sdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdhsdfhsadhasdhsdhsdh
Citation preview
PROYECTO:UBICACIN : CLASE DE MURO: cerco
DEPARTAMENTO : Ayacucho ALTURA DE MURO : 2.2 mtsPROVINCIA : huamanga ARRIOSTRE : 04 ladosDISTRITO : Ayacucho USO : colegio
MORTERO : sin cal
A) CALCULO DE ESPESOR DE MURO Y SEPARACION DE COLUMNAS (NORMA E-070)
Momento actuante Ma = 5.8806
m = 0.05 coeficiente de momentos NORMA E-070Ws = 24.3 carga uniforme sismicaa = 2.2 dimension critica asumida (mts)
Carga uniforme sismica
Z = 0.3 factor de zona de AyacuchoU = 1.5 factor de usoC1 = 0.25 coeficiente sismico
Peso por m2 de muro
t = 0.15 espesor de muro (m)m = 1800 peso especifico de muro Kg/m3
Momento resistente Mt = 5.625
ft = 1.5 esfuerzo de traccion por flexion Kg/cm2
Inercia
Debe cumplir : Ma =Mt 0.231
si a = 2.2 m = 0.05
Interpolando segn tabla N 12 de Norma E-070 para el caso de arriostre en 04
b/a = 1.028 b= 2.2616
Para el caso tenemos: b= 2.25 m (separacion entre columnas)a= 2.20 m (altura del muro)e= 0.15 m (espesor de muro)
CONSTRUCCION CENTRO EDUCATIVO YURACC YURACC
DISEO DE MUROS NO PORTANTES
= 0.0003
= 0.0750
lados
B
A
PROYECTO: CONSTRUCCION CENTRO EDUCATIVO YURACC YURACCDISEO DE MUROS NO PORTANTES
B) CALCULO DE CIMENTACION DE MUROS NO PORTANTES
Peso especifico de suelo : 1114Angulo de friccion : 33coeficiente de friccion : 0.13espesor de muro : 0.15coeficiente sisimico : 0.15altura de muro : 2.20altura de sobrecimiento : 0.6peso especifico de muro : 1800peso especifico de concreto : 2300esfuerzo permisible del terreno : 1 j = 0.3ancho de cimiento : 0.6 ha = 1.1altura de cimiento : 0.8
1.- POR DESLIZAMIENTO
Ka = 0.295 coeficiente de resistencia activakp = 3.392 coeficiente de resistencia pasiva
Ea = 198.69 Kg (empuje activo)Ep = 2286.19 Kg (empuje pasivo)
Pm = 594.00 Hr= 2709.05 Kg (fuerza resistente)Ps/c = 207.00 Ha= 686.61 Kg (fuerza actuante)Pc = 2301.40Ps = 150.39 F.S.D = 3.95 CUMPLE CONDICIONPt = 3252.79
2.- POR VOLTEOMomentos de volteo elemento H d M
muro 89.10 2.50 222.75sobrecimiento 31.05 1.10 34.16cimiento 345.21 0.40 138.08suelo 22.56 0.95 21.43empuje activo 29.80 0.37 10.93
Mv = 427.35 Kg-mMomentos resistentes
elemento H d Mmuro 594.00 0.08 44.55sobrecimiento 207.00 0.08 15.53cimiento 2301.40 0.30 690.42suelo 150.39 0.23 33.84empuje activo 2286.19 0.37 838.27
Mr = 1622.60 Kg-m
F.S.V = 3.80 CUMPLE CONDICION
3.- ESFUERZO SOBRE TERRENO
Xa = 0.37 cumple dentro del tercio centrale = 0.0675 cumple condicion de excentricidad
kg/m3m
mmkg/m3kg/m3kg/m3mm
H
Hs
Hc
a
j
PROYECTO: CONSTRUCCION CENTRO EDUCATIVO YURACC YURACCDISEO DE MUROS NO PORTANTES
Esfuerzos E1 = 0.91 cumple condicionE2 = 0.18 cumple condicion
C) DISEO DE COLUMNAS DE ARRIOSTRE
Ancho col. = 0.25Long. Col. = 0.25
Fuerza del muro = 0.091 Tn/mFuerza de columna = 0.023 Tn/m
W = 0.114 Tn/m
M diseo = 0.192 Tn/m
fs = 2100.00J = 0.875 Acero principal = 1/2d= 20.73 Estribo = 1/4 mm
As = 0.503560492 varillas : 4 As min