EVERGUARD ® TPO UTILITY FLASHING MEMBRANE (TPO ONLY) OR MIN. 8" (203 mm) WIDE REINFORCED EVERGUARD ® MEMBRANE HEAT WELD ON BOTH ENDS ROOF DECK/SUBSTRATE FOAM FILLED POCKET MIN 1" (25.4 mm) OR AS SPECIFIED 8" (203 mm) MIN. 8" (203 mm) MIN. DRILL-TEC PLATES & FASTENERS 12" (305 mm) O.C. DRILL-TEC FASTENER AND ANCHOR BAR 6" (152 mm) O.C. WARM COLD METAL CAP (OPTIONAL) MULTIPLE LAYERS OF ENERGYGUARD ROOF INSULATION, STAGGERED AND OFFSET ® EVERGUARD ® WATER BLOCK EVERGUARD ® BONDING ADHESIVE ISSUE / REVISION DATE DRAWING # GAF 1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411 LEGEND SCALE N.T.S. THIS DETAIL APPLIES TO: ColdStorage 3/1/21 SINGLE-PLY: TPO & PVC 60-80 mil membranes 130A COLD TO WARM TRANSITION TIE-IN ADHERED SYSTEMS MECHANICALLY ATTACHED SYSTEMS RHINOBOND SYSTEMS 1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL ON EACH SIDE, BOTH SIDES OF WALL. NOTE:

ColdStorage - GAF

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ColdStorage - GAF

EVERGUARD

®

TPO UTILITY

FLASHING MEMBRANE (TPO

ONLY) OR MIN. 8" (203 mm) WIDE

REINFORCED EVERGUARD

®

MEMBRANE

HEAT WELD ON BOTH ENDS

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

8" (203 mm) MIN. 8" (203 mm) MIN.

DRILL-TEC

PLATES &

FASTENERS 12" (305 mm) O.C.

DRILL-TEC

FASTENER AND

ANCHOR BAR 6" (152 mm) O.C.

WARM COLD

METAL CAP (OPTIONAL)

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

®

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

BONDING ADHESIVE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

130A

COLD TO WARM TRANSITION TIE-IN

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL ON EACH SIDE, BOTH SIDES OF WALL.

NOTE:

Page 2: ColdStorage - GAF

EVERGUARD

®

TPO UTILITY

FLASHING MEMBRANE (TPO

ONLY) OR MIN. 8" (203 mm)

REINFORCED EVERGUARD

®

MEMBRANE

HEAT-WELDED LAP

ON BOTH ENDS

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

DRILL-TEC

PLATES &

FASTENERS 12" (305 mm) O.C.

WARM COLD

METAL PANEL CAP

(BY OTHERS)

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

®

EVERGUARD

®

WATER BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

130B

COLD TO WARM TRANSITION TIE-IN WITH INSULATED

METAL PANEL ABOVE ROOF DECK

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

INSULATED METAL PANEL

MIN. 4" (102 mm)

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

MIN. 4" (102 mm)

NOTE:

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL, BOTH SIDES OF WALL.

2. AIR SEAL WALL-TO-ROOF DECK INTERFACE.

DRILL-TEC

FASTENER AND

ANCHOR BAR 6" (152 mm) O.C.

EVERGUARD

®

WATER BLOCK

THERMAL CUT IN PANEL SKIN

Page 3: ColdStorage - GAF

REINFORCED EVERGUARD

®

MEMBRANE

MULTIPLE LAYERS OF ENERGYGUARD

ROOF INSULATION, STAGGERED AND

OFFSET

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

130C

COLD TO WARM TRANSITION TIE-IN WITH WALL BELOW

ROOF DECK

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

SEAL MEMBRANE TO ROOF DECK

WITH APPROPRIATE ADHESIVE

INSULATED METAL PANEL

WARM COLD

MIN. 6" (152 mm) MIN. 6" (152 mm)

ROOF DECK/SUBSTRATE

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

NOTE:

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL ON EACH SIDE, BOTH SIDES OF WALL.

2. AIR SEAL WALL-TO-ROOF DECK INTERFACE PER ARCHITECTURAL DRAWINGS.

HEAT-WELDED LAP

WALL TO ROOF DECK INTERFACE PER

PANEL MANUFACTURER INSTRUCTIONS

Page 4: ColdStorage - GAF

REINFORCED EVERGUARD

®

MEMBRANE

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

DRILL-TEC

PLATES & FASTENERS

12" (305 mm) O.C.

WARM COLD

METAL PANEL CAP (BY OTHERS)

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

®

EVERGUARD

®

WATER BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/15/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

130D

COLD TO WARM TRANSITION TIE-IN WITH INSULATED METAL

PANEL ABOVE ROOF DECK - OFFSET IN ROOF LEVELS DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

INSULATED METAL PANEL

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

NOTE:

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL, BOTH SIDES OF WALL.

2. AIR SEAL WALL-TO-ROOF DECK INTERFACE.

DRILL-TEC

FASTENER AND

ANCHOR BAR 6" (152 mm) O.C.

EVERGUARD

®

WATER BLOCK

THERMAL CUT IN PANEL SKIN

HEAT-WELDED LAP ON BOTH ENDS

REINFORCED EVERGUARD

®

MEMBRANE

MIN. 6" (152 mm)MIN. 6" (152 mm)

Page 5: ColdStorage - GAF

EVERGUARD

®

TPO UTILITY

FLASHING MEMBRANE (TPO

ONLY) OR MIN. 8" (203 mm)

WIDE REINFORCED

EVERGUARD

®

MEMBRANE

REINFORCED EVERGUARD

®

MEMBRANE

WOOD NAILER MIN 2" X _"

WALL

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

EVERGUARD

®

COATED

METAL EDGE, SEE NOTE 1

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

201A

COATED METAL ROOF EDGE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

NOTE:

1. METAL EDGE SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7 AND

TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

Page 6: ColdStorage - GAF

EVERGUARD

®

TPO UTILITY FLASHING

MEMBRANE (TPO ONLY) OR MIN. 8" (203 mm)

WIDE REINFORCED EVERGUARD

®

MEMBRANE

REINFORCED EVERGUARD

®

MEMBRANE

INSULATED WALL PANEL

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

EVERGUARD

®

COATED

METAL EDGE, SEE NOTE 1

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

201C

COATED METAL ROOF EDGE AT INSULATED WALL PANEL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

METAL PANEL CAP

(BY OTHERS)

NOTE:

1. PERIMETER EDGE METAL SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. THE ATTACHMENT CAPACITY OF THE INSULATED METAL PANELS SHOULD BE VERIFIED.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

EVERGUARD

®

WATER BLOCK

HEAT-WELDED LAP ON

BOTH ENDS

THERMAL CUT IN PANEL SKIN

Page 7: ColdStorage - GAF

WOOD NAILER MIN 2" X _"

EVERGUARD

®

COATED METAL

GRAVEL STOP WITH HEMMED

EDGE, SEE NOTE 1

GALVANIZED ANGULAR RING

SHANK NAIL @ 4" (102 mm) O.C.

STAGGERED OR DRILL-TEC

FASTENERS 12" (305 mm) O.C.

EVERGUARD

®

TPO UTILITY

FLASHING MEMBRANE (TPO

ONLY) OR MIN. 8" (203 mm)

WIDE REINFORCED

EVERGUARD

®

MEMBRANE

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

202B

COATED METAL GRAVEL STOP AT ROOF EDGE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

1. METAL GRAVEL STOP SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7

AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE DECK

INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

3. AIR SEAL WALL-TO-ROOF DECK INTERFACE.

NOTE:

Page 8: ColdStorage - GAF

WOOD NAILER MIN 2" X _"

METAL GRAVEL STOP WITH

HEMMED EDGE, SEE NOTE 2

GALVANIZED ANGULAR RING

SHANK NAIL @ 4" (102 mm) O.C.

STAGGERED OR DRILL-TEC

FASTENERS 12" (305 mm) O.C.

EVERGUARD

®

TPO COVER TAPE

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

CONTINUOUS BEAD OF

FLEXSEAL

TM

CAULK GRADE

SEALANT.

®

EVERGUARD

®

WATER-BLOCKISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

202C

METAL GRAVEL STOP WITH HEMMED EDGE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

NOTE:

1. CLEAN METAL AND MEMBRANE WITH EVERGUARD

Ò TPO SEAM CLEANER AND ALLOW TO DRY. ONCE DRY, PRIME METAL AND

MEMBRANE WITH EVERGUARD

Ò TPO PRIMER BEFORE INSTALLING EVERGUARD

Ò TPO COVER TAPE.

2. METAL GRAVEL STOP SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

EVERGUARD

®

WATER BLOCK

Page 9: ColdStorage - GAF

EVERGUARD

®

COATED METAL

GRAVEL STOP WITH HEMMED

EDGE, SEE NOTE 1

EVERGUARD

®

TPO UTILITY FLASHING

MEMBRANE (TPO ONLY) OR MIN. 8" (203 mm)

WIDE REINFORCED EVERGUARD

®

MEMBRANE

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

202D

COATED METAL GRAVEL STOP AT ROOF EDGE AT

INSULATED METAL PANELS

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

INSULATED METAL PANEL

METAL PANEL CAP

(BY OTHERS)

NOTE:

1. PERIMETER EDGE METAL SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. THE ATTACHMENT CAPACITY OF THE INSULATED METAL PANELS SHOULD BE VERIFIED.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

EVERGUARD

®

WATER BLOCK

HEAT-WELDED LAP ON

BOTH ENDS

THERMAL CUT IN PANEL SKIN

Page 10: ColdStorage - GAF

METAL GRAVEL STOP WITH

HEMMED EDGE, SEE NOTE 2

EVERGUARD

®

TPO COVER

TAPE

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

NOTE:

1. CLEAN METAL AND MEMBRANE WITH EVERGUARD

Ò TPO SEAM CLEANER AND ALLOW TO DRY. ONCE DRY, PRIME METAL AND

MEMBRANE WITH EVERGUARD

Ò TPO PRIMER BEFORE INSTALLING EVERGUARD

Ò TPO COVER TAPE.

2. PERIMETER EDGE METAL SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7

AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

3. THE ATTACHMENT CAPACITY OF THE INSULATED METAL PANELS SHOULD BE VERIFIED.

4. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE DECK

INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

®

EVERGUARD

®

WATER-BLOCKISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

202E

METAL GRAVEL STOP WITH HEMMED EDGE AT INSULATED

METAL PANEL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

METAL PANEL CAP

(BY OTHERS)

INSULATED METAL PANEL

CONTINUOUS BEAD OF

FLEXSEAL

TM

CAULK GRADE

SEALANT

EVERGUARD

®

WATER BLOCK

THERMAL CUT IN PANEL SKIN

Page 11: ColdStorage - GAF

WOOD NAILER MIN 2" X _"

METAL GRAVEL STOP WITH

HEMMED EDGE, SEE NOTE 2

GALVANIZED ANGULAR RING

SHANK NAIL @ 4" (102 mm) O.C.

STAGGERED OR DRILL-TEC

FASTENERS 12" (305 mm) O.C.

EVERGUARD

®

TPO COVER TAPE

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

CONTINUOUS BEAD OF

FLEXSEAL

TM

CAULK GRADE

SEALANT.

®

EVERGUARD

®

WATER-BLOCKISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

202C

METAL GRAVEL STOP WITH HEMMED EDGE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

NOTE:

1. CLEAN METAL AND MEMBRANE WITH EVERGUARD

Ò TPO SEAM CLEANER AND ALLOW TO DRY. ONCE DRY, PRIME METAL AND

MEMBRANE WITH EVERGUARD

Ò TPO PRIMER BEFORE INSTALLING EVERGUARD

Ò TPO COVER TAPE.

2. METAL GRAVEL STOP SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

EVERGUARD

®

WATER BLOCK

Page 12: ColdStorage - GAF

REINFORCED EVERGUARD

®

MEMBRANE

INSULATED METAL PANEL

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

METAL EDGE, SEE NOTE 2

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

EVERGUARD

®

TPO COVER

TAPE

CONTINUOUS BEAD OF

FLEXSEAL

TM

CAULK GRADE

SEALANT

®

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

203D

METAL ROOF EDGE WITH COVER TAPE DETAIL AT

INSULATED METAL PANELS

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

METAL PANEL CAP

(BY OTHERS)

NOTE:

1. CLEAN METAL AND MEMBRANE WITH EVERGUARD

Ò TPO SEAM CLEANER AND ALLOW TO DRY. ONCE DRY, PRIME METAL AND

MEMBRANE WITH EVERGUARD

Ò TPO PRIMER BEFORE INSTALLING EVERGUARD

Ò TPO COVER TAPE.

2. PERIMETER EDGE METAL SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

3. THE ATTACHMENT CAPACITY OF THE INSULATED METAL PANELS SHOULD BE VERIFIED.

4. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

EVERGUARD

®

WATER BLOCK

THERMAL CUT IN PANEL SKIN

Page 13: ColdStorage - GAF

WOOD NAILER MIN 2" X _"

WALL

SNAP-ON FASCIA,

SEE NOTE 1

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

FLEXSEAL

TM

CAULK-GRADE SEALANT

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

205

SNAP ON FASCIA DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

1. SNAP-ON FASCIA SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7

AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

NOTE:

Page 14: ColdStorage - GAF

SHEET METAL GUTTER

WOOD NAILER MIN 2" X _"

WALL

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

EVERGUARD

®

TPO UTILITY FLASHING

MEMBRANE (TPO ONLY) OR MIN. 8"

(203 mm) WIDE REINFORCED

EVERGUARD

®

MEMBRANE

HEAT WELD BOTH SIDES

EVERGUARD

®

COATED

METAL EDGE, SEE NOTE 1

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

HEAT-WELDED

FLEXSEAL

TM

CAULK-GRADE SEALANT

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

211B

GUTTER WITH COATED METAL ROOF EDGE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

1. METAL EDGE SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7

AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

NOTE:

EVERGUARD

®

WATER BLOCK

Page 15: ColdStorage - GAF

SHEET METAL GUTTER

WOOD NAILER MIN 2" X _"

WALL

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

METAL EDGE, SEE NOTE 2

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

CONTINUOUS BEAD OF

FLEXSEAL

TM

CAULK GRADE

SEALANT OR EVERGUARD

®

CUT EDGE SEALANT.

EVERGUARD

®

TPO COVER

TAPE

®

FLEXSEAL

TM

CAULK-GRADE SEALANTISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

211C

GUTTER WITH METAL ROOF EDGE AND COVER TAPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

EVERGUARD

®

WATER BLOCK

NOTE:

1. CLEAN METAL AND MEMBRANE WITH EVERGUARD

Ò TPO SEAM CLEANER AND ALLOW TO DRY. ONCE DRY, PRIME METAL AND

MEMBRANE WITH EVERGUARD

Ò TPO PRIMER BEFORE INSTALLING EVERGUARD

Ò TPO COVER TAPE.

2. PERIMETER EDGE METAL SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

Page 16: ColdStorage - GAF

WOOD NAILER MIN 2" X _"

WALL

EVERGUARD

®

EZ FASCIA WITH

CONCEALED JOINT

SPLICE, SEE NOTE 1

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

FLEXSEAL

TM

CAULK-GRADE SEALANT

EVERGUARD

®

WATER-BLOCK

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

4/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

232E

EZ FASCIA DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

1. EZ FASCIA SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7 AND

TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN ANSI/SPRI ES-1.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

NOTE:

EVERGUARD

®

WATER BLOCK

Page 17: ColdStorage - GAF

®

NOTE:

1. EXPOSED WALLS/CURBS MUST BE WATERPROOFED AND MAINTAINED ABOVE THE BASE FLASHING IN ORDER FOR ANY

SURFACE-MOUNTED TERMINATION TO BE EFFECTIVE.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

-OPTIONAL UP TO 30" (762 mm) FLASHING HEIGHT

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

301B

WALL FLASHING WITH COUNTERFLASHING

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

FOAM FILLED POCKET MIN 1" (25.4 mm) OR AS SPECIFIED

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

ROOF DECK/SUBSTRATE

REINFORCED EVERGUARD

®

MEMBRANE

DRILL-TEC

TERMINATION BAR FASTENED 12" O.C.

EVERGUARD

®

WATER BLOCK

METAL SURFACE MOUNTED COUNTERFLASHING

DRILL-TEC

FASTENERS AND SEALING

WASHERS FASTENED 12" (305 mm) O.C.

FLEXSEAL

CAULK GRADE SEALANT

Page 18: ColdStorage - GAF

®

NOTE:

1. EXPOSED WALLS/CURBS MUST BE WATERPROOFED AND MAINTAINED ABOVE THE BASE FLASHING IN ORDER FOR ANY

SURFACE-MOUNTED TERMINATION TO BE EFFECTIVE.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/17/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

302B

WALL/CURB FLASHING WITH TERMINATION BAR DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT WELD LAP

FOAM FILLED POCKET MIN 1" (25.4 mm)

OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

REINFORCED EVERGUARD

®

MEMBRANE

EVERGUARD

®

BONDING ADHESIVE - OPTIONAL

UP TO 30" (762 mm) FLASHING HEIGHT

DRILL-TEC

TERMINATION BAR FASTENED

12" (305 mm) O.C.

EVERGUARD

®

WATER BLOCK

DRILL-TEC

TERMINATION BAR WITH

DRILL-TEC

FASTENERS AND SEALING

WASHERS FASTENED 12" (305 mm) O.C.

FLEXSEAL

CAULK GRADE SEALANT

EVERGUARD

®

WATER BLOCK OR

FLEXSEAL

CAULK GRADE SEALANT

EVERGUARD

®

WATER-BLOCK

Page 19: ColdStorage - GAF

®

NOTE:

1. METAL COPING CAP SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7

AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1.

2. THE ATTACHMENT CAPACITY OF THE INSULATED METAL PANELS SHOULD BE VERIFIED.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL

FOAM FILLED POCKET

MIN 1" (25.4 mm) OR AS

SPECIFIED

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

ROOF DECK/SUBSTRATE

REINFORCED EVERGUARD

®

MEMBRANE

METAL PANEL CAP (BY OTHERS)

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

303B

INSULATED METAL PANEL WALL WITH COPING CAP

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

METAL COPING CAP, SEE NOTE 1

INSULATED METAL PANEL

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

WATER BLOCK

HEAT-WELDED LAP

EVERGUARD

®

BONDING ADHESIVE

THERMAL CUT IN

PANEL SKIN

INSULATED METAL

PANEL

Page 20: ColdStorage - GAF

®

NOTE:

1. METAL COPING CAP SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7 AND

TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN ANSI/SPRI ES-1.

2. A VAPOR RETARDER AT THE DECK LEVEL MAY BE USED IF THERE ARE CONCERNS WITH POTENTIAL MOISTURE ISSUES DUE TO CERTAIN

CONSTRUCTION PROCESSES OR OTHER SOURCES DURING BUILDING USE.

3. REFER TO GAF SA PRIMER INSTALLATION INSTRUCTIONS FOR GENERAL GUIDELINES.

4. A MINIMUM

1

2

INCH THICK GLASS-MAT-FACED OR FIBER-REINFORCED GYPSUM BOARD IS REQUIRED OVER STEEL DECKS.

5. MAINTAIN SEPARATION BETWEEN VAPOR RETARDER AND MEMBRANE/ ADHESIVE TO AVOID POTENTIAL INCOMPATIBILITY ISSUES.

6. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE DECK

INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL, BOTH SIDES OF WALL.

7. AIR SEAL WALL-TO-ROOF DECK INTERFACE.

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

GAF SA VAPOR RETARDER, SEE NOTE 2.

EXTEND 2" MINIMUM (51 mm) UP WALL FACE

REINFORCED EVERGUARD

®

MEMBRANE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

4/6/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

303C

INSULATED METAL PANEL WALL WITH COPING CAP AND

SA VAPOR RETARDER

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

METAL COPING CAP, SEE NOTE 1

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

WATER BLOCK

HEAT-WELDED LAP

EVERGUARD

®

BONDING ADHESIVE

ROOF DECK/SUBSTRATE

WALL

GAF SA PRIMER

Page 21: ColdStorage - GAF

®

NOTE:

1. COATED METAL EDGE SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF

ASCE 7 AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN ANSI/SPRI ES-1.

2. STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE DECK

INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/22/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

304B

WALL FLASHING WITH COATED METAL EDGE DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

MULTIPLE LAYERS OF ENERGYGUARD

ROOF INSULATION

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

REINFORCED EVERGUARD

®

MEMBRANE

EVERGUARD

®

COATED METAL,

SEE NOTE 1

EVERGUARD

®

TPO UTILITY FLASHING

MEMBRANE OR 6" (152 mm) REINFORCED

EVERGUARD

®

MEMBRANE

WALL

ANGULAR ROOFING NAILS

12" (305 mm) O.C.

Page 22: ColdStorage - GAF

REINFORCED EVERGUARD

®

MEMBRANE

WOOD NAILER MIN 2" X _"

WALL

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

METAL EDGE, SEE NOTE 2

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

EVERGUARD

®

TPO COVER TAPE

CONTINUOUS BEAD OF

FLEXSEAL

TM

CAULK GRADE

SEALANT.

®

NOTE:

1. CLEAN METAL AND MEMBRANE WITH EVERGUARD

Ò TPO SEAM CLEANER AND ALLOW TO DRY. ONCE DRY, PRIME METAL AND

MEMBRANE WITH EVERGUARD

Ò TPO PRIMER BEFORE INSTALLING EVERGUARD

Ò TPO COVER TAPE.

2. METAL EDGE SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7 AND

TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN ANSI/SPRI ES-1.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/22/21

SINGLE-PLY: TPO 60-80 mil membranes

304C

WALL FLASHING WITH METAL EDGE WITH COVER TAPE

DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

WATER BLOCK

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

Page 23: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

4/6/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

309

BASE WALL TERMINATION WITH SA VAPOR RETARDER

DETAIL AT WALL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

GAF SA PRIMER

1.USE DETAIL IN CONJUNCTION WITH THE STANDARD TERMINATION DETAIL FOR APPROVED ROOF SYSTEM.

2. A VAPOR RETARDER AT THE DECK LEVEL MAY BE USED IF THERE ARE CONCERNS WITH POTENTIAL MOISTURE

ISSUES DUE TO CERTAIN CONSTRUCTION PROCESSES OR OTHER SOURCES DURING BUILDING USE.

3. REFER TO GAF SA PRIMER INSTALLATION INSTRUCTIONS FOR GENERAL GUIDELINES.

4. MAINTAIN SEPARATION BETWEEN VAPOR RETARDER AND MEMBRANE/ ADHESIVE TO AVOID POTENTIAL

INCOMPATIBILITY ISSUES.

5. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION

OF ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

6. AIR SEAL WALL-TO-ROOF DECK INTERFACE.

NOTE:

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

MINIMUM 1/2 INCH (12.7 mm)

THICK GLASS-MAT-FACED

OR FIBER-REINFORCED

GYPSUM BOARD

WALL

GAF SA VAPOR RETARDER, SEE

NOTE 2. EXTEND 2" MINIMUM

(51 mm) UP WALL FACE

REINFORCED EVERGUARD

®

MEMBRANE

STEEL DECK

REFERENCE EVERGUARD

®

300 SERIES PARAPET WALL

AND CURB DETAILS FOR

TERMINATION

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

REINFORCED EVERGUARD

®

MEMBRANE

FOAM FILLED GAP AT

PENETRATION OPENING

WHEN NEEDED TO

SUPPORT VAPOR

RETARDER

Page 24: ColdStorage - GAF

EVERGUARD

®

TPO UTILITY FLASHING MEMBRANE (TPO ONLY)

OR REINFORCED EVERGUARD

®

MEMBRANE

EVERGUARD

®

BONDING ADHESIVE

REINFORCED EVERGUARD

®

MEMBRANE

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1" (25.4 mm) OR AS SPECIFIED

DRILL-TEC™

PLATES &

FASTENERS 12"

(305 mm) O.C.

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

EVERGUARD

®

COATED METAL

®

NOTE:

1. STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

REINFORCED EVERGUARD

®

MEMBRANE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/15/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

323B

SCUPPER - FIELD FABRICATED WITH COATED METAL -

OVERFLOW

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

REFERENCE EVERGUARD

®

PARAPET WALL & CURB FLASHING

DETAILS (300 SERIES) FOR WALL OR CURB TERMINATION

HEAT WELD ON BOTH ENDS

HEAT-WELDED LAP

HEAT-WELDED

LAP

EVERGUARD

®

TPO UTILITY FLASHING MEMBRANE (TPO ONLY)

OR REINFORCED EVERGUARD

®

MEMBRANE

EVERGUARD

®

WATER-BLOCK

REINFORCED EVERGUARD

®

MEMBRANE

FLEXSEAL

TM

CAULK GRADE SEALANT

EVERGUARD

®

COATED METAL

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

BONDING ADHESIVE

HEAT-WELDED LAP

Page 25: ColdStorage - GAF

EVERGUARD

®

TPO UTILITY FLASHING

MEMBRANE (TPO ONLY) OR MIN. 8" (203 mm)

WIDE REINFORCED EVERGUARD

®

MEMBRANE

COPING CAP, SEE NOTE 1

EVERGUARD

®

BONDING ADHESIVE

REINFORCED EVERGUARD

®

MEMBRANE

EVERGUARD

®

WATER BLOCK

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1" (25.4 mm)

OR AS SPECIFIED

DRILL-TEC™ PLATES & FASTENERS

12" (305 mm) O.C.

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

SHEET METAL

CONDUCTOR

HEAD

EVERGUARD

®

COATED METAL

®

NOTE:

1. METAL EDGE SHOULD BE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH THE APPLICABLE EDITION OF ASCE 7

AND TESTED FOR CAPACITY IN ACCORDANCE WITH THE TEST METHODS IN THE APPLICABLE EDITION OF ANSI/SPRI ES-1. FOR

2. STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

HEAT-WELDED

FLEXSEAL

CAULK GRADE SEALANT

REINFORCED EVERGUARD

®

MEMBRANE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

324B

THROUGH WALL SCUPPER WITH COATED METAL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

CONTINUOUS BEAD OF FLEXSEAL

TM

CAULK

GRADE SEALANT.

Page 26: ColdStorage - GAF

ROOF DECK/SUBSTRATE

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

®

NOTE:

1. SCUPPER MUST ALSO BE SEALED ON OUTSIDE WALL.

2. FOR ALTERNATE BASE ATTACHMENT, REFER TO DETAIL 307.

3. STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL.

HEAT-WELDED

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/15/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

324D

THROUGH WALL SCUPPER - PREFABRICATED DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

REINFORCED EVERGUARD

®

MEMBRANE

REAR VIEW OF SCUPPER

REINFORCED EVERGUARD

®

MEMBRANE

SECURE WITH DRILL-TEC

FASTENERS

PREMANUFACTURED EVERGUARD

®

TPO SCUPPER FASTENED WITH 4

FASTENERS OR 12" (305 mm) O.C.

Page 27: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/22/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

350

AIR SEAL DETAIL AT STEEL DECK TO WALL INTERFACE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

STEEL DECK PARALLEL TO WALL

STEEL DECK PERPENDICULAR TO WALL

FILL FIRST TWO STEEL DECK FLUTES WITH SPRAY FOAM

INSULATION PRIOR TO THE INSTALLATION OF ABOVE DECK INSULATION

FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION

OF ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL

STEEL DECK

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

STEEL DECK

STEEL DECK

WALL

STEEL DECK

FOAM FILLED POCKET MIN. 1"

(25.4 mm) OR AS SPECIFIED

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

WALL

SHEET METAL CLOSURE

SHEET METAL CLOSURE

Page 28: ColdStorage - GAF

®

NOTE:

1. SEE EVERGUARD

®

DETAIL 330 FOR LAP APPLICATION.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM EDGE OF EXPANSION JOINT.

HEAT-WELDED

TACK WELD INTERMITTENTLY ON BOTH

CURBS TO HOLD IN PLACE IF NEEDED

FACTORY-FABRICATED

TPO EVERGUARD

®

EXPANSION JOINT COVER

COMPRESSIBLE

ROD/BATT INSULATION

FIELD MEMBRANE SHOULD RUN

INTO THE EXPANSION JOINT

CONTINUING ONTO THE OTHER SIDE

AND TERMINATING AS INDICATED

WOOD NAILER, 5/4"

(31.8 mm) x 4" (102 mm)

MIN. SECURED TO DECK

FOAM FILLED POCKET

MIN 1" (25.4 mm) OR AS

SPECIFIED

DRILL-TEC

FASTENERS

AND PLATES 12" (305 mm) O.C.

(FOR BALLASTED SYSTEMS 6"

[152 mm] O.C.)

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION

TAPERED EDGE STRIP

INSTALL THE EVERGUARD

®

FACTORY-FABRICATED EXPANSION

COVER OUT PAST THE MECHANICAL

ATTACHMENT AND HOT AIR-WELD

REINFORCED EVERGUARD

®

TPO MEMBRANE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO 60-80 mil membranes

401D

FACTORY FABRICATED EXPANSION JOINT DETAIL

- FLAT TYPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

Page 29: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/8/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

402D

FIELD FABRICATED EXPANSION JOINT - CURB TYPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

BONDING ADHESIVE

(OPTIONAL)

WOOD NAILERS MIN. 2" X _"

SECURED TO SUBSTRATE

DRILL-TEC

FASTENERS AND PLATES

12" (305 mm) O.C.

1. FIELD FABRICATED EXPANSION JOINT SHOULD BE SMOOTH BACKED MEMBRANE ONLY.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM EDGE OF EXPANSION JOINT.

NOTE:

BATT INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP

BACKER ROD 1-1/2 TIMES THE OPENING.

SECURE MEMBRANE AT TOP OF CURB WITH

RING SHANK ROOFING NAILS 12" (305 mm) O.C.

FOAM FILLED POCKET MIN 1" (25.4 mm)

OR AS SPECIFIED

REINFORCED EVERGUARD

®

MEMBRANE

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

REINFORCED EVERGUARD

®

MEMBRANE

HEAT-WELDED LAP

REINFORCED EVERGUARD

®

MEMBRANE

Page 30: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/8/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

402E

FACTORY FABRICATED EXPANSION JOINT - CURB TYPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

BONDING ADHESIVE

(OPTIONAL)

WOOD NAILERS MIN. 2" X _"

SECURED TO SUBSTRATE

DRILL-TEC

FASTENERS AND PLATES

12" (305 mm) O.C.

1. SEE EVERGUARD DETAIL 330 FOR LAP APPLICATION.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM EDGE OF EXPANSION JOINT.

NOTE:

BATT INSULATION

ROOF DECK/SUBSTRATE

HEAT-WELDED LAP

SECURE MEMBRANE AT TOP OF CURB WITH

RING SHANK ROOFING NAILS 12" (305 mm) O.C.

FOAM FILLED POCKET MIN 1" (25.4 mm)

OR AS SPECIFIED

MULTIPLE LAYERS OF ENERGYGUARD

ROOF

INSULATION, STAGGERED AND OFFSET

REINFORCED EVERGUARD

®

MEMBRANE

HEAT-WELDED LAP

TACK WELD INTERMITTENTLY ON BOTH

CURBS TO HOLD IN PLACE IF NEEDED

WHILE INSTALLING

FACTORY FABRICATED EVERGUARD

®

TPO

EXPANSION JOINT COVER

FOAM EXTENDS

2" (52 mm) INTO

OPENING

REINFORCED EVERGUARD

®

MEMBRANE

Page 31: ColdStorage - GAF

®

NOTE:

1. FIELD-FABRICATED EXPANSION JOINT SHOULD USE A SMOOTH BACKED MEMBRANE.

2. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL

FOAM FILLED POCKET MIN 1" (25.4 mm) OR

AS SPECIFIED

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

ROOF DECK/SUBSTRATE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/8/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

403D

FIELD FABRICATED WALL EXPANSION JOINT - FLAT TYPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

HEAT-WELDED

LAP

EVERGUARD

®

BONDING ADHESIVE

WOOD NAILERS MIN. 2" X _" SECURED TO

SUBSTRATE

REFERENCE EVERGUARD

®

PARAPET WALL

& CURB FLASHING DETAILS (300 SERIES)

FOR WALL OR CURB TERMINATION

REINFORCED EVERGUARD

®

MEMBRANE

REINFORCED EVERGUARD

®

SMOOTH MEMBRANE

DRILL-TEC

FASTENERS AND PLATES 12"

(305 mm) O.C.

BATT INSULATION

BACKER ROD

1-1/2 TIMES THE

OPENING

HEAT-WELDED LAP

Page 32: ColdStorage - GAF

®

NOTE:

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF WALL

FOAM FILLED POCKET MIN 1" (25.4 mm) OR AS SPECIFIED

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

ROOF DECK/SUBSTRATE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/29/21

SINGLE-PLY: TPO 60-80 mil membranes

404D

FACTORY FABRICATED WALL EXPANSION JOINT - CURB

TYPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

HEAT-WELDED

LAP

EVERGUARD

®

BONDING ADHESIVE

WOOD NAILERS MIN. 2" X _" SECURED TO SUBSTRATE

REFERENCE EVERGUARD

®

PARAPET WALL & CURB FLASHING

DETAILS (300 SERIES) FOR WALL OR CURB TERMINATION

REINFORCED EVERGUARD

®

MEMBRANE

DRILL-TEC

FASTENERS AND PLATES 12" (305 mm) O.C.

FOAM EXTENDS 3" (76 mm) INTO OPENING

TACK WELD FLANGE INTERMITTENTLY BETWEEN FASTENERS

ADJACENT TO BELLOWS

HEAT-WELDED LAP

FACTORY FABRICATED EVERGUARD

®

TPO EXPANSION

JOINT COVER

SECURE MEMBRANE AT TOP WITH RING SHANK ROOFING NAILS

12" (305 mm) O.C.

BASE FLASHING MEMBRANE SHOULD RUN INTO EXPANSION

JOINT AND CONTINUE UP THE WALL AND TERMINATE AS

INDICATED

BATT INSULATION

Page 33: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

503C

TERMINATION AT R.T.U. DETAIL WITH WELDED LAP

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

FOAM FILLED POCKET MIN 1" (25.4 mm)

OR AS SPECIFIED

R.T.U.

FASTENERS AT 12" (305 mm) O.C. MAX

INSULATED METAL CURB

WOOD NAILER THICKNESS OF INSULATION

ENERGYGUARD

ROOF INSULATION

DRILL-TEC

FASTENERS 12" (305 mm) O.C.

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION

ROOF DECK/SUBSTRATE

REFERENCE EVERGUARD

®

PARAPET WALL & CURB

FLASHING DETAILS (300 SERIES) FOR BASE TERMINATION

REINFORCED EVERGUARD

®

MEMBRANE

WOOD NAILERS MIN. 2" X _"

HEAT-WELDED

NOTE:

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF OPENING.

Page 34: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/29/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

505B

ROOF HATCH DETAIL - AMBIENT INTERIOR CONDITIONS

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

FOAM FILLED POCKET MIN 1" (25.4 mm) OR AS SPECIFIED

DRILL-TEC

FASTENERS 12" (305 mm) O.C.

ROOF DECK/SUBSTRATE

REINFORCED EVERGUARD

®

MEMBRANE

WOOD NAILERS MIN. 2" X _"

NOTE:

1. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF ABOVE

DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM FACE OF OPENING.

WALKWAY PAD REQUIRED

AT ROOF ACCESS

ROOF HATCH BY OTHERS

MEMBRANE MUST BE ON THREE SIDES OF HATCH OPENING

SOLID BACKER ROD 50% LARGER THAN OPENING

8" (203 m

m) M

IN

.

MULTIPLE LAYERS OF ENERGYGUARD

ROOF INSULATION,

STAGGERED AND OFFSET

HEAT-WELDED

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

BONDING ADHESIVE

Page 35: ColdStorage - GAF

[12" (305 mm) OR MORE OF INSULATION]

®

HEAT-WELDED

FLEXSEAL

CAULK GRADE SEALANT

NOTE:

1. DO NOT CUT SIDE OF PREMOLDED BOOT. IT MUST BE PULLED OVER VENT PIPE.

2. IF THE PLATES AND FASTENERS INTRUDE INTO BOOT FLANGE AREA, THEN A TARGET MUST FIRST BE INSTALLED OVER

PLATES AND FASTENERS BEFORE BOOT INSTALLATION.

2" (52 mm)

2" (52 mm)

ALTERNATE INSTALLATION

SEE NOTE #2

TARGET MADE FROM REINFORCED

EVERGUARD

®

MEMBRANE

EVERGUARD

®

PREMOLDED VENT BOOT

VENT STACK

EVERGUARD

®

WATER BLOCK OR

FLEXSEAL

CAULK GRADE SEALANT

STAINLESS

STEEL CLAMP

EVERGUARD

®

PREMOLDED VENT BOOT

REINFORCED

EVERGUARD

®

MEMBRANE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

ROOF DECK/SUBSTRATE

DRILL-TEC

PLATES

& FASTENERS

4 PER PENETRATION

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

506B

PREMOLDED VENT BOOT FLASHING DETAIL - AMBIENT

INTERIOR CONDITIONS

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

Page 36: ColdStorage - GAF

®

FOAM FILLED POCKET

MIN 1" (25.4 mm) OR AS SPECIFIED

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

506C

INSULATED PIPE PENETRATION DETAIL WITH FLASHING

TO PIPE

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

8" (203 m

m)

STAINLESS

STEEL CLAMP

PIPE PENETRATION

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF INSULATION

REINFORCED

EVERGUARD

®

MEMBRANE

EVERGUARD

®

WATER

BLOCK OR FLEXSEAL

CAULK GRADE SEALANT

EVERGUARD

®

DETAIL

MEMBRANE OR SPLIT

BOOT

REFERENCE EVERGUARD

®

ROOF PENETRATION

DETAILS (SERIES 500) FOR

FLASHING DETAILS

FLEXSEAL

CAULK

GRADE SEALANT

PIPE INSULATION AND

INSULATION JACKET

INSTALLED OVER

FLASHING

(SHOWN DASHED)

ROOF

DECK/SUBSTRATE

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

BONDING

ADHESIVE

Page 37: ColdStorage - GAF

®

FOAM FILLED POCKET

MIN 1" (25.4 mm) OR AS

SPECIFIED

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

506D

INSULATED PIPE PENETRATION DETAIL WITH FLASHING

TO PIPE INSULATION

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

8" (203 m

m)

PIPE PENETRATION

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION

REINFORCED

EVERGUARD

®

MEMBRANE

EVERGUARD

®

WATER

BLOCK OR FLEXSEAL

CAULK GRADE SEALANT

EVERGUARD

®

DETAIL

MEMBRANE OR SPLIT

BOOT

REFERENCE

EVERGUARD

®

ROOF

PENETRATION DETAILS

(SERIES 500) FOR FLASHING

DETAILS

FLEXSEAL

CAULK

GRADE SEALANT

PIPE INSULATION

JACKET INSTALLED

OVER FLASHING AND

PIPE INSULATION

ROOF

DECK/SUBSTRATE

PIPE INSULATION

CONTINUOUS THROUGH

ROOF DECK

HEAT-WELDED

EVERGUARD

®

WATER-BLOCK

EVERGUARD

®

BONDING ADHESIVE

EVERGUARD

®

BONDING

ADHESIVE

Page 38: ColdStorage - GAF

®

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

3/1/21

SINGLE-PLY: TPO & PVC 60-80 mil membranes

511B

EXPOSED WOOD EQUIPMENT SUPPORT SLEEPER DETAIL

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

ROOF

DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION

REINFORCED

EVERGUARD

®

MEMBRANE

WOOD SLEEPER

FOAM FILLED POCKET

MIN 1" (25.4 mm) OR AS

SPECIFIED

WOOD BLOCKING

EQUIPMENT SUPPORT

STAND

EVERGUARD

®

WALKWAY PAD OR

MEMBRANE PROTECTION PLY,

CONTINUOUS UNDER SLEEPER

Page 39: ColdStorage - GAF

®

EVERGUARD

®

WATER BLOCK

EVERGUARD

®

BONDING ADHESIVE

ISSUE / REVISION DATEDRAWING #

GAF ●

1 Campus Drive Parsippany, NJ 07054 ● www.gaf.com ● [email protected] ● 800-766-3411

LEGEND

SCALE

N.T.S.

THIS DETAIL APPLIES TO:

ColdStorage

4/6/21

SINGLE-PLY: TPO 60-80 mil membranes

609C

TPO TO EXISTING EPDM - NONADHERED

ADHERED SYSTEMS

MECHANICALLY ATTACHED SYSTEMS

RHINOBOND SYSTEMS

NOTE:

1. GAF DOES NOT GUARANTEE THE WATERTIGHT INTEGRITY OF TIE-INS TO OTHER MEMBRANE ROOF SYSTEMS.

2. WOOD BLOCKING MUST BE SEALED TO THE DECK. IF STEEL DECK, ALL LOWER FLUTES MUST BE SEALED TO PREVENT

WATER FROM GOING PAST THIS DETAIL UNDER THE ROOF.

3. FOR STEEL ROOF DECKS: FILL STEEL DECK FLUTES WITH SPRAY FOAM INSULATION PRIOR TO THE INSTALLATION OF

ABOVE DECK INSULATION A MINIMUM OF 12 INCHES (305 mm) FROM WOOD NAILER ON NEW TPO SIDE OF ROOF.

EXISTING EPDM

WOOD NAILERS,

MIN 2" X _"

ROOF DECK/SUBSTRATE

MULTIPLE LAYERS OF

ENERGYGUARD

ROOF

INSULATION, STAGGERED

AND OFFSET

REINFORCED EVERGUARD

®

TPO MEMBRANE

DRILL-TEC

TERMINATION BAR FASTENED 12" (305 mm)

3" (76 mm) EPDM SEAM TAPE AND PRIMER BY OTHERS

EVERGUARD

®

TPO COVER TAPE OVER SURFACE

PRIMED WITH EVERGUARD

®

TPO PRIMER

FOAM FILLED POCKET MIN 1"

(25.4 mm) OR AS SPECIFIED

EVERGUARD

®

WATER BLOCK