Car Park MV Calculation

Embed Size (px)

Citation preview

  • 8/8/2019 Car Park MV Calculation

    1/7

    Project: Shelford 23

    Contractor : Noris

    Location: Basement Car ParkSystem : Mechanical Ventilation System

    Eqv. Dia Area - A Cap - Q Vel - V VP Le ngth F ri- l os s F Ve l Pr Fr. Pr St. Pr Drop

    W (m) H (m) (m) (m2) (m3/s) (m/s) (V/1.3)2 (m) C Pa/m ( Pa) (Pa) (Pa)

    1 Grilles 0.500 0.200 - - - - - - 9.00 Annix A

    2 Tee 0.500 0.200 0.34 0.089 0.20 2.24 2.97 0.32 0.95 0.95

    3 Straight Duct 0.450 0.150 0.27 0.059 0.40 6.78 27.24 2.10 2.00 4.20 4.20

    4 Elbow 0.450 0.150 0.27 0.059 0.40 6.78 27.24 0.22 5.99 5.995 Straight Duct 0.400 0.150 0.26 0.053 0.40 7.53 33.52 3.40 2.00 6.80 6.80

    6 Transition (@30) 0.800 0.150 0.35 0.096 0.40 4.16 10.23 0.24 2.46 2.46

    7 Straight Duct 0.800 0.150 0.35 0.096 0.80 8.32 40.94 0.35 2.00 0.70 0.70

    8 Elbow 0.800 0.150 0.35 0.096 0.80 8.32 40.94 0.22 9.01 9.01

    9 Straight Duct 0.800 0.150 0.35 0.096 0.80 8.32 40.94 1.20 2.00 2.40 2.40

    10 Transition (@30) 0.500 0.250 0.38 0.114 0.80 7.02 29.18 0.09 2.63 2.63

    11 S bend- 30 degree 0.500 0.250 0.38 0.114 0.80 7.02 29.18 0.12 3.50 3.50

    12 Straight Duct 0.500 0.250 0.38 0.114 0.80 7.02 29.18 5.90 1.40 8.26 8.26

    13 Elbow 0.500 0.250 0.38 0.114 0.80 7.02 29.18 0.22 6.42 6.42

    14 Straight Duct 0.500 0.250 0.38 0.114 0.80 7.02 29.18 1.20 1.40 1.68 1.68

    15 Transition (@30) 0.500 0.375 0.47 0.175 0.80 4.57 12.36 0.09 1.11 1.11

    16 Straight Duct 0.500 0.375 0.47 0.175 1.19 6.81 27.41 19.00 1.00 19.00 19.00

    17 Elbow 0.500 0.375 0.47 0.175 1.19 6.81 27.41 0.19 5.21 5.21

    18 Straight Duct 0.500 0.375 0.47 0.175 1.19 6.81 27.41 2.65 1.00 2.65 2.65

    19 Elbow 0.500 0.375 0.47 0.175 1.19 6.81 27.41 0.19 5.21 5.21

    20 Straight Duct 0.500 0.375 0.47 0.175 1.19 6.81 27.41 5.10 1.00 5.10 5.10

    21 Elbow 0.500 0.375 0.47 0.175 1.19 6.81 27.41 0.19 5.21 5.21

    22 Straight Duct 0.500 0.375 0.47 0.175 1.19 6.81 27.41 1.20 1.00 1.20 1.20

    23 Transition (@30) 0.600 0.500 0.60 0.281 1.19 4.24 10.64 0.09 0.96 0.96

    24 Elbow 0.600 0.500 0.60 0.281 1.19 4.24 10.64 0.19 2.02 2.02

    25 Straight Duct 0.600 0.500 0.60 0.281 2.38 8.47 42.45 9.47 1.10 10.42 10.42

    26 Transition (@30) 0.725 0.500 0.66 0.337 2.38 7.06 29.46 0.09 2.65 2.65

    27 Straight Duct 0.725 0.500 0.66 0.337 2.38 7.06 29.46 9.47 1.00 9.47 9.47

    28 Elbow 0.725 0.500 0.66 0.337 1.19 3.53 7.38 0.19 1.40 1.40

    29 Straight Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 1.20 1.00 1.20 1.20

    Static Pressure Losses Calculation

    Sect;Size

    Description Reference

    Air Flow Capacity : 10000 CMH ( 2778 l/s)

    Shelford 23- Carpark MV calculation Shelford-Car Park-SI 1 of 2

  • 8/8/2019 Car Park MV Calculation

    2/7

    Project: Shelford 23

    Contractor : Noris

    Location: Basement Car ParkSystem : Mechanical Ventilation System

    Eqv. Dia Area - A Cap - Q Vel - V VP Le ngth F ri- l os s F Ve l Pr Fr. Pr St. Pr Drop

    W (m) H (m) (m) (m2) (m3/s) (m/s) (V/1.3)2 (m) C Pa/m ( Pa) (Pa) (Pa)

    Sect;Size

    Description Reference

    Air Flow Capacity : 10000 CMH ( 2778 l/s)

    30 Transition (@30) 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.09 3.62 3.62

    31 Straight Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 1.20 1.00 1.20 1.20

    32 Transition Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.12 4.82 4.82

    33 Silencer (maxi drop) 26.00 Annix B

    34 Fan

    35Silencer(maxi drop) 26.00 Annix C

    36 Transition Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.12 4.82 4.82

    37 Straight Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.45 1.00 0.45 0.45

    38 Elbow 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.19 7.64 7.64

    39 Straight Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 1.75 1.00 1.75 1.75

    40 Elbow with spliter 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.10 4.02 4.02

    41 Elbow with spliter 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.10 4.02 4.02

    42 Straight Duct 0.725 0.500 0.66 0.337 2.78 8.24 40.19 0.60 1.00 0.60 0.60

    43 Transition Duct 1.200 1.000 1.20 1.124 2.78 2.47 3.62 0.12 0.43 0.43 Dog-house

    44 Screen Net (80%) 1.200 1.000 1.20 1.124 2.78 2.47 3.62 0.10 0.36 0.36 ASHRAE

    45 External Louver 1.200 1.000 1.20 1.124 - - - - - - - 30.00 Annix D

    with 50% free area

    Sub Total 252.53

    Add 10% Safety Factor 25.25

    Total Static Pressure 277.79

    Shelford 23- Carpark MV calculation Shelford-Car Park-SI 2 of 2

  • 8/8/2019 Car Park MV Calculation

    3/7

  • 8/8/2019 Car Park MV Calculation

    4/7

    LINEAR BAR GRILLES LGW/LGF 300 SERIES

    ")/-

    Annix -A

  • 8/8/2019 Car Park MV Calculation

    5/7

    LINEAR BAR GRILLES LGW/LGF 300 SERIES

    ")/-

  • 8/8/2019 Car Park MV Calculation

    6/7

    MDF@H>@LM

    3

  • 8/8/2019 Car Park MV Calculation

    7/7

    WEATHER LOUVRES WLA/WLS 600 SERIES

    ")/-

    Design Q= 2778 L/sAnnix- D