Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
3.6m telescopeMAINTENANCE MANUALNUMBER 6
CABLING POSITIONCONTROLAND INTERLOCKS
Edition July 1977 J. Roozeveld van der Yen-~-----
CONTENTS
1. CABLE TWISTS
1.1 Principle
1.2 Description of parts
1.3 Maintenance
2. HEIDENHAIN POSITION INDICATOR (STRIP ENCODER)
2.1 Principle
2.2 Description of parts
2.3 Dismounting of parts
3. ITEK ENCODER
4. HEIDENHAIN BACK UP POSITION INDICATOR
5. SIEMENS POSITION INDICATOR
6. LIMIT, INIT AND POSITION SWITCHES
6.1 Polar Axis
6.2 Declination Axis
7. BALL LIMIT SWITCHES
7.1 Principle
7.2 Adjustment
7.3 Inspection
8. ON/OFF MOTORS CONTROLLED BY MOTOR CONTROL BOXES
(MCB)
Page
1
1
1
3
5
5
6
7
8
8
9
9
9
10
11
11
12
12
13
1. Modes of operation 13
2. Types of motordrive 13
3. Location of MCB's and motors on the telescope 14
9. DESCRIPTION OF MOTOR CONTROL BOXES (MCB)
1. General
2. Standard MCB
3. MCB's for main mirror handling
4. MCB's for platform drive motors
10. MODES OF MANUAL MOTOR COMMAND (OFF LINE)
1. By MCB
2. By Remote Control Handset
3. By portable handdrive box
4. Remotely from the control room
15
15
15
17
18
19
19
19
20
21
11. STANDARD JUNCTION BOXES AND MOTOR CONNECTIONS 21
12. THE INTERLOCK SYSTEMS 21
1. General
2. Motor Control Box safety interlocks
3. Principle of the MCB interlock circuit
4. The Interlock Panel
13. LIST OF COMMON ABBREVIATIONS AND EXPRESSIONS
21
22
23
23
25
Nr. Control Manual
14. LIST OF CONTROL MOTORS, MCB SWITCHED
15. LIST OF MCB's, FUNCTIONS AND
LOCATIONS
16. LIST OF JUNCTION BOXES
17. DESCRIPTION OF INTERLOCK SIGNALS
18. LIST OF INTERLOCK DATA
(3b. 6)
(3b.5)
(3b. 8)
(4a.4.4)
(4a.4.3)
page
27
30
34
36
42
- 1 -
1. CABLE TWISTS
Polar axis T25-100Declination axis T25-200
1.1 Principle
The cable twists accomodate besides cables, also fle
xible tubes for oil, water and air. They allow rotation
of the telescope without damage to cables and tubes. The
main part is the cage, consisting of parallel steel
tubes, welded to steel rings. At the inner diameter of
these rings are located the same number of rings or discs.
These parts can rotate or move on ball bearings. At the
polar axis the cage is fixed to the rotating structure
and at the declination axis to the centerpiece. At the
opposite side, there is a moment arm, which, at the
polar axis connects the ring to the pedestal. At the de
clination axis the moment arm connects the ring to the
polar axis structure. Cables and tubes are supported, or
fixed, to the rings. Moreover, there are three steel
cables to avoid pulling forces from the stabilising
springs in cables and tubes. The tubes at one of their
ends are provided with rotating joints.
1.2 Description of parts
1.2.1 ~~g~
Polar axis T25-101Declination axis T25-201
The principle of both cages is similar. Each
ring locates 3 ball bearings. Two of them have a fixed
position, the third one is spring loaded to eliminate
clearance. The rotation axis of the bearings in one of
the end rings is in tangential, that of the others axial
- 2 -
direction.
When fitted inside the telescope, both cages
are supported on two rings.
1.2.2 ~~~~~~_9~2£_~2~Y
Polar axis T25-102
Inside this part are located 21 cables, 1
flexible oil tube, 2 flexible water tubes and one air
tube. Three steel cables are fitted to take the pulling
forces, that result from the 3 compression springs.
These have a stabilisation function.
The flexible tubes are supported in a mecha
nism, that can rotate in 2 ball bearings. On this part
is screwed a rotating union, make Deublin. At the peri
phery, there is a track for the three ball bearings, that
allows only rotation but no axial translation.
Q~~~E_~~e!~_E~~g_~22Y
Declination axis T25-202
Inside this part are located 18 cables, 20
flexible water tubes and one flexible air tube. The
construction is similar to that of the polar axis.
1.2.3 !~~~E~~9~~~~_9~2~_~22Y / Polar axis T25-103
!~~~E~~9~~~~_~~e!~_E~~g_~~2Y/ Declination axisT25-203
The construction of both rings is similar.
Tubes and cables are not clamped, but only supported. At
the periphery there is a track for 3 ball bearings that
allow rotation and axial translation.
- 3 -
1.2.4 ~~E_9~~~_~~~Y / Polar axis T25-104
~~~~E_~~e!~_E~~g_~~~y / Declination axis T25-204
The construction of both rings is similar.
Tubes and cables are clamped. At the outside there is a
track for the three ball bearings, that allow only axial
translation.
1.2.5 Moment arm
T25-105 Polar axis / T25-205 Declination axis
The moment arms are of a similar construction.
It consists of a steel tube with at both ends spherical
units, make Unibal. Length adjustment can be done by
right- and left hand thread.
Make Deublin
Air Type 1300-82 air, rotor 1300-04
Water Type 055-80 water, rotor 055-94
Oil Type 20 oil, rotor 20-3A
1.3 Maintenance
1 x pro month
Inspection, cleaning and greasing by demounting the
unit of :
- greasing ball bearings
- cleaning and greasing of ball bearing tracks 1 x
- inspection tubes and cables pro 5 years.
- 4 -
- inspection rotating unions
1.4 Dismounting arid mounting procedure
Polar axis cable twist T25-l00
- disconnect cables and tubes
- dismount connection screws of part T25-101-10
- screw on "arm for alpha cable coil" T28-116 to
the cage at side V-beam
- take out screws of part T25-101-11
- lift the cable twist care-
fully backward by 12 t
crane
mounting in opposite direc
tion
fig. 1.4
1.5 Dismounting and mounting the declination axis
cable twist T 25-200
- disconnect cables and
tubes
- use "arm for delta cable
coil T28-115
- take out connection
screws between cage
and declination axis
- move the cable twist
out carefully Fig. 1.5
- 5 -
2. HEIDENHAIN POSITION INDICATOR (Strip encoder) T22-100
2.1 Principle (Creusot Loire drawings T22-02/T22-10)
On each of the telescope axes is mounted a strip en
coder make Heidenhain, Type Lida 55.123.
The main parts of each of the encoders are
- a precise linear coded strip, fixed at the peri
phery of a steel drum, that is screwed to the
telescope axis.
- a photo electric sensing head.
- a small carriage on which is mounted the sensing
head that runs over precise machined tracks on the
periphery of the steel drum. Tracks and strip loca
tion are machined with the same machine fixation
to guarantee an optimum concentricity, necessary
to keep the sensing head within a narrow tolerated
distance from the strip. The carriage is pressed on
its tracks by 2 springs and aXially fixed by a
small moment arm. The steel drum outside is pro
tected by a steel cover, that is provided with
several inspection holes. It is supported with 12
ball bearings on the steel drum. The cover is
connected by a moment arm to the structure to pre
vent rotation.
The resolution of the strip encoder at the polar
axis is 2 seconds of arc and at the declination
axis 3.05 seconds of arc. The resolutions are
reverse proportional to the drum diameters.
- 6 -
2.2 Description of parts
The carriages at both telescope axes are the
same. The frame is a machined steel structure. It runs
on 5 ball bearings, 3 of them for radial and 2 for axial
location. The radial bearings are mounted on excenter
shafts for adjustment. The sensing head is screwed to
the frame by means of a support. There are locations for
two compression springs that press the carriage on its
tracks. The spring force can be adjusted by a'screw
spindle and pushes the carriage at the same time to the
radial and axial tracks. At the end of the carriage,
there is made a provision for the fixation of a moment
arm. At the side of the sensing head there is an oval
hole in the carriage frame for adjustment of the sensing
head.
The drum is provided with two tracks for the
radial rollers and one for the axial. The strip is lo
cated in between them. The relative excentricity is
restricted to keep the maximum distance of the sensing
head to the strip within 0,1 of a mm. The tracks are
stainless steel rings, welded to the drum. The diameter
of the polar axis strip is 2'060 mm, and at the decli
nation axis 1'350 mm.
Is machined from high tensile steel. Twb
flexible regions with a diameter of 2 mm are machined
- 7 -
in t~,e, arm to obtain some flexibility" ,This is necessary
to absorb relative movements betwee~ q~um~a~d pedestal.
The fixation to the carriage is done with a cylindrical
part that allows axial adjusting. At the other end is a
spherical end that admits some angular adjustment during
mounting,. After adjusting the sphere will be blocked by
four M6 screws.
2.3 Dismounting of parts
- Disconnect cable.
- Dismount the sensing head by 3 screws M6.l6
from the carriage frame (take care to replace
eventual 'shims correctly when mounting agai~.
- Slacken 4 screws M3.l2 that fix the moment arm
to the carriage.
- Take out 4 screws M8.25, but take care to
support at the same time part 22-07-08 not to
overstress the moment arm.
- 'Move out carefully the moment arm in axial
direction.
- Unscrew the spindles for the compression
spr1ngs, and take them out.
- Remove the carriage.
2.3.2 QE~~_E~!~E_~~!~ (After dismounting of the carriage
and switches)
- Take out the moment a,rm.
- Dismount top C0ver T22-02~03.
- Dismount drum support for cables.
- Dismount steel protection, that can be split
into two parts.
- 8 -
For dismounting the drum the "T" shaped tool has to
be used and the 12 t crane.
Fig. 2.3.2
2.3.3 Drum declination axis (after dismounting of the---------------------carriage and switches)
Dismount the protection cover with help of a
non metallic sling through the inspection holes. Take
care not to touch the coded strip. After this the drum
can be dismounted with non metallic slings.
3. ITER ENCODER *) (Wayne-George RI l8/~5 (c) - QPZ)
This rotary incremental encoder has a shaft resolution
of 18 bits, which corresponds to about 5 seconds of arc. The
resolution in each telescope axis is increased by a factor
100 by a precise friction roller, that is driven by an inter
nal ground surface on the periphery of the large gearwheel
and increasing the resolution on the telescope axis to 0.05
seconds of arc.
4. HEIDENHAIN BACK UP POSITION INDICATOR *)
(Encoder type Rod 1/45.7 with 72000 inc./rev.)
This incremental rotary encoder is driven by one of
the backlash free pinions, engaging the large gearwheel, that
- 9 -
gives a step up ratio of 1 in 18 increasing the resolution
on the telescope axes to 1 second of arc.
5. SIEMENS POSITION INDICATOR *)
(Encoder type V23463-KOIOI-Dl13)
This absolute rotary encoder is driven by one of the
backlash free pinions, that engages the large gearwheel, that
gives a step up ratio of 1 in 18. The encoder itself is
internally provided ~ith a 1 in 10 speed reducer , that gives
the encoder a range of la 000 steps in la revolutions, resul
ting in a resolution on the telescope axis of 1.2 minute of
arc.
*) See also maintenance manual Nr. 2
6. LIMIT, INIT AND POSITION SWITCHES
6.1 Polar axis (T22-02)
The switches, make Bosch, are mounted inside a steel
protection. The drum is provided with 6 cam locations.
The carns are fixed with several clamps and can be shif
ted easily.
The switch positions are indicated on the above men
tioned drawing and correspond to the following functions
- Indication East-West
- Indication of the 12 Hr. position for initialising
purposes. (more practical to do it with the
Siemens encoder).
- 10 -
- Limitation of the rotation to + and - 1000
from the 12 Hr position.
- Limitation of the rotation to + and - 1050
from the 12 Hr position only in Off line mode.
In this mode the software limitswitch is eli
minated and replaced by this hardware limit
switch.
Normally the hardware limitswitches will not be tripped.
Only when the software limitswitch fails, this will
occur. In that case the telescope only can be turned
back when in the off line mode. In case that the 105 0
limit switch is tripped, the telescope only can be turned
back manually. In both cases the telescope will.be stopped
by brake directly.
6.2 Limit, init and position switches, declination axis
(T22-l0)
The position and make of the switches is similar to
that of the polar axis. The drum is provided with 8
camlocations. SWitchpositions are indicated on the
above drawing and correspond to the following functions
- Limitation of rotation to +80 0 and -150 0
- Limitation of rotation to +850 and -1550 only
in off line mode for the same reason as at
the polar axis.
- Indication horizontal position for top unit
exchange (more practical to do it with the
Siemens encoder).
- Indication vertical position, to allow
switching off of the radial airpads of the
main mirror.
- 11 -
- Indication pole position, to come out of the
ball limitswitch lock.
- Indication equator for intialising purposes
(more practical to do it with the Siemens
absolute encoder).
- Limitation to go 10 under the horizon, during
top unit exchange (only in 12 Hr position) .
7. BALL LIMIT SWITCHES T22-01
The three ball limit switches are mounted on an adjus
table frame, that is fitted to the centerpiece.
7.1 Principle
The main components of the limitswitches are :
- A stainless steel cylindrical part, for each
switch provided with a different internal cone of
150, 70 and 60 •
- A steel ball with diameter of 50 mm.
- Two inductive sensors.
The cones are filled with oil to damp the ball move
ment.
When the telescope tube nears any position smaller
than 150 above the horizon, the ball inside the 150
cone starts rolling over its slope.
The output of both sensors are combined logically
and generate a fail to safe signal. In this case the
slewing speed will be reduced automatically.
After 70 above the horizon the airclamps of the main
mirror are switched on. This allows the main mirror to
be safely tilted through its fully vertical position.
- 12 -
At 60 above the horizon the telescope will be stopped
(with the exception during top unit exchange in the 12
Hr. position).
To come out of the ball limitswitch lock, it is neces
sary to get the authorization of a responsable electronic.
In that case the following has to be done :
1) Press key on rearpanel of central interlock (in
control room)
2) ~ axis then will be activated
3) Turn ~axis in analog mode into pole direction
by handset (in contrd room)
4) Release key on rearpanel
7.2 Adjusting parallel to the tube axis
The frame consists of two parts, one screwed to the
centerpiece and the other fixed to. it by 3 adjustable
screws. These screws allow rotation about 2 axes per
pendicular to the tube axis.
7.3 Inspection
If necessary the ball switch can be opened by dis
mounting the cover. The best way to do this is in the
vertical telescope tube position, to unscrew the bottom
sensor and the M6 deairating screw, to get the oil out
and to clean the inner part of the cone.
For checking the sensors these can be screwed out
and replaced. Care has to be taken to degrease before
mounting the threads and put loctite or fluid packing
on it for oil tightness. The axial position of the sen
sors should be in such a way that the ball cannot touch
these. The face of the sensor therefore has to be re
cessed 1 mm.
- 13 -
8. ON/OFF MOTORS CONTROLLED BY MOTOR CONTROL BOXES (MCB)
For more details is refered to 3.6 m Control Manuals,
Part 1 and 2. Several Figures and lists are taken from these
manuals. They are provided with a new number. The numbers of
the manuals are put between brackets.
8.1 Modes of operation
The normal operation is via computer (On line) and
MCB. Several other modes of manual operation (Off line)
via MCB are possible either locally or remotely, allo
wing emergency action to be taken on the spot, routine
operational maintenance etc. and remote manual control
from the control room in event of computer failure. More
over it is possible to control a single motor directly
with the Portable Handrive Box, by passing the MCB and
its interlocks.
8.2 Types of motor drive
There are different ~ypes of motor drive
- motors with gear reduction
- motors with gear reduction and brake
- motors with gear reduction in line with clutch
in between
- linear action motors
When any intermediate position needs to be measured
then an aboslute digital encoder has been mounted. If a
limited number of intermediate positions has to be
indicated, additional switches are fitted.
All motors are three phase 380 volt star connected.
Their power consumption varies between 0,05 KW and 0,45
KW, exception case of the platform drive system where
0,9 motors are used and at the main mirror line where
a 3 KW motor is used.
- 14 -
8.3 Location of MCB's and motors on the telescope
(Refer to Figs. 8.3-1, -2 and -3)
Figs. 8.3-1 and 8.3-2 show the location of the various
motors and their control boxes on the telescope. All motor
control boxes, junction boxes and motors are identified by
a code which describes their general location and grouping
on the telescope.
The first symbol of all identifying codes is a single
letter which describes the general location as follows : -
A - Aluminizing plant
C - Cassegrain area
D - Dome
F - Fourth floor (Coude floor and hydraulic plant)
G - Gear drive servos (alpha and delta)
H - Hubsection (center section)
M - Mounting
P - Platform
Q - Observing floor
R - Readings (alpha and delta)
U - Top units
The first numerical digit, which follows immediately
after the single letter, is used to descripe different groups
or subassemblies in the same general location. Fig. 8.3-3
shows some examples of the use of this code. Motor control
box MCBHl is located on the hubsection (letter code H) and is
a member of subassembly group 1. Motors Hll and H12 are also
members of subassembly group 1 as the digit which immediately
follows the letter code is a 1. The second and last digits
refer to the numbering of the individual motors.
Junction boxes are similarly identified by a letter J
which is always inserted between the two digits to denote a
junction box. The identification of cables is similar.
- 15 -
9. DESCRIPTION OF MOTOR CONTROL BOXES (M.C.B.)
9.1 General
Each M.C.B. acts as a central grouping point to re
ceive command signals and generate control signals for
several motors.
Although there are minor variations in some of the
M.C.B.'s, all of them are based on a standard motor
control circuit and constructional layout.
Standard M.C.B. 's contain all motor control relays,
interlock protection circuits, computer command inter
faces and manual control facilities for the control of
up to 7 motors (M.C.B 8) and 4 motors (M.C.B. 4). Built
in indicator lights allow visual monitoring of the
control status of each motor.
Modified control boxes are used for the control of
the main mirror carriages (M.C.B. Ql, M.C.B.A) and the
platform drivesystem (M.C.B. Pl).
A special control system is used for controlling the
dome rotation and opening of the hatches. This was
necessary because the transmission of the numerous
control signals to the dome and hatches is wired through
a limited number of slip rings.
9.2 Standard Motor Control Boxes MCB8 and MCB4,
Figs. 9.2-1, -2, -3, -4
The standard MCB's are constructed from steel sheets
with hinged and lockable front doors. The outside di
mensions of the MCB8 are 400 x 400 x 180 mm, that of the
MCB4, 400 x 200 x 180 mm. Figures 9.2-1, -2 and -3 give
a view of the standard MCB.
- 16 -
The construction of the unit is divided into two se
parate parts. All 380 volt, 3 phase wiring, including
motor protection circuit-breakers, Rl/R2 motor control
relays and general interlock B relays, are mounted on
the backplate, Fig. 9.2-4. All 24 volt wiring,
computer control, local remote control circuits and
interlock system, are mounted inside the hinged module
directly behind the frontdoor. This module is normally
held firmly against the rearface of the frontdoor with
permanent magnet clamps. By pUlling the module body
outwards, away from the frontdoor, access is obtained
to the rear of the module. All of the 24 volt control
components are accessible through the rear. A single
large printed circUt inside the module frame carries all
of the 24 volt control components. On Fig. 9.2-3 a
sample is given of a printed circuit for the Coude
Top Unit.
For manual electrical command only the connectors
which are used for interface signals are of importance.
On the left handside are located 6 Hirschmann sockets,
each with 16 female pole connections and on the right
hand panel 1 similar Hirschmann socket. The sockets are
numbered from I to 7. The connectors for internal inter
connection are mounted on the main printed circuit
board inside the hinged module. The Hirschmann sockets
make the connection to the junction boxes via type H3
cable. The other Hirschmann socket at the right hand
side has 16 male pole connections and carries the 3
phase 380 volt power supply into the unit. Two Hughes
88 pole sockets are positioned at the top of the right
handside panel. They carry all the computer command
signals to the MCB and the status signals from the MCB
to the RIOS computer interface.
- 17 -
9.3 Motor control boxes for main mirror handling
MCBQl and MCBA
These MCB's of special design are installed on the
main mirror top carriage MCBQl and bottom carriage MCBA.
These carriages are provided to allow the main mirror to
be removed from the telescope and transported to the
aluminising plant on the basement floor. Control can
only be done by manual pushbuttons on the front door of
each MCB.
MCBQl, mounted on the main mirror top carriage may
also be controlled remotely by cable. Three drive motors
have to be controlled, fast and slow and one for the
hoist. Three phase power is supplied to the units by a
spring loaded cable drum, mounted on the carriage. When
running at fast speed an automatic clutch disengages
the slow motor. The hoist motor drives a screw roller
spindle for lifting the main mirror cell. An additional
interlock limit switch F3 is fitted. It cuts off the
power 20 mm before the mirror is being manoeuvred into
or out of its seating. This 20 mm has to be done manu
ally. When motorised lifting can be used, a green light
on the motor control box is illuminated. Three Hirsch
mann sockets, 16 pole female, are provided on the left
handside panel for connection to the motors via plugs
and H3 type cable and junction boxes. A large junction
box QIJl supplies the fast motor, slow motor and clutch.
The small junction box QIJ2 is used for the hoist motor.
A 19 pole Burndy socket on the right handside of the
MCB is provided for the Remote Control Box. This unit
requires no power supply as all its controls and indi
cators are wired directly ~n parallel with their counter
parts in the MCBQl.
- 18 -
MCBA, mounted on the main mirror bottom carriage, is
of similar design as the MCBQl, with exception that there
is no hoist motor and no remote control socket. Two
Hirschmann 16 pole female sockets are provided on the
left handside panel in a similar way as at the MCBQl.
9.4 Motor control boxes MCBPl for the platform drive motors
It is impossible to drive these motors directly by a
standard MCB, because they are too powerful. Control
signal outputs from MCBPl are wired to a BBC cupboard
on the platform. This is equipped with heavy duty motor
contactors, to operate the platform drive motors. The
BBC cupboard is also used to distribute power to the
MCBPl and the four standard MCB's on the carriages.
Command signals ON line (computer) or Off line
(manual) are received in the MCBPl. Fl and F2 limit
switches are fitted at each extreme of the platform's
travel. Four position microswitches are fitted to the
platform, to sense each of the four loading/unloading
positions. They prevent operation of a carriage until
the correct loading position has been reached. The four
positions are also transmitted to MCBPl and connected
to four indication lamps.
Interlocks within MCBPl prevent fast movement of the
platform drive once a carriage has left its fully back
position. To allow close visual inspection of the align
ment, the platform may be driven, at slow speed only by
the remote control handset. For computer control an
absolute position encoder is fitted.
- 19 -
10. MODES OF MANUAL MOTOR COMMAND (OFF LINE)
10.1 By MCB (Fig. 9.2-3 and 10.1)
The Module Front Panel locates pushbuttons with
indications for up to 7 on-off motors. At the right
handside top there is an On/Off-line selector. With
green light, the Off line mode is selected. The 2 x 7
pushbuttons correspond to the indicated motors. Turning
of the motors is only possible when the respective
interlocks are fulfilled. This is made visible with the
square green interlock signal lamps situated between the
red pushbuttons. When this green lamp is not lighted it
is necessary to check why not. For example considering
on printed circuit MCBU4 Coude Mirror (Fig. 9.2-3) the
locking manoeuvre : when the square green interlock
lamp "Lock" is not lighted, one or more of the small
interlock signal lamps 2.3 or 4 are not lighted. A check
then has to be made with help of Chapter 17, "Descrip
tion of the interlock signals". When lamp 2 is not lighted
at f5 is indicated: Unit locked to carriage. Locking
to the telescope then is impossible. When lamp 3 is not
lighted, see gl that indicates : Coude mirror cover
closed etc. Locking can be done when interlocks f5, gl
and dl are fulfilled. In chapter 18, "List of Interlock
Signal Data", further information is given.
10.2 By Remote Control Handset (Fig. 10.2)
The R.C.H. can be applied with all MCB's, by plugging
the 48 pole Burndy socket in the front door. The push
buttons are in the same configuration as that of the
Module Front Panel, (but without indication). In prac
tice the indication of the Module Front Panel has to be
noted and put on the R.C.H. Operation then will be
the same as directly with the MCB.
- 20 -
10.3 By Portable Handdrive Box (Fig. 10.3)
The motors, with their limit switches, are wired to
a junction box close to the motor. A 16 pole Hirschmann
socket on each junction box connects it via plugs and
H3 type cable to the MCB. With the Portable Handdrive
Box it is possible to operate a motor directly, bypassing
the MCB and its interlocks. This allows direct
on the spot operation of any single motor in emergency
or for maintenance. The Portable Handdrive Box is
equipped with an input supply lead which must be plugged
into a 380 volt, 3 phase supply socket. The 16 pole
Hirschmann socket with H3 type cable from the junction
box, has to be connected to the Portable Handdrive Box.
When the mechanism reaches the full extend of its travel
in either direction, the appropriate normally closed
limitswitch is tripped and an indicator light is illu
minated (Fl and F2). The supply ~o the motor is then
removed until the opposite direction of travel is selec
ted by the three position switch. Attention has to be
given that besides this protection, theIE are no general
interlocks, that f.i. are available when driving from
the MCB, Remote Control Handset o~ Control Room.
When a twospeed motordrive is to be controlled by the
Portable Handdrive Box, each motor must be controlled
individually. Two 16 pole Hirschmann sockets for that
reason are provided on the junction box. When the fast
motor is to be used, the clutch separating the two
motors must be disengaged with another switch on the
Portable Handdrive Box.
When linear motors are controlled, the state of the
internal limit contacts F3 and F4 is displayed on. built
in indicator lamps.
- 21 -
10.4 Remotely from the control room
Manual pushbuttons in the control room may also be
used to control an MCB remotely. Cables from the control
room pushbuttons are normally wired to the 48 pole Burndy
socket on the frontdoor of each MCB. Front panels in the
control room racks carry all the pushbuttons and indi
cator lamps which are required to operate each MCB. There
is a separate frontpanel for every two MCB's that are
controlled. Operation is exactly the same as described
for the Remote Control Handset.
11. STANDARD JUNCTION BOXES AND MOTOR CONNECTIONS
All motors, together with connections from their two
limitswitches Fl and F2, ~re wired to a local junction box
close to the motor. There are two sizes of standard junction
boxes, a small size box for connecting to a single motor
and a larger size for connection to two motors. There are
special types for a pair of motors, that are connected for
two speed drive and for linear motors.
Standard junction boxes act only as wiring connection
points for their respective motor and limitswitch cables.
12. THE INTERLOCK SYSTEMS (Fig.' 9.2-4)
12.1 General
Interlocks are necessary to protect the telescope
from damage and to ensure the safety of operating,per
sonnel and are incorporated in both the hardware and
software of the telescope. The software interlocks are
- 22 -
written into the computer programm to duplicate the
function of the hardware interlocks, giving a double
level of protection.
There are two systems of hardware interlocks.
!h~_~2~2E_£2~~E2!_!~~~E!29~§concern the operation ofthe ON/OFF switched motors, which are controlled by
the MCB's.
!h~_~~!~_§~EY29E!Y~_!~~~E~2~~§concern only the servomotors and brakes for the telescope main drives.
Interlocks ensure that proper procedures are followed
during the control of the telescope, during top unit ex
change and when removing certain parts from the telescope
for maintenance purposes. During manual control by MCB,
by Remote Control Handset and from the Control room,
these procedures are carried out automatically. If the
Portable Handdrive Box is used, then there is only
protection by the local Fl, F2 limitswitches.
12.2 Motor Control Box safety interlocks (Figs. 9.2-4,12.2-1
and -2)
The interlock system directly concern the operation
of the motors and their MCB's. The general safety inter
lock system is not constructed as a one piece unit. Every
MCB contains a logic panel which is a part of the inter
lock system. This panel defines the logical conditions
which must be satisfied before a motor is allowed to
operate.
All standard MCB's contain a special relay, the "B"
relay for each motor. This "B" relay must be energized
by the interlock system before the relevant motor can
be operated. A visual indication of the "B" relay. status
is provided. This is a green light positioned between
- 23 -
every pair of control pushbuttons for each motor.
The end positions are determined by Fl and F2 limit
switches which affects the Rl or R2 motor control relays
inside the MCB and the Fl and F2 indicator lights are
illuminated. In many cases the end position is a logical
condition that affects the "B" relays of other motors.
The Fl, F2 signals in that case are retransmitted out
of the MCB as a general safety signal. Movements of the
motor in either direction is controlled by the motor
control relays Rl and R2.
To simplify the distribution of interlock signals
between different parts of the system two distribution
boxes are used. These are labelled Distribution BoX H,
(DBXHl and Distribution BoX F, (DBXF) (Fig. 12.2-2).
As most of the interlock signals are generated by the
Fl F2 limitswitches of the motors, the motor code itself
is used. The code for the interlock signal becomes the
motor code followed by the limitswitch designation. For
example H13F2 is the code for the F2 limit switch signal
from motor H13. The abbreviated code for interlock signal
H13F2 is gl. Its function : M3 locked to arm (Chapter
18, list of Interlock Signal data).
12.3 Principle of the MCB Interlock Circuit (Fig. 9.2-4)
Each motor has an individual chain of interlock contacts
wired to its "B" relay. All three F contacts from other
motors must be closed to energize the "B" relay.
12.4 The interlock panel (Fig. 12.4)
Each standard MCB incorporates a panel which visually
illustrates the logical fuction of each motor. An example
- 24 -
is given in Fig. 12.4 which shows the interlock panel
for MCBHl (Mirror 3 arm). Each of the seven motors
controlled by the MCB is listed in a column on the left
handside. Across the top of the panel a row of twelve
LED indicators provide a visual signal for each of the
interlock conditions. Each relay contact which is used
to build up a motor function is shown on the panel by
a pair of adjacent small sockets. These sockets have a
functional purpose described below. The interlock chain
for each motor runs across the panel horizontally, from
right to left, and is drawn to represent the motor func
tion. The beginning of the chain, on the right, is the
point at which the 24 volt supply enters each chain. The
end of the chain on the left is the point to which each
"B" relay is connected.
Many motors such as HIS have a simple function which
is wired with a series chain of a few contacts. Other
motors have more complicated logical functions. The
interlock panel, together with the LED's, gives an
immediate representation of each motor's logical func
tion. The interlock panel also has a functional purpose.
Each pair of adjacent small sockets represents a relay
contact, but in practice they are also wired in parallel
with the actual relay contacts themselves. This allows
jumper link to be manually inserted across any interlock
contact to bypass it. This facility is provided in case
a fault develops in the wiring or source of an interlock
signal.
The insertion of these jumper links is a temporary
measure and never should be done by any mechanic without
a special authorisation of the responsable electronic.
- 25 -
13. LIST OF COMMON ABBREVIATIONS AND EXPRESSIONS
al •.••. Val
B19, B28, B48
All •••.• U4 7
B Relay
C Relay
R Relay
H6, H16
HGS 88
H3 cable
DBXH, DBXF
Fl I F2 relays
F3 I F4
Interlock
Interface
Display
Interlock signals
Burndy 19, 28 and 48 pole connector
Motor designation
General Interlock Relay
Computer interface
Motor Control Relay
Hirschmann 6 and 16 pole connector
Hughes 88 pole connector
Special cable with screened centersection
carrying 5 x 1 mm2 conductors for 3 phase
power lines and outersection of 11 x 0,4
mm2 conductors for 24 volt connectors
Distribution Boxes
Limitswitches
Intermediate switches
A device activated by the operation of
some other device with which it is directly
associated to govern succeeding operations
of the same or allied devices
Internal connection between two systems
A device used for the indication and
quantitative evaluation of computation
results
Monitoring element A device that converts the output quantity
into a signal
On line Computer controlled
Off line
MCB
JBX
Remote Control
RIOS
L.E.D.
CBR2
Hardware
Software
Logic
- 26 -
Manual controlled
Motor Control Box
Junction Box
Control of an operation from a distance
Remote Input Output Station
Light Emitting Diodes
Ball limit switch
The mechanical magnetic electrical and
electronic devices from which a computer
is constructed.
Instruction sequence for computers
The science that deals with the princi
nl p.~ i'lnd criteria o-F ~.raJJ.n.i tv in thought
and demonstration (Boolean Algebra)
- 27 -
14 (3b.6) LIST OF CONTROL MOTORS (MCB SWITCHED)
MotorDesignation
All
A12
Cll
C12
C13
C14
C15
C21
C22
C23
C24
F47
F48
Hll
H12
H13
H14
HIS
H21
H22
H23
H24
H25
H31
H32
H41
H42
H43
Function
Basement carriage, drive slow
Basement carriage, drive fast
Mirror 3, alignme~t drive 1
Mirror 3, alignment drive 2
Mirror 3, alignment drive 3
Mir+or 3, cover drive
Mirror 3, cover drive
Mirror 3, hook lock on baffle
Sky baffle drive
Mirror 3, power plug drive
Mirror 3, twin lock on baffle
Mirror 5, cover drive
Mirror 5, pivot arm drive
Mirror 3, arm drive slow
Mirror 3, arm dr~ve fast
Mirror 3, lower arm lock
Mirror 3, upper arm lock
Mirror 3 arm lock on hubsection
Counterweight 1, N-E
Counterweight 2, S-E
Counterweight 3, s-wCounterweight 4, N-W
Small horizontal counterweight
Main mirror cover drive
Main mirror cover drive
Top ring fixation 1
Top ring fixation 2
Top ring fixation 3
./ .
ControlMCB
MCBA
MCBA
MCBCl
MCBCl
MCBCl
MCBCl
MCBCl
MCBHl
MCBCl
MCBCl
MCBHl
MCBFl
MCBFl
MCBHl
MCBHl
MCBHl
MCBHl
MCBHl
MCBH2
MCBH2
MCBH2
MCBH2
MCBH2
MCBH2
MCBH2
MCBH3
.f.1CBH3
MCBH3
14 (3b.6)(Continued)
- 28 -
MotorFunction Control
Designation MCB
H44 Top ring fixation 4 MCBH3
Mll Mirror 4, alignment drive 1 MCBMl..M12 Mirror 4, alignment drive 2 MCBHl
M13 Mirror 4, alignment drive 3 MCBMl
M14 lUrror 4 cover drive MCBMl
M2l Pol~r counterweight MCBMl
M3l Declination lock drive MCBMl
Pll Platform drive 1 fast MCBPl
P12 Platform drive 1 slow MCBPl
P13 Platform drive 2 fast MCBPl
P14 Platform drive 2 slow MCBPl
P2l Carriage 3, drive slow MCBP2
P22 Carriage 3, drive fast MCBP2
P23 Carriage 3, lock top-unit in MCBP2,
P24 Carriage 3, rear lift MCBP2
P25 Carriage 3, front lift MCBP2
P3l Carriage 4, drive slow MCBP3
P32 Carriage 4, drive fast MCBP3
P33 Carriage 4 , lock top-unit in MCBP3
P34 Carriage 4, rear lift MCBP3
P35 Carriage 4, front lift MCBP3
P4l Carriage 1, drive slow MCBP4
P42 Carriage 1, drive fast MCBP4
P43 Carriage 1, lock top-unit in MCBP4
P44 Carriage 1, rear lift MCBP4
P4S Carriage 1, front lift MCBP4
PSl Carriage 2 drive MCBPS
P52 Carriage 2 lift MCBP5
./ .
14 (3b.6) (Continued)
MotorDesignation
- 29 -
Function ControlMCB
Qll Mirror top carriage, drive slow MCBQl
Q12 Mirror top carriage, drive fast MCBQl
Q13 Mirror top carriage, lift MCBQl
Q2l Polar lock drive MCBFl
Ull Prime focus, lock to telescope MCBUl
U12 Prime focus, lock to telescope MCBUl
U2l Prime focus, cage turn MCBUl
U22 Prime focus, chair drive MCBUl
U3l Cassegrain mirror, colI. drive MCBU3
U32 Cassegrain mirror, colI. drive MCBU3
U33 Cassegrain mirror, focus slow MCBU3
U34 Cassegrain mirror, focus fast MCBU3
U35 Cassegrain mirror, lock MCBU3
U36 Cassegrain mirror, lock MCBU3
U37 Cassegrain mirro~, cover drive MCBU3
U4l Coud~ mirrorl, colI. drive MCBU4
U42 Coud~ mirroxz, coll. drive MCBU4
U43 Coud~ mirron, focus slow MCBU4
U44 Coud~ mirrorl, focus fast MCBU4
U45 Coud~ mirror~, lock MCBU4
U46 Coud~ mirroIl, lock MCBU4
U47 Coud6 mirroD, co.ver drive MCBU4
- 30 -
15 (3b.5) LIST OF MCB's, THEIR FUNCTIONS AND LOCATIONS
Desig. Nr. of spare Function Locationmotors controls
MCBA* 2 All = Carriage drive slow Main mirrorAl2 = Carriage drive fast bottom carriag
MCBCl 7 0 Cll = Mirror 3 alignment drive Center pieceCl2 = Mirror 3 alignment driveCl3 = Mirror 3 alignment drive
I
C14 = Mirror 3 cover
ClS = Mirror 3 cover
C22 = Sky baffle drive
C23 = Mirror 3 power plug
MCBFI 3 4 F47 = Mirror 5 cover Fourth floorF48 = Mirror 5 arm drive
021 = Alpha lock drive
MCBHl 7 0 Hll = Mirror 3 arm drive slow Center piece
H12 = Mirror 3 arm drive fast
H13 = Mirror 3 lock to arm (lower)
Hl4 = Mirror 3 lock to arm (upper)
HIS = Mirror 3 arm lock on hubsect.
C2l = Mirr. 3' hook lock on sky baf.
C24 = Mirr. 3 twin lock on sky baf.,
MCBH2 7 0 H2l = Vertical counterw. N-E Center piece
H22 = Vertical counterw. S-E
H23 = Vertical counterw. s-wH24 = Vertical counterw. N-WH25 = Small horizont. counterw.
H3l/H32 = Main mirror cover, ./ .HSl = Contacts only for top units
15 (3b.5) (Continued)
- 31 -
-Desig. Nr. of spare Function Location
motors controls
-MCBH3 4 3 H4l = Top ring fixation Center piece
,"
H42 = Top ring fixation
H43 = Top ring fixation
H44 = Top ring fixation
.MCBMl 6 1 Mll = Mirror 4 alignment drive Mounting
Ml2 I: Mirror 4 alignment drive
Ml3 = Mirror 4 alignment drive
Ml4 = Mirror 4 cover
M2l = Polar counterweight
M3l = Delta lock drive
I
MCBP1* 2 0 P1l/13 = Platform drive slow Platform
P12/14 = Platform drive fast
W''SP2 5 2 P21 = Carriage 2 drive slow Carriage 2
P22 = Carriage 2 drive fast
P23 = Lock unit on carriage
P24 = Rear lift
P25 = Front lift
MCBP3 5 2 P31 = Carriage 4 drive slow Carriage 4
P32 = Carriage 4 drive fast
P33 = Lock unit on carriage
P34 = Rear lift
P35 = Front lift
. I .
- 32 -
15 (3b.5) (Continued)
nit
un!1
Desig. Nr. of Spare Function LocationMotors controls
MCBP4 5 2 P4l = Carriage 1 drive slow Carriage 1P42 = Carriage 1 drive fast
P43 = Lock unit on carriage
P44 = Rear lift
P45 = Front liftI
MCBP5 2 2 P51 = Carriage 2 drive Carriage 2
P52 Cl Carriage 2 lift.
MCBQl* 3 011 = Carriage drive slow Main mirror
Q12 1:1 Carriage drive fast top carriage
013 1:1 Lift drive.MCBUl 3 1 Ull/Ul2 Cl Prime focus unit lock Prime focus u
U21 III Prime focus cage chair turn
U22 = Prime focus cage chair drive
MCBU3 6 1 U31 1:1 Cassegr. mirror collimator Cass. mirror
U32 = Casse~r. mirror collimator
U33 1:1 Cassegr. mirror focus slow
U34 1:1 Cassegr. mirror focus fast
U35/U36 = Cassegr. mirr. unit lock
U37 = Cassegr. mirror cover
./ .
- 33 -
15 (3b.5) (Continued)
t
Desig. Nr. of spare Function LocationMotors controls
MCBU4 6 1 U4l = Coud~ mirror collimator Coud~ mirror uni
U42 = Coud~ mirror collimator
U43 = Coud~ mirror focus slow
l)44 = Coud~ mirror focus fast
U45/U46 = Couda'mirror unit lock
U47 = Coud~ mirror cover
* Special MCB's, refer to relevant section: -
(MCBA)
(MCBP1)
(MCBQ1)
- 3b.3,4
- 3b.4.5
- 3b.3.3} 3.6 m Control Manual Part 2
- 34 -
16 (3b.8) LIST OF JUNCTION BOXES
MOTOR (S) JUNCTION BOX E.S.O No. DWG. No.DESIGNATION
All, A12 A1J1 M-0431-l V .4.1
C1l to C15 *1 see note
C2l, C22 C2J1 E-0706-3 V .6.10
C23 C2J2 M-0333-1 V .6.4.'
C24 C2J3 E-0706-2 V .6.6
F47 F4J3 M-0511-2
F48 F4J1 M-0333-l V .6.4
Hll, Hl2 H1J1 E-0706-1 V .6.9,
HlJ5*2H13 H1J2, M-0334-1 V .6.1
H14 H1J3, H1J5*2 M-0334-1 V .6.1
H15 H1J4 M-0334-1 V .6.1
H21 H2Jl M-0334-l V .6.1
H22 H2J2 M-0334-l V .6.1
H23 H2J3 M-0334-l V .6.1
H24 H2J4 M-0334-1 V .6.1
H25 H2J5· M-0334-1 V .6.1
H31 H3J1 M-0332-1 V .6.2
H41 H4J1 M-0359-1 V .6.3
H42 H4J2 M-0359-1 V.6.3
H43 H4J3 M-0359-1 V .6.3
H44 H4J4 M-0359-1 V .6.3
Ml1, M14 MlJ1 M-0330-l V 6.7
M12, Ml3 MlJ2 M-0330-1 V .6.7
M2l M2Jl M-0334-1 V.6.1
M31 M3Jl M-0359-1 V .6.3
Pll to P14 no junct.box
P21, P22 P2J1 M-0336-1 V .6.13
P23, P24 P2J2 M-0337-1 V.6.l2
./ .
- 35 -
16 (3b.8) (Continued)
MOTOR(S)JUNCTION BOX E.S.O. No. Dt'JG. No.
DESIGNATION
P25 P2J3 M-0334-1 V .6.1
P31, P32 P3J1 M-0336-1 V .6.13
P33, P34 P3J2 M-0337-1 V .6.12
P35 P3J3 M-0334-1 V.6.1
P41, P42 P4J1 M-0336-1 V .6.13
P43, P44 P4J2 M-0337-1 V .6.12
P45 P4J3 M-0334-1 V .6.1
P51 PSJ1 M-0334-1 V .6.1
P52 P5J2 M-0333-1a v.6.5
011, Q12 Q1J1 M-0431-1 V.4.1
Q13 Q1J2 M-0431-1 V .4.1
021 Q2J1 M-0359-1 V .6.3
U11, U12 U1J1 M-0332-1 V .6.2
U21, U22 U2J1 M-0348-1 v.6.11
U31, U32 U3J1 M-0330-1, V .6.7
U33, U34 U3J2 M-0335-1 V .6.8
U35, U36 U3J3 M-0332-1 V .6.2
U37 U3J4 M-0334-1 V .6.1
U41, U42 U4J1 M-0330-1 V .6.7
U43, U44 U4J2 M-0335-1 V .6.8
U45, U46 U4J3 M-0332-1 V.6.2
U47 U4J4 M-0334-1 V .6.1
*1 _ Motors C11 to C21 are connected to their motor control
boxes via a motorized coupling mechanism. Connections are
made directly via the plugs and sockets and no junction
boxes are required.
*2 _ These junction boxes are wired to their motor control
box (MCBH1) via another junction box (H1J5).
- 36 -
17 (4a.4.4) DESCRIPTION OF THE INTERLOCK SIGNALS
Each interlock signal is identified by its two symbol
code. For the full codes refer to chapter 18, list of InterlockSignal Data.
al, a2, a3, a4 - 'Carriage completely back' - these four inter
lock signals are wired from Fl endswitches on
the top unit carriage drives. Each limit switch
is activated by a cam at the end of the appro
priate carriage rails. The signal is trans
mitted when the carriage has been drawn comple
tely back, away from the telescope tube.
zl - 'All carriages completely back' - this combined
interlock signal is generated in MCBPI using
the four signals listed above, (al.a2.a3.a4).
as, a6, a7, aB - 'Carriage on manual' - these local interlock
signals are only used in the carriage MCB's
where they. are generated. They transmit when
the appropriate carriage has been switched to
manual control and they are wired from the
ON LINE/OFF LINE selector relay.
bl, b2, b3, b4 - 'Carriage in loading/unloading position'
these interlock signals are generated by four
position switches which transmit in each of
the four loading/unloading positions of the
moving platform.
./ .
- 37 -
17 (4a. 4 .4) (Continued)
b5, b6, b7, ba - 'Carriage in fast drive sector' - these
local interlock signals are only used in the
carriage MCB's where they are generated. Each
limit switch follows a cam running alongside
the appropriate, carriage rails. When the
carriage 1s running over the centre section of
rail, clear of both the telescope tube end
and the completely back position, the interlock
signal is transmitted to allow the carriage
to be moved at fast speed.
cl, c2, c3
c4
dl
d2
- 'Top unit misalignment' - these interlock signals
are transmitted by sensor switches within the
top ring when the incoming top unit is not
correctly aligned.
- 'Tube upper misalignment' - this combined inter
lock signal is generated in MCBPl.
- 'Top unit fully in' - thi~ interlock signal is
generated by a sensor switch on the top ring.
The signal transmits when a top unit has been
driven fully into the telescope tube.
- 'Top ring locked' - combined interlock signal
which is generated in MCBH3. It transmits when
all four locks have fUlly engaged to lock the
top ring into the telescope.
./ .
17 (4a.4.4)
- 38 -
(Continued)
d3
el, e2, e3
eS, e6, e7
fl, f2, f3
'Top ring in' - these four local interlock
signals are only used in MCBH3. They ensure
that the top ring is in contact with all four
locks before the top ring is locked to the
telescope.
- 'Forks completely in' - these local interlock
signals are only used in the carriage MCB's
in which they are generated. A push switch on
each carriage transmits a signal when the forks
are fully engaged in the top unit. Each top unit
may only be locked to its respective carriage
after this signal has been transmitted.
- 'Carriage empty' - these local interlock signals
are only used in the carriage MeB's where they
are generated. The forks on each carriage are
fixed using a centre pivot bearing and a rear
spring mounting. When the top unit weight is
taken on the forks the mounting springs de
flect and trigger push switches at the rear
of ~~e carriages. These interlock signals prevent
the front lift motors from operating unless the
top unit is removed,
- 'Unit locked to telescope' - these interlock
signals are generated by F2 endswitches on the
top unit locks. The ~ignals are transmitted
when the appropriate top unit is fully locked
into the telescope tube.
. ./ .
- 39 -
17 (4a.4.4) (Continued)
fS, f6, f7
gl, g2
hI
- 'Unit locked to carriage' - these interlock
signals are generated by F2 endswitches on the
carriage locks. The signals are transmitted
when the appropriate top unit is fully locked
into its carriage.
- 'Mirror cover closed' - these signals are trans
mitted when the covers are fUlly closed to
protect the mirrors.
o- 'Tube above 15 ' - this interlock signal is
generated by a.ball switch in the ball switch
case, CBR2. It is transmitted when the optical
axis of the telescope tube is at an elevationo '
of greater than 15 with respect to the hori-
zon
h2 (tube above 70), h3 (tube above 6
0) - same type of function
as hI but for different elevation angles.
jl, j2, j3, j4
R2lFl to R2lF9
Fl (~) to F9 (cS)
'Telescope tube position' - these interlock
signals are generated by push switches follo-"
wing a cam on the declination axis drive. They
transmit at various different positions of the
telescope tube.
k
RllFl to RllF6
Fl Pl.) to F6 (ol)
- 'Horse-shoe position' - these interlock signals
are generated by push switches folloWing a cam
on the polar axis drive. They transmit at dif
ferent positions of the horse-shoe.
./ .
- 40 -
17 (4a.4.4) (Continued)
ml, m2 - 'Telescope tube lock' - Fl, F2 endswitch signals
from the declination axis lock pin.
m3, m4 - 'Telescope tube balanced' - when the telescope
tube is locked there is a small amount of free
side movemovement in the lock pin itself. Two
push switches are positioned on each side of
the lock pin to ensure that the tube is balanced
correctly. The interlock signals are transmitted
unless there is enough unbalance force in either
direction to depress one of the switches.
nI, n2 - 'Horse-shoe lock' - Fl, F2 endswitch signals
from the polar axis lock pin.
n3, n4 - 'Horse-shoe balanced' - same type of function
as m3, m4.
01, 02 - Oil lubrication - interlock signals from oil
pressure switches in the oil supply lines to
the gear drives of the declination and polar
axis. These interlock signals operate in an
inverted manner because the sensors used have
contacts of the normally open type. These
signals transmit when there is insufficient
oil pressure in the supply to the gear drives.
'. / .
- 41 -
17 (4a.4.4) (Continued)
03, 04 - Hydrostatic bearing oil pads - combined
interlock signals from the pressure and flow
monitors in the oil supply lines to the decli
nation and polar axis hydrostatic bearings. The
interlock signals transmit when the oil pressure
and flow to their respective bearing pads are
above the minimum required levels.
p1, p2, p3, p4 - Mirror 3 arm signals - these interlock signals
are generated by limit switches on mirror 3
arm. p1 is transmitted when the arm is locked
on the hubsection. p4 and p2 are the F1, F2
endswitch position signals from mirror 3 arm
drive. p3 is trans-
mitted when the arm is not at either end of its
travel, to allow the arm to be moved at fast
speed.
q1 to a6 _ Mirror 3 signals - these interlock signal are
all generated by the Fl, F2 endswitch position
signals of the various motorized mechanisms on
mirror 3.
r1, r2, r3, r4 - 'Emergency switches - these interlock signals
come from manually operated emergency switches
situated at various points on the telescope .
./ .
- 42 -
18 (4a.4.3) LIST OF INTERLOCK SIGNAL DATA
INTERLOCK SIGNAL TYPE SOURCE FUNCTION
al P41Fl EXT. MCBP4 Carriage 1 completely backa2 PSIFl EXT. MCBPS Carriage 2 completely backa3 P21FI EXT. MCBP2 Carriage 3 completely backa4 P31Fl EXT. MCBP3 Carriage 4 completely backzl (al. a2. a3 •a4) COMB. MCBPl All carriages completely back
as OFF line P2 LOCAL MCBP2 Carriage 3 on manuala6 OFF line P3 LOCAL MCBP3 Carriage 4 on manual
a7 OFF line P4 LOCAL MCBP4 Carriage I on manual'
aB OFF line PS LOCAL MCBPS Carriage 2 on manual
pl PISF3 LOCAL MCBPI Carriage 3 loading position
b2 PISF4 LOCAL MCBPI Carriage 4 loading positionb3 PlSFS LOCAL MCBPl Carriage 1 loading positionb4 PISF6 LOCAL MCBPl Carriage 2 loading position.bS P22FI, P22F2 LOCAL MCBP2 Carriage 3 fast drive sectorb6 P32Fl, P32F2 " LOCAL MCBP3 Carriage 4 fast drive sector
b7 P42FI, P42F2 LOCAL MCBP4 Carriage I fast drive sector
bB PS2FI, PS2F2 LOCAL MCBPS 'Carriage 2 fast drive sector
cl HSIFI EXT. MCBH2 No tube west misalignment
c2 HSIF2 EXT. MCBH2 No tube east misalignment
c3 HSIF3 EXT. MCBH2 No tube bottom misalignment
c4 (c1.c2) COMB. MCBPI No tube upper misalignment
dl HSIF4 EXT. MCBH2 Top unit fUlly in
d2 - COMB. MCBH3 Top ring locked
d3 n41F3toH44F3 LOCAL MCBH3 Top ring in.,
./ .
18 (4a. 4.3) (Continued)
- 43 -
INTERLOCK SIGNAL TYPE SOURCE FUNCTION II
el P23F3 LOCAL MCBP2 Carriage 3 forks in
e2 P33F3 LOCAL MCBP3 Carriage 4 forks in
e3 P43F3 LOCAL MCBP4 Carriage 1 forks in
eS P23F4 LOCAL MCBP2 Carriage 3 empty
e6 P33F4 LOCAL MCBP3 Carriage 4 empty
e7 P43F4 LOCAL MCBP4 Carriage 1 empty
.f1 U45F2 EXT. MCBU4 Coude locked to tube
f2 U3SF2 EXT. MCBU3 Cassegrain locked to tube
f3 UIIF2 EXT. MCBUl Prime focus locked to tube
fS P23F2 EXT. MCBP2 Unit locked to carriage 3
f6 P33F2 EXT. MCBP3 Unit locked to carriage 4
f7 P43F2 EXT. MCBP4 Unit locked to carriage 1:
gl U47F2 LOCAL MCBU4 Coude mirror cover closed
g2 U37F2 LOCAL MCBU3 Cassegrain mirr. cover closed
hl R22Fl EXT. CBR2 Tube above lSo
h2 R22F2 EXT. CBR2 Tube above 70
h3 R22F3 EXT. CBR2 Tube above 60
jl R2lF3 EXT. SERVOS Tube vertical
j2 R21F4 EXT. SERVOS Tube horizontal
j3 R21F7 LOCAL SERVOS Tube above horizon
j4 R2lF5 LOCAL SERVOS Tube above pole
Fl (6) R2lFl LOCAL SERVOS Tube limit south
F2 (6) R21F2 LOCAL SERVOS Tube limit north
FG (0) R2lFG LOCAL SERVOS Tube at equator
Fa (0') R21F8 LOCAL SERVOS Tube end stop south
F9(6") R2lF9 LOCAL SERVOS Tube end stop north
./ .
18 (4a.4.3) (Continued)
- 44 -
INTERLOCK SIGNAL TYPE SOURCE FUNCTION
k
Fle..:)
F2(Cll)
F3 (od
F5(~)
F6 (cO
ml
m2
m3
m4
nl
n2
n3
n4
01
02
03
04
pl
p2
p3
p4
RI1F4
RllFl
R1IF2
RllF3
R11F5
RllF6
M31F2
M31Fl
M31F3
M31F4
Q21F2
Q21Fl
Q21F3
Q21F4
G23Fl
G13Fl
H15F2
H11F2
HI1F3
HllFl
EXT.
LOCAL
LOCAL
LOCAL
LOCAL
LOCAL
EXT.
EXT.
LOCAL
LOCAL
EXT.
EXT.
LOCAL
LOCAL
LOCAL
LOCAL
EXT.
EXT.
EXT.
LOCAL
LOCAL
LOCAL
SERVOS
SERVOS
SERVOS
SERVOS
SERVOS
SERVOS
MCBMl
MCBM1
MCBMl
MCBMl
MCBFl
MCBFl
MCBFl
• MCBF1
HYD.*
HYD.*
HYD.*
HYD.*
MCBHl
MCBHl
MCBHl
MCBHl
Horse-shoe at 12 O'clock
Horse-shoe limit east
Horse-shoe limit west
Horse-shoe init. oi
Horse-shoe end stop east
Horse-shoe end stop west
Telescope tube lock in
Telescope tube lock out
Tube balanced +
Tube balanced -
Horse-shoe lock in
Horse-shoe lock out
Horse-shoe balanced +Horse-shoe balanced -
£oil lubrication
~ oil lubrication
b hydrostatic bearings
::.t hydrostatic bearings
M3 arm lock to Hubsection
M3 arm in
M3 arm on fast sector
M3 arm out on hubsection
ql H13F2
q2 C21F2
q3 C14F2, C1SF2
q4 C23Fl
LOCAL
LOCAL
EXT.
EX'I.' •
MCBHl
MCBHl
MCBCl
MCBCl
M3 locked to arm (lower)
M3 hook locked to sky baffle
1-13 cover closed
M3 power plug out
./ .
- 45 -
18 (4a.4.3) (Continued)
INTERLOCK SIGNAL TYPE SOURCE FUNCTION
q5
q6
q7
C24F2
Hl4Fl
C2lF3
EXT.
LOCAL
LOCAL
MCBHl
MCBHl
MCBHl
M3 twin locked to sky baffle
M3 unlocked to arm (upper)
M3 mech. locked to sky baf.
rl emergency SW.
r2 emergency SW.
r3 emergency SW.
r4 emergency SW.
zl (al.a2.a3.a4)
z2 (j2.k.nl.ml )
z3 (z2.cl.c2.c3)
z4 (k.nl)
LOCAL
LOCAL
LOCAL
LOCAL
COMB.
COMB.
COMB.
COMB.
SERVOS
SERVOS
SERVOS•
SERVOS
MCBPl
MCBFl
MCBPl
MCBFl
Prime focus cage emergency
Center section emergency
Cassegrain cage emergency
Platform emergency
tl
t2
t3
t4
Sal
Sa2
Val
Q3lF2
Q31Fl
Q3lF3
Q3lF4
LOCAL
LOCAL
LOCAL
SERVOS
SERVOS
CBR2
These interlock signals are
intended to replace
ml, m2, m3, m4.
Main mirror air support
Main mirror air clamps
HYD.* - These signals are wired in the BBC hydraulic plant,
MCBU
MIRROR 4',
M1', M12M13. M14
fU31' U32, U33, U34.U3S, U36 ,U37U41, U42, UI,3, UI,I"UI,S, U'&,UI,7Ul1, U12, U21) U22,U23
(MIRROO 3: C1l,C12 ,C13. C11, I C1S/ t~KY SAl;: C21 \ C22 , C23
READINGS R2l OBXH
R23
46
Approv,
Niln",:
S - 103
Number:
cs - E - 0654 - 2(rig. 3b.7-A)
Object:
LOCATIONS
ESO
OF ON - OFF MOTORS AND 'SERVOSFIG 8.3-1
EUROPEAN SOUTHERN OBSERVATORV,1211 GENEVA 23
TELESCOPE PROJECT DIVISiON·
..... 1, ..:r,-~ • ." .... ~ rl Y ':.
" ~-'- ~;.-=-- -,
"""" f 1.1-0"1 ""t "; .... u': .. r JIl'. C
., r • ')!: r"\
"
-1-
~. ~'__ SCCUCE
AlJXILIA~V
~\ I TELESC~PE~ ~.
~~:, \~J \\.,\~ , .... \~:'. .\' \ '1.\ •~~
-~~2.-':)~~'L..)::ff~i·- ---.:..... "'--::;"-~I~-··-·-·'
• \' wn ~.~~ : I :,
SYSTEM J j" ~~ \;..!'., 'r.-'~' MC:1-S
COMPUTER-,',· ~4' ·,/l_-<sc;;:-s: III ~ J.i _ I ! ..."; I oax - 5~ ~ C""'-'/
I L! ;.-.~ ..~, .'
,--r-- I iI I :
I 1 '. 1 ~
1
1 I !: .J ! I
l' I
"--
Mirror 5
1= -FOURTH FLOOR/' /V'CD Fl·n I
RIOS FODX F
•. - .- POXFl .·F2 ----
.OIL CONTROLPUMP STATION
'HYDRAULIC PLANT)
~-----.:
D-OOM[;
A - ALUMINIZ'NG PLANT
~-T~UNITSRIDS U3 ""'-RIOS U4
MC~ ~,....®._'"~0 -1:)
"TI-(;)(X)"tAlI
~
popLATFORMRIOS-PMCa -PtMCD""'\ I' I;: -P2·P5
~ -DOM;'" IMCD O! ( 'HATCHES. .' I! \\J< /OS 0' I ':.~/;:)sCR!;EI'lI I ' I I
I U, '. :' ; !' -
I'~~ r'-" ~~.
l·,,:J@0)I, .~I ("'\
r,f
. ~OO~A .;' "C'''',, I:' '../~;dso !~
I,' ~--- ......, 'I. R/CS-O [SV""~TS::vI1 )
48
m=LETTER FOR GENERAL LOCATION
~ Nw·mER OF GROUP (SU8ASSEM8LY)
t ,NUMBER OF MOTOR "
F1o
H11 F2o
Fto
Ht2 F2o
Hll- t Htt-2 Hl'-3 H12-1 H12-2 H12- 3
MOTOR CAN BE CONTROLEDHERE BY THE HAND -DRIVE
H1 J1
LETIERGEN.LOC.
No OF GROUp<I--'
.Jo OF BOX
H3 TYP CABLE,--~MCBH'
H10-2
(
Hl1-4 MAX.7 MOTORSPER BOX
RIOS H
H3 TYPE CABLEHtO-l
MCBH2
MCBH3
MCBC tCBR 2
H20-10'
H30-1
Cl0-1
R20-1
OSXHINTERLOCKS
380V
HOO-2 HOO-t
CS-E-0654-1
(Fig. 3b.7-C)
-~
s- 103Arprov.
.----,...---,------.----------t-'--------Dl'to: tl;Jme: Scalo: Number:I----·I-.-;.....;~-I---...:..~;",;."...-I
Drawn 2. 4. 7& KtU21
Object:
EXAMPLE OF ON-OFF MOTORS CABLING F'IG 8.3-3
C~OI.'t- <,;..; ._
EUROPfAU SOUTHERN OOSI:nVATORY. \211 GI:Nr:VA 23
T r: r r.:'~ f' [" ,,~~ tJ ~.~ (' •p= e""" ~... «"I~ ~ C ..,,r.. i. t:;" 'J v. a- • .. .... to.. J; -.. .... • I .. ' ". ......, .. 'J-_...- ..-~--~ • ...~~,. .~~-:-'t"j _'4.11.. •••• 't.c...-J.....
2 Hughes 88pole sockets tocarry computer signals to MCaand status signals from MCato RIOS computer inter face.
o 0
o 0
sittmcmsD7
o key
Front door
1
4
2
5
3
6
Do
o 0
."_.CO
!DN
I-
Burndy socket - 48 polasfor remote control Handset(normally comccted withControl room).
STANDARD MOTOR CONTROL BOX M.C.B.8
Left side -6 Hirschmam sockets16potes for 6 motors.
Back plate and 380 Vwiring
Front doorFront panel of hinged module
50
Back side offront panel
PHOTOGRAPH OF M.C.B
Fig. 9.2-2
I Collimator Focus IR- Red lightG - Gr~en light
Mol Prot.
ooff line
o
."1O"CDN
I
W
Collimation
Focus sLowFocus fastLock
Cover
IlID [[] rID [ID [Q] lID [ID [Q] [[] []] [[] (]J'U41 U42 U43 U44
J Lock Cover IIlID rID [[] [ID [ID [ID [BJ rnJ IJ[]I
unlock lock open dosed
(small interlock signal lamps)~ ~ ~ ~ 0 0 0 0 0 0 0 0 0.
U45l F£2 L-J-+-----------U41 ~---u:O-f1
U42~----1 : Interlock panel ..U43 : (printed circuit). .U44 U47:F2
U~6 P2d~:~10F447 f5 g1 d
MODULE FRONT PANEL
M.C.B. U4Coude mirror
(11....
+ +
lOCALINTERLOCK
----- F2F1' -----
yF-CONTACTS FROM OTHER MOTORS
3
GENERAL INTERLOCK
Onte: tlamel Scala: Number:Drawn 30.9.16 KLU'u FIG 9.2-4Approv, J!~ S -103
ObJecll( Fig. 4.2.4)PRINCIPLE OF INTERLOCKS
E" SO EUROPEAN· SOUTUERN OOSERVAYOICY,121t GENE~A 23
TELESCOPE PROJECT DIVISION
53
From Control Room-MeB
'- '''''----IRemote-Control__----. .Hgndset
~--1"""- To MCB HI' -H2.- H ,
CBR2.- UI.-(U3).- U~)
f, F 2
l'3)~i-@-t{( '.)JBX
'-) 1-~-~-?-rli~-eJ-------jO=380 v
To max 7 motors
CommandRIOSH
"'---4(RIOS U)~_~_-1Status
220v
220v
r-----
380 v
1-----1(omputer
DBX H
) ( & Cable Twist
) C:' Cable TWist
IIITo servos for I
eC+& axes I
I
IIL- .....l
CONTROL ROOM
DBX F
r------------------.I MCB
1---~~-1 PI
II '----I on carriages
ONPlATFORM=7--------~
GENERAL PRINCIPLE OF ON/OFFMOTOR COMMAND
Fig. 10.1
54
dy 48 pin
~-
Burn
II0 0 0 0
ICIJCDCIJ ITJIJ t
0 0 0 0
Ic::oCDD:JI1 ~ 1
"'"'"ON/OFF line selection
REMOTE CONTROL HANDSET
Fig. 10.2
~O
~O
Li'O
tr"O z(')lteye
S"0
0,....-
00
----
~0)
w>-a::Cl
I
ClZ«J:
w..Jm~a::oa.
Fig. 10.3-1
OJ
56
H~~IOl t: LOCAL+ HfM. L~C. + ++ +
! ~I! ! ! b ,! ~F1 I~~ COMPUTER
"~L~. ... COMPUTER " f2• \', \COMMAND ~ ,.l
:ND L I.:I"DWITCH SWITCH
LEFT
~TO Gt::NERAL
INTERLOCK CIRCUIT
+
COMPUT. STATUSF1 TO MOTOR
~
F2
+
/'7 ~ ~ ~q R
-tlr--~-1=t--+-{::==i.:n=I---,=;~~ M®PR~T~CT. (ONE LAMP PER Mesl
~LAYOUT OF CONTROL LAMPS
AND BUTTONS
FROM GENERALINTERLOCI< -e.--_
Dalo:
Drewn 13.9. 7G
Approv.
Namo:
S -103
Number:
FIG 12.2-1
Object:
PRINCIPLE OF A MOTOR CONTROL (Fig. 4.2.2.)'
ESOEUROPEAN SOUTIIERN ODSERVATORY.1211 GENEVA 23.TELESCOPE PROJECT D~V;S~O'~',,~
57
IO~u:Ell.
CDIJ1ull.~
~00
m Ncc
Ull. ~ ...J
~ 0cc....z0
~ m:- U
n: u M0 ::Ea. ;.-u.I- Ol/)<! >::.:::...J ccua. CD wet
u- ~ l/)a::iD.
I, I
x- ><_M~ (J)::>::>::> 0 r--
.... '--.,--J
Z IT]::> mMCl. Ux i>-0 ::E....
CONU xtu :::EUIJJa: N
a: 0::(X)
~ uzwu cou-.... u-
ID ..Ux::E
Dalo: Namo:Drawn 26. 1. 77 'c<Ll.R.tAApprov.
~ 1'-./ CL,,~- '-../
.... " U.,,'h' ><,.-.... ·tI a:,.-...., CD 0
l- D 9l/) ....~
l/) u.~.... .... :c....
0:t.' ::>z 0t= m_ u.
CDz u u-::> ~~ ~LL0::t:
NUlnber:
FIG 12.2-25-103
ObJoct:
(FIG 4.1.2)
ESO
LAYOUT OF THE INTERLOct< CABLH\!G
EunOPEAN SOUTHERN OUSERVATORY, 1211 GEUEVA 23
TELESCOPE PROJECT D~V!Sldr-J
o o o ® ~ o @ o @ ® o ®
1 2 3 4 5 6 7 8 9 10 11 12
Arm drive slow
km drive fast
Lower look in armUpper 100:< in <:.rm
Lock on hubs.Hook lockTwin lock
H11< ~ -0 C ~ = 0 0-----H12-..:::-0 ()-"'~-C C 0 o-JH13< 0 C--~ c--o 0--0 0H14<:::J- 0 C-------JH15< . -0 0--0 0-----C21< C~ C -0 COO-C24< 0 0 I
Hl1 F3 C21F3
p3 q7
C21F2
q2
H13F2
ql
H14F2
q1
H14Fl
q6
C24F2 C14/15F2" HllF2
q5 q3 p2
Hl1 F1
p4 z2C23Fl
q4
01en
p3 = mirror 3 arm on fast drive sectorq7 = ~ir. 3 locked to sky baf. (~ech. lock)q2 = mire 3 locked to sky baf. (hook lock)ql = nir. 3 locked to a~ (lower fi~ser)
q6 = nir. 3 ~nlocked fro~ arm (upper fi~ge=)
q5 = mir. 3 locked to sky baf. (twin lock)q3 = mirror 3 CO~2r closedp2 = nirror 3 ar~ inp4 = nirror 3 a~ outZ2 = Telescope position (see MeB?I)q4 = mir~or 3 pcwer plug out
iiliCBH 1
Mirror 3 Arm
Interlock panel
N:'~·1BER:
( ~. 4 ") -)r 19 . . _ . ::>
I::!!I'" 0'''1::' ,,·V-=,\11 """._- C'C_. ,_-
1-.. n. 9.i6 ;<...;.40:-.~I •I~l _
Nr.
8.3-1
8.3-2
8.3-3
Nr. ControlManual
3b.7-A
3b.7-B
3b.7-C
INDEX OF FIGURES----------------
Subject Page
Locations of ON/OFF motors 46and servos
Location of MCB and RIOS 47
Example of ON/OFF motors cabling 48
9.2-1
9.2-2
9.2-3
9.2-4
10.1
10.2
10.3-1
4.2.4
Standard Motor Control BOx MCB8
Photograph of MCBU4
Module Front Panel of MCBU4
Principle of interlocks
General principle of ON/OFFmotor command
Remote Control Handset
Portable Hand-Drive Box
49
50
51
52
53
54
55
12.2-1 4.2.2
12.2-24.1.2
Principle of a ON/OFF MotorControl
Layout of the Interlock cabling
56
57
12.4 4.2.5 MCBHl Mirror 3 Arm 58