  • IMFRTVDC-0209

    I N S T R U C T I O N M A N U A L

    FRT12 FLOW RATE TOTALISER

    Universal Mount Series

    Distributed by:

  • TABLE OF CONTENTS 1. INTRODUCTION 1.1 Model number designation 2 1.2 Specifications 3 1.3 Overview 4 1.4 LCD displays 4

    2. OPERATION 2.1 Accumulative total display 5 2.2 Resettable total display 5 2.3 Rate display 5 2.4 Low frequency cut-off 5 2.5 Inhibit total function 5 2.6 Keypad function matrix 6

    3. INSTALLATION 3.1 Mounting - wall / surface mount 6 - pipe mount 7 - panel mount 7 3.2 Flowmeter connections - unpowered sensors 8 - powered sensors 9 3.3 Wiring connections - external powering 10 - 4~20mA loop powering 10 - wiring requirements 10 - pulse outputs 11 - alarm outputs 11 - remote switches 18

    4. PROGRAM PARAMETERS 4.1 PIN number program protection 12 4.2 Resetting accumulative total 12 4.3 Engineering units 12

    4.4 K-factor (flow input scale factor) 12 4.5 Rate conversion factor 12 4.6 Rate dampening ( see response graph page 19 ) 12 & 19 4.7 Low frequency cut-off ( refer clause 2.4 page 5 ) 5 4.8 Pulse outputs ( scaleable or non-scaleable ) 12 4.9 Non linearity correction ( NLC) Linearisation 12 4.10 Presetting battery power levels 13

    5. ADDITIONAL PROGRAM PARAMETERS 5.1 Analog output 13 5.2 Flow alarms 13

    5.3 Flow alarm deadband 13 5.4 Dual flow inputs 13 & 20

    6. PROGRAMMING 6.1 Program levels 1~7 14 Program levels 8~13 15 6.2 Program levels 14~24 16 6.3 Program detail record 17

    7. TERMINAL LAYOUT, SELECTION LINKS & REMOTE SWITCHES 18 8. ALPHABETICAL INDEX 21

    R S Components Stock No. 596-602

    Farnell Components Order code 206-532

    Replacement Batteries:

    Trimec supplied batteries :

    Warning : Trimec Intrinsically safe battery

    assembly only is approved for RT12 mounted in a

    hazardous area.

    Non I.S. battery Trimec P/No. 1312007

    I.S. battery Trimec P/No. 1412028

    Suitable non I.S. batteries also available from :

    3.6V x 2.4Ah AA Lithium Thionyl Chloride non - rechargeable cell

    + -

    Press & hold Program key to show instrument model & software version

    PROG

    Software version 16.12.04 V 3.2 27.04.07 V 3.3

  • Introduction 2

    3 Introduction 1.2 Specifications Display : 8 digit alpha numeric LCD characters 9mm ( 0.35 ) high with second line sub script text,

    8 digits totalising, 5 digits rate. Programmable 0~3 decimal places for all displays. Signal Input : Universal pulse/frequency input compatible with Reed switch, Hall effect, Namur proximity detectors, Pulse wire, voltage, current & Coil (15mV P-P min). Max. input frequency 10Khz.

    Minimum input frequency for rate display is 0.1hz with low frequency cut off feature enabled, 0.3hz when disabled & 0.7hz if the non-linearity feature is enabled. Totals have no minimum.

    Battery power : Battery life expectancy can be up to 5~10 years when programmed with the unique

    Ultra Power Save sleep cycle. Battery life reduces when connected with a coil input from turbine flowmeters. Rate display defaults to total display 4 minutes after pressing the rate key in order to conserve battery power. (reverse polarity protected)

    External power : Regulated 8~24Vdc x 150mA or 4~20mA loop powered. Memory : All programmed & accumulated data is stored permanently in non-volatile memory. Pulse output : NPN-PNP transistor, scaleable (50hz max.) or non-scaleable ( 5000hz max.), 1A maximum

    drive capability. Analog output : Two wire loop powered, 12~28Vdc into 100~900D loop load, accuracy +/-0.25% FS, key entry programming of Zero & Span.

    Alarm outputs: Two NPN-PNP selectable FET (transistors) programmable low & high flow alarm with adjustable deadband (reset differential). Maximum drive 100mA resistive load. 24Vdc max.

    Physical : A) IP66 / 67 high impact glass reinforced nylon enclosure.

    B) 3 x M20 or NPT female conduit entries. C) 125mm diameter (5) x 61mm deep (2.5) x 400g (0.9lb). D) Temperature range from -20C to +80C ( -4F to +176F).

    Configuring : PIN protected data entry with scrolling English text prompts.

    K-factor range : Eg. Pulses/litre, gallon, lb etc. Programmable range is 0.001~ 9999999.999 with a floating decimal point during K-factor entry. Engineering units : Selectable Ltr, gal, m3, kgs, lbs (total). /sec,min,hr or day (rate). Rate conversion : Enables the rate to be displayed in different engineering units to that of the totals

    eg: totals in barrels (oil) & rate in US gallons. Battery modes : Ultra power save, standby or continuous display selectable.

    Dual Input option :Programmable for computations of A+B, A-B, or AB (ratio).

    1.1 Model number designation

    Model Function ( all instruments have program PIN protection )

    FRT12 Flow rate totaliser

    Electrical access

    1 3 x M20 x 1.5mm female threaded conduit entry ports 2 3 x 1/2" NPT female threaded conduit entry ports

    Flow input type

    D Digital ( pulse or frequency )Power supply

    0 Self powered ( battery ) or regulated 8~24VdcHousing type

    FM Universal mount ( field or panel )MM Integral meter mount

    Options

    - R Relay contol output board

    - I I.S. intrinsically safe Exia IIB T4 - IECEX & ATEX

    m o d e l No. e x a m p l eFRT12 0 D 0 FM - I

    Part No. ACCESSORIES FOR ABOVE SERIES

    1522001 stainless steel wall mount kit1522002 stainless steel 2" pipe mount kit1522011 MP series cooling fin kit for flowmeters with integral instruments 1522005 DP & Turbine stem adaptor - metric ( M16 to M20 )1522006 DP & Turbine stem adaptor - USA ( M16 to 1/2" NPT )1323006 DP490 stem ( 100mm effective height, threaded M16 male )1323011 DP525 stem ( 350mm effective height, threaded M16 male )1322071 3/4" BSPF fixed stem for Turbine flowmeters ( 3/4" BSPF to M16 )

    132822101 1" NPTF universal swivel stem for Turbine flowmeters ( 3/4" BSPF to M16 ) 1334001 DC switch mode DIN mount power supply - 100~240Vac input 1412063 Relay contol output board with two SPCO relays

  • Introduction 4 1.3 Overview The FRT is specifically designed for computing, displaying and transmitting totals and flowrate from flowmeters with pulse or frequency outputs. The instrument will display Flow Rate, Resettable Total and an Accumulated Total in engineering units as programmed by the user. Simple flow chart programming with scrolling English prompts guide you through the programming routine greatly reducing the need to refer to the instruction manual. All user program data is retained if the battery is removed. Environments The FRT is weatherproof to IP66/67 (Nema 4X) standards, UV resistant glass reinforced nylon with stainless screws & viton O-ring seals.The instrument suits harsh indoor and outdoor environments & conforms to EMC directive 89/336/EEC Electro Magnetic Compatibility. Features 10 point Linearisation, PIN Protection, NPN/PNP selectable autoranging pulse outputs (scaled or un-scaled), Low frequency cut-off, Battery conservation mode, 4~20mA output, High / Low flow alarms with adjustable deadbands, Dual inputs. Optional I.S. certification to IECex and ATEX directive, for conforming standards refer to I.S. supplement. Conforming standards include: EN 61326 ( immunity in industrial locations ) EN 62326 ( emissions in industrial locations ) EN 60529 ( degrees of protection [ IP ] ) Installation Specifically engineered to be directly mounted on a variety of flowmeters, wall or surface mounted, pipe or panel mounted. Various mounting kits are available. The instrument can be self powered or may be powered by an external dc supply or two wire loop powered. 1.4 LCD displays

    5 Operation

    2. OPERATION 2.1 Accumulative Total Accumulative total can be reset at L2 in the program mode. The accumulative total can be displayed momentarily or continuously through use of the front panel ACCUM TOTAL key. Momentary display : Accumulative total is displayed only whilst the key is held pressed. Latching display : To have the accum. total display latch when key is pressed simply press & hold the ACCUM TOTAL key for 10 seconds, the display will then latch each time the key is pressed. Holding the accumulative total key again for 10 seconds will revert this key function back to a momentary action. 2.2 Resettable Total ( also see page 18 for remote reset feature ) The display toggles between Rate & Total when the RATE-TOTAL key is pressed. Pressing the RESET key whilst displaying total will cause the total to reset to zero. 2.3 Rate display When rate is displayed the leading three alpha characters on the left of the display flash th