Refer to the service manual in the GSPN(see the rear cover) for the more information. ECO HEATING SYSTEM CONTENTS ECO HEATING SYSTEM OUTDOOR UNIT CONTROL KIT 1. Precautions 2. Product Specifications 3. Disassembly and Reassembly 4. Troubleshooting 5. PCB Diagram 6. Wiring Diagram 7. Schematic Diagram 8. Reference Sheet Model : RC160MHXGA RC140MHXGA RC120MHXGA RC160MHXEA RC140MHXEA RC120MHXEA RC090MHXEA MIM-E03A 5&0+;*$B60B(B$BFRLQGG

ECO HEATING SYSTEM - SOLFEX

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ECO HEATING SYSTEM - SOLFEX

Refer to the service manual in the GSPN(see the rear cover) for the more information.

ECO HEATING SYSTEM CONTENTS

ECO HEATING SYSTEMOUTDOOR UNIT CONTROL KIT

1. Precautions

2. Product Specifications

3. Disassembly and Reassembly

4. Troubleshooting

5. PCB Diagram

6. Wiring Diagram

7. Schematic Diagram

8. Reference Sheet

Model : RC160MHXGARC140MHXGARC120MHXGARC160MHXEARC140MHXEARC120MHXEARC090MHXEA

MIM-E03A

��

Page 2: ECO HEATING SYSTEM - SOLFEX

Contents

1. Precautions ..............................................................................................................................................................................3 1-1 Precautions for the Service ..........................................................................................................................................3

1-2 Precautions related to static electricity and PL ...................................................................................................3

1-3 Precautions for the Safety ............................................................................................................................................4

1-4 Precautions for handling a system containing refrigerants .........................................................................5

1-5 Precautions for the brazing .........................................................................................................................................5

1-6 Precautions for charging refrigerants .....................................................................................................................5

2. General Overview .............................................................................................................................................................6 2-1 Features of the System ..................................................................................................................................................6

2-1-1 Key features of the Monobloc ..........................................................................................................................7

2-2 Product Specifications ...................................................................................................................................................8

2-2-1 Hydro Unit .................................................................................................................................................................8

2-3 Specifications of optional items .............................................................................................................................10

2-3-1 Accessories .............................................................................................................................................................10

3. Disassembly and Reassembly .........................................................................................................................11 3-1 EHS Control Kit ...............................................................................................................................................................12

3-2 Outdoor Unit ...................................................................................................................................................................14

4. Troubleshooting.............................................................................................................................................................26 4-1 Wired remote controller .............................................................................................................................................26

4-2 Troubleshooting by symptoms ..............................................................................................................................29

4-2-1 Communication error after finishing Tracking ......................................................................................29

4-2-2 EEPROM circuit failure .......................................................................................................................................30

4-3 Control Kit(Mono) ........................................................................................................................................................31

4-3-1 EEPROM error .....................................................................................................................................................31

4-3-2 : Error due to abnormal data of Wired remote controller thermistor value ............................32

4-3-3 : Error due to abnormal data of Water outlet thermistor value ...............................33

4-3-4 : Error due to abnormal data of DHW tank thermistor value ...................................34

4-3-5 Water pump & flow switch OFF ...................................................................................................................35

4-3-6 Water pump & flow switch ON ....................................................................................................................36

4-3-7 Control KIT temperature sensor(open/short) .......................................................................................37

4-3-8 Communication error after finishing Tracking(Control KIT) ...........................................................38

4-4 Items to check before diagnostics .......................................................................................................................39

4-4-1 Test run mode and view mode ....................................................................................................................39

4-4-2 Troubleshooting for outdoor unit ..............................................................................................................40

��

Page 3: ECO HEATING SYSTEM - SOLFEX

Contents

4-5 Troubleshooting by symptoms .............................................................................................................................42

4-5-1 Communication error after finishing tracking (E202) ........................................................... 42

4-5-2 Time out (1min.) of communication error between MAIN PBA and INV. PBA (E203) ............ 43

4-5-3 Temperature sensor error (E221, E231, E251, E320 ) ...................................................................... 44

4-5-4 Fan error (E458, E475) ............................................................................................................................. 45

4-5-5 Compressor error (E461, E467) ............................................................................................................ 47

4-5-6 Current trip error (E462, E463) ............................................................................................................. 48

4-5-7 IPM(IGBT module) over current error (E464) ................................................................................. 49

4-5-8 DC-link voltage under/over error (E466) ......................................................................................... 51

4-5-9 GAS leak error(E554) ................................................................................................................................ 52

4-5-10 The other errors ....................................................................................................................................... 53

4-5-11 In case of heating at the cooling mode or coolin g at the heating mode ....................... 54

4-5-12 Outdoor unit is not powered on – Initial diagnosis .................................................................. 56

4-5-13 Outdoor unit power supply error ..................................................................................................... 57

5. PCB Diagram ............................................................................................................................................................................. 58

5-1 Control Kit......................................................................................................................................................... 58

5-2 Outdoor Unit ................................................................................................................................................... 59

5-3 Parts List ........................................................................................................................................................... 64

6. Wiring Diagram ........................................................................................................................ 78

6-1 Control Kit......................................................................................................................................................... 78

6-2 Outdoor Unit ................................................................................................................................................... 79

7. Schematic Diagram .................................................................................................................. 82

7-1 Control Kit......................................................................................................................................................... 82

7-2 Outdoor Unit ................................................................................................................................................... 84

8. Reference Sheet ....................................................................................................................... 85

8-1 Index for Model Name ................................................................................................................................ 85

8-1-1 Outdoor Unit ......................................................................................................................................... 85

8-2 Refrigerant Circuit Diagram .......................................................................................................................86

��

Page 4: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 3

1. Precautions

1-1 Precautions for the Service

Use the standard parts when replacing the electric parts. – Confirm the model name, rated voltage, rated current of the electric parts.

When repairing the equipment, connection of the harness parts must be firm and solid. – A loose connection may cause noise or other malfunction.

When assembling and disassembling the equipment while it is laid down, lay it on soft cloth. – Otherwise it may scratch the back of the exterior of the product.

Remove dust or dirt completely from the housing block, wiring block and service parts during repair. – This helps prevent the danger of fire caused by tracking or short circuit.

Fasten the valve caps of service valves and charging valves of outdoor unit as much as possible using adjustable wrenches.

Check the status of the components’ assembly after repair service. – The status must be the same as before the repair service.

1-2 Precautions related to static electricity and PL

The PCB power supply block is susceptible to static electricity. Therefore, care must be taken during repair or measuring while the power is on.

– Wear insulation gloves for PCB repair or measuring.

Check whether the installation location is at least two meters away from other electronic products such as TV, video, or audio.

– Otherwise, the video quality might be degraded or noise might be generated.

Do not let end users repair the products themselves. – Unauthorized disassembly might cause electric shock or fire.

��

Page 5: ECO HEATING SYSTEM - SOLFEX

4 Samsung Electronics

1-3 Precautions for the Safety

Do not pull any electric wires and do not touch an auxiliary power switch with a wet hand. – There is a danger of electric shock or fire.

In case any wire or power plug has been damaged, replace it to eliminate any possible danger.

Do not bend the power cord by force and do not put any heavy object on the power cord. – There is a danger of electric shock or fire.

Do not use multi socket. – There is a danger of electric shock or fire.

Ground the product if necessary. – Be sure to ground the product if there is any danger of electric leakage due to water or moisture.

Be sure to turn off the auxiliary power switch or pull out the power plug during replacement or repair of electric parts. – There is a danger of electric shock.

In case the product will not be in use for a long time, the battery of remote control should be kept separately. – Leakage of inside fluid can cause break down of remote control.

The installation must be done by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard. – Installation by an unqualified person may cause a water leakage, electric shock or fire and so on.

The electric work must be done by service agent or similarly qualified persons according to national wiring regulations and use only rated cable.

– If the capacity of the power cable is insufficient or electric work is not properly completed, electric shock or fire may occur.

Use only rated parts and tools. – If you don't use the rated parts and tools, it can cause trouble with the air conditioner and bring about injury.

If any gas or impurities except R410A refrigerant come into the refrigerant pipe, serious problem may occur and it may cause injury.

Leak test must be done using only Nitrogen(NO2)gas.

R410A refrigerant is used for EHS.

– When using R410A, moisture or foreign substances may affect to the capacity and reliability of the product.Safety precautions must be taken when installing the refrigerant pipe.

– The design pressure of the unit is 4.1MPa. Select appropriate material and thickness according to the regulations.

– R410A is a quasi-azeotrope of two refrigerants. Make sure to charge liquid one when adding refrigerant. If you charge gaseous refrigerant, it may affect the capacity and reliability of the product as a result of change formation of the refrigerant.

��

Page 6: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 5

1-4 Precautions for handling a system containing refrigerants

All system containing refrigerants shall be removed under regional regulations prior to the disposal to prevent the potential health and environmental consequences.

Harmful for human body – When emitted liquid refrigerant contacts human body, contacted area may get frostbite, blister or become numb.

If refrigerant leaks in airtight area, lack of oxygen may cause suffocation. When refrigerant is heated, it may generate harmful gas.

Precautions for handling container – Do not apply shock or heat to the refrigerant container.

1-5 Precautions for the brazing

Clear any dangerous or inflammable materials in surrounding environment.

Make sure to empty the remaining refrigerant in the product or pipe before brazing. – Brazing with the refrigerant still remaining in the product or pipe may cause poor result and generate harmful gas. Furthermore,

pressure of the refrigerant may increase and cause damage to the leaking part. This may lead harmful refrigerant and oil to spurt

out which can be dangerous for service personnel.

Use nitrogen gas to get rid of the oxide forming during brazing. – Using other type of gas may cause damage to the product or the exterior.

1-6 Precautions for charging refrigerants

Add quantity of the refrigerant using a scale and perform a test operation with S-net. – Product performance may decrease if you add excessive amount of refrigerant.

Do not charge refrigerants while heating the container up. – The container may get damaged by the heat and result in explosions.

Do not operate the product without pressure switch(for product protection) and sensor. – If there are any internal blockage, high refrigerant pressure increase may damage the product or exterior.

��

Page 7: ECO HEATING SYSTEM - SOLFEX

6 Samsung Electronics

2. General Overview

2-1 Features of the System

Overview EHS(Eco Heating System) is an integrated system with plate heat exchanger. This system provides customers lots of convenience such as Energy savings, Easy installation, and Comparable installation cost

POWER SAVINGEHS(Eco Heating System) considers the trend in air conditioner use. It optimizes the energy efficiency of loads ranging from partial to full. It achieves an excellent energy effect for the users of the air conditioner.

Samsung patented compressorSamsung has been researching and developing compressors since the 70's. It has developed power saving compressors for more than thirty years. The EHS(Eco Heating System) compressor adopts a double-rotor BLDC compressor with permanent magnets made by Samsung. Electricity for the compressor rotor is obtained from a neodium-iron-boron permanent magnetic material (boron magnet can attract iron material weighing 1000 times its own weight.) It strengthens the rotary moment of the compressor to maximize the entire efficiency of the compressor.

BLDC electricity

“Permanent magnet,” strong magnetic rotorDouble rotor compression cylinder

Nd-Fe-B Neodium-Iron-Boron magnet

SAMSUNG's double-rotor compressor has the upper and lower rotors designed symmetrically. The double rotor in symmetry can remove vibrations caused by the eccentric design of the cylinder.

2 rotors balancing the rotary moment

Centered symmetry

Upper rotor

Permanent magnet rotor

Lower cylinder

Upper cylinder

Lower rotor

High efficiency heat exchangerEHS(Eco Heating System) uses new multiple-teeth screw pipes with a diameter of 8 mm to improve the heat exchangeability of the pipe by

30.8%.

The water-friendly aluminum foil in the heat exchanger uses the G-fin patent design to improve the efficiency of heat exchange by 13%.

Summarize

DC fan electricityThe EHS(Eco Heating System) outdoor machine uses DC fan electricity. The rotational speed of electricity is 100 RPM to 1050 RPM with

step-free control. The electrical efficiency is improved by about 33% compared to AC electricity.

Efficiency

Multiple-teeth screw pipes General screw pipes

��

Page 8: ECO HEATING SYSTEM - SOLFEX

General Overview

Samsung Electronics 7

Quiet nightEHS(Eco Heating System)'s outdoor machine can be set to quiet nighttime operation mode. The outdoor machine executes quiet operation

(sleeping mode) after six hours. After 12 hours, it returns to the previous mode automatically.

Environment load change curves

Temperature change curve

Max temperature

Noise change curve(sleeping mode) After 6 hours

Start Stop

1 hour of quiet operation

2-1-1 Key features of the Monobloc

Running Costs-Reduction of Up to 33.3%

Samsung EHS, known for its world class efficiency (11kW floor heating system with COP of 4.55), can reduce 33.3% of your run-

ning costs as compared to a gas boiler.

Price and Space Reduction of Up to 50%

With an all-in-one outdoor unit capable of both air-to-water and air-to-air functions, Samsung EHS saves you in terms of the low

initial purchase price & installation fee as well as the space needed for an extra outdoor unit.

High Performance at Low Temperature

Samsung EHS is made up of an inverter compressor optimally operated according to the outdoor temperature, offering heating

performance of 90% at -10°C and reliable antifreezing protection at -20°C.

��

Page 9: ECO HEATING SYSTEM - SOLFEX

8 Samsung Electronics

2-2 Product Specifications

2-2-1 Hydro Unit

Item

RC160MHXGA RC140MHXGA RC120MHXGA

MIM-EO3A

3phase 16kW 3phase 14kW 3phase 12kW

Image

Outdoor unit

Control Kit

Remote Controller

Capacity (95%↑)

Heating 1 W 16,000 14,000 12,000 -

Heating 2 W 15,100 13,100 11,400 -

Cooling 1 W 17,000 16,000 13,500 -

Cooling 2 W 13,100 12,500 10,000 -

POWER CONSUMPTION (110%↓)

Heating 1 W 3,810 3,220 2,610 -

Heating 2 W 4,580 3,850 3,260 -

Cooling 1 W 5,710 5,250 3,910 -

Cooling 2 W 5,240 5,000 3,700 -

Running Current (110%↓)

Heating 1 A 6.0 5.1 4.1 -

Heating 2 A 7.2 6.0 5.1 -

Cooling 1 A 9.0 8.2 6.1 -

Cooling 2 A 8.2 7.8 5.8 -

Power SupplyCOP/EER (95%↑)

Ø,V,Hz 3/380-415/50 3/380-415/50 3/380-415/50 1/187~265/50Heating 1 W/W 4.20 4.35 4.60 -Heating 2 W/W 3.30 3.40 3.50 -Cooling 1 W/W 2.98 3.05 3.45 -Cooling 2 W/W 2.50 2.50 2.70 -

Refrigerant Chargeg,

type2,200 R410A 2,200 R410A 2,200 R410A -

Set Dimensions (W*H*D)

Net mm 940X1,420X330 940X1,420X330 940X1,420X330

Gross mm 995X1,548X426 995X1,548X426 995X1,548X426

Weight (Net/Gross) kg 103 / 113 103 / 113 103 / 113 35 / 5.5

Noise

Cooling Cond.1/2 dB(A) 62 62 62 -

Heating Cond.1/2 dB(A) 64 64 64 -

Operation range

Cooling ℃ 10~46 10~46 10~46 -

Heating ℃ -20~35 -20~35 -20~35 -

��

Page 10: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 9

Product Specifications (cont.)

Item

RC160MHXEA RC140MHXEA RC120MHXEA RC090MHXEA

1phase 16kW 1phase 14kW 1phase 12kW 1phase 9kW

Image

Outdoor unit

Control Kit

Remote Controller

Capacity (95%↑)

Heating 1 W 16,000 14,000 12,000 9,000

Heating 2 W 15,100 13,100 11,400 8,400

Cooling 1 W 17,000 16,000 13,500 10,000

Cooling 2 W 13,100 12,500 10,000 7,500

POWER CONSUMPTION (110%↓)

Heating 1 W 3,810 3,220 2,610 2,090

Heating 2 W 4,580 3,850 3,260 2,510

Cooling 1 W 5,860 5,330 4,070 2,860

Cooling 2 W 5,350 5,060 3,770 2,730

Running Current (110%↓)

Heating 1 A 17.1 14.4 11.7 9.9

Heating 2 A 20.5 17.3 14.6 11.9

Cooling 1 A 25.5 23.2 17.7 13.5

Cooling 2 A 23.3 22.0 16.4 12.9

Power SupplyCOP/EER (95%↑)

Ø,V,Hz 1/220-240/50 1/220-240/50 1/220-240/50 1 / 220-240 / 50Heating 1 W/W 4.20 4.35 4.60 4.30 Heating 2 W/W 3.30 3.40 3.50 3.35 Cooling 1 W/W 2.90 3.00 3.32 3.50 Cooling 2 W/W 2.45 2.47 2.65 2.75

Refrigerant Chargeg,

type2,200 R410A 2,200 R410A 2,200 R410A 1,400 R410A

Set Dimensions (W*H*D)

Net mm 940X1,420X330 940X1,420X330 940X1,420X330 940X998X330

Gross mm 995X1,548X426 995X1,548X426 995X1,548X426 995X1,096X426

Weight (Net/Gross) kg 103 / 113 103 / 113 103 / 113 75 / 83

Noise

Cooling Cond.1/2 dB(A) 62 62 62 60

Heating Cond.1/2 dB(A) 64 64 64 63

Operation range

Cooling ℃ 10~46 10~46 10~46 10~46

Heating ℃ -20~35 -20~35 -20~35 -20~35

��

Page 11: ECO HEATING SYSTEM - SOLFEX

10 Samsung Electronics

Item Description Code No. Q’ty Remark

Cap Drain DB63-10355C 3

Essential Offer (Outdoor Unit)

Drain Plug DB67-00806A 1

Rubber Leg DB73-20134A 4

ASSY-INSTALLATION MANUAL (Outdoor Unit)

DB98-34411A 1

Essential Offer (Panel)

ASSY-USER MANUAL

DB98-34412A 1

ASSY-INSTALLATION MANUAL (Control Kit)

DB98-34413A 1

Switch-Flow DB34-00079A 1

Essential Offer (Control Kit)

Wired remote controller DB93-09348A 1

Connector Wire (Smart Grid, 2000mm)

DB93-13255A 1

Connector Wire (Remote controller, 10,000mm)

DB93-13332A 1

Thermistor (Back-up Heater) DB95-05022A 1

Thermistor (Water Tank) DB95-05023A 1

2-3 Specifications of optional items

2-3-1 Accessories

��

Page 12: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 11

Hand Tool sets

3. Disassembly and Reassembly

Item Remark

+Screw Driver

Adjustable wrench

–Screw Driver

Nipper

Electric Motion Driver

L-Wrench

Torque Lench

Latchet Lench

��

Page 13: ECO HEATING SYSTEM - SOLFEX

12 Samsung Electronics

No Parts Procedure Remark

1 CABINET TOP You must turn off the Power before disas-sembly.

1) Unscrew and remove 2 mounting screw in the Cabinet top. (Use +Screw Driver)

2) Open the Cabinet top from the bottom.

2 ELCB 1) Unscrew and remove 2 screws of Power supply cable on the Terminal block.

(Use +Screw Driver)

2) Unscrew and remove 2 screws on top & bottom of the ELCB. (Use +Screw Driver)

3-1 EHS Control Kit

Be sure that the power switch is in the “OFF” and the power source cord shall be unplugged prior to disassembly and reassembly works.

��

Page 14: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 13

No Parts Procedure Remark

3 ASSY PCB MAIN OUT 1) Unscrew and remove 1 earth screw on the cabinet bottom. (Use +Screw Driver)

2) Unscrew and remove 3 screws on the PCB. (Use +Screw Driver)

3) Pull the PCB support to each direction.

Please note that PCB support may be brocken by your excessive pulling.

Disassembly and Reassembly

��

Page 15: ECO HEATING SYSTEM - SOLFEX

14 Samsung Electronics

No Parts Procedure Remark

1 Cabi Front RH You must turn off the Power before disassembly.

1) Unscrew and remove 3 mounting screw in the Cabinet Front RH. (Use +Screw Driver)

2 Cabi Top 1) Unscrew and remove 9 screws on each side of the Cabinet-Top. (Use +Screw Driver)

3 Cabi Install Front 1) Unscrew and remove 1 screw in the Cabinet-Install Front. (Use +Screw Driver)

RC090MHXEA

3-2 Outdoor Unit

��

Page 16: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 15

No Parts Procedure Remark

4 Guard Cond 1) Pull the sensor from Guard Cond.

2) Unscrew and remove 4 screws in the Guard Cond. (Use +Screw Driver)

Disassembly and Reassembly

��

Page 17: ECO HEATING SYSTEM - SOLFEX

Disassembly and Reassembly

16 Samsung Electronics

No Parts Procedure Remark

5 Cabi Back RH 1) Pull the sensor from Cabi Back RH.

2) Unscrew and remove 9 screws on each side of the Cabinet Back RH. (Use +Screw Driver)

��

Page 18: ECO HEATING SYSTEM - SOLFEX

Disassembly and Reassembly

Samsung Electronics 17

No Parts Procedure Remark

6 Cabi Install Back 1) Unscrew and remove 8 screws in the Cabinet-Front LF. (Use +Screw Driver)

��

Page 19: ECO HEATING SYSTEM - SOLFEX

Disassembly and Reassembly

18 Samsung Electronics

No Parts Procedure Remark

��

Page 20: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 19

Disassembly and Reassembly

No Parts Procedure Remark

7 Fan 1) Turn 2 mounting nuts as shown in the picture and remove it. (Use Adjustable Wrench)

��

Page 21: ECO HEATING SYSTEM - SOLFEX

20 Samsung Electronics

No Parts Procedure Remark

8 Motor 1) Separate the Fan Propeller. 2) Unscrew and remove the 8 Motor mounting

screws. (Use +Screw Driver)

3) Disconnect the Motor wire From

Ass'y Control Out.

Disassembly and Reassembly

��

Page 22: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 21

No Parts Procedure Remark

9 Bracket Motor 1) Unscrew and remove 2 mounting screws in Bracket Motor. (Use +Screw Driver)

10 Heater 1) Unscrew and remove 3 mounting screws in Bracket Motor. (Use +Screw Driver)

2) Disconnect the heater wire from Ass'y Control Out.

Disassembly and Reassembly

��

Page 23: ECO HEATING SYSTEM - SOLFEX

22 Samsung Electronics

Disassembly and Reassembly

No Parts Procedure Remark

11 Control Out 1) Disconnect 6 Connecters From Ass'y Control Out.

2) Unscrew and remove 3 mounting screw in Control Out. (Use +Screw Driver)

3) Separate Ass'y Control Out.

��

Page 24: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 23

Disassembly and Reassembly

No Parts Procedure Remark

12 Ass'y 4way Valve 1) Purge the Coolant first.2) Unscrew and remove 4 mounting screws

in Service Valve. (Use +Screw Driver)

3) Separate the pipe from the Entrance/Exit using a welder.

When removing the compressor, Heat Exchanger, and Pipe, purge the completely and remove the pipe with a welding flame.

��

Page 25: ECO HEATING SYSTEM - SOLFEX

24 Samsung Electronics

Disassembly and Reassembly

No Parts Procedure Remark

13 Compressor 1) Unscrew and remove 1 mounting nut in Cover Terminal. (Use Adjustable Wrench)

2) Separate the Comp wire.

3) Separate the Compressor Felt Sound.

4) As shown in the picture, unscrew and bottom. (Use Adjustable Wrench)

��

Page 26: ECO HEATING SYSTEM - SOLFEX

Disassembly and Reassembly

Samsung Electronics 25

No Parts Procedure Remark

14 Ass'y PHE 1) Separate the pipe from the Entrance/Exit using a welder.

2) As shown in the picture, unscrew and remove 2 mounting screws from the bracket PHE. (Use Adjustable Wrench)

15 Assy Cond Out 1) Unscrew and remove 2 screws on each side of the Assy Cond Out. (Use +Screw Driver)

��

Page 27: ECO HEATING SYSTEM - SOLFEX

26 Samsung Electronics

4. Troubleshooting

4-1 Wired remote controller

- If an error occurs, ( ) icon will be displayed on the wired remote controller.

- Press the Test button to see the error code.

Error mode Contents Measure

Product operation in error condition

Error typeOutdoor unit/

Compressor/Indoor unit

Indoor unit communication error

Check the communication cable of indoor unit. Check the DC output voltage at the communication terminal

Operation OffCommunication

error

Indoor unit/outdoor unit communication time-out error: errors in more than 6 packets

Check the outdoor communication cable connection. Check DC output voltage and the communication terminal

Operation OffCommunication

error

Indoor temperature sensor (open/short error)

Check indoor unit room temperature sensor. Check indoor unit PCB connector CN41 (White)

Operation OffIndoor sensor

error

Indoor unit Eva In sensor (Open/Short)

Check indoor unit pipe sensor. Check indoor PCB connector CN41(White)

Operation OffIndoor sensor

error

Indoor unit Eva In sensor disconnection

Check the disconnection of indoor unit pipe sensor Operation OffIndoor sensor

error

Indoor floating switch secondary detection

Check indoor unit float sensor. Check indoor PCB connector CN5 (black)

Operation OffSelf diagnostic

error

Indoor/outdoor communication error (1 min)

Check the communication connection between indoor and outdoor units. Check the power line and communication cable connection status

Operation OffCommunication

error

Communication error between indoor/outdoor INV MAIN MICOM (1 min)

Check MAIN MICOM Check INVERTER MICOM

-Communication

error

Outdoor temperature sensor error

Check sensor connection status Check sensor location Check sensor resistance

Operation OffOutdoor sensor

error

COND temperature sensor error Check sensor connection status Check sensor location Check sensor resistance

Operation OffOutdoor sensor

error

[Inverter] Emission temperature sensor error

Check sensor connection status Check sensor location Check sensor resistance

Operation OffOutdoor sensor

error

Emission temperature excessively high

No error (DISCHARGE temperature control) -Outdoor unit

protection control error

Heating operation blockedCheck the operation setting state Check temperature sensor

Operation OffSelf diagnostic

error

Cooling operation blockedCheck the operation setting state Check temperature sensor

Operation OffSelf diagnostic

error

Outdoor fan 1 error

Check input power connection status Check the connection status between the motor and outdoor unit PCB Check indoor/outdoor fuse

Operation OffSelf diagnostic

error

[Inverter] Compressor startup error

Check the compressor connection status Check the resistance between difference phases of the compressor

Operation OffOutdoor unit

protection control error

[Inverter] Total current error/PFC over current error

Check the input powerCheck the coolant charging status Check the normal operation of outdoor fan

Operation OffOutdoor unit

protection control error

��

Page 28: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 27

Wired remote controller (cont.)

Error mode Contents Measure

Product operation in error condition

Error typeOutdoor unit/Compressor/Indoor

unit

[Inverter] IPM over current error

Check coolant chargingCheck the compressor connection status and normal operation Check the obstacles around the indoor and outdoor unitsCheck whether the outdoor unit service valve is openCheck whether the indoor/outdoor installation pipe/wiring are correct

Operation OffOutdoor unit

protection control error

Compressor V limit errorCheck the compressor connection status Check the resistance between difference phases of the compressor

Operation OffOutdoor unit

protection control error

DC LINK over/low voltage errorCheck input power Check AC power connection

Restart in 3 minutesOutdoor unit

protection control error

[Inverter] Compressor rotation error

Check the compressor connection status Check the resistance between difference phases of the compressor

Operation OffOutdoor unit

protection control error

[Inverter] Current sensor errorCheck EEPROM DATACheck the normal operation of PCB

Operation OffOutdoor unit

protection control error

[Inverter] DC LINK voltage sensor error

Check the input power connection Check the status of RY21 and R200 in the INVERTER PCB

Operation OffOutdoor unit

protection control error

[Inverter] OTP errorCheck EEPROM DATACheck the normal operation of PCB

Operation OffOutdoor unit

protection control error

AC ZERO CROSSING SIGNAL OUT error

Check the input power status Operation OffOutdoor unit

protection control error

Compressor LOCK errorCheck the compressor connection status Check the resistance between difference phases of the compressor

Operation OffOutdoor unit

protection control error

Outdoor fan 2 error

Check the input power connection status Check the connection status of the motor and the outdoor unit PCBCheck the indoor/outdoor unit fuse

Operation OffSelf diagnostic

error

Gas leak error

Check the coolant charging statusCheck the indoor EVA sensorCheck if the outdoor unit service value is openCheck that the indoor/outdoor installation pipe/wiring are correct

Operation OffSelf diagnostic

error

Capacities not matched Check the option code of the indoor unit Operation OffOutdoor unit

protection control error

Communication error between the indoor unit and wired

remote controller

Check the connection wire between the indoor unit and the wired remote controller

Normal operationWired remote

controller error

Communication error between the Master and Slave wired

remote controllers

Check the option switch for defining the Master and Slave (only one Master and one Slave can exist)

Normal operationWired remote

controller error

��

Page 29: ECO HEATING SYSTEM - SOLFEX

28 Samsung Electronics

Wired remote controller (cont.)

Error mode Contents Measure

Product operation in error condition

Error typeOutdoor unit/Compressor/Indoor

unit

COM1/COM2 cross installation error

Check that wired remote controller is connected to the COM2 terminal of the indoor unit

Normal operationWired remote

controller error

Communication error between the Master and Salve wired

remote controllers

Check the option switch for defining the Master and salve(Only one Master can exist)

Normal operationWired remote

controller error

Wired remote controller COM2 option setting error

Check that Com1, Com2 setting DIP switch is set to Com2 Normal operationWired remote

controller error

��

Page 30: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 29

4-2 Troubleshooting by symptoms

Indoor unit display

Symptom Communication error between the indoor and outdoor unit for two minutes

Failure Communication error between the indoor unit and outdoor unit

4-2-1 Communication error after finishing Tracking

No

Yes

No

Yes

Is there a response from the indoor PCB? (LED900 (RED) is not ON)

In this case, is thevoltage waveform between the lines square wave with amplitude over ±0.7V as shown

in the following picture?

+0.7V

-0.7V

GoodBad

Check the communication cable and replace the indoor unit PCB

Remove the communication cableconnecting the outdoor unit to indoor unit,

and measure the signal on LINE 2 of the outdoor unit with a scope

Reconnect the cable connecting the outdoor unit to the indoor unit

and restart the unit. If the communication still doesn’t work,

replace the indoor unit PCB.

Check the communication cable in the outdoor unit PCB

and replace the PCB

LED01

��

Page 31: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

30 Samsung Electronics

Restart the unit after replacing the PCB

Indoor unit display

Symptom EEPROM circuit failure

Failure EEPROM component failure, EEPROM circuit parts missing/damaged/soldering failure

4-2-2 EEPROM circuit failure

No

YesAre the EEPROM circuit

components in good conditions? (missing components / damage /

soldering failure)

Replace the PCB if the restart fails

��

Page 32: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 31

4-3-1 EEPROM error

Indoor unit display ×(Operation) ◑(Timer) ◑(Fan) ◑(Filter) ×(Defrost)

Criteria

Cause of problem

Communication failure between EEPROM and MICOM

Outdoor unit display

Yes

Are there any problems such as short or dewetting between

EEPROM PIN?

If you restart after reentering model options and power reset, does the

error occur again?

Replace PCB

Yes

No

Normal operationNo

1. How to check

Check the location of EEPROM by referring to the schematic diagram

Replace PCB

4-3 Control Kit(Mono)

��

Page 33: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

32 Samsung Electronics

4-3-2 : Error due to abnormal data of Wired remote controller thermistor value

Wired remocon room thermistor has a defective OPEN/SHORT

Refer to how to determine below

Wired remocon display

Criteria

Cause of problem

Outdoor unit display x x x(x x x : The address of the error occurred indoor unit)

No

The thermistor needs to be replaced.

No

Re-start after put the connetor in the PBA.YesDoes wired remocon

room thermistor connector come out of the PBA?

Is the resistance value Deviated from the temp. table,

significantly?

Yes

1. How to check

After putting out the thermistor from the PBA Measure its resistance

value B/W two terminal.

Re-start after replacing PBA.

Temperature(°C)

Resistance(KΩ)

706050403021100

-10

2.23.04.25.88.3

12.118.027.343.0

Ex) In case of 26°C – its resistance : around 10.93KΩ

��

Page 34: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 33

4-3-3 : Error due to abnormal data of Water outlet thermistor value

Water outlet thermistor has a defective OPEN/SHORT

Refer to how to determine below

Wired remocon display

Criteria

Cause of problem

Outdoor unit display x x x(x x x : The address of the error occurred indoor unit)

No

Re-start after put the connetor in the PBA.Yes

1. How to check

After putting out the thermistor from the PBA Measure its resistance

value B/W two terminal.

The thermistor needs to be replaced.

No

Is the resistance value Deviated from the temp. table,

significantly?

Yes

Re-start after replacing PBA.

Temperature(°C)

Resistance(KΩ)

706050403021100

-10

2.23.04.25.88.3

12.118.027.343.0

Does Water outlet thermistor connector come out of the PBA?

Ex) In case of 26°C – its resistance : around 10.93KΩ

��

Page 35: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

34 Samsung Electronics

4-3-4 : Error due to abnormal data of DHW tank thermistor value

DHW tank thermistor has a defective OPEN/SHORT

Refer to how to determine below

Wired remocon display

Criteria

Cause of problem

Outdoor unit display x x x (x x x : The address of the error occurred indoor unit)

No

Re-start after put the connetor in the PBA.Yes

1. How to check

After putting out the thermistor from the PBA Measure its resistance

value B/W two terminal.

The thermistor needs to be replaced.

No

Is the resistance value Deviated from the temp. table,

significantly?

Yes

Re-start after replacing PBA.

Temperature(°C)

Resistance(KΩ)

706050403020100

435982

115166242362553

Does water tankthermistor connector come out

of the PBA?

Ex) In case of 26°C – its resistance : around 195KΩ

��

Page 36: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 35

4-3-5 Water pump & flow switch OFF

Flow switch signal is off during 10seconds when the water pump signal is ON

Refer to how to determine below

Wired remocon display

Criteria

Cause of problem

No

Re-start after put the connetor in the PBA.Yes

1. How to check

Flow S/W needs to be replaced.Is it OPEN?

Yes

Check water pump operates properly

Does flow S/W connector come out of the PBA?

Yes

After putting out the connector(F/S)from the PBA Measure its status is

OPEN or SHORT?

Re-start after replacing PBA.NoCheck water flow rate

Is it proper?

Yes

>16 LPM(NH160PHXEA)>12 LPM(NH080PHXEA)

<16 LPM(NH160PHXEA)<12 LPM(NH080PHXEA)

E911

No

Change water flow rate to proper level

Water pump needs to be replacedNo

No

��

Page 37: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

36 Samsung Electronics

4-3-6 Water pump & flow switch ON

Flow switch signal is on during 10seconds when the water pump signal is off)

Refer to how to determine below

Wired remocon display

Criteria

Cause of problem

No

Re-start after put the connetor in the PBA.Yes

1. How to check

Flow S/W needs to be replaced.

Yes

Is it short?

No

Measure status of PBA is OPEN or SHORT?

Does flow S/W connector come out of the PBA?

Yes

After putting out the connector(F/S)from the PBA Measure its status is

OPEN or SHORT?

NoIs it short?

Yes

E912

NoYes

YesDoes the water flow?

PBA needs to be replacedDoes any extra

water pump installed?

Yes

Check the extra pump

No

��

Page 38: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 37

Error Mode E901, E902, E903, E904, E906

Symptom In case of open or short circuit of indoor temperature sensor

Failure Short or leakage of the corresponding sensor

Yes

No

No

In this case, is the resistance value out of range in the temperature

table on the right?

YesIs temperature

sensor disconnected from the connector in PCB?

Restart the system after replacing the PCB

Restart the system after connecting to the PCB connector

Temperature sensor failure (replace)

Remove the temperature sensor connector from the PCB and measure the

resistance between two terminals

4-3-7 Control KIT temperature sensor(open/short)

Current temperature

(°C)

Resistance(kΩ)

60 59.16

55 69.44

50 81.92

45 96.95

40 115.4

35 137.8

30 165.7

25 200

20 242.5

15 295.4

10 362.4

<Water tank temperature sensor resistance value>

��

Page 39: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

38 Samsung Electronics

Error Mode E201, E202

Symptom Communication error between the Control KIT and outdoor unit for two minutes

Failure Communication error between the Control KIT unit and outdoor unit

4-3-8 Communication error after finishing Tracking(Control KIT)

No

Yes

No

Yes

Is there a response from the Control KIT PCB? (LED01 (RED) is not ON)

In this case, is thevoltage waveform between the lines square wave with amplitude over ±0.7V as shown

in the following picture?

+0.7V

-0.7V

GoodBad

Check the communication cable and replace the Control KIT unit PCB

Remove the communication cableconnecting the outdoor unit to Control KIT unit, and measure the signal on LINE 2 of the outdoor

unit with a scope

Reconnect the cable connecting the outdoor unit to the Control KIT unit

and restart the unit. If the communication still doesn’t work,

replace the Control KIT unit PCB.

Check the communication cable in the outdoor unit PCB

and replace the PCB

LED900

��

Page 40: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 39

4-4 Items to check before diagnostics

4-4-1 Test run mode and view mode

Display Option Key

KEY KEY operation 7-segment display

K1Press once : Heating test run

Press twice : Defrost test run

Press 3times : Finishing test mode

Press once : Cooling test run

Press twice : Finishing test mode

K3 Reset

K4 View mode Refer to View mode display

K2

-

-

7-segment display

KEY (K1~K4)

7-segment display

KEY (K1~K4)

■ VIEW mode display

Number of press

Display contentsDisplay

UnitsSegment 1 Segment 2 Segment 3 Segment 4

0 Communication State Two digits of Tx One digit of Tx Two digits of Rx One digit of Rx

1 Order frequency 1 Three digits Two digits One digit Hz

2 Current frequency 2 Three digits Two digits One digit Hz

3 Type of Outdoor unit(Mone/Split)

4 Out sensor 4 Two digits One digit First decimal °C

5 Discharge sensor 5 Two digits One digit First decimal °C

6 OLP sensor 6 Two digits One digit First decimal °C

7 Cond sensor 7 Two digits One digit First decimal °C

8 Current 8 Two digits One digit First decimal °C

9 Fan RPM 9 Three digits Two digits One digit rpm

10 Target discharge temperature A Three digits Two digits One digit °C

11 EEV B Three digits Two digits One digit step

12 Total indoor heat exchanger capacity C Two digits One digit First decimal kW

13 Protection control D0 : air conditioning1 : heating

Protection control0 : no protection

control1 : freezing2 : non-stop

defrosting3 : over-load4 : discharge

Frequency state0 : Normal1 : Hold2 : Down3 : Up_limit4 : Sown_limit

-

14Temperature of Heatsink at PBA

E Two digits One digits First decimal °C

15The Quantity of connected Indoor Unit

F Three digits Two digits One digit set

long-1 Main Micom version Year(Hex) Month(Hex) Day(two digit) Day(One digit) -

long-1 and 1

Inverter Micom version Year(Hex) Month(Hex) Day(two digit) Day(One digit) -

long-1 and 2

EEPROM version Year(Hex) Month(Hex) Day(two digit) Day(One digit) -

��

Page 41: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

40 Samsung Electronics

4-4-2 Troubleshooting for outdoor unit

If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.

No.LED Display Displayed

PCB AssyMeaning Remarks Error Code

Red Green Yellow

- MAIN/INVERTER

Normal operation (MAIN : Indoor Outdoor : Green ON)(INVERTER : MAIN PCB INVERTER PCB : Green ON)

-

1 MAIN Control Kit quantity is mismatched.Check Control Kit quantity setting in outdoor

E201

2 MAIN/INVERTERAbnormal state, no communication between Indoor and Outdoor Main PCB

Check electrical connection and setting

E202

4 MAIN/INVERTER1min. Time out of communcation error(Main Inverter)

Check electrical connection and setting

E203

5 MAIN Outdoor temp sensor errorCheck Outdoor sensor Open/Short

E221

6 MAIN Cond. temp sensor errorCheck Cond. sensor Open/Short

E231

7 MAIN Discharge temp sensor errorCheck Discharge sensor Open/Short

E251

8 MAIN OLP Sensor ErrorCheck OLP sensor Open/Short

E320

9 MAINDetection of Outdoor Freezing when Comp. Stop

Check Outdoor Cond. E403

10 MAINProtection of Outdoor Overload when Comp. Stop

Check Comp. when it start E404

11 MAINDischarge temperature of a compressor in an outdoor unit is overheated.

E416

12 MAINOutdoor EEV Open error

Check EEV E419

13 MAINMiss wiring error at 3Phase power source line (Only 3Phase Model)

Check Power Line-R,S,T,N

E425

14 MAINGas leakage error (Stop state)

Check Gas leak E439

15 MAINHeating operation is not available since the outdoor air temperature is over 35°C.

Heating E440

16 Cooling E441

16 MAINGas leakage error (Before operating)

Check Gas leak E443

17 MAIN/INVERTER Outdoor unit BLDC Fan 1 or Fan 2 errorFAN1 error E458

19 E475

18 MAIN/INVERTER Comp. Starting error E461

19 MAIN Primary Current Trip error E462

20 MAIN Over current trip / PFC over current error Check OLP sensor E463

21 MAIN/INVERTER IPM(IGBT Module) Over Current(O.C) E464

22 MAIN/INVERTER Comp. Over load error E465

23 MAIN/INVERTER DC-Link voltage under/over errorCheck AC Power or DC_Link voltage

E466

Off Blink On

��

Page 42: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 41

No.LED Display Displayed

PCB AssyMeaning Remarks Error Code

Red Green Yellow

24 MAIN/INVERTER Comp. wire missing error Check Comp. wire E467

25 MAIN/INVERTER Current sensor errorCheck Outdoor Inverter PBA

E468

26 MAINDC-Ling voltage Sensor error

Check Input voltage

E469

27 MAIN EEPROM read/write error Check EEPROM E470

28 MAIN Outdoor EEPROM errorCheck Outdoor EEPROM date

E471

29 MAIN/INVERTERIPM(IGBT Module) or PFCM Temperature sen-sor Error

Check Outdoor Inverter PBA

E474

30 MAIN/INVERTER PFC Overload ErrorCheck Outdoor Inverter PBA

E484

31 MAINInput current sensor error

E485

32 MAIN/INVERTER IPM is over heated.Check Outdoor Inverter PBA

E500

33 MAIN GAS Leak errorCheck indoor and outdoor unit model

E554

34 MAINWater inlet temperature sensor error

Check Water inlet sensor

E901

35 MAINWater outlet temperature sensor error

Check Water outlet sensor

E903

36 MAINRefriqerant gas inlet temperature sensor error

Check Gas inlet sensor

E906

Off Blink On

Troubleshooting for outdoor unit(con.)

If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.

��

Page 43: ECO HEATING SYSTEM - SOLFEX

42 Samsung Electronics

4-5 Troubleshooting by symptoms

4-5-1 Communication error after finishing tracking (E202)

1. Check items

1) Is the communication cable short/open?

2) Is there a response from the Control kit PCB?

2. Check procedure

No

Yes

Is there a response from the kit PCB? (LED901 (ORN) in NOT blinking)

No

Yes

In this case, is thevoltage waveform between the lines square wave with amplitude over ±0.7V as shown

in the following picture?

+0.7V

-0.7V

GoodBad

Check the communication cable and exchange the kit PCB

Remove the communication cableconnecting the outdoor unit to indoor unit,

and measure the signal on LINE 2 of the outdoor unit with a scope

Reconnect the cable connecting the outdoor unit to the indoor unit

and restart the unit. If the communication still doesn’t work,

dna BCP tik .mmoc eht ecalper

Check the communication BCP hcae ni elbac

and replace the PCB

Yes

Is the power/communicationcable connected correctly?

No Connect the power/communicationcable correctly.

outdoor unit PCB in order of mention.

cf.) If there is no oscillo scope, it can be replaced multimeter instead of osillo scope.

��

Page 44: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 43

4-5-2 Time out (1min.) of communication error between MAIN PBA and INV. PBA (E203)

1. Check items

1) Is the communication cable connected properly between MAIN PBA and INVERTER PBA?

2) Is the power cable connected correctly?

2. Check procedure

Does the communication error occur?

Yes

NoNormal operation

Is the communication/power cable connected properly between

MAIN PBA and INVERTER PBA?

Yes

Connect the connector right position

Exchange MAIN PBA/INVERTER PBA in order of mention

No

<CN39 in MAIN PBA> <CN31 in INVERTER PBA>

��

Page 45: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

44 Samsung Electronics

4-5-3 Temperature sensor error (E221, E231, E251, E320)

1. Check items

1) Is the sensor connected correctly (CN43 in MAIN PBA)?

2) Is the postion of sensor correct?

2. Check procedure

Is the connector connected to match the color?

Yes

NoConnect the connector to match the color

Is the temperature sensorconnected properly withoutfracture?

Yes

No

3) Does the value of resistance satisfy the each temperature condition?

Check the sensor cable and connector

Does the value of resistancesatisfy the each temperaturecondition? (*)

Yes

NoExchange the temperature sensor

Power on

Yes

Is the wire of sensor brokenor is there any poor contact?

Yes

Nothe temperature sensor

<Error code for each temperature sensor>

0

5

10

15

20

25

30

35

40

-10 -5 0 5 10 15 20 25 30 35

0

100

200

300

400

500

0 5 10 15 20 25 30 35 40 50 60 70

(*)Resistance value for temperature sensor <outdoor, condenser temp. sensor> <discharge, OLP temp. sensor>

ex) 10.17k ex) 205.4k

��

Page 46: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 45

Yes

Yes

Yes

4-5-4 Fan error (E458, E475)

1. Check items

2. Check procedure

Yes

No

Yes

No

Yes

No

No

FAN 1 error(E458), FAN 2 error(E475)

1) Are the input power voltage and power connection correct?

2) Is the motor wire connected to the outdoor PCB correctly?

3) Is there no obstacle at the surrounding of motor and propeller?

4) Does the driver in the motor case broken?

Is the connection of FAN housing certainly toPCB socket?(CN90, CN91)

Check the connection of CN90 and CN91

Take each Fan motor housing after 1 minutes from turning the power

Exchange the FAN motor because of driver inside of the motor case brokenIs each resistance of FAN cable housing normal?(*)

(*)Resistance of FAN cable housing at the normal temperature(10˚C~30˚C)

wire pin number Resistance Remark

RED - BLACK 1-3 over 1MΩ +300V motor power

WHITE - BLACK 4-3 1KΩ ~ 2KΩ +15V control power

YELLOW - BLACK 5-3 200KΩ ~ 300KΩ control

BLUE - BLACK 6-3 10KΩ ~ 50KΩ pulse

ORANGE - BLACK 7-3 10KΩ ~ 50KΩ reverse

Mount each Fan housing to PCB socket and turn on the power

Follow the check procedure of outdoor unit power supply error check

Is the Pin voltage #1 - #3 of CN90 and 91over 250V?

NoExchange INVERTER PCBIs the Pin voltage #5 - #3 of CN90 and 91 15V?

NoExchange INVERTER PCBIs the Pin voltage #5 - #3 of CN90 and 91

within 1-6V during the operation?

Exchange the FAN motor not in rotationIs the Fan in rotation during

TEST operation in cooling mode

Cont.

# TEST operation # press K1 or K2 button on the MAIN PCB after power on.

��

Page 47: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

46 Samsung Electronics

Yes

).tnoc( )574E ,854E( rorre naF

Yes

Yes

No

No

Cont.

Exchange INVERTER PCB

Exchange the FAN motor

Is the Pin voltage #6 - #3 of CN90 and 91changed high(4-5V) and low(0-1V) in case of

making manual rotation slowly?

Is the Pin voltage #7 - #3 of CN90 and 91 low(0-1V) in normal rotation?

Exchange INVERTER PCB

��

Page 48: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 47

4-5-5 Compressor error (E461, E467)

1. Check items

1) Is the power connected properly?

2) Is the connector of compressor connected correctly?

2. Check procedure

Does the error occur?

Yes

NoNormal operation

Is the value of resistancebetween each phase(*) for compressor

smaller than 2

Yes

No

3) Is the resistance normal between each phase for compressor ?

Exchange the compressor

Is the value of resistance mega between compressor and outdoor unit body?

Yes

No

Yes

NoCheck the wire of compressor

Compressor starting error(E461), Compressor wire missing error(E467)

(*) U↔V, V↔W, W↔U

Exchange the compressor

Is the wire of compressorconnected correctly?

��

Page 49: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

48 Samsung Electronics

4-5-6 Current trip error (E462, E463)

1. Check items

1) Is the voltage of power suitable?

2) Is refrigerant charged?

2. Check procedure

Is the outdoor unit installed wellaccording to installation manual?

Yes

NoReinstall after remove the obstacle

Yes

No

3) Does the fan of outdoor unit work normally?

Does the compressor work normal?

Yes

No

Are the service valves fully opened?

Yes

NoOpen the service valves

Primary current trip error(E462), Over current trip / PFC over current error(E463)

Exchange the compressor

4) Is there any obstacle around indoor and outdoor unit?

Is the indoor unit installed wellaccording to installation manual?

Reinstall after remove the obstacle

Exchange INVERTER PCB

��

Page 50: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 49

4-5-7 IPM(IGBT module) over current error (E464)

1. Check items

1) Is refrigerant charged?

2) Does the compressor work normally?

2. Check procedure

Is the outdoor unit installed wellaccording to installation manual?

Yes

NoReinstall after remove the obstacle

Yes

No

3) Is the connection of compressor correctly?

Are the service valves fully opened?

Yes

NoOpen the service valves

4) Is there any obstacle around indoor and outdoor unit?

Is the indoor unit installed wellaccording to installation manual?

Reinstall after remove the obstacle

Is the wire of compressorconnected correctly?

Yes

NoCheck the wire of compressor

Is the value of resistancebetween each phase(*) for compressor

smaller than 2

Yes

NoExchange the compressor

(*) U↔V, V↔W, W↔U

cont.

��

Page 51: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

50 Samsung Electronics

Yes

NoAre the position and measured value of temperature sensor normal? reposition the sensorreposition the sensor

cont.

Is the value of resistance mega between compressor and outdoor unit body?

Yes

NoExchange the compressor

Exchange INVERTER PCB

��

Page 52: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 51

4-5-8 DC-link voltage under/over error (E466)

1. Check items

1) Is the input power normal?

2) Is the AC power connected correctly?

2. Check procedure

Is the power cable connected correctly?

Yes

NoConnect the power cable

Yes

No

Check whether a fuse has blownYes

No

Exchange the fuse

Is the reactor connected correctly? Check the connection of reactor

Does the error occur frequently?Yes

No

Exchange INVERTER PCB

Check the input power(AC 230V ± 15%)

��

Page 53: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

52 Samsung Electronics

4-5-9 GAS leak error(E554)

1. Check items

1) Is refrigerant charged?

2) Is the evaporator sensor of indoor unit connected correctly?

2. Check procedure

Does the error occur?

Yes

NoNormal operation

Yes

No

Are the service valves fully opened?

Yes

NoOpen the service valves

Is the evaporator sensor of indoor unit connected correctly?

Yes

NoConnect the sensor’s connector

Yes

NoCharge refrigerant

Is the value of resistancebetween each phase(*) for compressor

smaller than 2Exchange the compressor

(*) U↔V, V↔W, W↔U

Is refrigerant charged?

Exchange INVERTER PCB

��

Page 54: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 53

4-5-10 The other errors

Error code

Meaning Troubleshooting

E177 Emergency stop Indoor unit ( kit) orders emergency stop. Check the indoor unit ( kit).

E201 Control Kit quantity is mismatched. Control kit quantity must be matched with outdoor unit 1 by 1. Check the kit quantity. It must be 1EA.

E403 Detection of outdoor freezing when compressor stops.

Outdoor unit (Condenser) froze. Check condenser.

E404 Protection of outdoor overload when compressor stops.

Compressor is overloaded. Please check same as E461 and check compressor when it starts.

E416 Discharge temperature of a compressor in an outdoor unit is overheated.

Discharge temperature is overheated.

E440 Heating operation is not available since the outdoor air temperature is over 35°C.

Check the outdoor temperature. E441

Cooling operation is not available since the outdoor air temperature is lower than -15°C.

E465 Compressor over load error Compressor is overloaded. Please check same as E461 and check compressor when it starts.

E468 Current sensor error Exchange INVERTER PBA.

E471 Outdoor EEPROM error EEPROM date is wrong. Exchange EEPROM or MAIN PBA. (This error don't occur in EMF 150-AM)

E474 IPM(IGBT Module) or PFCM temperature sensor error

Exchange INVERTER PBA.

E484 PFC overload error Check reactor located in control plate. If reactor is normal, exchange INVERTER PBA.

E500 IPM is over heated. down INVERTER PBA, and then restart the outdoor unit.

E556 Capacity mismatching between indoor and outdoor

EEPROM data is wrong. Exchange EEPROM or MAIN PBA

E557 Option code miss matching among the indoors(only for DPM)

Option setting data is wrong. (This error don't occur in EMF 150-AM)

��

Page 55: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

54 Samsung Electronics

4-5-11 In case of heating at the cooling mode or cooling at the heating mode

1. Troubleshooting procedure

Change the setting temperature of remote control.

Operate it with a heating modeas soon as the defrosting is shed.

After 3 minutes, coolingand heating start automatically.

No

No

No

Yes

Yes

Yes

Is the Thermo ?

Is the unit in the defrosting operation?

Is the compressorin 3 minutes

Check the resistance value of 4-WAY valve coil.

Go to the next page 4-WAY valve main body error

Attach the sensor correctly.

Over shortage of the refrigerant

Connect the connecter correctly.

4-WAY valve coil error

Exchangethe outdoor PCB.

No

Yes

Yes

Yes

OK

Yes

No

No

No

NG

No

Is much frostin the indoor heat

exchanger?

Does the 4-WAY valve operate

normally?

Is the outdoor air sensor and

outdoor heat exchanger attachedcorrectly?

Is the 4-WAY valve connector

connected correctly?

Dose thevoltage of AC220V

apply to the connector of 4-WAY valve coil during the

operation?

��

Page 56: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 55

In case of heating at the cooling mode or cooling at the heating mode (cont.)

Check the resistance value of outdoor fan.

Check the resistance value of EEV coil.

Does theEEV operate

normally?

Doesthe outdoor fan

operate at the operation of compressor?

Is theoutdoor fan connected

correctly?

Dose the voltage of DC300V

apply to the connector of outdoor fan during the operation of

outdoor unit?

The over shortage of refrigerant, t Capacity, Load estimation error

Connect the connector.

Outdoor fan error

Check the motor wire.

Exchangethe out PCB.

EEV coil error

Connect the connector.Is much frost

in the heat exchanger?

Is much frostin the heat exchanger?

Outdoor PCB error

EEV main body error

No No

NG

No

Yes

No

NG

Yes

No

Yes

OK

No

Yes

Yes

OK

Yes

From the previous page

��

Page 57: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

56 Samsung Electronics

4-5-12 Outdoor unit is not powered on – Initial diagnosis

1. Check items

1) Is the power supply voltage 380V?

2) Is the AC power connected correctly?

3) Are the LEDs in the main PCB and inverter PCB of the outdoor unit ON?

4) Is the input power voltage of the indoor unit 220V?

5) Is the wired remote controller connected correctly?

2. Check procedure

Yes

Turn o he main power switch (circuit break of power outlet) and turn on

again after 30 seconds.

Check the input powerNoIs the outdoor unit power

supply (N-R, N-S, N-T) 220Vac?

Yes

Check connection of the outdoor unit terminal block

NoIs the outdoor unit power voltage (L-N) 220Vac?

Yes

Check the connection wires and connectors of the indoor and outdoor units

NoIs the indoor unit power supply voltage (L-N) 220Vac?

Yes

Exchange the wired remote controllerNo

Does the air conditioner operate when pressing ON/OFF button of the

wired remote controller?

Yes

the option DIP switchesNoAre the option DIP switches

inside the wired remote controller co ured correctly?

No

Check the system depending on the error display

YesIs there an error message displayed on the wired remote

controller display?

Check the target temperature

��

Page 58: ECO HEATING SYSTEM - SOLFEX

Troubleshooting

Samsung Electronics 57

4-5-13 Outdoor unit power supply error

No

No

No

Yes

1. Checklist:

1) Are the input power voltage and power connection correct?

2) Is there any Fuse Short of the indoor or outdoor unit?

3) Is any LED lit on both MAIN PCB and INVERTER PCB?

4) Are Reactor wires of the outdoor unit connected correctly?

2. Troubleshooting procedure

Are wire and socket connected correctly? Power line N and T wire

Is voltage on N-T of terminal block over 300V? Check and correct the power cable wiring

Are wire and socket connected correctly? CN39(MAIN PCB),CN31(INVERTER PCB)

Is the FUSE on INVERTER PCB blown?

Check and correct the wire or socket connection

Check Fuses listed blow 3 FUSES in EMI PCB, 1 FUSE in MAIN PCB

No

Is there miss connection of power andcommunication wire between

indoor and outdoor?

Correct the cable wiringbetween indoor and outdoor

Check F1,F2 communication line wiring. CN50(MAIN PCB)

Check and correct the wiring

Exchange the FUSE

Exchange INVERTER PCB

Check each BLDC FAN motorshort or not, by resistance between

pin #1 and #3

Yes

No

Yes

No

Yes

Yes

Yes

MAIN PCB INVERTER PCB

ALL OFF ALL OFF

Error 202 display Normal

Error 203 display ALL OFF

Check LEDs on both MAIN PCBand INVERTER PCB after1 minutes

from power on

Exchange FAN motor

��

Page 59: ECO HEATING SYSTEM - SOLFEX

58 Samsung Electronics

5. PCB Diagram

5-1 Control Kit

1 2 3 4 5 6 7 8

① #1(L) : Phase L

#2(N) : Phase N

#3 : HEATER

#4 : HEATER

#1~26 : Check WIRING DIAGRAM

③ ④ #1 : SMART GRID sensor#2 : GND

⑤ #1 : FLOW SWITCH sensor#2 : GND

F1 : Communication signal F1F2 : Communication signal F2V1 : DC12VV2 : GNDF3 : Communication signal F3F4 : Communication signal F4

⑦#1 : WATER TANK sensor#2 : GND

⑧#1 : HEATER OUT sensor#2 : GND#3~#6 : Not used

TB-A – POWER IN / HEATER TB-B – TERMINAL BLOCK

TB-C – COM1/COM2 Communication

CN2 - DOWNLOAD

T4 : WATER TANK sensor

S/G – SMART GRID

T3 : HEATER sensorF/S – FLOW S/W

This Document can not be used without Samsung’s authorization.

��

Page 60: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

Samsung Electronics 59

5-2 Outdoor Unit

MAIN PCB

1 5 62 3 4

15

716 9 11 13

8 10 12 14

This Document can not be used without Samsung’s authorization.

��

Page 61: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

60 Samsung Electronics

①#1-#3 : 220~240Vac

②#1-#3 : 220~240Vac

③ #1-#3 : 220~240Vac

④#1-#3 : 220~240Vac

⑤#1 : RXD_INV #2 : TXD_INV #3, #8 : N.C #4 ~ #7 : Data signal #9 : GND #10 : DC 5V

⑥#1 : DC 5V #2 : MODE #3 : Reset #4~#6 : GRID_3/1/2 #7 : GND

⑦#1-#2 : Outdoor Temp. #3-#4 : Cond. Temp. #5-#6 : Discharge Temp. #7-#8 : OLP Temp.

⑧#1~#4 : Motor signal #5 : DC 12V

⑨#1~#4 : Motor signal #5 : DC 12V

⑩#1~#4 : Motor signal #5 : DC 12V

⑪#1 : TXD #2 : RXD #3 : GND #4 : DC 5V #5 : DC 12V #6 : INV. SMPS signal

⑫#1 : Temp. signal #2 : GND

⑬#1 : High Pressure temp. signal #3 : GND #4 : DC 5V

⑭#1 : DC 12V #2 : GND

⑮#1 : COM1#2 : COM2

⑯#1 : DC 12V#2 : GND#3 : DC 5V#4 : COM1#5 : COM2

CN11-AC POWER CN74-AC LOAD1 CN75-4WAY V/V CN71-AC LOAD2(Option)

CN37-Micom Download

CN82-EEV 2(Option)

CN42-High Pressure(Option)

CN35-AS-PRO

CN83-EEV 3(Option)

CN12-DC12V

CN43-Sensor

CN39-COMM-INV

CN31-Comm.

CN81-EEV 1

CN44-TEMP OPTION(Option)

CN33-Sub Comm.

��

Page 62: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

Samsung Electronics 61

2 6 7 3 4 59 8

①#R : AC 380~400V : WHT #S : AC 380~400V : BRN #T : AC 380~400V : BLK

②#1-#3 : AC 220~240V

③#1 : RXD , #2 : TXD #3 : GND, #4 : DC 5V #5 : DC 12V, #6 : INV. SMPS signal

④#1 : RXD_ATARO, #2 : TXD_ATARO #3, #8 : N.C, #4~#7 : DATA signal #9 : GND, #10 : DC 5V

⑤For S/W engineer debugging

⑥#1 : DC 360V , #2 : N.C #3 : GND, #4 : DC 15V #5 : FAN RPM, #6 : FAN RPM feedback

⑦#1 : DC 360V, #2 : N.C #3 : GND, #4 : DC 15V #5 : FAN RPM, #6 : FAN RPM feedback

⑧#1 : COMP. U-phase(RED) #2 : COMP. V-phase(BLU) #3 : COMP. U-phase(YEL)

⑨#1-#2 : DCL Reactor

RST-AC POWER 3phase CN100-AC POWER CN31-MAIN COMM CN22-Downloader

CN21-DAC/ENCODER

CN600-REACTOR

CN91-FAN2 CN90-FAN1 CN800-COMP.

1

INVERTER PCB

This Document can not be used without Samsung’s authorization.

��

Page 63: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

62 Samsung Electronics

①#R : AC 380~400V : WHT #S : AC 380~400V : BRN #T : AC 380~400V : BLK

②#1-#3 : AC 220~240V

RST-AC POWER 3phase CN100-AC POWER

21

EMI PCB

This Document can not be used without Samsung’s authorization.

��

Page 64: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

Samsung Electronics 63

Heater PCB

1 2

① AC POWER INPUT#1 AC POWER LINE - LIVE#2 AC POWER LINE - NEUTRAL

② AC POWER OUTPUT#1 AC POWER LINE - LIVE#2 AC POWER LINE - NEUTRAL

This Document can not be used without Samsung’s authorization.

��

Page 65: ECO HEATING SYSTEM - SOLFEX

64 Samsung Electronics

5-3 Parts List

MAIN PCB

Location Code Description Spec. Q`ty UnitSA/ SNA

DB93-11109D ASSY PCB MAIN-OUTEHS Remko 14KW,Inverter Platform #4, #5, #6

MAIN,Y,SMPS,TOP264VG,5Vdc, 12Vdc1 PC SA

DB93-11363C ASSY PCB MANUAL EHS Outdoor Main,14KW REMKO 1 PC SNA

ADHESIVE- SILICON

0201-001982 ADHESIVE-SIL TSE3854DS-W,White,2.2,MIL-A-46146B,UL94V-0 0.005 KG SNA

SOLDER-BAR 0202-001338 SOLDER-BARLeeD-free Solder BAR,W20L350H8,99.3Sn/0.7Cu/0.01

P10 G SNA

SOLDER-WIRE 0202-001608 SOLDER-WIRE FLUX LFC7-107,D0.8,99.3Sn/0.7Cu/0.01P,Flux3-4% 2 G SNA

FLUX 0204-002978 FLUX KSP-70M,84%,FLUX,SPRAY 1 G SNA

SOLVENT 0204-003174 SOLVENT S-E70,R-OH,100%,0.790 2 G SNA

IC102 1203-000002 IC-POSI.ADJUST REG.431,TO-92,3P,-,PLASTIC,2.44/2.58V,775MV,0TO+70C,10

0MA,-,ST,-1 PC SNA

IC101 1203-006612 IC-PWM CONTROLLER TOP264VG,DIP,12P,10.16x10.46mm,PLASTIC,TP 1 PC SNA

NTC01 1404-001274 THERMISTOR-NTC 22ohm,1.4A,3100K,9.5mW/C,-,7.0,- 1 PC SNA

X201 2802-001179 RESONATOR-CERAMIC 4MHZ,0.5%,BK,8X3X5.5MM 1 PC SNA

K1 3404-000165 SWITCH-TACT 12V,50mA,160gf,6x6x5,SPST 1 PC SNA

K2 3404-000165 SWITCH-TACT 12V,50mA,160gf,6x6x5,SPST 1 PC SNA

K3 3404-000165 SWITCH-TACT 12V,50mA,160gf,6x6x5,SPST 1 PC SNA

K4 3404-000165 SWITCH-TACT 12V,50mA,160gf,6x6x5,SPST 1 PC SNA

SW02 3407-000121 SWITCH-DIP 24V,300mA,SLIDE,STANDARD 1 PC SNA

RY72 3501-001163 RELAY-MINIATURE 12V,200mW,5000mA,1FormA,10ms,5ms 1 PC SNA

RY73 3501-001163 RELAY-MINIATURE 12V,200mW,5000mA,1FormA,10ms,5ms 1 PC SNA

RY74 3501-001163 RELAY-MINIATURE 12V,200mW,5000mA,1FormA,10ms,5ms 1 PC SNA

FUSE02 3601-000263 FUSE-CARTRIDGE 250V,3.15A,TIME-LAG,GLASS,5x20mm 1 PC SA

F101 3602-001012 FUSE-BLOCK 500V,-,100MOhm 1 PC SNA

IC83 3704-001601 SOCKET-IC 8P,SN,2.54mm 1 PC SNA

CN45 3711-000024 HEADER-BOARD TO CABLE BOX,3P,1R,2.5MM,STRAIGHT,SN,WHT 1 PC SNA

CN12 3711-000176 HEADER-BOARD TO CABLE 1WALL,2P,1R,3.96mm,STRAIGHT,SN,BLU 1 PC SNA

CN31 3711-000177 HEADER-BOARD TO CABLE 1WALL,2P,1R,3.96MM,STRAIGHT,SN,RED 1 PC SNA

CN11 3711-000203 HEADER-BOARD TO CABLE 1WALL,2P/3P,1R,7.92mm,STRAIGHT,SN,WHT 1 PC SNA

CN32 3711-000996 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN,BLK 1 PC SNA

CN81 3711-000997 CONNECTOR-HEADER BOX,5P,1R,2.5mm,STRAIGHT,SN,BLU 1 PC SNA

CN39 3711-001038 HEADER-BOARD TO CABLE BOX,6P,1R,2.5mm,STRAIGHT,SN,WHT 1 PC SNA

CN43 3711-001084 HEADER-BOARD TO CABLE BOX,8P,1R,2.5MM,STRAIGHT,SN,WHT 1 PC SNA

CN75 3711-003406 HEADER-BOARD TO CABLE 1WALL,2P,1R,7.92MM,STRAIGHT,SN,YEL 1 PC SNA

CN74 3711-003407 HEADER-BOARD TO CABLE 1WALL,2P,1R,7.92MM,STRAIGHT,SN,RED 1 PC SNA

CN35 3711-003873 HEADER-BOARD TO CABLE BOX,7P,1R,2mm,STRAIGHT,SN,WHT 1 PC SNA

CN37 3711-005716 HEADER-BOARD TO CABLE BOX,10P,1R,2mm,STRAIGHT,SN,BLK 1 PC SNA

CN33 3711-007422HEADER-BOARD TO

BOARD7P,1R,2mm,STRAIGHT,BRASS,BLK 1 PC SNA

DP51 DB07-00054A LED DISPLAYSSD-A3202GS-A13,LED DISPLAY,2 DIGIT,16 SEGMENT,2

DIGIT,16.6x16x13mm,GREEN,50mW,91 PC SNA

DP52 DB07-00054A LED DISPLAYSSD-A3202GS-A13,LED DISPLAY,2 DIGIT,16 SEGMENT,2

DIGIT,16.6x16x13mm,GREEN,50mW,91 PC SNA

PT01 DB26-00122A TRANS SWITCHINGEE2525,RC100PHXEA,GLOBAL

4WAY,310V,200~400V,PL-7, PM- 7,5V,12V,ER25*25 V10,50HZ,1.56mH,MULTI OUTPUT

1 PC SNA

��

Page 66: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

Samsung Electronics 65

Location Code Description Spec. Q`ty UnitSA/ SNA

COIL01 DB27-00082A COIL CHOKE

CV305400SJ,RC100PHXEA,GLOBAL 4WAY,40mH,+50~- 30%,706mohm,0.5A,13*7*5,16*18.5*10,3.4mm*8.4m

m,1.2mm,PAD,- 25℃~+105℃

1 PC SNA

ASSY CW EARTH

DB93-05379GASSY CONNECTOR WIRE

EARTHRC140RHXEA 1 PC SNA

DB93-11372C ASSY PCB AUTO EHS Outdoor Main,14KW REMKO 1 PC SNA

R110 2003-000855 R-METAL OXIDE(S) 47Kohm,5%,3W,AA,TP,6x16mm 1 PC SNA

C103 2201-000322 C-CERAMIC,DISC 2.2nF,10%,2000V,Y5P,13x5mm,10mm 1 PC SNA

C107 2201-000551 C-CERAMIC,DISC 0.47nF,10%,1000V,Y5P,6.3x5mm,5mm 1 PC SNA

C104 2201-000983 C-CERAMIC,DISC 1nF,10%,2000V,Y5P,TP,9x5mm,7.5mm 1 PC SNA

C116 2201-000987 C-CERAMIC,DISC 2.2nF,20%,400V,Y5U,TP,12.5x6mm,10mm 1 PC SNA

C117 2201-000987 C-CERAMIC,DISC 2.2nF,20%,400V,Y5U,TP,12.5x6mm,10mm 1 PC SNA

YC01 2301-001220 C-FILM,LEAD-PPF 100nF,10%,275V,BK,18x6x12mm 1 PC SNA

YC02 2301-001220 C-FILM,LEAD-PPF 100nF,10%,275V,BK,18x6x12mm 1 PC SNA

C118 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C111 2401-001103 C-AL 330uF,20%,16V,WT,TP,8x11.5mm,5 1 PC SNA

C112 2401-001103 C-AL 330uF,20%,16V,WT,TP,8x11.5mm,5 1 PC SNA

C108 2401-001838 C-AL 470uF,20%,25V,WT,TP,10x16,5 1 PC SNA

C109 2401-001838 C-AL 470uF,20%,25V,WT,TP,10x16,5 1 PC SNA

C106 2401-002438 C-AL 47uF,20%,50V,WT,TP,6.3x11,5mm 1 PC SNA

C115 2401-003645 C-AL 1UF,20%,50V,WT,TP,4X5MM,5 1 PC SNA

C101 2401-003861 C-AL 68UF,20%,400V,WT,TP,18X25MM,7.5 1 PC SNA

C102 2401-003861 C-AL 68UF,20%,400V,WT,TP,18X25MM,7.5 1 PC SNA

F102 3601-001308 FUSE 250V,1.6A,TIME-LAG,PLASTIC,8.4x7.6mm 1 PC SNA

DB93-11369C ASSY PCB SMD EHS Outdoor Main,14KW REMKO 1 PC SNA

SOLDER- CREAM

0202-001459 SOLDER-CREAM S3X58-M405,D20~38um,96.5Sn/3Ag/0.5Cu,FLUX 5% 10 G SNA

D105 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D201 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D202 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D203 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D204 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D209 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D210 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D211 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D212 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D213 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D214 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D391 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D392 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D104 0402-001192 DIODE-RECTIFIER ES2D,200V,2A,SMB,TP 1 PC SNA

BD101 0402-001298 DIODE-BRIDGE DF06S,600V,1A,SMD-4,TP 1 PC SNA

D102 0402-001427 DIODE-RECTIFIER ES1D,200V,1A,DO-214AC,TP 1 PC SNA

D103 0402-001427 DIODE-RECTIFIER ES1D,200V,1A,DO-214AC,TP 1 PC SNA

D101 0402-001429 DIODE-RECTIFIER US1J,600V,1A,DO-214AC,TP 1 PC SNA

CD31 0406-001204 DIODE-TVS SMBJ5.0CA,6.4/-/7.25V,600W,SMB 1 PC SNA

CD32 0406-001204 DIODE-TVS SMBJ5.0CA,6.4/-/7.25V,600W,SMB 1 PC SNA

MAIN PCB(cont.)

��

Page 67: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

66 Samsung Electronics

Location Code Description Spec. Q`ty UnitSA/ SNA

CD33 0406-001204 DIODE-TVS SMBJ5.0CA,6.4/-/7.25V,600W,SMB 1 PC SNA

Q501 0504-000001 TR-DIGITAL DTA114EKA,PNP,200mW,10K/10K,SOT-23,TP 1 PC SNA

Q502 0504-000001 TR-DIGITAL DTA114EKA,PNP,200mW,10K/10K,SOT-23,TP 1 PC SNA

Q503 0504-000001 TR-DIGITAL DTA114EKA,PNP,200mW,10K/10K,SOT-23,TP 1 PC SNA

Q504 0504-000001 TR-DIGITAL DTA114EKA,PNP,200mW,10K/10K,SOT-23,TP 1 PC SNA

Q103 0504-000127 TR-DIGITAL FJV3102R,NPN,200mW,10K/10Kohm,SOT-23,TP 1 PC SNA

IC51 0506-000175 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1 PC SNA

IC52 0506-000175 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1 PC SNA

IC71 0506-000175 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1 PC SNA

IC81 0506-000175 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1 PC SNA

LD74 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LD75 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LD01 0601-002345 LED SMD,RED,1.6x0.8x0.55mm,660nm,1.6x0.8x0.55mm 1 PC SNA

PC01 0604-001172 PHOTO-COUPLER TR,150-300,200mW,SOP,TP 1 PC SNA

IC32 0801-000393 IC-CMOS LOGIC74HC86,OR GATE,SOP,14P,150MIL,QUAD,ST,-

,2.0/6.0V,0.26V,- 40to+85C,180mW,4.2V,1uA,

1 PC SNA

IC31 1006-001325 IC-BUS TRANSCEIVERISL81487LIBZ,SO,8P,4.9x3.8 mm,SINGLE,ST,PLASTIC,5V,-

40to+85C,520mW,1,1,1.5/5.0V1 PC SNA

R202 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R203 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R309 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R310 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R411 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R413 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R415 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R417 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R121 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R302 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R303 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R501 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R502 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R503 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R504 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R505 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R506 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R507 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R704 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R705 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R304 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R305 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R306 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R307 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R308 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R311 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R312 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

MAIN PCB(cont.)

��

Page 68: ECO HEATING SYSTEM - SOLFEX

PCB Diagram

Samsung Electronics 67

Location Code Description Spec. Q`ty UnitSA/ SNA

R313 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R314 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R391 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R512 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R513 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R514 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R515 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R201 2007-000116 R-CHIP 120ohm,5%,1/10W,TP,1608 1 PC SNA

R301 2007-000116 R-CHIP 120ohm,5%,1/10W,TP,1608 1 PC SNA

R100 2007-000134 R-CHIP 33Kohm,5%,1/10W,TP,1608 1 PC SNA

R221 2007-000238 R-CHIP 1.5Kohm,1%,1/8W,TP,2012 1 PC SNA

R118 2007-000297 R-CHIP 10Kohm,1%,1/8W,TP,2012 1 PC SNA

R119 2007-000297 R-CHIP 10Kohm,1%,1/8W,TP,2012 1 PC SNA

R111 2007-000409 R-CHIP 15Kohm,5%,1/8W,TP,2012 1 PC SNA

R108 2007-000441 R-CHIP 180Kohm,1%,1/8W,TP,2012 1 PC SNA

R412 2007-000455 R-CHIP 18Kohm,1%,1/10W,TP,1608 1 PC SNA

R414 2007-000455 R-CHIP 18Kohm,1%,1/10W,TP,1608 1 PC SNA

R101 2007-000481 R-CHIP 1Mohm,5%,1/4W,TP,3216 1 PC SNA

R102 2007-000481 R-CHIP 1Mohm,5%,1/4W,TP,3216 1 PC SNA

R103 2007-000481 R-CHIP 1Mohm,5%,1/4W,TP,3216 1 PC SNA

R104 2007-000481 R-CHIP 1Mohm,5%,1/4W,TP,3216 1 PC SNA

R113 2007-000592 R-CHIP 22ohm,1%,1/4W,TP,3216 1 PC SNA

R416 2007-000614 R-CHIP 24Kohm,1%,1/10W,TP,1608 1 PC SNA

R418 2007-000614 R-CHIP 24Kohm,1%,1/10W,TP,1608 1 PC SNA

R117 2007-000683 R-CHIP 3.3Kohm,1%,1/10W,TP,1608 1 PC SNA

R114 2007-000701 R-CHIP 3.6Kohm,1%,1/10W,TP,1608 1 PC SNA

R340 2007-000869 R-CHIP 4.7Kohm,1%,1/10W,TP,1608 1 PC SNA

R109 2007-000941 R-CHIP 47Kohm,5%,1/8W,TP,2012 1 PC SNA

R120 2007-000941 R-CHIP 47Kohm,5%,1/8W,TP,2012 1 PC SNA

R115 2007-001131 R-CHIP 68ohm,1%,1/10W,TP,1608 1 PC SNA

R105 2007-007385 R-CHIP 1.2Mohm,1%,1/4w,TP,3216 1 PC SNA

R106 2007-007385 R-CHIP 1.2Mohm,1%,1/4w,TP,3216 1 PC SNA

R107 2007-007385 R-CHIP 1.2Mohm,1%,1/4w,TP,3216 1 PC SNA

R112 2007-010635 R-CHIP 6.8ohm,1%,1/10,TP,1608 1 PC SNA

C301 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C302 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C303 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C512 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C513 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C514 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C515 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C120 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C215 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C203 2203-002304 C-CER,CHIP 10pF,5%,50V,TH,BK,1608,- 1 PC SNA

C105 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C110 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C113 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

MAIN PCB(cont.)

��

Page 69: ECO HEATING SYSTEM - SOLFEX

68 Samsung Electronics

Location Code Description Spec. Q`ty UnitSA/ SNA

C114 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C119 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C202 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C204 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C205 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C206 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C207 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C208 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C209 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C211 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C212 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C213 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C214 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C216 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C217 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C304 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C305 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C311 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C312 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C403 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C404 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C405 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C406 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C501 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C502 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C701 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C801 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C201 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

C210 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

C221 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

L101 2703-002297 INDUCTOR-SMD 4.7uH,20%,6060 1 PC SNA

L102 2703-002297 INDUCTOR-SMD 4.7uH,20%,6060 1 PC SNA

PCB DB41-01034A PCB MAIN-OUTGLOBAL-4WAY OUTDOOR,FR-4,2,ver

2.4,T1.6,120*142,UB1, UB2, UB3,Outdoor,Inverter Platform #4, #5, #6 MAIN,600

1 PC SNA

IC21 DB91-01333A ASSY-MICGen3 Outdoor,STM-10A5-OS, S3F4A1H, 100TQFP,

ROM 512KB1 PC SNA

DB09-00535A IC MICOMS3F4A1H,100P,DC5V,12 MHz,TQFP,16 Bit,16

Bit,TQFP,QFP,16 Bit,- 40~+105,512K

1 PC SNA

MAIN PCB(cont.)

��

Page 70: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 69

INVERTER PCB

Location Code Description Spec. Q`ty UnitSA/ SNA

- DB93-11114A ASSY PCB MAIN-INVERTERRC100DHXGA, RC100PHXGA, RC125PHXGA,

RC125DHXGA,Inverter Platform #6,Y,SMPS,TOP243P,3.3V, 5V, 12V, 15V

1 PC SA

- DB93-11362A ASSY PCB MANUAL RC100DHXGA, RC140DHXGA,Inverter #6, 3phase 1 PC SNA

ADHESIVE-SILICON

0201-001982 ADHESIVE-SIL TSE3854DS-W,White,2.2,MIL-A-46146B,UL94V-0 0.02 KG SNA

SOLDER BAR 0202-001338 SOLDER-BAR LeeD-free Solder BAR,W20L350H8,99.3Sn/0.7Cu/0.01P 12.4 G SNA

SOLDER WIRE 0202-001608 SOLDER-WIRE FLUX LFC7-107,D0.8,99.3Sn/0.7Cu/0.01P,Flux3-4% 3.2 G SNA

FLUX 0204-002978 FLUX KSP-70M,84%,FLUX,SPRAY 10 G SNA

SOLVENT 0204-003174 SOLVENT S-E70,R-OH,100%,0.790 10 G SNA

IC601 0402-001994 DIODE-BRIDGE DF30NA160,1600V,30A,SIP-5,ST 1 PC SNA

IC104 1203-002735 IC-POSI.FIXED REG.KIA7815API,TO-220IS,3P,10.3x15.3mm,PLASTIC,14.4/15.6V,

2W,-30to+150,1A,ST1 PC SNA

IC101 1203-003527 IC-PWM CONTROLLERTOP243,DIP,7P,9.83x6.6mm,plastic,-0.3/700V,25W,-

40to+150,1.44A,TP1 PC SNA

PT100 1404-001498 THERMISTOR-PTC 40ohm,25%,290Vac,7A,TR 1 PC SNA

VA100 1405-000154 VARISTOR 460Vdc,2500A,17.5x7.5mm,TP 1 PC SNA

C820 2301-001830 C-FILM,MPEF 1000nF,5%,1000V,BK,28x18x31 1 PC SNA

C602 2401-004278 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

C603 2401-004278 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

C604 2401-004278 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

C605 2401-004278 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

C606 2401-004278 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

C607 2401-004278 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

C123 2401-004279 C-AL 560uF,20%,400V,WT,BK,35x50mm,14.2mm 1 PC SNA

L100 2702-001123 INDUCTOR-RADIAL 4.7uH,10%,6.5x7.5mm 1 PC SNA

RY12 3501-001163 RELAY-MINIATURE 12V,200mW,5000mA,1FormA,10ms,5ms 1 PC SNA

RY13 3501-001163 RELAY-MINIATURE 12V,200mW,5000mA,1FormA,10ms,5ms 1 PC SNA

RY11 3501-001264 RELAY-POWER 12V,200mW,5000mA,1FormA,10ms,10ms 1 PC SNA

RY14 3501-001264 RELAY-POWER 12V,200mW,5000mA,1FormA,10ms,10ms 1 PC SNA

RY600 3501-001411 RELAY-POWER 12V,30000mA,2FormA 1 PC SNA

FUSE400-1 3601-000263 FUSE-CARTRIDGE 250V,3.15A,TIME-LAG,GLASS,5x20mm 1 PC SA

FUSE100-1 3601-000297 FUSE-CARTRIDGE 250V,5A,TIME-LAG,GLASS,5.2x20mm 1 PC SA

FUSE100 3602-001012 FUSE-BLOCK 500V,-,100MOhm 1 PC SNA

FUSE400 3602-001012 FUSE-BLOCK 500V,-,100MOhm 1 PC SNA

CN100 3711-000203 HEADER-BOARD TO CABLE 1WALL,2P/3P,1R,7.92mm,STRAIGHT,SN,WHT 1 1 PC SNA

CN90 3711-000296 HEADER-BOARD TO CABLE 1WALL,6P,1R,3.96MM,STRAIGHT,SN,WHT 1 PC SNA

CN91 3711-000296 HEADER-BOARD TO CABLE 1WALL,6P,1R,3.96MM,STRAIGHT,SN,WHT 1 PC SNA

CN31 3711-001038 HEADER-BOARD TO CABLE BOX,6P,1R,2.5mm,STRAIGHT,SN,WHT 1 PC SNA

CN21 3711-003843 HEADER-BOARD TO CABLE BOX,8P,1R,2mm,STRAIGHT,SN,WHT 1 PC SNA

CN800 3711-007276 CONNECTOR-HEADER 3P,1R,10mm,STRAIGHT,AU,BLK 1 PC SNA

CN600 3711-007649 CONNECTOR-HEADER 2,1R,10mm,STRAIGHT,BRASS,BLK 1 PC SNA

CN22 3711-007706 HEADER-BOARD TO CABLE BOX,10P,1R,2mm,STRAIGHT,SN,RED 1 PC SNA

R-IN 3712-001139 CONNECTOR-TERMINAL TAB,MALE,6.35x0.8mm 1 PC SNA

S-IN 3712-001139 CONNECTOR-TERMINAL TAB,MALE,6.35x0.8mm 1 PC SNA

T-IN 3712-001139 CONNECTOR-TERMINAL TAB,MALE,6.35x0.8mm 1 PC SNA

IPM800 4719-002494 POWER MODULE I IPM,1200V/35A 1 PC SNA

ST11 DB26-00123A TRANS SWITCHINGEE2218,RC100PHXEA,GLOBAL 4WAY,310V,200~400V,PL-7,

PM-1 PCSNA1 PC SNA

DB93-11373A ASSY PCB AUTO RC100DHXGA, RC140DHXGA,Inverter #6, 1phase 1 PC SNA

D102 0402-000012 DIODE-RECTIFIER UF4007,1000V,1A,DO-41,TP 1 PC SNA

ZD800 0406-001434 DIODE-TVS P6KE18A,200,185,215,DO-15 1 PC SNA

��

Page 71: ECO HEATING SYSTEM - SOLFEX

70 Samsung Electronics

Location Code Description Spec. Q`ty UnitSA/ SNA

R101 2003-000855 R-METAL OXIDE(S) 47Kohm,5%,3W,AA,TP,6x16mm 1 PC SNA

R108 2006-001149 R-CEMENT,NON 1Kohm,5%,15W,CA,BK,48x12.5x12.5mm 1 PC SNA

C101 2201-000154 C-CERAMIC,DISC 10nF,+80-20%,2000V,Y5P,20x5mm,7.5mm 1 PC SNA

C102 2201-000322 C-CERAMIC,DISC 2.2nF,10%,2000V,Y5P,13x5mm,10mm 1 PC SNA

C103 2201-000551 C-CERAMIC,DISC 0.47nF,10%,1000V,Y5P,6.3x5mm,5mm 1 PC SNA

C106 2201-000551 C-CERAMIC,DISC 0.47nF,10%,1000V,Y5P,6.3x5mm,5mm 1 PC SNA

C113 2201-000551 C-CERAMIC,DISC 0.47nF,10%,1000V,Y5P,6.3x5mm,5mm 1 PC SNA

C119 2201-000551 C-CERAMIC,DISC 0.47nF,10%,1000V,Y5P,6.3x5mm,5mm 1 PC SNA

C104 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C124 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C125 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C201 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C300 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C326 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C405 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C407 2401-000481 C-AL 10uF,20%,50V,WT,TP,5x11,5 1 PC SNA

C803 2401-002438 C-AL 47uF,20%,50V,WT,TP,6.3x11,5mm 1 PC SNA

C807 2401-002438 C-AL 47uF,20%,50V,WT,TP,6.3x11,5mm 1 PC SNA

C811 2401-002438 C-AL 47uF,20%,50V,WT,TP,6.3x11,5mm 1 PC SNA

C813 2401-002438 C-AL 47uF,20%,50V,WT,TP,6.3x11,5mm 1 PC SNA

C107 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C109 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C112 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C114 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C115 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C117 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C120 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C121 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C401 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

C403 2401-003585 C-AL 220uF,20%,35V,WT,TP,8x11.5mm,5 1 PC SNA

DB93-11368A ASSY PCB SMD RC100DHXGA, RC140DHXGA,Inverter #6, 3phase 1 PC SNA

SOLDER CREAM 0202-001459 SOLDER-CREAM S3X58-M405,D20~38um,96.5Sn/3Ag/0.5Cu,FLUX 5% 3.8 G SNA

D107 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D300 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D301 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D303 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D304 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D600 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D601 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D700 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D701 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D702 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D703 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D901 0401-001099 DIODE-SWITCHING 1N4148WS,75V,150mA,SOD-323,TP 1 PC SNA

D104 0402-001192 DIODE-RECTIFIER ES2D,200V,2A,SMB,TP 1 PC SNA

D105 0402-001192 DIODE-RECTIFIER ES2D,200V,2A,SMB,TP 1 PC SNA

D100 0402-001427 DIODE-RECTIFIER ES1D,200V,1A,DO-214AC,TP 1 PC SNA

D103 0402-001427 DIODE-RECTIFIER ES1D,200V,1A,DO-214AC,TP 1 PC SNA

D400 0402-001427 DIODE-RECTIFIER ES1D,200V,1A,DO-214AC,TP 1 PC SNA

D401 0402-001427 DIODE-RECTIFIER ES1D,200V,1A,DO-214AC,TP 1 PC SNA

INVERTER PCB(cont.)

��

Page 72: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 71

Location Code Description Spec. Q`ty UnitSA/ SNA

D800 0402-001993 DIODE-RECTIFIER STTH112,1200V,1A,SMA 1 PC SNA

D801 0402-001993 DIODE-RECTIFIER STTH112,1200V,1A,SMA 1 PC SNA

D802 0402-001993 DIODE-RECTIFIER STTH112,1200V,1A,SMA 1 PC SNA

ZD600 0403-000282 DIODE-ZENER MMBZ5232B,5%,300mW,SOT-23,TP 1 PC SNA

ZD700 0403-000282 DIODE-ZENER MMBZ5232B,5%,300mW,SOT-23,TP 1 PC SNA

ZD701 0403-000282 DIODE-ZENER MMBZ5232B,5%,300mW,SOT-23,TP 1 PC SNA

ZD801 0403-001816 DIODE-ZENER 1SAM5934BT3,22.8/25.2V,1500mW,SMA,TP 1 PC SNA

ZD802 0403-001816 DIODE-ZENER 1SAM5934BT3,22.8/25.2V,1500mW,SMA,TP 1 PC SNA

ZD803 0403-001816 DIODE-ZENER 1SAM5934BT3,22.8/25.2V,1500mW,SMA,TP 1 PC SNA

D305 0404-001020 DIODE-SCHOTTKY BAT54C,30V,200mA,SOT-23,TP 1 PC SNA

Q500 0501-000534 TR-SMALL SIGNAL 2SC2412K,NPN,200mW,SOT-23,TP,180-390 1 PC SNA

Q400 0504-000127 TR-DIGITAL FJV3102R,NPN,200mW,10K/10Kohm,SOT-23,TP 1 PC SNA

Q401 0504-000127 TR-DIGITAL FJV3102R,NPN,200mW,10K/10Kohm,SOT-23,TP 1 PC SNA

IC200 0506-000175 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1 PC SNA

LED100 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LED101 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LED102 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LED301 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LED600 0601-001816 LED SMD,Y-GRN,1.6X0.8X0.55MM,570NM,1.6X0.8X0.55MM 1 PC SNA

LED300 0601-001954 LED SMD(TOP VIEW),YEL,1.6x0.8x0.8mm,587nm,1.6x0.8x0.8mm 1 PC SNA

LED302 0601-002345 LED SMD,RED,1.6x0.8x0.55mm,660nm,1.6x0.8x0.55mm 1 PC SNA

PC111 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC400 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC401 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC402 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC403 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC500 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC501 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC502 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

PC900 0604-001002 PHOTO-COUPLER TR,100-600%,200mW,SOP-4,TP 1 PC SNA

IC300 0801-002530 IC-CMOS LOGIC74VHCT245,TRANSCEIVER,TSSOP,20P,173MIL,OCTAL,TP,PLAS

TIC,3-STATE,-,0.36V,-40to+851 PC SNA

IC102 1203-002948 IC-POSI.ADJUST REG.TL431ACD,SOP,8P,4.9X3.9MM,PLASTIC,36V,1.5W,0TO+70C,15

0MA,2.44/2.55V,TP1 PC SNA

IC100 1203-005454 IC-POSI.FIXED REG.LD1117S33-HF,SOT-223,4P,6.5x3.5mm,PLASTIC,3.267/3.333,-

40to+125C,0.8,TP1 PC SNA

R808 2007-000043 R-CHIP 1Kohm,1%,1/10W,TP,1608 1 PC SNA

R339 2007-000070 R-CHIP 0ohm,5%,1/10W,TP,1608 1 PC SNA

R308 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R337 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R800 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R801 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R803 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R805 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R811 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R813 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R814 2007-000074 R-CHIP 100ohm,5%,1/10W,TP,1608 1 PC SNA

R325 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R326 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R327 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R500 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

INVERTER PCB(cont.)

��

Page 73: ECO HEATING SYSTEM - SOLFEX

72 Samsung Electronics

Location Code Description Spec. Q`ty UnitSA/ SNA

R502 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R506 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R900 2007-000076 R-CHIP 330ohm,5%,1/10W,TP,1608 1 PC SNA

R320 2007-000077 R-CHIP 470ohm,5%,1/10W,TP,1608 1 PC SNA

R328 2007-000077 R-CHIP 470ohm,5%,1/10W,TP,1608 1 PC SNA

R505 2007-000077 R-CHIP 470ohm,5%,1/10W,TP,1608 1 PC SNA

R305 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R306 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R307 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R309 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R310 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R312 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R313 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R314 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R317 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R318 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R319 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R501 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R503 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R504 2007-000078 R-CHIP 1Kohm,5%,1/10W,TP,1608 1 PC SNA

R809 2007-000080 R-CHIP 2Kohm,5%,1/10W,TP,1608 1 PC SNA

R100 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R105 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R109 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R111 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R600 2007-000082 R-CHIP 3.3Kohm,5%,1/10W,TP,1608 1 PC SNA

R300 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R301 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R302 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R311 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R315 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R321 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R322 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R323 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R324 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R329 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R330 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R331 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R332 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R333 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R334 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R335 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R336 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R400 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R401 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R406 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R407 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R614 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R615 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R700 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

INVERTER PCB(cont.)

��

Page 74: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 73

Location Code Description Spec. Q`ty UnitSA/ SNA

R701 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R702 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R703 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R905 2007-000084 R-CHIP 4.7Kohm,5%,1/10W,TP,1608 1 PC SNA

R403 2007-000087 R-CHIP 6.8Kohm,5%,1/10W,TP,1608 1 PC SNA

R410 2007-000087 R-CHIP 6.8Kohm,5%,1/10W,TP,1608 1 PC SNA

R812 2007-000087 R-CHIP 6.8Kohm,5%,1/10W,TP,1608 1 PC SNA

R303 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R316 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R402 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R404 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R409 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R411 2007-000090 R-CHIP 10Kohm,5%,1/10W,TP,1608 1 PC SNA

R340 2007-000109 R-CHIP 1Mohm,5%,1/10W,TP,1608 1 PC SNA

R103 2007-000111 R-CHIP 6.8ohm,5%,1/10W,TP,1608 1 PC SNA

R807 2007-000239 R-CHIP 1.5Kohm,1%,1/10W,TP,1608 1 PC SNA

R901 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R902 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R903 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R904 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R906 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R907 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R908 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R909 2007-000285 R-CHIP 100Kohm,5%,1/4W,TP,3216 1 PC SNA

R802 2007-000308 R-CHIP 10ohm,5%,1/8W,TP,2012 1 PC SNA

R804 2007-000308 R-CHIP 10ohm,5%,1/8W,TP,2012 1 PC SNA

R806 2007-000308 R-CHIP 10ohm,5%,1/8W,TP,2012 1 PC SNA

R616 2007-000385 R-CHIP 14.3Kohm,1%,1/4W,TP,3216 1 PC SNA

R113 2007-000619 R-CHIP 24ohm,5%,1/4W,TP,3216 1 PC SNA

R119 2007-000619 R-CHIP 24ohm,5%,1/4W,TP,3216 1 PC SNA

R114 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R115 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R116 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R117 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R613 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R617 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R618 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R619 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R620 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R621 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R622 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R623 2007-000924 R-CHIP 470Kohm,1%,1/4W,TP,3216 1 PC SNA

R118 2007-000929 R-CHIP 470ohm,1%,1/10W,TP,1608 1 PC SNA

R102 2007-000950 R-CHIP 47ohm,5%,1/4W,TP,3216 1 PC SNA

R110 2007-000950 R-CHIP 47ohm,5%,1/4W,TP,3216 1 PC SNA

R112 2007-000950 R-CHIP 47ohm,5%,1/4W,TP,3216 1 PC SNA

R405 2007-001118 R-CHIP 680ohm,5%,1/8W,TP,2012 1 PC SNA

R408 2007-001118 R-CHIP 680ohm,5%,1/8W,TP,2012 1 PC SNA

R341 2007-002454 R-CHIP 5.1Mohm,5%,1/10W,TP,1608 1 PC SNA

INVERTER PCB(cont.)

��

Page 75: ECO HEATING SYSTEM - SOLFEX

74 Samsung Electronics

Location Code Description Spec. Q`ty UnitSA/ SNA

R107 2007-007342 R-CHIP 1.82Kohm,1%,1/10W,TP,1608 1 PC SNA

R106 2007-007445 R-CHIP 9.09Kohm,1%,1/10W,TP,1608 1 PC SNA

R810 2007-007735 R-CHIP 91ohm,1%,1/10W,TP,1608 1 PC SNA

R601 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R602 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R603 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R604 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R605 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R606 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R607 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R608 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R609 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R610 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R611 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

R612 2007-008023 R-CHIP 100Kohm,5%,1W,TP,6432 1 PC SNA

C303 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C317 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C318 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C327 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C400 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C402 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C500 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C501 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C502 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C504 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C505 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C814 2203-000257 C-CER,CHIP 10nF,10%,50V,X7R,TP,1608 1 PC SNA

C301 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C302 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C309 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C313 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C316 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C600 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C601 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C700 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C702 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C703 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C705 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C801 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C805 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C809 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C815 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C817 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C818 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C819 2203-000440 C-CER,CHIP 1nF,10%,50V,X7R,TP,1608 1 PC SNA

C319 2203-002002 C-CER,CHIP 0.033nF,5%,50V,NP0,TP,1608 1 PC SNA

C320 2203-002002 C-CER,CHIP 0.033nF,5%,50V,NP0,TP,1608 1 PC SNA

C321 2203-002002 C-CER,CHIP 0.033nF,5%,50V,NP0,TP,1608 1 PC SNA

C322 2203-002002 C-CER,CHIP 0.033nF,5%,50V,NP0,TP,1608 1 PC SNA

C323 2203-002002 C-CER,CHIP 0.033nF,5%,50V,NP0,TP,1608 1 PC SNA

INVERTER PCB(cont.)

��

Page 76: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 75

Location Code Description Spec. Q`ty UnitSA/ SNA

C324 2203-002002 C-CER,CHIP 0.033nF,5%,50V,NP0,TP,1608 1 PC SNA

C816 2203-002398 C-CER,CHIP 22nF,10%,50V,X7R,1608 1 PC SNA

C100 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C105 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C108 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C110 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C111 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C116 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C118 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C122 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C126 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C200 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C307 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C308 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C310 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C311 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C312 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C314 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C315 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C503 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C608 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C701 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C704 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C800 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C802 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C804 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C806 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C808 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C810 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C812 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C900 2203-005249 C-CER,CHIP 100nF,10%,50V,X7R,TP,1608 1 PC SNA

C404 2203-006104 C-CER,CHIP 1000nF,10%,50V,X7R,TP,3225,2.5T 1 PC SNA

C406 2203-006104 C-CER,CHIP 1000nF,10%,50V,X7R,TP,3225,2.5T 1 PC SNA

C304 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

C305 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

C325 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

C328 2203-006348 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1 PC SNA

X300 2802-001211 RESONATOR-CERAMIC 8MHZ,0.1%,TP,3.2X1.3X0.9 MM 1 PC SNA

IC600 3201-001860 SENSOR MAG ACS710KLATR-12CB-T,37.5A,-40to+125C,8V 1 PC SNA

IC700 3201-001860 SENSOR MAG ACS710KLATR-12CB-T,37.5A,-40to+125C,8V 1 PC SNA

IC701 3201-001860 SENSOR MAG ACS710KLATR-12CB-T,37.5A,-40to+125C,8V 1 PC SNA

PCB DB41-01033A PCB MAIN-INVERTER

RC100DHXGA, RC100PHXGA, RC125PHXGA, RC125DHXGA,FR-

4,2,ver 0.8,T1.6,220*195,UB1, UB2,Outdoor,2oz, Inverter Platform #6,60

1 PC SNA

IC201 DB91-01179A ASSY-MICGlobal 4 way Outdoor Inverter MICOM,STM-1043-OS,

LM3S817, 48LQFP, ROM 64KB

1 PC SNA

DB09-00591A IC MICOMLM3S817,48,DC3V,50 MHz,LQFP,LQFP,LQFP,-40 ~

85,64KB,LQFP1 PC SNA

INVERTER PCB(cont.)

��

Page 77: ECO HEATING SYSTEM - SOLFEX

76 Samsung Electronics

Location Code Description Spec. Q`ty UnitSA/ SNA

DB93-11111A ASSY PCB SUB-EMI GLOBAL-4WAY OUTDOOR,Inverter Platform #6 3Phase EMI,N 1 PC SA

ADHESIVE- SILICON

0201-001982 ADHESIVE-SIL TSE3854DS-W,White,2.2,MIL-A-46146B,UL94V-0 0.01 KG SNA

VA01 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA02 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA03 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA04 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA05 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA06 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA07 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA08 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA09 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

VA10 1405-001204 VARISTOR 670Vdc,4500A,17x6.3mm,BK 1 PC SNA

R01 2003-002038 R-METAL OXIDE(S) 1Mohm,5%,2W,AA,TP,4x12mm 1 PC SNA

R02 2003-002038 R-METAL OXIDE(S) 1Mohm,5%,2W,AA,TP,4x12mm 1 PC SNA

R03 2003-002038 R-METAL OXIDE(S) 1Mohm,5%,2W,AA,TP,4x12mm 1 PC SNA

YC01 2201-000024 C-CERAMIC,DISC 4.7nF,20%,250V,Y5U,TP,16x7mm,7.5mm 1 PC SNA

YC02 2201-000024 C-CERAMIC,DISC 4.7nF,20%,250V,Y5U,TP,16x7mm,7.5mm 1 PC SNA

C11 2201-000153 C-CERAMIC,DISC 10nF,+80-20%,250V,Y5V,-,14.6x6mm,7.5 1 PC SNA

C12 2201-000153 C-CERAMIC,DISC 10nF,+80-20%,250V,Y5V,-,14.6x6mm,7.5 1 PC SNA

C13 2201-000153 C-CERAMIC,DISC 10nF,+80-20%,250V,Y5V,-,14.6x6mm,7.5 1 PC SNA

C14 2201-000153 C-CERAMIC,DISC 10nF,+80-20%,250V,Y5V,-,14.6x6mm,7.5 1 PC SNA

C08 2301-001285 C-FILM,LEAD-PPF 680nF,10%,275V,BK,31x11x21mm 1 PC SNA

C09 2301-001285 C-FILM,LEAD-PPF 680nF,10%,275V,BK,31x11x21mm 1 PC SNA

C10 2301-001285 C-FILM,LEAD-PPF 680nF,10%,275V,BK,31x11x21mm 1 PC SNA

C01 2301-001853 C-FILM,LEAD 2200nF,10%,275V,BK,18X28X31 1 PC SNA

C02 2301-001853 C-FILM,LEAD 2200nF,10%,275V,BK,18X28X31 1 PC SNA

C03 2301-001853 C-FILM,LEAD 2200nF,10%,275V,BK,18X28X31 1 PC SNA

F101-1 3601-001426 USE-CARTRIDGE 500,25A,SLO-BLO,FIBER,10.3x38.1mm 1 PC SNA

F102-1 3601-001426 USE-CARTRIDGE 500,25A,SLO-BLO,FIBER,10.3x38.1mm 1 PC SNA

F103-1 3601-001426 USE-CARTRIDGE 500,25A,SLO-BLO,FIBER,10.3x38.1mm 1 PC SNA

F101 3602-001040 FUSE-CLIP 250,30A,4MOhm 1 PC SNA

F102 3602-001040 FUSE-CLIP 250,30A,4MOhm 1 PC SNA

F103 3602-001040 FUSE-CLIP 250,30A,4MOhm 1 PC SNA

CN01 3711-000203 HEADER-BOARD TO CABLE 1WALL,2P/3P,1R,7.92mm,STRAIGHT,SN,WHT 1 PC SNA

R-OUT 3712-001139 CONNECTOR-TERMINAL TAB,MALE,6.35x0.8mm 1 PC SNA

S-OUT 3712-001139 CONNECTOR-TERMINAL TAB,MALE,6.35x0.8mm 1 PC SNA

T-OUT 3712-001139 CONNECTOR-TERMINAL TAB,MALE,6.35x0.8mm 1 PC SNA

FT11 DB27-00033A COIL CHOKE FILTER,S50,-0%,5A,14mH 1 PC SNA

FT01 DB27-00039A COIL CHOKESSC5122020B,UH140GAV,2mH,+-

20%,50mOHM,18A,Ф51x31x13,14,Ф 51x31x13, PBT,21,2.2,BOX,-25 to +85C

1 PC SNA

FT02 DB27-00039A COIL CHOKESSC5122020B,UH140GAV,2mH,+-

20%,50mOHM,18A,Ф51x31x13,14,Ф 51x31x13, PBT,21,2.2,BOX,-25 to +85C

1 PC SNA

PCB DB41-01035A PCB SUB-EMIGLOBAL-4WAY OUTDOOR,FR-4,2,ver 2.3,T1.6,130*230,UB1,

UB2,Outdoor,Inverter Platform #6 EMI,6001 PC SNA

DSA01 DB47-00016A POSISTOR DSA-332MA,2pF MAX,100MOhm,ASM-3500 1 PC SNA

ASSY CW EARTH

DB93-05379FASSY CONNECTOR WIRE-

EARTHRC140RHXEA 1 PC SNA

ASSY CW POWER-RSTN

DB93-10811AASSY CONNECTOR WIRE-EMI

TO TERMINAL POWERC160RHXH1 1 PC SNA

ASSY CW POWER-TN

DB93-10871AASSY CONNECTOR WIRE-

POWERRC160RHXH1 1 PC SNA

EMI PCB

��

Page 78: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 77

REF Part No. Spec

CN02 3711-003406 HEADER-BOARD TO CABLE;1WALL,2P,1R,7.92MM,STRAIGHT, (YEL)

CN03 3711-000203 HEADER-BOARD TO CABLE;1WALL,2P/3P,1R,7.92mm,STRAIG (WHT)

FUSE-L 3602-001012 FUSE-BLOCK;500V,-,100MOhm

FUSE-L 3601-000416 250V,1A,FAST-ACTING,GLASS,5.2x20mm

FUSE-N 3602-001012 FUSE-BLOCK;500V,-,100MOhm

FUSE-N 3601-000416 250V,1A,FAST-ACTING,GLASS,5.2x20mm

JP01 DB47-90005A JUMPER WIRE;TA0.6PI/52MM,P0509-400-108,-,-

VA01 1405-000154 VARISTOR;460Vdc,4500A,17.5x7.5mm,BK,920V,600pF

PCB DB41-01132A PCB SUB - HEATER

HEATER PCB

��

Page 79: ECO HEATING SYSTEM - SOLFEX

78 Samsung Electronics

6. Wiring Diagram

6-1 Control Kit

Sensor part

This Document can not be used without Samsung’s authorization.

��

Page 80: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 79

6-2 Outdoor Unit

3Phase / 2FAN Model Diagram

This Document can not be used without Samsung’s authorization.

��

Page 81: ECO HEATING SYSTEM - SOLFEX

Wiring Diagram

80 Samsung Electronics

1Phase / 2FAN Model

This Document can not be used without Samsung’s authorization.

��

Page 82: ECO HEATING SYSTEM - SOLFEX

MEMO

Samsung Electronics 81

��

Page 83: ECO HEATING SYSTEM - SOLFEX

82 Samsung Electronics Samsung Electronics 83

7. Schematic Diagram

7-1 Control Kit

VCC

GND

MODE

DYNAMIC_GRID1

RST

DYNAMIC_GRID2

R310

0.1WJ

10K

21

Solar_N

R417

F6.8K

1/10W

21

CE104470uF25V

2

1

C607

25V100nF

2

1

C608100nF25V

2

1

C17100nF50V

21

R60110K

J0.1W

21

C606100nF25V

2

1

R604

10K

J0.1W

21

50V100nFC12

21

C31510nF50V

2

1

PC304

50-600%TLP180

4 3

5 2

6 1

12V

0.1WJ

10K

R603

21

Thermo_12V

YELSMW250-02

T4

2

1

CE109

25V470uF

2

1

CE10547uF50V

2

1

CN510

SMW250-03WHT

3

2

1

CN600

YW396-02VRED

2

1

93LC56

IC4

5 4

6 3

7 2

8 1CSVCC

CLKNC_7

DINC_6

DOVSS

C16

25V100nF

2

1

T3

SMW250-06WHT

6

5

4

3

2

1

330J 0.1W

R821

12V

R300

56K J 2W

21

TB-C

DAPC-2009-6P

6

5

4

3

2

1

DYNAMIC_GRID3

Neutral_

100nF25V

C15

2

1

100nF25V

C14

2

1

F_R_N

SOLAR_TEMP_SENSOR

R303

56K J 2W

21

CN601-1

SMW250-04RED

4

3

2

1

0.2WDTA114EKA

Q904

2

1

3

OI

G

C13

2

1100nF

25V

VCC

RY500

PCFN-112D2M

23

14

12V

PIPE_SUC_TEMP

R150-2

2WJ56K

21

C31410nF50V

2

1

Neutral_

R181

0.1WJ

10K

21

0.1WJ

10K

R341

21

R156

0.1WJ1K

21

C152

50V10nF

2

1

0.1WJ10KR7

21

R304-1

56K J 2W

21

R302

56K J 2W

21

C302

50V100nF

2

1

L600

CV305400SJ40m

3 2

4 1

RXD_MAINOUT

1N4148WS

75V150mA

D1

21

C303100nF50V

2

1

C300

50V100nF

2

1

0.1WJ330

R41821

25V100nFC605

2

1

GND

C60410nF50V

2

1

0.1WJ

1K

R607

21

C603100nF25V

2

1

WATER_TANK_SENSOR

25V100nF

C602

2

1

C601100nF25V

2

1

C60010nF50V

2

1

CD605

21

2W2_NO

2W2_NC

CN601-2

REDSMW250-04

4

3

2

1

DA38-362M

DSA100

21

RY502

PCJ-112D3MH

6 3

2 5

41

GND

WATER_IN_TEMP

R412

1/10W

6.8KF

21

R416

330J 0.1W

21

D500

1N4148WS75V150mA

21

0.1W

F24K

R415

21

R414

24KF0.1W2

1

R304-2

2WJ56K

21

R150-1

56K J 2W

21

12V

0.1WJ330

R41321

R905

0.1WJ3.3K

21

MM74HC86M

IC602

8 7

9 6

10 5

11 4

12 3

13 2

14 1VCC

GND

R408

F6.8K

1/10W

21

C304

50V100nF

2

1

S1

SSR-10C

5

4321b3

b2

b1

b0

C

PIPE_DIS_TEMP

R411

1/10W

6.8KF

21

R410

F6.8K

1/10W

21

C901

50V10nF

2

1

0.1WJ10KR900

21

Q1502SC2412K0.2W

2

1

3

CB

E

D900

1N4148WS75V150mA

21

0.1WJ

10K

R602

21

2WAY3

D901

21

2WAY3

1300MN-4P

TB-A

4

3

2

1

S2SSR-16C

5

4321b3

b2

b1

b0

C

RY_2WAY_3

Thermo_Feedback

S3

BSD-104

54

63

72

81

R407

330J 0.1W

21

0.1WJ

10K

R608

21

R405

1/10W

6.8KF

21

Neutral

D902

21

D903

21

CD604

21

600W7.1V

SMBJ5.0CACD603

21

CD602

21

CN2

SMW200-10BLK

10

9

8

7

6

5

4

3

2

1

1W2003

IC1

2

161

15

3 14

4 13

5 12

6 11

7 10

8 9VCCGND

O7I7

O6I6

O5I5

O4I4

O3I3

O2

I1 O1

I2

ZCP

CE103

25V1000u

2

1

DYNAMIC_DATA7

DYNAMIC_DATA6

S4

BSD-104

54

63

72

81

GND

Fused_Live

CN4

SMW200-07BLK

7

6

5

4

3

2

1

F100

250V T5A

21

C301100nF50V

2

1

DYNAMIC_DATA5

DYNAMIC_DATA4

Live

RY503

PCJ-112D3MH

6 3

2 5

41

AGND

LED901

1.6x0.8mmYEL

2 1

C400

100nF25V

2

1

DC310V

R108

21

Neutral_

R60010K

J0.1W

21

Live_Heater

2W3_NO

Fused_Live

D904

21

Live

DC_Ther1-1

D905

21

D906

21

WATER_OUT_TEMP

LED_COM1

Neutral

D907

21

D908

21

DYNAMIC_GRID2

0.2WDTA114EKA

Q903

2

1

3

OI

G1W2003

IC900

2

161

15

3 14

4 13

5 12

6 11

7 10

8 9VCCGND

O7I7

O6I6

O5I5

O4I4

O3I3

O2

I1 O1

I2

C15310nF50V

2

1

HEATER_OUT_TEMP

CD601

21

DC_Ther2-2Neutral

Smart_grid

25V100nF

C410

2

1

LED_COM2

12V

0.1WJ

3.3K

R182

21

R420

330J 0.1W

21

PC300

TLP18050-600%

4 3

5 2

6 1

R323

0.1WJ

10K

21

TOP255YN

IC100

4

53

62

71V D

X NC

C G

S

1.6x0.8mmRED

LED900

2 1

0.1WJ330

R40621

TE1

wire_hole_2.61

25V100nF

C11

21

Live_Heater

C411

100nF25V

2

1

CN5

SMW250-03YEL

3

2

1

R5

10K J 0.1W

21

TB-B

DB65-00329A

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

D909

21

D910

21

D911

21

D912

21

Neutral_

BOILER

BCK_HT2

PUMP

R60510K

J0.1W

21

Neutral_

0.1WJ

1K

R157

21

2W1_NO

25V100nFC9

2

1

2W1_NC

25V100nF

C412

2

1

R901

0.1WJ10K

21

D913

21

R90210KJ

0.1W

21

R90310KJ

0.1W

21

50V10nFC900

2

1

C90210nF50V

2

1

C903

50V10nF

2

1

R904

3.3K J 0.1W

21

D914

21

CN3

SMW250-04YEL

4

3

2

1

0.1W

J0R510

21

D915

1N4148WS75V150mA

21

VA102

560VINR14D561K

21

2W3_NC

DYNAMIC_GRID5

Fused_Live

VCCVCC

C413

100nF25V

2

1

C414

100nF25V

2

1

DYNAMIC_GRID4

VCC

VCC

ROOM

DC_Ther2-1

GND

VCC

DC_Ther1-2

DYNAMIC_GRID3

VCC

VCC

CN1

SMW250-06BLU

6

5

4

3

2

1

DYNAMIC_GRID2

DYNAMIC_GRID1

TXD_MAINOUT

VCC

12V

GND

COM2_RXD

Neutral_

GND

REDSMW250-02

S/G

2

1

DC_Ther1-2

VCC

DC_Ther1-1

Fused_Live

Q304

2SC2412K0.2W

2

1

3

CB

E

DC_Ther2-1

12V

EXT_CTRL_2_HEATINGDC_Ther2-2

12V

DYNAMIC_GRID0

12V

HYDRO_LED

VCC

VCC

Smart_grid

VCC

DYNAMIC_DATA6DYNAMIC_DATA6

Neutral_

GND

T5

SMW250-02BLK

2

1

PCH-112D2RY507

4

3 2

5 1

DYNAMIC_DATA4DYNAMIC_DATA4

FLOW_SW

COM1_INVERSE

WATER_TANK_SENSOR

0.1WJ330

R41921

0.1WJ330

R42221

VCC

DYNAMIC_GRID4

C308

50V10nF

2

1

COM1_RXD

VA100

INR14D561K560V

21

LED_COM2

GRID0

GRID3

COM1_RXD

LED_COM1

RY_BOILER_CTRL

ZCP

4MHzCSTCR4M00G55-R0

X1

2

31

R344

0.1WJ

1K

21

DYNAMIC_DATA7DYNAMIC_DATA7

TMS

DYNAMIC_DATA5DYNAMIC_DATA5

BLUYW396-02V

F/S

2

1

TDI

C309

50V10nF

2

1

PC302

TLP18050-600%

4 3

5 2

6 1

H_U_PUMP

COM2_RXD

T2

SMW250-04WHT

4

3

2

1

50-600%TLP180

PC150

43

52

61

Fused_Live

TCK

PC303

TLP18050-600%

4 3

5 2

6 1

0.1W

F18K

R421

21

GRID2

C31310nF50V

2

1

PC301

50-600%TLP180

4 3

5 2

6 1

L2C

GND

GRID2

R343

1K

J0.1W

21

COM2_ENABLE

0.1W

F18K

R423

21

R329

1K

J0.1W

21

GRID5

L2H

GRID3

COM1_ENABLE

TDO

PC100

TLP181-GB100-600%

4 3

5 2

6 1

EXT_CTRL_2_COOLING

COM1_TXD

TDO

R424

18KF0.1W2

1

0.2W2SC2412K

Q303

2

1

3

CB

E

R400

330J 0.1W

21

COM1_INVERSE

COM1_ENABLE

VCC

0.1W

F24K

R425

21

H_U_PUMP_CTRL

GRID5

2WJ100KR350

21

Neutral_

0.1W

F18K

R426

21

HYDRO_LED_12V

COM2_INVERSE

COM1_TXD

25V100nF

C401

2

1

DYNAMIC_GRID5

R427

330J 0.1W

21

GND

C2_1

L1H

L1C

Fused_Live

C181

50V100nF

2

1

C2_2

C402

100nF25V

2

1

Solar_L

C2_1

25V100nF

C403

2

1

C404

100nF25V

2

1

25V100nF

C405

2

1

GRID0

COM2_TXD

C406

100nF25V

2

1

COM1_TXD

C2_2

R609

1/10W120

J

21

25V100nF

C407

2

1

C408

100nF25V

2

1

R340

1KJ 0.1W

2 1

DYNAMIC_GRID0 TCK

TDI

TMS

VCC

C316

50V10nF

2

1

RY504

PCJ-112D3MH

6 3

2 5

41

IC600

MAX1487ESA

5 4

6 3

7 2

8 1VCC

GND

D

R

R60610K

J0.1W

21

IC101TL431AILP

1

23C

A

R

IC601

MAX1487ESA

54

63

72

81 VCC

GND

D

R

R3512WJ100K

21

T1

SMW250-02WHT

2

1

1W

IC3

2003

2

161

15

3 14

4 13

5 12

6 11

7 10

8 9VCCGND

O7I7

O6I6

O5I5

O4I4

O3I3

O2

I1 O1

I2

0.1WJ

3.3K

R10221

0.1WJ

330R104

21

0.1WJ

1KR103

21

0.1WJ

6.8

R110

21

C610100nF25V

2

1

EEV_B

C111100nF25V

2

1

C130100nF25V

2

1

C100

25V100nF

2

1

C102100nF25V

2

1

C104

25V100nF

2

1

C103100nF25V

2

1

R109

0.25WJ

3.6K

21

100nF25V

C8

2

1

TS1

SMW250-03RED

3

2

1

C904

25V100nF

2 1

HYDRO_LED

TS2

SMW250-03BLU

3

2

1

C611

25V100nF

2

1

C612

25V100nF

2

1

C609100nF25V

2

1

C650100nF25V

2

1

EEV_B1

T100

DB26-00128A*

65

74

83

92

101

BD100

1A600VDF06S

3

14

2

DYNAMIC_GRID0

2WJ56K

R30121

COM2_ENABLE

R92

1/10W680

J

21

EEV_A1

BACK_UP_HEATER1

RY_2WAY_1

EEV_A

100-600%TLP181-GB

PC92

43

52

61

PC91

100-600%TLP181-GB

4 3

5 2

6 1

COM1_RXD

COM2_INVERSE

C150

50V100nF

2

1

COM2_TXD

GND

C9210nF50V

2

1

C91

50V10nF

2

1

0.1WJ330

R40121

R6

1/10W1K

F

21

EEV_A1

EEV_B1

EEV_B

EEV_A

H_U_PUMP_CTRL

BOILER_CTRL

C9310nF50V

2

1

GND

VCC

25V1000nFC10

2

1

0.1WJ

1M

R1

21

EXT5V

0.1WJ

47K

R3

21

R4

0.1WJ

47K

21

VCC

0.1WJ330

R40221

VCC

GND

RST

GND

GND

VCC

BCK_HT_1

R328

0.1WJ1K

21

FLOW_SW

SOLAR_TEMP_SENSOR

EXT_CTRL_1_HEATING

HEATER_OUT_TEMP

WATER_OUT_TEMP

R91

1K

J0.1W

21

EXT5V

EXT5V

WATER_IN_TEMP

PIPE_DIS_TEMP

PIPE_SUC_TEMP

ROOM

VCC

EXTGND

EXTGND

BOOST_HEATER

BACK_UP_HEATER2

BACK_UP_HEATER1

2WAY1

2WAY2

C305

50V10nF

2

1

Q3022SC2412K

0.2W

2

1

3

CB

E

EXT_CTRL_1_HEATING

EXT_CTRL_1_COOLING

EXT_CTRL_2_HEATING

R93

J

6801/10W

21

150mA75V1N4148WS

D18021

EXT_CTRL_2_COOLING

R94

0.1WJ

1K

21

Neutral_

SOLAR_PUMP_OP

VCC

VCC

VCC

GND

GND

TXD_MAINOUT

RXD_MAINOUT

GND

C30710nF50V

2

1

VA101

21

GND

IC2S3F4A1HKZZ-TX8H

50

49

48

47

46

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

5125

5224

5323

5422

5521

5620

5719

5818

5917

6016

6115

6214

6313

6412

6511

6610

679

688

697

706

715

724

733

742

751

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

96

97

98

99

100

VSSIO0

VDDIO0

VDDCORE0

VSSCORE0

VDDCOREOUT

XOUT

XIN

TMS

TDI

TCK

TD0

NRESET/NTRST

AVSS

AVREF

AVDD

P2.15/TIOB2/AIN15

P2.14/TIOA2/AIN14

P2.13/CAPT0/AIN13

P2.12/IRQ11/AIN12

P2.11/IRQ10/AIN11

P2.10/AIN10

P2.9/AIN9

P2.8/AIN8

P2.7/AIN7

P2.6/AIN6

VDDPLLOUT P2.5/AIN5

P0.0/NSS0/SM00 P2.4/AIN4

P0.1/MISO0/SM01 P2.3/AIN3

P0.2/MOSI0/SM02 P2.2/AIN2

P0.3/SPCK0/SM03 P2.1/AIN1

P0.4/IRQ0/SM10 P2.0/AIN0

P0.5/TCLK0/SM11 P1.31/ADTRG/SCL0

P0.6/TCLK1/SM12 P1.30/IRQ9/SDA0

P0.7/TCLK2/SM13 P1.29/CANTXD1/SEG29

P0.8/UARTRXD1/SM20 P1.28/CANRXD1/SEG28

P0.9/UARTTXD1/SM21 P1.27/PWM1/SEG27

P0.10/TIOA1/SM22 P1.26/PWM0/SEG26

P0.11/TIOB1/SM23 P1.25/SPCK1/SEG25

P0.12/IRQ1/SM30 P1.24/MOSI1/SEG24

P0.13/USARTCLK0/SM31 P1.23/MISO1/SEG22

P0.14/USARTRXD0/SM32 P1.22/NPCS0/SEG20

P0.15/USARTTXD0/SM33 P1.21/NPCS1/SEG21

VDDIO2 P1.20/NPCS2/SEG20

VSSIO2 P1.19/NPCS3/SEG19

P0.16/CANRXD0/IRQ2 P1.18/IRQ8/SEG18

P0.17/CANTXD0/IRQ3 P1.17/IRQ7/SEG17

P0.18/UARTRXD0/IRQ4 P1.16/IRQ6/SEG16

P0.19/UARTTXD0/IRQ5 P1.15/SEG15

P0.20/TIOA0/SDA1 P1.14/SEG14

P0.21/TIOB0/SCL1 P1.13/SEG13

MD1

MD0

VDDIO1

VSSIO1

VDDCORE1

VSSCORE1

VPP

VLCD

P0.22/COM0

P0.23/COM1

P0.24/COM2

P0.25/COM3

P1.0/SEG0

P1.1/SEG1

P1.2/SEG2

P1.3/SEG3

P1.4/SEG4

P1.5/SEG5

P1.6/SEG6

P1.7/SEG7

P1.8/SEG8

P1.9/SEG9

P1.10/SEG10

P1.11/SEG11

P1.12/SEG12

2WAY1

RY_BOOST_HEATER

RY_BACK_UP_HEATER2

BOILER_CTRL

BOOST_HEATER

2WAY2RY_2WAY_2

BACK_UP_HEATER2

MODE

100nF25V

C6

2

1

GND

C5100nF25V

2

1

GND

R404

1/10W

6.8KF

21

R32010K

J0.1W

21

R342

0.1WJ

10K

21

GND

R117

1/4W1M F

21

R2

120

J0.1W

21

100nFC4

25V

2

1

R116F1M

1/4W

21

R115

1/4W1M F

21

GND

C3

25V100nF

2

1

R111F1M

1/4W

2 1

C2100nF

25V

2

1

HYDRO_LED_12V

GND

25V1000nF

C1

21

GND

GND

7.1V600W

CD600SMBJ5.0CA

21

R114

1/4W4.7K

J

21

R113

J

4.7K1/4W

21

0.2WDTA114EKA

Q9022

1

3

OI

G

Q901

DTA114EKA0.2W

2

1

3

OI

G

R112

1/4W4.7K

J

21

RY_BACK_UP_HEATER1

GND

C101

50V100n

21

RY501

PCJ-112D3MH

6 3

2 5

41

1N4148WS

75V150mA

D2

21

R200

1/10W

10KJ

21

VCC

0.1WJ330

R40921

GND

GND

R316

1K

J0.1W

21

EXT_CTRL_1_COOLING

R315

0.1WJ1K

21

VCC

C31710nF50V

2

1

R305

1K J 0.1W

21

Q3012SC2412K

0.2W

2

1

3

CB

E

R306

0.1WJ

1K

21

GND

50V100nFC7

2

1

R345

0.1WJ1K

21

VCC

C30610nF50V

2

1

0.2W2SC2412K

Q300

2

1

3

CB

E

150mA75V

1N4148WS

D3

21

1N4148WS

75V150mA

D4

21

150mA75V

1N4148WS

D5

21

1N4148WS

75V150mA

D6

21

150mA75V

1N4148WS

D7

21

0.1WJ3.3K

R50121

R500

0.1WJ3.3K

21

R502

0.1WJ3.3K

21

R503

3.3K J 0.1W

21

R504

0.1WJ3.3K

21

R505

0.1WJ3.3K

21

R506

3.3K J 0.1W

21

R507

0.1WJ3.3K

21

0.1WJ

10K

R180

21

0.1WJ

10K

R150

21

R183

1K

J0.1W

21

Thermo_Feedback

RY_2WAY_3

Fused_Live

BOILER

LED500YEL1.6x0.8mm

21

LED503YEL1.6x0.8mm

21

20A250V

F50021

RY_2WAY_2

RY_BACK_UP_HEATER1

RY_BACK_UP_HEATER2

Fused_Live

RY_BOOSTER_HEATER

RY_2WAY_12W1_NC

Thermo_12V

Thermo_12V

Live

H_U_PUMP

2W1_NO

2W2_NO

GND

RY_BOILER_CTRL

LED501

YEL1.6x0.8mm

21

12V

Fused_Live

BCK_HT_1

BCK_HT2

1.6x0.8mmYEL LED502

21

12V

12V

Fused_Live

PUMP

1.6x0.8mmYEL

LED504

21

12V

PCH-112D2RY505

4

3 2

5 1

Fused_Live

LED505YEL1.6x0.8mm

21

12V

RY506PCH-112D2

4

3 2

5 1

Fused_Live

2W2_NC

1.6x0.8mmYEL

LED506

21

12V

2W3_NC

12V

LED507

YEL1.6x0.8mm

21

2W3_NO

Fused_Live

BEAD10030ohm

21

C109

2KV1nF

2

1

R107

2WJ

47K

21

D104

1A1KV

1N4007

21

D103

2A200VUG2D

21

AGND

C108

400V2.2nF

21

C1072.2nF400V

21

CE106

50V47uF

2

1

D1024A200VUG4D

21

C1062KV1nF

21

R1060.5WJ22

21

L1012000A4.7uH

21

CE102470uF25V

2

1

GND

D100

2A200VUG2D

21

C1053KV82pF

21

R1050.5WJ22

21

L100

2000A4.7uH

21

R10110K

F0.125W

21

CE101

50V10uF

2

1

GND

R100

0.125WF

10K

21

D101

21

DC310V

XC100470nF275V

2

1FT100

14mH5A

3 2

4 1

XC101

275V470nF

2

1

NTC100

1.4A22

21

CE10047uF450V

2

1

F101

250V 1A

21

12V

12V

12V

12V

12V

12V

12V

12V

12V

12V

GRID3

GRID5

GRID5

GRID0 GRID2

FLOW_SW

FLOW_SW

DYNAMIC_DATA4

DYNAMIC_DATA4

DYNAMIC_DATA7

DYNAMIC_DATA7

DYNAMIC_DATA6

DYNAMIC_DATA6

DYNAMIC_DATA5

DYNAMIC_DATA5

COM2_ENABLE

COM2_ENABLE

COM2_INVERSE

COM2_INVERSE

COM2_TXD

COM2_TXD

COM2_RXD

COM2_RXD

COM1_ENABLE

ZCP

ZCP

COM1_TXD

COM1_TXD

COM1_TXD

COM1_RXD

COM1_RXD

COM1_INVERSE

COM1_INVERSE

LED_COM1

LED_COM1

LED_COM2

LED_COM2

MODE

TDO

TDO

TCK

TCK

TDI

TDI

TMS

TMS

WATER_OUT_TEMP

WATER_OUT_TEMP

WATER_IN_TEMP

WATER_IN_TEMP

SOLAR_TEMP_SENSOR

SOLAR_TEMP_SENSOR

WATER_TANK_SENSOR

WATER_TANK_SENSOR

RST

RST

ROOM

ROOM

DYNAMIC_GRID2

DYNAMIC_GRID2

DYNAMIC_GRID2

DYNAMIC_GRID1

DYNAMIC_GRID1

DYNAMIC_GRID0

DYNAMIC_GRID0

DYNAMIC_GRID0

VCC

VCC

VCC

H_U_PUMP_CTRL

H_U_PUMP_CTRL

H_U_PUMP

H_U_PUMP

RY_BACK_UP_HEATER2

RY_BACK_UP_HEATER2

RY_BACK_UP_HEATER1

RY_BACK_UP_HEATER1

GND

GND

GND

GND

GND

GND

GNDGND

RY_BOILER_CTRL

RY_BOILER_CTRL

BOILER_CTRL

BOILER_CTRL

EEV_A1

EEV_A1

EEV_B1

EEV_B1

EEV_B

EEV_B

EEV_A

EEV_A

C2_2

C2_2

C2_1

C2_1

PIPE_DIS_TEMP

PIPE_DIS_TEMP

PIPE_SUC_TEMP

PIPE_SUC_TEMP

HEATER_OUT_TEMP

HEATER_OUT_TEMP

HYDRO_LED

HYDRO_LED

BOOST_HEATER

BOOST_HEATER

BACK_UP_HEATER1

BACK_UP_HEATER1

BACK_UP_HEATER2

BACK_UP_HEATER2

DYNAMIC_GRID5

DYNAMIC_GRID5

EXT_CTRL_2_COOLING

EXT_CTRL_2_COOLING

RY_BOOST_HEATER

RY_BOOST_HEATER

SOLAR_PUMP_OP

SOLAR_PUMP_OP

EXT_CTRL_1_COOLING

EXT_CTRL_1_COOLING

EXT_CTRL_1_HEATING

EXT_CTRL_1_HEATING

EXT_CTRL_2_HEATING

EXT_CTRL_2_HEATING

L2C

L2C

L1H

L1H

L1C

L1C

Live_Heater

Live_Heater

Thermo_12V

Thermo_12V

Thermo_12V

Thermo_Feedback

Thermo_Feedback

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

Fused_Live

RY_2WAY_2

RY_2WAY_2

RY_2WAY_3

RY_2WAY_3

RY_2WAY_1

RY_2WAY_1

2WAY2

2WAY2

2WAY1

2WAY1

2WAY3

2WAY3

Smart_grid

Smart_grid

Neutral

Neutral

Neutral

2W3_NO

2W3_NO

2W3_NC

2W3_NC

2W2_NC

2W2_NC

2W2_NO

2W2_NO

2W1_NC

2W1_NC

2W1_NO

2W1_NO

PUMP

PUMP

BOILER

BOILER

BCK_HT2

BCK_HT2

BCK_HT_1

BCK_HT_1

AGND

Live

Live

Live

DYNAMIC_GRID3

DYNAMIC_GRID3

DYNAMIC_GRID4

DYNAMIC_GRID4

DC310V

DC310V

Solar_L

Solar_L

Solar_N

Solar_N

F_R_N

F_R_N

F_R_N

F_R_N

F_R_N

L2H

L2HDC_Ther1-1

DC_Ther1-1

DC_Ther1-2

DC_Ther1-2

DC_Ther2-1

DC_Ther2-1

DC_Ther2-2

DC_Ther2-2

HYDRO_LED_12V

HYDRO_LED_12V

EXTGND

RXD_MAINOUT

RXD_MAINOUT

TXD_MAINOUT

TXD_MAINOUT

Neutral_

Neutral_

Neutral_

Neutral_

Neutral_

Neutral_

Neutral_

Neutral_

Neutral_

AC230V INPUT

103WT

AC230V INPUT

TO OUTDOOR UNIT

SELECT

TO WIRED RMC

HEATER DETECT

SMART GRID

THERMOSTAT1-2

BUFFER

EXT_CTRL_PART

DOWNLOAD

THERMOSTAT2-1

103WT

103WT

THERMISTOR

SMART GRID

THERMOSTAT1-1

103WT

103WT

THERMOSTAT2-2

DC THERMOSTAT

THERMOSTAT1-C

MICOM

POWER

RS-485 COMMUNICATIONZCP DETECT

SOLAR PUMP OP.

THERMOSTAT2-C

SELECT

(M/C Drive)

SILK; 250V T5A

#3,4 ; HEATER POWER OUTPUT

103WT

204CTB

204CTB

25W SMPS

#1 & #96 must bypass over 1.1uF capacitor.And contact tight within 5mm

* RECOMMANDATION *

EEV

#1,2 ; MAIN POWER INPUT

DOWNLOAD

FLOW SWITCH

MICOM TEST

* OPTION

* OPTION

Boiler

Booster Heater

Back_up_Heater

LOAD CONTROL

* OPTION

NC

Water_Pump

(3KW Direct Drive)

(M/C Drive)

* OPTION

2way_Valve1

2way_Valve2

2way_Valve3 NO

NO

NO

NC

NC

* OPTION

* OPTION

* OPTION

* OPTION

* OPTION

* OPTION

* OPTION

* OPTION

SMPS

This Document can not be used without Samsung’s authorization.

AC Power part

Sensor part

AC Zero Cross circuit part

Communication part

��

Page 84: ECO HEATING SYSTEM - SOLFEX

84 Samsung Electronics

This Document can not be used without Samsung’s authorization.

YELYW396-03AV

CN02

3

2

1

BLK

YW396-03AV

CN01

321

V052 A1F

FUSE-L21

FUSE-N

V052 A1F

21

560V

INR14D561K

VA01

21

560V

INR14D561K

VA03

21

VA02

2

560V

INR14D561K

1

JUMPER

JP0121

JUMP

*wire_hole_2.4

TE1

1

OPTIONSELECT

POWERINPUT CONNECTION

HEATER

EARTH WIRETHERMO

STAT

HEATER PBA

7-2 Outdoor Unit

��

Page 85: ECO HEATING SYSTEM - SOLFEX

Samsung Electronics 85

8. Reference Sheet

8-1 Index for Model Name

8-1-1 Outdoor Unit

Model Code

RC 160 M

Product group

R C Single(EHS)

Capacity (3 Digit)

HP / kW / BTU / TON

H

Product notation

E ECO Heating(Single)

P ECO Heating(Multi), TDM

M Mono Type

H High Temp Split Type

N High Temp Mono Type

Mode

C C/O

H H/P

T TROPICAL C/O

Q TROPICAL H/P

Refrigerant

R R22

X R410A

X

Rating voltage

A 115V, 60Hz

B 220V, 60Hz

C 208~230V, 60Hz

D 200~220V, 50Hz

E 220~240V, 50Hz

F 208~230V, 60Hz, 3Phase

G 380~415V, 50Hz, 3Phase

M 127V, 50Hz

H 380V, 60Hz, 3Phase

J 460V, 60Hz, 3Phase

Version

1~9Change point (Korean market)

A~ZChange point(export/foreign market)

AG / SER

*Buyer Name

��

Page 86: ECO HEATING SYSTEM - SOLFEX

86 Samsung Electronics

8-2 Refrigerant Circuit Diagram

Part Description

PHE Plate heat exchanger

T/S #1 For water outlet temp sensor

T/S #2 For water inlet temp sensor

T/S #3 For PHE in temp

T/S #4 For PHE out temp

T/S #5 For discharge temp

T/S #6 For cond temp

T/S #7 For ambient temp sensor

S/V Service valve ¼ inch

Accum Accumulator

PHE

T/S #3

T/S #4

S/V S/V

4WAY v/v

T/S #5

Comp

Filter

HP s/w

FilterExp. v/v

AccumT/S #6

T/S #7

T/S #1

T/S #2

This Document can not be used without Samsung’s authorization.

��

Page 87: ECO HEATING SYSTEM - SOLFEX

This Service Manual is a property of Samsung Electronics Co., Ltd.Any unauthorized use of Manual can be punished under applicableInternational and/or domestic law.

© Samsung Electronics Co., Ltd. Jan. 2012. Printed in Korea. Code No. DB98-34513A(1)