances that can beeasily detected with data trending.

•  Absorption Index (AI). It is a ratio between the currents after 30 and 60 secondssubtracting the leakage current while the 30 minutes charge cycle. It indicates if a

 problem is internal (low values) or external (high values) to the dielectric. It is based inchanges of the groundwall insulation homogeneity due to the presence of contaminantscoming from the outside: moisture, oil or others ingresses flowing into the dielectric.

7

Page 8: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 8/32

This behavior can be appreciated again from figure 7 because: Cg gets charged beforethe 30 seconds and in 30 minutes leakage current is most contributed from Ri, so Riinfluence is neglected. What remains?, only the effect of the equivalents Ra/Ca andCwx., If the plot of the current gives a defined corner slope it gives high AI valuesindicating external contamination, if the slope is slow it means that the insulation has

 problems in the Ra/Ca component indicating through low AI values internal problems.

•  Reabsorption Current (RC). After 30 minutes, the insulation is considered fullycharged. Then a short-circuit is made and flows the Re-turned absorption current thatwas acquired while the absorption period but this time without the influence of the other currents. The value is taken after one minute of the discharge cycle. If there is a bigger heterogeneity inside the dielectric (water, vapor, oil, dust…), it has more areas to storeenergy as polarized dipoles, leading to bigger repolarization currents. From previoustests, if RC goes up, it is possibly due to the degradation of the insulation (delamination,increase of voids, etc). It’s possible to detect uncured resin if we compare this parameter with test results from similar machines.

•  Time Constant (TC). It is the product of an Insulation Resistance (IR) value and the ACCapacitance. New machines must show high initial values because of the high IR expected initial values. In a normal life and degradation, both IR and CAC decrease, sothroughout the life of the machine TC descends slightly. Therefore, if the value fallsfaster than expected, it indicates a faster aging, and so an abnormal degradation. Itconfirms contamination or delamination problems, depending of the case. It must betemperature normalized.

•  Leakage Current Ratio (LCR). It’s the ratio between the leakage current (current after the 30 minutes of charge process) measured at the first voltage and at the second voltage.The result is made comparable through the voltage ratio between the two processes. Theideal value is 1,0: This value would mean that the insulation behavior is linear with

voltage. If the value is far from the ideal value, it should confirm a problem detectedwith the other parameters.

•  Insulation Resistance (IR). Every machine should be above a minimum value,depending on the machine voltage. The decrement of this value indicates insulationcontamination or degradation. After external cleaning it should increase noticeably. Ascan be seen in figure 7, Ri is made up from surface resistance influenced bycontamination and internal resistance that includes internal insulation contamination and

 possible aging. It requires temperature correction.

•  Polarization Index (PI). It indicates together with IR different problems likecontamination and moisture absorption. If PI tendency is going down from previoustests, the machine has one of the described problems. Otherwise, if PI increases inexcess, it can indicate brittle insulation in some older types of insulation.

8

Page 9: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 9/32

 3.-  SECOND INSTANCE STATOR INSULATION TEST TECHNIQUES

When EDA test gives evidences of one or more insulation problem, it’s the time to confirm this issuewith 2nd instance techniques, before taking the decision of opening the machine. These techniquesusually need more expensive or complex equipment and needs better trained people not just for thetesting but for the interpretation of the results as well, so they are only performed when the firstinstance tests recommends a deeper study. These techniques are also non destructive tests and could

 be:

•  Internal Visual Inspection. The scope of this inspection will depend on theaccessibility to the winding of the machine, performed by expert personnel. This will bethe most valuable tool to detect the effects of the different degradation mechanisms,especially if those happen in the end-winding area.

•  Power factor or Dissipation factor (tan δ) and tip-up. Tan delta gives a globalindication of losses in the dielectric and can give a clue of the thermal aging status of the

machine. Also, this test could give information about end-winding area with UST TestTechniques.

•  Capacitance and capacitance tip-up. High voltage capacitance deduced from tan δ testalso gives clear indication of changes in the insulation system. It monitors moisture andother abnormal conditions. The tip-up indicates how changes the equivalent capacitancewith voltage, this says us how changes the amount of PD (Partial Discharges) voidsactivated by voltage increase. It also monitors moisture ingress and delamination.

•  Partial discharge analysis. Monitors degradation of the insulation system. It can be onor off-line. It can also give an indication of the possible location of the discharges insidethe dielectric (next to the coil, in the groundwall or in the interface to the core).

•  TVA probe. TVA Probe testing (Tennessee Valley Authority Probe) allows physicallocation of the partial discharge activity, mainly if it is a slot discharge problem.

•  Surge Test. It is intended to test turn-to-turn insulation in form-wound multiturn coils.

•  Hi-pot. It is a destructive test that should be performed with extreme caution. It must beevaluated the convenience of the performance of this test.

9

Page 10: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 10/32

 

4.-  TEST DESCRIPTION

Here we present a study of some real cases to show how the value and the trends of these parameters are reliable and help to detect evolving problems in several situations. The cases aretaken from Iberdrola testing files and describe problem detection through different EDA testresults and how the described 2nd instance techniques confirm the problems.

  Base information about the sample and study follows in the table:

Description of the study: Sample, machine data, how tests are performed and diagnosed.

Ages:1,8,26,40,42Tests from: 7 years2001…2007

Machines: 33 Motors named:[00]…[32] Mean age:37,3

Test population is located in a Thermal Power Plant. It is an IBERDROLA utility producing around 580MW.

Conditions: Next to the sea (moisture & salt), next to industrial area, fuel central.

Sample

Contaminants: Dust, moisture from ambient or leaks and oil from bearings.Machines Voltage: 4,16kV Power:0,1…3,68MVA Insulation: Epoxi-

MicaPerformed: 204 Validated: 181 (~89%) Tester: EDAIII30min charge (usual: 1500/ 3000V), 2 min discharge

Low voltage DC / AC (1KHz)capacitances

% moisture,ambient andmachine ºC

Tests

Performed at two voltages in order to check insulation linearity with voltage.Diagnosis is taken from the maintenance records of the real status of the machine atthe date of each test.

OK,Operable:43

SurfaceContam.: 24 Internal Degradation: 107 InternalContamination: 07Diagnosisof Tests

Parameters for diagnosis are taken from High voltage results, so that any kind of  problem will be hardly marked because of the bigger electric field stress.

  All test performed were validated before being processed. Test system (EDAIII) is intended toeliminate most of human error, but apart from this, many test were invalidated because of veryhigh moisture in ambient or machine. This could cause moisture deposit in machine’s surface,most of failed tests were repeated after the machine was dried and results changed to normalvalues.

  After validation, and although more complex intermediate results could be defined, for thisstudy, tests diagnosis are only classified in four categories, the most usual in the testenvironment and corresponding to the records on machine maintenance history:

[1]  Healthy machines, suitable for operation. The insulation is in good condition, thereis no serious contamination level. If the unit is old (>30years), the degradation degreeis according to normal aging and doesn’t show symptoms of accelerated or abnormalthermal aging.

[2]  Surface contamination problems. Due to dust, insects, oil or simply moisture or alsoto a combination of several of these factors. If nothing was done, it could lead toelectrical tracking and contamination ingress in the insulation decreasing its usefullife. It is most of the times easily reversible with cleaning & drying works.

10

Page 11: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 11/32

 [3]  Internal  degradation problems. Usually due to thermal aging. It is irreversible and

makes necessary a more intensive trending up to the rewinding of the machine beneeded. Insulation exceeds usual aging values; it is losing its properties and cansupport less stress. The machine is subject to a greater probability of failure in service.

[4]  Internal  contamination problems. This situation is not very usual in epoxyinsulation, but sometimes and due to cracks or fissures in insulation, delamination andingress of moisture, dirty or oil can also flow inside the coil insulation. It is most of the times hardly to reverse.

  It is obvious that some machines can have (normally) more than one problem at a time. For this study, only one problem is allowed in each diagnose, the usual preference is: First  Health machines, Contaminated  &  Degraded  as the last. Take note that both contaminations canchange  Degraded values and change  Degradation diagnosis, so the user should first try tosolve this easy to reverse problems in Contaminated machines before evaluating other hardlyto solve problems related to  Degradation. It is also logic that most of the times that Internal

Contamination happens; it will also show External Contamination traces.  The last step of the investigation was to execute histograms for the different test parameters

under study: For each parameter, the first histogram presents data distribution from lowvoltage / high voltage test. The second histogram presents data classification for this four diagnosis categories.

5.-  TEST CONCLUSIONS

After the investigation of each parameter, their relationship with their different degradationmechanism and correlation between the parameters, here are the conclusions that could be extracted.

For each problem mode not all the results answer always in the limited ranges, a few tests show valuesout of range that should be further investigated. Some values are given as an approximation andanother with no relevant influence are marked as [??], and the units of each parameter are: CR [%],AI[Dimensionless], RC[mA/FV], TC[seconds], LCR [Dimensionless], IR [GΩ@20ºC],PI[Dimensionless].

  Machine in correct conditions.

•  Punctual Data: Good values for machines in good conditions are: CR[<10%],AI[>1,56], RC[>5,0], TC[>300], LCR[0,9…1,2], IR[>1], PI[>2]. 

•  Trending data: Correct machines don’t show large evolution changes in any parameters.If the machine is in a good aging status, CAC shouldn’t increase and have a decreaserhythm below 1% / year. For the machine not to show contamination signs, CDC shouldnot go 10% above CAC. 

  Surface contamination.

•  Punctual Data: The set of values that can monitor this condition are: CR[>10%],AI[>1,56], RC[??], TC[<400], LCR[<0,9 or >1,2], IR[<5], PI[<2,5]. If moisture is

 present the changes in parameters are more noticeable. •  Trending data: Machines with surface contamination will show increase in CR values.

Watching tendency CR will show an increase coming from an increase of  CDC with nonoticeable change in CAC. If it also increases, CAC it means that some moisture can

have gone inside the insulation. 

11

Page 12: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 12/32

  Internal contamination.

•  Punctual Data: The parameters and values that give clues to monitor this problemwill be: CR[??] AI[<1,56], RC[??], TC[<400], LCR[<0,9 or >1,2], IR[<5], PI[<2,5]. 

•  Trending Data: CAC should only go down with aging. When contamination goesinside the insulation, C

ACwill go up because of the change of the dielectric constant,

the effect will be more pronounced when contamination goes with water. It is usualthat internal contamination goes together with surface contamination, so we shouldalso expect an increase of CDC in this situation. 

  Thermal Aging.

•  Punctual Data: The values that should be monitored to check this problem are:CR[??], AI[??], RC[>5], TC[<400], LCR[???], IR[??], PI[??]. It is relevant to say that

 both IR and PI don’t give any indication of this problem.•  Trending Data: Two relevant parameters indicate this effect: CAC : when it has an

decrease rhythm above 1% / year and RC when it has an increase rhythm above than

0,5+(0,2*year). The usual trend of TC is to keep at low values [<400] or decrease. 

12

Page 13: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 13/32

6.-  TEST RESULTS

As previously explained, the test is performed in a sample of motors in a thermal central. Now we present all the parameters subject to analysis. For each one an introductory table is presented, and after follows numerical results and each parameter conclusions.

PARAMETER: Acronym = IR Insulation Resistance

Units [G ] Formula

min1min1

 I 

V K  IR ⋅= [01]

K= Temperaturecompensation

V= Test voltage, named LowV & High V

I1min= Current measured after 1 minute in load period

Minimum: 0,202GΩ Mean: 3,689GΩ Maximum: 51,604GΩ  Recommended minimum values for operation or hipot from standard IEEE 43-2000 are…:

Minimum IR M  (40ºC) 

Test specimen Minimum IR tolerable fortested 4,16kV motors

IR 1min=(kV+1)MΩ  Most windings before 1970, all fieldwindings and others not described below

0,00516GΩ 

IR 1min=100MΩ  Most dc armature and ac windings after 1970 (form wound coils)

0,100GΩ ~0,500GΩ @ 20ºC

Insulation Resistance Histogram

0

2

4

6

8

10

12

14

16

18

0 0,2 0 ,4 0 ,6 0 ,8 1 1,2 1 ,4 1 ,6 1 ,8 2 2,2 2 ,4 2 ,6 2 ,8 3 3,2 3 ,4 3 ,6 3 ,8 4 4,2 4 ,4 4 ,6 4,8 5 5,2 5 ,4 5,6 5 ,8 6 7 8 9 10 20 30 40 51,6

Gohm (20ºC)

# Tests

Low V High V

 Figure 8: Histogram with IR values distribution of Tests performed.

The histogram with all valid samples indicates that almost all samples concentrate between 0,6GΩ and7GΩ. Note that to include most samples in the plot, it is presented with a no lineal step changeranging: 0,2Gohm step between [0…6GΩ], 1GΩ step between [6GΩ…10GΩ] and 10GΩ step

 between [10GΩ…50GΩ].

13

Page 14: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 14/32

Insulation Resistance Histogram

0

1

2

3

4

5

6

7

8

9

10

0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 3,2 3,4 3,6 3,8 4 4,2 4,4 4,6 4,8 5 5,2 5,4 5,6 5,8 6 7 8 9 10 20 30 40 51,6

Gohm (20ºC)

# Tests

O K ope rati on Sur fac e Contami nat ion Inte rnal De gr adati on Inte rnal Contami nati on

 Figure 9: Histogram with IR values related to Tests diagnosis distribution.

The histogram with diagnosis results indicates that:-  OK for operation tests are regularly spread [0,9GΩ…51GΩ].-  Surface Contamination ranges [0,4GΩ…4,4GΩ], most samples around 1GΩ.-  Internal Degradation are regularly spread [0,4G…20GΩ], most samples around 1,6GΩ.-  Internal Contamination ranges [0,8G…3,4GΩ], most samples around 0,9GΩ.

IR Conclusions: Insulation Resistance has been historically the minimum parameter used to diagnosea machine. It is most made up by conduction current (across the insulation) and leakage current(across the surface of the insulation). Both test collection and individual test help us overview thisconclusions:

-  The result depends too much of moisture. If the machine is in a high relative humidityenvironment and wasn’t properly maintained above ambient temperature, it can have moisturedeposit in the surface, driving IR to low values dangerous for service or for testing with other 2nd test techniques. If the machine has cracks, humidity could ingress into the insulationdecreasing even more the result. 

1,803

1,127

1,291

2,691

1,775

2,7052,7052,7052,705

1,451

1,111

0,722

2,828

1,387

2,4562,4562,4562,456

0

0,5

1

1,5

2

2,5

3

5/11/01 24/05/02 10/12/02 28/06/03 14/01/04 1/08/04 17/02/05 5/09/ 05 24/03/06 10/10/06 28/04/07 14/11/07

IR1

IR2

 Figure 10: Evolution of IR of machine [13]. It shows two dates of cleaning works, 2005 & 2007

both with moisture contamination.

14

Page 15: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 15/32

 

Figure 11: Photo of machine [13] before cleaning works in March, 05 of 2007 (see previous

figure).

-  For dry-good “OK operation” insulation status, the machine should be above 0,5GΩ at 20ºC.Different Machines show values from 0,9GΩ to 51GΩ depending on machine age, size,temperature, moisture and others.

-  Both “Surface contamination” and “Internal contamination” problems decrease IR valuesdown to 1GΩ area, but no minimum value to indicate this problems can be defined becausethere are also healthy machines with similar values. In order to discern these problems it isnecessary to correlate this data with Polarization Index. Also, trending data can be used to

detect this effect and check the efficiency of cleaning works.-  “Internal degradation” doesn’t necessary change much IR values except if there are

conduction paths inside the insulation, then values go down to 1GΩ area.-  Changes: IR decreases with temperature increase (so the data should be temperature

corrected), decreases with pollution, moisture (results can’t be corrected with moisture, butmoisture should be measured), oil or other contaminants either internal or external. After maintenance works like cleaning, drying, etc IR should increase again.

15

Page 16: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 16/32

 

PARAMETER: Acronym = PI Polarization Index

Units [Dimensionless] 

Formula

min1

min10

 IR

 IRPI = [02]

IR 10min= Current measured after 10 minutes in load period

IR 1min= Current measuredafter 1 minute in load Period

Minimum: 0,48 Mean: 3,298 Maximum: 6,6  Recommended minimum values for operation or hipot from standard IEEE 43-2000 are…:

Thermal class rating Minimum P.I. Minimum tolerable for

tested 4,16kV motors

Class A 1,5 Not the caseClass B, F & H 2,0 2,0

Polarization Index Histogram

0

2

4

6

8

10

12

14

16

0,1 0,4 0,7 1 1,3 1,6 1,9 2,2 2,5 2,8 3,1 3,4 3,7 4 4,3 4,6 4,9 5,2 5,5 5,8 6,1 6,4 6,7 7,1

Adimensional

# Tests

High_V Low_V

 Figure 12: Histogram with PI values distribution of Tests performed.

The histogram with all valid samples indicates that almost all samples concentrate between 2 and 5,with a mean around 3,6. The step is linear in all range of 0,1. 

16

Page 17: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 17/32

Polarization Index Histogram

0

1

2

3

4

5

6

7

8

9

0,1 0,4 0,7 1 1,3 1,6 1,9 2,2 2,5 2,8 3,1 3,4 3,7 4 4,3 4,6 4,9 5,2 5,5 5,8 6,1 6,4 6,7 7,1

Adimensional

# Tests

O K operation S urface Contamination Internal Degradation In ternal Contamination

 

Figure 13: Histogram with PI values related to Tests diagnostic distribution.

The histogram with diagnosis results indicates that:-  OK for operation ranges [2,1…6,6], most samples around 3,7.-  Surface Contamination ranges [1…3,5], most samples around 2.-  Internal Degradation spreads [0,5…5,5], most samples around 3,4.-  Internal Contamination spreads [0,8…3,1], most samples around 1,9.

PI Conclusions: Polarization Index has been historically the second parameter used to diagnose amachine. This parameter informs of the slope of the IR curve versus time: if plots keep increasingwith time, they give good PI, if plots remain flat with time because of the preponderance of leakage or conduction currents it give bad PI. This parameter has some details to take into account:

-  About “OK operation” values, they are always above 2 as standards indicate and go up tovalues up to 6,6.

-  Both “Surface Contamination” and “Internal Contamination” problems show values below 2,5 but three special cases in which exist surface or internal moisture that giveindications in another parameters but doesn’t decrease too much PI.

17

Page 18: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 18/32

 Figure 14: Evolution of PI of motor [13]: It shows clean works in 2005 and 2007.

-  For “Internal Degradation”, the results don’t necessary show values under 2. Even more,most of the values seem very good and around 3, so to estimate this problem this parameter isnot significant and should be used another parameter like Reabsorption Current.

-  Changes: PI has almost no change with temperature; it decreases with pollution, most of thetimes also with moisture, oil or other contaminants either internal or external. After 

maintenance cleaning, drying, etc PI should increase again.

18

Page 19: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 19/32

 

PARAMETER: Acronym = CR Capacitance Ratio

Units [Dimensionless, %] 

Formula

 DC 

 AC  DC 

C C CR −⋅= 100 [03]

Inside Formula

S  pF C  ε =)( [04]

CDC= Low voltage directcurrent capacitance

CAC= Low voltage alternatecurrent (1KHz) capacitance

Where C = [Pico Farads],ε=εr*ε0=8,854(pF/mm)* ε0 

ε0 aire=1, ε0 epoxi-mica=4, ε0 agua=80

S=area of one plate (mm2) d=distance between plates(mm)

CR Minimum: -5,25% CR Mean: 7,172% CR Maximum: 57,89% CDC Minimum: 19nF CDC Mean: 89,7nF CDC Maximum: 351nF 

CAC Minimum: 16nF CAC Mean: 83,1nF CAC Maximum: 332nF 

Capacitance Ratio

0

2

4

6

8

10

12

14

-5,25 0,5 1,25 2 2,75 3,5 4,25 5 5,75 6,5 7,25 8 8,75 9,5 11 14 17 20 23 26 29 32 35 38 41 44

Adimensional %

# Tests Low_V

 Figure 15: Histogram with CR values related to Tests performed.

The histogram with all valid samples shows some values around 0 (equal capacitances) and theremaining results range from 2 to 17 with a mean around 8. Step is of 0,25 up to 10 and of 1 up to 46.

19

Page 20: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 20/32

Capacitance Ratio

0

1

2

3

4

5

6

7

8

9

10

-5,25 0,5 1 ,25 2 2,75 3,5 4 ,25 5 5,75 6,5 7 ,25 8 8,75 9,5 11 14 17 20 23 26 29 32 35 38 41 44

Adimensional %

# Tests

OK ope rati on S urface Contami nati on Inte rnal Deg radati on Inter nal Contami nati on

 Figure 16: Histogram with CR values related to Tests diagnostic distribution.

The histogram with diagnosis results indicates that:-  OK for operation range [0…10], most samples around 3,7.-  Surface Contamination ranges [2…41], most samples around 11.-  Internal Degradation spreads [0…21], most samples around 5.-  Internal Contamination spreads [6…22], most samples around 8.

CR Conclusions: DC & AC capacitances, Capacitance Ratio and trending of them are good tools tohelp discern and confirm surface / internal contamination.

Figure 17: Diagram that explains CAC / CDC variations: LS & CS are the slot components, LE &

CE are the end-winding components and R E is the end-winding contamination effect.

The diagram in figure 17 explains why CAC and CDC measurements are performed. The capacitanceevaluated with the capacimeter is the geometric capacitance. With the aid of the DC & ACmeasurement options, we can discern some effects related with contamination. In general, CG (Geometric) can be expanded into this complex model including CS (slot component) and CE (endwinding component). In general, when external contamination appears, a layer deposit on the endwinding area extends the ground plate of CE capacitor (effect simulated in the figure as R E) increasingDC measured capacitance. When AC capacitance is taken, both LS and LE begin to open at testfrequency (standard 1KHz) and decrease the measurement of this capacitances.

-  The “OK operation” results show values of CR up to 10 (all range), so good machines arediscerned with the aid of PI>2. As can be seen from figure 17, any new machine will haveCDC > CAC because LS will also decrease CS (CR mean value in ok machines is ~4%). Abouttrending, the important is that although CDC >CAC, both shouldn’t change much in time as seen

20

Page 21: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 21/32

in the first 3 tests in Figure 18.-  For the problems “Surface Contamination” and “Internal Contamination”, it is necessary

to discern problematic machines with the aid of PI<2.-  “Surface Contamination”: From the explanation before, 1KHz measurement takes apart

contamination influence, so when CDC >> CAC (CR goes from 4% to above 10%) a surfacecontamination problem exist. In trending the observable effect is that C

ACdoesn’t almost

change and CDC increases as in figure 18, some time after the contamination is taken out andCDC returns to normal values.

107 107 106

142140

108

177 178178

104 104 103106105103

167169169

100

110

120

130

140

150

160

170

180

6/12/99 19/04/01 1/09/02 14/01/04 28/05/05 10/10/06 22/02/08

Cdc

Cac

 Figure 18: Effect of Contamination in machine [17]. CDC remains almost flat. After four days

maintenance works finally take contamination out. Next year the unit is rewound.

-  “Internal Contamination”: In epoxy based insulation it is no usual water ingress, but in theevent of degraded machines with cracks and some delamination degree, water flows insidespaces in the insulation and increases permittivity from near 4 to around 80 finally increasingcapacitance both in DC and AC. It is the same situation if some strange material like oil entersinside the insulation. This increase of AC capacitance is usually greater than the relativedecrease relative to aging. Watching trending, it is usual to see a slow decrease both in AC &DC capacitances because of aging. When the machine admits water inside the insulation, bothcapacitances change and show a large increase. 

Cac Ageing indication (Relevant Samples )

-9,00

-8,00

-7,00

-6,00

-5,00

-4,00

-3,00

-2,00

-1,00

0,00

1,00

0,00 1,00 2,00 3,00 4,00 5,00 6,00

Years% Decrease

Motor 0

Motor 3

Motor 5

Motor 13

Motor 19

Motor 22

 Figure 19: CAC aging decay related with time of work for some relevant samples.

-  The problem “Internal Degradation” can only be discerned with trending of AC capacitancealong time. The usual increase per year is around 0,5…1%. Values above this top level

21

Page 22: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 22/32

correspond to machines under serious risk of failure and should be taken into account to check for thermal aging. Aging processes delaminates insulation material and replaces this spacewith air decreasing capacitance with time; permittivity goes from 4 (epoxy) to 1 (air), it alsodecreases the distance between plates. The insulation degrades, losses electric, mechanical andthermal properties and is less resistant to stress. Think about the CAC decay along the life of the machine: with a 1% of decay per year, after 40 years a machine will have decreased itsgeometric capacitance a 40%. This mean two things:

  A decrease in the dielectric constant that leads to a lower breakdown voltage.  A shrink effect in the groundwall that also decreases breakdown characteristic and

that can compromise semi-conductive coating layer by vibration.-  Changes: Geometric capacitance has a different value for each machine because of its

different design, power, working voltage and insulation chosen. The value of capacity itself can only give an indication of the size of the machine. The important is to compare AC to DCcapacitances and its tendencies. Note that AC capacitance is part of TC, so CR will also affectTC. It follows a table with a resume of all changes. 

Trending from

an OK status

Punctual

value

Diagnosis

CDC CAC CR  Values for CR are based from test sample mean values= = <6% No problem in the machine↑ = >10% External contamination problem. R E↓ makes CDC↑. LS & LE try to open

at 1KHz & CAC shows less influence↑  ↑ >6% Internal contamination problem. Water goes inside the insulation and

CAC increases too much to be reduced with frequency effect.↑  ↑↑ <0 Possible moisture effect. Monitored in some situations out of this

sample. Good theories about it but no definitive explanation.↕  ↓ Depends Usual aging effect. Because CDC is very sensitive to other effects, its

 better to use CAC to correlate this decrease.

22

Page 23: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 23/32

 

PARAMETER: Acronym = AI Absorption Index

Units [Dimensionless] 

Formula

min30.sec60

min30.sec30

 I  I 

 I  I  AI −

−= [05]

I30,60sec= Current measured 30 or 60seconds after the begin of the load period

I30min= Current measured at 30 minutes (the endof the load period)

Minimum: -0,14 Mean: 1,594 Maximum: 3,98 

Absorption Index

0

5

10

15

20

25

-0,23 1,32 1,36 1,4 1,44 1,48 1,52 1,56 1,6 1,64 1,68 1,72 1,76 1,8 1,84 1,88 1,92 1,96 2

Adimensional

# Tests

Low__V High_V

 

Figure 20: Histogram with AI values related to Tests performed.The “All valid test” histogram indicates that almost all samples concentrate in a very close range from1.4 to 1.74, so 1,3…2 area is plotted in the graphs. The step is linear and of 0,02 in all range.

Absorption Index

0

2

4

6

8

10

12

14

16

-0,23 1,32 1,36 1,4 1,44 1,48 1,52 1,56 1,6 1,64 1,68 1,72 1,76 1,8 1,84 1,88 1,92 1,96 2

Adimensional

# Tests

OK ope rati on Sur fac e Contami nati on Inte rnal De gr adati on Inte rnal Contami nati on

 Figure 21: Histogram with AI values related to Tests diagnostic distribution.

The “Diagnose test” histogram indicates that:

-  OK for operation range [1,40…1,88]. Most samples around 1,56.-  Surface Contamination ranges [1,38…1,92]. Most samples around 1,64.

23

Page 24: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 24/32

-  Internal Contamination ranges [0…1,62]. Most samples around 1,48.-  Internal Degradation ranges [1,34…1,82]. Most samples around 1,56.

AI Conclusions: Polarization Index takes data from minutes 1 and 10 to get a wide part of the IR variation. Another approach is to use Absorption Index to check the insulation. This parameter focusesthe attention in the area of the first part of the IR variation (0…60sec.). There, it is located the mostimportant component of the exponential decay of the absorption current. If the decay is fast it givesgood >1,56 =high AI, if the decay is slow it is an indication of irregularities present in the insulation,so it gives bad <1,4=low AI values. So, with AI we can detect the homogeneity of the machine and theamount of contamination that ingresses inside the insulation. It is a degree to differentiate if thecontamination is out in the surface (AI=high) or could enter inside the insulation (AI=low).

-  “OK operation”. This results keep in a close range 1,43 to 1,88. It gives the idea of aminimum “healthy” value of 1,43.

-  “Surface & Internal Contamination”. Both problems seem to be between 1,34 to 1,92 goingdown with the degree of contamination in the machine. This parameter should be correlated

with PI & capacitance trending. Internal degradation problems seem to be below 1,62. It doesalso exist some Surface contamination problems below 1,6. It seems logic that both surface &internal contamination will decrease this parameter and the bigger the decrease, the mostinternal the problem should be. After cleaning, the parameter should recover again up to goodvalues >1,56. This is the point where seems to be the limit for diagnosis.

-  “Internal Degradation”. Aged or deteriorated machines with age show no clear tendency inthis parameter, most machines are around 1,56 but there are both healthy (1,82) andcontaminated machines (1,34) in the sample.

-  Changes: AI decreases with any kind of pollution, oil, water or solid. As with PI it shows lessvariation with temperature. 

Figure 22: Evolution of AI of machine [00] related to CR. CR indicates contamination and AI

decreases to values indicative of an internal problem. 

24

Page 25: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 25/32

 

PARAMETER: Acronym = RC Reabsorption Current

Units [mA/FV] 

FormulaK C V 

 I  RC  AC 

 R

⋅⋅

⋅−=.sec601000 [06]

I60secR = Reabsorption period V= Test voltage CAC= Low voltage alternatecurrent (1KHz) capacitance

K= TemperaturecompensationMinimum: 0,32 Mean: 7,646 Maximum: 34,48 

Reabsorption Current

0

2

4

6

8

10

12

14

16

0 0,3 0,6 0,9 2 3,5 5 6,5 8 9,5 11 12,5 14 15,5 17 18,5 20

mA/FV

# Tests

Low_V High_V

 Figure 23: Histogram with RC values related to Tests performed.  

The “All valid test” histogram indicates that almost all samples concentrate 0,9 to 19 with a meanaround 6. Note that for representation there are two steps: 0,1 up to 1 and 0,5 to the end.

Reabsorption Current

0

2

4

6

8

10

12

14

16

0 0,3 0,6 0,9 2 3,5 5 6,5 8 9,5 11 12,5 14 15,5 17 18,5 20

mA/FV

# Tests

OK operation S urface Contamination Internal Degradation Internal Contamination

 Figure 24: Histogram with RC values related to Tests diagnostic distribution.

25

Page 26: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 26/32

 The “Diagnose test” histogram indicates that:

-  OK for operation range [0,4…5], with mean around 2,2.-  Surface Contamination spreads [1…20]. No defined mean.-  Internal Contamination range [2,5…7,5]. Mean around 6.-  Internal Degradation ranges [4,5…20]. Mean around 9

RC Conclusions: Returned Absorption Current (RC) is taken 1 minute after the begin of reabsorption period. It is temperature, voltage and capacitance normalized in order to obtain a similar range of variation in different size of machines.

-  The results for “OK operation” show that values keep under 5. Only two cases are above:5,63 related with high ambient moisture (83%) and another of 5,91 where maintenance reportsindicate begin of aging.

-  Results for “Surface Contamination” and “Internal Contamination”, Both problems seemto increase the value of this currents beginning from 2, but don’t show any correlation.

-  “Internal Degradation”. The results are all above 4,5. Well cured new insulation shows very

low values 0…2. As the units degrade, the value begins to grow. In this sample of 33machines, 29 are 40 or more years old. In the next plot, “OK operation” machines are picturedin red. Note how aging changes up this value up to a value below 5…7 for good machines.Aged machines increase this value more because more internal discontinuities inside theinsulation are created. This process is irreversible and defines the design life limit of themachine. This differentiates from surface contamination because IR and PI have good values.From the mean values result of this test, a very clean and well cured insulation should nothave a value greater than 0,5+(0,2*year) to be in a good condition of aging.

Reabsorption Currents / Ageing

0

5

10

15

20

25

30

35

0,00 5,00 10,00 15,00 20,00 25,00 30,00 35,00 40,00 45,00

Years of life

   m     A     /     F     V

Low V

High V

Good

 Figure 25:Distribution of RC with aging of the machines.

-  Changes: RC is temperature compensated. Anyway, it will increase with moisture, aging,excess of heat in the unit or other degradation process.

26

Page 27: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 27/32

 

PARAMETER: Acronym = TC Time Constant

Units [seconds] 

Formula  AC C  IRTC  ⋅= min2 [07]IR 2min= Load Period CAC= Low voltage alternate

current (1KHz) capacitanceMinimum: 10,96 Mean: 344,21 Maximum: 6411,9 

Time Constant

0

10

20

30

40

50

60

0 30 60 90 300 600 900 3000 6000

Seconds

# Tests

Low_V High_V

 

Figure 26: Histogram with TC values related to Tests performed.

The “All valid test” histogram indicates that samples spread from 30 to 3000seg. Note that for representation there are three steps: 10 up to 100, 100 up to 1000 and 1000 up to 7000.

Time Constant

0

5

10

15

20

25

30

35

40

45

50

0 30 60 90 300 600 900 3000 6000

Seconds

# Tests

OK operation S urface Contami nati on Internal Deg radati on Internal Contami nation

 Figure 27: Histogram with TC values related to Tests diagnostic distribution.

The “Diagnose test” histogram indicates that:-  OK for operation range [300…7000], with mean around 400.-  Surface Contamination spreads [20…1000]. Mean around 50.

27

Page 28: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 28/32

-  Internal Contamination ranges [60…600]. Mean around 200.-  Internal Degradation ranges [40…400]. Mean around 200. 

TC Conclusions: This parameter is much related with CR, because uses CAC in its equation. TCshould remain above a minimum value of ~300 for good machines. Machines with low capacitance(less insulation weight), usually have high IR 2, and those with high capacitance could have IR 2 somehow reduced. About aging, TC is most influenced by IR 2, as CAC changes in an inferior degreewith the pass of the years.

-  “OK operation” values should be above 300. Fully new machines well cured give values of up to 3000…7000. IR 2 shows a clear influence.

-  “Surface Contamination”. Usually below 400. There are three samples from 400 to 1000related with good machines with light surface contamination problems.

-  “Internal Contamination”. Usually below 400. There is a value of 600 related to a lightwater contaminated machine where CAC increases and the surface of the machine is cleangiving also a good IR 2.

-  “Internal Degradation”. All degraded samples are at or below 400, and concentrate around

200. The degradation decreases CAC and also IR 2. TC is again a good way to monitor aging.-  Changes: TC has a small change with temperature depending from IR 2, so it will decrease

with temperature. It will also decrease with contamination, aging and should increase after cleaning works.

28

Page 29: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 29/32

 

PARAMETER: Acronym = LCR Leakage Current Ratio

Units [No] 

Formula

1

2

 LEAKV 

 LEAKV 

 I 

 I  LCR = [08]

Inside Formula

K C V 

 I  I 

 AC 

 LEAK ⋅⋅

⋅−=

min301000[09]

I30min= After load period V= Test voltage CAC= Low voltage alternatecurrent (1KHz) capacitance

K= TemperaturecompensationMinimum: 0 Mean: 1,230 Maximum: 10,6 

Leakage Current Ratio

0

5

10

15

20

25

30

35

0 0,6 0,75 0,9 1,05 1,2 1,35 1,5 1,65 1,8 1,95 2,1 2,25 2,4

Adimensional

# Tests High V / Low V

 Figure 28: Histogram with LCR values related to Tests performed.

The “All valid test” histogram indicates that samples range from 0,75 to 1,5 with a mean around 1.The step is linear, of 0,05 in all range.

Leakage Current Ratio

0

5

10

15

20

25

0 0,6 0,75 0,9 1,05 1,2 1,35 1,5 1,65 1,8 1,95 2,1 2,25 2,4

Adimensional

# Tests

OK oper ati on S ur face Contami nati on Internal De gr adati on Inte rnal Contami nati on

 Figure 29: Histogram with LCR values related to Tests diagnostic distribution.

29

Page 30: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 30/32

 

The “Diagnose test” histogram indicates that:-  OK for operation range [0,55…1,65], with mean around 1.-  Surface Contamination spreads [0,75…3,89]. Mean around 1,2.-  Internal Contamination ranges [0,75…10,6]. Mean around 1,2.-  Internal Degradation ranges [0,62…8,96]. Mean around 0,95.

Figure 30: IR change with test voltage. Tests on machine #24, [#24/5] Date 05/April/2005 with

LCR=1,00 & [#24/6] Date 25/August/2005 with LCR=1,24. Values for LCR are taken after 30

minutes but IR plot gives good view of the effect.

LCR Conclusions: LCR is the parameter that talks about linearity with test voltage. It should be near 1 because insulation behavior should be linear with voltage. As IEEE Std-43-2000 says  IR can

decrease somewhat with an increase in applied voltage. Dry good insulation should give the same IR

with test voltage up to the peak value of rated voltage. Significant decrease may indicate imperfectionsor fractures in insulation, aggravated if presence of dirt or moisture.

-  “OK operation” . As from LCR, from the sample and IEEE we should tolerate 10% below 1 but 20% above 1. So the range is 0,9…1,2. Elements out of range are all either with high IR &PI>3 or those combined with a little moisture. So with PI>2 it should not be necessary tocheck this parameter.

-  For  “Surface Contamination” or  “Internal Contamination”, the sample goes out of therange for most samples. The effect is based in that surface resistance is very sensitive to testvoltage increase. This parameter can be used to corroborate contamination with the aid of theother parameters.

-  “Internal Degradation”. Does not necessary change this parameter. Even more, there are a big number of cases without problems. This is that the degeneration can degrade the insulation but only sometimes open cracks or spaces for water or contamination to go inside changingLCR.

-  Changes: Because it is again a ratio of currents, it is expected not to change too much withtemperature. It will change with contamination and degradation of the insulation related withcracks.

30

Page 31: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 31/32

 

7.-  CONCLUSIONS

About of the process of diagnosis, several things to take into account:•  Test performance:

 Ambient and machine temperatures & moisture must be monitored.  Test system should be properly grounded both for safety and better noise performance of test instrumentation.

  It is important to use a comments sheet or software remarks screen in order to include testvariations (rain, moisture excess, measurements from control cabinet…) that could distorttest results. This way, diagnosis could also be aided when data appeared incongruent.

  Test should include all the relevant information around the machine, running hours, installdate, rewind date, kind of insulation… It is also of importance to have detailedinformation about maintenance history of the machine.

  After a problem is detected in a machine and if the problem can be solved (as is the caseof moisture or contamination), a new test should be done to check the good solution of the

 problem and to have new data baseline for trending.

•  Test validation:  Although test are usually performed by automatic equipment, it always exist chances to

commit errors that could change test results or make them inconsistent.  Each test should be checked by an expert looking for irregular plots, extreme temperature

& moisture conditions, measurement oscillations, out of usual range parameters, etc  If the machine was at ambient temperature without space heating elements, it could absorb

moisture making dangerous to perform another 2nd test techniques or restart the machineagain (as recommended by regulations). In order to check degradation of the insulation itis best to eliminate moisture and other surface contamination problems that could mask 

 parameters related with aging.•  Punctual Diagnosis:

   Diagnosis priorities: CR, RC, TC, LCR & PI give a fast idea of the possibility of 

 problems in the insulation. It is risky to asses a diagnosis on a single parameter, it is bestto use two parameters to distinguish the problem in the machine. The correlation betweenthem as we saw along the paper gives an idea of the kind of problem. IR & AI give an ideaof the degree of the degradation that the contamination is causing and how inside theinsulation it has progressed.

  Contamination. Either surface or internal will be detected both in punctual diagnosis or trending with the aid of CR. CR should be checked carefully if the contamination wasinternal: in this situation the increase of both CAC & CDC could mask the change of CR. TC& LCR will confirm the problem together with low IR & PI. AI can indicate how muchthe problem is inside the insulation.

   Aging. It won’t necessary decrease IR & PI, so older techniques based in these valueswon’t detect this effect. The best parameters used to confirm this problem are RC, C

AC 

evolution and TC. Because of that surface & internal contamination could mask agingdiagnosis in punctual diagnosis, it is better to diagnose first for inexistence of bothcontaminations after the machine is dry and clean. If no problem was detected, then aging

 problems of the machine could be better evaluated.•   About Trending:

  Most important than punctual data is trending because you get a better figure of the actualsituation. It is important to have a zero test (baseline data performed in commissioning or when this methodology is first applied in order to have good data guidance).

  Capacitance variation both DC and AC at 1KHz is a good mean to check contamination &degradation of insulation.

EDA is a good tool to perform a 1st

approach to machine diagnosis. If everything goes well, parameters show good, when something goes wrong several parameters indicate the most possible

31

Page 32: EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

7/29/2019 EDA TEST TO PERFORM PREDICTIVE MAINTENANCE IN RELEVANT ROTATING MACHINES

http://slidepdf.com/reader/full/eda-test-to-perform-predictive-maintenance-in-relevant-rotating-machines 32/32

 problem. After that, the user decides to continue testing with 2nd test techniques like partial discharge,tan delta, surge test,..

This paper described the EDA test through the Iberdrola experience using it as the first level operationtest within their predictive maintenance policy, helping the decision making process or determiningthe need of second instance tests. It’s then the easiest way to analyze the evolution of the external andinternal evolution of the insulation.

 Nowadays, EDA test has been adopted by some of the main utilities and motors manufacturers andworkshops in Europe, and everyday new companies worldwide decide to take advantage of it.

8.-  BIBLIOGRAPHY 

 Next are given different references from EDAIII, from other 2nd instance test and about relatedinternational normative.

[1]  IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus-Electrical

Machinery. IEEE Std. 62.2-2000.[2]  IEEE Guide for Operation and Maintenance of Hydro-Generators. IEEE Std. 492-1999.

[3]  IEEE Guide: Test Procedures for Synchronous Machines. IEEE Std. 115-1995.[4]  IEEE Guide for Insulation Maintenance of Large Alternating-Current Rotating

Machinery (10 000 kVA and Larger). IEEE Std. 56-1997.[5]  IEEE Recommended practice for Testing Insulation Resistance of Rotating

Machinery. IEEE Std. 43-2000.[6]  A. Tabernero and B. Batlle. “EDAIII: STATOR INSULATION DIAGNOSIS &

PREDICTIVE MAINTENANCE”. UNITRONICS, S.A. Spain. 10th Insucon InternationalConference Birmingham 2006.

[7]  A. Tabernero and B. Batlle. “Predictive Maintenance in Hydrogenerators”. Hydro 2007.

Granada, Spain, October 2007.[8]  Manés Fernández Cabanas, Manuel García Melero, “Técnicas para el mantenimiento

y diagnóstico de máquinas eléctricas rotativas” ABB Service, S.A. Marcombo 1998, pp235-248.

[9]  Óscar Duque & Marcelo Pérez, “Motores de Inducción. Técnicas de MantenimientoPredictivo”. Abecedario Sept. 2005, pp248-150.

[10]  Emilio Sierra, “Mantenimiento del bobinado estatórico de MT basado en elestado. Método EDA” Magazine Mantenimiento, No.146, Julio-Agosto 2001.

[11]  Luis Odriozola Arteaga, “Evaluación del estado del aislamiento en bobinadosde máquinas eléctricas rotativas” Anales de mecánica y electricidad, Enero-Febrero2004, pp26-33.

[12]  Joan Puigmal Pairot, “Diagnóstico del estado del aislante en grandesmáquinas eléctricas rotativas mediante el estudio de la capacidad del bobinado”Magazine Mantenimiento, No.81 Enero-Febrero 1995. pp31-36.

[13]  Salvador Carreras. “Mantenimiento predictivo en los devanados de lasmáquinas eléctricas rotativas de alta tension” Magazine Mantenimiento, No.119,

 Noviembre 1998, pp13-22.[14]  IEEE Recommended Practice for Insulation Testing of AC Electric Machinery

(2300V and Above) with High Direct Voltage, IEEE Std. 95-2002.[15]  Isidor Kerszenbaum. “Inspection of Large Synchronous Machines. Checklists, Failure

Identification, and Troubleshooting”. IEEE Power Engineering Series. 1996.[16]  Greg C. Stone. Edward A. Boulter, Ian Culbert, Hussein Dhirani. “Electrical

Insulation for Rotating Machines. Design, evaluation, aging, testing and repair”. IEEE Press.

Wiley-Interscience. 2004.[17]  Geoff Klempner & Isidor Kerszenbaum. “Operation and Maintenance of Large Turbo-G t ” IEEE P Wil I t i 2004