DCX Series

Embed Size (px)

Citation preview

  • 7/29/2019 DCX Series

    1/20

    District Cooling

    Chilled Water Fan Coil Units

    DCX SeriesDCX02 thru DCX14

    200 CFM thru 1400 CFM

  • 7/29/2019 DCX Series

    2/20

    Company Business

    Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabiaand today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.

    Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55

    countries in the Middle East, Europe, Africa and Asia.

    The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product andservice brands as well as a number of international brands under the OEM sales.

    The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

    The four SBUs are:1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.

    2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.

    3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance,

    retrofit & operation services and parts.

    4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHUs.

    The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operationsfrom the corporate headquarters in Dammam, Saudi Arabia.

    Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.

    All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at

    its best and achieve the corporate goals of maximizing customer satisfaction.

    Factories and Productions

    Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facilityin Italy operated by Geoclima.

    The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air

    Conditioning systems per year.

    Quality & Product Certificates

    The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.

    Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)

    Certificate for Room Air Conditioners. ZACs products are also certified with:

    1. CE (Council of European Community)

    2. UL (Underwriters Laboratory)

    3. Eurovent (Certified Performance)

    4. ETL (Test Facilities)

    5. SASO (Saudi Arabian Standards Organization)

    6. ISO 9001:2008 (International Organization for Standardization)7. ASME (American Quality of Mechanical Engineers)

    Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammedbin Fahd Al Saud Award for Factory Safety.

    Our Products

    In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Condition-ers manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from theConcealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin

    Air Handling Units up to 138,316 CFM and the Water Chillers up to 500 TR cooling capacity.

  • 7/29/2019 DCX Series

    3/20

    Contents Page

    District cooling .......................................................................................................................................... 2

    Model decoding ........................................................................................................................................ 3

    Unit features ............................................................................................................................................. 3

    Standard specifications ......................................................................................................................... 3-4

    Options ..................................................................................................................................................... 4

    Physical data ............................................................................................................................................ 5

    Cooling capacities ................................................................................................................................. 6-9

    Fan performance data ....................................................................................................................... 10-11

    Sound power data .................................................................................................................................. 12

    Unit dimensions ...................................................................................................................................... 13

    Coil connection dimensions .................................................................................................................... 14

    Heater box dimensions & arrangements ................................................................................................ 15

    Valve packages ...................................................................................................................................... 15

    Typical schematic wiring diagram ........................................................................................................... 16

    Installation .............................................................................................................................................. 17

    Electrical ................................................................................................................................................. 17

    Maintenance ........................................................................................................................................... 17

    INDEX

    CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.

    THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

    1

  • 7/29/2019 DCX Series

    4/20

    DISTRICT COOLINGDistrict cooling provides chilled water from a cooling plant through a network of pipes to multipleresidential, industrial and commercial buildings for air conditioning purpose.

    A typical district cooling system requires the FCUs to operate with a 80C - 90C delta temperature.

    Entering water temperature to the Fan Coil Unit is expected to be between 5.50C and 6.50C.

    District Cooling Benefits:

    District cooling systems provide a variety of benefits, both qualitative and economic. The qualitativeadvantages are perceived in terms of better comfort, better reliability and maximized convenience.Mechanical cooling and air conditioning requirements are growing rapidly throughout the world,partly because there are many new buildings being built and partly because those buildings arebeing built in warm climates. However, no matter where those buildings are built, they tend to betighter and more densely packed than they used to be. This creates a need for air conditioning even

    in cold climates.

    People are also increasingly emitting more and more heat into buildings through all types of electronicequipment that generate extra heat such as computers and various other gadgets. All this has led toa growing demand for comfort in homes and offices, a need that is directly addressed by DistrictCooling.

    The economic benefits can be experienced by both the owner and the tenant, where the capitalcosts of control panels, internal power distribution, annual maintenance and power consumptioninside the building are reduced and the cost of chillers are eliminated.

    * Better quality of cooling

    * Maximum cost effectiveness

    * Capital cost elimination

    * Space saving

    * Decrease in sound pollution

    * Environmental friendly

    2

  • 7/29/2019 DCX Series

    5/20

    1, 2 & 3BASIC (SERIES)

    4 & 5SIZE

    (x 100 CFM)

    6ELECTRICAL

    SUPPLY (V-Ph-Hz)

    13OPTION

    DCX

    HORIZONTAL

    CONCEALED

    CHILLEDWATER

    DISTRICT

    COOLING

    FAN COIL UNITS

    C : 208/230-1-60 N :STANDARD

    UNIT(WITHOUT

    THERMO-STAT)

    T :UNIT WITH

    THERMO-STAT

    MODEL DECODING12

    FILTER

    N :NONE

    A :ALUMINUM

    (1/2" THICK)

    C :SYNTHETIC(1/2" THICK)

    11COIL

    CONNECTION

    R : RH SIDE,

    STANDARD(FACING AIR

    DISCHARGE)

    L :LH SIDE,OPTIONAL

    (FACING AIRDISCHARGE)

    10FINS

    A : ALUMINUM

    FIN

    B : COATEDALUMINUM

    FIN

    C : COPPER FIN

    9ACCESSORIES

    N : STANDARD

    B : 3D VALVE PACKAGE

    (COOL ONLY)

    8HEATER

    N : NO HEATERB :1 kWD :2 kW

    E :3 kWF :4 kWG:5 kW

    7COIL

    A : 3 ROW CHILLED

    WATER

    B: 4 ROW CHILLEDWATER

    UNIT FEATURESLOW HEIGHT UNITSGood for spaces with low ceiling height.

    COMPACT DIMENSIONSIdeal to fit into tight spaces.

    EASY MAINTENANCE / ONE SIDE ACCESSFilters can be easily removed by sliding. Piping and controls are on one side for easy access.

    BACK AND BOTTOM RETURN AIR OPTIONS

    SINGLE COIL FOR RH & LH APPLICATIONS (FIELD CHANGEABLE FOR RH & LH APPLICATIONS)

    VALVE PACKAGES FOR 2 PIPE SYSTEMS

    WIDE RANGE OF HEATER SIZES

    QUIET, PULSE FREE AIR DELIVERYCentrifugal fans that are statically and dynamically balanced, handle up to 0.5" w.g. external static pressure allowing you

    to keep the unit away from your comfort zone.

    STANDARD SPECIFICATIONS

    UNIT CONSTRUCTIONThese units are fabricated of heavy gauge galvanized steel to ensure lasting durability and dependable performance with

    minimum maintenance. The panels are insulated to provide positive protection against sweating and maximum damping

    of air noise.

    This unit is designed for those concealed overhead installations which require supply ductwork. A 1" duct collar isprovided into the front panel for supply air duct connection. The standard arrangement provides return air from the rear

    side. This arrangement may be reversed to provide bottom return air by simply interchanging the bottom and rear panel.

    This reversal can be easily accomplished in the field.

    Access to the blower motor assembly is provided through the removable bottom panel from where the complete fan/

    motor can be removed for servicing.

    FANSThe centrifugal, forward curved, double width fan wheels are statically and dynamically balanced for quiet and smooth

    performance. Blower housing is rugged galvanized steel to provide added rigidity and assure quiet & smooth operation.

    N : NO HEATER

    D :2 kW

    E :3 kW

    F :4 kW

    G:5 kW

    J :7 kW

    M: 10 kW

    02

    03

    04

    06

    08

    10

    12

    14

    3

  • 7/29/2019 DCX Series

    6/20

    MOTORSMotors are permanent split capacitor type with three speed windings and built-in thermal overload protection. The bear-

    ings are of sleeve type.

    FILTERSAll models are furnished with 1/2" thick permanent washable type aluminum filters as standard. Synthetic filters can beprovided as an option.

    COILSCoils are 3/8" OD copper tubing, constructed of enhanced copper tubes and mechanically bonded to aluminum fins.As an

    option, corrugated copper fins or coated aluminum fins may be provided. Manual air vents are provided on all

    chilled water coils. The standard chilled water coil is 3 rows for all models & 4 row chilled water coil is also provided as an

    option. Each coil is pressure tested in the factory at not less than 300 psi (2070 kpa) air pressure. Coils conform to ARI 410.

    DRAIN PANThe condensate drain pan is fabricated of 18 gauge galvanized steel. The drain pan is powder coat painted. The outersurface is thermally insulated.

    DRIP LIPThe purpose of a 'drip-lip' is to capture any condensate from the valve packages and direct it to the drain pan. It is

    fabricated of a single metal formed to fit on the side of the drain pan. They may be installed in the field and should alwaysbe pitched towards the drain pan to assure proper drainage. This will be supplied loose for field installations along withvalve packages.

    OPTIONSELECTRIC HEATERSThe heater element is of the resistance open coil type. Thermal overheat cut-outs and fusible links are provided to shut-off power to heaters in case of airflow failure.

    VALVE PACKAGESValve packages are available as an option (3D for two pipe system). These valves can be factory installed or supplied

    loose for field installation.

    THERMOSTATAn attractive wall mount three speed electronic thermostat with all required functions and features for safe and smoothoperation which can be used for cooling & heating requirements. This thermostat can be supplied loose through separate

    Kit number.

    TYPICAL THERMOSTAT

    4

  • 7/29/2019 DCX Series

    7/20

    PHYSICAL DATA

    MODEL NUMBER DCX02 DCX03 DCX04 DCX06 DCX08 DCX10 DCX12 DCX

    POWER SUPPLY, V-Ph-Hz 208/230-1-60

    BLOWER Type Forward Curved

    Size (mm) 146x192 146x192 146x192 146x232 146x232 185x232 185x232 185x2

    Quantity 1 1 1 2 2 2 2 2

    BLOWER MOTOR Quantity 1 1 1 1 1 1 1 1

    FLA 0.66 0.66 0.66 1.16 1.16 2.52 2.52 2.5

    Watts @ 0.0 ESP, high speed 100 116 134 171 280 396 487 565

    COOLING COIL Type Corrugated Fin & Tube

    Rows, Standard 3 3 3 3 3 3 3 3

    Tube dia. - FPI 3/8 - 14 3/8 - 14 3/8 - 14 3/8 - 14 3/8 - 14 3/8 - 14 3/8 - 14 3/8 -

    COIL CONNECTIONS Chilled water, Inlet (inch) 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8

    (3 OR 4 ROWS)Chilled water, Outlet (inch) 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8

    DRAIN CONNECTION Size (inch) 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

    RETURN AIR FILTER Size (inch) 8 x 23-3/8 8 x 23-3/8 8 x 23-3/8 8 x 19-5/8 8 x 19-5/8 10 x 26-1/8 10 x 26-1/8 10 x 26

    (1/2'' THICK)Quantity 1 1 1 2 2 2 2 2

    SHIPPING WEIGHT kg. (approx.) 30 30 30 40 40 54 54 54

    5

  • 7/29/2019 DCX Series

    8/20

    CHILLED WATER COOLING CAPACITIES - 3 ROW COIL (ENGLISH UNITS)

    UNIT

    SIZEWTR

    (0F)

    16

    15

    14

    ENTERING AIR TEMP. = 730F DB/620F WB (@ HIGH SPEED) ENTERING AIR TEMP. = 750F DB/640F WB (@ HIGH SPEED)

    NOTE:

    For any other conditions, please use selection software for fan coil units.

    Apart from capacities, this software provides;

    a) Sensible heat ratio

    b) Leaving air temperature (DB/WB) - 0F

    c) Leaving water temperature - 0F

    d) Leaving water velocities (FPM)

    e) Water pressure drop (feet of water)

    LEGEND:

    TC - Total Capacity (MBH)

    SC - Sensible Heat Capacity (MBH)

    WTR- Water Temperature Rise (0F)

    EWT- Entering Water Temperature (0F)

    GPM- Water flow (Gallons Per Minute)

    430F EWT

    TC SC GPM

    420F EWT

    TC SC GPM

    440F EWT

    TC SC GPM

    UNIT

    SIZEWTR

    (0F)

    16

    15

    14

    430F EWT

    TC SC GPM

    420F EWT

    TC SC GPM

    440F EWT

    TC SC GPM

    02 6.46 4.66 0.81 6.10 4.50 0.76 5.74 4.34 0.72

    03 7.34 5.37 0.92 6.92 5.18 0.87 6.50 4.99 0.81

    04 7.95 5.86 1.00 7.48 5.64 0.94 7.02 5.44 0.88

    06 12.69 9.22 1.59 11.94 8.87 1.49 11.20 8.54 1.40

    08 15.43 11.37 1.93 14.49 10.93 1.81 13.54 10.50 1.69

    10 20.98 15.30 2.62 19.74 14.72 2.47 18.49 14.15 2.31

    12 22.78 16.71 2.85 21.40 16.07 2.68 20.03 15.44 2.50

    14 25.04 18.37 3.13 23.51 17.65 2.94 21.99 16.95 2.75

    02 6.59 4.76 0.82 6.22 4.59 0.78 5.85 4.42 0.73

    03 7.49 5.48 0.94 7.06 5.28 0.88 6.63 5.09 0.83

    04 8.11 5.97 1.02 7.63 5.76 0.95 7.16 5.54 0.90

    06 12.94 9.40 1.62 12.18 9.05 1.52 11.42 8.71 1.43

    08 15.74 11.60 1.97 14.78 11.15 1.85 13.82 10.71 1.73

    10 21.40 15.60 2.67 20.13 15.02 2.52 18.86 14.43 2.36

    12 23.24 17.04 2.90 21.83 16.39 2.73 20.43 15.75 2.55

    14 25.54 18.74 3.19 23.98 18.00 3.00 22.43 17.29 2.80

    02 6.72 4.85 0.84 6.34 4.68 0.79 5.97 4.51 0.75

    03 7.64 5.59 0.96 7.20 5.39 0.90 6.76 5.19 0.84

    04 8.27 6.09 1.03 7.78 5.87 0.97 7.30 5.65 0.91

    06 13.19 9.58 1.65 12.42 9.23 1.55 11.65 8.88 1.46

    08 16.05 11.82 2.00 15.07 11.37 1.88 14.09 10.92 1.76

    10 21.82 15.91 2.73 20.53 15.31 2.57 19.23 14.71 2.40

    12 23.69 17.38 2.96 22.26 16.71 2.78 20.83 16.06 2.60

    14 26.05 19.10 3.26 24.45 18.36 3.06 22.87 17.63 2.86

    02 8.69 5.71 1.09 8.32 5.55 1.04 7.95 5.40 0.99

    03 9.95 6.62 1.24 9.51 6.44 1.19 9.08 6.26 1.14

    04 10.82 7.24 1.35 10.34 7.04 1.29 9.87 6.85 1.23

    06 17.34 11.45 2.17 16.56 11.11 2.07 15.79 10.79 1.97

    08 21.36 14.28 2.67 20.37 13.86 2.54 19.38 13.44 2.42

    10 28.80 19.07 3.60 27.49 18.49 3.44 26.19 17.96 3.27

    12 31.44 20.93 3.93 29.99 20.29 3.75 28.55 19.69 3.57

    14 34.68 23.08 4.33 33.06 22.36 4.13 31.45 21.69 3.93

    02 8.86 5.83 1.11 8.48 5.67 1.06 8.11 5.51 1.01

    03 10.15 6.75 1.27 9.71 6.56 1.21 9.27 6.39 1.16

    04 11.03 7.39 1.38 10.55 7.18 1.32 10.06 6.98 1.26

    06 17.68 11.68 2.21 16.89 11.33 2.11 16.10 11.00 2.01

    08 21.79 14.57 2.72 20.77 14.14 2.60 19.77 13.71 2.47

    10 29.38 19.45 3.67 28.04 18.86 3.50 26.71 18.31 3.34

    12 32.07 21.34 4.01 30.59 20.69 3.82 29.12 20.08 3.64

    14 35.37 23.54 4.42 33.72 22.81 4.21 32.08 22.12 4.01

    02 9.04 5.94 1.13 8.65 5.78 1.08 8.27 5.62 1.03

    03 10.34 6.89 1.29 9.90 6.69 1.24 9.45 6.51 1.18

    04 11.25 7.53 1.41 10.75 7.32 1.34 10.26 7.12 1.28

    06 18.03 11.90 2.25 17.22 11.55 2.15 16.42 11.22 2.05

    08 22.22 14.85 2.78 21.18 14.41 2.65 20.16 13.98 2.52

    10 29.95 19.84 3.74 28.59 19.23 3.57 27.24 18.67 3.40

    12 32.70 21.76 4.09 31.19 21.10 3.90 29.69 20.48 3.71

    14 36.06 24.00 4.51 34.38 23.26 4.30 32.71 22.55 4.09

    6

  • 7/29/2019 DCX Series

    9/20

    CHILLED WATER COOLING CAPACITIES - 4 ROW COIL (ENGLISH UNITS)

    NOTE:

    For any other conditions, please use selection software for fan coil units.

    Apart from capacities, this software provides;

    a) Sensible heat ratio

    b) Leaving air temperature (DB/WB) - 0F

    c) Leaving water temperature - 0F

    d) Leaving water velocities (FPM)

    e) Water pressure drop (feet of water)

    LEGEND:

    TC - Total Capacity (MBH)

    SC - Sensible Heat Capacity (MBH)

    WTR- Water Temperature Rise (0F)

    EWT- Entering Water Temperature (0F)

    GPM- Water flow (Gallons Per Minute)

    UNIT

    SIZEWTR

    (0F)

    16

    15

    14

    ENTERING AIR TEMP. = 730F DB/620F WB (@ HIGH SPEED) ENTERING AIR TEMP. = 750F DB/640F WB (@ HIGH SPEED)

    430F EWT

    TC SC GPM

    420F EWT

    TC SC GPM

    440F EWT

    TC SC GPM

    UNIT

    SIZEWTR

    (0F)

    16

    15

    14

    430F EWT

    TC SC GPM

    420F EWT

    TC SC GPM

    440F EWT

    TC SC GPM

    02 7.45 5.27 0.93 7.04 5.09 0.88 6.63 4.90 0.83

    03 8.61 6.19 1.08 8.12 5.96 1.02 7.63 5.75 0.95

    04 9.34 6.76 1.17 8.80 6.51 1.10 8.27 6.28 1.03

    06 14.93 10.35 1.87 14.06 10.24 1.76 13.20 9.85 1.65

    08 18.28 13.23 2.28 17.18 12.71 2.15 16.08 12.21 2.01

    10 24.75 17.68 3.09 23.29 17.02 2.91 21.84 16.36 2.73

    12 26.95 19.39 3.37 25.33 18.63 3.17 23.73 17.91 2.97

    14 29.67 21.35 3.71 27.87 20.50 3.48 26.10 19.69 3.26

    02 7.60 5.38 0.95 7.18 5.19 0.90 6.76 5.00 0.85

    03 8.78 6.31 1.10 8.28 6.08 1.04 7.79 5.87 0.97

    04 9.53 6.90 1.19 8.98 6.64 1.12 8.43 6.41 1.06

    06 15.23 10.56 1.90 14.34 10.45 1.79 13.46 10.05 1.68

    08 18.65 13.49 2.33 17.52 12.96 2.19 16.40 12.46 2.05

    10 25.24 18.04 3.15 23.76 17.36 2.97 22.28 16.69 2.78

    12 27.48 19.78 3.43 25.84 19.01 3.23 24.21 18.27 3.03

    14 30.26 21.78 3.78 28.43 20.91 3.55 26.62 20.09 3.33

    02 7.75 5.48 0.97 7.32 5.29 0.92 6.90 5.10 0.86

    03 8.95 6.43 1.12 8.44 6.20 1.06 7.94 5.98 0.99

    04 9.71 7.03 1.21 9.16 6.77 1.15 8.60 6.53 1.08

    06 15.53 10.77 1.94 14.62 10.65 1.83 13.73 10.24 1.72

    08 19.01 13.76 2.38 17.86 13.21 2.23 16.72 12.70 2.09

    10 25.74 18.39 3.22 24.22 17.70 3.03 22.72 17.02 2.84

    12 28.02 20.17 3.50 26.34 19.38 3.29 24.68 18.62 3.08

    14 30.86 22.20 3.86 28.99 21.32 3.62 27.14 20.48 3.39

    02 9.99 6.45 1.25 9.57 6.17 1.20 9.15 6.09 1.14

    03 11.61 7.47 1.45 11.11 7.39 1.39 10.62 7.18 1.33

    04 12.66 8.34 1.58 12.10 8.10 1.51 11.55 7.87 1.44

    06 20.37 13.21 2.54 19.46 12.81 2.43 18.55 12.41 2.32

    08 25.26 16.60 3.16 24.08 16.08 3.01 22.92 15.58 2.86

    10 33.92 22.05 4.24 32.37 21.37 4.05 30.84 20.71 3.86

    12 37.13 23.73 4.64 35.41 23.52 4.43 33.71 22.78 4.21

    14 41.04 26.45 5.13 39.11 25.96 4.89 37.21 25.14 4.65

    02 10.19 6.58 1.27 9.76 6.29 1.22 9.33 6.21 1.17

    03 11.85 7.62 1.48 11.34 7.54 1.42 10.83 7.32 1.35

    04 12.91 8.50 1.61 12.34 8.26 1.54 11.78 8.03 1.47

    06 20.78 13.47 2.60 19.84 13.07 2.48 18.92 12.66 2.36

    08 25.77 16.93 3.22 24.56 16.40 3.07 23.38 15.89 2.92

    10 34.59 22.49 4.32 33.02 21.80 4.13 31.46 21.12 3.93

    12 37.87 24.21 4.73 36.12 23.99 4.51 34.38 23.24 4.30

    14 41.86 26.98 5.23 39.90 26.48 4.99 37.96 25.65 4.74

    02 10.39 6.71 1.30 9.95 6.42 1.24 9.52 6.33 1.19

    03 12.08 7.77 1.51 11.56 7.69 1.44 11.04 7.47 1.38

    04 13.16 8.67 1.64 12.59 8.42 1.57 12.02 8.18 1.50

    06 21.18 13.74 2.65 20.23 13.32 2.53 19.29 12.91 2.41

    08 26.27 17.26 3.28 25.05 16.72 3.13 23.84 16.21 2.98

    10 35.27 22.93 4.41 33.67 22.23 4.21 32.08 21.53 4.01

    12 38.61 24.68 4.83 36.83 24.46 4.60 35.06 23.70 4.38

    14 42.68 27.51 5.33 40.68 27.00 5.08 38.70 26.15 4.84

    7

  • 7/29/2019 DCX Series

    10/20

    CHILLED WATER COOLING CAPACITIES - 3 ROW COIL (METRIC UNITS)

    UNIT

    SIZEWTR

    (0C)

    9

    8.5

    8

    ENTERING AIR TEMP. = 230C DB/170C WB (@ HIGH SPEED) ENTERING AIR TEMP. = 240C DB/180C WB (@ HIGH SPEED)

    NOTE:

    For any other conditions, please use selection software for fan coil units.

    Apart from capacities, this software provides;

    a) Sensible heat ratio

    b) Leaving air temperature (DB/WB) - 0C

    c) Leaving water temperature - 0C

    d) Leaving water velocities (m/s)

    e) Water pressure drop (kp)

    LEGEND:

    TC - Total Capacity (kW)

    SC - Sensible Heat Capacity (kW)

    WTR- Water Temperature Rise (0C)

    EWT- Entering Water Temperature (0C)

    LPS - Water flow (Liters Per Second)

    60C EWT

    TC SC LPS

    5.50C EWT

    TC SC LPS

    6.50C EWT

    TC SC LPS

    UNIT

    SIZEWTR

    (0C)

    9

    8.5

    8

    60C EWT

    TC SC LPS

    5.50C EWT

    TC SC LPS

    6.50C EWT

    TC SC LPS

    02 2.09 1.45 0.06 2.00 1.41 0.05 1.90 1.37 0.05

    03 2.39 1.68 0.06 2.27 1.63 0.06 2.16 1.58 0.06

    04 2.59 1.83 0.07 2.46 1.77 0.07 2.34 1.72 0.06

    06 4.13 2.88 0.11 3.93 2.79 0.10 3.73 2.70 0.10

    08 5.04 3.57 0.13 4.79 3.45 0.13 4.54 3.34 0.12

    10 6.84 4.79 0.18 6.51 4.63 0.17 6.18 4.49 0.16

    12 7.44 5.23 0.20 7.07 5.07 0.19 6.70 4.90 0.18

    14 8.18 5.76 0.22 7.77 5.57 0.21 7.37 5.39 0.20

    02 2.13 1.48 0.06 2.04 1.44 0.05 1.94 1.40 0.05

    03 2.44 1.71 0.06 2.32 1.66 0.06 2.20 1.61 0.06

    04 2.64 1.87 0.07 2.51 1.81 0.07 2.39 1.75 0.06

    06 4.21 2.94 0.11 4.01 2.85 0.10 3.80 2.75 0.10

    08 5.14 3.64 0.13 4.89 3.52 0.13 4.63 3.41 0.12

    10 6.98 4.89 0.18 6.64 4.72 0.17 6.30 4.58 0.16

    12 7.59 5.33 0.20 7.21 5.17 0.19 6.83 5.00 0.18

    14 8.34 5.88 0.22 7.93 5.68 0.21 7.52 5.50 0.20

    02 2.17 1.51 0.06 2.08 1.47 0.05 1.98 1.42 0.05

    03 2.49 1.75 0.06 2.36 1.70 0.06 2.25 1.64 0.06

    04 2.69 1.90 0.07 2.56 1.84 0.07 2.43 1.79 0.06

    06 4.30 3.00 0.11 4.09 2.90 0.10 3.88 2.81 0.10

    08 5.24 3.71 0.14 4.98 3.59 0.14 4.72 3.47 0.12

    10 7.11 4.98 0.19 6.77 4.82 0.18 6.43 4.67 0.17

    12 7.74 5.44 0.21 7.35 5.27 0.20 6.97 5.10 0.19

    14 8.51 5.99 0.23 8.08 5.79 0.22 7.66 5.61 0.21

    02 2.68 1.72 0.07 2.59 1.68 0.07 2.49 1.64 0.07

    03 3.07 1.99 0.08 2.96 1.95 0.08 2.85 1.90 0.08

    04 3.35 2.18 0.09 3.22 2.13 0.09 3.09 2.08 0.08

    06 5.37 3.45 0.14 5.16 3.36 0.14 4.96 3.28 0.13

    08 6.63 4.32 0.18 6.36 4.20 0.17 6.10 4.09 0.16

    10 8.92 5.75 0.24 8.57 5.60 0.23 8.23 5.46 0.22

    12 9.75 6.32 0.26 9.36 6.15 0.25 8.98 5.99 0.24

    14 10.76 6.97 0.29 10.32 6.78 0.27 9.90 6.61 0.26

    02 2.73 1.75 0.07 2.64 1.71 0.07 2.54 1.67 0.07

    03 3.13 2.03 0.08 3.02 1.99 0.08 2.91 1.94 0.08

    04 3.42 2.22 0.09 3.28 2.17 0.09 3.15 2.12 0.08

    06 5.48 3.52 0.14 5.26 3.43 0.14 5.06 3.35 0.13

    08 6.76 4.41 0.18 6.49 4.28 0.17 6.22 4.17 0.16

    10 9.10 5.87 0.24 8.74 5.71 0.23 8.39 5.57 0.22

    12 9.95 6.45 0.27 9.55 6.27 0.26 9.16 6.11 0.24

    14 10.98 7.11 0.30 10.53 6.92 0.28 10.10 6.74 0.27

    02 2.79 1.79 0.07 2.69 1.75 0.07 2.59 1.71 0.07

    03 3.19 2.07 0.08 3.08 2.03 0.08 2.96 1.98 0.08

    04 3.48 2.27 0.09 3.35 2.22 0.09 3.21 2.16 0.08

    06 5.58 3.59 0.15 5.37 3.49 0.15 5.16 3.41 0.14

    08 6.90 4.49 0.19 6.61 4.37 0.18 6.34 4.25 0.17

    10 9.28 5.98 0.25 8.91 5.82 0.24 8.56 5.68 0.23

    12 10.14 6.57 0.27 9.73 6.40 0.26 9.34 6.23 0.25

    14 11.19 7.25 0.30 10.73 7.05 0.28 10.30 6.87 0.27

    8

  • 7/29/2019 DCX Series

    11/20

    CHILLED WATER COOLING CAPACITIES - 4 ROW COIL (METRIC UNITS)

    NOTE:

    For any other conditions, please use selection software for fan coil units.

    Apart from capacities, this software provides;

    a) Sensible heat ratio

    b) Leaving air temperature (DB/WB) - 0C

    c) Leaving water temperature - 0C

    d) Leaving water velocities (m/s)

    e) Water pressure drop (kp)

    LEGEND:

    TC - Total Capacity (kW)

    SC - Sensible Heat Capacity (kW)

    WTR- Water Temperature Rise (0C)

    EWT- Entering Water Temperature (0C)

    LPS - Water flow (Liters Per Second)

    UNIT

    SIZEWTR

    (0C)

    9

    8.5

    8

    ENTERING AIR TEMP. = 230C DB/170C WB (@ HIGH SPEED) ENTERING AIR TEMP. = 240C DB/180C WB (@ HIGH SPEED)

    60C EWT

    TC SC LPS

    5.50C EWT

    TC SC LPS

    6.50C EWT

    TC SC LPS

    UNIT

    SIZEWTR

    (0C)

    9

    8.5

    8

    60C EWT

    TC SC LPS

    5.50C EWT

    TC SC LPS

    6.50C EWT

    TC SC LPS

    02 2.41 1.64 0.06 2.30 1.59 0.06 2.19 1.54 0.06

    03 2.79 1.93 0.07 2.66 1.87 0.07 2.53 1.82 0.07

    04 3.03 2.11 0.08 2.89 2.05 0.08 2.75 1.98 0.07

    06 4.86 3.33 0.13 4.62 3.22 0.12 4.39 3.12 0.12

    08 5.97 4.15 0.16 5.67 4.01 0.15 5.38 3.88 0.14

    10 8.06 5.51 0.21 7.67 5.36 0.20 7.28 5.18 0.19

    12 8.79 6.08 0.23 8.36 5.88 0.22 7.93 5.69 0.21

    14 9.69 6.70 0.26 9.21 6.47 0.24 8.73 6.26 0.23

    02 2.46 1.67 0.06 2.35 1.62 0.06 2.23 1.57 0.06

    03 2.85 1.97 0.07 2.71 1.91 0.07 2.58 1.86 0.07

    04 3.09 2.15 0.08 2.95 2.09 0.08 2.81 2.02 0.07

    06 4.96 3.40 0.13 4.71 3.28 0.12 4.48 3.18 0.12

    08 6.09 4.23 0.16 5.78 4.09 0.15 5.49 3.96 0.14

    10 8.22 5.62 0.21 7.82 5.47 0.20 7.43 5.28 0.19

    12 8.97 6.20 0.23 8.53 6.00 0.22 8.09 5.80 0.21

    14 9.88 6.83 0.27 9.39 6.60 0.24 8.90 6.39 0.23

    02 2.51 1.71 0.06 2.39 1.65 0.06 2.28 1.60 0.06

    03 2.90 2.01 0.07 2.77 1.94 0.07 2.63 1.89 0.07

    04 3.15 2.19 0.08 3.01 2.13 0.08 2.86 2.06 0.07

    06 5.05 3.46 0.14 4.80 3.35 0.12 4.57 3.24 0.12

    08 6.21 4.32 0.17 5.90 4.17 0.16 5.60 4.04 0.15

    10 8.38 5.73 0.22 7.98 5.57 0.21 7.57 5.39 0.20

    12 9.14 6.32 0.24 8.69 6.12 0.23 8.25 5.92 0.22

    14 10.08 6.97 0.27 9.58 6.73 0.25 9.08 6.51 0.24

    02 3.09 1.94 0.08 2.97 1.89 0.08 2.86 1.85 0.08

    03 3.59 2.27 0.10 3.46 2.23 0.09 3.32 2.18 0.09

    04 3.91 2.51 0.10 3.77 2.45 0.10 3.62 2.39 0.10

    06 6.31 3.99 0.17 6.06 3.88 0.16 5.82 3.78 0.15

    08 7.83 5.01 0.21 7.52 4.88 0.20 7.21 4.75 0.19

    10 10.51 6.66 0.28 10.10 6.48 0.27 9.69 6.30 0.26

    12 11.51 7.34 0.31 11.05 7.13 0.29 10.60 6.94 0.28

    14 12.73 8.11 0.34 12.22 7.88 0.32 11.71 7.66 0.31

    02 3.15 1.98 0.08 3.03 1.93 0.08 2.92 1.89 0.08

    03 3.66 2.32 0.10 3.53 2.27 0.09 3.39 2.22 0.09

    04 3.99 2.56 0.10 3.85 2.50 0.10 3.69 2.44 0.10

    06 6.44 4.07 0.17 6.18 3.96 0.16 5.94 3.86 0.15

    08 7.99 5.11 0.21 7.67 4.98 0.20 7.35 4.85 0.19

    10 10.72 6.79 0.29 10.30 6.61 0.28 9.88 6.43 0.27

    12 11.74 7.49 0.32 11.27 7.27 0.30 10.81 7.08 0.29

    14 12.98 8.27 0.35 12.46 8.04 0.33 11.94 7.81 0.32

    02 3.21 2.02 0.08 3.09 1.97 0.08 2.98 1.92 0.08

    03 3.74 2.36 0.10 3.60 2.32 0.09 3.45 2.27 0.09

    04 4.07 2.61 0.10 3.92 2.55 0.10 3.77 2.49 0.10

    06 6.56 4.15 0.18 6.30 4.04 0.17 6.06 3.93 0.16

    08 8.15 5.21 0.22 7.82 5.08 0.21 7.50 4.94 0.20

    10 10.93 6.93 0.29 10.51 6.74 0.28 10.08 6.55 0.27

    12 11.98 7.64 0.32 11.50 7.42 0.30 11.03 7.22 0.29

    14 13.24 8.44 0.35 12.71 8.20 0.33 12.18 7.97 0.32

    9

  • 7/29/2019 DCX Series

    12/20

    0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.4 0.5

    HIGH 295 288 280 266 252 239 225 195 180

    DCX02 MEDIUM 266 253 240 235 230 223 215 175 160

    LOW 225 218 210 203 195 188 180 165 -

    HIGH 380 369 358 343 327 307 287 250 197

    DCX03 MEDIUM 330 324 318 311 303 288 272 234 180

    LOW 266 253 240 235 230 223 215 175 160

    HIGH 438 422 405 390 374 355 335 288 224

    DCX04 MEDIUM 401 389 377 361 345 324 303 264 208

    LOW 330 324 318 311 303 288 272 234 180

    HIGH 613 592 571 548 525 479 432 355 221

    DCX06 MEDIUM 567 546 525 503 481 438 395 288 175

    LOW 505 485 465 426 386 355 323 241 160

    HIGH 853 822 790 755 720 681 641 505 368

    DCX08 MEDIUM 730 703 675 651 627 576 525 420 276

    LOW 613 592 571 548 525 479 432 355 221

    HIGH 1044 1022 1000 980 960 928 895 870 770

    DCX10 MEDIUM 880 860 840 831 821 799 776 715 645

    LOW 805 781 756 736 715 688 661 615 560

    HIGH 1200 1178 1156 1129 1102 1068 1033 960 870

    DCX12 MEDIUM 995 973 950 933 915 883 850 830 730

    LOW 880 860 840 831 821 799 776 715 645

    HIGH 1320 1286 1251 1221 1190 1157 1123 1040 940

    DCX14 MEDIUM 1200 1178 1156 1129 1102 1068 1033 960 870

    LOW 995 973 950 933 915 883 850 830 730

    FAN PERFORMANCE DATA - 3 ROW COILS (ENGLISH UNITS)CFM @ EXTERNAL STATIC PRESSURE (Inches of water)BLOWER MOTOR

    SPEED

    MODEL

    NUMBER

    NOTE: 1. Values include losses for dry coil and filters.2. Airflow values are in CFM.

    FAN PERFORMANCE DATA - 4 ROW COILS (ENGLISH UNITS)CFM @ EXTERNAL STATIC PRESSURE (Inches of water)BLOWER MOTOR

    SPEED

    MODEL

    NUMBER 0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.4 0.5

    HIGH 288 280 266 252 239 225 210 188 165

    DCX02 MEDIUM 253 240 235 230 223 215 195 168 139

    LOW 218 210 203 195 188 180 173 - -

    HIGH 369 358 343 327 307 287 269 224 170

    DCX03 MEDIUM 324 318 311 303 288 272 253 207 145

    LOW 253 240 235 230 223 215 195 168 115

    HIGH 422 405 390 374 355 335 312 256 190

    DCX04 MEDIUM 389 377 361 345 324 303 284 236 159

    LOW 324 318 311 303 288 272 253 207 135

    HIGH 592 571 548 525 479 432 394 288 201

    DCX06 MEDIUM 546 525 503 481 438 395 342 232 165

    LOW 485 465 426 386 355 323 282 201 146

    HIGH 822 790 755 720 681 641 573 437 285

    DCX08 MEDIUM 703 675 651 627 576 525 473 348 204

    LOW 592 571 548 525 479 432 394 288 160

    HIGH 1022 1000 980 960 928 895 883 820 680

    DCX10 MEDIUM 860 840 831 821 799 776 746 680 602

    LOW 781 756 736 715 688 661 638 588 530

    HIGH 1178 1156 1129 1102 1068 1033 997 915 810

    DCX12 MEDIUM 973 950 933 915 883 850 840 780 670

    LOW 860 840 831 821 799 776 746 680 620

    HIGH 1286 1251 1221 1190 1157 1123 1082 990 880

    DCX14 MEDIUM 1178 1156 1129 1102 1068 1033 997 915 830

    LOW 973 950 933 915 883 850 840 780 680

    10

  • 7/29/2019 DCX Series

    13/20

    0.0 12.5 25 37.5 50 62.5 75 100 125

    HIGH 136 132 126 119 113 106 99 88 78

    DCX02 MEDIUM 119 113 111 109 105 101 92 79 66

    LOW 103 99 96 92 88 85 81 39 0

    HIGH 174 169 162 154 145 135 127 105 80

    DCX03 MEDIUM 153 150 147 143 136 128 119 98 68

    LOW 119 113 111 109 105 101 92 79 54

    HIGH 199 191 184 177 167 158 147 121 90

    DCX04 MEDIUM 184 178 170 163 153 143 134 111 75

    LOW 153 150 147 143 136 128 119 98 64

    HIGH 279 269 259 248 226 204 186 136 95

    DCX06 MEDIUM 258 248 237 227 207 186 161 109 78

    LOW 229 219 201 182 167 152 133 95 69

    HIGH 388 373 356 340 321 303 270 206 135

    DCX08 MEDIUM 332 319 307 296 272 248 223 164 96LOW 279 269 259 248 226 204 186 136 76

    HIGH 482 472 463 453 438 422 417 387 321

    DCX10 MEDIUM 406 396 392 387 377 366 352 321 284

    LOW 368 357 347 337 325 312 301 277 250

    HIGH 556 546 533 520 504 488 470 432 382

    DCX12 MEDIUM 459 448 440 432 417 401 396 368 316

    LOW 406 396 392 387 377 366 352 321 293

    HIGH 607 590 576 562 546 530 510 467 415

    DCX14 MEDIUM 556 546 533 520 504 488 470 432 392

    LOW 459 448 440 432 417 401 396 368 321

    0.0 12.5 25 37.5 50 62.5 75 100 125

    HIGH 139 136 132 126 119 113 106 92 85

    DCX02 MEDIUM 126 119 113 111 109 105 101 83 76

    LOW 106 103 99 96 92 88 85 78 0

    HIGH 179 174 169 162 154 145 135 118 93

    DCX03 MEDIUM 156 153 150 147 143 136 128 110 85

    LOW 126 119 113 111 109 105 101 83 76

    HIGH 207 199 191 184 177 167 158 136 106

    DCX04 MEDIUM 189 184 178 170 163 153 143 125 98

    LOW 156 153 150 147 143 136 128 110 85

    HIGH 289 279 269 259 248 226 204 168 104

    DCX06 MEDIUM 268 258 248 237 227 207 186 136 83

    LOW 238 229 219 201 182 167 152 114 76

    HIGH 403 388 373 356 340 321 303 238 174

    DCX08 MEDIUM 345 332 319 307 296 272 248 198 130

    LOW 289 279 269 259 248 226 204 168 104

    HIGH 493 482 472 463 453 438 422 411 363

    DCX10 MEDIUM 415 406 396 392 387 377 366 337 304

    LOW 380 368 357 347 337 325 312 290 264

    HIGH 566 556 546 533 520 504 488 453 411

    DCX12 MEDIUM 470 459 448 440 432 417 401 392 345

    LOW 415 406 396 392 387 377 366 337 304

    HIGH 623 607 590 576 562 546 530 491 444

    DCX14 MEDIUM 566 556 546 533 520 504 488 453 411

    LOW 470 459 448 440 432 417 401 392 345

    FAN PERFORMANCE DATA - 3 ROW COILS (METRIC UNITS)LITERS PER SECOND @ EXTERNAL STATIC PRESSURE (Pascal )BLOWER MOTOR

    SPEED

    MODEL

    NUMBER

    NOTE: 1. Values include losses for dry coil and filters.

    2. Airflow values are in Liters per second.

    FAN PERFORMANCE DATA - 4 ROW COILS (METRIC UNITS)LITERS PER SECOND @ EXTERNAL STATIC PRESSURE (Pascal )BLOWER MOTOR

    SPEED

    MODEL

    NUMBER

    11

  • 7/29/2019 DCX Series

    14/20

    SOUND POWER LEVEL (dB re 1012 Watts)

    125 250 500 1000 2000 4000 8000

    HIGH 55 46 41 37 36 30 26

    DCX02 MEDIUM 52 47 40 38 37 32 26

    LOW 50 46 37 35 33 31 25

    HIGH 57 53 47 47 46 42 36

    DCX03 MEDIUM 54 46 39 37 35 30 26

    LOW 51 46 38 37 35 31 26

    HIGH 61 56 51 50 49 43 38

    DCX04 MEDIUM 60 56 51 50 48 42 37

    LOW 57 53 46 47 47 42 35

    HIGH 66 63 58 55 55 51 45

    DCX06 MEDIUM 64 58 55 51 53 48 41

    LOW 61 54 53 49 51 45 40

    HIGH 67 65 62 57 58 55 48

    DCX08 MEDIUM 66 63 58 55 55 51 45

    LOW 64 58 55 53 53 48 41

    HIGH 69 67 63 63 62 59 53

    DCX10 MEDIUM 68 64 60 59 58 54 47

    LOW 66 63 59 58 57 53 45

    HIGH 71 70 67 66 65 62 56

    DCX12 MEDIUM 69 67 63 63 62 59 53

    LOW 68 64 60 59 58 54 47

    HIGH 72 71 70 69 68 65 61

    DCX14 MEDIUM 71 70 67 66 65 62 56

    LOW 69 67 63 63 62 59 53

    OCTAVE BAND CENTER FREQUENCY - HzBLOWER MOTOR

    SPEED

    MODEL

    NUMBER

    AT 0.15 ESP

    12

  • 7/29/2019 DCX Series

    15/20

    7

    5

    4

    3

    1

    15 (0.590)

    25 (1.000)

    184 (7.250)

    109 (4.281)

    J

    E

    H

    D

    B

    A

    TOP VIEW END VIEW

    FRONT VIEW

    62

    G

    F

    C

    A B C D E F G H J

    DCX02 622 (24.5) 591 (23.3) 254 (10) 591 (23.25) 287 (11.3) 529 (20.8) 176 (6.93) 611 (24.04) 212 (8.33)

    DCX03 622 (24.5) 591 (23.3) 254 (10) 591 (23.25) 287 (11.3) 529 (20.8) 176 (6.93) 611 (24.04) 212 (8.33)

    DCX04 622 (24.5) 591 (23.3) 254 (10) 591 (23.25) 287 (11.3) 529 (20.8) 176 (6.93) 611 (24.04) 212 (8.33)

    DCX06 1029 (40.5) 591 (23.3) 254 (10) 997 (39.25) 287 (11.3) 934 (36.8) 176 (6.93) 1017 (40.04) 212 (8.33)

    DCX08 1029 (40.5) 591 (23.3) 254 (10) 997 (39.25) 287 (11.3) 934 (36.8) 176 (6.93) 1017 (40.04) 212 (8.33)

    DCX10 1359 (53.5) 652 (25.7) 305 (12) 1327 (52.25) 298 (11.75) 1265 (49.8) 227 (8 .93) 1347 (53.04) 262 (10.33)

    DCX12 1359 (53.5) 652 (25.7) 305 (12) 1327 (52.25) 298 (11.75) 1265 (49.8) 227 (8 .93) 1347 (53.04) 262 (10.33)

    DCX14 1359 (53.5) 652 (25.7) 305 (12) 1327 (52.25) 298 (11.75) 1265 (49.8) 227 (8 .93) 1347 (53.04) 262 (10.33)

    DIMENSIONS

    MODELS: DCX02 - DCX14

    MODELDIMENSIONS

    NOTE: All dimensions are in mm (dimensions in brackets are in inches).

    LEGEND:

    1. Blower & motor assembly

    2. Cooling coil

    3. Control box

    4. Filter rack

    5. Mounting holes

    6. Drain pan

    7. Duct connector

    NO. OF

    MOTORS

    NO. OF

    BLOWERS

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    2

    2

    2

    2

    2

    13

  • 7/29/2019 DCX Series

    16/20

    DIMENSIONAL DATA - COIL CONNECTIONS

    CHILLED WATER COIL

    3 ROW COILMODEL

    DCX02 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

    DCX03 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

    DCX04 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

    DCX06 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

    DCX08 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

    DCX10 100 (3.91) 143 (5.61) 38 (1.5) 90 (3.53) 130 (5.11) 57 (2.25)

    DCX12 100 (3.91) 143 (5.61) 38 (1.5) 90 (3.53) 130 (5.11) 57 (2.25)

    DCX14 100 (3.91) 143 (5.61) 38 (1.5) 90 (3.53) 130 (5.11) 57 (2.25)

    A B C A B C

    NOTE: All dimensions are in mm (dimensions in brackets are in inches).

    4 ROW COIL

    DIMENSIONS

    14

    25 (1.00")

    INLET

    OUTLET

    B

    C

    A

  • 7/29/2019 DCX Series

    17/20

    SLIDING FRAME WITH HEATER

    HEATER BOX

    C

    B

    A

    Two gate valves

    One balancing valve

    One 3-way motor valve

    1

    2

    3

    HEATER ARRANGEMENTS

    A B C

    DCX 02/03/04 685 (27) 180 (7.1) 223 (8.8)

    DCX 06/08 939 (37) 180 (7.1) 223 (8.8)

    DCX 10/12/14 1269 (50) 231 (9.1) 150 (5.9)

    MODELDIMENSIONS

    DIMENSIONS - HEATER BOX

    NOTE: All dimensions are in mm (dimensions in brackets are in inches).

    VALVE PACKAGES

    1

    2

    3

    Two gate shut off valves

    One balancing valve

    One 3-way motor valve

    VALVE PACKAGE 3-D (for 2-pipe)

    CHILLER

    FCU 3

    1

    21

    15

  • 7/29/2019 DCX Series

    18/20

    MED-HI

    DCX 02

    DCX 14

    DCX 08

    DCX 12

    DCX 10

    DCX 06

    DCX 03

    DCX 04

    MODEL

    WIRE COLOR

    SPEED

    BLK

    HI

    BLU FREQUENCY

    APPLICABLEMED

    RED

    LOW

    YEL

    LOWEST

    ORG

    COM

    WHT

    60

    60

    60

    60

    60

    60

    60

    60

    IN HERTZ

    L/L1

    TO FUSE DISCONNECT SWITCH

    T'STAT

    22

    21

    7

    20

    22

    20

    21

    7

    1

    6

    N

    1

    N

    6

    ATB

    GND

    22

    21

    20

    6

    7

    N

    HVTB

    L2/N

    HC

    T2G

    T1G

    T2F

    T1F 0HT1

    0HT2

    HEATER OPTION

    HTR2

    HTR1

    Refer to table below for Speed Connections.

    TYPICAL SCHEMATIC WIRING DIAGRAM

    HEAT/COOL MODELS - ELECTRIC HEATER(POWER SUPPLY: 208/230V - 1Ph - 60Hz)

    LEGENDATB AUXILIARY TERMINAL BLOCK

    CAP CAPACITOR

    EV ELECTRIC VALVE

    FM FAN MOTOR

    GND LUG GROUND

    HC HEATER CONTACTOR

    HTR HEATER

    HVTB HIGH VOLTAGE TERMINAL BLOCK

    L/L1 LINE OR LINE 1

    L2/N LINE 2 OR NEUTRAL

    OHT OVER HEAT THERMOSTAT

    _ _ _FIELD WIRING

    FACTORY WIRING

    NOTES

    1. MOTORS THERMALLY PROTECTED.

    2. USE COPPER CONDUCTOR WIRES ONLY.

    3. HVTB IS NOT REQUIRED FOR HEATER MODELS.

    4. USE HEATER AS PER OPTION REQUIRED. IF

    EV & HEATERS ARE FACTORY INSTALLED,PLEASE READ DASHED LINE AS CONTINUOUS

    LINE.

    16

  • 7/29/2019 DCX Series

    19/20

    INSTALLATIONThe complete shipment should be inspected for damage. Any damage, visible or concealed, should be reported immedi-ately to the delivery man or driver and noted on the shipping invoice.

    Place unit in position and make sure that unit is level. This is important to assure proper drainage and operation. Slots

    provided in the mounting brackets should be used for installing the units.

    ELECTRICALPlease ensure power supply (V-Ph-Hz) to the unit is as per unit nameplate requirements.

    Caution: Operation of the unit on improper power supply will result in damage to the unit.

    Warning: Before installation or servicing, always TURN OFF all power to the unit. There may be more than one discon-

    nect switch. Ensure all of them are turned off.

    GROUND & POWER WIRESConnect power wires as per wiring diagram. Connect ground wire to the ground lug inside the control box.

    MAINTENANCECOILCoil may be cleaned by removing and brushing between fins with a stiff wire brush. Brushing should be followed by cleaning

    with vacuum cleaner. The coil may also be cleaned by using a high pressure air, if compressed air source is available. It

    should be pointed out that if air filters are used and periodically cleaned, the coils will not be clogged up prematurely.

    DRAIN PIPEDrain pipe should be checked before summer operation of unit. If it is clogged, steps should be taken to clear the debrisso that condensate will flow out easily. A standard pipe cleaner for 1/2" ID pipe may be used. Periodic checks of the drain

    pipe should be taken during summer operation, as there is a possibility of it becoming clogged with dirt.

    FILTER CLEANINGRemove access panel, slide filter out of filter rack, and clean as follows:Tap filter on solid surface to dislodge heavy particles. Wash under stream of hot water. If filter has been put to exceptional

    service, a mild solution of Sal-Soda, Tri-Sodium Phosphate or any other commercial solvent can be used. Set filter onend with slots in frame down, which allows it to drain. Filters should dry thoroughly before reuse.

    REPLACEMENT PARTSWhen writing for replacement parts, refer to model number and serial number on the nameplate of the unit.

    17

  • 7/29/2019 DCX Series

    20/20

    PL-AP-DCX-10-2M-E