2
- F - 20001 D CAT.NO. MANUAL FIRE ALARM BOX FEATURES Cutting-edge compact design Push-button-type manual fire alarm box Easy reset after operation Addressable and conventional types available Telecommunication means provided (except FMMN202-U) Response lamp provided (except FMMN202-U) NOHMI’s FMMN, FMRN & FMBN series manual fire alarm box was designed based on a new concept considering functionality, accessibility, and usability, and won the Japan Good Design Gold Award 2014 together with the ring-shaped location lamp. The fire alarm box is 40mm smaller in diameter than the previous model to match the ring-shaped location lamp. The fire alarm box can be installed without any mounting plate, or can be installed with a surface or recess adapter in retrofit applications. The manual fire alarm box initiates a fire alarm signal by pushing the plexi-glass, which is noticeable by its white edge. The operated plexi-glass can be restored by only lifting up the reset lever inside the jack cover. A telephone jack is provided inside the jack cover on the fire alarm box except FMMN202-U. Inserting the plug of a telephone handset into the jack makes telecommunication ready between the fire alarm control panel and the manual fire alarm box. A response lamp is also provided on fire alarm box except FMMN202-U to indicate that a fire alarm signal has been received at the fire alarm control panel. The fire alarm signal initiated from a manual fire alarm box can be utilized to start the hydrant pump with a NOHMI’s FYH series hydrant pump starting relay box incorporated. ●HEAD OFFICE:7-3, Kudan-Minami 4-chome, Chiyoda-ku, Tokyo 102-8277, Japan ●PHONE:( 81)3-3265-0231 ●FAX:( 81)3-3265-5348 ●Accessories: Model no. ZBMJ002-U (Recess mounting adapter plate) Model no. ZBMJ002-UW (Recess mounting adapter plate, outdoor use) Model no. ZBMJ002-R (Surface mounting box) SPECIFICATIONS WITH SURFACE BOX WITH RECESS ADAPTER MANUAL FIRE ALARM BOX MODEL NO. FMMN102-UW FMRN102-U SYSTEM TYPE USE SPECIFICATIONS TELEPHONE JACK RESPONSE LAMP CIRCUIT VOLTAGE MONITORING CURRENT MATERIALS COLOR WEIGHT Polycarbonate resins (Self-extinguishing) Red (equivalent to Munsell 5R4/14) DESCRIPTION FMMN202-U FMBN102-UW Conventional Outdoor Yes FMMN102-U Conventional Indoor Yes Conventional Indoor No Addressable (No address no.) Indoor Yes FMBN102-U Addressable Indoor Yes Addressable Outdoor Yes Yes 30VDC, 500mA N/A S+ S-:24VDC, 200mA Approx. 0.25mA Yes No Yes Yes Yes Approx. 130g Approx. 137g Approx. 130g Approx. 145g Approx. 135g Approx. 142g FMMN , FMRN & FMBN SERIES FMMN , FMRN & FMBN SERIES

CAT.NO.D MANUAL FIRE ALARM BOX FMMN FMRN & FMBN … · box can be utilized to start the hydrant pump with a NOHMI’s FYH series hydrant pump starting relay box incorporated. HEAD

Embed Size (px)

Citation preview

Page 1: CAT.NO.D MANUAL FIRE ALARM BOX FMMN FMRN & FMBN … · box can be utilized to start the hydrant pump with a NOHMI’s FYH series hydrant pump starting relay box incorporated. HEAD

-F-20001DCAT.NO.

MANUAL FIRE ALARM BOX

FEATURES●Cutting-edge compact design●Push-button-type manual fire alarm box●Easy reset after operation●Addressable and conventional types available●Telecommunication means provided (except FMMN202-U)●Response lamp provided (except FMMN202-U)

NOHMI’s FMMN, FMRN & FMBN series manual fire alarm box was designed based on a new concept considering functionality, accessibility, and usability, and won the Japan Good Design Gold Award 2014 together with the ring-shaped location lamp.The fire alarm box is 40mm smaller in diameter than the previous model to match the ring-shaped location lamp. The fire alarm box can be installed without any mounting plate, or can be installed with a surface or recess adapter in retrofit applications.The manual fire alarm box initiates a fire alarm signal by pushing the plexi-glass, which is noticeable by its white edge. The operated plexi-glass can be restored by only lifting up the reset lever inside the jack cover.A telephone jack is provided inside the jack cover on the fire alarm box except FMMN202-U. Inserting the plug of a telephone handset into the jack makes telecommunication ready between the fire alarm control

panel and the manual fire alarm box.A response lamp is also provided on fire alarm box except FMMN202-U to indicate that a fire alarm signal has been received at the fire alarm control panel.The fire alarm signal initiated from a manual fire alarm box can be utilized to start the hydrant pump with a NOHMI’s FYH series hydrant pump starting relay box incorporated.

●HEAD OFFICE:7-3, Kudan-Minami 4-chome, Chiyoda-ku, Tokyo 102-8277, Japan ●PHONE:(81)3-3265-0231 ●FAX:(81)3-3265-5348

●Accessories: Model no. ZBMJ002-U (Recess mounting adapter plate)  Model no. ZBMJ002-UW (Recess mounting adapter plate, outdoor use)  Model no. ZBMJ002-R (Surface mounting box)

SPECIFICATIONS

WITH SURFACE BOXWITH RECESS ADAPTER

MANUAL FIRE ALARM BOX

MODEL NO. FMMN102-UW FMRN102-U

SYSTEM TYPE

USE SPECIFICATIONSTELEPHONE JACKRESPONSE LAMPCIRCUIT VOLTAGE MONITORING CURRENTMATERIALSCOLORWEIGHT

Polycarbonate resins (Self-extinguishing)Red (equivalent to Munsell 5R4/14)

DESCRIPTION

FMMN202-U FMBN102-UW

Conventional

OutdoorYes

FMMN102-U

Conventional

IndoorYes

Conventional

IndoorNo

Addressable(No address no.)

IndoorYes

FMBN102-U

Addressable

IndoorYes

Addressable

OutdoorYes

Yes30VDC, 500mA

N/A

S+ S-:24VDC, 200mA

Approx. 0.25mA

Yes No Yes Yes Yes

Approx. 130g Approx. 137g Approx. 130g Approx. 145g Approx. 135g Approx. 142g

FMMN, FMRN& FMBN SERIESFMMN, FMRN

& FMBN SERIES

Page 2: CAT.NO.D MANUAL FIRE ALARM BOX FMMN FMRN & FMBN … · box can be utilized to start the hydrant pump with a NOHMI’s FYH series hydrant pump starting relay box incorporated. HEAD

MANUAL FIRE ALARM BOX SERIESTYPICAL WIRING DIAGRAM

DIMENSIONS

INSTALLATION

180810 -F-20001YO1D

-F-20001DCAT. NO.

●●●

These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation, and maintenance.Specifications are subject to change without notice. Contact NOHMI before relying on the above specifications.Actual performance is based on proper application of the product by a qualified professional.Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser's purposes, the matter should be referred to NOHMI or a distributer in your region.

●HEAD OFFICE: 7-3, Kudan Minami 4-chome, Chiyoda-ku, Tokyo 102-8277, Japan●PHONE: (81)3-3265-0231●F A X: (81)3-3265-5348●U R L: https://www.nohmi.co.jp/english/

P-1-Typeconventional

fire alarmcontrol panel

T

A

L1~Ln

C

T

A

L

CEOL

Conventional manual

fire alarm box FMMN102-U(W)

Connection of FMMN102-U(W) to conventional fire alarm control panel

P-2-Type conventional

fire alarm control panel

A A

L1~Ln L

C C

EOL

Conventional manual

fire alarm box FMMN202-U

Connection of FMMN202-U to conventional fire alarm control panel

Addressable fire alarm

control panel

Addressable module

Manual fire alarm box FMRN102-U

(No address no.)

Connection of FMRN102-U to addressable fire alarm control panel

S+

S-

A

TC

T

L

CEOL

+

-

T

NO(NC)

C

A

AC

TC

S+

S-

+

-

Addressable fire alarm

control panel

S+

S-

TC

T

S+

S-

TC

T

Addressable manual

fire alarm box FMBN102-U(W)

Connection of FMBN102-U(W) to addressable fire alarm control panel

4914.62

83.5

φ10

0

φ14

0

WITH RECESS ADAPTER

WITH RECESS ADAPTER

MANUAL FIRE ALARM BOX

MANUAL FIRE ALARM BOX

COVER PLATE

JACK COVER

PUSH BUTTONSWITCH

RESPONSE LAMP

ACRYLIC PLASTIC COVER

BODY TERMINALCOVER

56.6

497.6800~1500

φ10

08.

6

WITH SURFACE BOX

WITH SURFACE BOX

64.1

φ50

83.5

Wall (sheet metal etc.)

Rainproof packing*

Mounting screws

Plate removed (front view)

83.5

φ10

0

Installation diagram

Side viewCaulking (all around)

Fixing screws*

Mounting plate

Cover plate

Fixing screws*

Surface box - front view

(a)6

6.7

(b)8

3.5

φ 50

(b)46

Wire hole

(a)66.7

(a) : JIS C 8340For medium-sized square coating cover (5)Installation pitch

(b) : JIS C 8340For a switch box cover for two units Installation pitch

WallSurface box

Mounting screws

Mark

*The fixing screws are shipped together with the surface box.

Installation diagram

Front View

12083.5

51

71

46

46 83.5 89

Rainproof packing*

Mounting plate

Fixing screws *

Installation diagram

Mark

Mounting plateCover plate

Mounting screws